2x150MWCOALBASEDTHERMALPOWERPROJECT

M/SSHREECEMENTLTD.,
BEAWAR,RAJASTHAN(INDIA)

DocNo.
3VYN291401A.R0
ABBLIMITED
SHORTCIRCUITFORCEFOREQUIPMENT
INTERCONNECTION
Sheet1of17

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
ABB eBoP.






SHORTCIRCUITFORCEFOR
EQUIPMENTINTERCONNECTION








OWNER M/SSHREECEMENTLTD.



OWNERSENGINEER
EvonikEnergyServices(I)Pvt.Ltd.,
Noida


EPCCONTRACTOR
CetharVesselsLimited,
Tiruchirapalli



eBOPCONTRACTOR ABBLimited,Faridabad








R0

21.04.2010

RK/RM
Rev
No.
Date
Prepared
by
Reviewed
by
Approved
by
Remarks



2x150MWCOALBASEDTHERMALPOWERPROJECT
M/SSHREECEMENTLTD.,
BEAWAR,RAJASTHAN(INDIA)

DocNo.
3VYN291401A.R0
ABBLIMITED
SHORTCIRCUITFORCEFOREQUIPMENT
INTERCONNECTION
Sheet2of17

We reserve all rights in this document and in the information therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
ABB eBoP.



REVISIONSTATUSSHEET

REV.NO.

DATE DESCRIPTION

R0

21.04.2010 FORAPPROVAL






I System Data:
1.1 Nominal System voltage in kV = 400
1.2 System short circuit current in A (I"k3) = 40000
1.3 Factor for peak short circuit current () = 1.81
1.4 Phase spacing in m (a m) = 7
1.5 System frequency in Hz (f) = 50
1.6 Auto Reclosing Feature YES
II Conductor data:
21 Busbar selected = 4" IPS(Schedule80) Al
Short Circuit Force Calculation
(For Equipments)
2.1 Busbar selected
2.2 Outer diameter (Do) = 114.3 mm
2.3 Inner Diameter (Di) = 97.18 mm
2.4 Area of Cross section (A) = 2844 sq.mm
2.5 Moment of inertia (J ) = 4.00E-06 m^4
2.6 Weight (m') = 7.678 kg/m
2.7 Young's Modulus (E) = 6.57E+10 N/ sq.m
III Reference
3.1 IEC 865 -1(1993): short circuit current calculation effects
4 IPS (Schedule 80) Al

e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 3 of 17 3VYN291401A-R0
IV Legend: Symbol Unit
4.1 Initial symmetrical short circuit current (r.m.s) I"k3 Amps
4.2 Peak short circuit current Ip3 Amps
4.3 Effective distance between main conductors am m
4.4 Span between supports l m
4.5 Outer Diameter of the conductor Do m
4.6 Absolute permeability of vacuum o
4.7 Ratio of dynamic and static force on support (As per
equation in page no. 107 of IEC 865 -1(1993)) V F
4.8 Ratio of stress for a main conductor with or with out three
phase auto reclosing (As per equation in page no. 109 of
IEC 865 -1(1993)) V r
4.9 Factor for force on support (from table 3 of pg. 67 of IEC
865-1(1993)) a
4.10 Factor for relevant natural frequency estimation (From
table 3 of pg. 67 of IEC 865-1, 1993)
4.11 Natural frequency of the tube fc Hz
4.12 Electromagnetic force F m kg
4.13 Total static weight of bus M kg
4.14 Reaction due to electrodynamic force Fd kg
4.15 Youngs Modulus of conductor E N/m
4.16 Moment of Inertia of main conductor J m^4
e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 4 of 17 3VYN291401A-R0
V Formulae Used
5.1 Peak value of short circuit current (Ip3) =I"k3 x k x Sqr(2) Amps
5.2
Electro magnetic force between
conductors (Fm) = x Sqr(3) x ( Ip3) x l kg
2 x 2 p x 9.81 x am
5.3 Electro dynamic force on busbar (Fd) = Vf x Vr x a x Fm kg
5.4 Natural Frequency of the tube (fc) = x Sqr ( E J /m') Hz
l
5.5 Calculation of V
F
As per IEC 865-I (Page-107)
fc/f
V
F
<0.04 0.232+3.52*EXP(-1.45*k)+0.166*LOG10(fc/f)
0.04......0.8 MAX(0.839+3.52*EXP(-1.45*k)+0.6*LOG10(fc/f),2.38+6*LOG10(fc/f))
0.8.......1.2 1.8
1.2.........1.6 1.23+7.2*LOG10(fc/f)
1.6.......2.4 2.7
2.4......2.74 8.59-15.5*LOG10(fc/f)
2.74......3.0 8.59-15.5*LOG10(fc/f)
3.0........6.0 1.5-0.646*LOG(fc/f)
>6 1
5.6 Calculation of V
r
fc/f V
r
<=0.05 1.8
>0.05 and <1 1-0.615Log(fc/f)
>=1 1
e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 5 of 17 3VYN291401A-R0
VI Support Arrangement
Refer Figure 1
6.1 Equipment Dimension (Terminal to Terminal) in m 4.8 m
Left Right
6.2 Support Span in Metre (L) = 9 10.5
6.3 Equipment Dimension (Terminal to Terminal) in m 4.821 0
6.4 Support type for Equipment FIXED SIMPLE
6.5 Support type for other equipment SIMPLE FIXED
VII Calculation
7.1 Peak short circuit current Ip3 = 102389 A
Left Right
7.2 Factor a at Support A 0.625 0.375
7.3 Factor a at Support B 0.375 0.625
7.4 Factor b 0.73 0.73
7.5 Factor 2.45 2.45
7.6 Effective Distance (mts) l = 4.19 8.1
7.7 Electromagnetic forces between conductors Fm = 110.79 214.18
7.8 Natural frequency of the Tube (Hz) fc = 25.824 6.9099
7.9 Ratio fc / f = 0.5165 0.1382
7.10 Ratio of dynamic & Static force on supports VF = 1.0128 0.6692
7.11 Ratio of stress for main conductor with &
without 3 phase Auto reclosing VR = 1.1765 1.5286
7.12 Factor a 0.625 0.375
7.13 Dynamic force (Bending Force) (kg) Fd = 82.505 82.164
7.14 Total Dynamic force due to Left & Right spans = 164.67 kg
TYPICAL SHORT CIRCUIT FORCE CALCULATION FOR 400kV
ISOLATOR
e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 6 of 17 3VYN291401A-R0
e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 7 of 17 3VYN291401A-R0
VI Support Arrangement
Refer Figure 2
6.1 Equipment Dimension (Terminal to Terminal) in m 4.821 m
Left Right
6.2 Support Span in Metre (L) = 12 9
6.3 Equipment Dimension (Terminal to Terminal) in m 0.55 4.8
6.4 Support type for Equipment SIMPLE SIMPLE
6.5 Support type for other equipment FIXED FIXED
VII Calculation
7.1 Peak short circuit current Ip3 = 102389 A
Left Right
7.2 Factor a at Support A 0.375 0.375
7.3 Factor a at Support B 0.625 0.625
7.4 Factor b 0.73 0.73
7.5 Factor 2.45 2.45
7.6 Effective Distance (mts) l = 9.315 4.189
7.7 Electromagnetic forces between conductors Fm = 246.31 110.77
7.8 Natural frequency of the Tube (Hz) fc = 5.2249 25.836
7.9 Ratio fc / f = 0.1045 0.5167
7.10 Ratio of dynamic & Static force on supports VF = 0.5964 1.0129
7.11 Ratio of stress for main conductor with & without
3 phase Auto reclosing
VR = 1.6032 1.1763
7.12 Factor a 0.375 0.375
7.13 Dynamic force (Bending Force) Fd = 88.317 49.492
7.14 Total Dynamic force due to Left & Right spans = 137.81 kg
TYPICAL SHORT CIRCUIT FORCE CALCULATION FOR 400kV
CIRCUIT BREAKER
e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 8 of 17 3VYN291401A-R0
e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 9 of 17 3VYN291401A-R0
VI Support Arrangement
Refer Figure 3
6.1 Equipment Dimension (Terminal to Terminal) in m 0.55 m
Left Right
6.2 Support Span in Metre (L) = 12 5.5
6.3 Equipment Dimension (Terminal to Terminal) in m 4.82 4.8
6.4 Support type for Equipment FIXED SIMPLE
6.5 Support type for other equipment SIMPLE FIXED
VII Calculation
7.1 Peak short circuit current Ip3 = 102389 A
Left Right
7.2 Factor a at Support A 0.625 0.375
7.3 Factor a at Support B 0.375 0.625
7.4 Factor b 0.73 0.73
7.5 Factor 2.45 2.45
7.6 Effective Distance (mts) l = 9.318 2.827
7.7 Electromagnetic forces between conductors Fm = 246.39 74.7526
7.8 Natural frequency of the Tube (Hz) fc = 5.2215 56.7273
7.9 Ratio fc / f = 0.1044 1.13455
7.10 Ratio of dynamic & Static force on supports VF = 0.5962 1.8
7.11 Ratio of stress for main conductor with & without
3 phase Auto reclosing
VR = 1.6034 1
7.12 Factor a 0.625 0.375
7.13 Dynamic force (Bending Force) Fd = 147.22 50.458
7.14 Total Dynamic force due to Left & Right spans = 197.67 kg
TYPICAL SHORT CIRCUIT FORCE CALCULATION FOR 400kV
CURRENT TRANSFORMER
e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 10 of 17 3VYN291401A-R0
e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 11 of 17 3VYN291401A-R0
VI Support Arrangement
Refer Figure 4
6.1 Equipment Dimension (Terminal to Terminal) in m 0 m
Left Right
6.2 Support Span in Metre (L) = 10.5 0
6.3 Equipment Dimension (Terminal to Terminal) in m 4.8 0
6.4 Support type for Equipment FIXED
6.5 Support type for other equipment SIMPLE
VII Calculation
7.1 Peak short circuit current Ip3 = 102389 A
Left Right
7.2 Factor a at Support A 0.625 0
7.3 Factor a at Support B 0.375 0
7.4 Factor b 0.73 0
7.5 Factor 2.45 0
7.6 Effective Distance (mts) l = 8.1 0
7.7 Electromagnetic forces between conductors Fm = 214.18 0
7.8 Natural frequency of the Tube (Hz) fc = 6.9099 0
7.9 Ratio fc / f = 0.1382 0
7.10 Ratio of dynamic & Static force on supports VF = 0.6692 0
7.11 Ratio of stress for main conductor with & without
3 phase Auto reclosing
VR
= 1.529
7.12 Factor a 0.625 0
7.13 Dynamic force (Bending Force) Fd = 136.94 0
7.14 Total Dynamic force due to Left span = 136.94 kg
TYPICAL SHORT CIRCUIT FORCE CALCULATION FOR 400kV
BUS POST INSULATOR
e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 12 of 17 3VYN291401A-R0
e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 13 of 17 3VYN291401A-R0
S
l
.
N
o
.
T
o
t
a
l



F
d

(
K
g
)
L
e
f
t
R
i
g
h
t
L
e
f
t
R
i
g
h
t
L
e
f
t
R
i
g
h
t
L
e
f
t
R
i
g
h
t
L
e
f
t
R
i
g
h
t
L
e
f
t
R
i
g
h
t
L
e
f
t
R
i
g
h
t
L
e
f
t
R
i
g
h
t
L
e
f
t
R
i
g
h
t
A
4
0
0
k
V

I
s
o
l
a
t
o
r
F
I
X
E
D
S
I
M
P
L
E
S
I
M
P
L
E
F
I
X
E
D
9
1
0
.
5
4
.
1
9
8
.
1
1
1
0
.
8
2
1
4
.
1
8
2
5
.
8
6
.
9
1
1
.
0
1
2
8
0
.
6
6
9
2
1
.
1
7
6
1
.
5
2
9
8
2
.
5
0
5
8
2
.
1
6
3
8
1
6
4
.
6
6
8
8
B
4
0
0
k
V

C
i
r
c
u
i
t

B
r
e
a
k
e
r
S
I
M
P
L
E
S
I
M
P
L
E
F
I
X
E
D
F
I
X
E
D
1
2
9
9
.
3
1
5
4
.
1
8
9
2
4
6
.
3
1
1
0
.
7
7
5
.
2
2
2
5
.
8
4
0
.
5
9
6
4
1
.
0
1
2
9
1
.
6
0
3
1
.
1
7
6
8
8
.
3
1
7
4
9
.
4
9
1
9
1
3
7
.
8
0
9
C
4
0
0
k
V

C
u
r
r
e
n
t

T
r
a
n
s
f
o
r
m
e
r
F
I
X
E
D
S
I
M
P
L
E
S
I
M
P
L
E
F
I
X
E
D
1
2
5
.
5
9
.
3
1
8
2
.
8
2
7
2
4
6
.
4
7
4
.
7
5
3
5
.
2
2
5
6
.
7
3
0
.
5
9
6
2
1
.
8
1
.
6
0
3
1
1
4
7
.
2
2
5
0
.
4
5
8
1
9
7
.
6
7
4
9
D
4
0
0
k
V

B
u
s

P
o
s
t

I
n
s
u
l
a
t
o
r
F
I
X
E
D
0
S
I
M
P
L
E
0
1
0
.
5
0
8
.
1
0
2
1
4
.
2
0
6
.
9
1
0
0
.
6
6
9
2
0
1
.
5
2
9
0
1
3
6
.
9
4
0
1
3
6
.
9
3
9
6
T
A
B
L
E

1
.

B
e
n
d
i
n
g

F
o
r
c
e

o
n

4
0
0
k
V

E
q
u
i
p
m
e
n
t
s
E
q
u
i
p
m
e
n
t

S
u
p
p
o
r
t
O
t
h
e
r

E
q
u
i
p
m
e
n
t

S
u
p
p
o
r
t
F
d

(
K
g
)
D
i
s
t
a
n
c
e

b
e
t
w
e
e
n

E
q
p
t
s
(
m
)
E
f
f
e
c
t
i
v
e

L
e
n
g
t
h
(
m
)
F
m

(
K
g
)
f
c

(
H
z
)
V
r
V
F







e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 14 of 17 3VYN291401A-R0
1. FORMULAE USED
Electro magnetic force on flexible main conductors in 3 Phase System is given by
(F') =Mo * 0.75 * (ik3) /(2 * pi * am) (As per IEC-865-1 Page No. 39)
2. LEGEND
F' =Electro magnetic force in N/m
ik3 =Initial symmetrical short circuit current in amps
Mo =Absolute permeability of vacuum , 4 (pi) x 10^(-7) in H/m
am =Effective distance between main conductor (phase spacing) in metres
3. SYSTEM DATA
System short circuit current (ik3) in Amps = 40000 (i.e. 40 kA)
Phase spacing (am) in metres = 7
4. CALCULATION
Refer Figure No.5
Electromagnetic force on conductor (TWIN Moose ACSR)
(Short circuit force) (F') = 34.29 N/m
= 3.5 Kg/m
Force on CVT (15.13m span) = 52.96 Kg
Force on LA (14.75m span) = 51.63 Kg
400kV SHREE CEMENT S/S
CALCULATION OF SHORT CIRCUIT FORCE FOR TWIN MOOSE ACSR IN
400kV SYSTEM
e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 15 of 17 3VYN291401A-R0
e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 16 of 17 3VYN291401A-R0
Summary :
PART A Calculation of Short Circuit force on Equipments with 4'' IPS Al. Tube
1.
Force for 400kV = 164.67 kg
2.
Force for 400kV = 137.81 kg
3. Current Transformer
Force for 400kV = 197.67 kg
4. Bus Post Insulator
Force for 400kV = 136.94 kg
PART B Calculation of Short Circuit force on Equipments with TWIN MOOSE ACSR
1. CVT
Force for 400kV = 52.96 kg
1. LA
Force for 400kV = 51.63 kg
400kV SHREE CEMENT S/S
Isolator
Circuit Breaker
e-BOP:ABB LIMITED - Faridabad CUSTOMER: (2x150 MW) M/S SHREE CEMENT LTD.,
Short Circuit Force For Equipment Interconnection Page 17 of 17 3VYN291401A-R0

Você também pode gostar