This document provides specifications for glazed aluminum curtain walls and mashrabiya screens for a private residence in Abu Dhabi, UAE. It includes details on the curtain wall and mashrabiya system, submittal requirements, and performance standards. The curtain wall will surround the entrance foyer and include an aluminum mashrabiya shading screen and maintenance walkway. Calculations and shop drawings must be submitted and certified by a professional engineer showing the system meets structural and thermal requirements. Samples of materials and finishes are also required.
This document provides specifications for glazed aluminum curtain walls and mashrabiya screens for a private residence in Abu Dhabi, UAE. It includes details on the curtain wall and mashrabiya system, submittal requirements, and performance standards. The curtain wall will surround the entrance foyer and include an aluminum mashrabiya shading screen and maintenance walkway. Calculations and shop drawings must be submitted and certified by a professional engineer showing the system meets structural and thermal requirements. Samples of materials and finishes are also required.
This document provides specifications for glazed aluminum curtain walls and mashrabiya screens for a private residence in Abu Dhabi, UAE. It includes details on the curtain wall and mashrabiya system, submittal requirements, and performance standards. The curtain wall will surround the entrance foyer and include an aluminum mashrabiya shading screen and maintenance walkway. Calculations and shop drawings must be submitted and certified by a professional engineer showing the system meets structural and thermal requirements. Samples of materials and finishes are also required.
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 1 Sec. 08 44 13
SECTION 08 44 13
GLAZED ALUMINIUM CURTAIN WALL & MASHRABIYA
REVISION HISTORY
(0) August. 2011 RE RE MSH Rev Date Description of Revision Prepared by Checked by Authorized by
Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 2 Sec. 08 44 13
SECTION 08 44 13
GLAZED ALUMINIUM CURTAIN WALL
&
MASHRABIYA
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of Contract, including General and Particular Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Specification Section includes aluminium glazed curtain walling system for the Majalis (Block B), as shown on the drawings surrounding the entrance foyer. It includes the aluminium mashrabiya shading screen surrounding it along with the maintenance cleaning walkway in between. It also includes the aluminium shading screen of same pattern on the same building, and as labelled as 2d on the drawings.
B. Testing for airtightness : the same standard for site testing will apply for the Majlis as a whole ie: the wole building will be pressurized.
C. Related Sections include but are not necessarily restricted to:
1. Proposal from the Contractor for the work of this section shall be accompanied with drawings and data details which show how manufacturer intends to comply with requirements of this specification section for the exterior elements as follows: Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 3 Sec. 08 44 13
1. Show typical head, sill jamb and corner details and typical intermediate mullions. 2. Indicate the aluminium system type selected and glazing system also. 3. Junction with and anchorage to the building structure. 4. Air barriers and vapour barriers. 5. Dialectic separator details. 6. Thermal separator details as and wherever required. 7. Provisions for thermally induced expansion and contraction of members. 8. Provisions for absorption of the building structure movements. 9. Water drainage system 10. Detail at parapet condition, and all aluminium appings. 11. Pressure equalization system and air ventilation to the glass rebate. 12. Certified U-value calculations for glazing panels which shall include for the aluminium framing as well. 13. Design of all flashings and roof abutments, and any miscellaneous aluminium trim. 14. Design of metal walkway deck, including all connections. 15. Mashrabiya Panels, including detail of section and sample 200x200mm elevation at 1:1 scale
2. By submitting a proposal, the Contractor agrees that the data submitted with the bid and subsequent discussions do not negate the requirements of the specifications.
The drawings shall be either in CAD format or printed at a sufficiently detailed scale for the Engineer to understand all the details. This may typically mean details at 1:20, !:5 and 1:1 scale.
The design and performance specified are minimum requirements. Methods which may be suggested by these specifications for achieving the design and performance requirements are not intended to limit methods of achieving the required design and performance criteria. This shall not be construed to mean work of less quality and performance than specified may be supplied.
1.4 OTHER SUBMITTALS
1. Product Data
1. Submit manufacturer's specifications, fabrication requirements, and installation instructions, with amendments to obtain requirements of this section of the specifications. 2. Include erection and glazing details, maintenance and cleaning instructions. 3. Furnish data clearly describing reglazing techniques. 4. Furnish maintenance and cleaning instructions.
2. Calculations:
.1 Submit calculations, under seal and signature of the Professional Engineer, substantiating sizes and physical properties of the aluminium profiles, connections to the structure, glass type and thickness and also showing Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 4 Sec. 08 44 13
.5 Materials proposed and their allowable sheer and bending stresses.
.6 Deflections and expansion and contractions.
2 Prepare engineers calculations in a clear, comprehensive manner to permit easy review. Incomplete or haphazard calculations will be rejected unreviewed.
3. Shop Drawings:
.1 Submit shop drawings as specified.
.2 Each shop drawing shall bear seal and signature of the Professional Engineer.
.3 Show:
.1 Elevations
.2 Detailed design, dimensions, members, profiles, joint location and sizes, arrangement of units, horizontal to vertical connections, thicknesses, details of special shapes, reinforcing, drainage details, and flow diagrams, baffles, flashings, insulation, anchorage system interfacing with building structure, connections and joints and seals to adjacent building envelope systems, provisions for thermally induced expansion and contraction, provisions for absorption of building structure movements and creep and thermal break details. .3 Locations of exposed fasteners and joints. .4 Glazing details, methods, if done in field, in shop, locations of various types and thicknesses of glass. .5 Panels, related reinforcements and securement methods. .6 Sealant type and size of sealant joint.
Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 5 Sec. 08 44 13
.4 Samples:
.1 Submit samples as specified.
.2 Submit three samples of each material with respective finishes as follows:
.1 Extrusions : 300 long
.2 Sheets : minimum 300mm x 300mm
.3 Gaskets and tapes: 900mm long section of each type.
.4 Sealants: 150mm bead strips applied to metal sheet, showing colours.
.5 Fasteners : Three of each type
.6 Glass: 300 mm x 300mm of each type.
.3 Samples shall represent physical and chemical properties, finishes and colours to be supplied.
.5 Glass Stress Analysis Reports: Submit glass stress analysis performed by glass manufacturer/supplier of all glass. Identify locations of each glass unit on building, its stress factors and statement whether glass unit is to be annealed, heat strengthened or tempered. Bid price shall include for providing glass consistent with minimum results as determined by the glass stress analysis.
.6 Certifications:
.1 Submit statements certified by the professional Engineer stating:
.2 Work of this sections is engineered, supplied and installed as specified herein, including sound insulation values between dwellings via spandrel panels and acoustic stops being achieved in completed product.
.7 Submit statements certified by the sealant manufacturers attesting that:
.1 Sealants selected are suitable for purposes intended.
.2 Sealants will not deteriorate due to exposure to ultraviolet radiation (sunlight).
.3 Joint designs are correct.
Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 6 Sec. 08 44 13
.4 Sealants are compatible with other materials with which they come in contact.
.5 Sealant are suitable for temperature and humidity conditions at time of application.
.6 Surfaces are properly prepared and primed to accept sealants.
.7 Project Taking-Over Data: Submit Data Books, Operating Instructions Manual and Preventive Maintenance Manual for work of this section and as specified.
.8 Quality Control Assurance Programme covering production, assembly and structural glazing procedure. Contractor shall submit for approval a quality control programme to assure compliance with the specified finishes requirements. Contractor shall maintain complete certified inspection, testing and process records of finishing procedures and make them available to Architect upon request.
7. Prequalifications
1. Submit fabricators prequalifications, which shall include company profile, recent project references including jobs available for inspection. Reference information shall include contract value, product type, main consultants, architects, and completion dates
1. Submit a statement from the glass supplier that each product to be furnished is approved by them for the application shown, along with complete instructions for installation, replacement and cleaning.
1.5 DESIGN REQUIREMENTS
1. This shall be a fully capped stick curtain wall system of 52mm module from one of the manufacturers listed in 01 23 01 Schedule of Approved Manufacturers. Use Technal MX series or equal approved from one of the other manufacturers. The doors in this system shall be 52mm module with thermally broken profiles. The approved system for doors is Technal FXi series or equivelant from one of the othe approved manufacturers listed.
2. Mashrabiya Screen : to be made of aluminium perforated sheet of a thickness sufficient for it to remain flat and undistorted when erected. In any case at least 8mm thick. The pattern will be cut with a water jet. The screen will be discretely connected to a secondary aluminium Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 7 Sec. 08 44 13
structure forming an external skin to the double height curtain wall. The supporting structure of the mashrabiya will be connected to the curtain wall structure providing 600mm gap between the two skins and have cat walks for maintenance purposes.
3. Mashrabiya Panels : these are located above door/window openings in the Majalis block as shown labeled 2d on the drawings. They shall be made of exactly the same pattern of the perforated water jet cut aluminium as used in the Mashrabiya but will be mounted directly onto the wall behind using stainless steel fixings. These to be arranged to give a 40mm airspace between rear face of screen and external face of plastered wall behind.
4. Follow profiles, perimeter sizes and arrangements of components and assemblies indicated on the drawings to obtain the required appearance to the Engineer's approval.
5. All glass units of each type shall be same and shall have a consistent, uniform colour and appearance.
6. Installed glass components shall be free of distortion, oil canning and pillowing.
7. Exposed metal components shall be of uniform colour, sheen and appearance, within components and from component to component and shall match approved samples and mock-ups.
8. Exposed metal sheets, plates and extrusions shall be visually flat under all lighting conditions.
9. Grain and rolling direction of non-painted metal sheets and plates when installed on the building faces shall run in the same direction.
10. Grain and rolling direction of non-painted braked formed trims, sills and reveals and the extruded direction of not painted metal reveals, trims, sills. When installed on the building faces shall run in same direction.
11. Engineer and install glass units so each glass unit can be removed from the exterior side without removing adjacent glass units and metal panels.
12. Transoms to mullions connections shall be done with cast aluminium spigots and junction sealed with butyl sealant.
13. Accurately size mullions and cover caps at intersecting joints to obtain minimal joints, just wide enough to permit thermal expansion and contractions so no damages and distortions to the work occur due to thermally induced movements.
14. Conceal securement devices. Should it be demonstrated satisfactorily Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 8 Sec. 08 44 13
to Engineer's approval that some exposed securement devices are necessary, they shall be of same finish and colour of member in which they occur.
15. Ensure components and assemblies drain to building exterior.
16. Ensure components are designed, fabricated and installed to prevent build-up of sand with the cladding cavities and glazing pockets which could cause blockages to drainage of water.
17. The expansion joint of the vertical aluminium profile shall be sealed to prevent any leakage of water from the profile drainage groove to the inside section.
18. The transom mullion joint shall be overlapped and sealed.
19. All the gasket joints shall be welded or sealed by a glue compatible to the gasket material.
1.6 PERFORMANCE REQUIREMENTS
1. Pressure Equalization
a. Prove pressure equalization to glazing pockets, to exterior components of frames to column covers.
b. Provide baffles to prevent air flow within components and spaces as may be induced by stack effect and by wind forces. Locate baffles:
- Vertically orientated at every building corner..
- Horizontally orientated within extruded mullions at roof level.
- Horizontally orientated at window (vision areas) sills and heads.
- Provide baffles to prevent excessive rain entry into the components which could lead to water ponding and the prevention of pressure equalization.
- Provide baffles to prevent excessive sand entry into the components which could lead to blockages, built-up which could cause damaging expansion stresses and which could prevent pressure equalization.
2. Make provisions to accommodate the thermal expansion and contraction movements of the Curtain Wall for the following Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 9 Sec. 08 44 13
temperature range: - Exterior - From 0 o C to +60 o C - Interior - From +15 o C to +35 o C .
.1 Engineer work to accommodate within its components and to accommodate between the work and the building structure and other constructions, expansion and contractions due to cyclic temperature changes described under mechanical design conditions to prevent damages and distortions.
.2 Engineer work to accommodate within its components and to accommodate between the work and the building structure and other constructions, expansion and contractions due to cyclic heat gain and loss from the absorption of the components of heat which caused the components to get hotter than the temperature described under mechanical design temperatures.
.3 Thermal conductance of the work (U-value), including aluminium sections:
a.) Overall curtain wall assembly including windows and doors 2.8 w/m2K.
.4 Provide thermal breaks between interior and exterior components to prevent thermal bridges by using polythermid insulators, as such that all exterior components shall be condensation-free.
4. Water and moisture:
.1 Provide a watertight and air-tight assembly. Water leakage is defined as the appearance of uncontrolled water, other than condensation, on any inboard part of the Curtain wall and aluminium joinery. Engineer work to quickly drain any water and condensate moisture which may enter within the cladding components, to the building exterior.
.2 Engineer work to prevent entry of water and moisture to the building interior side of the work. Water tightness standard to be E600 when tested in accordance with the European Standard EN1027. There is to be no water penetration under a static air pressure of 600Pa.
5. Air Infiltration and Exfiltration:
.1 Air movement through the work, building interior to building exterior and building exterior to building interior shall not exceed: Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 10 Sec. 08 44 13
- A4 when tested in accordance with European Standard EN1026.
- Air leakage should be less than 2.5m3/hr/m2 and less than 1.0m3/hr/m of crack joint when tested at 600 Pa.
.2 Allow for mechanically induced air pressure at the building interior.
.3 No detectable drafts permitted.
6. Glazing:
.1 Engineer glazing systems to allow for characteristics of framing and effects of connections and sealant and frame connections.
.2 Engineer work, metal, glass, glazing to ensure no more than 8 glass units per 1000 break during the building's life.
.3 Pressure plates and other glass retaining devices shall apply uniform, continuous pressure to glass to prevent:
- Distortion, oil canning and pillowing of glass
- Pressure points on the glass which could contribute to stress breakage.
.4 Metal in direct contact with glass is not permitted.
.5 Insulating glass units must not have their seals in contact with water.
7. Acoustics: Provide completed installation free of rattles, wind whistles and other noise due to thermal and structural movements and due to differential atmospheric pressure. The complete curtain walling assemblies, including frames and seals, shall provide an airborne sound insulation rating STC 33 measured in accordance with ASTM E 1408 Standard Test Method for Laboratory Measurement of the Sound Transmission Loss of Door Panels and Door Systems and rated in accordance with ASTM E 413 Classification for Rating Sound Insulation:
8. UV and Heat Resistance: All materials provided which are exposed to atmospheric heat and which are exposed to sunlight including materials exposed through glass shall be formulated not to lose properties due to exposure to heat and due to exposure to ultra-violet radiation.
Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 11 Sec. 08 44 13
9. Structural:
.1 Base design on pressures, positive and negative as created by wind on a min. velocity of 45m/sec. (162 km/hr) computed in accordance to BS-CP3 Chapter V: Part2. Allow for impact, suction, up lift and gusting of wind.
.2 Engineer work to withstand within acceptable deflection limits, it own weight, forces applied by building structure movements, forces applied by adjacent components and design loads due to wind, stack effect and rain. The window cleaning catwalk must be able support operatives and window cleaning equipment.
.3 Engineer work to accommodate and submit design criteria for approval for following items:
.1 Movements within components.
.2 Movements applied due to attached adjacent constructions.
.3 Movement applied due to the building structure, long and short term creep, column shortening, deflections, torsion, sway and racking.
.4 Movements due to vibrations.
Provisions shall ensure no damages, distortions, misalignments occur to the work and that integrity of thermal, air infiltration/exfiltration, weather and watertightness barriers are maintained and aesthetic considerations are maintained.
.4 Engineer work not to exceed following deflections under full design loads:
.1 Normal to the Curtain wall plane: 1/175 of the vertical span or 19mm whichever is the lesser for spans less than 4.1m.For spans higher than 4.1m 1/240 + 6.35mm. Parallel to the Curtain wall plane 1/300 of span or or 10mm, whichever is less. Notwithstanding the above limits, the Curtain Wall shall not deflect sufficient to cause noise, break seals or otherwise affect the integrity of the glazing elements.
.5 Engineer elastic deflections to prevent reduction of Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 12 Sec. 08 44 13
glass bite under full load from exceeding 2.5mm.
.6 Engineer deflection limits to ensure integrity of seals and glazing are maintained under full load, dynamically applied.
.7 Permanent deformation of members shall not occur under loading 1.5 times the Design Load (positive or negative). Permanent deformation is defined as deflection without recovery exceeding 1/500.
.8 All elements used in anchoring the Curtain Wall to the structure including fastenersshall be designed with 50% safety factor above the design load conditions.
.9 Engineer work to keep stresses on components, assemblies and materials within working range of components, assemblies and materials. Make provisions to accommodate the relative movement of the structure due to long term (creep) loads as well as live loads.
.10 Expansion joints shall be sealed to the inside with special accessory and mastic that will allow movement and keep the air and water tightness below the specified limits.
.11 The joint between the transom and mullions shall be sealed with EPDM sealing strips.
10. Acoustic:
.1 Refer to 01 80 00
1.7 TOLERANCES
1. Tolerances shall be:
.1 Vertical position : plus/minus 2mm
.2 Horizontal portion: plus/minus 2mm.
.3 Racking in elevation : nil.
.4 Deviation from true plumb over full height: max. 6mm.
.5 Deviation from true straight in plane over full length of each building face; maximum 6mm.
2. Tolerances, not accumulative. Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 13 Sec. 08 44 13
1.8 QUALITY ASSURANCE
GENERAL
Character of these documents is intended to provide performance type specification for design, fabrication and installation of aluminium curtain wall systems. Contractor is responsible for engineering and design of all components and materials as well as fabrication, installation and performance of these systems.
a. Architectural drawings are diagrammatic. Architectural details shown are intended as guide for aesthetic and interfacing requirements of various components of exterior wall to and with other work. Requirements shown by details are intended to establish basic dimensions of module and sight lines, jointing and profiles of members. Contractor is responsible for design and engineering of system within these aesthetic parameters. Drawings are not to be construed as engineering design, or adequate to meet engineering design requirements.
b. It is recognized that architectural design details do not cover some conditions or modifications, which may be required. It is, however, intended that conditions not detailed shall be developed through Contractors shop drawings to same level of aesthetics and in compliance with performance criteria as indicated for detailed areas and as stipulated in these specifications. Contractor, by accepting contract for this work, acknowledges this and agrees that the Engineer shall have final say as to all matters whether detailed or not in architectural design details.
1. Engineering:
.1 Have work engineered by a licensed Professional Engineer.
.2 Have submittals, proposals, samples, shop drawings, certifications, proposed substitutions bear the seal and signature of the Professional Engineer.
.3 Have fabrication and installation of work inspected and certified approved by the Professional Engineer.
2. Fabricator's Qualifications:
All works shall be Pre-Designed, extruded, fabricated and finished at the Factory in country of origin of the approved system manufacturers which has to have skilled workmen, specially trained and experienced in this type of work.
.1 Firm must be regularly engaged in engineering, manufacturing, Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 14 Sec. 08 44 13
fabricating, finishing, installing, glazing and sealing of the type of work specified in this section for minimum of five years.
.2 Firm must be able to demonstrate satisfactorily completed works of minimum size as this project.
.3 Firm must be able to demonstrate thorough understanding of the principles of air seals, dynamic forces, behaviour of cast-in- place concrete structures, water and weather controls as affecting building systems.
.4 Owner and the Engineer reserve right to visit fabricating facilities of the approved manufacturers at any time and at Contractor expense when work is in progress. All shop and field materials and workmanship subject to observation by the Engineer at all times. Such observations do not relieve Contractor from obligations to provide work conforming to all requirements of Documents and as specified herein.
3. Prototype for Laboratory Testing:
.1 Provide prototype of curtain wall and other glazed panel systems for inspection and testing. Modify prototype as necessary to pass inspection and testing.
.2 Prototype shall be 2 floors high and about 5m wide and shall include framing, glass, spandrels, metal air/vapour barrier, insulation, seals, gaskets, flashings, anchorages on to structure, baffles, and all accessories as necessary to provide a complete system.
.3 Install prototype components in same sequence and utilizing same methods and personnel as will be used for actual on building installations.
.4 Connect prototypes air-tight to test chambers.
.5 Should prototype fail to meet performance requirements, make corrections and modifications for further testing at no cost to the Owner. Costs of further tests shall be paid for by the Aluminium works Sub-contractor.
.6 Tests to be done:
a. Air infiltration test according to ASTM E283 & AAMA.
b. Water penetration test according to ASTM E331 and AAMA.
c. Structural deflection test according to ASTM E330 & AAMA. Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 15 Sec. 08 44 13
d. Water test according to ASTM E331 & AAMA
e. Structural performance test at 1.5 times the design load.
.7 There should be no failure or permanent deformation when applying a load of 1.5 times the design load.
4. All production shall be done in the sub-contractor's own plant under full time quality controlled conditions.
5. Sub-contractor shall submit for approval a quality control programme covering all aspect of production and glazing that has been reviewed and approved in writing by the approved silicone manufacturer.
6. A full time in plant test programme is to be implemented and maintained for the full duration of the project, with weekly reports submitted to the Engineer covering all aspects of the operation.
7. Sub-contracting of any work included hereunder is specifically prohibited, except for that approved by the Engineer in writing.
1.9 PROTECTION
1. Protect work from damage.
2. Do not apply snap-on caps and spandrels until the building is closed in, until the roofing is installed and until no possibility of alkaline substances can be washed from the building and building structure onto the work.
.3 Should work be prefabricated into assembled units complete with glazing, snap-on caps, in the factory and installed on the building as complete units, precautions shall be taken to protect units and glass from damage due to alkaline bearing water.
.4 Clean glass as necessary to prevent etching due to alkaline bearing water.
1.9.1 WARRANTIES
1. Submit written warranty in form acceptable to Owner as described on Spec Section 05 50 01 Aluminum Fabrications, jointly signed by Contractor and by sub-contractor for the work, warranting against defective materials, products, workmanship, watertightness, design, performance and glass breakage, due to defective engineering fabrication and installation and for Ten Year period following date of substantial performance of the work. This to extend to include all Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 16 Sec. 08 44 13
glazing, windows and doors incorporated into the curtain walling system.
2. Ten Year warranty shall include but not necessarily be limited to:
.1 Complete watertight and airtight work within specified tolerances.
.2 Structural soundness and freedom and distortion, and within elastic deflection limits specified.
.3 Glass or snap-on mullion covers will not break or 'pop' from frames due to design wind loads, expansion or contraction movements, or structural loading.
.4 Metal finish will not crack, peel, pit, corrode, or discolour.
.5 Sealants and gaskets shall remain free from deterioration, oxidation or dislocation due to sunlight and weather conditions.
.6 Completed installation shall remain free from rattles, wind whistles, and noise due to thermal and structural movements and wind pressure.
3. Warrant the seals on insulated glass units for ten years. Units shall be free from condensation, fogging, and obstruction of vision due to film on internal surfaces.
4. Warrant the polyester powder coatings or anodized surfaces will be free from peeling, cracking, pitting, corroding, or non-uniformity of colour, or gloss deterioration per approved paint manufacturer's for a period of Ten Years.
5. Warranty for Ten years, the metallic oxide coating on light and heat reflecting glass.
6. Coating shall be free of oxidation, delamination, colour change, streaks, disintegration and Scratches.
2.00 PRODUCTS
2.01 MATERIALS
These descriptions apply in addition to or amplification of those in Spec Section 05 50 01
1. Materials: Inorganic, resistant to rodents, vermin, mildew, fungus and algae, as necessary to obtain design and performance requirements and as follows:
Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 17 Sec. 08 44 13
2. Framing, Trim and Flashings:
.1 Aluminium Components:
a. Extrusions: Aluminium Alloy 6063-T6 Temper.
b. Sheet: Alloy 5005 H14 Temper or equal.
.2 Steel : Structural Steel ASTM A36 or equal. Stainless Steel ASTM A167, type 304 or 316, or equal. Fasteners : stainless steel 300 series or hot dipped galvanized steel.
.3 Slip Washers : nylon
.4 Thermal Separator (thermal break): Use Polythermid insulator, sized to conform to extruded aluminium members and to provide required U-Value.
.5 Dielectric Separator: Bituminous paint, tape or dielectric coating.
.7 Insulation for packing between frames and adjacent construction: light weight, inorganic mineral wool of 50 kg/m cu nominal density or as otherwise directed by Contractors Cladding Design Engineer to achieve required sound and fire stopping. Continuous foil vapour barrier externally.
2.02 SEALANTS
A. Non-Structural:
1. All joints, which are sealed with sealant as part of the fabrication or erection procedure, shall be sealed with an approved medium modules silicone (exposed or concealed)sealant. All perimeter sealant (metal to adjacent construction) shall be medium modules silicone sealant. Silicone sealant shall meet the requirements of ASTM C 920 and shall be as manufactured as per 01 23 01 Schedule of Approved Manufacturers.
Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 18 Sec. 08 44 13
2. In using specified sealants, strictly observe the printed instructions of sealant manufacturer and ASTM C 962 regarding joint size, limitations, backer rod, mixing, cleaning, surface preparation, priming and application. A primer shall be used only if required by sealant manufacturer to obtain specified adhesion and performance. Sealant shall not be applied when substrates are wet or when the temperature is below 40 Deg. F. unless special low temperature application procedures, as recommended in writing by the sealant manufacturer are adhered to.
3. Where required, care shall be exercised to prevent 'three surface adhesion', bond barkers shall be provided where necessary.
4. Contractor shall provide certification from sealant manufacturer that the sealant manufacturer has reviewed the Contractor's shop drawings and sealant details, and finds same suitable for the purpose for the purpose intended, and has tested all components in contact with sealant for compatibility and will not satin the surfaces with which they are in contact. Statement as to compatibility by ASTM C 1087, adhesion by ASTM C 794 and non-staining by manufacturers standard stain test shall be accompanied by actual results on the project production materials and finishes performed in accord with applicable test procedures.
B. Structural Sealant:
1. All structural glazing, shall be done with an approved structural silicone sealant meeting the requirements of ASTM, C 920, black colour, approved products are in 01 23 01 Schedule of Approved Manufacturers. All glazing with structural silicone sealant shall be accomplished in the shop under controlled conditions and with full time quality control monitoring and testing taking place.
2. In using specified sealants, strictly observe the printed instructions of sealant manufacturer and ASTM C962 regarding joint size, limitations, backet rod, mixing, cleaning, surface preparation, priming and application. A primer shall be used only if required by sealant manufacturer to obtain specified adhesion and performance. Sealant shall not be applied when substrates are wet or when the temperature is below 40 Deg. F. Units shall not be moved until structural silicone Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 19 Sec. 08 44 13
seal has achieved full cure, the parameter of when units may be moved to be established and confirmed with silicone manufacture in writing.
3. Contractor shall provide certification from sealant manufacturer that the sealant manufacturer has reviewed the Contractor's shop drawings and sealant details and has tested all components, materials, finishes, etc., in contact with sealant, and finds same compatible and suitable for the purpose intended. Sealant manufacturer's certification as to compatibility and adhesion shall be accompanied by actual test results on production substrates performed in accordance with applicable ASTM procedures and shall include the following based upon tests performed on the project production run materials:
.a Adhesion of each structural sealant to production samples of each metal finish and glass type, when tested in accordance with ASTM C 794, establishing adhesion over the temperature range as described under the performance criteria section of this specification.
.b Compatibility of production samples of each material and finish in contact with the sealants such as other sealants, gaskets, spacers, and setting blocks when tested in accordance with ASTM C 1087.
.c Stress statement for sealant profile (per shop details), that when exposed to the specified windload, the design stress on the silicone sealant does not exceed the permissible stresses specified by the manufacturer.
4. Sub-Contractor shall establish and submit for review a quality control programme covering the cleaning, priming, silicone sealant application, gaskets, spacers, setting blocks and other materials and finishes.
Programme shall, cover the initial testing for adhesion/compatibility, and also regular periodic testing to be done during the production of the project on production run materials, etc. Specifically including shop 'peel and adhesion' test of silicone, prior to its use. Reports of such tests shall be kept in file available for review by the Engineer. Also include methods which will be employed to monitor workmanship such as substrate cleaning and priming and sealant application both for shop fabrication and necessary job site replacement Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 20 Sec. 08 44 13
glazing, repair and remedial work. No sealant or glazing work shall be performed prior to sealant manufacturer's written acceptance of the Quality Control Programme.
. Sealant manufacturer shall be requested to make periodic inspections of glazing work, the initial one being at the start of glazing for job production units, to verify that sealant work is proceeding in accordance with its recommendations, including de-glazing of randomly selected units to inspect and verify quality of sealant and workmanship. Sealant manufacturer shall submit inspection reports covering his observations and any recommendations.
2.04 GLAZING
General
All the glass shall be float quality, with a minimum thickness of 6mm.
All the glass shall be heat strengthened or tempered in accordance with the suppliers recommendation.
Definitions: Heat Strengthened Glass: To BS 952-1, BS 952-2 and ASTM C-1048 or CAN2- 12.1-M76, tong free, with strength mid-way between annealed glass and fully tempered glass. Glass shall bear a factory applied permanently stamped impression in one corner and visible when glass is installed, which identifies the glass as being heat-strengthed.
Definitions: Fully Tempered Glass: To BS 952-1, BS 952-2 and ASTM C-1048 or CAN2- 12.1-M76, tong free. Glass shall bear a factory applied permanently stamped impression in one corner and visible when glass is installed, which identifies the glass as being fully- tempered.
Glazing materials, whether in monolithic state or as lite of thermal insulating unit shall be heat-strengththened or tempered where required by glass manufacturers design calculations to resist stress caused by glass orientations, sizes and configurations, heat stress, inherent imperfections, wind loading, glazing conditions, temperature differential, inside window treatment and other conditions affecting breakage probability.
1 For heat treated glass, orient lits with roll-distortion parallel to head and sill members. 2 Tempered and wire glazing materials must comply with BS 952-1, BS 952-2 and ANSI Z97-1. 3 Labels: Identify glass panes and insulating glass units with labels, showing thickness, glass type and manufacturer's name. Labels on insulating glass units shall also show orientation and location of outer light. 4 Vision through glass: Distortion free. 5 Shims: Pressure sensitive, resilient, extruded synthetic rubber as recommended by glass manufacturer. 6 Spacers and setting blocks: 50 to 70 Durometer A hardness plus/minus 5 respectively, neoprene rubber, resistant to sunlight, weathering, oxidation, and Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 21 Sec. 08 44 13
permanent deformation under load. 7 Glazing compound: Use two components silicone from Dow Corning or any other approved supplier, which shall be suitable for the structural glazing application as secondary seal. The primary seal should be polyisobutylene. 8 Glazing Tapes: Extruded, ribbon shaped, non-drying, non-skinning, non-oxidizing, UV blocked, reinforced with internal shim rod, of sufficient width and thickness to permit continuous void-free seal between metal and glass. 9 Glazing Wedges : EPDM or Neoprene 150mm long, 80-90 durometer Shore and/or rigid silicone wedges for Structural Glazed Panle 80-90 durometer Shore and/or aluminium wedges 150mm long with EDPD adhesive tape, as applicable. 10 Glazing Gaskets: shall be made from high performance quality EPDM or neoprene. Hardness 50-60 durometer Shore. At corners use single piece vulcanized gaskets. Use special sealing adhesive to joint the gasket and to fill grooves below the corner vulcanized gasket. 11 Colours of glazing compounds, gaskets: As designated by the Engineer from the manufacturers standard colour range.
Glass shall be fixed into frames by means of extruded neoprene glazing gaskets of proper profiles, sections and sizes to fit the various aluminium sections and to ensure a tight and waterproof seal against the glass.
Glass must rest on purpose made PVV glazing blocks which suits sections design.
All units shall be installed in the positions assigned to them plumb square and level and in alignments with the surrounding work. They shall be securely fixed and all opening parts shall function properly without there being any to use force for operating them.
All glazing work has to comply with DIN 18361, 18545, 18055 and other relevant codes.
The Contractor shall provide and fix all necessary silicone sealers to effectively seal junctions between masonry and aluminium frames.
Storage and Handling:
All glass must be installed using procedure and materials that comply with normal industry practice.
It is glazing Contractors responsibility to ensure that all glazing materials are compatible with the units and that the methods used are appropriate for the type of installation, wind loads and other conditions.
Thermal Stress:
The potential risk of thermal breakage shall be calculated by a thermal stress analysis (or thermal check) which should be carried out by the glazing manufacturer. A copy of this should be submitted to the Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 22 Sec. 08 44 13
Engineer for approval.
The edge of all type of glass, especially heat strengthened and solar control glazing must remain clean cut for optimal resistance to thermal breakage.
Particular Glazing Specifications:
Refer to 08 81 00 Glazing.
2.05 FINISHES
All exposed aluminium shall be powder polyester coated finish as Section 09 91 01. Colour RAL as approved mock-up colour to be permanent and free from "banding" or "streaking" and to the approval of the Engineer. Any aluminium sections which are completely concealed and therefore do not require the facing colour shall be clear (silver) anodised to a minimum standard of BS EN 12373: 2001.
1. Exposed fastenings if occurring: Finished and coloured to match the finish and colour of the material in which they appear. The finish provided shall be permanent and durable.
All non-exposed steel to be hot-dipped galvanized.
Provide separation between all steel and aluminium elements in order to avoid electrochemical corrosion.
Make provisions for differential expansion of aluminium and stell elements.
2.06 FABRICATION : GENERAL
1. Fabricate all components in compliance with shop drawings submitted and cleared with Engineers stamp. Do not commence until Engineer has cleared all samples. Fabricate and assemble units with joints at intersections of members with uniform hairline connections. Shop fabricate units to greatest extent practicable. Submit to the Engineer prior to commencement the names of all suppliers of materials, including hardware. Submit samples and finishes of hardware to the Engineer.
2. Insofar as practical, execute fitting and assembly in the shop with the various parts or assemblies ready for erection at the building site.
3. Take field measurements and levels required to varify or supplement those shown on the drawings for the proper layout and installation of the work.
Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 23 Sec. 08 44 13
4. Coordinate dimensional tolerances in adjacent building elements and confirm prior to the commencement of the work. Commencement of installation floor by floor shall be construed as acceptance of building conditions. Work shall not deviate from tolerances specified.
5. Accurately machine, file, fit and securely frame together all joints, corners, mitres. Match components carefully to produce perfect continuity of lines and design. Make all joints weathertight. Maximum allowable tolerance at joints 1mm
6. Location of exposed joints shall be submitted to the Engineer.
7. Make exposed work free of machine marks and dimpling. All the screws, bolts, rivets reinforcing, as well as the connections shall be concealed. Exposed fasteners will not be allowed.
8. Fabricate components to avoid force fitting to obtain alignment with adjacent components.
9. Fabricate curtain/window wall system to allow for thermal movement within construction.
Fabricate curtain/window wall components allowing for accurate and rigid fit of joints and corners. Match components carefully ensuring continuity of line and design. Ensure joints and connections will be flush, hairline and weatherproof.
10 Fabricate curtain/window wall system to collect and remove all water from within system to weep to exterior. Provide weep holes of sufficient size and in sufficient number in order to achieve both the instant pressure equalization and the drainage of water from the system.
Fabricate horizontal strip windows with continuous gutter and weep holes at glass sill, and with continuous gutter at glass head which drains directly to exterior.
Fabricate corner pieces, filler pieces, flashings, capping and closures to the profiles shown on the drawings. Make corners square and use concealed fixings. Provide backing plates at all joints
11. Reinforcement: Reinforce aluminium work at anchorage and support- points, at joints and attachment points for interfacing work. Provide noncorrosive anchors for fasteners in aluminium less than 3mm thick.
12. Reinforce all frames by concealed means as necessary to meet the specified design requirements.
13. Provide steel brackets and support framing to fasten frames in place in opening. Provide slotted connections as required to accommodate Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 24 Sec. 08 44 13
defection of opening components.
14. Where frame members are lapped, the faces exposed to the weather shall be in full, tight contact. Allow minimal clearance for snap-on components.
15. Where mullions are extended and connected to the underside of the building structure above, provide slotted connections to accommodate structure deflection.
16. Fabricate corner pieces and filler pieces of thick plate aluminium to the profiles shown, by welding prior to application of finish.
17. Provide concealed clips for fastening plate assemblies in place.
18. Identify units with corresponding opening code. Mark only on frame parts to be concealed in installation process.
19. Ship units packaged in polyethylene bags with cardboard ears.
20. All metalwork shall be accurately set out, cut, framed and executed using proper rivets, bolts or self tapping stainless steel screws.
21. Aluminium elements in curtain/window wall systems, doors, windows and screens shall be of the dimensions, sizes and sections as shown on the drawings, fabricated and supplied only by one of the approved nominated system - manufacturers.
22. All the Aluminium elements of the project has to be fabricated in the own plant of the approved system manufacturer. No local fabrication shall be allowed.
PART 3 - EXECUTION
3.1 PREPARATION
A. Co-ordinate and provide details of the work as necessary to ensure co- ordination with related building elements and services. Liase as necessary to help ensure coordination of the work with related building elements and services, provide fabrication/installation drawings and other information requested, submit sufficient copies of drawings, etc., for approval. Make any necessary amendments in accordance with any comments of the Engineer and without delay and resubmit unless it is confirmed that this is not necessary and submit sufficient copies of final version of drawings, etc., for distribution to all affected parties.
B. Take field measurements from actual structure and verify prior to commencement of fabrication. Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 25 Sec. 08 44 13
C. Remove dust and other loose material from openings.
3.2 INSTALLATION: GENERAL
1. Installation will be supervised continuously and carried-out only by skilled mechanics with successful experience in installing the proposed system. Erect all work plumb and true and in proper alignment and relationship to established lines and grades and to specified tolerances. Bear the cost of surveying the work, using state- of-the-art equipment during the whole installation.
2. All devices for anchoring the frame assemblies to the building structure shall have sufficient adjustment to permit correct accurate alignment. After alignment, rivet, weld or positively lock anchorage devices to prevent movement other than those designed for expansion and contraction. The temperature prevailing at the time of erection must be taken into consideration.
3. Site located fixings to the in-situ structure shall be an approved material. Perform drilling of concrete as required to install fixings. Bear cost of repair satisfactory to the Engineer of concrete chipped by drilling or fixing operations.
4. Supply and install aluminium/stainless steel parapets, copings flashings, cap flashings and base and waterproofing membrane to all joints between the aluminium and the building structure.
5. Provide continuity of thermal and air barriers with adjacent thermal and air/vapour systems.
a. Gun-apply a continuous 6mm bead of sealant to all joints and barrier junctions with adjacent construction Liberally butter screw fastenings with sealant.
b. Apply insulation to the building interior side (metal on warm side) of the metal air barriers erected. Cut insulation slightly over-size as required to ensure tight butt joints.
6. Ensure air tight seal at air barrier penetrations for mechanical and electrical services. Provide water and airtight seals between the Curtain wall and adjacent construction.
3.2 INSTALLATION: GLAZING
1. Clean all surfaces of dust, dirt, moisture, oil and all other foreign matter detrimental to glazing material adhesion. Ensure that no drainage holes are blocked. Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 26 Sec. 08 44 13
2. Mask surfaces subject to staining, to ensure a neat appearance of the glazing bead. Remove masking after application.
3. Accurately size glass to fit openings, allowing clearances according to trade practices and specifications.
4. Inspect glass edges and verify that they are clean-cut. Do not install glass with damaged edges. For all heat strengthened and tempered glass, the edges must be polished.
5. Replace all materials damaged due to faulty installation, careless handling or other causes resulting from the work.
6. Use spacers, setting blocks and shims of sizes recommended by the glass manufacturer, to support and hold the glass in position. Place only two setting blocks under each glass unit and quarter points. Avoid blocking the water drainage from the system.
7. Install glazing gaskets in continuous length between corners, not stretched, and seal vulcanize or weld joints at corners to prevent air and water entry.
8. Set glass properly centred, with uniform bite and face and edge clearances, free from twist, warp or other distortion likely to develop stress in the glass.
9. Ensure a weathertight and rattle-free seal for glass-cusioning. Minimum clearances allowable: Edge Clearance : 6mm Face Clearance : 5mm Glazing should be executed only at temperatures between 5 and 38 degrees Celsius.
10. Spares: provide 2% of typical glazing units as spares.
3.2 INSTALLATION: SEALANT
1. Make surfaces to be sealed, sound, dry, free from dirt, water, frost, loose scale, corrosion, asphalt, paints or other contaminants which may adversely affect the performance of the sealing materials.
2. Perform cleaning to the extent required to achieve acceptable joints surfaces.
3. Joints and spaces which are to receive sealing compound shall in no Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 27 Sec. 08 44 13
case be less than 4mm deep; nor shall they be less than 6mm nor more than 15mm wide.
4. Fill joints to within 5mm of the surface with backup material.
5. Mask areas adjacent to the joints as required. Prevent contamination of adjacent surfaces. Remove masking promptly after the joint has been completed.
6. Perform priming immediately before installation of sealant.
7. Before any sealing is commenced, test the materials for indications of staining or poor adhesion.
8. Use sufficient pressure to fill all voids and joints. Sealants shall bond to all sides of joint except where backup material is used, sealant shall bond to both sides of joint and shall not adhere to the backup material.
9. Sealant installations shall be a full bead free from air pockets and embedded impurities and having smooth surfaces, free from ridges, wrinkles, sags, and imbedded impurities.
10. After joints have been completely filled, tool them neatly to a slight concave profile.
11. Cover all fasteners penetrating the air seal with sealant.
12. Seal all gasketting at sills.
13. Immediately clean adjacent surfaces which have been soiled and leave work in a neat, clean condition. Remove excess materials and droppings using recommended cleaners and solvent.
14. The fact that the drawings do not show all locations to be sealed does not limit responsibility to seal all locations required to create and secure a continuous enclosure.
15. Apply sealant only when the ambient temperature is between 5 and 38degrees Celsius and in low humidity.
3.2 ADJUSTMENTS AND CLEANING
1. Clean regularly during progress. Remove concrete and alkali wash- offs to prevent etching of glass and metal finishes. Upon completion of the project and just prior to the handing over of the building of the Owner or at a time as directed, inspect and make good installation.
2. Adjust all operating devices and doors to proper and trouble free operating condition.
Private Residence on Plot #9, Sec. E/49, Eastern Mangrove, Abu Dhabi, UAE Main Contract
Bureau of Excellence in Architecture & Design Rev (0) www.bead-architects.com Project A10-18 October 2011 28 Sec. 08 44 13
3. Inspect all units for damage and correct same immediately.
4. When building completed, clean metal and glass thoroughly. Remove excess sealant using solvent approved by the sealant manufacturer and without damaging finishes or coatings.
5. Upon completion remove all debris, equipment and excess materials from the site..
Document History (Office Use)
Date of previous use
Project
Comments Oct 2010 A9-30 Reference to it just being a performance specification omitted. Acoustic Consultant notes added