Spin III Web v.1 Section Title Air Handling Unit Operational Control Spreadsheet Training Objectives 3 To provide a tool for systematic review of AHU performance Paper based or Excel spreadsheet based For use by operations and maintenance personnel Applies logical checks Illogical outcomes highlighted for investigation Layout Macro tools One for RH system, one for heating systems Determine desired AHU status from temp & RH requirements Determine room needs from temp & RH requirements Check sheet Customise sheet per AHU Include design operational control parameters 4 Macro tools Assessment Tools- allows the operator to determine the desired status of the AHU based on air temp & RH. (i.e. should the AHU be in dehum mode based on outside temp and RH Also determines the room requirements. 5 AHU Condition Assessment Tool Outside Air Temperature-Enter value between -20 0 C and 35 0 C Relative Humidity-Insert value between 0% and 100% Fresh Air Requirements-Insert value between 0% and 100% AHU Supply Air Condition- Insert value between 5 0 C and 25 0 C AHU Supply Air condition-Insert value between 0% and 100% AHU Conditions Required Red-Heating Blue-Cooling Green Rehumification Blue-Dehumification Indicates Room Requirement Insert Room Temperature and Humidity Specifications between 15 0 C to 25 0 C and 0% To 100% AHU Return Air Requirements- Insert value between 5 0 C and 25 0 C AHU Return Air Condition-Insert value between 0% and 100% Check sheet 7 Enter AHU Number Insert Description of AHU including location and areas served by AHU Insert Date (Format 03 Mar 10) Insert Time (24 Hour Clock format e.g. 16.45) Insert Room Humidification Requirement from Macro Tool DeHum Rehum N/A (when Dehum or Rehum are not required) Enter Room Heating Requirements- Heating Cooling None Insert AHU Humidification Status from Macro Tool DeHum Rehum N/A (when Dehum or Rehum are not required) Enter AHU Heating Status- Heating Cooling None AHU Set point Status & Conditions Insert design supply air temperature and humidity set points. Insert the Original Supply Air Volume and Return Air Volume set points. Insert Filter dP limits. Insert actual setpoint values from BMS screen Insert value for each of the conditions from BMS screen Insert commissioning report data. AHU Set up Check Determine Result from Building Management System (BMS). Enter Yes No or N/A. Red colour indicates incorrect result/problem on system Determine Result from BMS. When mixing section is fixed enter N/A. Determine Results from BMS. Enter Yes, No or N/A Determine result from BMS. View trends for Control Valves, Speed etc to determine if record is stable. Enter Yes No or N/A Confirm on BMS room pressure operating according to specification. Enter Yes, No or N/ A AHU Operating Situation Enter AHU pre-heating value which can be obtained from BMS. Enter AHU pre-cooling value which can be obtained from BMS. Enter cooling valve data from BMS. Enter heating valve data from BMS. Enter pre-dehumidifcation value data from BMS. Enter de-humidifcation value data from BMS. Enter heat recovery data from BMS. If heat recovery fixed record 100% for running and enter 0% if heat recovery is not running Enter fresh air and mixing air data from BMS. AHU Conditions Enter AHU mode. This has already been determined in Macro status Section. Consult Macro Section when entering value. Determine if heating and cooling valves are open at same time. When heating is required heat recovery should be the first stage of heating. When cooling is required heat recovery should be off. Enter yes, No or N/A Free cooling from outside should be maximized when available, and should be the first stage of cooling. If outside air is colder than return air then100% fresh air should be used before chilled water. Free heating from outside should be maximized when available, and should be the first stage of heating if outside air is hotter than return air then in this case 100% fresh air should be used before heat recovery or LPHW. Determine if the rooms supplied by AHU are within specification for temp and RH. Using the Macro Status information determine if the AHU is achieving the conditions required for each room. Determine if the heating/Cooling valves are operating at 100% If answer is Yes then a system is maxed out and may indicate a problem. AHU Conditions Determine DeHum mode from Macro Status for AHU. Determine if the AHU is carrying out DeHum and Re-Hum at the same time. One should always be at 0%. Determine if chilled water Pre-DeHum is maximized when Dehum is required. (Pre-DeHum with chilled water is cheaper than dessicant drying, and therefore the Pre-DeHum should be 100% before dessicant drying commences) Determine if Room temperature conditions are being met. When in DeHum mode or ReHum mode verify if the system control the final temperature of the rooms. See the Macro Status .Determine if the AHU status match the room status. Determine if enthalpy control is being used Confirm that the positions of the exhaust air and mixing dampers approximately = 100% Determine if the fan speed is increasing/decreasing over time and determine if this can be explained by filter conditions Determine if the statis pressures is increasing/ decreasing over time and determine if this cat be explained by the filter conditions. Determine if the fan power is increasing/ decreasing over time and determine if this can be explained by the filter conditions. Compare the changes in filter DP with the filter change history. Step reductions in DP should correspond with filter changes Use of check-sheet (Paper) 13 Customise worksheet per AHU Copy insert or delete lines as required Fill in design data Fit one or multiple AHU spreadsheets in each page Print workbook Use of check-sheet (excel) Customise worksheet per AHU Copy insert or delete lines as required Fill in design data Fit one or multiple AHU spreadsheets in each page Complete the spreadsheet Insert new column for further data entry as per next slide 14 To Copy Cells for Adding Data 15 Highlight Column E of Excel Sheet. Right Click and select Copy Right Click and select Insert Copied Cells Delete Contents of Copied Cell and add AHU data as required Use of check-sheet (excel) All cells highlighted in red have potential issues causing excessive energy usage All issues should be fed into maintenance system on site Spreadsheet can form part of the operational control clause of the energy management system AHU Operational Control Spreadsheet Training