Summary For Addressible System & Voice Evacuation System
Sl.
No
Description Unit Qty Rate Amount
A FIRE PANELS & SOFTWARE
1
Microprocessor based 10 loop , Networkable Analogue
addressable type fire alarm control panel with 640
character LCD display, The panel should be equipped
with sufficient numbers of loop with each loop having a
capacity of 300 analog addressables in one loop, QWERTY
style alphanumeric keypad for the field programming and
control of the fire alarm system, panel shall maintain a
history file of the last 2000 events, 240 volts AC power
supply, automatic battery charger, 24 volts sealed lead
acid batteries sufficient for 24 hours normal working and
then be capable of operating the system for 2 hours
during an emergency conditions as required. The
Network speed of the panel shall be atleat 12 MBPS on
copper. (UL 9th Edition Approved)
Nos. 1 535,000.00 535,000.00
B
1
Integrated 8 channel Digital Voice Evacuation and 2
way Communication Fire Fighters System capable to
supervision of all the speaker circuits, with one number
of digital amplifiers to run upto 200 speakersand
acessories required to compelete the system. The
equipment shall be of same make as panel.
Nos. 1 175,000.00 175,000.00
2
Fire panel supervised 2W, 70db-84db Ceiling Mounted
Hooter Cum Speakers for lobbies
Nos. 113 1,025.00 115,825.00
4 2 way communication Fire Fighter's Telephone Jack Nos. 32 2,500.00 80,000.00
5 2 way communication Fire Fighter's Handset Nos. 5 3,200.00 16,000.00
C DETECTORS & INITIATIING DEVICES
1
Automatic Floating Sensitivity type Analog addressable
Photo thermal detector (with dual thermal element
and a photo element) with mounting based LED, Address
Switch to programme the detectors, complete as
required. For lobbies and utility area
Nos. 1216 3,200.00 3,891,200.00
2
Addressable Beam detector with 4 manual & 2
acclimate senstivity settings, Transmitter/receiver built
into same unit, Six user-selectable sensitivity levels, 16'
to 328' protection range, Digital display, Built-in
automatic gain control compensates for signal
deterioration from dust buildup, Address Switch to
programme the detectors, complete as required
Nos. 2 42,000.00 84,000.00
3
Addressable Dual action Manual Call Station for
initiation of fire alarm
Nos. 62 3,150.00 195,300.00
ADDRESSABLE FIRE DETECTION & DIGITAL VOICE EVACUATION SYSTEM WITH FIRE FIGHTERS TWO
WAY COMMUNICATION FOR
TOWER 1
DIGITAL VOICE EVACUATION SYSTEM WITH FIRE FIGHTER COMMUNICATION SYSTEM
Sl.
No
Description Unit Qty Rate Amount
D MODULES & NOTIFICATION DEVICES
1
Fault isolator module for isolating shorted, dewired and
loose circuits between two successive fault isolators with
automatic resetting arrangement
Nos. 76 2,800.00 212,800.00
2
Addressable relay modules for driving outputs like
AHU, dampers, pressurisation fans, lifts etc.
Nos. 5 2,500.00 12,500.00
3
Addressable monitor modules to give input to FAS like
Sprinkler Flow Switch & WLD Monitoring
Nos. 26 2,700.00 70,200.00
4
Addressable control modules for hooters, strobes and
fire fighter telephone jacks
Nos. 75 3,100.00 232,500.00
6
Hooter cum Strobe withmin 75DB output and 110 cd.
The strobes shall be synchronized for better evacuation. Nos. 62 3,150.00 195,300.00
E CABLES AND CONDUITS
1
Supply and drawing of 2 C X 1.5 Sq mm Twisted FRLS
copper multistranded wire Complete with terrmination
and testing as per requirement. In existing conduits
Rmt. 10500 45.00 472,500.00
2
20mm dia PVC Conduit
Rmt. 10000 20.00 200,000.00
TOTAL 6,488,125.00
Sl.
No
Description Unit Qty Rate Amount
A FIRE PANELS & SOFTWARE
1
Microprocessor based 6 loop expandable to 10 loop ,
Networkable Analogue addressable type fire alarm control
panel with 640 character LCD display, The panel should be
equipped with sufficient numbers of loop with each loop
having a capacity of 300 analog addressables in one loop,
QWERTY style alphanumeric keypad for the field
programming and control of the fire alarm system, panel
shall maintain a history file of the last 2000 events, 240 volts
AC power supply, automatic battery charger, 24 volts sealed
lead acid batteries sufficient for 24 hours normal working
and then be capable of operating the system for 2 hours
during an emergency conditions as required. The Network
speed of the panel shall be atleat 12 MBPS on copper. (UL
9th Edition Approved)
Nos. 1 425,000.00 425,000.00
B
1
Integrated 8 channel Digital Voice Evacuation and 2 way
Communication Fire Fighters System capable to
supervision of all the speaker circuits, with one number of
digital amplifiers and acessories required to compelete the
system. The equipment shall be of same make as panel.
Nos. 1 175,000.00 175,000.00
2
Fire panel supervised 2W, 70db-84db Ceiling Mounted Hooter
Cum Speakers for lobbies
Nos. 58 1,025.00 59,450.00
4 2 way communication Fire Fighter's Telephone Jack Nos. 18 2,500.00 45,000.00
5 2 way communication Fire Fighter's Handset Nos. 5 3,200.00 16,000.00
ADDRESSABLE FIRE DETECTION & DIGITAL VOICE EVACUATION SYSTEM WITH FIRE FIGHTERS TWO WAY
COMMUNICATION FOR
TOWER 2
DIGITAL VOICE EVACUATION SYSTEM WITH FIRE FIGHTER COMMUNICATION SYSTEM
Sl.
No
Description Unit Qty Rate Amount
C DETECTORS & INITIATIING DEVICES
1
Automatic Floating Sensitivity type Analog addressable
Photo thermal detector (with dual thermal element and a
photo element) with mounting based LED, Address Switch to
programme the detectors, complete as required. For
lobbies and utility area
Nos. 784 3,200.00 2,508,800.00
2
Addressable Beam detector with 4 manual & 2 acclimate
senstivity settings, Transmitter/receiver built into same
unit, Six user-selectable sensitivity levels, 16' to 328'
protection range, Digital display, Built-in automatic gain
control compensates for signal deterioration from dust
buildup, Address Switch to programme the detectors,
complete as required
Nos. 2 42,000.00 84,000.00
3
Addressable Dual action Manual Call Station for initiation of
fire alarm
Nos. 48 3,150.00 151,200.00
D MODULES & NOTIFICATION DEVICES
1
Fault isolator module for isolating shorted, dewired and
loose circuits between two successive fault isolators with
automatic resetting arrangement
Nos. 50 2,800.00 140,000.00
2
Addressable relay modules for driving outputs like AHU,
dampers, pressurisation fans, lifts etc.
Nos. 5 2,500.00 12,500.00
3
Addressable monitor modules to give input to FAS like
Sprinkler Flow Switch & WLD Monitoring
Nos. 17 2,700.00 45,900.00
4
Addressable control modules for hooters, strobes and fire
fighter telephone jacks
Nos. 60 3,100.00 186,000.00
6
Hooter cum Strobe withmin 75DB output and 110 cd. The
strobes shall be synchronized for better evacuation.
Nos. 48 3,150.00 151,200.00
E CABLES AND CONDUITS
1
Supply and drawing of 2 C X 1.5 Sq mm Twisted FRLS copper
multistranded wire Complete with terrmination and testing
as per requirement. In existing conduits
Rmt. 7000 45.00 315,000.00
2
20mm dia PVC Conduit
Rmt. 6500 20.00 130,000.00
TOTAL 4,445,050.00
Sl.
No
Description Unit Qty Rate Amount
A FIRE PANELS & SOFTWARE
1
Microprocessor based 6 loop expandable to 10 loop ,
Networkable Analogue addressable type fire alarm control
panel with 640 character LCD display, The panel should be
equipped with sufficient numbers of loop with each loop
having a capacity of 300 analog addressables in one loop,
QWERTY style alphanumeric keypad for the field
programming and control of the fire alarm system, panel
shall maintain a history file of the last 2000 events, 240 volts
AC power supply, automatic battery charger, 24 volts sealed
lead acid batteries sufficient for 24 hours normal working and
then be capable of operating the system for 2 hours during
an emergency conditions as required. The Network speed of
the panel shall be atleat 12 MBPS on copper. (UL 9th Edition
Approved)
Nos. 1 425,000.00 425,000.00
B
1
Integrated 8 channel Digital Voice Evacuation and 2 way
Communication Fire Fighters System capable to supervision
of all the speaker circuits, with one number of digital
amplifiers and acessories required to compelete the system.
The equipment shall be of same make as panel.
Nos. 1 175,000.00 175,000.00
2
Fire panel supervised 2W, 70db-84db Ceiling Mounted Hooter
Cum Speakers for lobbies
Nos. 58 1,025.00 59,450.00
4 2 way communication Fire Fighter's Telephone Jack Nos. 18 2,500.00 45,000.00
5 2 way communication Fire Fighter's Handset Nos. 5 3,200.00 16,000.00
ADDRESSABLE FIRE DETECTION & DIGITAL VOICE EVACUATION SYSTEM WITH FIRE FIGHTERS TWO WAY
COMMUNICATION FOR
TOWER 3
DIGITAL VOICE EVACUATION SYSTEM WITH FIRE FIGHTER COMMUNICATION SYSTEM
Sl.
No
Description Unit Qty Rate Amount
C DETECTORS & INITIATIING DEVICES
1
Automatic Floating Sensitivity type Analog addressable
Photo thermal detector (with dual thermal element and a
photo element) with mounting based LED, Address Switch to
programme the detectors, complete as required. For lobbies
and utility area
Nos. 757 3,200.00 2,422,400.00
2
Addressable Beam detector with 4 manual & 2 acclimate
senstivity settings, Transmitter/receiver built into same unit,
Six user-selectable sensitivity levels, 16' to 328' protection
range, Digital display, Built-in automatic gain control
compensates for signal deterioration from dust buildup,
Address Switch to programme the detectors, complete as
required
Nos. 2 42,000.00 84,000.00
3
Addressable Dual action Manual Call Station for initiation of
fire alarm
Nos. 42 3,150.00 132,300.00
D MODULES & NOTIFICATION DEVICES
1
Fault isolator module for isolating shorted, dewired and
loose circuits between two successive fault isolators with
automatic resetting arrangement
Nos. 48 2,800.00 134,400.00
2
Addressable relay modules for driving outputs like AHU,
dampers, pressurisation fans, lifts etc.
Nos. 2 2,500.00 5,000.00
3
Addressable monitor modules to give input to FAS like
Sprinkler Flow Switch & WLD Monitoring
Nos. 17 2,700.00 45,900.00
4
Addressable control modules for hooters, strobes and fire
fighter telephone jacks
Nos. 52 3,100.00 161,200.00
6
Hooter cum Strobe withmin 75DB output and 110 cd. The
strobes shall be synchronized for better evacuation.
Nos. 42 3,150.00 132,300.00
E CABLES AND CONDUITS
1
Supply and drawing of 2 C X 1.5 Sq mm Twisted FRLS copper
multistranded wire Complete with terrmination and testing
as per requirement. In existing conduits
Rmt. 7000 45.00 315,000.00
2
20mm dia PVC Conduit
Rmt. 6500 20.00 130,000.00
TOTAL 4,282,950.00
Sl.
No
Description Unit Qty Rate Amount
A FIRE PANELS & SOFTWARE
1
Microprocessor based 10 loop , Networkable Analogue
addressable type fire alarm control panel with 640
character LCD display, The panel should be equipped
with sufficient numbers of loop with each loop having a
capacity of 300 analog addressables in one loop, QWERTY
style alphanumeric keypad for the field programming and
control of the fire alarm system, panel shall maintain a
history file of the last 2000 events, 240 volts AC power
supply, automatic battery charger, 24 volts sealed lead
acid batteries sufficient for 24 hours normal working and
then be capable of operating the system for 2 hours
during an emergency conditions as required. The
Network speed of the panel shall be atleat 12 MBPS on
copper. (UL 9th Edition Approved)
Nos. 1 535,000.00 535,000.00
B
1
Integrated 8 channel Digital Voice Evacuation and 2
way Communication Fire Fighters System capable to
supervision of all the speaker circuits, with one number
of digital amplifiers to run upto 200 speakersand
acessories required to compelete the system. The
equipment shall be of same make as panel.
Nos. 1 175,000.00 175,000.00
2
Fire panel supervised 2W, 70db-84db Ceiling Mounted
Hooter Cum Speakers for lobbies
Nos. 122 1,025.00 125,050.00
4 2 way communication Fire Fighter's Telephone Jack Nos. 32 2,500.00 80,000.00
5 2 way communication Fire Fighter's Handset Nos. 5 3,200.00 16,000.00
C DETECTORS & INITIATIING DEVICES
1
Automatic Floating Sensitivity type Analog addressable
Photo thermal detector (with dual thermal element
and a photo element) with mounting based LED, Address
Switch to programme the detectors, complete as
required. For lobbies and utility area
Nos. 1233 3,200.00 3,945,600.00
2
Addressable Beam detector with 4 manual & 2
acclimate senstivity settings, Transmitter/receiver built
into same unit, Six user-selectable sensitivity levels, 16'
to 328' protection range, Digital display, Built-in
automatic gain control compensates for signal
deterioration from dust buildup, Address Switch to
programme the detectors, complete as required
Nos. 2 42,000.00 84,000.00
3
Addressable Dual action Manual Call Station for
initiation of fire alarm
Nos. 63 3,150.00 198,450.00
ADDRESSABLE FIRE DETECTION & DIGITAL VOICE EVACUATION SYSTEM WITH FIRE FIGHTERS TWO
WAY COMMUNICATION FOR
TOWER 2
DIGITAL VOICE EVACUATION SYSTEM WITH FIRE FIGHTER COMMUNICATION SYSTEM
Sl.
No
Description Unit Qty Rate Amount
D MODULES & NOTIFICATION DEVICES
1
Fault isolator module for isolating shorted, dewired and
loose circuits between two successive fault isolators with
automatic resetting arrangement
Nos. 78 2,800.00 218,400.00
2
Addressable relay modules for driving outputs like
AHU, dampers, pressurisation fans, lifts etc.
Nos. 5 2,500.00 12,500.00
3
Addressable monitor modules to give input to FAS like
Sprinkler Flow Switch & WLD Monitoring
Nos. 26 2,700.00 70,200.00
4
Addressable control modules for hooters, strobes and
fire fighter telephone jacks
Nos. 76 3,100.00 235,600.00
6
Hooter cum Strobe withmin 75DB output and 110 cd.
The strobes shall be synchronized for better evacuation. Nos. 63 3,150.00 198,450.00
E CABLES AND CONDUITS
1
Supply and drawing of 2 C X 1.5 Sq mm Twisted FRLS
copper multistranded wire Complete with terrmination
and testing as per requirement. In existing conduits
Rmt. 10600 45.00 477,000.00
2
20mm dia PVC Conduit
Rmt. 10100 20.00 202,000.00
TOTAL 6,573,250.00
Sl.
No
Description Unit Qty Rate Amount
1
The GUI based Network Control Station with UL Listed
fire graphic software capable of graphically
representing each facility being monitored with floor
plans and icons depicting the actual locations of the
various systems; and / or sensors locations. The NCS
shall have a desktop with following specification:
Nos. 1 216,000.00 216,000.00
Intel Pentium Core II Duo (tm)-processor, operating at a
minimum of 1GB of RAM, , 80 Gbyte hard disk, mouse,
32X CD-ROM, 3PCI / 1 ISA expansion slots, sound card,
200 watt power supply, and SVGA graphics with a screen
resolution of 1024 x 768.
Nos. 1 45,000.00 45,000.00
Flat Screen 17 Inch Monitor Nos. 1 15,000.00
Laser Printer Nos. 1 15,000.00 15,000.00
2
Network Control Annunciator, 640-characters; The NCA
will be the Display for the network systems, complete
with annunciator box, blank modules, backbox etc.as
required for mounting. (Guard Room)
Nos. 2 45,000.00 90,000.00
3
Network Control Annunciator of 640-characters with
Integrated 8 channel Digital Voice Evacuation and 2
way Communication Fire Fighters System capable to
supervision of all the speaker circuits, complete with 24
Zone selector switches MIC and telephone handset,
The equipment shall be of same make as panel.
Nos. 1 275,000.00 275,000.00
1
Supply and drawing of 4 C X 2.5 Sq mm Twisted FRLS
copper multistranded cable for FIRE NETWORK with
speed of 12mbps. Complete with termination and testing
as per requirement. In existing cable tray
Rmt. 1000 55.00 55,000.00
2
20mm dia PVC Conduit
Rmt. 1000 20.00 20,000.00
TOTAL 716,000.00
ADDRESSABLE FIRE DETECTION & DIGITAL VOICE EVACUATION SYSTEM WITH FIRE FIGHTERS TWO
WAY COMMUNICATION
CONTROL ROOM