www.hilti.at Profis Anchor 2.4.

8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

1
RTT:YAW-
Center Pole with edges
20/07/2014

Specifier's comments: 45 deggree Wind ( Tension at edge diagonal). with Slab thk 110,f'c=21N/mm2
1 Input data
Anchor type and diameter: HIT-RE 500-SD + Rebar 12mm
Effective embedment depth: h
ef,opti
= 78 mm (h
ef,limit
= 78 mm)
Material: B500B
Evaluation Service Report: ESR-2322
Issued I Valid: 1/02/2014 | 1/04/2016
Proof: design method ACI 318 / AC308
Stand-off installation: e
b
= 0 mm (no stand-off); t = 1 mm
Anchor plate: l
x
x l
y
x t = 600 mm x 600 mm x 1 mm; (Recommended plate thickness: not calculated)
Profile: Pipe; (L x W x T) = 108 mm x 108 mm x 4 mm
Base material: cracked concrete, , f
c
' = 3046 psi; h = 110 mm, Temp. short/long: 40/24 C
Installation: hammer drilled hole, installation condition: dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: > No. 4 bar
Seismic loads (cat. C, D, E, or F) no
Geometry [mm] & Loading [kN, kNm]
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

2
RTT:YAW-
Center Pole with edges
20/07/2014

2 Load case/Resulting anchor forces
Load case: Design loads
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 7.663 0.575 0.406 0.406
2 6.248 0.575 0.406 0.406
3 4.834 0.575 0.406 0.406
4 3.419 0.575 0.406 0.406
5 6.248 0.575 0.406 0.406
6 4.834 0.575 0.406 0.406
7 3.419 0.575 0.406 0.406
8 2.005 0.575 0.406 0.406
9 4.834 0.575 0.406 0.406
10 3.419 0.575 0.406 0.406
11 2.005 0.575 0.406 0.406
12 0.591 0.575 0.406 0.406
13 3.419 0.575 0.406 0.406
14 2.005 0.575 0.406 0.406
15 0.591 0.575 0.406 0.406
16 0.000 0.575 0.406 0.406
max. concrete compressive strain: 0.08 []
max. concrete compressive stress:
2.50 [N/mm
2
]
resulting tension force in (x/y)=(-78/-78): 55.536 [kN]
resulting compression force in (x/y)=(247/247): 18.936 [kN]
Tension
Compression

1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
x
y
3 Tension load
Load N
ua
[kN] Capacity
ffff
N
n
[kN] Utilization
bbbbN
= N
ua
/
ffff
N
n
Status
Steel Strength* 7.663 40.300 20 OK
Bond Strength** 55.536 54.917 102 not recommended
Concrete Breakout Strength** 55.536 55.186 101 not recommended
* anchor having the highest loading **anchor group (anchors in tension)
3.1 Steel Strength
N
sa
= ESR value refer to ICC-ES ESR-2322
f
N
steel
N
ua
ACI 318-08 Eq. (D-1)
Variables



n





A
se,N
[mm
2
]





f
uta
[N/mm
2
]


1 113 549.86
Calculations



N
sa
[kN]


62.000
Results



N
sa
[kN]




fsteel





f
N
sa
[kN]





N
ua
[kN]


62.000 0.650 40.300 7.663
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

3
RTT:YAW-
Center Pole with edges
20/07/2014

3.2 Bond Strength
N
ag
=
(
A
Na
A
Na0
)

yed,Na

yg,Na

yec,Na

yp,Na
N
a0
ICC-ES AC308 Eq. (D-16b)
f
N
ag
N
ua
ACI 318-08 Eq. (D-1)
A
Na
= see ICC-ES AC308, Part D.5.3.7
A
Na0
= s
2
cr,Na
ICC-ES AC308 Eq. (D-16c)
s
cr,Na
= 20d

tk,uncr
1450
3 h
ef
ICC-ES AC308 Eq. (D-16d)
c
cr,Na
=
s
cr,Na
2
ICC-ES AC308 Eq. (D-16e)
yed,Na
= 0.7 + 0.3
(
c
a,min
c
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16m)
yg,Na
=
yg,Na0
+
[(
s
avg
s
cr,Na
)
0.5
(1 -
yg,Na0
)
]
1.0 ICC-ES AC308 Eq. (D-16g)
yg,Na0
= n -
[
(n - 1)
(
tk,c
tk,max,c
)
1.5
]
1.0 ICC-ES AC308 Eq. (D-16h)
tk,max,c
=
k
c
p
d
h
ef
f
'
c
ICC-ES AC308 Eq. (D-16i)
yec,Na
=
(
1
1 +
2e
''
N
s
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16j)
yp,Na
= MAX
(
c
a,min
c
ac
,
c
cr,Na
c
ac
)
1.0 ICC-ES AC308 Eq. (D-16p)
N
a0
=
tk,c

kbond

p
d h
ef
ICC-ES AC308 Eq. (D-16f)
Variables


tk,c,uncr
[N/mm
2
]





d
anchor
[mm]





h
ef
[mm]





c
a,min
[mm]





s
avg
[mm]





n




tk,c
[N/mm
2
]


15.50 12 78 150 160 15 7.50



k
c






f
'
c
[psi]





e
c1,N
[mm]





e
c2,N
[mm]





c
ac
[mm]




kbond



17 3046 62 62 186 1.00
Calculations



s
cr,Na
[mm]





c
cr,Na
[mm]





A
Na
[mm
2
]





A
Na0
[mm
2
]




yed,Na





tk,max
[N/mm
2
]


234 117 484196 54756 1.000 7.64


yg,Na0





yg,Na





yec1,Na





yec2,Na





yp,Na






N
a0
[kN]


1.077 1.013 0.654 0.654 1.000 22.054
Results



N
ag
[kN]




fbond





f
N
ag
[kN]





N
ua
[kN]


84.488 0.650 54.917 55.536
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

4
RTT:YAW-
Center Pole with edges
20/07/2014

3.3 Concrete Breakout Strength
N
cbg
=
(
A
Nc
A
Nc0
)

yec,N

yed,N

yc,N

ycp,N
N
b
ACI 318-08 Eq. (D-5)
f
N
cbg
N
ua
ACI 318-08 Eq. (D-1)
A
Nc
see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b)
A
Nc0
= 9 h
2
ef
ACI 318-08 Eq. (D-6)
yec,N
=
(
1
1 +
2 e
'
N
3 h
ef
)
1.0 ACI 318-08 Eq. (D-9)
yed,N
= 0.7 + 0.3
(
c
a,min
1.5h
ef
)
1.0 ACI 318-08 Eq. (D-11)
ycp,N
= MAX
(
c
a,min
c
ac
,
1.5h
ef
c
ac
)
1.0 ACI 318-08 Eq. (D-13)
N
b
= k
c

l
f
'
c
h
1.5
ef
ACI 318-08 Eq. (D-7)
Variables



h
ef
[mm]





e
c1,N
[mm]





e
c2,N
[mm]





c
a,min
[mm]




yc,N



78 62 62 150 1.000



c
ac
[mm]





k
c





l






f
'
c
[psi]


186 17 1 3046
Calculations



A
Nc
[mm
2
]





A
Nc0
[mm
2
]




yec1,N





yec2,N





yed,N





ycp,N






N
b
[kN]


484196 54756 0.654 0.654 1.000 1.000 22.458
Results



N
cbg
[kN]




fconcrete





f
N
cbg
[kN]





N
ua
[kN]


84.902 0.650 55.186 55.536
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

5
RTT:YAW-
Center Pole with edges
20/07/2014

4 Shear load
Load V
ua
[kN] Capacity
ffff
V
n
[kN] Utilization
bbbbV
= V
ua
/
ffff
V
n
Status
Steel Strength* 0.575 22.500 3 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength
controls)**
9.192 291.474 4 OK
Concrete edge failure in direction x-** 6.500 55.010 12 OK
* anchor having the highest loading **anchor group (relevant anchors)
4.1 Steel Strength
V
sa
= (n 0.6 A
se,V
f
uta
) refer to ICC-ES ESR-2322
f
V
steel
V
ua
ACI 318-08 Eq. (D-2)
Variables



n





A
se,V
[mm
2
]





f
uta
[N/mm
2
]





(n 0.6 A
se,V
f
uta
) [kN]


1 113 549.86 37.500
Calculations



V
sa
[kN]


37.500
Results



V
sa
[kN]




fsteel





f
V
sa
[kN]





V
ua
[kN]


37.500 0.600 22.500 0.575
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

6
RTT:YAW-
Center Pole with edges
20/07/2014

4.2 Pryout Strength (Bond Strength controls)
V
cpg
=k
cp[(
A
Na
A
Na0
)

yed,Na

yg,Na

yec,Na

yp,Na
N
a0]
ACI 318-08 Eq. (D-31)
f
V
cpg
V
ua
ACI 318-08 Eq. (D-1)
A
Na
see ICC-ES AC308, Part D.5.3.7
A
Na0
= s
2
cr,Na
ICC-ES AC308 Eq. (D-16c)
s
cr,Na
= 20 d

tk,uncr
1450
3 h
ef
ICC-ES AC308 Eq. (D-16d)
c
cr,Na
=
s
cr,Na
2
ICC-ES AC308 Eq. (D-16e)
yed,Na
= 0.7 + 0.3
(
c
a,min
c
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16m)
yg,Na
=
yg,Na0
+
[(
s
avg
s
cr,Na
)
0.5
(1 -
yg,Na0
)
]
1.0 ICC-ES AC308 Eq. (D-16g)
yg,Na0
= n -
[
(n - 1)
(
tk,c
tk,max,c
)
1.5
]
1.0 ICC-ES AC308 Eq. (D-16h)
tk,max,c
=
k
c
p
d
h
ef
f
'
c
ICC-ES AC308 Eq. (D-16i)
yec,Na
=
(
1
1 +
2
'
e,N
s
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16j)
yp,Na
= MAX
(
c
a,min
c
ac
,
c
cr,Na
c
ac
)
1.0 ICC-ES AC308 Eq. (D-16p)
N
a0
=
tk,c

kbond

p
d h
ef
ICC-ES AC308 Eq. (D-16f)
Variables



k
cp





tk,c,uncr
[N/mm
2
]




tk,c
[N/mm
2
]





d
anchor
[mm]





h
ef
[mm]





s
avg
[mm]





n


2.000 15.50 7.50 12 78 160 16



k
c






f
'
c
[psi]





e
c1,N
[mm]





e
c2,N
[mm]





c
a,min
[mm]





c
ac
[mm]




kbond



17 3046 0 0 150 186 1.00
Calculations



s
cr,Na
[mm]





c
cr,Na
[mm]





A
Na
[mm
2
]





A
Na0
[mm
2
]




yed,N





tk,max
[N/mm
2
]


234 117 509796 54756 1.000 7.64


yg,Na0





yg,Na





yec1,N





yec2,N





yp,Na






N
a0
[kN]


1.081 1.014 1.000 1.000 1.000 22.054
Results



V
cpg
[kN]




fconcrete





f
V
cpg
[kN]





V
ua
[kN]


416.392 0.700 291.474 9.192
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

7
RTT:YAW-
Center Pole with edges
20/07/2014

4.3 Concrete edge failure in direction x-
V
cbg
=
(
A
Vc
A
Vc0
)

yec,V

yed,V

yc,V

yh,V

yparallel,V
V
b
ACI 318-08 Eq. (D-22)
f
V
cbg
V
ua
ACI 318-08 Eq. (D-2)
A
Vc
see ACI 318-08, Part D.6.2.1, Fig. RD.6.2.1(b)
A
Vc0
= 4.5 c
2
a1
ACI 318-08 Eq. (D-23)
yec,V
=
(
1
1 +
2e
'
v
3c
a1
)
1.0 ACI 318-08 Eq. (D-26)
yed,V
= 0.7 + 0.3
(
c
a2
1.5c
a1
)
1.0 ACI 318-08 Eq. (D-28)
yh,V
=

1.5c
a1
h
a
1.0 ACI 318-08 Eq. (D-29)
V
b
=
(
7
(
l
e
d
a
)
0.2
d
a)

l
f
'
c
c
1.5
a1
ACI 318-08 Eq. (D-24)
Variables



c
a1
[mm]





c
a2
[mm]





e
cV
[mm]




yc,V






h
a
[mm]


150 150 0 1.200 110



l
e
[mm]




l






d
a
[mm]





f
'
c
[psi]




yparallel,V



78 1.000 12 3046 2.000
Calculations



A
Vc
[mm
2
]





A
Vc0
[mm
2
]




yec,V





yed,V





yh,V






V
b
[kN]


94050 101250 1.000 1.000 1.430 24.648
Results



V
cbg
[kN]




fconcrete





f
V
cbg
[kN]





V
ua
[kN]


78.586 0.700 55.010 6.500
5 Combined tension and shear loads


bN





bV





z






Utilization
bN,V
[%]

Status
1.011 0.118 1.000 95 OK
bNV
= (
bN
+
bV
) / 1.2 <= 1
6 Warnings
Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!
Condition A applies when supplementary reinforcement is used. The factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
The ACI 318-08 version of the software does not account for adhesive anchor special design provisions corresponding to overhead
applications.
Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
Fastening does not meet the design criteria!
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

8
RTT:YAW-
Center Pole with edges
20/07/2014

Coordinates Anchor mm
Anchor x y c
-x
c
+x
c
-y
c
+y
1 -240 -240 150 - 150 -
2 -80 -240 310 - 150 -
3 80 -240 470 - 150 -
4 240 -240 630 - 150 -
5 -240 -80 150 - 310 -
6 -80 -80 310 - 310 -
7 80 -80 470 - 310 -
8 240 -80 630 - 310 -
Anchor x y c
-x
c
+x
c
-y
c
+y
9 -240 80 150 - 470 -
10 -80 80 310 - 470 -
11 80 80 470 - 470 -
12 240 80 630 - 470 -
13 -240 240 150 - 630 -
14 -80 240 310 - 630 -
15 80 240 470 - 630 -
16 240 240 630 - 630 -
7 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-RE 500-SD + Rebar 12mm
Profile: Pipe; 108 x 108 x 4 mm Installation torque: 0.000 kNm
Hole diameter in the fixture: d
f
= 12 mm Hole diameter in the base material: 16 mm
Plate thickness (input): 1 mm Hole depth in the base material: 78 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 110 mm
Cleaning: Premium cleaning of the drilled hole is required


1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
60 160 160 160 60
6
0
1
6
0
1
6
0
1
6
0
6
0
x
y
300 300
3
0
0
3
0
0
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

9
RTT:YAW-
Center Pole with edges
20/07/2014

8 Remarks; Your Cooperation Duties
Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

1
RTT:YAW-
Center Pole with edges
20/07/2014

Specifier's comments: 225 deggree Wind ( Tension at edge interior diagonal). with Slab thk 110,f'c=21N/mm2
1 Input data
Anchor type and diameter: HIT-RE 500-SD + Rebar 12mm
Effective embedment depth: h
ef,opti
= 78 mm (h
ef,limit
= 78 mm)
Material: B500B
Evaluation Service Report: ESR-2322
Issued I Valid: 1/02/2014 | 1/04/2016
Proof: design method ACI 318 / AC308
Stand-off installation: e
b
= 0 mm (no stand-off); t = 1 mm
Anchor plate: l
x
x l
y
x t = 600 mm x 600 mm x 1 mm; (Recommended plate thickness: not calculated)
Profile: Pipe; (L x W x T) = 108 mm x 108 mm x 4 mm
Base material: cracked concrete, , f
c
' = 3046 psi; h = 110 mm, Temp. short/long: 40/24 C
Installation: hammer drilled hole, installation condition: dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: > No. 4 bar
Seismic loads (cat. C, D, E, or F) no
Geometry [mm] & Loading [kN, kNm]
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

2
RTT:YAW-
Center Pole with edges
20/07/2014

2 Load case/Resulting anchor forces
Load case: Design loads
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.000 0.575 -0.406 -0.406
2 0.591 0.575 -0.406 -0.406
3 2.005 0.575 -0.406 -0.406
4 3.419 0.575 -0.406 -0.406
5 0.591 0.575 -0.406 -0.406
6 2.005 0.575 -0.406 -0.406
7 3.419 0.575 -0.406 -0.406
8 4.834 0.575 -0.406 -0.406
9 2.005 0.575 -0.406 -0.406
10 3.419 0.575 -0.406 -0.406
11 4.834 0.575 -0.406 -0.406
12 6.248 0.575 -0.406 -0.406
13 3.419 0.575 -0.406 -0.406
14 4.834 0.575 -0.406 -0.406
15 6.248 0.575 -0.406 -0.406
16 7.663 0.575 -0.406 -0.406
max. concrete compressive strain: 0.08 []
max. concrete compressive stress:
2.50 [N/mm
2
]
resulting tension force in (x/y)=(78/78): 55.536 [kN]
resulting compression force in (x/y)=(-247/-247): 18.936 [kN]
Tension
Compression

1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
x
y
3 Tension load
Load N
ua
[kN] Capacity
ffff
N
n
[kN] Utilization
bbbbN
= N
ua
/
ffff
N
n
Status
Steel Strength* 7.663 40.300 20 OK
Bond Strength** 55.536 54.917 102 not recommended
Concrete Breakout Strength** 55.536 55.186 101 not recommended
* anchor having the highest loading **anchor group (anchors in tension)
3.1 Steel Strength
N
sa
= ESR value refer to ICC-ES ESR-2322
f
N
steel
N
ua
ACI 318-08 Eq. (D-1)
Variables



n





A
se,N
[mm
2
]





f
uta
[N/mm
2
]


1 113 549.86
Calculations



N
sa
[kN]


62.000
Results



N
sa
[kN]




fsteel





f
N
sa
[kN]





N
ua
[kN]


62.000 0.650 40.300 7.663
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

3
RTT:YAW-
Center Pole with edges
20/07/2014

3.2 Bond Strength
N
ag
=
(
A
Na
A
Na0
)

yed,Na

yg,Na

yec,Na

yp,Na
N
a0
ICC-ES AC308 Eq. (D-16b)
f
N
ag
N
ua
ACI 318-08 Eq. (D-1)
A
Na
= see ICC-ES AC308, Part D.5.3.7
A
Na0
= s
2
cr,Na
ICC-ES AC308 Eq. (D-16c)
s
cr,Na
= 20d

tk,uncr
1450
3 h
ef
ICC-ES AC308 Eq. (D-16d)
c
cr,Na
=
s
cr,Na
2
ICC-ES AC308 Eq. (D-16e)
yed,Na
= 0.7 + 0.3
(
c
a,min
c
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16m)
yg,Na
=
yg,Na0
+
[(
s
avg
s
cr,Na
)
0.5
(1 -
yg,Na0
)
]
1.0 ICC-ES AC308 Eq. (D-16g)
yg,Na0
= n -
[
(n - 1)
(
tk,c
tk,max,c
)
1.5
]
1.0 ICC-ES AC308 Eq. (D-16h)
tk,max,c
=
k
c
p
d
h
ef
f
'
c
ICC-ES AC308 Eq. (D-16i)
yec,Na
=
(
1
1 +
2e
''
N
s
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16j)
yp,Na
= MAX
(
c
a,min
c
ac
,
c
cr,Na
c
ac
)
1.0 ICC-ES AC308 Eq. (D-16p)
N
a0
=
tk,c

kbond

p
d h
ef
ICC-ES AC308 Eq. (D-16f)
Variables


tk,c,uncr
[N/mm
2
]





d
anchor
[mm]





h
ef
[mm]





c
a,min
[mm]





s
avg
[mm]





n




tk,c
[N/mm
2
]


15.50 12 78 150 160 15 7.50



k
c






f
'
c
[psi]





e
c1,N
[mm]





e
c2,N
[mm]





c
ac
[mm]




kbond



17 3046 62 62 186 1.00
Calculations



s
cr,Na
[mm]





c
cr,Na
[mm]





A
Na
[mm
2
]





A
Na0
[mm
2
]




yed,Na





tk,max
[N/mm
2
]


234 117 484196 54756 1.000 7.64


yg,Na0





yg,Na





yec1,Na





yec2,Na





yp,Na






N
a0
[kN]


1.077 1.013 0.654 0.654 1.000 22.054
Results



N
ag
[kN]




fbond





f
N
ag
[kN]





N
ua
[kN]


84.488 0.650 54.917 55.536
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

4
RTT:YAW-
Center Pole with edges
20/07/2014

3.3 Concrete Breakout Strength
N
cbg
=
(
A
Nc
A
Nc0
)

yec,N

yed,N

yc,N

ycp,N
N
b
ACI 318-08 Eq. (D-5)
f
N
cbg
N
ua
ACI 318-08 Eq. (D-1)
A
Nc
see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b)
A
Nc0
= 9 h
2
ef
ACI 318-08 Eq. (D-6)
yec,N
=
(
1
1 +
2 e
'
N
3 h
ef
)
1.0 ACI 318-08 Eq. (D-9)
yed,N
= 0.7 + 0.3
(
c
a,min
1.5h
ef
)
1.0 ACI 318-08 Eq. (D-11)
ycp,N
= MAX
(
c
a,min
c
ac
,
1.5h
ef
c
ac
)
1.0 ACI 318-08 Eq. (D-13)
N
b
= k
c

l
f
'
c
h
1.5
ef
ACI 318-08 Eq. (D-7)
Variables



h
ef
[mm]





e
c1,N
[mm]





e
c2,N
[mm]





c
a,min
[mm]




yc,N



78 62 62 150 1.000



c
ac
[mm]





k
c





l






f
'
c
[psi]


186 17 1 3046
Calculations



A
Nc
[mm
2
]





A
Nc0
[mm
2
]




yec1,N





yec2,N





yed,N





ycp,N






N
b
[kN]


484196 54756 0.654 0.654 1.000 1.000 22.458
Results



N
cbg
[kN]




fconcrete





f
N
cbg
[kN]





N
ua
[kN]


84.902 0.650 55.186 55.536
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

5
RTT:YAW-
Center Pole with edges
20/07/2014

4 Shear load
Load V
ua
[kN] Capacity
ffff
V
n
[kN] Utilization
bbbbV
= V
ua
/
ffff
V
n
Status
Steel Strength* 0.575 22.500 3 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength
controls)**
9.192 291.474 4 OK
Concrete edge failure in direction x-** 9.192 24.755 38 OK
* anchor having the highest loading **anchor group (relevant anchors)
4.1 Steel Strength
V
sa
= (n 0.6 A
se,V
f
uta
) refer to ICC-ES ESR-2322
f
V
steel
V
ua
ACI 318-08 Eq. (D-2)
Variables



n





A
se,V
[mm
2
]





f
uta
[N/mm
2
]





(n 0.6 A
se,V
f
uta
) [kN]


1 113 549.86 37.500
Calculations



V
sa
[kN]


37.500
Results



V
sa
[kN]




fsteel





f
V
sa
[kN]





V
ua
[kN]


37.500 0.600 22.500 0.575
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

6
RTT:YAW-
Center Pole with edges
20/07/2014

4.2 Pryout Strength (Bond Strength controls)
V
cpg
=k
cp[(
A
Na
A
Na0
)

yed,Na

yg,Na

yec,Na

yp,Na
N
a0]
ACI 318-08 Eq. (D-31)
f
V
cpg
V
ua
ACI 318-08 Eq. (D-1)
A
Na
see ICC-ES AC308, Part D.5.3.7
A
Na0
= s
2
cr,Na
ICC-ES AC308 Eq. (D-16c)
s
cr,Na
= 20 d

tk,uncr
1450
3 h
ef
ICC-ES AC308 Eq. (D-16d)
c
cr,Na
=
s
cr,Na
2
ICC-ES AC308 Eq. (D-16e)
yed,Na
= 0.7 + 0.3
(
c
a,min
c
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16m)
yg,Na
=
yg,Na0
+
[(
s
avg
s
cr,Na
)
0.5
(1 -
yg,Na0
)
]
1.0 ICC-ES AC308 Eq. (D-16g)
yg,Na0
= n -
[
(n - 1)
(
tk,c
tk,max,c
)
1.5
]
1.0 ICC-ES AC308 Eq. (D-16h)
tk,max,c
=
k
c
p
d
h
ef
f
'
c
ICC-ES AC308 Eq. (D-16i)
yec,Na
=
(
1
1 +
2
'
e,N
s
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16j)
yp,Na
= MAX
(
c
a,min
c
ac
,
c
cr,Na
c
ac
)
1.0 ICC-ES AC308 Eq. (D-16p)
N
a0
=
tk,c

kbond

p
d h
ef
ICC-ES AC308 Eq. (D-16f)
Variables



k
cp





tk,c,uncr
[N/mm
2
]




tk,c
[N/mm
2
]





d
anchor
[mm]





h
ef
[mm]





s
avg
[mm]





n


2.000 15.50 7.50 12 78 160 16



k
c






f
'
c
[psi]





e
c1,N
[mm]





e
c2,N
[mm]





c
a,min
[mm]





c
ac
[mm]




kbond



17 3046 0 0 150 186 1.00
Calculations



s
cr,Na
[mm]





c
cr,Na
[mm]





A
Na
[mm
2
]





A
Na0
[mm
2
]




yed,N





tk,max
[N/mm
2
]


234 117 509796 54756 1.000 7.64


yg,Na0





yg,Na





yec1,N





yec2,N





yp,Na






N
a0
[kN]


1.081 1.014 1.000 1.000 1.000 22.054
Results



V
cpg
[kN]




fconcrete





f
V
cpg
[kN]





V
ua
[kN]


416.392 0.700 291.474 9.192
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

7
RTT:YAW-
Center Pole with edges
20/07/2014

4.3 Concrete edge failure in direction x-
V
cbg
=
(
A
Vc
A
Vc0
)

yec,V

yed,V

yc,V

yh,V

yparallel,V
V
b
ACI 318-08 Eq. (D-22)
f
V
cbg
V
ua
ACI 318-08 Eq. (D-2)
A
Vc
see ACI 318-08, Part D.6.2.1, Fig. RD.6.2.1(b)
A
Vc0
= 4.5 c
2
a1
ACI 318-08 Eq. (D-23)
yec,V
=
(
1
1 +
2e
'
v
3c
a1
)
1.0 ACI 318-08 Eq. (D-26)
yed,V
= 0.7 + 0.3
(
c
a2
1.5c
a1
)
1.0 ACI 318-08 Eq. (D-28)
yh,V
=

1.5c
a1
h
a
1.0 ACI 318-08 Eq. (D-29)
V
b
=
(
7
(
l
e
d
a
)
0.2
d
a)

l
f
'
c
c
1.5
a1
ACI 318-08 Eq. (D-24)
Variables



c
a1
[mm]





c
a2
[mm]





e
cV
[mm]




yc,V






h
a
[mm]


150 150 0 1.200 110



l
e
[mm]




l






d
a
[mm]





f
'
c
[psi]




yparallel,V



78 1.000 12 3046 1.000
Calculations



A
Vc
[mm
2
]





A
Vc0
[mm
2
]




yec,V





yed,V





yh,V






V
b
[kN]


94050 101250 1.000 0.900 1.430 24.648
Results



V
cbg
[kN]




fconcrete





f
V
cbg
[kN]





V
ua
[kN]


35.364 0.700 24.755 9.192
5 Combined tension and shear loads


bN





bV





z






Utilization
bN,V
[%]

Status
1.011 0.371 1.000 116 not recommended
bNV
= (
bN
+
bV
) / 1.2 <= 1
6 Warnings
Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!
Condition A applies when supplementary reinforcement is used. The factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
The ACI 318-08 version of the software does not account for adhesive anchor special design provisions corresponding to overhead
applications.
Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
Fastening does not meet the design criteria!
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

8
RTT:YAW-
Center Pole with edges
20/07/2014

Coordinates Anchor mm
Anchor x y c
-x
c
+x
c
-y
c
+y
1 -240 -240 150 - 150 -
2 -80 -240 310 - 150 -
3 80 -240 470 - 150 -
4 240 -240 630 - 150 -
5 -240 -80 150 - 310 -
6 -80 -80 310 - 310 -
7 80 -80 470 - 310 -
8 240 -80 630 - 310 -
Anchor x y c
-x
c
+x
c
-y
c
+y
9 -240 80 150 - 470 -
10 -80 80 310 - 470 -
11 80 80 470 - 470 -
12 240 80 630 - 470 -
13 -240 240 150 - 630 -
14 -80 240 310 - 630 -
15 80 240 470 - 630 -
16 240 240 630 - 630 -
7 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-RE 500-SD + Rebar 12mm
Profile: Pipe; 108 x 108 x 4 mm Installation torque: 0.000 kNm
Hole diameter in the fixture: d
f
= 12 mm Hole diameter in the base material: 16 mm
Plate thickness (input): 1 mm Hole depth in the base material: 78 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 110 mm
Cleaning: Premium cleaning of the drilled hole is required


1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
60 160 160 160 60
6
0
1
6
0
1
6
0
1
6
0
6
0
x
y
300 300
3
0
0
3
0
0
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE engineering
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

9
RTT:YAW-
Center Pole with edges
20/07/2014

8 Remarks; Your Cooperation Duties
Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

1
RTT:YAW
Corner (Strut)
20/07/2014

Specifier's comments: 45 degree wind,Tension at diagonal /w Slab thk=110, f'c=21N/mm2
1 Input data
Anchor type and diameter: HIT-RE 500-SD + Rebar 12mm
Effective embedment depth: h
ef,opti
= 78 mm (h
ef,limit
= 78 mm)
Material: B500B
Evaluation Service Report: ESR-2322
Issued I Valid: 1/02/2014 | 1/04/2016
Proof: design method ACI 318 / AC308
Stand-off installation: e
b
= 0 mm (no stand-off); t = 1 mm
Anchor plate: l
x
x l
y
x t = 600 mm x 600 mm x 1 mm; (Recommended plate thickness: not calculated)
Profile: Pipe; (L x W x T) = 108 mm x 108 mm x 4 mm
Base material: cracked concrete, , f
c
' = 3046 psi; h = 110 mm, Temp. short/long: 40/24 C
Installation: hammer drilled hole, installation condition: dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: > No. 4 bar
Seismic loads (cat. C, D, E, or F) no
Geometry [mm] & Loading [kN, kNm]
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

2
RTT:YAW
Corner (Strut)
20/07/2014

2 Load case/Resulting anchor forces
Load case: Design loads
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 8.166 1.679 1.188 1.188
2 6.623 1.679 1.188 1.188
3 5.079 1.679 1.188 1.188
4 3.536 1.679 1.188 1.188
5 6.623 1.679 1.188 1.188
6 5.079 1.679 1.188 1.188
7 3.536 1.679 1.188 1.188
8 1.992 1.679 1.188 1.188
9 5.079 1.679 1.188 1.188
10 3.536 1.679 1.188 1.188
11 1.992 1.679 1.188 1.188
12 0.448 1.679 1.188 1.188
13 3.536 1.679 1.188 1.188
14 1.992 1.679 1.188 1.188
15 0.448 1.679 1.188 1.188
16 0.000 1.679 1.188 1.188
max. concrete compressive strain: 0.10 []
max. concrete compressive stress:
2.99 [N/mm
2
]
resulting tension force in (x/y)=(-81/-81): 57.664 [kN]
resulting compression force in (x/y)=(242/242): 27.164 [kN]
Tension
Compression

1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
x
y
3 Tension load
Load N
ua
[kN] Capacity
ffff
N
n
[kN] Utilization
bbbbN
= N
ua
/
ffff
N
n
Status
Steel Strength* 8.166 40.300 21 OK
Bond Strength** 57.664 53.026 109 not recommended
Concrete Breakout Strength** 57.664 53.286 109 not recommended
* anchor having the highest loading **anchor group (anchors in tension)
3.1 Steel Strength
N
sa
= ESR value refer to ICC-ES ESR-2322
f
N
steel
N
ua
ACI 318-08 Eq. (D-1)
Variables



n





A
se,N
[mm
2
]





f
uta
[N/mm
2
]


1 113 549.86
Calculations



N
sa
[kN]


62.000
Results



N
sa
[kN]




fsteel





f
N
sa
[kN]





N
ua
[kN]


62.000 0.650 40.300 8.166
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

3
RTT:YAW
Corner (Strut)
20/07/2014

3.2 Bond Strength
N
ag
=
(
A
Na
A
Na0
)

yed,Na

yg,Na

yec,Na

yp,Na
N
a0
ICC-ES AC308 Eq. (D-16b)
f
N
ag
N
ua
ACI 318-08 Eq. (D-1)
A
Na
= see ICC-ES AC308, Part D.5.3.7
A
Na0
= s
2
cr,Na
ICC-ES AC308 Eq. (D-16c)
s
cr,Na
= 20d

tk,uncr
1450
3 h
ef
ICC-ES AC308 Eq. (D-16d)
c
cr,Na
=
s
cr,Na
2
ICC-ES AC308 Eq. (D-16e)
yed,Na
= 0.7 + 0.3
(
c
a,min
c
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16m)
yg,Na
=
yg,Na0
+
[(
s
avg
s
cr,Na
)
0.5
(1 -
yg,Na0
)
]
1.0 ICC-ES AC308 Eq. (D-16g)
yg,Na0
= n -
[
(n - 1)
(
tk,c
tk,max,c
)
1.5
]
1.0 ICC-ES AC308 Eq. (D-16h)
tk,max,c
=
k
c
p
d
h
ef
f
'
c
ICC-ES AC308 Eq. (D-16i)
yec,Na
=
(
1
1 +
2e
''
N
s
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16j)
yp,Na
= MAX
(
c
a,min
c
ac
,
c
cr,Na
c
ac
)
1.0 ICC-ES AC308 Eq. (D-16p)
N
a0
=
tk,c

kbond

p
d h
ef
ICC-ES AC308 Eq. (D-16f)
Variables


tk,c,uncr
[N/mm
2
]





d
anchor
[mm]





h
ef
[mm]





c
a,min
[mm]





s
avg
[mm]





n




tk,c
[N/mm
2
]


15.50 12 78 200 160 15 7.50



k
c






f
'
c
[psi]





e
c1,N
[mm]





e
c2,N
[mm]





c
ac
[mm]




kbond



17 3046 65 65 186 1.00
Calculations



s
cr,Na
[mm]





c
cr,Na
[mm]





A
Na
[mm
2
]





A
Na0
[mm
2
]




yed,Na





tk,max
[N/mm
2
]


234 117 484196 54756 1.000 7.64


yg,Na0





yg,Na





yec1,Na





yec2,Na





yp,Na






N
a0
[kN]


1.077 1.013 0.642 0.642 1.000 22.054
Results



N
ag
[kN]




fbond





f
N
ag
[kN]





N
ua
[kN]


81.579 0.650 53.026 57.664
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

4
RTT:YAW
Corner (Strut)
20/07/2014

3.3 Concrete Breakout Strength
N
cbg
=
(
A
Nc
A
Nc0
)

yec,N

yed,N

yc,N

ycp,N
N
b
ACI 318-08 Eq. (D-5)
f
N
cbg
N
ua
ACI 318-08 Eq. (D-1)
A
Nc
see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b)
A
Nc0
= 9 h
2
ef
ACI 318-08 Eq. (D-6)
yec,N
=
(
1
1 +
2 e
'
N
3 h
ef
)
1.0 ACI 318-08 Eq. (D-9)
yed,N
= 0.7 + 0.3
(
c
a,min
1.5h
ef
)
1.0 ACI 318-08 Eq. (D-11)
ycp,N
= MAX
(
c
a,min
c
ac
,
1.5h
ef
c
ac
)
1.0 ACI 318-08 Eq. (D-13)
N
b
= k
c

l
f
'
c
h
1.5
ef
ACI 318-08 Eq. (D-7)
Variables



h
ef
[mm]





e
c1,N
[mm]





e
c2,N
[mm]





c
a,min
[mm]




yc,N



78 65 65 200 1.000



c
ac
[mm]





k
c





l






f
'
c
[psi]


186 17 1 3046
Calculations



A
Nc
[mm
2
]





A
Nc0
[mm
2
]




yec1,N





yec2,N





yed,N





ycp,N






N
b
[kN]


484196 54756 0.642 0.642 1.000 1.000 22.458
Results



N
cbg
[kN]




fconcrete





f
N
cbg
[kN]





N
ua
[kN]


81.979 0.650 53.286 57.664
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

5
RTT:YAW
Corner (Strut)
20/07/2014

4 Shear load
Load V
ua
[kN] Capacity
ffff
V
n
[kN] Utilization
bbbbV
= V
ua
/
ffff
V
n
Status
Steel Strength* 1.679 22.500 8 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength
controls)**
26.870 291.474 10 OK
Concrete edge failure in direction x-** 19.000 63.053 31 OK
* anchor having the highest loading **anchor group (relevant anchors)
4.1 Steel Strength
V
sa
= (n 0.6 A
se,V
f
uta
) refer to ICC-ES ESR-2322
f
V
steel
V
ua
ACI 318-08 Eq. (D-2)
Variables



n





A
se,V
[mm
2
]





f
uta
[N/mm
2
]





(n 0.6 A
se,V
f
uta
) [kN]


1 113 549.86 37.500
Calculations



V
sa
[kN]


37.500
Results



V
sa
[kN]




fsteel





f
V
sa
[kN]





V
ua
[kN]


37.500 0.600 22.500 1.679
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

6
RTT:YAW
Corner (Strut)
20/07/2014

4.2 Pryout Strength (Bond Strength controls)
V
cpg
=k
cp[(
A
Na
A
Na0
)

yed,Na

yg,Na

yec,Na

yp,Na
N
a0]
ACI 318-08 Eq. (D-31)
f
V
cpg
V
ua
ACI 318-08 Eq. (D-1)
A
Na
see ICC-ES AC308, Part D.5.3.7
A
Na0
= s
2
cr,Na
ICC-ES AC308 Eq. (D-16c)
s
cr,Na
= 20 d

tk,uncr
1450
3 h
ef
ICC-ES AC308 Eq. (D-16d)
c
cr,Na
=
s
cr,Na
2
ICC-ES AC308 Eq. (D-16e)
yed,Na
= 0.7 + 0.3
(
c
a,min
c
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16m)
yg,Na
=
yg,Na0
+
[(
s
avg
s
cr,Na
)
0.5
(1 -
yg,Na0
)
]
1.0 ICC-ES AC308 Eq. (D-16g)
yg,Na0
= n -
[
(n - 1)
(
tk,c
tk,max,c
)
1.5
]
1.0 ICC-ES AC308 Eq. (D-16h)
tk,max,c
=
k
c
p
d
h
ef
f
'
c
ICC-ES AC308 Eq. (D-16i)
yec,Na
=
(
1
1 +
2
'
e,N
s
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16j)
yp,Na
= MAX
(
c
a,min
c
ac
,
c
cr,Na
c
ac
)
1.0 ICC-ES AC308 Eq. (D-16p)
N
a0
=
tk,c

kbond

p
d h
ef
ICC-ES AC308 Eq. (D-16f)
Variables



k
cp





tk,c,uncr
[N/mm
2
]




tk,c
[N/mm
2
]





d
anchor
[mm]





h
ef
[mm]





s
avg
[mm]





n


2.000 15.50 7.50 12 78 160 16



k
c






f
'
c
[psi]





e
c1,N
[mm]





e
c2,N
[mm]





c
a,min
[mm]





c
ac
[mm]




kbond



17 3046 0 0 200 186 1.00
Calculations



s
cr,Na
[mm]





c
cr,Na
[mm]





A
Na
[mm
2
]





A
Na0
[mm
2
]




yed,N





tk,max
[N/mm
2
]


234 117 509796 54756 1.000 7.64


yg,Na0





yg,Na





yec1,N





yec2,N





yp,Na






N
a0
[kN]


1.081 1.014 1.000 1.000 1.000 22.054
Results



V
cpg
[kN]




fconcrete





f
V
cpg
[kN]





V
ua
[kN]


416.392 0.700 291.474 26.870
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

7
RTT:YAW
Corner (Strut)
20/07/2014

4.3 Concrete edge failure in direction x-
V
cbg
=
(
A
Vc
A
Vc0
)

yec,V

yed,V

yc,V

yh,V

yparallel,V
V
b
ACI 318-08 Eq. (D-22)
f
V
cbg
V
ua
ACI 318-08 Eq. (D-2)
A
Vc
see ACI 318-08, Part D.6.2.1, Fig. RD.6.2.1(b)
A
Vc0
= 4.5 c
2
a1
ACI 318-08 Eq. (D-23)
yec,V
=
(
1
1 +
2e
'
v
3c
a1
)
1.0 ACI 318-08 Eq. (D-26)
yed,V
= 0.7 + 0.3
(
c
a2
1.5c
a1
)
1.0 ACI 318-08 Eq. (D-28)
yh,V
=

1.5c
a1
h
a
1.0 ACI 318-08 Eq. (D-29)
V
b
=
(
7
(
l
e
d
a
)
0.2
d
a)

l
f
'
c
c
1.5
a1
ACI 318-08 Eq. (D-24)
Variables



c
a1
[mm]





c
a2
[mm]





e
cV
[mm]




yc,V






h
a
[mm]


200 200 0 1.200 110



l
e
[mm]




l






d
a
[mm]





f
'
c
[psi]




yparallel,V



78 1.000 12 3046 2.000
Calculations



A
Vc
[mm
2
]





A
Vc0
[mm
2
]




yec,V





yed,V





yh,V






V
b
[kN]


107800 180000 1.000 1.000 1.651 37.948
Results



V
cbg
[kN]




fconcrete





f
V
cbg
[kN]





V
ua
[kN]


90.076 0.700 63.053 19.000
5 Combined tension and shear loads


bN





bV





z






Utilization
bN,V
[%]

Status
1.087 0.301 1.000 116 not recommended
bNV
= (
bN
+
bV
) / 1.2 <= 1
6 Warnings
Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!
Condition A applies when supplementary reinforcement is used. The factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
The ACI 318-08 version of the software does not account for adhesive anchor special design provisions corresponding to overhead
applications.
Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
Fastening does not meet the design criteria!
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

8
RTT:YAW
Corner (Strut)
20/07/2014

Coordinates Anchor mm
Anchor x y c
-x
c
+x
c
-y
c
+y
1 -240 -240 200 - 200 -
2 -80 -240 360 - 200 -
3 80 -240 520 - 200 -
4 240 -240 680 - 200 -
5 -240 -80 200 - 360 -
6 -80 -80 360 - 360 -
7 80 -80 520 - 360 -
8 240 -80 680 - 360 -
Anchor x y c
-x
c
+x
c
-y
c
+y
9 -240 80 200 - 520 -
10 -80 80 360 - 520 -
11 80 80 520 - 520 -
12 240 80 680 - 520 -
13 -240 240 200 - 680 -
14 -80 240 360 - 680 -
15 80 240 520 - 680 -
16 240 240 680 - 680 -
7 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-RE 500-SD + Rebar 12mm
Profile: Pipe; 108 x 108 x 4 mm Installation torque: 0.000 kNm
Hole diameter in the fixture: d
f
= 12 mm Hole diameter in the base material: 16 mm
Plate thickness (input): 1 mm Hole depth in the base material: 78 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 110 mm
Cleaning: Premium cleaning of the drilled hole is required


1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
60 160 160 160 60
6
0
1
6
0
1
6
0
1
6
0
6
0
x
y
300 300
3
0
0
3
0
0
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

9
RTT:YAW
Corner (Strut)
20/07/2014

8 Remarks; Your Cooperation Duties
Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

1
RTT:YAW
Corner (Strut)
20/07/2014

Specifier's comments: 225 degree wind,Tension at diagonal /w Slab thk=110, f'c=21N/mm2
1 Input data
Anchor type and diameter: HIT-RE 500-SD + Rebar 12mm
Effective embedment depth: h
ef,opti
= 78 mm (h
ef,limit
= 78 mm)
Material: B500B
Evaluation Service Report: ESR-2322
Issued I Valid: 1/02/2014 | 1/04/2016
Proof: design method ACI 318 / AC308
Stand-off installation: e
b
= 0 mm (no stand-off); t = 1 mm
Anchor plate: l
x
x l
y
x t = 600 mm x 600 mm x 1 mm; (Recommended plate thickness: not calculated)
Profile: Pipe; (L x W x T) = 108 mm x 108 mm x 4 mm
Base material: cracked concrete, , f
c
' = 3046 psi; h = 110 mm, Temp. short/long: 40/24 C
Installation: hammer drilled hole, installation condition: dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: > No. 4 bar
Seismic loads (cat. C, D, E, or F) no
Geometry [mm] & Loading [kN, kNm]
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

2
RTT:YAW
Corner (Strut)
20/07/2014

2 Load case/Resulting anchor forces
Load case: Design loads
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.000 1.679 -1.188 -1.188
2 0.448 1.679 -1.188 -1.188
3 1.992 1.679 -1.188 -1.188
4 3.536 1.679 -1.188 -1.188
5 0.448 1.679 -1.188 -1.188
6 1.992 1.679 -1.188 -1.188
7 3.536 1.679 -1.188 -1.188
8 5.079 1.679 -1.188 -1.188
9 1.992 1.679 -1.188 -1.188
10 3.536 1.679 -1.188 -1.188
11 5.079 1.679 -1.188 -1.188
12 6.623 1.679 -1.188 -1.188
13 3.536 1.679 -1.188 -1.188
14 5.079 1.679 -1.188 -1.188
15 6.623 1.679 -1.188 -1.188
16 8.166 1.679 -1.188 -1.188
max. concrete compressive strain: 0.10 []
max. concrete compressive stress:
2.99 [N/mm
2
]
resulting tension force in (x/y)=(81/81): 57.664 [kN]
resulting compression force in (x/y)=(-242/-242): 27.164 [kN]
Tension
Compression

1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
x
y
3 Tension load
Load N
ua
[kN] Capacity
ffff
N
n
[kN] Utilization
bbbbN
= N
ua
/
ffff
N
n
Status
Steel Strength* 8.166 40.300 21 OK
Bond Strength** 57.664 53.026 109 not recommended
Concrete Breakout Strength** 57.664 53.286 109 not recommended
* anchor having the highest loading **anchor group (anchors in tension)
3.1 Steel Strength
N
sa
= ESR value refer to ICC-ES ESR-2322
f
N
steel
N
ua
ACI 318-08 Eq. (D-1)
Variables



n





A
se,N
[mm
2
]





f
uta
[N/mm
2
]


1 113 549.86
Calculations



N
sa
[kN]


62.000
Results



N
sa
[kN]




fsteel





f
N
sa
[kN]





N
ua
[kN]


62.000 0.650 40.300 8.166
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

3
RTT:YAW
Corner (Strut)
20/07/2014

3.2 Bond Strength
N
ag
=
(
A
Na
A
Na0
)

yed,Na

yg,Na

yec,Na

yp,Na
N
a0
ICC-ES AC308 Eq. (D-16b)
f
N
ag
N
ua
ACI 318-08 Eq. (D-1)
A
Na
= see ICC-ES AC308, Part D.5.3.7
A
Na0
= s
2
cr,Na
ICC-ES AC308 Eq. (D-16c)
s
cr,Na
= 20d

tk,uncr
1450
3 h
ef
ICC-ES AC308 Eq. (D-16d)
c
cr,Na
=
s
cr,Na
2
ICC-ES AC308 Eq. (D-16e)
yed,Na
= 0.7 + 0.3
(
c
a,min
c
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16m)
yg,Na
=
yg,Na0
+
[(
s
avg
s
cr,Na
)
0.5
(1 -
yg,Na0
)
]
1.0 ICC-ES AC308 Eq. (D-16g)
yg,Na0
= n -
[
(n - 1)
(
tk,c
tk,max,c
)
1.5
]
1.0 ICC-ES AC308 Eq. (D-16h)
tk,max,c
=
k
c
p
d
h
ef
f
'
c
ICC-ES AC308 Eq. (D-16i)
yec,Na
=
(
1
1 +
2e
''
N
s
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16j)
yp,Na
= MAX
(
c
a,min
c
ac
,
c
cr,Na
c
ac
)
1.0 ICC-ES AC308 Eq. (D-16p)
N
a0
=
tk,c

kbond

p
d h
ef
ICC-ES AC308 Eq. (D-16f)
Variables


tk,c,uncr
[N/mm
2
]





d
anchor
[mm]





h
ef
[mm]





c
a,min
[mm]





s
avg
[mm]





n




tk,c
[N/mm
2
]


15.50 12 78 200 160 15 7.50



k
c






f
'
c
[psi]





e
c1,N
[mm]





e
c2,N
[mm]





c
ac
[mm]




kbond



17 3046 65 65 186 1.00
Calculations



s
cr,Na
[mm]





c
cr,Na
[mm]





A
Na
[mm
2
]





A
Na0
[mm
2
]




yed,Na





tk,max
[N/mm
2
]


234 117 484196 54756 1.000 7.64


yg,Na0





yg,Na





yec1,Na





yec2,Na





yp,Na






N
a0
[kN]


1.077 1.013 0.642 0.642 1.000 22.054
Results



N
ag
[kN]




fbond





f
N
ag
[kN]





N
ua
[kN]


81.579 0.650 53.026 57.664
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

4
RTT:YAW
Corner (Strut)
20/07/2014

3.3 Concrete Breakout Strength
N
cbg
=
(
A
Nc
A
Nc0
)

yec,N

yed,N

yc,N

ycp,N
N
b
ACI 318-08 Eq. (D-5)
f
N
cbg
N
ua
ACI 318-08 Eq. (D-1)
A
Nc
see ACI 318-08, Part D.5.2.1, Fig. RD.5.2.1(b)
A
Nc0
= 9 h
2
ef
ACI 318-08 Eq. (D-6)
yec,N
=
(
1
1 +
2 e
'
N
3 h
ef
)
1.0 ACI 318-08 Eq. (D-9)
yed,N
= 0.7 + 0.3
(
c
a,min
1.5h
ef
)
1.0 ACI 318-08 Eq. (D-11)
ycp,N
= MAX
(
c
a,min
c
ac
,
1.5h
ef
c
ac
)
1.0 ACI 318-08 Eq. (D-13)
N
b
= k
c

l
f
'
c
h
1.5
ef
ACI 318-08 Eq. (D-7)
Variables



h
ef
[mm]





e
c1,N
[mm]





e
c2,N
[mm]





c
a,min
[mm]




yc,N



78 65 65 200 1.000



c
ac
[mm]





k
c





l






f
'
c
[psi]


186 17 1 3046
Calculations



A
Nc
[mm
2
]





A
Nc0
[mm
2
]




yec1,N





yec2,N





yed,N





ycp,N






N
b
[kN]


484196 54756 0.642 0.642 1.000 1.000 22.458
Results



N
cbg
[kN]




fconcrete





f
N
cbg
[kN]





N
ua
[kN]


81.979 0.650 53.286 57.664
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

5
RTT:YAW
Corner (Strut)
20/07/2014

4 Shear load
Load V
ua
[kN] Capacity
ffff
V
n
[kN] Utilization
bbbbV
= V
ua
/
ffff
V
n
Status
Steel Strength* 1.679 22.500 8 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength
controls)**
26.870 291.474 10 OK
Concrete edge failure in direction x-** 26.870 28.374 95 OK
* anchor having the highest loading **anchor group (relevant anchors)
4.1 Steel Strength
V
sa
= (n 0.6 A
se,V
f
uta
) refer to ICC-ES ESR-2322
f
V
steel
V
ua
ACI 318-08 Eq. (D-2)
Variables



n





A
se,V
[mm
2
]





f
uta
[N/mm
2
]





(n 0.6 A
se,V
f
uta
) [kN]


1 113 549.86 37.500
Calculations



V
sa
[kN]


37.500
Results



V
sa
[kN]




fsteel





f
V
sa
[kN]





V
ua
[kN]


37.500 0.600 22.500 1.679
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

6
RTT:YAW
Corner (Strut)
20/07/2014

4.2 Pryout Strength (Bond Strength controls)
V
cpg
=k
cp[(
A
Na
A
Na0
)

yed,Na

yg,Na

yec,Na

yp,Na
N
a0]
ACI 318-08 Eq. (D-31)
f
V
cpg
V
ua
ACI 318-08 Eq. (D-1)
A
Na
see ICC-ES AC308, Part D.5.3.7
A
Na0
= s
2
cr,Na
ICC-ES AC308 Eq. (D-16c)
s
cr,Na
= 20 d

tk,uncr
1450
3 h
ef
ICC-ES AC308 Eq. (D-16d)
c
cr,Na
=
s
cr,Na
2
ICC-ES AC308 Eq. (D-16e)
yed,Na
= 0.7 + 0.3
(
c
a,min
c
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16m)
yg,Na
=
yg,Na0
+
[(
s
avg
s
cr,Na
)
0.5
(1 -
yg,Na0
)
]
1.0 ICC-ES AC308 Eq. (D-16g)
yg,Na0
= n -
[
(n - 1)
(
tk,c
tk,max,c
)
1.5
]
1.0 ICC-ES AC308 Eq. (D-16h)
tk,max,c
=
k
c
p
d
h
ef
f
'
c
ICC-ES AC308 Eq. (D-16i)
yec,Na
=
(
1
1 +
2
'
e,N
s
cr,Na
)
1.0 ICC-ES AC308 Eq. (D-16j)
yp,Na
= MAX
(
c
a,min
c
ac
,
c
cr,Na
c
ac
)
1.0 ICC-ES AC308 Eq. (D-16p)
N
a0
=
tk,c

kbond

p
d h
ef
ICC-ES AC308 Eq. (D-16f)
Variables



k
cp





tk,c,uncr
[N/mm
2
]




tk,c
[N/mm
2
]





d
anchor
[mm]





h
ef
[mm]





s
avg
[mm]





n


2.000 15.50 7.50 12 78 160 16



k
c






f
'
c
[psi]





e
c1,N
[mm]





e
c2,N
[mm]





c
a,min
[mm]





c
ac
[mm]




kbond



17 3046 0 0 200 186 1.00
Calculations



s
cr,Na
[mm]





c
cr,Na
[mm]





A
Na
[mm
2
]





A
Na0
[mm
2
]




yed,N





tk,max
[N/mm
2
]


234 117 509796 54756 1.000 7.64


yg,Na0





yg,Na





yec1,N





yec2,N





yp,Na






N
a0
[kN]


1.081 1.014 1.000 1.000 1.000 22.054
Results



V
cpg
[kN]




fconcrete





f
V
cpg
[kN]





V
ua
[kN]


416.392 0.700 291.474 26.870
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

7
RTT:YAW
Corner (Strut)
20/07/2014

4.3 Concrete edge failure in direction x-
V
cbg
=
(
A
Vc
A
Vc0
)

yec,V

yed,V

yc,V

yh,V

yparallel,V
V
b
ACI 318-08 Eq. (D-22)
f
V
cbg
V
ua
ACI 318-08 Eq. (D-2)
A
Vc
see ACI 318-08, Part D.6.2.1, Fig. RD.6.2.1(b)
A
Vc0
= 4.5 c
2
a1
ACI 318-08 Eq. (D-23)
yec,V
=
(
1
1 +
2e
'
v
3c
a1
)
1.0 ACI 318-08 Eq. (D-26)
yed,V
= 0.7 + 0.3
(
c
a2
1.5c
a1
)
1.0 ACI 318-08 Eq. (D-28)
yh,V
=

1.5c
a1
h
a
1.0 ACI 318-08 Eq. (D-29)
V
b
=
(
7
(
l
e
d
a
)
0.2
d
a)

l
f
'
c
c
1.5
a1
ACI 318-08 Eq. (D-24)
Variables



c
a1
[mm]





c
a2
[mm]





e
cV
[mm]




yc,V






h
a
[mm]


200 200 0 1.200 110



l
e
[mm]




l






d
a
[mm]





f
'
c
[psi]




yparallel,V



78 1.000 12 3046 1.000
Calculations



A
Vc
[mm
2
]





A
Vc0
[mm
2
]




yec,V





yed,V





yh,V






V
b
[kN]


107800 180000 1.000 0.900 1.651 37.948
Results



V
cbg
[kN]




fconcrete





f
V
cbg
[kN]





V
ua
[kN]


40.534 0.700 28.374 26.870
5 Combined tension and shear loads


bN





bV





z






Utilization
bN,V
[%]

Status
1.087 0.947 1.000 170 not recommended
bNV
= (
bN
+
bV
) / 1.2 <= 1
6 Warnings
Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. The anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading!
Condition A applies when supplementary reinforcement is used. The factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions
The ACI 318-08 version of the software does not account for adhesive anchor special design provisions corresponding to overhead
applications.
Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!
Fastening does not meet the design criteria!
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

8
RTT:YAW
Corner (Strut)
20/07/2014

Coordinates Anchor mm
Anchor x y c
-x
c
+x
c
-y
c
+y
1 -240 -240 200 - 200 -
2 -80 -240 360 - 200 -
3 80 -240 520 - 200 -
4 240 -240 680 - 200 -
5 -240 -80 200 - 360 -
6 -80 -80 360 - 360 -
7 80 -80 520 - 360 -
8 240 -80 680 - 360 -
Anchor x y c
-x
c
+x
c
-y
c
+y
9 -240 80 200 - 520 -
10 -80 80 360 - 520 -
11 80 80 520 - 520 -
12 240 80 680 - 520 -
13 -240 240 200 - 680 -
14 -80 240 360 - 680 -
15 80 240 520 - 680 -
16 240 240 680 - 680 -
7 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-RE 500-SD + Rebar 12mm
Profile: Pipe; 108 x 108 x 4 mm Installation torque: 0.000 kNm
Hole diameter in the fixture: d
f
= 12 mm Hole diameter in the base material: 16 mm
Plate thickness (input): 1 mm Hole depth in the base material: 78 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 110 mm
Cleaning: Premium cleaning of the drilled hole is required


1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
60 160 160 160 60
6
0
1
6
0
1
6
0
1
6
0
6
0
x
y
300 300
3
0
0
3
0
0
www.hilti.at Profis Anchor 2.4.8
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
MTE
Kyaw Thura
No.,9,Bld.51,9Qtr.,Hlaing Tsp,YGN,MM
+95095019332 |
engineering.mte@gmail.com
Page:
Project:
Sub-Project I Pos. No.:
Date:

9
RTT:YAW
Corner (Strut)
20/07/2014

8 Remarks; Your Cooperation Duties
Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.
EMBEDMENT PLATE CALCULATION (Demo Version)
Per Building Code Requirements for Structural Concrete ( ACI 318-08)
Design of (4) Stud Embed Plate Anchorage per Appendix D
Job Name: RTT Subject: Back Plate Date: 21/07/2014 2:07
Job Number: YAW Originator: ND Checker: MTE
Input Data:
N
ua(max.)
= 39.00 kN
V
ua(Max.),Any direction
=
9.20 kN h
ef
(mm)= 150
M
ua(Max.),Any direction
= 9.90 kN
V
ua,x
= 6.51 kN
V
ua,y
=
6.51 kN Direction of Wind ()= 45 deg.
M
ua,x
= 7.00 kN-m Pedestal,x--> D1= 550 mm
M
ua,y
= 7.00 kN-m Pedestal,y--> D2= 550 mm
e
x(Max.)
= 0.18 m Pedestal,Z--> H= 250 mm
e
x,y(Max.)
= 0.18 m
170 250
thk. Of PL(mm)
170 12 250 150
250
Steel strength of anchor in tension 0.53
Concrete Breakout strength of anchor in tension 0.37
Side-Face Blowout strength of anchor in tension N/A
Steel strength of anchor in shear 0.03
Breakout strength of anchor in shear (X-Dir, Perp.) 0.32
Breakout strength of anchor in shear (Y-Dir, Perp.) 0.24
Breakout strength of anchor in shear (X-Dir, Parallel) 0.12
Breakout strength of anchor in shear (Y-Dir, Parallel) 0.12
Concrete Pryout strength of anchor in shear 0.04
Interaction of tensile and shear forces 0.85
Dimensional Requirements
Minimum Spacing requirements SATISFACTORY
Minimum Concrete Edge distance SATISFACTORY
Minimum Steel Edge distance SATISFACTORY
Minimum Concrete thickness SATISFACTORY
0
90
X
Y
Req'd Back PL
Bolt spacing
Anchor Elevation
D1
D2
Concrete
Back Plate
This Checking is only for
Pedestal dimensions.
The tower supplier is
needed to design Back
Plate.
Embedment, hef
Summary of Check Stress Ratio
Back Plate Analysis 1 of5
EMBEDMENT PLATE CALCULATION (Demo Version)
Per Building Code Requirements for Structural Concrete ( ACI 318-08)
Design of (4) Stud Embed Plate Anchorage per Appendix D
Job Name: RTT Subject: Back Plate Date: 21/07/2014 2:07
Job Number: YAW Originator: ND Checker: MTE
Loads:
N
ua
= 8.7672 kips (Tension)
V
ua,x
= 1.46241 kips
V
ua,y
= 1.46241 kips c
x1
= 190 c
y1
= 190
ex = 7.07 in. c
x2
= 190 c
y2
= 190
ey = 7.07 in. S
x1
= 170 S
y1
= 170
b
x1
= 40 b
y1
= 40
b
x2
= 40 b
y2
= 40
Dimensions:
bx1 = 1.57 in. PL Edge Distance
bx2 = 1.57 in. PL Edge Distance f'c= 30 Mpa Base concrete
by1 = 1.57 in. PL Edge Distance fy
(Anchor)
= 50 Ksi Strength of Anchor
by2 = 1.57 in. PL Edge Distance
sx1 = 6.69 in. Spacing in x-dir.
of DB bar=
20 mm
sy1 = 6.69 in. Spacing in y-dir.
cx1 = 7.48 in. Edge Distance to Conc.
cx2 = 7.48 in. Edge Distance to Conc. Stud Reactions (k)
cy1 = 7.48 in. Edge Distance to Conc. Axial Rz Shear Rh
cy2 = 7.48 in. Edge Distance to Conc. #1: 7.07 0.52
#2: -2.19 0.52
Parameters: #3: -2.19 0.52
Anchor Dia., d
b
= 3/4 in. Stud Anchor Diameter #4: -11.45 0.52
Concrete, f'
c
=
4350 psi Specified Compressive strength of Concrete
Anchor, f
y
= 51 ksi Specified Yield strength of anchor steel
Anchor, f
uta
= 65 ksi Specified Tensile strength of anchor steel
Steel Element = Ductile (Section D.1)
Embedment, hef = 4.93 in. The overall depth through which the anchor transfers force to and from the concrete.
Thickness, h
a
=
8 in. Thickness of member in which an anchor is located,
Supp. Reinf.? Yes Potential Failure Surfaces crossed by supplementary reinforcement (Section D.4.2.1)
Cracking Anticip.? No Cracking at service levels (Section D.6.2.7) Case? Case 2
Seismic (Chapt.21) No Anchors are located in structure assigned to Seismic Design Category C, D, E, or F. (Sect. D3.3)
Concrete Type = Normalwt (Section 2.2)
Per Sect. D.6.2.3? Yes For cast-in headed studs that are continuously welded to steel attachments having a minimum
thickness of > 3/8" and db/2 provided that: (a) spacing > 2.5 in. and (b) reinforcement is provided
at the corners if ca2 < 1.5hef.
Results:
1. Steel strength of anchor in tension: (Section D.5.1)
N
sa
=A
se
f
uta
(Equation D-3)
A
se, N
=
0.44
in
2
Effective Cross Sectional Area of Anchor
N
sa
= 28.60 kips = 0.75
N
sa
=
21.45 kips / bolt
N
u,max
=
11.45
kips =>
OK
(continued)
Dimension (mm)
Material strength
Anchor Bolt
All calculation units are in Kip, in..
Back Plate Analysis 2 of5
EMBEDMENT PLATE CALCULATION (Demo Version)
Per Building Code Requirements for Structural Concrete ( ACI 318-08)
Design of (4) Stud Embed Plate Anchorage per Appendix D
Job Name: RTT Subject: Back Plate Date: 21/07/2014 2:07
Job Number: YAW Originator: ND Checker: MTE
2. Concrete Breakout strength of anchor in tension: (Section D.5.2)
N
cbg
= A
nc
Y
ec,N
Y
ed,N
Y
c,N
Y
cp,N
N
b
(Equation D-5)
A
nco
A
nc
= 461.91
in
2
A
nco
= 219.02
in
2
A
nco
= 9h
ef
2
Y
ec,N(x-dir)
=
0.83
Y
ec,N
=
1
< 1
Y
ec,N(y-dir)
= 0.83 (1 + 2e'
N
)
Y
ec,N(comb.)
= 0.69 3h
ef
Y
ed,N
= 1.00 Y
ed,N
= 1 (if C
min
> 1.5h
ef
) -OR- 0.7 + 0.3c
min
/ (1.5 h
ef
) (if C
min
< 1.5h
ef
)
e'
Nx
= 2.42 in Eccentricity of all tension forces on a group of anchors in the x dir.
e'
Ny
= 2.42 in Eccentricity of all tension forces on a group of anchors in the y dir.
Y
c,N
= 1.25 Y
c,N
= 1.25 for Cast-in-place anchors
Y
cp,N
= 1 Y
cp,N
= 1.0 for Cast-in-place anchors
l = 1
k
c
=
24
k
c
= 24 for Cast-in-place anchors
N
b
= 17.34 kips N
b
=
klf'
c
1/2
h
ef
3/2
N
b,max
=
16lf'
c
1/2
h
ef
5/3
if 11in. < h
ef
< 25in.
= 0.75
N
cbg
= 23.75 kips N
ua
= 8.77
kips =>
OK
3. Pullout strength of anchor in tension: (Section D.5.3)
N
pn
=Y
c,P
N
p
(Equation D-14)
A
brg
= 0.79
in
2
N
p
= 27.49 N
p
=A
brg
8f'
c
(Equation D-15)
Y
c,P
= 1.40 = 0.75
N
pn
= 28.87 kips / bolt N
u,max
= 11.45
kips =>
OK
4. Concrete Side-Face Blowout strength of Headed anchor in tension: (Section D.5.4)
N
sb
= 160c
a1
A
brg
1/2
lf'
c
1/2
(Equation D-17)
N
sbg
= (1 + s/6c
a1
)N
sb
(Equation D-18)
C
a1
= 7.48
C
a2
= 7.48
C
a2
/ C
a1
= 1.00
1.0 < C
a2
/ C
a1
< 3.0
Factor = 0.50
N
sb
= N/A kips Ca1 > 0.4 hef => Not Applicable (Section D.5.4.1) = 0.75
N
sbg
= N/A kips Ca1 > 0.4 hef and/or s > 6ca1=> Not Applicable (Section D.5.4.2)
N =
N/A kips N
u,max
= 2.19
kips =>
N/A
5. Steel strength of anchor in shear: (Section D.6.1)
V
sa
=A
se,V
f
uta
(Equation D-19)
A
se,V
= 0.44
in
2
Effective Cross Sectional Area of Anchor
f
uta
= 65.00 ksi
V
sa
= 28.60 kips/bolt = 0.65
V
sa
= 18.59 kips/bolt V
u,max
= 0.52
kips =>
OK
(continued)
Back Plate Analysis 3 of5
EMBEDMENT PLATE CALCULATION (Demo Version)
Per Building Code Requirements for Structural Concrete ( ACI 318-08)
Design of (4) Stud Embed Plate Anchorage per Appendix D
Job Name: RTT Subject: Back Plate Date: 21/07/2014 2:07
Job Number: YAW Originator: ND Checker: MTE
6. Concrete Breakout strength of anchor in shear: (Section D.6.2)*
Vb = 8
(l
e
/d
a
)
0.2
d
a
1/2
lf'
c
1/2
C
a1
1.5
(Equation D-25)
V
cbg
= A
vc
Y
ec,V
Y
ed,V
Y
c,V
Y
h,V
V
b
(Equation D-22)
A
vco
h
a
= 8.00 in Thickness of member in which an anchor is located
l
e
= 4.93 in Load bearing length (le = minimum of hef or 8 d
a
))
d
a
= 0.75 in d
a
= d
b
(Outside diameter of shaft of headed stud)
e'
vx
= 7.07 in Eccentricity of shear force on a group of anchors in the x dir.
e'
vy
= 7.07 in Eccentricity of shear force on a group of anchors in the y dir.
l =
1 Concrete Type Modification Factor
Y
c,V
= 1.40 Cracking Modification Factor (per Section D.6.2.7)
X - Direction (perpendicular to edge):
ca1 = 12.03 in ca1 = (cx1 or cx2) + sx1 or minimum required per Section D.6.2.4
Y
ec,V
= 0.72 Y
ec,V
= 1 / (1+2e'v,y/(3ca1))
Y
ed,V
= 0.82 Y
ed,V
= 1 (if ca2 > 1.5ca1) or 0.7 + 0.3ca2/(1.5ca1)
Y
h,V
= 1.00 Y
h,V
= (1.5ca1/ha)^0.5 < 1.0
A
VC
= 173.23
in
2
A
VC
= (MIN(1.5ca1,ca2(a))+MIN(3ca1,sy1)+MIN(1.5ca1,ca2(b))) x MIN(1.5*ca1,ha)
A
VCO
= 650.84
in
2
A
VCO
= 4.5(ca1)^2
V
b
= 27.78 kips
V
cbg,x
= 6.13 kips = 0.75
V
cbg,x
= 4.60 kips V
u,max
= 1.46
kips =>
OK
Y - Direction (perpendicular to edge):
ca1 = 5.33 in ca1 = (cy1 or cy2) + sy1 or minimum required per Section D.6.2.4
Y
ec,V
= 0.53 Y
ec,V
= 1 / (1+2e'v,y/(3ca1))
Y
ed,V
= 0.98 Y
ed,V
= 1 (if ca2 > 1.5ca1) or 0.7 + 0.3ca2/(1.5ca1)
Y
h,V
= 1.00 Y
h,V
= (1.5ca1/ha)^0.5 < 1.0
A
VC
= 173.23
in
2
A
VC
= (MIN(1.5ca1,ca2(a))+MIN(3ca1,sy1)+MIN(1.5ca1,ca2(b))) x MIN(1.5*ca1,ha)
A
VCO
= 128.00
in
2
A
VCO
= 4.5(ca1)^2
V
b
= 8.20 kips Vb = 8
(l
e
/d
a
)
0.2
d
a
1/2
lf'
c
1/2
C
a1
1.5
V
cbg,y
= 8.09 kips = 0.75
V
cbg,y
= 6.07 kips V
u,max
= 1.46
kips =>
OK
X - Direction (parallel to edge):
V
cbg,x
= 16.18 kips Per Section D.6.2.1.(c) = 0.75
V
cbg,x
= 12.14 kips V
u,max
= 1.46
kips =>
OK
Y - Direction (parallel to edge):
V
cbg,y
= 16.18 kips Per Section D.6.2.1.(c) = 0.75
V
cbg,y
= 12.14 kips V
u,max
= 1.46
kips =>
OK
*NOTE: Case 1 calculation (evaluation of bolt to closest edge) not req'd. (See Section RD6.2.1, 3rd paragraph)
7. Concrete Pryout strength of anchor in shear: (Section D.6.3)
V
cpg
=k
cp
N
cbg
(Equation D-31)
k
cp
= 2.00
kcp = 1.0 (for hef < 2.5in.); kcp = 2.0 (for hef > 2.5in.)
N
cbg
= 31.66 kips from Equation D-5 (See previous Section D.5.2 calcs)
V
cpg
= 63.33 kips = 0.75
V
cpg
= 47.50 kips V
u,max
= 2.07
kips =>
OK
V
u,max
= sum of each bolt shear
(continued)
Back Plate Analysis 4 of5
EMBEDMENT PLATE CALCULATION (Demo Version)
Per Building Code Requirements for Structural Concrete ( ACI 318-08)
Design of (4) Stud Embed Plate Anchorage per Appendix D
Job Name: RTT Subject: Back Plate Date: 21/07/2014 2:07
Job Number: YAW Originator: ND Checker: MTE
8. Interaction of tensile and shear forces: (Section D.7)
Tension Ratio = N
UA
N
n
Steel: 0.534 Steel strength of anchor in tension
Breakout: 0.369 Concrete Breakout strength of anchor in tension
Pullout: 0.397 Pullout strength of anchor in tension
Sideface Blowout: N/A Concrete Side-Face Blowout strength of Headed anchor
in tension
Shear Ratio = V
UA
V
n
Steel: 0.028 Steel strength of anchor in shear
Breakout (Case2): 0.318 Concrete Breakout strength of anchor in shear - perp.
Breakout (Case3): 0.120 Concrete Breakout strength of anchor in shear - parallel
Pryout: 0.044 Concrete Pryout strength of anchor in shear
Combined Stress Ratio (CSR) = N
UA
V
UA
N
n
V
n
CSR: 0.85
EMBEDMENT STRENGTH (Per ACI 318-08 - Appendix D) OK
9. Required edge distances & spacings: (ACI 318-08Section D.7&ASIC Table J 3.4)
s
min
= 3.00 in Minimum spacing = s
min
= 4 x da (for untorqued cast-in-place anchors)
s
act
= 6.69 in Actual lesser of two spacings, sy1 &sx1 OK
Conc. Edge dist, min = 4.50 in Assume torqued cast-in headed anchors (conservative). See Section 7.7 else.
Conc. Edge dist, act = 7.48 in Actual lesser of four edge distances, cy1/2 &cx1/2 OK
Edge dist, min = 1.25 in Minimum steel edge distance per Table J3.4
Edge dist, act = 1.57 in Actual lesser of four edge distances, cy1/2 &cx1/2 OK
Req'd thick., ha,
min
= 5.68 in. ha,min = hef + 0.75"
Actual thickness, ha = 8.00 in. OK
10. Plate Bearing: (ACI 318-08Section 10.14)
Plate Area, A1 = 96.88 in
2
A1 = (bx1 + sx1 + bx2)(by1 + sy1 + by2)
Concrete Area, A2 = 468.88 in
2
A2 = (cx1 + sx1 + cx2)(cy1 + sy1 +cy2)
Multiplication Factor = 2.00 Multiplication Factor = (A2/A1)^0.5 < 2.0
Pn = 716.39 kips Pn = 0.85fc'A1 x (Multiplication Factor)
Pn = 465.65 kips N
ua
= N/A
kips =>
N/A
11. Plate Punching Shear: (ACI 318-08Section 11.12.2.1)
Perimeter, bo = 19.69 in bo = (bx1 + sx1 + bx2) + (by1 + sy1 + by2)
Concrete depth, d = 6.00 in d = ha - 2in. (Assume 2"clear cover)
b = 1.00 b = Length of: Long side of plate / Short side of plate
Factor = 4.00 Factor = Minimum of (2 + 4/b) or 4
Vc = 31.16 kips Vc = Factor x (fc')^0.5 x bo x d
Vc = 20.25 kips N
ua
= N/A
kips =>
N/A
+ < 1.2
Back Plate Analysis 5 of5
EMBEDMENT PLATE CALCULATION (Demo Version)
Per Building Code Requirements for Structural Concrete ( ACI 318-08)
Design of (4) Stud Embed Plate Anchorage per Appendix D
Job Name: RTT-Strut Subject: Back Plate Date: 21/07/2014 2:14
Job Number: YAW Originator: ND Checker: MTE
Input Data:
N
ua(max.)
= 32.40 kN
V
ua(Max.),Any direction
=
27.00 kN h
ef
(mm)= 150
M
ua(Max.),Any direction
= 2.40 kN
V
ua,x
= 19.09 kN
V
ua,y
=
19.09 kN Direction of Wind ()= 45 deg.
M
ua,x
= 1.70 kN-m Pedestal,x--> D1= 550 mm
M
ua,y
= 1.70 kN-m Pedestal,y--> D2= 550 mm
e
x(Max.)
= 0.05 m Pedestal,Z--> H= 250 mm
e
x,y(Max.)
= 0.05 m
202 352
thk. Of PL(mm)
80 12 230 150
250
Steel strength of anchor in tension 0.24
Concrete Breakout strength of anchor in tension 0.31
Side-Face Blowout strength of anchor in tension N/A
Steel strength of anchor in shear 0.08
Breakout strength of anchor in shear (X-Dir, Perp.) 0.79
Breakout strength of anchor in shear (Y-Dir, Perp.) 0.48
Breakout strength of anchor in shear (X-Dir, Parallel) 0.24
Breakout strength of anchor in shear (Y-Dir, Parallel) 0.24
Concrete Pryout strength of anchor in shear 0.13
Interaction of tensile and shear forces 1.10
Dimensional Requirements
Minimum Spacing requirements SATISFACTORY
Minimum Concrete Edge distance SATISFACTORY
Minimum Steel Edge distance SATISFACTORY
Minimum Concrete thickness SATISFACTORY
0
90
X
Y
Req'd Back PL
Bolt spacing
Anchor Elevation
D1
D2
Concrete
Pedestal
Back Plate
This Checking is only for
Pedestal dimensions.
The tower supplier is
needed to design Back
Plate.
Embedment, hef
Summary of Check Stress Ratio
Back PL
Back Plate Analysis 1 of5
EMBEDMENT PLATE CALCULATION (Demo Version)
Per Building Code Requirements for Structural Concrete ( ACI 318-08)
Design of (4) Stud Embed Plate Anchorage per Appendix D
Job Name: RTT-Strut Subject: Back Plate Date: 21/07/2014 2:14
Job Number: YAW Originator: ND Checker: MTE
Loads:
N
ua
= 7.28352 kips (Tension)
V
ua,x
= 4.2918553 kips
V
ua,y
= 4.2918553 kips c
x1
= 174 c
y1
= 235
ex = 2.06 in. c
x2
= 174 c
y2
= 235
ey = 2.06 in. S
x1
= 202 S
y1
= 80
b
x1
= 75 b
y1
= 75
b
x2
= 75 b
y2
= 75
Dimensions:
bx1 = 2.95 in. PL Edge Distance
bx2 = 2.95 in. PL Edge Distance f'c= 30 Mpa Base concrete
by1 = 2.95 in. PL Edge Distance fy
(Anchor)
= 50 Ksi Strength of Anchor
by2 = 2.95 in. PL Edge Distance
sx1 = 7.95 in. Spacing in x-dir.
of DB bar=
20 mm
sy1 = 3.15 in. Spacing in y-dir.
cx1 = 6.85 in. Edge Distance to Conc.
cx2 = 6.85 in. Edge Distance to Conc. Stud Reactions (k)
cy1 = 9.25 in. Edge Distance to Conc. Axial Rz Shear Rh
cy2 = 9.25 in. Edge Distance to Conc. #1: 1.51 1.52
#2: -0.38 1.52
Parameters: #3: -3.26 1.52
Anchor Dia., d
b
= 3/4 in. Stud Anchor Diameter #4: -5.15 1.52
Concrete, f'
c
=
4350 psi Specified Compressive strength of Concrete
Anchor, f
y
= 51 ksi Specified Yield strength of anchor steel
Anchor, f
uta
= 65 ksi Specified Tensile strength of anchor steel
Steel Element = Ductile (Section D.1)
Embedment, hef = 4.93 in. The overall depth through which the anchor transfers force to and from the concrete.
Thickness, h
a
=
8 in. Thickness of member in which an anchor is located,
Supp. Reinf.? Yes Potential Failure Surfaces crossed by supplementary reinforcement (Section D.4.2.1)
Cracking Anticip.? No Cracking at service levels (Section D.6.2.7) Case? Case 2
Seismic (Chapt.21) No Anchors are located in structure assigned to Seismic Design Category C, D, E, or F. (Sect. D3.3)
Concrete Type = Normalwt (Section 2.2)
Per Sect. D.6.2.3? Yes For cast-in headed studs that are continuously welded to steel attachments having a minimum
thickness of > 3/8" and db/2 provided that: (a) spacing > 2.5 in. and (b) reinforcement is provided
at the corners if ca2 < 1.5hef.
Results:
1. Steel strength of anchor in tension: (Section D.5.1)
N
sa
=A
se
f
uta
(Equation D-3)
A
se, N
=
0.44
in
2
Effective Cross Sectional Area of Anchor
N
sa
= 28.60 kips = 0.75
N
sa
=
21.45 kips / bolt
N
u,max
=
5.15
kips =>
OK
(continued)
Dimension (mm)
Material strength
Anchor Bolt
All calculation units are in Kip, in..
Back Plate Analysis 2 of5
EMBEDMENT PLATE CALCULATION (Demo Version)
Per Building Code Requirements for Structural Concrete ( ACI 318-08)
Design of (4) Stud Embed Plate Anchorage per Appendix D
Job Name: RTT-Strut Subject: Back Plate Date: 21/07/2014 2:14
Job Number: YAW Originator: ND Checker: MTE
2. Concrete Breakout strength of anchor in tension: (Section D.5.2)
N
cbg
= A
nc
Y
ec,N
Y
ed,N
Y
c,N
Y
cp,N
N
b
(Equation D-5)
A
nco
A
nc
= 388.66
in
2
A
nco
= 219.02
in
2
A
nco
= 9h
ef
2
Y
ec,N(x-dir)
=
0.89
Y
ec,N
=
1
< 1
Y
ec,N(y-dir)
= 0.92 (1 + 2e'
N
)
Y
ec,N(comb.)
= 0.82 3h
ef
Y
ed,N
= 0.98 Y
ed,N
= 1 (if C
min
> 1.5h
ef
) -OR- 0.7 + 0.3c
min
/ (1.5 h
ef
) (if C
min
< 1.5h
ef
)
e'
Nx
= 1.44 in Eccentricity of all tension forces on a group of anchors in the x dir.
e'
Ny
= 1.03 in Eccentricity of all tension forces on a group of anchors in the y dir.
Y
c,N
= 1.25 Y
c,N
= 1.25 for Cast-in-place anchors
Y
cp,N
= 1 Y
cp,N
= 1.0 for Cast-in-place anchors
l = 1
k
c
=
24
k
c
= 24 for Cast-in-place anchors
N
b
= 17.34 kips N
b
=
klf'
c
1/2
h
ef
3/2
N
b,max
=
16lf'
c
1/2
h
ef
5/3
if 11in. < h
ef
< 25in.
= 0.75
N
cbg
= 23.21 kips N
ua
= 7.28
kips =>
OK
3. Pullout strength of anchor in tension: (Section D.5.3)
N
pn
=Y
c,P
N
p
(Equation D-14)
A
brg
= 0.79
in
2
N
p
= 27.49 N
p
=A
brg
8f'
c
(Equation D-15)
Y
c,P
= 1.40 = 0.75
N
pn
= 28.87 kips / bolt N
u,max
= 5.15
kips =>
OK
4. Concrete Side-Face Blowout strength of Headed anchor in tension: (Section D.5.4)
N
sb
= 160c
a1
A
brg
1/2
lf'
c
1/2
(Equation D-17)
N
sbg
= (1 + s/6c
a1
)N
sb
(Equation D-18)
C
a1
= 6.85
C
a2
= 9.25
C
a2
/ C
a1
= 1.35
1.0 < C
a2
/ C
a1
< 3.0
Factor = 0.59
N
sb
= N/A kips Ca1 > 0.4 hef => Not Applicable (Section D.5.4.1) = 0.75
N
sbg
= N/A kips Ca1 > 0.4 hef and/or s > 6ca1=> Not Applicable (Section D.5.4.2)
N =
N/A kips N
u,max
= 3.26
kips =>
N/A
5. Steel strength of anchor in shear: (Section D.6.1)
V
sa
=A
se,V
f
uta
(Equation D-19)
A
se,V
= 0.44
in
2
Effective Cross Sectional Area of Anchor
f
uta
= 65.00 ksi
V
sa
= 28.60 kips/bolt = 0.65
V
sa
= 18.59 kips/bolt V
u,max
= 1.52
kips =>
OK
(continued)
Back Plate Analysis 3 of5
EMBEDMENT PLATE CALCULATION (Demo Version)
Per Building Code Requirements for Structural Concrete ( ACI 318-08)
Design of (4) Stud Embed Plate Anchorage per Appendix D
Job Name: RTT-Strut Subject: Back Plate Date: 21/07/2014 2:14
Job Number: YAW Originator: ND Checker: MTE
6. Concrete Breakout strength of anchor in shear: (Section D.6.2)*
Vb = 8
(l
e
/d
a
)
0.2
d
a
1/2
lf'
c
1/2
C
a1
1.5
(Equation D-25)
V
cbg
= A
vc
Y
ec,V
Y
ed,V
Y
c,V
Y
h,V
V
b
(Equation D-22)
A
vco
h
a
= 8.00 in Thickness of member in which an anchor is located
l
e
= 4.93 in Load bearing length (le = minimum of hef or 8 d
a
))
d
a
= 0.75 in d
a
= d
b
(Outside diameter of shaft of headed stud)
e'
vx
= 2.06 in Eccentricity of shear force on a group of anchors in the x dir.
e'
vy
= 2.06 in Eccentricity of shear force on a group of anchors in the y dir.
l =
1 Concrete Type Modification Factor
Y
c,V
= 1.40 Cracking Modification Factor (per Section D.6.2.7)
X - Direction (perpendicular to edge):
ca1 = 14.12 in ca1 = (cx1 or cx2) + sx1 or minimum required per Section D.6.2.4
Y
ec,V
= 0.91 Y
ec,V
= 1 / (1+2e'v,y/(3ca1))
Y
ed,V
= 0.83 Y
ed,V
= 1 (if ca2 > 1.5ca1) or 0.7 + 0.3ca2/(1.5ca1)
Y
h,V
= 1.00 Y
h,V
= (1.5ca1/ha)^0.5 < 1.0
A
VC
= 173.23
in
2
A
VC
= (MIN(1.5ca1,ca2(a))+MIN(3ca1,sy1)+MIN(1.5ca1,ca2(b))) x MIN(1.5*ca1,ha)
A
VCO
= 897.28
in
2
A
VCO
= 4.5(ca1)^2
V
b
= 35.34 kips
V
cbg,x
= 7.23 kips = 0.75
V
cbg,x
= 5.43 kips V
u,max
= 4.29
kips =>
OK
Y - Direction (perpendicular to edge):
ca1 = 5.33 in ca1 = (cy1 or cy2) + sy1 or minimum required per Section D.6.2.4
Y
ec,V
= 0.80 Y
ec,V
= 1 / (1+2e'v,y/(3ca1))
Y
ed,V
= 0.96 Y
ed,V
= 1 (if ca2 > 1.5ca1) or 0.7 + 0.3ca2/(1.5ca1)
Y
h,V
= 1.00 Y
h,V
= (1.5ca1/ha)^0.5 < 1.0
A
VC
= 173.23
in
2
A
VC
= (MIN(1.5ca1,ca2(a))+MIN(3ca1,sy1)+MIN(1.5ca1,ca2(b))) x MIN(1.5*ca1,ha)
A
VCO
= 128.00
in
2
A
VCO
= 4.5(ca1)^2
V
b
= 8.20 kips Vb = 8
(l
e
/d
a
)
0.2
d
a
1/2
lf'
c
1/2
C
a1
1.5
V
cbg,y
= 11.82 kips = 0.75
V
cbg,y
= 8.87 kips V
u,max
= 4.29
kips =>
OK
X - Direction (parallel to edge):
V
cbg,x
= 23.65 kips Per Section D.6.2.1.(c) = 0.75
V
cbg,x
= 17.74 kips V
u,max
= 4.29
kips =>
OK
Y - Direction (parallel to edge):
V
cbg,y
= 23.64 kips Per Section D.6.2.1.(c) = 0.75
V
cbg,y
= 17.73 kips V
u,max
= 4.29
kips =>
OK
*NOTE: Case 1 calculation (evaluation of bolt to closest edge) not req'd. (See Section RD6.2.1, 3rd paragraph)
7. Concrete Pryout strength of anchor in shear: (Section D.6.3)
V
cpg
=k
cp
N
cbg
(Equation D-31)
k
cp
= 2.00
kcp = 1.0 (for hef < 2.5in.); kcp = 2.0 (for hef > 2.5in.)
N
cbg
= 30.94 kips from Equation D-5 (See previous Section D.5.2 calcs)
V
cpg
= 61.88 kips = 0.75
V
cpg
= 46.41 kips V
u,max
= 6.07
kips =>
OK
V
u,max
= sum of each bolt shear
(continued)
Back Plate Analysis 4 of5
EMBEDMENT PLATE CALCULATION (Demo Version)
Per Building Code Requirements for Structural Concrete ( ACI 318-08)
Design of (4) Stud Embed Plate Anchorage per Appendix D
Job Name: RTT-Strut Subject: Back Plate Date: 21/07/2014 2:14
Job Number: YAW Originator: ND Checker: MTE
8. Interaction of tensile and shear forces: (Section D.7)
Tension Ratio = N
UA
N
n
Steel: 0.240 Steel strength of anchor in tension
Breakout: 0.314 Concrete Breakout strength of anchor in tension
Pullout: 0.178 Pullout strength of anchor in tension
Sideface Blowout: N/A Concrete Side-Face Blowout strength of Headed anchor
in tension
Shear Ratio = V
UA
V
n
Steel: 0.082 Steel strength of anchor in shear
Breakout (Case2): 0.791 Concrete Breakout strength of anchor in shear - perp.
Breakout (Case3): 0.242 Concrete Breakout strength of anchor in shear - parallel
Pryout: 0.131 Concrete Pryout strength of anchor in shear
Combined Stress Ratio (CSR) = N
UA
V
UA
N
n
V
n
CSR: 1.10
EMBEDMENT STRENGTH (Per ACI 318-08 - Appendix D) OK
9. Required edge distances & spacings: (ACI 318-08Section D.7&ASIC Table J 3.4)
s
min
= 3.00 in Minimum spacing = s
min
= 4 x da (for untorqued cast-in-place anchors)
s
act
= 3.15 in Actual lesser of two spacings, sy1 &sx1 OK
Conc. Edge dist, min = 4.50 in Assume torqued cast-in headed anchors (conservative). See Section 7.7 else.
Conc. Edge dist, act = 6.85 in Actual lesser of four edge distances, cy1/2 &cx1/2 OK
Edge dist, min = 1.25 in Minimum steel edge distance per Table J3.4
Edge dist, act = 2.95 in Actual lesser of four edge distances, cy1/2 &cx1/2 OK
Req'd thick., ha,
min
= 5.68 in. ha,min = hef + 0.75"
Actual thickness, ha = 8.00 in. OK
10. Plate Bearing: (ACI 318-08Section 10.14)
Plate Area, A1 = 125.49 in
2
A1 = (bx1 + sx1 + bx2)(by1 + sy1 + by2)
Concrete Area, A2 = 468.88 in
2
A2 = (cx1 + sx1 + cx2)(cy1 + sy1 +cy2)
Multiplication Factor = 1.93 Multiplication Factor = (A2/A1)^0.5 < 2.0
Pn = 896.89 kips Pn = 0.85fc'A1 x (Multiplication Factor)
Pn = 582.98 kips N
ua
= N/A
kips =>
N/A
11. Plate Punching Shear: (ACI 318-08Section 11.12.2.1)
Perimeter, bo = 22.91 in bo = (bx1 + sx1 + bx2) + (by1 + sy1 + by2)
Concrete depth, d = 6.00 in d = ha - 2in. (Assume 2"clear cover)
b = 1.53 b = Length of: Long side of plate / Short side of plate
Factor = 4.00 Factor = Minimum of (2 + 4/b) or 4
Vc = 36.27 kips Vc = Factor x (fc')^0.5 x bo x d
Vc = 23.58 kips N
ua
= N/A
kips =>
N/A
+ < 1.2
Back Plate Analysis 5 of5