Escolar Documentos
Profissional Documentos
Cultura Documentos
COOLING WATER
TREATMENT
EMAMI LIMITED
13, B.T. ROAD, KOLKATA 700 056.
WEST BENGAL, INDIA
Page 1 of 12
This document is a sole property of Chemtex Speciality Limited. It is a confidential company document
for Chemtex and its buyer as mentioned above. Any unauthorized circulation or making duplicate
copies of the document is illegal and the company reserves its rights to take judicial action for such
offence.
FACILITY LOCATION
13, B.T. Road, Kolkata 700 056.
FOR KIND ATTENTION OF:Mr. Baroda Prosanna Rath
Mob: +91 9088910991
Email: baroda.rath@emamigroup.com
Mr. Raktim Roy
Mob: +91 9432371574
Email: raktimroy@emamigroup.com
Mr. Ashish Das
Mob:+919007361521
Email: ashishdas@emamigroup.com
Dear Sir,
With reference to your valued enquiry for cooling water chemical treatment
program, we are pleased to submit our detailed Techno-Commercial offer for the
same, as follows.
We shall look forward to the opportunity to serve you to the best of our ability and
have your esteemed organization name to our elite clientele.
For any queries or clarifications, please feel free to contact the undersigned.
Thanking you,
yours faithfully,
for CHEMTEX SPECIALITY LTD
Soumo Biswas
Engineer-Sales & Service
Mobile:+91 9830840044
E Mail:wtc@chemtexlimited.com
Direct No: (033) 7111-1117 (Extn:137)
Page 2 of 12
To
To
To
To
To
To
To control the TDS, hardness salts, chloride and silica level in re-circulating water
in limit
To remove suspended foreign matters from the CT sump
To reduce turbidity of circulating water
Page 3 of 12
Abr.
Unit
Values
CT#
Nos.
No. of cells
Nos.
Induced Draft
CT Sump Distribution
Separate
CT Capacity
TR
Range (Delta T)
DT
Current Blow-down
Not Known
8 approx
m per hour
200 approx
Deg C
m per hour
0.3
Current Evaporation
m per hour
1.5
Raw Water
Unit
COC
Total Hardness
Calcium
Hardness
Chloride
ppm as CaCO3
<300
Not known
ppm as Ca
<150
Not known
ppm as Cl
<100
Not known
TDS
ppm
<500
Not known
Not known
Not known
Maximum COC
Our Recommended COC
(COC based on Total Hardness)
Not known
6-8
Unit
Recirculation Water
pH
pH
7.2
Total Hardness
ppm as CaCO3
350
Calcium
ppm as Ca
210
Chloride
ppm as Cl
500
TDS
ppm
1130
Page 4 of 12
Silica
Free Chlorine
ppm as SiO2
ppm as cl
Not Known
Not Known
Unit
Recirculation Water
pH
pH
7.5-8.0
Total Hardness
ppm as CaCO3
<300
Calcium
ppm as Ca
<150
Chloride
ppm as Cl
<100
TDS
ppm
<1000
Silica
Langelier Saturation
Index
Free Chlorine
ppm as SiO2
<150
LSI
<+ 1.0
ppm as cl-
<0.5
Page 5 of 12
OUR RECOMMENDATIONS:We recommend the following chemical treatment program for your cooling tower
water
SHOCK DOSE for preparing system for a new chemical treatment program
for R&D Cooling Tower
Particular
Description
Shock Dose
Benefits
ALSTACOOL
Scale & Corrosion
3.5 kgs as
Removes adhering loose scales
AS 10
Inhibitor for cooling
slug in the
and rust
water
first week
Establishes instant passive coat
of multi metal corrosion
inhibitors
Blow down
Water draw off
0.300m3/hr
Will remove or minimize the
from the next
existing chemical concentration
day
SHOCK DOSE for preparing system for a new chemical treatment program
for R&D Roof Cooling Tower
Particular
Description
Shock Dose
Benefits
ALSTACOOL
Scale & Corrosion
2 kgs as slug Removes adhering loose scales
AS 10
Inhibitor for cooling
in the first
and rust
water
week
Establishes instant passive coat
of multi metal corrosion
inhibitors
Blow down
Water draw off
0.050m3/hr
Will remove or minimize the
from the next
existing chemical concentration
day
SHOCK DOSE for preparing system for a new chemical treatment program
for WHO GMP Cooling Tower
Particular
Description
Shock Dose
Benefits
ALSTACOOL
Scale & Corrosion
2.5 kgs as
Removes adhering loose scales
AS 10
Inhibitor for cooling
slug in the
and rust
water
first week
Establishes instant passive coat
of multi metal corrosion
inhibitors
Blow down
Water draw off
0.050m3/hr
Will remove or minimize the
from the next
existing chemical concentration
day
Page 6 of 12
Establishes instant
AS 10
us (Daily)
cooling
passive coat of corrosion
water
inhibitors
Quick removal of algae
0.700
Biocide for
Slug
and bio-films from the
ALSTACIDE
kgs/alternate
bio-fouling
(alternate
system
CW20
week after
control
Weekly)
Removes algae to a
sunset
great extent
0.700
Page 7 of 12
BLOW
DOWN
Water draw
off
Daily
0.050m3/hr
Establishes instant
AS 10
us (Daily)
cooling
passive coat of corrosion
water
inhibitors
Quick removal of algae
0.400
Biocide for
Slug
and bio-films from the
ALSTACIDE
kgs/alternate
bio-fouling
(alternate
system
CW20
week after
control
Weekly)
Removes algae to a
sunset
great extent
0.400
Page 8 of 12
COMMERCIAL OFFER
Total Cost Involved In Chemical Treatment of R&D Cooling Tower Water
ONE TIME
Regular Treatment Cost
Shock Dose
(Yearly Basis)
Product
Price
4 Weeks/28 Days
Qty
Amount
Yearly
Amount
Name
(Rs/kg)
Required
(In Rs.)
Requireme
(In Rs.)
nt
ALSTACOOL 275.00
3.5 kgs
962.50
28 kgs
7,700.00
AS 10
ALSTACIDE
253.00
1.4 kgs
354.20
CW 20
ALSTACIDE
267.00
1.4 kgs
373.80
CW25
TOTAL
3.5 Kgs
962.50
30.8 kgs
8,428.00
Total Cost Involved In Chemical Treatment of R&D ROOF Cooling Tower
Water
ONE TIME
Regular Treatment Cost
Shock Dose
(Yearly Basis)
Product
Price
4 Weeks/28 Days
Qty
Amount
Yearly
Amount
Name
(Rs/kg)
Required
(In Rs.)
Requireme
(In Rs.)
nt
ALSTACOOL 275.00
2 kgs
550.00
11.2 kgs
3,080.00
AS 10
ALSTACIDE
253.00
0.8 kgs
202.40
CW 20
ALSTACIDE
267.00
0.8 kgs
213.60
Page 9 of 12
CW25
TOTAL
2 Kgs
550.00
12.8 kgs
3,496.00
Page 10 of 12
Our Roles and Responsibilities:1. To ensure that the chemical dosing is being done as prescribed and the same
is being noted in the log book (provided by us).
2. To ensure prompt deliveries of chemicals as and when required
3. To inspect the cooling tower once in every month and e-mailing our
observations to the concerned department
4. To draw water samples and record the analysis reports Monthly basis
5. To ensure and train your employees to take all necessary human safety
measures for handling chemicals.
Page 12 of 12