Você está na página 1de 30

AM2000

Analog fire panel


Installation
manual

AM2000 Installation Manual INDEX
NOTIFIER ITALIA DOC.195.2-AM2000-ENG Rev. A.2 AM2000_MANU_INST
I
I
N
N
D
D
E
E
X
X

Cabinet & dimensions 1
Front panel indication & keypad 2
AM-2000 CPU board 3
Connector CN1 on AM-2000 Power Supply Board 4
Serial printer connections 5
Alphanumeric terminal connections 5
LCD-6000 PROGRAMMING 6
SW1 DIP SWITCH 6
SW2 DIP SWITCH 6
Connector CN0 on LCD- 6000 7
Siren and AM-2000 Main board wiring 8
SLC Loop analog devices components 8
Detector and Modules wiring - Typical LOOP line (style 6) 9
Class A wiring circuit and line isolators 10
Notes about loop wiring 11
SLC loop shield wiring 15
SIB-600 board 16
Connector CN2 on SIB-600 optional board 16
Annunciator connection 17
ACS Wiring 17
ACM Series 18
LDM Series 19
Appendix 21
AM-2000 Power Supply Board 22
The 220 VAC Power Supply line 23
Current calculation 24
Alarm condition 25
Battery capacity calculation 26

AM2000 Installation Manual INDEX
NOTIFIER ITALIA DOC.195.2-AM2000-ENG Rev. A.2 AM2000_MANU_INST






ADHERENCE TO THE FOLLOWING WILL AID IN PROBLEM-FREE INSTALLATION WITH LONG-TERM RELIABILITY

WARNING
Several different sources of power can be connected to this fire alarm control panel. Disconnect all sources of power before
servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or
interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is
read and understood.

CAUTION
The System and all its components have to be installed in an environment with the following features:
Temperature: 0-49 C
Humidity: 85% RH (non-condensing) @ 30C.

However, the useful life of the system's standby batteries and the electronic components may be adversely affected by
extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in
an environment with a nominal room temperature of 15-27 C.

Verify that wire sizes are adequate for all initiating and indicating device loop. Most devices cannot tolerate more than a 10%
I.R. drop from the specified device voltage.

Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning
induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding
will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby
lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.

Disconnect AC power and batteries prior to removing or inserting circuits boards. Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all
cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer,
and printed circuit board location.

Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal contact
pressure and difficulty with screw terminal removal.

This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any
circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies
removed from the unit.

Follow the instructions in the installation, operating and programming manuals. These instructions must be followed to avoid
damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.

Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or roofs, or on
the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor building. Furthermore, all
types of smoke detectors have sensing limitations.

A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby
batteries only for a specified time.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed
for service with your control panel.

The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring
should be tested and maintained by professional fire alarm installers following written procedures supplied with each device.
System inspection and testing should be scheduled monthly or as required by National and/or local fire codes. Adequate
written records of all inspections should be kept.

AM2000 Installation Manual PAGE - 1
NOTIFIER ITALIA Doc. M-195.2-AM2000-ENG Rev. A.2 AM2000_MANU-INST
C CA AB BI IN NE ET T D DI IM ME EN NS SI IO ON N

TOP-VIEW
PAGE - 2 Installation Manual AM2000
AM2000_MANU-INST Doc. M-195.2-AM2000-ENG Rev. A.2 NOTIFIER ITALIA
F FR RO ON NT T P PA AN NE EL L I IN ND DI IC CA AT TI IO ON N E E K KE EY YP PA AD D

AM2000 Installation Manual PAGE - 3
NOTIFIER ITALIA Doc. M-195.2-AM2000-ENG Rev. A.2 AM2000_MANU-INST
A AM M- -2 20 00 00 0 C CP PU U B BO OA AR RD D

PAGE - 4 Installation Manual AM2000
AM2000_MANU-INST Doc. M-195.2-AM2000-ENG Rev. A.2 NOTIFIER ITALIA
C CO ON NN NE EC CT TO OR R C CN N1 1 o on n A AM M- -2 20 00 00 0 P PO OW WE ER R S SU UP PP PL LY Y B BO OA AR RD D




NOTES
1) These two outputs CANNOT operate simultaneously. The operator
must select the Type of Connection to employ, from the Control Panel
Main Programming Menu (refer to AM-2000 Programming Manual).

2) Alarm and Trouble Controls: voltage FREE contacts Normally
closed/open selectable with Jumper JALL/JGST. Use to drive resistive
loads only.
Alarm is activated if a detector of the lines is in ALARM condition.
Trouble is activated if a detector of the lines is in TROUBLE condition.

3) If a line is programmed as Style 6 (loop line), terminals A are the
OUTWARDS and terminals B are the RETURN.

*) In order to execute the Upload/Download operations it is necessary to
select the relative function in the Modify Status menu.
AM2000 Installation Manual PAGE - 5
NOTIFIER ITALIA Doc. M-195.2-AM2000-ENG Rev. A.2 AM2000_MANU-INST
S SE ER RI IA AL L P PR RI IN NT TE ER R C CO ON NN NE EC CT TI IO ON NS S




PLUG THE DB-25 CONNECTOR INTO THE EIA-232 PORT OF THE PRINTER.





A AL LP PH HA AN NU UM ME ER RI IC C T TE ER RM MI IN NA AL L C CO ON NN NE EC CT TI IO ON NS S



PLUG DB-25 CONNECTOR INTO THE EIA-232 PORT OF THE CRT TERMINAL.
PAGE - 6 Installation Manual AM2000
AM2000_MANU-INST Doc. M-195.2-AM2000-ENG Rev. A.2 NOTIFIER ITALIA
L LC CD D- -6 60 00 00 0 P PR RO OG GR RA AM MM MI IN NG G



S SW W1 1 D DI IP P S SW WI IT TC CH H

D DI IP P # # D DE EN NO OM MI IN NA AT TI IO ON N U US SE E
1 1 N NO OT T U US SE ED D
2 2 N NO OT T U US SE ED D
3 3 N NO OT T U US SE ED D
4 4 N NO OT T U US SE ED D
5 5 N NO OT T U US SE ED D
6 6 O ON N T TH HE E L LA AS ST T R RE EP PE EA AT TE ER R I IT T M MU US ST T B BE E i in n O ON N P PO OS SI IT TI IO ON N
7 7 I IT T M MU US ST T B BE E i in n O OF FF F P PO OS SI IT TI IO ON N
8 8 N NO OT T U US SE ED D


NOTE: ON= Last device / OFF= Intermediate device.

The LAST DEVICE is connected on the return lines towards the control panel, directly
connected to the terminals 23 and 24 of control panel CN1 connector. .









S SW W2 2 D DI IP P S SW WI IT TC CH H

TERMIN. NR. DENOMINATION USE
1
N NO OT T U US SE ED D
2
O ON N : : E EA AC CH H E EV VE EN NT T I IS S S SI IG GN NA AL LL LE ED D V VI IA A B BU UZ ZZ ZE ER R
A AC CT TI IV VA AT TI IO ON N
3
O ON N : : I IT T E EN NA AB BL LE ES S T TH HE E R RE ES SE ET T B BU UT TT TO ON N O ON N L LC CD D
K KE EY YP PA AD D
4
O ON N : : I IT T E EN NA AB BL LE ES S A AC CK K B BU UT TT TO ON N O ON N L LC CD D K KE EY YP PA AD D
5
O ON N : : I IT T E EN NA AB BL LE ES S T TH HE E S SI IG GN NA AL L S SI IL LE EN NC CE E B BU UT TT TO ON N
6
P PA AN NE EL L T TY YP PE E S SE EL LE EC CT TI IO ON N: : O OF FF F= =A AM M6 60 00 00 0
7
N NO OT T U US SE ED D
8
N NO OT T U US SE ED D

AM2000 Installation Manual PAGE - 7
NOTIFIER ITALIA Doc. M-195.2-AM2000-ENG Rev. A.2 AM2000_MANU-INST
C CO ON NN NE EC CT TO OR R C CN N0 0 O ON N L LC CD D- -6 60 00 00 0

TERMIN. NR. DENOMINATION NOTES USE CABLE
COLOUR/NUM
.
1
EARTH

2
NOT USED

3
NOT USED

4
NOT USED

5
NOT USED

6
NOT USED

7
GND

8
LIN + A (OUT) RS 422 CONNECTION TO THE PANEL

9
LIN - A (OUT) RS 422 CONNECTION TO THE PANEL

10
GND

11
LIN + R (IN) RS 422 CONNECTION FROM THE PANEL

12
LIN - R (IN) RS 422 CONNECTION FROM THE PANEL

13
+ 24 V REPEATER POWER SUPPLY

14
+ 24 V REPEATER POWER SUPPLY

15
GND REPEATER POWER SUPPLY

16
GND REPEATER POWER SUPPLY





E EX XA AM MP PL LE E O OF F C CO ON NN NE EC CT TI IO ON N A AM MO ON NG G S SE EV VE ER RA AL L L LC CD D- -6 60 00 00 0 R RE EP PE EA AT TE ER RS S


NOTE: Power supplies are not indicated. By using local power supply the operator must remember that the
control panel and LCD-6000 repeaters must share the same negative.
PAGE - 8 Installation Manual AM2000
AM2000_MANU-INST Doc. M-195.2-AM2000-ENG Rev. A.2 NOTIFIER ITALIA
S SI IR RE EN N A AN ND D A AM M2 20 00 00 0 M MA AI IN N B BO OA AR RD D W WI IR RI IN NG G














S SL LC C L LO OO OP P A AN NA AL LO OG G D DE EV VI IC CE ES S C CO OM MP PO ON NE EN NT TS S


DETECTOR and MODULE COMMUNICATION LINES
The AM-2000 System communicates with intelligent and addressable, monitor and control devices through a
2-wire line.
The lines can be wired to meet the requirements of an NFPA STYLE 4, STYLE 6 or STYLE 7.
The peripheral devices are powered using the same line as for data communication.

ISOLATOR MODULES
Isolator modules (ISO-X) permit a group of devices and modules to be electrically isolated from the
reminder of the SLC Loop, allowing critical loops components to operate even in case of a short circuit of the
communication line.

MONITOR MODULES
Addressable Monitor Modules (MMX) allow the AM-2000 to monitor N.O. Contacts, alarm initiating devices,
manual pull stations, 4-wire conventional smoke detectors, heat detectors, water-flow and supervisory
devices.

CONTROL MODULES
Through addressable Control Modules (CMX) the AM-2000 can selectively activate notification appliance
circuits or FORM-C (Voltage free contacts) output relays.

INTELLIGENT DETECTORS
The AM-2000 can communicate with intelligent ionization, photoelectric, thermal and Rate-of-Rise detectors.


AM2000 Installation Manual PAGE - 9
NOTIFIER ITALIA Doc. M-195.2-AM2000-ENG Rev. A.2 AM2000_MANU-INST
D DE ET TE EC CT TO OR R A AN ND D M MO OD DU UL LE E W WI IR RI IN NG G



PAGE - 10 Installation Manual AM2000
AM2000_MANU-INST Doc. M-195.2-AM2000-ENG Rev. A.2 NOTIFIER ITALIA
C CL LA AS SS S A A W WI IR RI IN NG G C CI IR RC CU UI IT T A AN ND D L LI IN NE E I IS SO OL LA AT TO OR RS S

F Fu un nc ct ti io on ns s i in n a ac cc co or rd da an nc ce e w wi it th h N NF FP PA A S ST TY YL LE E 7 7 S Si ig gn na al li in ng g L Li in ne e C Ci ir rc cu ui it t







































NOTE: The number of addressable devices between ISO-X modules must not exceed 25 devices.


OPERATION

By separating each group of SLC Loop devices, with a pair of ISO-X Trouble Isolator Modules, each device is
protected from open and short circuits on all other sections.

For instance, a trouble on Section 2 will not affect Section 1 and 3.
The Isolator Modules on either side of Section 2 will open the SLC Loop. Section 1 will still operate from
power on Channel A, and Section 3 will operate from Channel B.
Since the control panel will no longer be able to communicate with the SLC Loop devices on Section 2, a
trouble signal will be generated (INVALID REPLY from Section 2 Points).
The circuit is a variaton of an NFPA Style 6 Signaling Line Circuit, therefore no T-Tapping or branching is
allowed.
The ratings and features are the same as for the Style 6 circuit.
AM2000 Installation Manual PAGE - 11
NOTIFIER ITALIA Doc. M-195.2-AM2000-ENG Rev. A.2 AM2000_MANU-INST
N NO OT TE ES S A AB BO OU UT T L LO OO OP P W WI IR RI IN NG G



CLASS A WIRING
Total lenght of the SLC Loop pair (from the control panel output and back to the control panel) CANNOT
exceed 3000 meters.



The DC resistance of the SLC Loop pair CANNOT exceed 40 Ohm.

The measurement must be made by disconnecting Channels A and B at the control panel, shorting the two
leads of Channel A together, and metering the two leads of Channel B.
PAGE - 12 Installation Manual AM2000
AM2000_MANU-INST Doc. M-195.2-AM2000-ENG Rev. A.2 NOTIFIER ITALIA
CLASS B WIRING

BRANCH RESISTANCE

Short the termination point of one branch at a time and measure the DC resistance, from the beginning of the
channel to the end of that particular branch.
The total DC resistance from panel to branch end CANNOT exceed 40 Ohm.
Repeat the procedure for all remaining branches.
The total of all branches on Channel B CANNOT exceed 3000 meters.




The total of all branches on Channel A and Channel B CANNOT exceed 3000 meters.
For each channel:
Add the lenghts of all branches.
The total CANNOT exceed 3000 m.
(BranchA)+(Branch B)+(Branch C)+(Branch D)+(Branch E)<=
3000 meters.
AM2000 Installation Manual PAGE - 13
NOTIFIER ITALIA Doc. M-195.2-AM2000-ENG Rev. A.2 AM2000_MANU-INST
ANALOG SYSTEM LINE TEST PROCEDURE
Before powering the control panel lines verify the following values:
NOTE: DIGITAL VOLTAGE METER NEEDED

a) Line Resistance

Short positive and negative of one end of the system. Place tester probes on the (+) and (-) sides of the line.


The resistance CANNOT exceed 40 Ohm.

b) Line Isolation
Remove the prior short circuit. Place the tester probes on the positive (+) and negative (-) sides of the line
with detectors or modules installed, and verify as follows:

b1)
Connect:
Tester (+) / Line (+) and Tester (-) / Line (-)
Verify:
Resistance: 1 - 1.3 MOhm

b2)
Connect:
Tester (+) / Line (-) and Tester (-) / Line (+)
Verify:
Resistance: 0.7 - 0.9 MOhm

c) Line and Cable Shield Isolation
Place one probe of the tester on the line wire shield and the other one on the positive (+) side of the line. The
resistance MUST exceed 15 - 20 MOhm, better if infinite. Performe the same procedure between the shield
and the negative (-) side of the line, and verify that the resistance exceed 15 - 20 MOhm.

d) Line and System Earth Isolation
Place one probe of the tester on the System Earth and the other one on the positive (+) side of the line. The
resistance MUST exceed 15 - 20 MOhm, better if infinite. Performe the same procedure between earth and
the negative (-) side of the line, and verify that the resistance exceed 15 - 20 MOhm.

e) Cable Shield and System Earth Isolation
Place one probe of the tester on the System Earth and the other one on the shield. The resistance MUST
exceed 15 - 20 MOhm, better if infinite.

f) Line Voltage
When the detector/module line is connected, the LIB output voltage (terminal 1 - 3) must be 24 VDC without
device polling (no Points programmed).
A voltage lower than 14 VDC, indicates a polarity inversion on at least one device.
PAGE - 14 Installation Manual AM2000
AM2000_MANU-INST Doc. M-195.2-AM2000-ENG Rev. A.2 NOTIFIER ITALIA
CABLE REQUIREMENTS

Type of cable: 2-conductor TWISTED pitch 5 cm. and SHIELDED cable.
Sections concerning the line total lenght (for the line STYLE 6" or CLOSED LOOP, the operator must
consider the loop lenght) which CANNOT exceed 3000 meters and whose resistance must be lower than 40
Ohm.

Example: Up to 1.000 meters cable 2 x 1 mm2 18 AWG Belden 9574
Up to 1.500 meters . cable 2 x 1.5 mm2 16 AWG Belden 9575
Up to 2.000 meters cable 2 x 2 mm2 14 AWG Belden 9581
Up to 3.000 meters cable 2 x 3 mm2 12 AWG Belden 9583

As far as the laying of cables is concerned, follow the below listed instructions:

- Suitable pipes;
- The cables must run at a proper distance from the power lines and must not be in the vicinity of any High
Voltage.

Troubles often may be caused by:

Air-conditioning installation
Engines or electric welding machines
Electrical furnaces and elevators
Radio links, etc.


ELECTRIC POWER
Power supply voltage: 220 V single phase +/- 10%.
Frequency: 50 Hz +/- 1 Hz.

NOTE: pay special attention when installing the system near big electromagnetic sources (REPEATERS).


EARTH PLANT
The earth plant must be performed according to the CEI and ISPLES rules. The resistance CANNOT exceed
10 Ohm (to be measured at the well with disconnected mains).

AM2000 Installation Manual PAGE - 15
NOTIFIER ITALIA Doc. M-195.2-AM2000-ENG Rev. A.2 AM2000_MANU-INST
S SL LC C L LO OO OP P S SH HI IE EL LD D W WI IR RI IN NG G


FOR SLC LOOP WHICH IS NOT CONTAINED IN PIPING OR METAL PIPING

A) NOTE:
Maintain the continuity of the shield wire throughout the loop, BUT DO NOT connect to any devices.
Connect the shield wire to the outside of the control panel cabinet and the cabinet to earth.



FOR SLC LOOP WHICH IS CONTAINED IN METAL PIPING OR IN CONDUIT

B) NOTE:
In this case, DO NOT allow the shield drain or shield foil to touch the cabinet.
For Style 6 field wirings, connect ONLY ONE END of the shield to the negative side of Channel A.
Maintain the continuity of the shield wire throughout the loop, BUT DO NOT connect to any devices.
PAGE - 16 Installation Manual AM2000
AM2000_MANU-INST Doc. M-195.2-AM2000-ENG Rev. A.2 NOTIFIER ITALIA
S SI IB B- -6 60 00 0 B BO OA AR RD D





















JUMPER ON RS-485 - 2-WIRE OPEN LINE
JUMPER ON RS-422 - 4-WIRE (OUTWARD/RETURN) CLOSED LINE (LOOP)


C CO ON NN NE EC CT TO OR R C CN N2 2 o on n S SI IB B- -6 60 00 0 O OP PT TI IO ON NA AL L B BO OA AR RD D


N NO OT TE E: : A As s f fo or r w wi ir ri in ng g o of f m ma ax xi im mu um m 1 15 5 m me et te er rs s u us se e 2 23 32 2 s se er ri ia al l l li in ne e ( (t te er rm mi in na al ls s 4 4- -5 5- -6 6) ); ;
A As s f fo or r w wi ir ri in ng g e ex xc ce ee ed di in ng g 1 15 5 m me et te er rs s u us se e 4 48 85 5 s se er ri ia al l l li in ne e w wi it th h I IT T- -4 48 85 5 i in nt te er rf fa ac ce e ( (t te er rm mi in na al ls s 7 7- -1 11 1) ). .
AM2000 Installation Manual PAGE - 17
NOTIFIER ITALIA Doc. M-195.2-AM2000-ENG Rev. A.2 AM2000_MANU-INST
A AN NN NU UN NC CI IA AT TO OR R C CO ON NN NE EC CT TI IO ON N




A AC CS S W WI IR RI IN NG G
AWG 16 section (1,31 mm2) shielded cable. Maximum lenght: 1800 meters.

Up to 500 meters 0,5 mm2
Up to 1000 meters 1 mm2
Up to 1500 meters 1,5 mm2




N NO OT TE E: :
ACS power supply is not indicated.
By using local power supply the operator must remember that the control panel and annunciator repeaters
must share the same negative.
PAGE - 18 Installation Manual AM2000
AM2000_MANU-INST Doc. M-195.2-AM2000-ENG Rev. A.2 NOTIFIER ITALIA
ANNUNCIATOR DEVICES WHICH CAN BE INTERFACED WITH THE AM-2000 CONTROL PANEL

ACM 16
ACM 16-E
ACM 32
ACM 32-E
LDM 32
LDM 32-E
ACM-8R


Some basic indications about the different annunciator model configuration are related below.
For further informations refer to the relative manuals.

ACM Series



DIP SWITCH SETTING FOR THE AM-2000

DIP 1 OFF
DIP 2 INSTALLED EXPANSIONS None
DIP 3 INSTALLED EXPANSIONS None
DIP 4 OFF
DIP 5 OFF
DIP 6 ACS Buzzer Enabled: OFF ACS Buzzer disabled: ON
DIP 7 OFF
DIP 8 OFF

AM2000 Installation Manual PAGE - 19
NOTIFIER ITALIA Doc. M-195.2-AM2000-ENG Rev. A.2 AM2000_MANU-INST
POWER SUPPLY TERMINAL BLOCK (TB1)




TERMINAL BLOCK TO CONNECT THE 485 SERIAL (TB2)




LDM Series



7
2
PAGE - 20 Installation Manual AM2000
AM2000_MANU-INST Doc. M-195.2-AM2000-ENG Rev. A.2 NOTIFIER ITALIA
SW 3 DIP SWITCH SETTING FOR THE AM-2000

DIP 1 OFF
DIP 2 INSTALLED EXPANSION None
None OFF
One ON
Two OFF
Three ON
DIP 3 INSTALLED EXPANSION None
None OFF
One OFF
Two ON
Three On
DIP 4 OFF
DIP 5 OFF
DIP 6 Buzzer Enabled: OFF
Buzzer Disabled: ON
DIP 7 OFF
DIP 8 OFF



POWER SUPPLY TERMINAL BLOCK (TB 1)





TERMINAL BLOCK TO CONNECT THE 485 SERIAL (TB2)


AM2000 Installation Manual PAGE - 21
NOTIFIER ITALIA Doc. M-195.2-AM2000-ENG Rev. A.2 AM2000_MANU-INST
A AP PP PE EN ND DI IX X

PAGE - 22 Installation Manual AM2000
AM2000_MANU-INST Doc. M-195.2-AM2000-ENG Rev. A.2 NOTIFIER ITALIA
A AM M- -2 20 00 00 0 P PO OW WE ER R S SU UP PP PL LY Y B BO OA AR RD D

AM2000 Installation Manual PAGE - 23
NOTIFIER ITALIA Doc. M-195.2-AM2000-ENG Rev. A.2 AM2000_MANU-INST
T TH HE E 2 22 20 0 V VA AC C P PO OW WE ER R S SU UP PP PL LY Y L LI IN NE E

The AM-2000 control panel requires connection to a separate 220 VAC 50 Hz line, which must be labeled
FIRE ALARM.
No other equipment may be powered by the circuit employed for the fire alarm system.

Overcurrent protection for this circuit must comply with local normatives.
Use proper section wire with minimum 600-volt insulation.


TABLE 1 : 220 VAC SERVICE LINE CURRENT REQUIREMENTS

The table 1 allows to calculate the total amount of corrent, in AC amps, that the AC service line must be
capable of supplying to the system.



PAGE - 24 Installation Manual AM2000
AM2000_MANU-INST Doc. M-195.2-AM2000-ENG Rev. A.2 NOTIFIER ITALIA
C CU UR RR RE EN NT T C CA AL LC CU UL LA AT TI IO ON N
The power Supply must be capable of powering, all internal system devices (and all external devices)
continuously during stand-by condition.
Use table 2 to determine the stand-by load.
Use table 3 to determine the additional current needed during Alarm condition.
The requirements for stand-by and alarm current loads cannot exceed the capabilities of the power supply in
either case.
The Power Supply provides a 24 VDC current up to 1 amp so that the system could operate during stand-by
or alarm condition.

Fill in the table 2 for devices that must be steadly powered only.

NOTE:
in table 2 use the current value indicated for the stand-by condition (refer to manufacturers instructions for
detector current draws).
Write the alarm condition absorption into table 3.

TABLE 2: STAND-BY CONDITION CURRENT REQUIREMENTS (24 VDC)



NOTE: the total of stand-by load obtained in table 2 CANNOT exceed 1
AM2000 Installation Manual PAGE - 25
NOTIFIER ITALIA Doc. M-195.2-AM2000-ENG Rev. A.2 AM2000_MANU-INST
A AL LA AR RM M C CO ON ND DI IT TI IO ON N

The table 3 allows the system designer to determine the current load that must be supported by the power
supply during an alarm condition.

The total current drawn from the Power Supply in alarm condition cannot exceed 1 Amp.
Enter the number of devices, for each type, the control panel must power simultaneously during alarm
conditions.


NOTE:
in table 3 use the current value indicated for the alarm condition (refer to manufacturers instructions for
detector current draws).

Table 3: alarm condition current requirements



NOTE: If the total load obtained exceeds 1 Amp (provided by the power supply), the batteries will
supply the current to support alarm conditions.
PAGE - 26 Installation Manual AM2000
AM2000_MANU-INST Doc. M-195.2-AM2000-ENG Rev. A.2 NOTIFIER ITALIA
B BA AT TT TE ER RY Y C CA AP PA AC CI IT TY Y C CA AL LC CU UL LA AT TI IO ON N

The table 4 allows to determine the size of the batteries needed to support both stand-by condition and five
minutes of alarm operation.

Table 4 : battery current load required





NOTIFIER ITALIA S.r.l.
A socio unico - 20097 San Donato Milanese (Ml) - Via Grandi, 22 - Tel.: 02/518971 - Fax: 02/5189730 - Capitale Sociale
2.700.000,00 i.v. - C.C.A.A. 1456164 - Trib. Milano Reg. Soc. 348608 - Vol. 8549 Fasc. 8 - Partita IVA IT 11319700156
(informativa privacy art. 3 Digs 196/03).
UFFICI REGIONALI:
10151 Torino - Via Pianezza, 181 - Tel.: 011/4531193 - Fax: 011/4531183 - E-mail: notifier.torino@notifier.it - 35128 Padova Via
Turazza, 30 - Tel.: 049/8943911 - Fax: 049/8943930 - E-mail: notifier.padova@notifier.it - 40050 Funo di Argelato (BO) - Asta
Servizi, Bl. 3B, Gall. B n. 85, Centergross - Tel.: 051/864855 - Fax: 051/6647638 - E-mail: notifier.bologna@notifier.it 50122
Firenze - Piazza de'Cimatori.1 Tel/Fax: 055/289177 - 00040 Roma (Morena) - Via Del Casale Santarelli, 51 - Tel.: 06/7988021 -
Fax: 06/79880250 - E-mail: notifier.roma@notifier.it - 80143 Napoli - Palazzo Prof. Studi - Centre Direzionale, Isola G1, Scala D,
Piano 15 - Tel.: 081/7879398 - Fax: 081/7879159 - E-mail: notifier.napoli@notifier.it - 70125 Bari - Via Delia Costituente, 29 -
Tel.: 080/5013247 - Fax: 080/5648114 - E-mail: notifier.bari@notifier.it - 95126 Catania - Via del Rotolo, 40 Scala A - Tel.:
095/7128993 - Fax: 095/7120753 - E-mail: notifier.catania@notifier.it
20097 Tel: 02/518971
San Donato Milanese Fax: 02/5189730
(MILANO) www.notifier.it