Você está na página 1de 22

STANDARD REFERNCE SHEET

SAESJ902

7 Enclosures

7.1 Enclosures for instruments in outdoor plant areas shall
be NEMA Type 4 in accordance with NEMA ICS 6 and
NEMA 250 or IEC 60529 Type IP 65. Enclosures in
severe corrosive environments shall be NEMA Type 4X
or IEC 60529 Type IP 66.

7.2 The field junction box, in a Class I, Zone 2 location
and in non-hazardous areas, shall be a single door NEMA
Type 4X or IEC 60529 Type IP 66 box. The box
construction shall meet the following requirements:

7.2.1 Type 316 stainless steel body, door and
hardware.
7.2.2 Continuously welded seams, finished
smooth.
7.2.3 Stainless steel hinge.
7.2.4 Stainless steel captive clamps.
7.2.5 Data/Print pocket on inside of door.
7.2.6 External mounting brackets.
7.2.7 Collar studs for mounting inside panel.
7.2.8 Ground stud for terminating A/C safety
ground wire.
7.2.9 Removable door
7.3 All field junction boxes shall be mounted
vertically, i.e., the door shall open from left-to-
right or from right-to-left.
7.4 Instrument enclosures and junction boxes having
an internal volume exceeding 2,000 cm shall be
provided with Type 300 Series stainless steel
breather and drain fittings, or a combination
breather and drain fitting.

10.2.10 The terminals shall be mounted on vertical DIN
rails (i.e., horizontal DIN rails are not allowed).

Commentary Note:
This section is specifying vertical DIN rails in 'field junction
boxes'. This section is not intended to apply to ancillary
termination boxes, e.g., smart ZV control stations, GUA fittings,
etc.

10.2.11 The DIN rail shall only be mounted on the inside
panel (back-pan) of the junction box.



16.3 Terminal Reference

16.3.1 Each row of terminals shall be uniquely
identified alphanumerically, e.g., TS-101,
TS-102, etc.

16.3.2 The terminals in each row shall be
sequentially numbered starting at number
one (1).

17.2 Safety Ground

17.2.1 All exposed non-current-carrying metallic
parts that could become energized with hazardous
potentials must be reliably connected to the
equipment grounding circuits. This assures that
hazardous potential differences do not exist between
individual instrument cases or between an instrument
case and ground. Therefore, all metal equipment and
enclosures within a panel or series of panels (i.e.,
instrument cases, hinged doors, racks, etc.) shall be
bonded with bonding jumpers and connected to a
safety ground bus with a minimum copper wire size
of 12 AWG. Two copper conductors, 25 mm
minimum, shall be connected from the safety ground
bus to a single tie point on the safety ground grid in a
closed loop configuration. Safety ground connections
must be made such that when a case-grounded
instrument is removed, the integrity of the rest of the
safety ground system is maintained.

34-SAMSS-820
5.3 Heat dissipation calculations shall be submitted
for any cabinet that houses power supplies, PCs or other
heat generating components. The calculations shall show
that the components installed inside the cabinet will not
be exposed to a temperature above their temperature
rating.


SL.NO Originator Action By Compliance Status Status On
1
2
3
4
5
6
7
1
2
3
4
5
6
1
2
ACCESSFITTINGSJUNCTIONBOX
RS485REPEATERJUNCTIONBOX
CRMSSYSTEMCABINET
TheTerminalMarkingIdentification:TheTerminalsInEachRowShallBeSequentiallyNumbered
StartingatNumber1.(TB2,TB3,TB4..TerminalMarkingShallBeStartFromNo1).
EnclosuresDrain&BreatherMaterialType:InstrumentEnclosureAndJunctionBoxesHavingAn
InternalVolumeExceeding2,000Cm3ShallBeProvidedWithType300StainlessSteelBreather
AndDrainFittings,OrACombinationBreatherAndDrainFitting).(NowDrain&BreatherMaterial
IsPlastic).
HeatDissipationCalculations:HeatDissipationCalculationsShallBeSubmittedForAnyCabinet
ThatHousesPowerSupplies,PCsOrOtherHeatGeneratingComponents.TheCalculationsShall
ShowThatTheComponentsinstalledInsideTheCabinetWIllNotBeExposedToATemperature
AboveTheirTemperatureRating.(NotAvilable).
BackPanMaterial:316StainlessSteelBackPanels.(NowBackPanIsGalvanize).
TheTerminalMarkingIdentification:TheTerminalsInEachRowShallBeSequentiallyNumbered
StartingatNumber1.(TB2TerminalMarkingShallBeStartFromNo1).
HingedDoorSafetyGround:Therefore,AllMetalEquipmentAndEnclosuresWithinAPanelOr
SeriesOfPanelsHingedDoorShallBeBondedWithBondingJumbersAndConnectedToASafety
GroundBus.
DoorLocks:KeyLocksPadlocksAreNotAcceptable.(316StainlessSteelCaptiveScrewsMayBe
UsedInLieuOfCaptiveClampsProvidedThatTheScrewDoNotPenetrateTheDoorGasket).
Data/PrintPocket:Data/PrintPocketOnInsideOfDoor.(Data/PrintPocketMissing).
EnclosuresDoor:StainlessSteelHingeRemovableDoor.(DoorHingeMissing)
HingedDoorSafetyGround:Therefore,AllMetalEquipmentAndEnclosuresWithinAPanelOr
SeriesOfPanelsHingedDoorShallBeBondedWithBondingJumbersAndConnectedToASafety
GroundBus.(NewHingeTypeDoorSafetyGround).
Data/PrintPocket:Data/PrintPocketOnInsideOfDoor.(Data/PrintPocketMissing).
BackPan:TheDINRailShallOnlyBeMountedOntheInsidePanel(BackPan)OfTheJunction
Box.(BackPanelMissing).
BackPanMaterial:TheDINRailShallOnlyBeMountedOntheInsidePanel(BackPan)OfThe
JunctionBox.(TheNewBackPanelMaterialShallBeSS316).
TheTerminalDINRailMountingPosition:TheTerminalsShallBeMountedOnVerticalDINRails
(i.e.,HorizontalDINRailsAreNotAllowed).(NowTerminalsAreInHorizontalPosition).
CRMSSYSTEMINSPECTIONPUNCHLIST
Punch List description Comments
TheTerminalMarkingIdentification:EachRowOfTerminalsShallBeUniquelyIdentified
Alphanumerically(TB1IdentificationMissing)

Você também pode gostar