POWER SUPPLY SYSTEMS

LIGHTNING CURRENT ARRESTERS TYPE 1


39 www.dehn.de
For protection of low voltage consumers installations against surges
even at direct lightning strikes. For use in the lightning protection zones
concept at boundaries 0
A
1.
Encapsulated RADAX Flow spark gap
with high follow current limitation
No tripping of 32/35 A gL/gG fuses
Coordinated directly with DEHNguard
surge protective device without addi-
tional cable length or decoupling coil
Low protection level
Allows installation upstream of supply
meters thanks to its high insulation
resistance
Double terminals for serial connection
Multifunctional connection for
conductors and busbars
Available with operating voltage
indication
DBM 1 255: Coordinated, single-pole lightning current
arrester with high follow current limitation
DBM 1 255 L:Coordinated, single-pole lightning current
arrester with high follow current limitation
and operating voltage indication
DEHNbloc

Maxi
Coordinated Lightning Current Arrester
The coordinated lightning current arresters of the DEHNbloc Maxi family
adjust themselves to every kind of application. Whether being used in an
exposed position or in rough industrial applications: DEHNbloc Maxi
always offers the right solution. The single-pole devices are originally
coordinated with the approved DEHNguard surge arresters of the
Red/Line family. Independent from cable lengths and without requiring
additional decoupling coils, the surge protection concept can be adapted
individually to all conditions at the installation.
DEHNbloc Maxi devices provide the patented technologies of an encap-
sulated creepage discharge spark gap and RADAX-Flow follow current
limitation. Special safety distances from busbars or equipment belong to
the past as well as tripped backup fuses due to lacking selectivity bet-
ween the protective device and overcurrent protection. This ensures the
highest possible system availability.
For indicating the presence of phase voltages and readiness for operation
on site, DEHNbloc Maxi Type DBM 1 255 L provides an integrated opera-
ting voltage indication. Optionally, DEHNbloc Maxi devices can also be
used for signalling the readiness for opera-
tion of the equipment as well as the pre-
sence of operating voltage to a superior
control system via remote signalling con-
tact.
Using the double terminals
of DEHNbloc Maxi devices,
which are suitable for all
types of conductors, allows
to realise a serial connecti-
on up to nominal currents
of 125 A in a space- and
cost-saving way, as prefer-
red by standard IEC 60364-
5-53. The multifunctional
terminal is suitable for
simultaneous connection of
conductors and a busbars.
This allows an easy wiring
to other DIN rail mounted
devices.
SPD Type 1 according to EN 61643-11;
Classification B according to E DIN VDE 0675-6;
SPD Class I according to IEC 61643-1;
POWER SUPPLY SYSTEMS
LIGHTNING CURRENT ARRESTERS TYPE 1
40 www.dehn.de
DEHNbloc

Maxi
DBM 1 255 (L)
900 025 DBM 1
255
900 026 DBM 1
255 L
DBM 1 255 DEHNbloc
Maxi 1, 25 kA 900 025
DBM 1 255 L DEHNbloc
Maxi 1 with operation indicator, 25 kA 900 026
L L'
N/PEN N/PEN
H
Basic circuit diagram DBM 1 255 L Dimension drawing DBM 1 255 (L)
DBM 1 255: Coordinated lightning current arrester with high follow current limitation.
DBM 1 255 L: Coordinated lightning current arrester with high follow current limitation and
operating voltage indication.
DBM 1 255 DBM 1 255 L
SPD according to EN 61643-11 Type 1 Type 1
SPD according to IEC 61643-1 Class I Class I
Classification according to E DIN VDE 0675-6 B B
Max. continuous ac voltage U
C
255 V 255 V
Lightning impulse current (10/350) I
imp
25 kA 25 kA
Nominal discharge current (8/20) I
n
25 kA 25 kA
Voltage protection level U
P
! 2.5 kV ! 2.5 kV
Follow current extinguishing capability I
fi
25 kA
rms
25 kA
rms
Follow current limitation / Selectivity no tripping of a 35 A gL/gG fuse up to 25 kA
rms
(prosp.) no tripping of a 35 A gL/gG fuse up to 25 kA
rms
(prosp.)
Response time t
A
! 100 ns ! 100 ns
Max. backup fuse (L) up to I
K
= 25 kA
rms
315 A gL/gG 315 A gL/gG
Max. backup fuse (L) at I
K
> 25 kA
rms
200 A gL/gG 200 A gL/gG
Max. backup fuse (L-L) 125 A gL/gG 125 A gL/gG
TOV voltage U
T
335 V / 5 sec. 335 V / 5 sec.
Operating temperature range (parallel wiring) T
UP
-40C...+80C -40C...+80C
Operating temperature range (through-wiring) T
US
-40C...+60C -40C...+60C
Cross-sectional area (L, L, N/PEN) min. 10 mm
2
solid / flexible 10 mm
2
solid / flexible
Cross-sectional area (L, N/PEN) max. 50 mm
2
stranded / 35 mm
2
flexible 50 mm
2
stranded / 35 mm
2
flexible
Cross-sectional area (L, N/PEN) max. 35 mm
2
stranded / 25 mm
2
flexible 35 mm
2
stranded / 25 mm
2
flexible
Mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material red thermoplastic, UL 94 V-0 red thermoplastic, UL 94 V-0
Degree of protection IP 20 IP 20
Dimension 2 mods., DIN 43880 2 mods., DIN 43880
Operation indicator green light
Ordering information
Type DBM 1 255 DBM 1 255 L
Part No. 900 025 900 026
Packing unit 1 pc(s) 1 pc(s)
Accessory Part for DEHNbloc

Maxi
DEHNsignal DV
DSI DV: Remote signalling module for
multipole SPDs with 4-wire interface DSI DV
(e.g. DEHNventil TNC / ... TNS / ... TT)
single-pole SPDs with single-wire interface DSI DV in TN-S and
TT systems (e.g. DEHNbloc Maxi)
PU Part
Type pc(s) No.
DSI DV 1 910 620
910 620 DSI DV
DSI DV
DEHNsignal 910 620
Accessory Part for DEHNbloc

Maxi
DEHNsignal DBM
DSI DBM: Remote signalling module for single-pole SPDs with single-
wire interface DSI DV in TN-C systems (e.g. DEHNbloc Maxi)
PU Part
Type pc(s) No.
DSI DBM 1 910 623
910 623 DSI DBM
DSI DBM
DEHNsignal DB M Remote Signalling Module 910 623
DEHN + SHNE GmbH + Co. KG Hans-Dehn-Str. 1 Postfach 1640 D-92306 Neumarkt Tel. +499181 906-0 www.dehn.de
3,
tested
: Tested +: New (: Discontinued Model
Product Data Sheet: DEHNbloc M
DB M 1 255 (961 120)
Coordinated spark-gap-based lightning current arrester consisting of a base part and plug-in protection module
Maximum system availability due to RADAX Flow follow current limitation
Directly coordinated with DEHNguard surge protective devices without additional cable length
Figure without obligation
Basic circuit diagram DB M 1 255 Dimension drawing DB M 1 255
Coordinated modular single-pole ightning current arrester with high follow current limitation
Type DB M 1 255
Part No. 961 120
SPD according to EN 61643-11 Type 1
SPD according to IEC 61643-1/-11 Class I
Max. continuous operating a.c. voltage (U
C
) 255 V
Lightning impulse current (10/350 s) (I
imp
) 50 kA
Specific energy (W/R) 625.00 kJ/ohms
Nominal discharge current (8/20 s) (I
n
) 50 kA
Voltage protection level (U
P
) 2.5 kV
Follow current extinguishing capability a.c. (I
fi
) 50 kA
rms
Follow current limitation/Selectivity no tripping of a 32 A gL/gG fuse up to 50 kA
rms
(prosp.)

Response time (t
A
) 100 ns
Max. backup fuse (L) up to I
K
= 50 kA
rms
(t
a
0.2 s) 500 A gL/gG
Max. backup fuse (L) up to I
K
= 50 kA
rms
(t
a
5 s) 315 A gL/gG
Max. backup fuse (L-L') 125 A gL/gG
Temporary overvoltage (TOV) (U
T
) 440 V / 5 sec.
TOV characteristic withstand
Operating temperature range (parallel connection) (T
UP
) -40C...+80C
Operating temperature range (series connection) (T
US
) -40C...+60C
Operating state/fault indication green / red
Number of ports 1
Cross-sectional area (L/N, L'/N', N/PE (N)) (min.) 10 mm
2
solid/flexible
Cross-sectional area (L/N, N/PE(N)) (max.) 50 mm
2
stranded/35 mm
2
flexible
Cross-sectional area (L'/N') (max.) 35 mm
2
stranded/25 mm
2
flexible
For mounting on 35 mm DIN rails acc. to EN 60715
Enclosure material thermoplastic, red, UL 94 V-0
Place of installation indoor installation
Degree of protection IP 20
Capacity 2 module(s), DIN 43880
Approvals VDE, KEMA, UL
Extended technical data:
Use in installations with prospective short-circuit
currents of more than 50 kA
rms
(tested by VDE)

Maximum prospective short-circuit current 100 kA
rms
(220 kA
peak
)

Limitation/extinction of mains follow currents up to 100 kA
rms
(220 kA
peak
)

Max. backup fuse (L) up to I
K
= 100 kA
rms
(t
a
0.2 s) 500 A gL/gG
Max. backup fuse (L) up to I
K
= 100 kA
rms
(t
a
5 s) 315 A gL/gG
Weight 340 g
Customs tariff number 85363030
GTIN 4013364118614
PU 1 pc(s)
We reserve the right to introduce changes in performance, configuration and technology, dimensions, weights and materials in the course of technical progress. The figures are shown without obligation.