Você está na página 1de 16

1-16 broch telecom eng

6-02-2013

10:36

Pagina 1

TELECOMRANGE

Units for mobile telecommunication


applications, split versions, indoor & outdoor
packaged units, range from 1,5 20 kW, with
Free Cooling and the new FULL INVERTER DC
Brushless versions in R410a.

1-16 broch telecom eng

6-02-2013

10:36

Pagina 2

CLIMAVENETA

TELECOMRANGE

OPERATING RELIABILITY AND CONTINUITY


Constructional rationality plus the proven high quality of
the components ensure that Climavenetas units offer:
- Continuous operation
(24 hours a day, 365 days a year)
- Design life of over 10 years.
- MTBF and MTTR values at the top of their category.

HIGH SENSIBLE COOLING CAPACITY


No latent cooling required.
Unmanned premises with almost
nil latent heat value.
Required S.H.R. 95%

Since the technological rooms are unmanned, the


latent heat values remain almost zero. Thus, the
requested S.H.R. values (Sensible and Total Cooling
Capacity Ratio) are 95%, compared to typical S.H.R
values around 60% in the manned premises.

Manned premises with latent


heat value.
Required S.H.R. 60%

95%

BLACK-OUT MANAGEMENT
UPS connections system (24/48V DC)

60%

Shelter Inside Temperature

Black-Out - Power Loss

System On

For the double power supply versions (UPS, 48V DC),


instant activation of the FreeCooling function in the
event of a blackout.

70

Without Free Cooling


60

50

40

With Free Cooling


30

20

15'

30'

45'

Time

2 l 3

TELECOMRANGE

1h

15'

30'

45'

2h

1-16 broch telecom eng

6-02-2013

10:36

Pagina 3

MICROPROCESSOR CONTROL
Stand-By and Alarm management
The microprocessor allows:
- easy use by the operator
- management of the unit in stand-by
- automatic rotation on a time basis
- alarm rotation
- alarm management and transmission
- LAN management between connected units
- connection to supervisor systems (SMS)
- double power supply management
- multi-language management
- test function management

60

MINIMUM SOUND EMISSION


50

40
decibel dB

The sound emission reduction of air conditioning units


is one of the greatest needs of telephone units in urban
areas.
Climaveneta has therefore made a new range of highefficiency air conditioners featured by a strong sound
emission reduction:

Measurement on outside with evaporating fan only in Free Cooling.


Measurement on outside during recirculation.

30

20

10

0
-50

Hz

100

200

500

1K

2K

5K

10K

20K(L) (A)

frequency
80

Others/Competitors
Climaveneta

70

60
decibel dB

 Sound proofing delivery plenum


 Antivibrating feet
 Compressor inside a sound proofing box
with lead
 Sound proofing recirculating fans cap
 Fan speed condenser regulator
 Autotransformer to reduce vibration

50

40

30
25
6 kW

9 kW

HED + HC

15 kW

AT

6 kW

9 kW

MED

15 kW

6 kW

9 kW

MID

15 kW

1-16 broch telecom eng

6-02-2013

10:36

Pagina 4

CLIMAVENETA

TELECOMRANGE

TELEPHONE EXCHANGES, SHELTERS, CABINETS:


THE MODERN APPLICATIONS ARE
CHARACTERIZED BY SPECIFIC NEEDS, WHICH
REQUIRE THE MOST SUITABLE AND
TECHNOLOGICALLY ADVANCED SOLUTIONS.
The constant attention to the market in order to closely monitor and
anticipate the needs and tendencies of the consumer has lead to the
creation of Telecom Range.
This new range of high-efficiency solutions, such as split air
conditioners, indoor and outdoor packaged units are available in Free
Cooling versions with capacities from 1,5 to 20 kW.

4 l 5

TELECOMRANGE

1-16 broch telecom eng

6-02-2013

10:37

Pagina 5

The latest range of products combines Climavenetas


experience in research and development, with the
quality and reliability of its products.
This strictly depends on the constant improvement of
the technology. Climaveneta has also an extensive sales
network and a series of high standard after sales
services which include: in-house technicians to provide
back-up for the distribution network, training for
external technicians, informative multimedia material,
quality support for sales outlets and a user information
service to guarantee quality.







End-of-line testing on all units


Dedicated project team for telephony products
R&D and up of 200 technicians
Customized solutions to customer specifications
Accreditation service for direct orders
Certification of unit specifications in the 8
Climaveneta in-house climatic test chambers
 Training and technological testing on site

HED-HCAT

00110061

pg. 8

MED

0010091

pg. 12

Split-Air Conditioners Cooling capacity from 4,9 to 15,7 kW


FREE COOLING

Packaged Air Conditioners Cooling capacity from 1,5 to 20 kW


FREE COOLING

MID

LED

0010061

pg. 10

Packaged Air Conditioners Cooling capacity from 1,5 to 14,8 kW


FREE COOLING

0010E0015E

pg. 14

Packaged Air Conditioners Cooling capacity from 2,5 to 5,7 kW


FREE COOLING

1-16 broch telecom eng

6-02-2013

10:37

Pagina 6

CLIMAVENETA

TELECOMRANGE

CLIMAVENETA TELECOM RANGE IS THE RESULT OF A RESEARCH AND


DEVELOPMENT PROJECT AMONG DIFFERENT TELECOMMUNICATION
COMPANIES IN ORDER TO OFFER A NO-COMPROMISE SOLUTION.
 Low operational costs and Low
maintenance costs
 Free Cooling with the maximum level of
energy saving
 Sound emission reduction thanks to low
noise versions
 Continuous operation
(24 hours a day, 365 days a year)
 Very high sensible cooling
 Precision control and reliability
 Microprocessor control (stand-by and alarm
management)
 Back-up system and UPS system (24/48 VDC)
 Design life of over 10 years

6 l 7

TELECOMRANGE

1-16 broch telecom eng

6-02-2013

10:37

Pagina 7

INVERTER TECHNOLOGY
The inverter driven compressor, through variable frequency,
modulates the power capacity provided, optimizing the
performances at part load and increasing efficiency.
A larger capacity can be reached at full load, thus ensuring
that the required temperature will be reached in a shorter
time. Afterwards temperature variations can be easily
controlled with minimized energy consumption because
once the set is reached, the compressor works at part load,
reducing energy consumption and effectively maintaining the
desired conditions.

These units make use of electronic thermostatic valves and


the new generation of EC fans.
Both solutions allow to perfectly adapt the units
performance to the real requirements of the building even at
part load, which represent more than 75% of the operating
time of the system. This ensures an energy saving up to
50% higher than solutions based on traditional ON/OFF
compressors.

LOW OPERATIONAL COSTS AND


MAINTENANCE COSTS
Choosing the correct, long lasting air conditioning systems
for TLC applications should combine low initial investment
and low operational and maintenance costs.
For this reason the modern FULL INVERTER units deliver
the best costs and benefits ratios, highlighting the meaning
of the TCO (Total Cost of Ownership).
As a consequence, payback time is 2 years compared to
NON FULL INVERTER solutions where payback per unit of
about 3000 units comes only after 10 years.

50% SAVING:
FREE COOLING + INVERTER
It is well known that energy savings are guaranteed with
FREE COOLING systems. Modern FULL INVERTER units
with FREECOOLING combine the technology of modulation
cooling resulting in a 35% energy saving.

Annual Energy Consumption


In case of low Hz Operation

100%
Max 70%

In this respect the new Climaveneta TLC range represents


the ultimate solution in air conditioning for the MOBILE
TELEPHONY, thanks to the most updated compressors DC
Inverter Brushless in all the units.

55%
30%
Constant speed

AC Inverter

DC Inverter

1-16 broch telecom eng

6-02-2013

10:37

Pagina 8

TELECOMRANGE

HED-HCAT

00110061

SPLIT AIR CONDITIONERS FOR TELECOMMUNICATION SHELTERS


FREE COOLING

UNIT DESCRIPTION

FEATURES

The split air conditioners for telecommunication shelters


offer cooling capacity from 4,9 to 15,7 kW.
They are direct expansion systems consisting of motoroperated condensers HCAT 00110061 combined with
indoor units HED 00110061 FC.
Suitable for horizontal installation, they are fitted with
external panels in electrogalvanized steel sheet painted by
cataphoretic process.
The units can be fitted with a Free Cooling damper, which
offers 30% energy savings compared to standard systems.
The evaporating section fan works on a direct current at 48
Volt to ensure operation in an emergency.
Climaveneta units are also made to ensure a standard level
of operation even under extreme environmental conditions
with temperatures up to +48C.

 Structure and paneling in galvanized cataphoretic coated steel for


maximum resistance to rust.
 The reliability and functionality of the compressor and all other
components are guaranteed by leading companies in the telecoms sector.
 External air intake for Free Cooling units with opening from 0 to 100%
(optional).
 Contacts for alarms and working state signal plots.
 Universal terminal board for outside complete control of the PLC unity.
 Adjustable fan speed (optional).
 Condensing control for lower noise levels.
 Safety pressure switches.
 Condensing coil protection grills.
 Availability of all accessories required for easy and correct installation,
and for a complete and efficient air treatment system.
 Electric heating (optional).
 Remote terminal per standard provide, on board version (optional).
 Serial cards for BMS interconnection (optional).
 Humidity sensor (optional).
 Condensate draining pump (optional).

SPLIT

Free Cooling

8 l 9

TELECOMRANGE

Mechanical

1-16 broch telecom eng

6-02-2013

10:37

Pagina 9

ON/OFF VERSION
HED HCAT
Power supply

V/Ph/Hz

0011

0021

0031

0041

0051

0056

0061

230/1/50

230/1/50

400/3N/50

400/3N/50

400/3N/50

400/3N/50

Total cooling capacity

kW

4,94

6,36

8,43

9,71

10,63

14,28

15,77

Sensible cooling capacity

kW

4,94

5,65

6,77

9,17

9,53

12,47

13,76

Compressor power input

kW

1,18

1,62

2,27

2,37

2,72

3,64

4,1

Evaporator air flow

m3/h

1450

1450

1600

2450

2450

3200

3200

Freecooling air flow

m3/h

1450

1450

1600

2450

2450

3200

3200

Evaporator fan AC power input

kW

0,24

0,24

0,29

0,32

0,32

0,48

0,48

Evaporator fan DC power input

kW

0,2

0,2

0,24

0,32

0,32

0,48

0,48

m3/h

2500

2500

2500

4000

4000

4900

4900

Condenser fan AC power input

kW

0,16

0,16

0,16

0,14

0,14

0,32

0,32

Max ambient temperature

+48

+48

+48

+48

+48

+48

+48

Min ambient temperature

-25

-25

-25

-25

-25

-25

-25

dB(A)

52

53

56

56

56

58

58

Condenser max air flow

Outdoor sound pressure level at 1mt


Design conditions

Indoor=27- 45%UR Outdoor=35C

DIMENSIONS
HED

0011

0021

0031

0041

0051

0056

0061

Width

mm

930

930

930

1050

1050

1050

1050

Depth

mm

311

311

311

406

406

406

406

Height

mm

1500

1500

1500

1524

1524

1524

1524

HCAT

0011

0021

0031

0041

0051

0056

0061

Width

mm

900

900

900

900

900

900

900

Depth

mm

370

370

370

370

370

370

370

Height

mm

740

740

740

990

990

1240

1240

INVERTER VERSION
HED HCAT
Power supply

V/Ph/Hz

0031

0051

0061

230/1/50

230/1/50

400/3N/50

Min

Max

Min

Max

Min

Total cooling capacity

kW

4,34

9,73

4,84

12,61

6,97

17,3

Sensible cooling capacity

kW

4,34

7,29

4,84

11,02

6,97

15,64

Compressor power input

Max

kW

0,75

2,38

0,78

3,18

1,1

4,23

Evaporator air flow

m3/h

1450

1450

1600

1600

2000

3900

Freecooling air flow

m3/h

1450

1450

1600

1600

2000

3900

Evaporator fan AC power input

kW

0,15

0,29

0,18

0,36

0,26

0,52

Evaporator fan DC power input

kW

0,12

0,24

0,16

0,32

0,2

0,4

m3/h

2500

2500

2500

2500

8640

8640

Condenser fan AC power input

kW

0,16

0,16

0,32

0,32

0,45

0,45

Max ambient temperature

+48

+48

+48

+48

+48

+48

Min ambient temperature

-25

-25

-25

-25

-25

Condenser max air flow

Outdoor sound pressure level at 1mt

dB(A)

Design conditions

-25

56

56

58

Indoor=27- 45%UR Outdoor=35C

Indoor=27- 45%UR Outdoor=35C

Indoor=27- 45%UR Outdoor=35C

DIMENSIONS
HED

0031

0051

0061

Width

mm

930

930

930

930

1350

Depth

mm

311

311

406

406

406

406

Height

mm

1500

1500

1500

1500

1524

1524

Width

mm

900

900

900

900

1700

Depth

mm

420

420

420

420

570

570

Height

mm

1290

1290

1290

1290

1470

1470

HCAT

0031

Note
* Available in double configuration 230/1/50 or 400/3N/50

0051

1350

0061
1700

1-16 broch telecom eng

6-02-2013

10:37

Pagina 10

TELECOMRANGE

MID

0010061

PACKAGED AIR CONDITIONERS FOR TELECOMMUNICATION SHELTERS


FREE COOLING

UNIT DESCRIPTION

FEATURES

The packaged air conditioners for telecommunication shelters


offer cooling capacity from 1,5 to 14,8 kW. They are direct
expansion packaged systems for indoor installation, which
are fitted with external panels in electrogalvanized steel sheet
painted by cataphoretic process.
The units can be fitted with a Free Cooling damper (optional),
which offers 30% energy savings compared to standard
systems. The evaporating section fan (optional) works on a
direct current at 48 Volt to ensure operation in an emergency.
Climaveneta units are also made to ensure a standard level of
operation even under extreme environmental conditions with
temperatures up to +48C.
Available in super silent version.

 Structure and paneling in galvanized cataphoretic coated steel for maximum


resistance to rust (upon request available in peraluman panels).
 The reliability and functionality of the compressor and all other components
are guaranteed by leading companies in the telecoms sector.
 External air intake for Free Cooling units with opening from 0 to 100% (optional).
 Universal terminal board for outside and complete control of the PLC unity.
 Contacts for alarms and working state signal plots.
 Double filter (a pre-filter for external air and one for internal one).
 Adjustable fan speed(optional).
 Condensing control for lower noise levels.
 Safety pressure switches.
 Differential air pressure switch for dirty filters or faulty fans.
 Available with 48 VD/C fans.
 Availability of all accessories required for easy and correct installation, for a
complete and efficient air treatment system.
 Customer Assistance.
 Electric heating (optional).
 On board terminal as standard provide, remote terminal version (optional).
 Serial cards for BMS interconnection (optional).
 Humidity sensor (optional).
 Condensate draining pump (optional).

INDOOR

Free Cooling

Mechanical

Upflow
10 l 11

TELECOMRANGE

Free Cooling

Dowflow

Mechanical

1-16 broch telecom eng

6-02-2013

10:37

Pagina 11

ON/OFF VERSION
MID
Power supply

V/Ph/Hz

001

003

004

0011

0021

0031

0041

0051

0056

0061

230/1/50

230/1/50

230/1/50

230/1/50

230/1/50

400/3N/50

400/3N/50

400/3N/50

400/3N/50

Total cooling capacity

kW

1,95

2,91

3,45

4,94

6,09

8,14

9,52

10,64

13,77

14,82

Sensible cooling capacity

kW

1,42

2,67

2,88

4,94

5,49

6,72

8,64

9,07

12,46

12,93

Compressor power input

kW

0,6

0,81

0,98

1,18

1,69

2,33

2,35

2,78

3,51

4,09

Evaporator air flow

m3/h

300

700

700

1450

1450

1600

2200

2200

3200

3200

Freecooling air flow

m3/h

300

700

700

1450

1450

1600

2200

2200

3200

3200

Evaporator fan AC power input

kW

0,04

0,115

0,115

0,2

0,2

0,24

0,22

0,22

0,28

0,28

Evaporator fan DC power input

kW

0,04

0,12

0,12

0,2

0,2

0,24

0,32

0,32

0,4

0,4

m3/h

500

1100

1100

2600

2600

2600

3700

3700

4500

4500

Condenser fan AC power input

kW

0,12

0,155

0,155

0,42

0,42

0,42

0,45

0,45

0,9

0,9

Max ambient temperature

48

48

48

+48

+48

+48

+48

+48

+48

+48

-25

-25

-25

-25

-25

-25

-25

-25

-25

-25

dB(A)

49

52

52

53

53

54

56

56

60

61

Condenser max air flow

Min ambient temperature


Outdoor sound pressure level at 1mt
Design conditions

Indoor=27- 45%UR Outdoor=35C

DIMENSIONS
MID

001

003

004

0011

0021

0031

0041

0051

0056

0061

Width

mm

394

505

505

650

650

650

895

895

895

895

Depth

mm

250

398

398

650

650

650

750

750

750

750

Height

mm

900

1265

1265

2075

2075

2075

2050

2050

2050

2050

INVERTER VERSION
MID
Power supply

V/Ph/Hz

0031

0051

0061

230/1/50

230/1/50

400/3N/50

Min

Max

Min

Max

Min

Max

Total cooling capacity

kW

4,34

9,53

4,84

12,25

6,58

15,05

Sensible cooling capacity

kW

4,34

7,09

4,84

10,68

6,26

12,81

Compressor power input

kW

0,75

2,37

0,78

3,18

1,1

4,66

Evaporator air flow

m3/h

800

1600

1600

3200

1600

3200

Freecooling air flow

3200

m3/h

800

1600

1600

3200

1600

Evaporator fan AC power input

kW

0,14

0,24

0,22

0,4

0,22

0,4

Evaporator fan DC power input

kW

0,12

0,24

0,13

0,26

0,13

0,26

m3/h

2600

2600

4500

4500

4500

4500

Condenser fan AC power input

kW

0,42

0,42

0,45

0,45

0,45

0,45

Max ambient temperature

+48

+48

+48

+48

+48

+48

Min ambient temperature

-25

-25

-25

-25

-25

Condenser max air flow

Outdoor sound pressure level at 1mt

dB(A)

31

Design conditions

51

-25
61

Indoor=27- 45%UR Outdoor=35C

DIMENSIONS
MID

0031

0051

0061

Width

mm

650

895

895

Depth

mm

650

750

750

Height

mm

2075

2050

2050

Note
* Available in double configuration 230/1/50 or 400/3N/50

1-16 broch telecom eng

6-02-2013

10:37

Pagina 12

TELECOMRANGE

MED

0010091

PACKAGED AIR CONDITIONERS FOR TELECOMMUNICATION SHELTERS


FREE COOLING

UNIT DESCRIPTION

FEATURES

The packaged air conditioners for telecommunication shelters


offer cooling capacity from 1,5 to 20 kW. They are direct
expansion packaged systems for outdoor installation.
They are fitted with external paneling in electrogalvanized steel
sheet painted by cataphoretic process. The units can be fitted
with a Free Cooling damper (optional), which offers 30% energy
savings compared to standard systems.
The evaporating section fan works on a direct current at 48 Volt
to ensure operation in an emergency.
Climaveneta units are also made to ensure a standard level of
operation even under extreme environmental conditions with
temperatures up to +48C.
Available in super silent version.

 Structure and paneling in galvanized cataphoretic coated steel for maximum


resistance to rust (on request also available in peraluman panels).
 The reliability and functionality of the compressor and all other components
are guaranteed by leading companies in the telecoms sector.
 External air intake for Free Cooling units with opening from 0 to 100%
(optional).
 Contacts for alarms and working state signal plots.
 Universal terminal board for outside complete control of the PLC unity
 Adjustable fan speed(optional).
 Condensing control for lower noise levels.
 Safety pressure switches.
 Condensing coil protection grills.
 Availability of all accessories required for easy and correct installation, for a
complete and efficient air treatment system.
 Customer Assistance.
 Electric heating (optional).
 On board terminal as standard provide, remote terminal version (optional).
 Serial cards for BMS interconnection (optional).
 Humidity sensor (optional).
 Condensate draining pump (optional).

OUTDOOR

Free Cooling

Mechanical

Upflow
12 l 13

TELECOMRANGE

Free Cooling

Mechanical

Dowflow

1-16 broch telecom eng

6-02-2013

10:37

Pagina 13

ON/OFF VERSION
MED
Power supply

V/Ph/Hz

001

003

004

0011

0021

0031

0041

230/1/50

230/1/50

230/1/50

230/1/50

230/1/50

400/3N/50

0051

0056

0061

0071

400/3N/50 400/3N/50 400/3N/50

0091

400/3N/50 400/3N/50

Total cooling capacity

kW

1,95

2,91

3,45

4,94

6,36

8,43

9,72

10,72

14,26

16,8

18,36

20,57

Sensible cooling capacity

kW

1,42

2,67

2,88

4,94

5,65

6,77

9,18

9,58

12,54

14,2

14,82

16,56

Compressor power input

kW

0,6

0,81

0,98

1,18

1,62

2,27

2,38

2,74

3,41

3,9

4,85

5,61

Evaporator air flow

m3/h

300

700

700

1450

1450

1600

2450

2450

3200

3500

3500

3900

Freecooling air flow

3900

m3/h

300

700

700

1450

1450

1600

2450

2450

3200

3500

3500

Evaporator fan AC power input

kW

0,04

0,115

0,115

0,2

0,2

0,24

0,32

0,32

0,4

0,46

0,46

0,52

Evaporator fan DC power input

kW

0,04

0,12

0,12

0,2

0,2

0,24

0,21

0,21

0,26

0,32

0,32

0,32

m3/h

500

1100

1100

2500

2500

2500

4000

4000

4900

5900

5900

5900

Condenser fan AC power input

kW

0,12

0,155

0,155

0,16

0,16

0,16

0,29

0,29

0,78

0,45

0,45

0,45

Max ambient temperature

48

48

48

+48

+48

+48

+48

+48

+48

+48

+48

+48

Min ambient temperature

-25

-25

-25

-25

-25

-25

-25

-25

-25

-25

-25

-25

dB(A)

49

52

52

53

53

56

56

56

58

65

65

65

Condenser max air flow

Outdoor sound pressure level at 1mt


Design conditions

Indoor=27- 45%UR Outdoor=35C

DIMENSIONS
MED

001

003

004

0011

0021

0031

0041

0051

0056

0061

0071

0091

Width

mm

394

505

505

960

960

960

990

990

990

1120

1120

1120

Depth

mm

250

398

398

500

500

500

600

600

600

780

780

780

Height

mm

900

1265

1265

1700

1700

1700

2100

2100

2100

2240

2240

2240

INVERTER VERSION
MED
Power supply

V/Ph/Hz

0031

0051

0091

230/1/50

230/1/50

400/3N/50

Min

Max

Min

Max

Min

Total cooling capacity

kW

4,34

9,53

4,95

12,56

7,96

17,6

Sensible cooling capacity

kW

4,34

7,22

4,95

10,97

7,96

15,45

Compressor power input

Max

kW

0,75

2,37

0,78

3,18

1,18

4,49

Evaporator air flow

m3/h

1600

1600

3200

3200

3900

3900

Freecooling air flow

m3/h

1600

1600

3200

3200

3900

3900

Evaporator fan AC power input

kW

0,24

0,24

0,4

0,4

0,52

0,52

Evaporator fan DC power input

kW

0,12

0,24

0,13

0,26

0,2

0,4

m3/h

2500

2500

4000

4000

5900

5900

Condenser fan AC power input

kW

0,16

0,16

0,29

0,29

0,45

0,45

Max ambient temperature

+48

+48

+48

+48

-25

-25

-25

Condenser max air flow

Min ambient temperature


Outdoor sound pressure level at 1mt

dB(A)

52

Design conditions

-25
58

62

Indoor=27- 45%UR Outdoor=35C

DIMENSIONS
MED

0031

0051

0091

Width

mm

960

990

1120

Depth

mm

500

600

780

Height

mm

1700

2100

2240

Note
* Available in double configuration 230/1/50 or 400/3N/50

1-16 broch telecom eng

6-02-2013

10:37

Pagina 14

TELECOMRANGE

LED

0010E0015E

PACKAGED AIR CONDITIONERS FOR TELECOMMUNICATION CABINET


FREE COOLING

UNIT DESCRIPTION

FEATURES

Packaged air conditioners for telecommunication CABINETS


come in from the 2.5 kW to the 5,5 kW size.
They are direct expansion packaged systems for outdoor
installation. They are fitted with external panels in
electrogalvanized steel sheet painted with cataphoretic
process or in peraluman panels on request.
The units can be fitted with a Free Cooling damper, which
offers 30% energy savings compared to standard systems.
The evaporating section fan works on direct current at 48V to
ensure operation in an emergency.
Climaveneta units are also made to ensure a standard level of
operation even under extreme environmental conditions with
temperatures up to +46C.

 Structure and paneling in galvanized cataphoretic coated steel for maximum


resistance to rust (on request also available in peraluman panels).
 The reliability and functionality of the compressor and all other components
are guaranteed by leading companies in the telecoms sector.
 External air intake for the Free Cooling with opening from 0 to 100%
(optional).
 Available both in electro-mechanic version and electronic version.
 Contacts for alarms and working state signal plots.
 Universal terminal board for outside complete control of the PLC unity
 Double filter (a pre-filter for external air and one for internal one).
 Adjustable fan speed (optional).
 Condensing control for lower noise levels.
 Safety pressure switches.
 Condensing coil protection grills.
 Availability of all accessories required for easy and correct installation, and for
a complete and efficient air treatment system.
 Available both electromechanical version and electronic version.
 Customer Assistance.
 Electric heating (optional).
 On board terminal per standard provide, remote terminal version (optional).
 Serial cards for BMS interconnection (optional).
 Humidity sensor (optional).
 Condensate draining pump (optional).

OUTDOOR/INDOOR

Mechanical

14 l 15

TELECOMRANGE

Free Cooling

1-16 broch telecom eng

6-02-2013

10:37

LED
Power supply

Pagina 15

0010-0010E
V/Ph/Hz

0015-0015E
220/1/50

Total cooling capacity

kW

2,5

Sensible cooling capacity

kW

2,2

5,2

Compressor AC power input

kW

0,84

1,6

Condenser AC power input

kW

0,10

0,40

Evaporator AC power input

kW

0,18

0,9

Evaporator fan DC power input (48VDC)

kW

0,1

0,14

Freecooling air flow

m3/h

470

1500

Evaporator air flow

m3/h

500

1600

Condenser max air flow

m3/h

750

2000

Outdoor sound pressure level at 1mt

dB(A)

50

53

Outdoor sound pressure level at 5mt

dB(A)

36

39

Max ambient temperature

46

46

Electric heating

kW

1,5

5,7

DIMENSIONS
LED

0010

0010E

0015-0015E

Width

mm

600

750

1000

Depth

mm

600

750

800

Height

mm

353

353

410

6-02-2013

10:37

Pagina 16

TELECOMRANGE_09.2011_GB_00

1-16 broch telecom eng

Você também pode gostar