Installation Equipment
Select two of the elliptical holes on Hang the equipment on the upper
edge of the rear iron cover, and
then press the equipment down.
Push the equipment backward to hang
the entire equipment onto the rear cover.



on the surface for fixing (Which may
be on a distribution cabinet, ceiling
or other weatherproof position).
1 2 3
1.Cautions
1)The access controller provides lock control output. For a lock which should be open when being energized and be closed
Unlock at power off
Unlock at power on
+
+
-
-
Enlar ged diagram
NC
NO
COM
when being de-energized, the COM and NO terminals should be used. For a lock which should be open when being
de-energized and be closed when being energized, the COM and NC terminals should be used.
Diode
Diode
Lock
Lock
+
+
-
-
FR107
FR107
3. Lock Connection
External power supply for electronic lock
p q
RS-485 EXT
W
IEG
AND 3
IN5
IN6
O
UT5
O
UT6
W
IEG
AND 4
IN7
IN8
O
UT7
O
UT81
3
1
3
1
2
1
2
1
10
1
3
1
3
1
2
1
2
1
10
1
6
W
IEG
AND 1
IN1
IN2
O
UT1
O
UT2
W
IEG
AND 2
IN3
IN4
O
UT3
O
UT4
1
3
PO
W
ER
1
5
1
10
1
2
1
2
1
3
1
3
1
10
1
2
1
2
1
3
Reset
Lock Power
+
+
-
-
Lock Power
3) Each relay may work under the wet mode or dry mode by setting the jumper terminal. If the 12V power
1 2 3 4
supply inside the access controller uses external power supply, the output of each relay is under the wet mode.
O
U
T
4
Relay
Relay
Jumper terminals
Jumper terminals
wet mode:
O
U
T
8
O
U
T
7
Relay
Relay
O
U
T
3
dry mode:
IN8
IN4
Please notice the following cautions. Mis-operation may lead to personal injury or
1) Do not energize the system before installation is complete. Never carry out installation
2) All peripheral devices must be grounded.
activities when the system is energized.
the rear iron cover. Drill two holes
2) If the electrical lock is connected to the access control system, you need to parallel one FR107 diode (Equipped
in the package) to prevent the self-inductance EMF affect the system, do not reverse the polarities.
If the external power supply uses potential free contacts, the dry mode should be used. please refer to
Instructions for Hardware of C4-200/400 Access Controller.
* It is recommended to short 2-3 ports, the output use the dry mode, the electronic lock use the external power supply.
of lock ports
equipment failure:
Relay output ports and jumper terminals setting (The second layer of PCB)
4 3 2 1 1 2 3 4
1 2 3 4 1 2 3 4
1 2 3 4
1 2 3 4
Jumpi ng Termi nals
Distribution
diagram of the
factory default
jumper cap:
1 2 3 4
3) It is recommended that all wires run through casing pipes which may by PVC or galvanized
5) Its recommended that card readers and buttons installed at height of 1.4m-1.5mabove ground.
6) It is recommended to use the power supply in case for control panel, and external power
4) It is strongly recommended that the length of exposed part of any connection cable
should not be longer than 4 mm. avoid Professional clamping tools may be used to
unintentional contact of exposed wires to avoid short-circuit or communication failure.
supply for each lock.
ones.
4) he standard Considering of the consumption of the control panel, the Wiegand reader and the inBIO reader, t
power supply is 12V/3A the control panel . So we don' t recommend the lock and use the common power supply.
If it is necessary to use, we suggest to change the bigger one, such as 12V/5A.Except the power consumption
reserved, there are 2Acurrent for the lock. For the common electrical lock (the standby current is 300mA, the
max current is 500mA), the max connected lock is 4.
4.485 Reader (inBIO Reader) Connection
PC
TCP/IP Ethernet
RS485 Ports
Card Reader
1# Controller 2# Controller n# Controller
p q
RS-485 EXT
WIEGAND 3
IN5
IN6
OUT5
OUT6
WIEGAND 4
IN7
IN8
OUT7
OUT81
3 1
3 1
2 1
2
1
10
1
3
1
3
1
21
2
1
10
1
6
WIEGAND 1
IN1
IN2
OUT1
OUT2
WIEGAND 2
IN3
IN4
OUT3
OUT4
1
3
POWER
1
5
1
10
1
21
21
3 1
3
1
10
1
21
2 1
3
Reset
p q
RS-485 EXT
WIEGAND 3
IN5
IN6
OUT5
OUT6
WIEGAND 4
IN7
IN8
OUT7
OUT81
3 1
3 1
2 1
2
1
10
1
3
1
3
1
21
2
1
10
1
6
WIEGAND 1
IN1
IN2
OUT1
OUT2
WIEGAND 2
IN3
IN4
OUT3
OUT4
1
3
POWER
1
5
1
10
1
21
21
3 1
3
1
10
1
21
2 1
3
Reset
p q
RS-485 EXT
WIEGAND 3
IN5
IN6
OUT5
OUT6
WIEGAND 4
IN7
IN8
OUT7
OUT81
3 1
3 1
2 1
2
1
10
1
3
1
3
1
21
2
1
10
1
6
WIEGAND 1
IN1
IN2
OUT1
OUT2
WIEGAND 2
IN3
IN4
OUT3
OUT4
1
3
POWER
1
5
1
10
1
21
21
3 1
3
1
10
1
21
2 1
3
Reset
1) TCP/IP Mode:
2) RS485 Mode:
3) The recommended bus length of RS485 communication is less than 600 meters.
485-
485+
GND
485- 485- 485- 485+ 485+ 485+ GND GND GND
Serial Bus
4 3 2 1 4 3 2 1
4 3 2 1
8# Controller 2# Controller 1# Controller
p q
RS-485 EXT
WIEGAND 3
IN5
IN6
OUT5
OUT6
WIEGAND 4
IN7
IN8
OUT7
OUT81
3 1
3 1
2 1
2
1
10
1
3
1
3 1
21
2
1
10
1
6
WIEGAND 1
IN1
IN2
OUT1
OUT2
WIEGAND 2
IN3
IN4
OUT3
OUT4
1
3
POWER
1
5
1
10
1
21
21
3 1
3
1
10
1
21
2 1
3
Reset
p q
RS-485 EXT
WIEGAND 3
IN5
IN6
OUT5
OUT6
WIEGAND 4
IN7
IN8
OUT7
OUT81
3 1
3 1
2 1
2
1
10
1
3
1
3 1
21
2
1
10
1
6
WIEGAND 1
IN1
IN2
OUT1
OUT2
WIEGAND 2
IN3
IN4
OUT3
OUT4
1
3
POWER
1
5
1
10
1
21
21
3 1
3
1
10
1
21
2 1
3
Reset
p q
RS-485 EXT
WIEGAND 3
IN5
IN6
OUT5
OUT6
WIEGAND 4
IN7
IN8
OUT7
OUT81
3 1
3 1
2 1
2
1
10
1
3
1
3 1
21
2
1
10
1
6
WIEGAND 1
IN1
IN2
OUT1
OUT2
WIEGAND 2
IN3
IN4
OUT3
OUT4
1
3
POWER
1
5
1
10
1
21
21
3 1
3
1
10
1
21
2 1
3
Reset
Notes:
Switch
4) When the bus is longer than 300 m, to enhance the stability of communication, it is necessary
RS 485 Convertor
1) Internationally accepted RVVP (shielded twisted-pair) wires should be used for communication
to RS485 communication wires should be connected by means effectively avoid interference.
of bus cascade connection.
2) Theoretically, in RS485 communication, one bus may be connected with 64 access controllers.
to change J24 on the first layer of PCB (see the figure below) inthe first and the last units (see
unit 8# as shown in the figure above) to short pins 2-3. This method is equivalent to connect
The PC software communicate with the system through two protocols (RS485 and TCP/IP) for data
exchange and remote management.The communication cable should be away from high-voltage
lines as far as possible. Do not keep the communication cable in parallel with power cords or bind
them together.
PC
It is recommended to conenct with no more than 32 devices.
with a resistance of 120 ohm.
1 1
2 2
3 3
J24 Enlargement
Factory default Terminal resistance setting
11
22
33
RS485
J
2
4
Terminal resistance setting diagram (The first layer of PCB)
The control panel supports inBIO biometric verification reader and Wiegand reader. In use of inBIO reader,
inBIO reader connection: First of all, set the 485 address (device number) of reader by software, DIP switch or
keypad. For reader 1, 2 (the odd number is for enter reader, and the even number is for exit reader), the door
all operations including storage, verification, etc. execute in control panel. No need to re-register the fingerprints
for reader changing. Realize the real biometric reader connection.
number is 1. And the 485 address is 1, 2. Such as the below figure connection. For more information, please refer
to the software user manual.
5.Equipment Communication
Version 2.1 Date: Dec. 2011
inBIO 480 Installation and Connection Guide
+12V
GND
#3 Reader
+12V
GND 485- GND
485+
#1 Reader #2 Reader #8 Reader
Separate power supplies Separate power supplies
PC
p q
RS-485 EXT
WIEGAND 3
IN5
IN6
OUT5
OUT6
WIEGAND 4
IN7
IN8
OUT7
OUT81
3 1
3 1
2 1
21
10
1
3 1
3 1
21
21
10
1
6
WIEGAND 1
IN1
IN2
OUT1
OUT2
WIEGAND 2
IN3
IN4
OUT3
OUT4
1
3
POWER
1
5
1
10
1
21
21
3 1
3 1
10 1
21
2 1
3
Reset
100mA, the max current is less than 120mA, When the device is start, Instantaneous current can reach 240 mA.
sure the steady operation.
Besides, a single EXT485 interface can supply 500mA(12V)current maximum. So the entire current consumption
should be less than this max value when the readers share power with the panel. In calculation, please
use max current of the reader, and the start current is usually more than twice of the normal work
current, please consider of this situation. For example, use the FR1200 reader, the standby current is less than
As inBIO reader, consider the starting current is bigger,through the EXT485 interface can only connect
two reader for power supply. So the power of control panel connect only nearest 2 readers. For some
of the devices with much greater consumption, we suggest to using the separately power supplies, to make
Data_Tx-
Data_Tx+
GND
Data_RxTx-
Data_RxTx+
Shield
+12V
GND
Shield
AC Fail
Battery Fail
VCC 12V
GND
D0
D1
Shield
LED_G
LED_R
BEEP
Hold
Card_present
VCC 12V
GND
D0
D1
Shield
LED_G
LED_R
BEEP
Hold
Card_present
Card_present
Hold
BEEP
LED_R
LED_G
Shield
D1
D0
GND
VCC 12V
Card_present
Hold
BEEP
LED_R
LED_G
Shield
D1
D0
GND
VCC 12V
GND
Analog_input
GND
Analog_input
GND
Analog_input
GND
Analog_input
Analog_input
GND
Analog_input
GND
Analog_input
GND
Analog_input
GND
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
Lock 2
Auxiliary Output
Lock 1
Lock 3
Lock 4
Auxiliary Output
Auxiliary Output
Auxiliary Output
Magnet 3
Magnet 4
Magnet 3
Magnet 1
Door Switch 3
Door Switch 1
Door Switch 3
Door Switch 4
12V Power Input
Shield Wire
AC Fail Detection
12V Power Output
12V Power Out
12V Power Output
12V Power Output
Wiegand Input
Wiegand Input
Wiegand Input
Wiegand Input
Shield Wire
Sheild Wire
Shield Wire
Shield Wire
Green
Green
Red
Red
Red
Red
Green
Green
Beep
Beep
Beep
Beep
Controlled Reader Hold
Controlled Reader Hold
Controlled Reader Hold
Card Present
Card Present
Card Present
Card Present
{
{
{
{
{
{
{
{
{
{
{
{
{
{
{
Shield Wire
}
}
}
}
}
}
}
}
}
}
}
}
RS 422 Send
}
RS422 Receive
or RS485 Comm. }
Controlled Reader Hold


Output
Output
Output
*
*
*
*
*
*
*
p q
R
S
-
4
8
5

E
X
T
W
I
E
G
A
N
D

3
I
N
5
I
N
6
O
U
T
5
O
U
T
6
W
I
E
G
A
N
D

4
I
N
7
I
N
8
O
U
T
7
O
U
T
8
1
3
1
3
1
2
1
2
1
1
0
1
3
1
3
1
2
1
2
1
1
0
1
6
W
I
E
G
A
N
D

1
I
N
1
I
N
2
O
U
T
1
O
U
T
2
W
I
E
G
A
N
D

2
I
N
3
I
N
4
O
U
T
3
O
U
T
4
1
3
P
O
W
E
R
1
5
1
1
0
1
2
1
2
1
3
1
3
1
1
0
1
2
1
2
1
3
R
e
s
e
t
Front View
Front Side View
R
S
-
2
3
2
I
N
9
O
U
T
9
I
N
1
2
I
N
1
1
I
N
1
0
O
U
T
1
0
R
S
-
4
8
5
1
3
1
3
1
2
1
2
1
2
1
2
1
4
1
4
Output
*
*
*
*
*
TXD232
RXD232
/
GND
Shield
RS 485-
RS 485+
GND
USB
TCP/IP
Analog_input
GND
Analog_input
GND
Analog_input
GND
Analog_input
GND
NO
COM
NC
NO
COM
NC
U Disk
TCP/IP Comm.
RS 232 Send
Auxiliary Input
Auxiliary Input
Auxiliary Input
Auxiliary Input
Auxiliary Output
Auxiliary Output
Shield Wire
RS485 Comm.
RS485 Ground
RS 232 Receive
Idle
RS 232 Ground
*
*
*
*
*
*
A
B
B
B
B
C
C
C
C
C
C
C
C
C
C
D
D
D
D
D
D
D
D
D
D
D
D
*
*
}}
1) The auxiliary input may be connected to infrared body detectors, smoke detectors, gas detectors, window magnetic alarms, wireless exit switches, etc.
2) The auxiliary output may be connected to locks, monitors, alarms, door bells, etc.
3) The auxiliary input and the auxiliary output via Access Software setting.
support for ordering machines with GPRS and WiFi functions.
5) Recommened use of wires
Notes:
4) GPRS, WiFi and the following items indicated with "*" are optional. Please contact our business representatives or pre-sale technical
6.Terminals Connection
Battery Fail Detection
Interface Wire specification Network Cable Maximum length
PowerA 18AWG*2PIN / 1.5M
WiegandB
24AWG*6PIN
(6PIN, 8PIN, 10PIN for different readers option)
CAT-5 or above network cable, one way
DC impedance is less than 100KM
100M
Electric-lockC
18AWG*2PIN+24AWG*2PIN:
118AWG*2PIN for lock connection,
24AWG*2PIN for door sensor connection
/ 50M
PowerD 24AWG*2PIN / 100M
EXT485E
20AWG*2PIN+24AWG*2PIN:
20AWG*2PIN for reader power supply
24AWG*2PIN for RS485 communication
CAT-5 or above network cable, one way
DC impedance is less than 100KM
In wire connection, +12V and GND of Power
supply need to be parallel and use double wires
Share power with control panel:100M
Use readers independence power supply
(connect RS485 signal interface only ): 1000M