Escolar Documentos
Profissional Documentos
Cultura Documentos
2
Ventialtion Solutions
Want More on the
ASHRAE 62.2
Standard?
Visit ASHRAE's web site to
view or buy the ASHRAE 62.2
Standard at www.ashrae.org
ASHRAE 62.2 is a minimum national standard that provides
methods for achieving acceptable indoor air quality in typical
residences. The standard has three main components: Whole
House Ventilation, Local Exhaust, and Source Control. The
recommendations that follow are for most common conditions,
extreme conditions require additional consideration.
The exhaust fan dilutes the air in the main living spaces with outside
air to remove unavoidable contaminants from people, pets,
cleaning, offgassing, etc. The whole house fan flow rate is
determined based on the floor space and the number of bedrooms.
The whole house fan provides multiple air exchanges within the
home each day. The operation can be continuous or intermittent
(much higher airflow cycled by a timer) if less than 1 sone. The
chart below outlines the minimum ventilation requirements for
continuous operation.
Continuous Ventilation
Ventilation Air Requirements, CFM
Floor Area Bedrooms
(ft2) 0-1 2-3 4-5 6-7 >7
<1500 30 45 60 75 90
1501-3000 45 60 75 90 105
3001-4500 60 75 90 105 120
4501-6000 75 90 105 120 135
6001-7500 90 105 120 135 150
>7500 105 120 135 150 165
The key with a Whole House Exhaust Fan is quiet. In most cases
Products Resources Learning Center About Us
Air King Ventilation Ashrae 62.2 Standard Information http://www.airkinglimited.com/page/ashrae622.html
1 of 5 8/29/2014 8:16 PM
the exhaust fan will be located in a central location of the home and
will run continuously, so you want it to be quiet. ASHRAE 62.2 calls
for continuously running exhaust fan to have a sound rating of less
than 1.0 sones. Air King has engineered multiple products to meet
and exceed the ASHRAE 62.2 standard, giving you a choice that
fits your ventilation need and your budget.
Whole House Continuous Ventilation Exhaust
Fan Options
ESB Series ESBH Series ESBG Series AKLS6 Series
AK150LS AKF Series AK Series BFQ50
BFQF50 FRAK Series
Local Exhaust removes high concentrations of contaminants in the
rooms where they occur (kitchens and bathrooms). The local
exhaust fans can operate continuously at a lower flow rate (CFM),
or intermittently (cycled by a switch or timer) at a higher flow rate if
less than 1 sone. If operated continuously or on a timer the local
exhaust fan flow reduces the whole house exhaust fan flow
requirement. ASHRAE 62.2 Local Exhaust can be solved in three
ways On Demand Local Exhaust, Continuous Local Exhaust, or
Intermittent Local Exhaust.
ASHRAE 62.2 requires each room that creates contaminants
(bathrooms, kitchens, art studios, etc.) must have some type of
exhaust that clears the air to the outside of the home. For this
scenario a whole house continuous exhaust fan would be located in
a central area of the home to meet the requirements for whole
house ventilation. In each of the rooms that create contaminants an
exhaust fan (or range hood for the kitchen) would be utilized.
Air King Ventilation Ashrae 62.2 Standard Information http://www.airkinglimited.com/page/ashrae622.html
2 of 5 8/29/2014 8:16 PM
Exhaust fans need to operate at less than 3.0 sones and typically
utilize at least a 4" duct. Air King recommends this scenario
because by locating the continuous exhaust in a central location of
the home, it maximizes the effectiveness. By using separate local
exhaust, it allows the room to be properly ventilated for size and
need (a bathroom with a steam shower is going to need more than
a powder room). This arrangement is already understood by home
owners and installers and requires no new technology or training.
Air King has a multitude of fan solutions for local exhaust including
fan/light combination units, fire rated units and more. All Air King
ENERGY STAR