Escolar Documentos
Profissional Documentos
Cultura Documentos
1
= (Rs/SR) [ 1 /(1 + (Rs/X))]
22 IEC 60287
Type of insulation Temperature limit
a, d
Polyvinyl chloride (PVC) (Thermo-plastics) 70C at the conductor
Cross-lined polyethylene (XLPE) and ethylene
propylene rubber (EPR) (Thermosetting)
90C at the conductor
b
Mineral (PVC covered or bare exposed to touch) 70C at the sheath
Mineral (bare not exposed to touch and not in contact
with combustible material)
105C at the sheath
b, c
Table 12 Temperature limit of cables (Table B52.1 of 60364-5-52)
23 VOLTAGE STANDARD
23
r d
August 2014
IEC 60287 Electric cables Calculation of the current rating
Part 1 Current rating equations (100 % load factor) and calculation of
losses:
Section 1: General;
Section 2: Sheath eddy current loss factors for two circuits in flat
formation;
Section 3: Current sharing between parallel single-core cables and -
calculation of circulating current losses;
Part 2 Thermal resistance:
Section 1: Calculation of thermal resistance;
Section 2: A method for calculating reduction factors for groups of cables
in free air, protected from solar radiation
Part 3 Sections on operating conditions:
Section 1: Reference operating conditions and selection of cable type;
Section 2: Economic optimization of power cable size;
Section 3: Cables crossing external heat sources
23
r d
August 2014
23
r d
August 2014
25 EXAMPLE 1
Circuit 1 Lighting 8 nos 80W each
Circuit 2 2x13A socket outlet in radial circuit
Circuit 3 1x15A water heater
Circuit 4 1x15A, air cool split unit air conditioning
Circuit 5 4x13A socket outlet in ring circuit
Circuit 6 6x13A socket outlet in ring circuit
Example 1, domestic wiring diagram with typical circuits
23
r d
August 2014
26 EXAMPLE 1
Circuit 1 Lighting 8 nos 80W each
Circuit 2 2x13A socket outlet in radial circuit
Circuit 3 1x15A water heater
Circuit 4 1x15A, air cool split unit air conditioning
Circuit 5 4x13A socket outlet in ring circuit
Circuit 6 6x13A socket outlet in ring circuit
Example 1, domestic wiring diagram with typical circuits
23
r d
August 2014
27 EXAMPLE 1
N
o
Fuse rating Conductor
(mm)
Comments
1 6 Amps 1.5 mm Lighting circuit (8 nos x 80W). Clause 524,
Table 52.2 of 60364-5-52 requires minimum
cable size at 1.5mm.
2 15 Amps 2.5 mm 2x13A socket outlet in radial circuit (2x300W)
3 20 Amps 4 mm 1x15A socket outlet for water heater
(2,000W)
4 15 Amps 2.5 mm 1x15A socket outlet for (1x750W)
5 30 Amps 2.5 mm 4x13A socket outlet in ring circuit (4x300W)
6 30 Amps 4 mm 6x13A socket outlet in ring circuit (6x300W)
7 60 Amps 25 mm Main feeder cables to consumer unit (total
load = 6,690W (38A).
Table 13A; Example 1, schedule of circuits
23
r d
August 2014
28 EXAMPLE 1
Load Estimate
Select Earthing
System
Determine
Installation
Method
Select & Size
Wiring / Cables
Table 13A
(previous slide)
TN-S
PVC single core
in conduit;
method A1
IEC60364-5-52,
method A1; Table
B52.2
23
r d
August 2014
29 EXAMPLE 1
Cct
No
Load/ current
(3)
I
B
(A)
MCB (type B) Cable Comments
Nom.
rating I
N
Effective
trip I
2
(1)
Size mm I
z
(A)
(2)
230V single phase
1 8x80W ~ 3.3A 6A 9A 1.5 14.5 Lighting circuit
2 2x300W ~ 3.3A 15A 22.5A 2.5 19.5 Socket outlet radial
circuit
3 2000W ~ 9.7A 20A 30A 4 26 Water heater
4 750W ~ 3.8A 15A 22.5A 2.5 19.5 15A outlet with air
conditioning unit
5 4x300W ~ 6.5A 30A 45A 2.5 2x19.5 Ring circuit subject to
national conditions.
6 6x300W ~ 9.8A 30A 45A 4 2x26
7 6,690W ~ 36A 60A 90A 25 80 Main power intake
(1) Assume effective trip current to be 1.5 x I
N
.
(2) Cable installation assumes PVC insulated cables, 2 single core in conduit embedded in walls.
Current capacity referenced from IEC 60364, table B52.2, installation method A1.
(3) Load estimate are presented here without consideration of diversity as an illustration only.
The subject of load diversity can be a detail subject which may require national statistics on
average usage of electrical appliances.
Check: I
B
< I
N
< I
Z
I
2
< 1.45 x I
Z
23
r d
August 2014
23
r d
August 2014
31 EXAMPLE 2 LARGE CABLES
C
a
s
e
Installation Config-
uration
(1)
; XLPE cable
Conductor
size
(1)
(mm)
Current capacity
of cables
Group
rating factor
(2) (3)
Corrected
current
capacity
Multi core cable (B52.12, column 3, method E) B52.20
(a) 3 x 4 core, 1 cable
diameter apart
3x300mm / 4
core
3x621A = 1,853A 1 1,853A
(b) 3 x 4 core, 1 cable
diameter apart
2x240mm / 4
core
3x538A = 1,614A 1 1,614A
Single core cables in trefoil (B52.12, column 5, method F) B52.21
(a) Trefoil, 2 circuit @ 2 cable
diameter apart on 1 ladder
7x400mm / 1
core
(5)
2x823A = 1,646A 1 1,646A
(b) Trefoil, 3 circuit touching 11x240mm / 1
core
(5)
3x607A = 1,821A 0.82
(4)
1,493A
(b) Trefoil, 3 circuit @ 2 cable
diameter apart on 1 ladder
11x240mm / 1
core
(5)
3x607A = 1,821A 1
)
1,821A
Single core cables in flat formation (B52.12, column 6 or 7,
method F or G)
B52.21
(a) Cable touching (method
F), 2 circuits, 1 ladder.
7x400mm / 1
core
(5)
2x868A = 1,736A 0.97 1,684A
(b) 1 cable diameter apart,
(method G), 2 circuits, 1
ladder.
7x300mm / 1
core
(5)
2x902A = 1,804A 0.97 1,750A
(b) 1 cable diameter apart,
(method G), 2 circuits, 1
ladder.
7x240mm / 1
core
(5)
2x781A = 1,562A 0.97 1,515A
23
r d
August 2014
32 EXAMPLE 2 LARGE CABLES
Notes:
(1) Installation configuration and conductor sizes are based on table B52.12 for
XLPE insulated copper cables.
(2) Group rating factor where only 1 cable ladder is used is referenced from table
B52.17 row 5. Finer graduation in group factor can be obtained from tables
B52.20 (for multi core cables and B52.21 (for single core cables).
(3) In all cases, we assume only one cable ladder used.
(4) Group rating for case 2(b). Table B52.21 for single core cables on ladder in
trefoil only considers case of cable-circuits laid 2 D
e
apart. To consider case of
cable touching, table B52.17 is referred for reduction factor.
(5) For single core cables, we assume neutrals to be sizes. The odd cable is
therefore used as neutral e.g. 11 core means 3x1 core for each line conductor
and 2x1 core for neutral. In some national jurisdiction, size neutral may not
be allowed.
(6) Ambient temperature is assumed to be at 30C, for temperature correction
factor at 1 (from table B52.14).
Table 14A; Example 2, schedule of cable sizes and configurations
23
r d
August 2014
33 EXAMPLE 2 LARGE CABLES
23
r d
August 2014
34 EXAMPLE 2 LARGE CABLES
23
r d
August 2014
35 EXAMPLE 2 LARGE CABLES
Cable Sizing For Safe Power System Based
o n I E C S t a n d a r d s
I r . H. P. Looi ( me k t r i c o n @g ma i l . c o m)
B. Eng ( Hons ) , FI EM, J ur ut er a Gas
Cable Sizing Fundamentals and
El e c t r i c a l LV St a n d a r d
Ar mada Hot el , Pet al i ng J ay a
23
r d
Augus t 2014
P a r t 2 C a b l e S i z i n g
ThankYou f or your At t ent i on !