Technical Forum
Decentral Peripherie
how to configure s7-300 and s7.1200 communication through Profibus if I have
CM1242-5 module?
Thread Starter: kolma46 Started: 3/9/2012 12:10 PM Replies: 2
Previous thread Next thread Enable Notification
3/9/2012, 12:10 PM
kolma46
Joined 12/16/2010
Last visit: 11/16/2012
Posts: 1
Rating:
(0)
(0) Rate Thank
Hello!
how to configure s7-300 and s7.1200 communication through Profibus if I
have CM1242-5 module?
So in my case 313C-2DP will be master and CP1242-5 slave.
IS there any example for 300<-->1200 communication?

Thanks,
Andrej
=== Edited by O_Moderator @ 3/12/2012 10:42 AM [GMT ] ===
new subject after splitting from Config and Programming S7 - 1200
communicate with S7-300 by Profibus Network
=== Edited by kolma46 @ 3/9/2012 12:12 PM [GMT ] ===
Private message
3/9/2012, 2:29 PM
UMENCHO
Joined 3/21/2006
Last visit: 1/13/2014
Posts: 9561
Rating:
(1011)
(0) Rate Thank
Hello,
I think fo rthe moment that kind of sample project doen't exist here. Basically
you need a GSD file for CM1242-5Download GSD File CM 1242-5 .There you
can find an info S7-1200 Profibus communicaion
Best regards,
Hristo Mihalev
Private message
1/14/14 how to configure s7-300 and s7.1200 communication through Profibus if I have CM1242-5 module? - Siemens Industry Online Support - Technical Forum (m
https://www.automation.siemens.com/WW/forum/guests/PostShow.aspx?HTTPS=REDIR&PostID=348410&language=en 2/2
Inf orm Moderators Reply Quote Top
Page 1 of 1 (3 items)
12/15/2012, 2:43 PM
Milosh
Joined 8/16/2010
Last visit: 1/13/2014
Posts: 297
Rating:
(0)
(0) Rate Thank
I have similar problem. And I found the solution.
In hw config of s7-300,:
1: added gsd for CM-1242 address 3
then added 16 byte input and 16 byte output
2. DP address 2
in hw confihg of CM in tia:
1. added subnet profibus_1
2. address of cm-1242 is 3
3. then added transfer area 1 16 byte output and transfer area 2 16 byte
input
Look at the order of byte in hw config. You need to provide reverse order of
data to work properly.
Best regarda,
Milo
Private message
Thank you f or this post f rom:
alex_zanella, dchartier
Actions
Copy Link
To conference
New post