PT. TRAFOINDO PRIMA PERKASA Spec. No. PT.

TRAFOINDO PRIMA PERKASA


Kantor : Jl. Hayam Wuruk 4 FX Jakarta 10120 Phone : 3451384,3850703,3861865 ; Fac. : 3850702,3861869
Pabrik : Jl. Siliwangi (Pasar Kemis), Desa Gembor, Kecamatan Jatiuwung, Tangerang 7. APPROXIMATE WEIGHT AND DIMENSION WITHOUT PACKING : to be informed later on
e-mail : trafo@trafoindonesia.com ; http : //www.trafoindonesia.com 7 - 1 The outline drawing of the transformer will be submited to customer
SPECIFICATION FOR TRANSFORMER
8. ACCESSORIES : The Transformer will be furnished with all necessary accessories as follow :
To. Date 12 JULY 2012
Spec No. GENERAL ACCESSORIES SPECIAL ACCESSORIES
HV Porcelain Bushing on cover - Plug in Bushing mm2 c/w straight connector on cover
1. TYPE ONAN : Oil immersed self cooled / in / out door use / step-up / step-down / hermetically sealed LV Porcelain Bushing c/w Copper Link on cover
distribution transformer - Oil Level Indicator DGPT-2 / RIS / DMCR
- Thermometer - Magnetic Oil Level Gauge c/w Contact
2. SERVICE CONDITION : The Transformer will be installed at the altitudes below 1.000 meters and the maximum Manual Off-Load Tap Changer - Dial Thermometer c/w Alarm & Trip Contact
ambient temperature does not exceed 40
o
C Name Plate - Buchholz Relay
Earth Terminal - Conservator c/w Sampling Valve
3. STANDARD : The Transformer is designed, manufactured and tested in accordance with : Radiator - Breather c/w Silicagel
IEC 600-76 / SPLN 50 / 97 / SLI 1985 Drain Valve - Air-filled LV Juntion Box
- Sampling Valve HV/LV Cable Box
4. RATING Lifting lug - N2 Filling Valve
4 - 1 Number of Phase : 3 phase 4 - 2 Frequency : 50 Hz - Jacking Lug - Pressure Relief Valve
4 - 3 Primary Voltage : 6 kV 4 - 4 Secondary Voltage : 400 Volt Roller - Pressure Vacuum Gauge
Winding Connection : DELTA Winding Connection : WYE - Square Hole - Pressure Relief Device c/w contact
4 - 5 Rated Capacity (total) : 2,000 kVA - Skid Base (Pad Mounted) - Radiator Fans
I f d bl i lt it ill b H ( P l M t d ) R di t V l

ISO 9001 : 2000
Lic no: QEC 22216

ISO 14001 : 2004
Li c no: CEM 20294

OHS 18001
Li c no: OHS 20195


Incase of double primary voltage, capacity will be : - Hanger ( Pole Mounted ) - Radiator Valves
at : - kV Rated Capacity : - kVA - Thermometer Pocket - Winding Thermometer c/w contact
at : - kV Rated Capacity : - kVA Oil Filter valve - Terminal control Box
Incase of double secondary voltage, capacity will be : - Voltage Change Over Board - Neutral CT
at : - V Rated Capacity : - kVA - CT for Winding Thermometer
at : - V Rated Capacity : - kVA - Ladder
4 - 6 Additional Taps on High Voltage :
9. DEVIATION LIST :
5. POLARITY AND PHASOR RELATIONSHIP : The Transformer will be subtractive polarity for single phase and
phasor relationship for three will be Dyn-11 DESCRIPTION CUSTOMER SPEC. TRAFINDO SPEC.
6. ELECTRIC PERFORMANCE :
Primary Voltage Secondary Voltage
6 - 1 Insulation Class : 7.2 kV 1.1 kV
6 - 2 Basic Impulse Level : 60 kV - kV
6 - 3 Applied Voltage Test During 1 Minute : 20 kV 3 kV
6 - 4 Induced Voltage Test : Apply 2 times of the rate voltage at 350 cycles per second for 18 second
6 - 5 Temperature Rise : The coil temperature rise measured by resistance method will not exceed 65
o
C
and the oil temperature rise will not exceed 60
o
C
6 - 6 Losses at Rated Voltage 6 / 0.4 kV
No Load Losses : 3,600 Watt Note : - Painting RAL 7035
Load Losses ( at 75 C ) : 21,000 Watt - Painting Off-Shore (150 Micron)
Total Losses : 24,600 Watt - Winding Cu-Cu
6 - 7 Efficiency at % Rated Capacity : 100 75 50 25 %
at P.F. = 1,0 : 98.78 98.98 99.12 99.03 %
6 - 8 Exciting Current / Off load Current at nominal voltage : 2.00 % Date of Approval :
6 - 9 Percent Impedance : 7.00 % PROPOSER :
6 - 10 Voltage Regulation at P.F. = 1,0 : 1.29 %
Voltage Regulation at P.F. = 0.8 : 5.11 % hp
+/- 2.5 % & +/- 5 % ( 5 Taps )
0582/ENG/2012 - Af