Você está na página 1de 4

TCY3-T0121R

Doc: 70-000002 V1.0, 20100420 Vector Controls GmbH, Switzerland Page 1


Subject to alteration
TCY3-T0121R Series Intelligent Compact Controller
Features
Temperature control for 2-pipe, 4-pipe HVAC
systems.
-H version: Humidity control with integrated
humidity sensor
Universal PID and binary control for any
analog input/output signal and range
4 independent PID sequences, 12
independent binary sequences
1 modulating output for DC 0...10V or 020
mA actuators with 10 bit resolution.
1 Input for DC 05V, 010V or 020 mA
sensors with 10 bit resolution
1 internal temperature sensor and 1 external
sensor input
Multiple functions on external input: auto
changeover, remote control
Monitoring of low and high limits on all inputs.
Programmable reaction in case of alarm.
Feedback function for internal sensors and
set points.
Special functions for dehumidifying, set point
shift and VAV control
Transformation of display value according to
analog sensor range
Password protected programmable user and
control parameters
Blue backlight
Deluxe Version only:
o Power Cap protected real time clock with 24h
power backup
o 16 switching times, grouped in 4 time
schedules.
o Infrared remote control
Applications
Air Only Systems: Constant or Variable Air Volume systems for single or dual duct systems with options of:
o up to two reheat stages
o supply air, extract air cascade control
o humidity control
o Control for variable speed fans

Air/Water Systems:
o Fan Coil units for 2-pipe or 4-pipe systems with options of:
Humidity control
Pressure control
o radiator control, chilled ceiling

Water Only Systems: Radiator, floor heating or chilled ceilings

Individual room control for hotel rooms, meeting rooms, etc.
General Description
The TCY3 is a stand-alone electronic universal controller with two autonomous control loops. Each control loop may use up
to 2 PID sequences and 6 binary sequences. The TCY3-T0121R features 1 NTC temperature sensor and 1 analog input, 2
binary outputs and one analog output. The outputs need to be assigned to the control sequences by parameters. A
detailed configuration is possible by following a simple setup routine. The TCY3 can be configured using the standard
operation terminal. No special tool or software is required.


TCY3-T0121R Technical Data

Doc: 70-000002 V1.0, 20100420 Vector Controls GmbH, Switzerland Page 2
Subject to alteration
Name
C Y T T 0 1 2 1 H (- ) U (- ) D (- ) - 3 R

Ordering
Model Stock code Variant Mounting size Type Key-data
TCY3-T0121R 40-10 0021 Standard
88mm x 88mm
No humidity
sensor
Compact PI controller
with:
1 TI int or ext
1 AI
2 DO (Relay)
1 AO
TCY3-T0121R-D 40-10 0022 Deluxe
TCY3-T0121R-U 40-10 0023 Standard
2 x 4
TCY3-T0121R-U-D 40-10 0024 Deluxe
TCY3-T0121R-H 40-10 0025 Standard
88mm x 88mm
With humidity
sensor
TCY3-T0121R-H-D 40-10 0026 Deluxe
TCY3-T0121R-H-U 40-10 0027 Standard
2 x 4
TCY3-T0121R-H-U-D 40-10 0028 Deluxe
Dimensions [mm] (inch)


Deluxe version
2 x 4 housing
Integrated Humidity sensor
Relays for binary outputs
Number of analog outputs (AO) = 1
Number of binary output (DO) = 2
Number of analog inputs (AI) = 1
Number of binary inputs (DI) = 0
With external temperature input (RT)
Series (TCY3)
88 (3.5) 32 (1.2)
21
(0.8)
8
8

(
3
.
5
)

5
8

(
2
.
3
)

5
8

(
2
.
3
)

1
1
2

(
4
.
4
)

73 (2.9)
32 (1.2)
15
(0.6)

TCY3-T0121R Technical Data

Doc: 70-000002 V1.0, 20100420 Vector Controls GmbH, Switzerland Page 3
Subject to alteration
Technical specifications
Power Supply
Operating Voltage 24 V AC/DC 10 %, 5060 Hz
Power Consumption Max. 3 VA
Electrical Connection Terminal Connectors,
wire 0.342.5 mm
2
(AWG 2412)

Internal rectification:
Signal ground = power ground
Half wave rectified
Security transformer required
Clock backup 24 hours (Deluxe version only)
Signal inputs
Analog Input
Input Signal
Resolution
AI1
0...10 V or 0...20 mA
9.76 mV or 0.019 mA (10 bit)
Temperature Input
Range Int. NTC: 050 C (32122 F)
Ext. NTC (Sxx-Tn10 sensor): -40140 C (-40284 F)
Accuracy -400 C (-4032 F): 0.5 K
050 C (32122 F): 0.2 K
50100 C (122212 F): 0.5 K
> 100 C (> 212 F): 1 K
Humidity Input: (-H Version only)
Range
Accuracy at 55 % r.H.
Hysteresis
Repeatability
Stability
H1 Thermoset Polymer-Based Capacity
0100 % r.H.
3.0 % at 25 C (77 F)
3 % between 1590 % r.H.
0.5 %
0.5 % / year if used within 050 C (32122 F)
Signal outputs
Analog Outputs
Output Signal
Resolution
Maximum Load in voltage mode
AO1
DC 0...10 V or 0...20 mA (250 max.)
9.76 mV resp. 0.019 mA (10 bit)
10 mA
Relays Outputs
AC Voltage
DC Voltage
DO1, DO2
048 VAC, 2 (1.2) A max. each output
030 VDC, 2 (1.2) A max. each output
Environment
Operation
Climatic Conditions
Temperature
Humidity
To IEC 721-3-3
class 3 K5
050 C (32122 F)
<95 % r.H. non-condensing
Transport & Storage
Climatic Conditions
Temperature
Humidity
Mechanical Conditions
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-2570 C (-13158 F)
<95 % r.H. non-condensing
class 2M2
Standards
conform according to
EMC Standard
89/336/EEC
EMEI Standard 73/23/EEC

EN 61 000-6-1/ EN 61 000-6-3
Product standards
Automatic electrical controls for
household and similar use
Special requirement on
temperature dependent controls

EN 60 730 1

EN 60 730 2 9
Degree of Protection IP30 to EN 60 529
Safety Class III (IEC 60536)
Cover, back part
Mounting Plate
Fire proof ABS plastic (UL94 class V-0)
Galvanized Steel
General
Dimensions (H x W x D) Front part: 88 x 88 x 21 mm (3.5 x 3.5 x 0.8)
Power case: 58 x 32 mm ( 2.3 x 1.3)
Dimensions (H x W x D), U-version Front part: 112 x 73 x 15 mm (4.4 x 2.9 x 0.6)
Power case: 58 x 32 mm ( 2.3 x 1.3)

Weight (controller only) 180 g (6.3 oz)

Weight (including package) 260 g (9.2 oz)

TCY3-T0121R Technical Data

Doc: 70-000002 V1.0, 20100420 Vector Controls GmbH, Switzerland Page 4
Subject to alteration
Selection of actuators and sensors
Temperature Sensors:
Use only our approved NTC sensors to achieve maximum accuracy. Recommended is SDB-Tn10-20 as Duct sensor, SRA-
Tn10 as Room sensor and SDB-Tn10-20 with AMI-S10 as immersion sensor.
Modulating Actuators:
Choose actuators with an input signal type of 0-10 V DC or 4-20 mA. Minimum and maximum signal limitations may be
set in software.
Floating Actuators:
Actuators with constant running time are recommended. Observe power limits on binary devices.
Binary auxiliary devices:
E.g. pumps, fans, on/off valves, humidifiers, etc. Do not directly connect devices that exceed 48 VAC, 2(1.2) A. Observe
startup current on inductive loads.
Connection diagram

Y
B1
Y
B2
Y
M1
X
A1
R
T
2 3
1 4 5 6 7 8
TCY3-T0121..
24V AC/DC 10%
0...48 V
AC
0...30 V
DC
0V (GND)
0V


Description:
Y
B1
Binary output 1: 048 VAC or 030 VDC
Y
B2
Binary output 2: 048 VAC or 030 VDC
X
A1
Analog input 1: 05 V, 010 V or
*
020 mA
Y
M1
Analog output 1: 010 V or
*
020 mA
R
T
Temperature input 1: NTC 10k @ 25C (77F)


*
) selectable by jumper


WARNING:
Power supply is half-wave rectified:
Signal ground = Power ground

Connect through a safety isolation transformer


!