frequency 50 Hz or 60Hz(selectable) Rated current Inom 1A or 5A (selectable) Power consumption In CT circuit with Inom=1A 0.05VA In CT circuit with Inom=5A .30VA In CT circuit for High sensitive groung (earth) fault protection at 1A .05VA Thermal overload capability in CT circuit In CT circuit 100*Inom for 1 sec 30*Inom for 10 sec 4*Inom continuous In CT circuit for high sensitive ground (earth) fault protection 300 A for 1 sec 100 A for 10sec 15 A contibuous dynamic overload capability In CT circuits 250*Inom (one half cycle) In CT circuit for high sensitive ground (earth) fault protection 250*Inom (one half cycle) Tolerances Typical 0.3 % of indicated measured value or 0.5 % Inom 50 Hz or 60Hz(selectable) 1A or 5A (selectable) 100*Inom for 1 sec 30*Inom for 10 sec 4*Inom continuous 300 A for 1 sec 100 A for 10sec 15 A contibuous 250*Inom (one half cycle) 250*Inom (one half cycle) Typical 0.3 % of indicated measured value or 0.5 % Inom 7SJ62 Multi function protection Relay frequency 50 Hz or 60Hz(selectable) Rated current Inom 1A or 5A (selectable) option:Sensitive earth fault CT Iee<1.6A Power consumption In CT circuit with Inom=1A 0.05VA In CT circuit with Inom=5A .30VA In CT circuit for High sensitive groung (earth) fault protection at 1A .05VA Overload Capability Thermal effective 100*Inom for 1 sec 30*Inom for 10 sec 4*Inom continuous dynamic impulse current 250*Inom (one half cycle) overload capability if equipped with sensitiveearth fault CT Thermal efective 300 A for 1 sec 100 A for 10sec dynamic impulse current 750 A (half cycle) Range 10% to 200% Tolerance 0.1 % of indicated measured value or 0.5 % Inom 50 Hz or 60Hz(selectable) 1A or 5A (selectable) 100*Inom for 1 sec 30*Inom for 10 sec 4*Inom continuous 250*Inom (one half cycle) 300 A for 1 sec 100 A for 10sec 750 A (half cycle) 10% to 200% 0.1 % of indicated measured value or 0.5 % Inom 7SS52 Busbar and Breaker failure protection frequency 50 Hz or 60Hz(selectable) Rated current Inom 1A or 5A (selectable) option:Sensitive earth fault CT Iee<1.6A Power consumption In CT circuit with Inom=1A <0.1VA In CT circuit with Inom=5A <0.2VA Overload Capability Thermal effective 100*Inom for 1 sec 10*Inom for 10 sec 4*Inom continuous central unit Range 0 to 1000% In Tolerance typically 2% of measured value bay unit Range 0 to 6000% In Tolerance typically 2% of measured value 50 Hz or 60Hz(selectable) 1A or 5A (selectable) 100*Inom for 1 sec 10*Inom for 10 sec 4*Inom continuous 0 to 1000% In typically 2% of measured value 0 to 6000% In typically 2% of measured value 7VK61 Breaker Management realy frequency 50 Hz or 60Hz(selectable) Rated current Inom 1A or 5A (selectable) option:Sensitive earth fault CT Iee<1.6A Power consumption In CT circuit with Inom=1A approx 0.05 VA In CT circuit with Inom=5A approx 0.3 VA Overload Capability Thermal effective 500A for 1 sec 150 A for 10 sec 20A continuous Dynamic 1250 A (half cycle) Tolerance typ. 0.3 % of indicated measured value or 0.5 % Inom 50 Hz or 60Hz(selectable) 1A or 5A (selectable) approx 0.05 VA approx 0.3 VA 500A for 1 sec 150 A for 10 sec 20A continuous 1250 A (half cycle) typ. 0.3 % of indicated measured value or 0.5 % Inom 7UT613 Differential protection relay for transformers, generators, motors and busbars frequency 50 Hz or 60Hz(selectable) Rated current Inom 0.1A or 1A or 5A (selectable) Power consumption In CT circuit with Inom=1A approx 0.05 VA In CT circuit with Inom=5A approx 0.3 VA In CT circuit with Inom=0.1A approx. 0.001 Overload Capability Thermal effective 100In for 1 sec 30 In for 10 sec 4In continuous Dynamic 250 A (half cycle) Tolerance operational measured values I L1 I L2 I L3 In=5A or 1A 1% of measured value or 1% of In In=0.1A 1% of measured value or 2% of In operational measured values 3I 0 I 1 I 2 2% of measured value or 2% of In 50 Hz or 60Hz(selectable) 0.1A or 1A or 5A (selectable) approx 0.05 VA approx 0.3 VA approx. 0.001 100In for 1 sec 30 In for 10 sec 4In continuous 250 A (half cycle) 1% of measured value or 1% of In 1% of measured value or 2% of In 2% of measured value or 2% of In