Você está na página 1de 86

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 1/86

Ex.No.1 .a) OPEN CIRCUIT CHARACTERISTICS AND LOAD CHARACTERISTICS


OF SEPARATELY EXCITED DC SHUNT GENERATOR.

AIM:
To conduct the open circuit test on the DC separately excited generator and to draw its
open circuit characteristics curve.
To conduct the load test on the given DC separately excited generator and to draw its
(internal and external characteristics) load characteristics curve.
NAME PLATE DETAILS:

FUSE RATING & METER RANGE FIXING:
125 % of Rated current
APPARATUS REQUIRED:
S.No. Apparatus Range Type Quantity






PRECAUTIONS:
The field rheostat of motor should be in minimum resistance position at the time of
starting and stopping the machine.
The field rheostat of generator should be in maximum resistance position at the time of
starting and stopping the machine.
The speed of the generator must be kept constant throughout the expirement.
PROCEDURE OF OCC
1. Connections are made as per the circuit diagram.
2. Start the DC motor by closing the DPST switch and using the starter (moving the starter
arm from minimum to maximum position).Make the motor to run at rated speed by
adjusting the field regulator.

Kings College of Engineering/ EE1257/

3. Now the generator runs at rated speed.
4. Note down the reading of voltemeter connected ac
ammeter connected in series with field winding of the generator.
5. Vary the field current in convenient steps and note down the corresponding voltmeter
and ammeter readings.
6. Repeat the above procedure up
7. The graph is drawn between field current and generator emf at no load.

CIRCUIT DIAGRAM OF OCC:



TABULATION OF OCC:






S.No



/Electrical Engineering &Control Systems Laboratory
Now the generator runs at rated speed.
Note down the reading of voltemeter connected across the generator armature and
ammeter connected in series with field winding of the generator.
Vary the field current in convenient steps and note down the corresponding voltmeter
Repeat the above procedure up-to a higher value than the rated voltage.
The graph is drawn between field current and generator emf at no load.
CIRCUIT DIAGRAM OF OCC:
Field Current
I
f
(Amps)
Armaure Voltage
E
o
(Volts)



Page 2/86
ross the generator armature and
Vary the field current in convenient steps and note down the corresponding voltmeter



Kings College of Engineering/ EE1257/


MODEL GRAPH OF OCC:




PROCEDURE OF LOAD TEST:

1. Connections are made as per the circuit diagram.
2. Start the DC motor by closing the DPST switch and using the starter (moving the starter
arm from minimum to maximum position).Make the motor to run at
adjusting the field regulator.
3. Adjust the field current of the generator to obtain the rated terminal voltage.
4. Close the load side DPST switch and load the generator in suitable steps.
5. For each step of load, the generator speed is maintained constant and corresponding
voltmeter & ammeter readings were noted.
6. Repeat the above procedure till the rated load of the generator is reached.
7. Then load characterstics curves are drawn.





/Electrical Engineering &Control Systems Laboratory


OF LOAD TEST:
Connections are made as per the circuit diagram.
Start the DC motor by closing the DPST switch and using the starter (moving the starter
arm from minimum to maximum position).Make the motor to run at
ator.
Adjust the field current of the generator to obtain the rated terminal voltage.
Close the load side DPST switch and load the generator in suitable steps.
of load, the generator speed is maintained constant and corresponding
ammeter readings were noted.
Repeat the above procedure till the rated load of the generator is reached.
Then load characterstics curves are drawn.
Page 3/86
Start the DC motor by closing the DPST switch and using the starter (moving the starter
arm from minimum to maximum position).Make the motor to run at rated speed by
Adjust the field current of the generator to obtain the rated terminal voltage.

of load, the generator speed is maintained constant and corresponding
Repeat the above procedure till the rated load of the generator is reached.

Kings College of Engineering/ EE1257/

CIRCUIT DIAGRAM OF LOAD TEST


DETERMINATION OF ARMATURE RESISTANCE:

PROCEDURE:
1. Connections are made as per the circuit diagram.
2. Supply is given by closing the DPST switch.
3. Readings of Ammeter and Voltmeter are noted.
4. Armature resistance in Ohms is calculated as R
/Electrical Engineering &Control Systems Laboratory
CIRCUIT DIAGRAM OF LOAD TEST:
DETERMINATION OF ARMATURE RESISTANCE:
re made as per the circuit diagram.
2. Supply is given by closing the DPST switch.
3. Readings of Ammeter and Voltmeter are noted.
4. Armature resistance in Ohms is calculated as R
a
= (Vx1.5) /I
Page 4/86



Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 5/86

TABULATION TO FIND ARMATURE RESISTANCE:

S.No. Voltage
V (Volts)
Current
I (Amps)
Armature Resistance
R
a
(Ohms)









TABULATION OF LOAD TEST:



FORMULAE:
E
g
= V + I
a
R
a
(Volts)
I
a
= I
L
+ I
f
(Amps)
Where,
E
g
: Generated emf in Volts
V : Terminal Voltage in Volts
I
a
: Armature Current in Amps
I
L
: Line Current in Amps
I
f
: Field Current in Amps
R
a
: Armature Resistance in Ohms
S.No.
Field
Current
I
f
(Amps)
Load
Current
I
L
(Amps)
Terminal
Voltage
(V) Volts
I
a
= I
L
+ I
f
(Amps)

E
g
=V + I
a
R
a
(Volts)






Kings College of Engineering/ EE1257/


MODEL GRAPH:














RESULT:
Thus the No-load test has been conducted on given separ
No load curve drawn.
Thus the load test has been conducted on given separately excited dc generator and load
curve drawn.
/Electrical Engineering &Control Systems Laboratory

load test has been conducted on given separately excited dc generator and
the load test has been conducted on given separately excited dc generator and load
Page 6/86
ately excited dc generator and
the load test has been conducted on given separately excited dc generator and load

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 7/86


Ex.No.1 .b) OPEN CIRCUIT CHARACTERISTICS AND LOAD CHARACTERISTICS
OF SELF EXCITED DC SHUNT GENERATOR.

AIM:
To conduct the open circuit test on the DC self excited generator and to draw its
open circuit characteristics curve.
To conduct the load test on the given DC self excited generator and to draw its
(internal and external characteristics) load characteristics curve.
NAME PLATE DETAILS:

FUSE RATING & METER RANGE FIXING:
125 % of Rated current

APPARATUS REQUIRED:

S.No. Apparatus Range Type Quantity






PRECAUTIONS:
The field rheostat of motor should be in minimum resistance position at the time of
starting and stopping the machine.
The field rheostat of generator should be in maximum resistance position at the time of
starting and stopping the machine.
SPST switch is kept open during starting and stopping.



Kings College of Engineering/ EE1257/

PROCEDURE OF OCC:
1. Connections are made as per the circuit diagram.
2. After checking minimum position of motor field rheostat, maximum position of generator
field rheostat, DPST switch
3. By adjusting the field rheostat, the motor is brought to rated speed.
4. Voltmeter and ammeter readings are taken when the SPST switch is kept open.
5. After closing the SPST switch, by varying the generat
ammeter readings are taken.
6. After bringing the generator rheostat to maximum position, field rheostat of motor to
minimum position, SPST switch is opened and DPST switch is opened.

CIRCUIT DIAGRAM OF OCC:








/Electrical Engineering &Control Systems Laboratory
Connections are made as per the circuit diagram.
After checking minimum position of motor field rheostat, maximum position of generator
field rheostat, DPST switch is closed and starting resistance is gradually removed.
By adjusting the field rheostat, the motor is brought to rated speed.
Voltmeter and ammeter readings are taken when the SPST switch is kept open.
After closing the SPST switch, by varying the generator field rheostat, voltmeter and
ammeter readings are taken.
After bringing the generator rheostat to maximum position, field rheostat of motor to
minimum position, SPST switch is opened and DPST switch is opened.

Page 8/86
After checking minimum position of motor field rheostat, maximum position of generator
is closed and starting resistance is gradually removed.
Voltmeter and ammeter readings are taken when the SPST switch is kept open.
or field rheostat, voltmeter and
After bringing the generator rheostat to maximum position, field rheostat of motor to


Kings College of Engineering/ EE1257/

TABULATION OF OCC:

S.No.



MODEL GRAPH OF OCC:

PROCEDURE OF LOAD TEST:
1. Connections are made as per the circuit diagram.
2. After checking minimum position of DC shunt motor field rheostat and
position of DC shunt generator field rheostat, DPST switch is closed and starting
resistance is gradually removed.
3. Under no load condition, Ammeter and Voltmeter readings are noted, after bringing the
voltage to rated voltage by adjusting the field
4. Load is varied gradually and for each load, voltmeter and ammeter readings are noted.
/Electrical Engineering &Control Systems Laboratory
Field Current
I
f
(Amps)
Armature Voltage
E
o
(Volts)












PROCEDURE OF LOAD TEST:
Connections are made as per the circuit diagram.
After checking minimum position of DC shunt motor field rheostat and
position of DC shunt generator field rheostat, DPST switch is closed and starting
resistance is gradually removed.
Under no load condition, Ammeter and Voltmeter readings are noted, after bringing the
voltage to rated voltage by adjusting the field rheostat of generator.
Load is varied gradually and for each load, voltmeter and ammeter readings are noted.
Page 9/86
After checking minimum position of DC shunt motor field rheostat and maximum
position of DC shunt generator field rheostat, DPST switch is closed and starting
Under no load condition, Ammeter and Voltmeter readings are noted, after bringing the
Load is varied gradually and for each load, voltmeter and ammeter readings are noted.

Kings College of Engineering/ EE1257/

5. Then the generator is unloaded and the field rheostat of DC shunt generator is brought to
maximum position and the field rheostat of DC shunt moto
switch is opened.

CIRCUIT DIAGRAM:

DETERMINATION OF ARMATURE RESISTANCE:

PROCEDURE:
1. Connections are made as per the circuit diagram.
2. Supply is given by closing the DPST switch.
3. Readings of Ammeter and Voltmeter
4. Armature resistance in Ohms is calculated as R
/Electrical Engineering &Control Systems Laboratory
Then the generator is unloaded and the field rheostat of DC shunt generator is brought to
maximum position and the field rheostat of DC shunt motor to minimum position, DPST
DETERMINATION OF ARMATURE RESISTANCE:
1. Connections are made as per the circuit diagram.
2. Supply is given by closing the DPST switch.
3. Readings of Ammeter and Voltmeter are noted.
4. Armature resistance in Ohms is calculated as R
a
= (Vx1.5) /I
Page 10/86
Then the generator is unloaded and the field rheostat of DC shunt generator is brought to
r to minimum position, DPST



Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 11/86

TABULATION TO FIND ARMATURE RESISTANCE:

S.No. Voltage
V (Volts)
Current
I (Amps)
Armature Resistance
R
a
(Ohms)









TABULATION OF LOAD TEST:

FORMULAE:
E
g
= V + I
a
R
a
(Volts).
I
a
= I
L
+ I
f
(Amps).
Where,
E
g
: Generated emf in Volts
V : Terminal Voltage in Volts
I
a
: Armature Current in Amps
I
L
: Line Current in Amps
I
f
: Field Current in Amps
R
a
: Armature Resistance in Ohms
S.No.
Field
Current
I
f
(Amps)
Load
Current
I
L
(Amps)
Terminal Voltage
(V) Volts
I
a
= I
L
+ I
f
(Amps)

E
g
=V + I
a
R
a
(Volts)






Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 12/86

MODEL GRAPH:














RESULT:
Thus the No-load test has been conducted on given self excited dc generator and
No load curve drawn.
Thus the load test has been conducted on given self excited dc generator and load curve
drawn.



Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 13/86

EXPT: 2 LOAD TEST ON DC SHUNT MOTOR
DATE:

AIM:
To conduct the load test on a given DC shunt motor and to draw its performance curves.

NAME PLATE DETAILS:

FUSE RATING:


APARATUS REQUIRED:


S.NO
NAME OF THE
APPARATUS

TYPE

RANGE

QUANTITY





PRECAUTIONS:
1. DC shunt motor should be started and stopped under no load condition.
2. Field rheostat should be kept in the minimum position.
3. Brake drum should be cooled with water when it is under load.

PROCEDURE:
1. Connections are made as per the circuit diagram.
2. After checking the no load condition, and minimum field rheostat position, DPST switch
is closed and starter resistance is gradually removed.
3. The motor is brought to its rated speed by adjusting the field rheostat.

Kings College of Engineering/ EE1257/

4. Ammeter, Voltmeter readings, speed and spring balance readings are noted under no load
condition.
5. The load is then added to the motor gradually and for each load, voltmeter, ammeter,
spring balance readings and speed of the motor are noted.
6. The motor is then brought to no load condition and field rheostat to minimum position,
then DPST switch is opened.


CIRCUIT DIAGRAM:


FORMULAE:

1. Torque T= (S
1
-S
2
) x(R+t/2) x9.81
Where, R-radius of brake drum in m
t- Thickness of the belt in m
S
1,
S2-spring balance reading in Kg
2. Input power=V
L
x I
L
in W
Where V
L
-load voltage in V
/Electrical Engineering &Control Systems Laboratory
Ammeter, Voltmeter readings, speed and spring balance readings are noted under no load
The load is then added to the motor gradually and for each load, voltmeter, ammeter,
pring balance readings and speed of the motor are noted.
The motor is then brought to no load condition and field rheostat to minimum position,
then DPST switch is opened.
) x9.81 Nm
dius of brake drum in m
of the belt in m
spring balance reading in Kg
load voltage in V
Page 14/86
Ammeter, Voltmeter readings, speed and spring balance readings are noted under no load
The load is then added to the motor gradually and for each load, voltmeter, ammeter,
The motor is then brought to no load condition and field rheostat to minimum position,


Kings College of Engineering/ EE1257/

I
L
-load current in A
3. Output power = 2 NT/60 in W
Where N-Speed of the armature in rpm
T-Torque in Nm
4. Percentage of efficiency = (Output power/Input power) x 100

MODEL GRAPH:









/Electrical Engineering &Control Systems Laboratory
load current in A
NT/60 in W
Speed of the armature in rpm
ntage of efficiency = (Output power/Input power) x 100.
Electrical Characteristics



Mechanical Characteristics.
Page 15/86


Kings College of Engineering/ EE1257/

Load Current Vs Torque, Speed Characteristics

TABULATION:

Radius of the brake drum(R) = Thickness of the

S
.
N
O

L
o
a
d


c
u
r
r
e
n
t

i
n

A
m
p
s

L
o
a
d

V
o
l
t
a
g
e

i
n

V
o
l
t
s

S
p
e
e
d

o
f

t
h
e

(I
L
) (V
L
)



RESULT:

Thus the load test is conducted and the performance curve is drawn
/Electrical Engineering &Control Systems Laboratory



Load Current Vs Torque, Speed Characteristics
Radius of the brake drum(R) = Thickness of the belt (
S
p
e
e
d

o
f

t
h
e

m
o
t
o
r


Spring balance
reading
T
o
r
q
u
e

N
-
m


O
u
t
p
u
t

p
o
w
e
r

I
n

w
a
t
t
s

I
n
p
u
t

p
o
w
e
r


s1

s2

s1-
s2

(N) Kg N-m W W

Thus the load test is conducted and the performance curve is drawn
Page 16/86
belt (t) =

V
L
I
L



W %
















Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 17/86

EXPT: 3.a. SWINBURNES TEST
DATE:

AIM:
To predetermine the efficiency of a given Dc shunt machine by Swinburnes test when
working as motor as well as Generator and also to draw the characteristics curves.

NAME PLATE DETAILS:


FUSE RATING:

No load: 10% of rated current (Full load current).

APPARATUS REQUIRED:


S.NO
NAME OF THE
APPARATUS

TYPE

RANGE

QUANTITY






PRECAUTION:
(i) The motor field rheostat should be kept at minimum resistance position.
(ii) The motor should be at no load condition throughout the experiment.

PROCEDURE:
1. Connections are made as per the circuit diagram.
2. The machine is run as a motor under no load at its rated voltage.
3. The speed is adjusted to its rated speed using a rheostat in the field circuit.
4. The input voltage, no load current and the field current are noted down.
5. Calculations are done for motor and generator.

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 18/86

CIRCUIT DIAGRAM:



FORMULAE:

Constant Losses Wc = VIo (Io Ish)
2
Ra Watts.

AS A MOTOR:
Input power = V
L
I
L
Watts
Ia =I
L
If Amps.
Armature Cu loss = Ia
2
Ra Watts.
Total Loss = Wc + Cu loss Watts.
Output power = Input Total loss Watts.
% Efficiency = Output/Input * 100.

AS A GENERATOR:
Ia =I
L
+ If Amps.
Armature Cu loss = Ia
2
Ra Watts.
Total Loss = Wc + Cu loss Watts.
Output power = V
L
I
L
Watts.
Input power = Output + Total loss Watts.
% Efficiency = Output/Input * 100.

Kings College of Engineering/ EE1257/

DETERMINATION OF ARMATURE RESISTANCE:

PROCEDURE:
1. Connections are made as per the circuit diagram.
2. Supply is given by closing the DPST switch.
3. Readings of Ammeter and Voltmeter are noted.
4. Armature resistance in Ohms is calculated as R


TABULATION TO FIND ARMATURE RESISTANCE:

S.No. Voltage
V (Volts)





/Electrical Engineering &Control Systems Laboratory
DETERMINATION OF ARMATURE RESISTANCE:
1. Connections are made as per the circuit diagram.
2. Supply is given by closing the DPST switch.
3. Readings of Ammeter and Voltmeter are noted.
Ohms is calculated as R
a
= (Vx1.5) /I
ARMATURE RESISTANCE:
Voltage
V (Volts)
Current
I (Amps)
Armature Resistance
R
a
(Ohms)






Page 19/86

Armature Resistance

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 20/86

TABULATION TO FIND THE CONSTANT LOSSES:

S. No Terminal
Voltage
No Load
Current
Field
Current
No Load
Armature
Current(Iao)
Constant Loss
Wco= V
Io
Iao
2
Ra

V A A A W












RESULTANT TABULATION TO FIND OUT THE EFFICIENCY RUNNING AS MOTOR

Armature Resistance (Ra) = Rated Current (If) =
Constant Loss (Wco) = Field Current (If) =
Terminal Voltage (V) =


RUNNING AS MOTOR

CALCULATION OF EFFICIENCY:

S.NO Fraction
of load
(X)
Load
current
I
L
=Xxlr
Armature
current
Ia= I
L
Ir
Armature
cu loss
Wcu
=Ia
2
Ra
Total
loss
W
Total

Input
power
Wi=V
I
L

Output
power
Wo=Wi-
W
Total

Efficiency

=Wo/Wi
A W W W W W %
1
2
3
4 1







Kings College of Engineering/ EE1257/

RUNNING AS GENERATOR
CALCULATION OF EFFICIENCY:

SNO Fraction
of load
(X)
Load
current
I
L
=Xxl
r
Armature
current
Ia= I
A
1
2
3
4 1


MODEL GRAPH:







RESULT:
Thus the efficiency of a given DC shunt machine is calculated by conducting
Swinburnes test.
/Electrical Engineering &Control Systems Laboratory
RUNNING AS GENERATOR

CALCULATION OF EFFICIENCY:
Armature
current
Ia= I
L
Ir
Armature
cu loss
Wcu
=Ia
2
Ra
Total
loss
W
Total

Input
power
Wi=V I
L

Output
power
Wo=Wi
W
Total
W W W W W








Thus the efficiency of a given DC shunt machine is calculated by conducting
Page 21/86
Output
power
Wo=Wi-
Total

Efficiency

=Wo/Wi
W %




Thus the efficiency of a given DC shunt machine is calculated by conducting

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 22/86

EXPT: 3.b. SPEED CONTROL OF DC SHUNT MOTOR.
DATE:

AIM:
To plot the variation of speed by varying the armature voltage at a particular field current
and by varying the field current at a particular armature voltage.

NAME PLATE DETAILS:



FUSE RATING:

40% of rated current (Full load current).


APPARATUS REQUIRRED:



S.NO
NAME OF THE
APPARATUS

TYPE

RANGE

QUANTITY






PRECAUTIONS:
1. Armature rheostat must be kept at maximum resistance position.
2. Field rheostat should be kept at minimum resistance minimum position.






Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 23/86

PROCEDURE:

(a).ARMATURE CONTROL METHOD:
The connections are made as per the circuit diagram.
Put on the main switch and start the motor, following the precaution.
Bring the rated value of the speedby varying both armature and field rheostats.
Adjust convenient field current and note armature voltage & speed.
Vary the speed by varying the armature rheostat.At each step note the speed & armature
voltage.
Now set up a new value of field current and the above procedure is repeated.
The graphs are drawn between speed & armature voltage for various field current.

(b). FLUX CONTROL METHOD:

The connections are made as per the circuit diagram.
Put on the main switch and start the motor, following the precaution.
Bring the rated value of the speedby varying both armature and field rheostats.
Adjust convenient armature voltage and note the field current & speed.
Vary the field current by varying the field rheostat.At each step note the speed & field
current.
Now set up a new value of armature voltage and the above procedure is repeated.
The graphs are drawn between speed & field current for various armature voltages.














Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 24/86

TABULATION:

ARMATURE CONTROL METHOD:


S.No.

Field Current If = A Field Current If = A
Armature
Voltage (Va)
in Volts
Speed (N)
in RPM
Armature
Voltage Va
V
Speed N
RPM
1.


2.


3


4


5


6




FIELD CONTROL METHOD:


S.No.

Armature Voltage Va= V Armature Voltage Va = V
Field Current(If)
in Amps
Speed (N)
in RPM
Field Current(If)
in Amps
Speed (N)
in RPM
1.


2.


3


4


5


6







Kings College of Engineering/ EE1257/

CIRCUIT DIAGRAM:



GRAPH:
Armature Voltage Vs Speed.
Field Current Vs Speed.





RESULT:
The variation of speed with change in armature voltage and in field current has been
studied ang graphs are plotted.






/Electrical Engineering &Control Systems Laboratory
Speed.
.

e variation of speed with change in armature voltage and in field current has been
Page 25/86

e variation of speed with change in armature voltage and in field current has been

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 26/86


EXPT: 4. a. LOAD TEST ON SINGLE PHASE TRANSFORMER
DATE:

AIM:
To conduct the load test on a given single phase transformer and to draw its performance
curves.

NAME PLATE DETAILS:
Transformer Auto Transformer

FUSE RATING:

Primary current = KVA Rating of the transformer / Primary voltage

Secondary current = KVA Rating of the transformer / Secondary voltage

125 % of Primary current (fuse rating for primary side)

125 % of Secondary current (fuse rating for secondary side).

APPARATUS REQUIRED:


S.NO
NAME OF THE
APPARATUS

TYPE

RANGE

QUANTITY





PRECAUTION:
At the time of starting transformer should be at no load condition.
High voltage and low voltage sides of the transformer should be properly used as primary
or secondary respective experiments.




Kings College of Engineering/ EE1257/

PROCEDURE:
Connections are given as per the circuit diagram.
The SPST Switch on the primary side is closed
side is opened.
The Autotransformer is adjusted to energize the transformer with rated primary voltage.
The Voltmeter and Ammeter readings are noted and tabulated at no load condition.
The DPST switch on the secondary
The transformer is loaded up to 130% of the Rated load, corresponding Ammeter,
Voltmeter and Wattmeter readings are noted and tabulated.
The tabulation for load test on single
After the observation of all the readings the load is released gradually to its initial
position.
The Autotransformer is brought to its initial position.
The Supply is switched off.
The graph for load test on single


MODEL GRAPH:




/Electrical Engineering &Control Systems Laboratory
Connections are given as per the circuit diagram.
The SPST Switch on the primary side is closed and the DPST Switch on the Secondary
The Autotransformer is adjusted to energize the transformer with rated primary voltage.
The Voltmeter and Ammeter readings are noted and tabulated at no load condition.
on the secondary side is closed.
The transformer is loaded up to 130% of the Rated load, corresponding Ammeter,
Voltmeter and Wattmeter readings are noted and tabulated.
The tabulation for load test on single-phase transformer is shown in table 6.2.
f all the readings the load is released gradually to its initial
The Autotransformer is brought to its initial position.
The Supply is switched off.
The graph for load test on single-phase transformer is shown in fig 6.2.
Page 27/86
and the DPST Switch on the Secondary
The Autotransformer is adjusted to energize the transformer with rated primary voltage.
The Voltmeter and Ammeter readings are noted and tabulated at no load condition.
The transformer is loaded up to 130% of the Rated load, corresponding Ammeter,
phase transformer is shown in table 6.2.
f all the readings the load is released gradually to its initial


Kings College of Engineering/ EE1257/





CIRCUIT DIAGRAM:

FORMULAE:

Input Power = (Wattmeter reading
Where,
(Rating of pressure coil
Multiplication factor =
Full

Output Power = (V
SY
I
SY
Where,
V
SY
= Secondary Voltage in V.
I
SY
= Secondary current in A.
Output Power
% Efficiency = Input Power

/Electrical Engineering &Control Systems Laboratory
Input Power = (Wattmeter reading Multiplication factor) in Watts
(Rating of pressure coil Rating of current coil pf)

Full-scale reading
SY
cos ) in Watts
= Secondary Voltage in V.
Secondary current in A.
Output Power
Input Power 100
Page 28/86

pf)

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 29/86

V
NL
V
LOAD
x100
% Regulation = V
LOAD
Where,
V
NL
= No load voltage in V.
V
LOAD
= Load voltage in V.

TABULATION:


S.No
Primary
Voltage
(V
PY
)
Primary
Current
(I
PY
)
Sry
Voltage
(V
SY
)
Sry
Current
(I
SY
)
Wattmeter
readings (W)
Input
Power
(W)
Output
Power


%Regn.

Obs. Act.
V A V A W W W W %






RESULT:

Thus the load test on single-phase transformer is conducted and performance
characteristics curves are drawn.


Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 30/86

EXPT: 4. b. OPEN CIRCUIT AND SHORT CIRCUIT TEST ON SINGLE PHASE
TRANSFORMER
DATE:

AIM:
To predetermine the efficiency and Regulation of a given single Phase transformer by
conducting the open circuit test and also to drive its Equivalent circuit.

NAME PLATE DETAILS:
Transformer Auto Transformer

FUSE RATING:

Primary Current=KVA Rating of the Transformer/Primary Voltage.
Secondary Current= KVA Rating of the Transformer/Secondary Voltage.
10% of Primary current (fuse rating for open circuit test).
125% of secondary current (fuse rating for Short circuit test).
APPARATUS REQUIRED:


S.NO
NAME OF THE
APPARATUS

TYPE

RANGE

QUANTITY





PRECAUTIONS:

At the time of startling transformer should be at no load condition.
High voltage and low voltage sides of the transformer should be properly used a primary
secondary respective for the experiments.


Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 31/86

OPEN CIRCUIT TEST:

Connections are made as per the circuit diagram.
The SPST Switch on the primary side is closed.
The autotransformer is adjusted to energise the transformer with rated primary voltage on
the LV side.
The voltmeter, Wattmeter and Ammeter Readings are noted at no load condition.
The auto transformer is brought to its initial position.
The supply is switched off.
SHORT CIRCUIT TEST:

Connections are made as per the circuit diagram.
The SPST Switch on the primary side is closed.
The autotransformer is adjusted to energise the transformer with rated primary voltage on
the HV side.
The voltmeter, Wattmeter and Ammeter Readings are noted at short circuit condition.
The auto transformer is brought to its initial position.
The supply is switched off.
FORMULAE:

OPEN CIRCUIT TEST:
No load Power Factor (cos
0
)=W
oc
/V
oc
xI
oc

Where, Woc-open circuit power in W
V
oc
- open circuit voltage in V
I
oc
- open circuit current in A
No load Working component Resistance (Ro)= V
oc
/I
oc
x cos
0
In
Where,
V
oc
- open circuit voltage in V
I
oc
- open circuit current in A
No load Magnetizing Component Current Reactance (X
o
)= V
oc
/I
oc
xsin
0
in
Where,
V
oc
- open circuit voltage in V
I
oc
- open circuit current in A

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 32/86

SHORT CIRCUIT TEST:
Equivalent impedance referred to HV side (Z02)=Vsc/Isc in
Where,
Voc- short circuit voltage in V
Ioc - short circuit current in A
Equivalent resistance referred to HV side (R02)=Wsc/Isc
2
in
Where, Wsc -short circuit power in W
Equivalent resistance referred to HV side(X02) = Z
2
02 - R
2
02 in
Transformer ratio (K)=V2/V1
Where, V1 =Primary voltage in V
V2=Secondary voltage in V
Equivalent resistance referred to LV side (R01) = R02/K
2
in
Equivalent resistance referred to LV side(X01) = X02/K
2
in

EFFICIENCY AND REGULATION:
Output Power=(X*KVA*cos )in W
Where, X=Fraction of load
KVA=Power Rating of Transformer
cos =power factor
Copper loss=(X
2
*Wsc )in W
Where, Wsc-copper loss in short circuit condition
Total loss=(cu loss+iron loss)in W
Efficiency= output power/(output power+total losses)x100%
Regulation=X*Isc[R02* cos +X02*sin ]/V2
0
*100%
Where,V2
0-
open circuit voltage on HV side +for lagging-for lagging.







Kings College of Engineering/ EE1257/

CIRCUIT DIAGRAM:
OPEN CIRCUIT DIAGRAM:


SHORT CIRCUIT DIAGRAM:





/Electrical Engineering &Control Systems Laboratory

Page 33/86



Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 34/86

TABULATION:
OPEN CIRCUIT TEST:

V
O
Volts
I
O
Amps
Wattmeter Reading
(mf = )
Observed W
O
ActualW
O
x mf
Watts






SHORT CIRCUIT TEST:

V
SC
Volts
I
SC
Amps
Wattmeter Reading
(mf = )
Observed
W
SC
Actual W
SC
x mf
Watts







PREDETERMINATION OF EFFICIENCY AT DIFFERENT LOADS:

(i) At Unity Power Factor

Load
Current
I
Amps
% of full
load
X
(as
decimal
fraction)
Input
Losses
W
i
= W
O
x
mf
Watts
W
C
=
X
2
W
SC
x
mf
Watts
Total
Losses
W
i
+W
C
Watts
Output
Power

Watts
Input
Power

Watts
Efficiency

%

(0.25)

(0.5)
(0.75)
1(full
load)


Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 35/86


(ii) At 0.8 Power Factor (lag)

Load
Current
I
Amps
% of full
load
X
(as
decimal
fraction)
Input
Losses
W
i
= W
O
x
mf
Watts
W
C
=
X
2
W
SC
x
mf
Watts
Total
Losses
W
i
+W
C
Watts
Output
Power

Watts
Input
Power

Watts
Efficiency

%

(0.25)

(0.5)
(0.75)
1(full
load)





GRAPHS:

% Regulation Vs power factor
Output power Vs efficiency











RESULT:
Thus the OC & SC test on single phase transformer was performed and the respective graphs
were drawn.


Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 36/86

EX NO: 5. REGULATION OF THREE PHASE ALTERNATOR BY EMF AND MMF
METHODS.
DATE:

AIM:
To predetermine the regulation of three phase alternator by EMF and MMF methods and
also draw the vector diagrams.

NAME PLATE DETAILS:

3 Alternator DC Shunt Motor



FUSE RATING:

125% Of Rated Current (Full Load Current)

For DC Shunt Motor: Amps

For Alternator: Amps

APPARATUS REQUIRED:









PRECAUTIONS:
The motor field rheostat should be kept in the minimum resistance position.
The alternator field potential divider should be in minimum voltage position.
Initially all switches are in open position.


S.NO
NAME OF THE
APPARATUS

TYPE

RANGE

QUANTITY





Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 37/86

PROCEDURE: (FOR BOTH EMF AND MMF METHODS):

Note down the name plate details of the motor and alternator.
Connections are made as per the circuit diagram.
Switch ON the supply by closing the DPST switch.
Using the Three point starter, start the motor to run at the synchronous speed by adjusting
the motor field rheostat.
Conduct Open Circuit test by varying the potential divider for various values of field
current and tabulate the corresponding Open Circuit Voltage readings.
Conduct Short Circuit test by closing the TPST switch and adjust the potential divider to
set the rated armature current and tabulate the corresponding field current.
The Stator resistance per phase is determined by connecting any one phase stator winding
of the alternator as per the circuit diagram using MC voltmeter and ammeter of suitable
ranges.

FORMULAE:
1. Armature Resistance Ra =

2. Synchronous Impedance Zs = O.C. voltage
S.C. current

3. Synchronous Reactance Xs = Zs
2
Ra
2


4. Open circuit voltage for lagging p.f = (Vcos + IaRa)
2
+ (Vsin + IaXs)
2


5. Open circuit voltage for leading p.f. = (Vcos + IaRa)
2
+ (Vsin IaXs)
2


6. Open circuit voltage for unity p.f = (V + IaRa)
2
+ ( IaXs)
2


7. Percentage regulation = Eo V x 100
V


Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 38/86

TABULATION:


OPEN CIRCUIT TEST:


S.No.
Field
Current (If)
Open Circuit
Line Voltage
(Vo
L
)
Open circuit
Phase Voltage
(Voph)
Amps Volts Volts





SHORT CIRCUIT TEST:


S.No.

Field Current (If)

Short Circuit Current
(120% to 150% of
rated current) (I
SC
)
Amps Amps




























Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 39/86

EMF METHOD:


SL.NO.

Power
factor

Eph (V) % Regulation

Lag

Lead

Lag

Lead















MMF METHOD:


S.NO.

P.F

Vph
(V)

If1
(A)

If2
(A)

Ifr
(A)
Eph (V) % Regulation
Lag Lead Lag Lead Lag Lead






















Kings College of Engineering/ EE1257/

CIRCUIT DIAGRAM:



PROCEDURE TO DRAW GRAPH FOR EMF METHOD:

Draw the Open Circuit Charact
current).
Draw the Short Circuit Characteristics curve (Short circuit current VS Field current)
From the graph find the open circuit voltage per phase (E
current (Isc).
By using respective formulae find the Zs, Xs, Eo and percentage regulation



/Electrical Engineering &Control Systems Laboratory
PROCEDURE TO DRAW GRAPH FOR EMF METHOD:
Draw the Open Circuit Characteristic curve (Generated Voltage per phase VS Field
Draw the Short Circuit Characteristics curve (Short circuit current VS Field current)
From the graph find the open circuit voltage per phase (E
1
(ph) for the rated short circuit
By using respective formulae find the Zs, Xs, Eo and percentage regulation
Page 40/86

eristic curve (Generated Voltage per phase VS Field
Draw the Short Circuit Characteristics curve (Short circuit current VS Field current).
(ph) for the rated short circuit
By using respective formulae find the Zs, Xs, Eo and percentage regulation.

Kings College of Engineering/ EE1257/

MODELGRAPH OF EMF:


PROCEDURE TO DRAW GRAPH FOR MMF METHOD:

Draw the Open Circuit Characteristic curve (Generated Voltage per phase VS Field
current).
Draw the Short Circuit Characteristics curve (Short circuit current VS Field current)
From the OCC find the field current
From SCC find the magnitude of field
current.
Draw If2 at angle (90+) from
current is leading, take the
Find the resultant field current,
From OCC. find the voltage




/Electrical Engineering &Control Systems Laboratory

PROCEDURE TO DRAW GRAPH FOR MMF METHOD:
Draw the Open Circuit Characteristic curve (Generated Voltage per phase VS Field
Characteristics curve (Short circuit current VS Field current)
From the OCC find the field current If1 to produce rated voltage V.
From SCC find the magnitude of field current If2 to produce the required
at angle (90+) from If1, where is the phase angle of current fromvoltage. If
current is leading, take the angle of If2 as (90-).
Find the resultant field current, If and mark its magnitude on the field current
From OCC. find the voltage corresponding to If, which will be E0.
Page 41/86
Draw the Open Circuit Characteristic curve (Generated Voltage per phase VS Field
Characteristics curve (Short circuit current VS Field current).
to produce the required armature
is the phase angle of current fromvoltage. If
mark its magnitude on the field current axis.

Kings College of Engineering/ EE1257/

MODEL GRAPH OF MMF:









RESULT:

Thus the regulation of three phase alternator was calculated by EMF and MMF methods.





/Electrical Engineering &Control Systems Laboratory



Thus the regulation of three phase alternator was calculated by EMF and MMF methods.
Page 42/86
Thus the regulation of three phase alternator was calculated by EMF and MMF methods.

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 43/86

EX NO: 6. LOAD TEST ON THREE PHASE INDUCTION MOTOR.
DATE:

AIM:
To conduct the load test on three phase squirrel cage induction motor and to draw the
performance characteristic curves.

NAME PLATE DETAILS:
3 Induction Motor


APPARATUS REQUIRED:












FUSE RATING:

125% of rated current(full load current)= Amps

FORMULAE USED:

1.Torque=(S
1
-S
2
)(R+t/2)*9.81 N-m
where , S
1
-S
2
-spring balance in kg
R=radius of the brake drum
T=thickness of the belt in m.
2. Output power=2NT/60 W
Where N-rotor speed in rpm
T-torque in N-m
3. Input power=(W
1
+W
2
) W
W
1
,W
2
-wattmeter readings in W
4. Percentage of efficiency=(output power/input power)*100%

S.NO
NAME OF THE
APPARATUS

TYPE

RANGE

QUANTITY





Kings College of Engineering/ EE1257/

PRECAUTIONS:
TPST switch is kept open initially.
Autotransformer is kept at min. voltage position.
There must be no load when starting the load.
PROCEDURE:
Connections are given as per circuit diagram.
3- induction motor is started by using auto transformer.
If the pointer of one of the wattmeter readings reverses, interchange the current coil
terminals and take the rea
The no load readings are taken.
The motor is loaded step by step till we get the rated current and the readings of the
voltmeter, ammeter, wattmeters, spring balance are noted.

CIRCUIT DIAGRAM:







/Electrical Engineering &Control Systems Laboratory
TPST switch is kept open initially.
Autotransformer is kept at min. voltage position.
oad when starting the load.
Connections are given as per circuit diagram.
induction motor is started by using auto transformer.
If the pointer of one of the wattmeter readings reverses, interchange the current coil
terminals and take the reading as negative.
The no load readings are taken.
The motor is loaded step by step till we get the rated current and the readings of the
voltmeter, ammeter, wattmeters, spring balance are noted.
Page 44/86
If the pointer of one of the wattmeter readings reverses, interchange the current coil
The motor is loaded step by step till we get the rated current and the readings of the


Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 45/86

TABULATION:



GRAPHS:

Output Power vs Efficiency
Output Power vs Torque
Output Power vs Speed
Output Power vs %s






RESULT:
Thus the performance characteristics of a 3- squirrel cage induction motor by
conducting load test have been drawn.

S.NO

V
L



I
L


Input power
Speed
of the
motor
(N)
Spring
Balance
Reading Torque O/P
Slip
(S)
Power
Factor
Obs Act S
1
S
2

S
1
-
S
2

V A W W RPM Kg W Kg N-m W % %


Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 46/86

EX NO: 7. NO LOAD AND BLOCKED ROTOR TESTS ON THREE PHASE
INDUCTION MOTOR
DATE:

AIM:
To conduct the no load & blocked rotor test on 3- phase induction motor & to draw the
equivalent circuit of 3- phase squirrel cage induction motor.

NAME PLATE DETAILS:
3 Induction Motor


APPARATUS REQUIRED:












FUSE RATING:

125% of rated current (full load current)= Amps

PRECAUTIONS:
NO LOAD TEST:
Initially TPST switch is kept open.
Autotransformer must be kept at minimum potential position.
The machine must be started at no load.
BLOCKED ROTOR TEST:
Initially the TPST switch is kept open.
Autotransformer must be kept at minimum potential position.
The machine should be started on full load.

S.NO
NAME OF THE
APPARATUS

TYPE

RANGE

QUANTITY





Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 47/86

PROCEDURE:
NO LOAD TEST:
Connections are given as per the circuit diagram.
Precautions are observed and motor is started on the no load.
Autotransformer is varied to have rated voltage applied.
The meter readings are then tabulated.
BLOCKED ROTOR TEST:
Connections are given as per circuit diagram.
Precautions are observed and motor is started on full load or blocked rotor position.
Autotransformer is varied to have rated current flowing in motor.
The meter readings are then tabulated.

FORMULA USED:
FOR NO LOAD TEST:

Wsc = 3 V
o
I
o
COS watts
I
w
= I
o
cos amps
R
o
= V
0
/ I
w

X
o
= V
o
/I
u


FOR BLOCKED ROTOR TEST:

Wsc =3*I
2
*R
o
watts
Ro1 = Wsc/3*(Isc)
2

Zo1 = Vsc/Isc
Xo1 = ((Zo1)
2
-(Ro1)
2
)






Kings College of Engineering/ EE1257/

CIRCUIT DIAGRAM:
NO LOAD TEST:



BLOCKED ROTOR TEST:


/Electrical Engineering &Control Systems Laboratory Page 48/86



Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 49/86



EQUIVALENT CIRCUIT:










RESULT:
Thus the no load test and blocked rotor test on three phase squirrel cage induction motor
was conducted and the corresponding equivalent circuit was drawn.




Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 50/86

EX NO: 8. STUDY OF D.C. MOTOR AND INDUCTION MOTOR STARTERS.
DATE:



AIM:
To Study the DC and AC motor starters.

NECESSITY OF STARTER IN INDUCTION MOTOR:

In a three phase induction motor, the magnitude of an induced e.m.f. in the rotor circuit
depends on the slip of the induction motor. This induced e.m.f. effectively decides the
magnitude of the rotor current. The rotor current in the running condition is given by,
sE
2
I
2r
=
R
2
2
+ (s
2
)
2

But at start, the speed of the motor is zero and slip is at its maximum i.e. unity. So
magnitude of rotor induced e.m.f. is very large at start. As rotor conductors are short circuited,
the large induced e.m.f. circulates very high current through rotor at start.
The condition is exactly similar to a transformer with short circuited secondary. Such a
transformer when excited by a rated voltage circulates very high current through short circuited
secondary. As secondary current is large, the primary also draws very high current from the
supply.
Similarly in a three phase induction motor, when rotor current is high, consequently the
stator draws a very high current from the supply. This current can be of the order of 5 to 8 times
the full load current, at start.
Due to such heavy inrush of current at start there is possibility if damage of the motor
winding. Similarly such sudden inrush of current causes large line voltage drop. Thus other
appliances connected to the same line may be subjected to voltage spikes which may affect their
working. To avoid such effects, it is necessary to limit the current drawn by the motor at start.

Kings College of Engineering/ EE1257/

The starter is a device which is basically used to limit high starting current by supplying reduced
voltage to the motor at the time of starting. Such a reduced voltage is applied only for short
period and once rotor gets accelerated, full normal rated
Not only the starter limits the starting current but also provides the protection to the
induction motor against overt loading and low voltage situations. The protection against single
phasing is also provided by the starter. The ind
withstand starting currents hence such motors can be started directly on line. But such motors
also need overload, single phasing and low voltage protection which is provided by a starter.

STAR DALTA STARTER:




This is the cheapest starter of all and hence used very commonly for the induction
motors. It uses triple pole double throw (TPDT) switch. The switch connects the stator winding
in star at start. Hence per phase voltage gets reduced by the factor
voltage, the starting current is limited. When the switch is thrown on other side, the winding gets
/Electrical Engineering &Control Systems Laboratory
is a device which is basically used to limit high starting current by supplying reduced
voltage to the motor at the time of starting. Such a reduced voltage is applied only for short
period and once rotor gets accelerated, full normal rated voltage is applied.
Not only the starter limits the starting current but also provides the protection to the
induction motor against overt loading and low voltage situations. The protection against single
phasing is also provided by the starter. The induction motors having rating below 5 h.p. can
withstand starting currents hence such motors can be started directly on line. But such motors
also need overload, single phasing and low voltage protection which is provided by a starter.
This is the cheapest starter of all and hence used very commonly for the induction
motors. It uses triple pole double throw (TPDT) switch. The switch connects the stator winding
in star at start. Hence per phase voltage gets reduced by the factor 1 / 3. Due to this reduced
voltage, the starting current is limited. When the switch is thrown on other side, the winding gets
Page 51/86
is a device which is basically used to limit high starting current by supplying reduced
voltage to the motor at the time of starting. Such a reduced voltage is applied only for short
Not only the starter limits the starting current but also provides the protection to the
induction motor against overt loading and low voltage situations. The protection against single
uction motors having rating below 5 h.p. can
withstand starting currents hence such motors can be started directly on line. But such motors
also need overload, single phasing and low voltage protection which is provided by a starter.

This is the cheapest starter of all and hence used very commonly for the induction
motors. It uses triple pole double throw (TPDT) switch. The switch connects the stator winding
3. Due to this reduced
voltage, the starting current is limited. When the switch is thrown on other side, the winding gets

Kings College of Engineering/ EE1257/

connected in delta, across the supply. So it gets normal rated voltage. The windings are
connected in delta when motor gathe
shown in the Fig.3.3. The operation of the switch can be automatic by using relays which ensures
that motor will not start with the switch in Run position. The cheapest of all and maintenance
free operation are the two important advantages of this starter. While is limitations are, it is
suitable for normal delta connected motors and the factor by while voltage change is 1
cannot be changed.

STATOR RESISTANCE STARTER:



In order to apply the reduced voltage to the stator of the induction motor
are added in series with each phase of the stator winding. Initially the resistances are kept
maximum in the circuit. Due to this large voltage gets dropped acr
reduced voltage gets applied to the stator, which reduces the high starting current. The
schematic diagram showing stator resistances is shown in the Fig.3.1. When the motor starts
running, the resistances are gradually cut o
entirely removed from the stator circuit i.e. rheostats in RUN position then rated voltage gets
applied to the stator. Motor runs with normal speed. The starter is simple in construction and
/Electrical Engineering &Control Systems Laboratory
connected in delta, across the supply. So it gets normal rated voltage. The windings are
connected in delta when motor gathers sufficient speed. The agreement of star
shown in the Fig.3.3. The operation of the switch can be automatic by using relays which ensures
that motor will not start with the switch in Run position. The cheapest of all and maintenance
free operation are the two important advantages of this starter. While is limitations are, it is
suitable for normal delta connected motors and the factor by while voltage change is 1
STATOR RESISTANCE STARTER:
In order to apply the reduced voltage to the stator of the induction motor,
are added in series with each phase of the stator winding. Initially the resistances are kept
maximum in the circuit. Due to this large voltage gets dropped across the resistances. Hence a
reduced voltage gets applied to the stator, which reduces the high starting current. The
schematic diagram showing stator resistances is shown in the Fig.3.1. When the motor starts
running, the resistances are gradually cut off from the stator circuit. When the resistances are
entirely removed from the stator circuit i.e. rheostats in RUN position then rated voltage gets
applied to the stator. Motor runs with normal speed. The starter is simple in construction and
Page 52/86
connected in delta, across the supply. So it gets normal rated voltage. The windings are
rs sufficient speed. The agreement of star delta starter is
shown in the Fig.3.3. The operation of the switch can be automatic by using relays which ensures
that motor will not start with the switch in Run position. The cheapest of all and maintenance
free operation are the two important advantages of this starter. While is limitations are, it is
suitable for normal delta connected motors and the factor by while voltage change is 1 3 which

, three resistances
are added in series with each phase of the stator winding. Initially the resistances are kept
oss the resistances. Hence a
reduced voltage gets applied to the stator, which reduces the high starting current. The
schematic diagram showing stator resistances is shown in the Fig.3.1. When the motor starts
ff from the stator circuit. When the resistances are
entirely removed from the stator circuit i.e. rheostats in RUN position then rated voltage gets
applied to the stator. Motor runs with normal speed. The starter is simple in construction and

Kings College of Engineering/ EE1257/

cheap. It can be used for both star and delta connected stator. But there are large power losses
due to resistances. Also the starting torque of the motor reduces due to reduced voltage applied
to the stator.

AUTOTRANSFORMER STARTER:



A three phase star connected autotransformer can be used to reduce the
the stator. Such a starter is called an autotransformer starter. The schematic diagram of
autotransformer starter is shown in the Fig.
switch is in the start position, the stator winding is supplied with reduced voltage. This can be
controlled by tapping provide with autotransformer. When motor gathers 80% of the normal
speed, the change over switch is thrown into run position. Due
/Electrical Engineering &Control Systems Laboratory
t can be used for both star and delta connected stator. But there are large power losses
due to resistances. Also the starting torque of the motor reduces due to reduced voltage applied
AUTOTRANSFORMER STARTER:
nected autotransformer can be used to reduce the voltage applied to
the stator. Such a starter is called an autotransformer starter. The schematic diagram of
starter is shown in the Fig. It consists of a suitable change over switch. When
switch is in the start position, the stator winding is supplied with reduced voltage. This can be
controlled by tapping provide with autotransformer. When motor gathers 80% of the normal
speed, the change over switch is thrown into run position. Due to this, rated voltage gets applied
Page 53/86
t can be used for both star and delta connected stator. But there are large power losses
due to resistances. Also the starting torque of the motor reduces due to reduced voltage applied

oltage applied to
the stator. Such a starter is called an autotransformer starter. The schematic diagram of
It consists of a suitable change over switch. When the
switch is in the start position, the stator winding is supplied with reduced voltage. This can be
controlled by tapping provide with autotransformer. When motor gathers 80% of the normal
to this, rated voltage gets applied

Kings College of Engineering/ EE1257/

to stator winding. The motor starts rotating with normal speed. Changing of switch is done
automatically by using relays. The power loss is much less in this type of starting. It can be
used for both star and delta connected motors. But it is expensive than stator resistance starter.

ROTOR RESISTANCE STARTER:

To limit the rotor current which consequently reduces the current drawn by the motor
from the supply, the resistance can be inserted in the rotor circuit at
resistance in rotor is in the form of 3 phase star connected rheostat. The arrangement is shown in
the Fig.3.4. The external resistance is inserted in each phase of the rotor winding through slip
ring and brush assembly. Initially maximum resistance is in the circuit. As motor gathers speed,
the resistance is gradually cutoff. The operation may be manual or automatic. We have seen that
the starting torque is proportional to the rotor resistance. Hence important advantage of
method is not only the starting current is limited but starting torque of the motor also gets
improved. The only limitation of the starter is that it can be used only for slip ring induction
motors as in squirrel cage motors; the rotor is permanentl

DIRECT ON LINE STARTER (D.O.L):
In case of small capacity motors having rating less than 5 h.p., the starting current is not
very high and such motors can withstand such starting current without any starter. Thus there is
no need to reduce applied voltage, to control the starting current. Such motors use a type of
/Electrical Engineering &Control Systems Laboratory
to stator winding. The motor starts rotating with normal speed. Changing of switch is done
automatically by using relays. The power loss is much less in this type of starting. It can be
onnected motors. But it is expensive than stator resistance starter.
ROTOR RESISTANCE STARTER:
To limit the rotor current which consequently reduces the current drawn by the motor
from the supply, the resistance can be inserted in the rotor circuit at start. This addition of the
resistance in rotor is in the form of 3 phase star connected rheostat. The arrangement is shown in
the Fig.3.4. The external resistance is inserted in each phase of the rotor winding through slip
tially maximum resistance is in the circuit. As motor gathers speed,
the resistance is gradually cutoff. The operation may be manual or automatic. We have seen that
the starting torque is proportional to the rotor resistance. Hence important advantage of
method is not only the starting current is limited but starting torque of the motor also gets
improved. The only limitation of the starter is that it can be used only for slip ring induction
motors as in squirrel cage motors; the rotor is permanently short circuited.
DIRECT ON LINE STARTER (D.O.L):
In case of small capacity motors having rating less than 5 h.p., the starting current is not
very high and such motors can withstand such starting current without any starter. Thus there is
educe applied voltage, to control the starting current. Such motors use a type of
Page 54/86
to stator winding. The motor starts rotating with normal speed. Changing of switch is done
automatically by using relays. The power loss is much less in this type of starting. It can be
onnected motors. But it is expensive than stator resistance starter.

To limit the rotor current which consequently reduces the current drawn by the motor
start. This addition of the
resistance in rotor is in the form of 3 phase star connected rheostat. The arrangement is shown in
the Fig.3.4. The external resistance is inserted in each phase of the rotor winding through slip
tially maximum resistance is in the circuit. As motor gathers speed,
the resistance is gradually cutoff. The operation may be manual or automatic. We have seen that
the starting torque is proportional to the rotor resistance. Hence important advantage of this
method is not only the starting current is limited but starting torque of the motor also gets
improved. The only limitation of the starter is that it can be used only for slip ring induction
In case of small capacity motors having rating less than 5 h.p., the starting current is not
very high and such motors can withstand such starting current without any starter. Thus there is
educe applied voltage, to control the starting current. Such motors use a type of

Kings College of Engineering/ EE1257/

starter which is used to connect stator directly to the supply lines without any reduction in
voltage.


Hence the starter is known as direct
the applied voltage, it is used because it protects the motor from various severe abnormal
conditions like over voltage, single phasing etc. The Fig.3.5 shows the arrangement of various
components in direct on line starter. The NO contact is normally open and NC is normally
closed. At start, NO is pushed for fraction of second due to which coil gets energized and
attracts the contactor. So stator directly gets supply. The additional contact provided
that as long as supply in ON, the coil gets supply and keeps contactor in ON position. When NC
is pressed, the coil circuit gets opened due to which coil gets de
switched OFF from the supply. Under over load condition, c
due to which there is an excessive heat produced, which increase temperature beyond limit.
Thermal relays gets opened due to high temperature, protecting the motor from overload
conditions.

/Electrical Engineering &Control Systems Laboratory
starter which is used to connect stator directly to the supply lines without any reduction in

Hence the starter is known as direct on line starter. Though this starter does not reduce
the applied voltage, it is used because it protects the motor from various severe abnormal
conditions like over voltage, single phasing etc. The Fig.3.5 shows the arrangement of various
irect on line starter. The NO contact is normally open and NC is normally
closed. At start, NO is pushed for fraction of second due to which coil gets energized and
attracts the contactor. So stator directly gets supply. The additional contact provided
that as long as supply in ON, the coil gets supply and keeps contactor in ON position. When NC
is pressed, the coil circuit gets opened due to which coil gets de-energized and motor gets
switched OFF from the supply. Under over load condition, current drawn by the motor increase
due to which there is an excessive heat produced, which increase temperature beyond limit.
Thermal relays gets opened due to high temperature, protecting the motor from overload
Page 55/86
starter which is used to connect stator directly to the supply lines without any reduction in
on line starter. Though this starter does not reduce
the applied voltage, it is used because it protects the motor from various severe abnormal
conditions like over voltage, single phasing etc. The Fig.3.5 shows the arrangement of various
irect on line starter. The NO contact is normally open and NC is normally
closed. At start, NO is pushed for fraction of second due to which coil gets energized and
attracts the contactor. So stator directly gets supply. The additional contact provided, ensures
that as long as supply in ON, the coil gets supply and keeps contactor in ON position. When NC
energized and motor gets
urrent drawn by the motor increase
due to which there is an excessive heat produced, which increase temperature beyond limit.
Thermal relays gets opened due to high temperature, protecting the motor from overload

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 56/86


EX NO: 9. DIGITAL SIMULATION OF LINEAR SYSTEMS
DATE:

AIM:
To digitally simulate the time response characteristics of higher order MIMO linear
systems with step and impulse input.

EQUIPMENT:

System with MATLAB/MATHCAD.

THEORY:
A system is linear if it obeys the principle of super position and homogeneity. The
principle implies that if a system model has responses Y
1
(t) and Y
2
(t) to any inputs X
1
(t) and
X
2
(t)respectively. The system response to the linear combination of these inputs a
1
X
1
(t)+ a
2

X
2
(t) is given by linear combination of individual outputs a
1
Y
1
(t)+ a
2
Y
2
(t ) where a
1
and a
2
are
constant gains of the systems. A mathematical model will be linear if the differential equations
describing the system have constant coefficients. All physical systems are nonlinear in nature.
The presence of nonlinearity can be neglected and the system can be treated as a linear system.
The linear systems are broadly classified into two categories according to the no. of inputs and
no. of outputs. They are (i) single input single output system. (ii) Multiple input and multiple
output system.

(i)Single input and single output system
If a control system has one input and an output, it is termed as single input single output
(SISO) system.

(ii) Multiple input and multiple output system:
If a control system has multiple input and multiple output, it is known as Multiple input
multiple output system (MIMO)

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 57/86


PROCEDURE:
1. Open the mat lab command window from the startup or from the short cut
2. Type edit to open the tool box
3. Create the new file
4. Write the program
5. Save the program and run it
6 . Observe the wave form and verify the output with the theoretical values

(OR)

1. Open the MATLAB command window from the start up menu.
2. Click on file menu and select model.
3. Create a model file.
4. Get the blocks from the simulink library browser.
5. The input signals are in the source library.
6. The output can be viewed using the SCOPE block which are in the sinks library
7. Connect the blocks properly and simulate the block diagram.


DIGITAL SIMULATION OF THE LINEAR SYSTEM

OUTPUT RESPONSE OF THE FIRST ORDER SYSTEM WITH STEP INPUT
PROGRAM

Transfer function = 1/S+5
num = [0 1];
den = [1 5];
step(num,den)
grid;
title (First Order System of G(s) = 1/(S+5))

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 58/86


OUTPUT RESPONSE OF THE SECOND ORDER SYSTEM WITH STEP INPUT
PROGRAM:

Transfer function = 25/S^2+4s+25
num = [0 0 25];
den = [1 4 25];
step(num,den)
grid;
title (Unit step response of G(s) = 25/ (S^2+4s +25))

OUTPUT RESPONSE OF THE SECOND ORDER SYSTEM WITH IMPULSE INPUT
PROGRAM:

Transfer function = 1/S^2+0.2s+1
num= [0 1 0];
den = [1 0.2 1];
impulse(num,den)
grid;
title (Impulse Response of G(s) = 1 / (S^2+0.2s +1))


RESULT:
Thus the time response characteristics of higher order MIMO linear systems were
digitally simulated.







Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 59/86

EX NO: 10. STABILITY ANALYSIS OF LINEAR SYSTEM USING MATLAB.
DATE:

AIM:
To analyze the stability of the following Transfer function, Using
i) Bode plot = 25 / s
2
+4s+25
ii) Nyquist plot = 1 / s (s+1)
iii) Root locus plot = 1 / s
3
+4s
2
+5s

EXERCISE
1. Write a program to obtain the Bode/Root locus/Nyquist plot for a given system.
2. Access the stability of the given system using the plot obtained.
3. Compare the usage of various plot in assessing stability.

EQUIPMENT
System with MATLAB/MATHCAD.

DESCRIPTION:
i) Root locus:
Root locus is one in which the roots of characteristics equation are plotted for all values of
a system parameter. The roots corresponding to a particular value of this parameter can be
located on the resulting graph. By using root locus method the designer can predict the effects of
adding open poles and or open loop zeros.
ii) Bode diagram:
A bode diagram consists of two graphs. One is plot of the logarithm of the magnitude of a
sinusoidal transfer function and other in plot of phase angle.
iii)Nyquist Plot:
Nyquist Plots are a way of showing frequency responses of linear systems.

Nyquist plots display both amplitude and phase angle on a single plot, using frequency as a
parameter in the plot. Nyquist plots have properties that allow you to see whether a system is

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 60/86

stable or unstable. It will take some mathematical development to see that, but it's the most
useful property of Nyquist plots.

PROCEDURE
1. Open the mat lab command window from the start up or from the short cut.
2. Type edit to open the tool box.
3. Create the new file.
4. Write the program file.
5. Save the program and run it.
6. Observe the wave form and verify the output with the theoretical values.

STABILITY ANALYSIS OF NYQUIST PLOT PROGRAM:

Transfer function = 1/(S
2
+0.8S+1)
num = [0 0 1];
den = [1 0.8 1];
nyquist(num,den)
v = [-2 2 -2 2];
axis (v);
grid;
title (nyquist plot of G(S) = 1 / S^2+0.8S+1));

Conclusion: The given system is stable.

STABILITY ANALYSIS OF BODE PLOT PROGRAM

Transfer function = 25/ S
2
+4s+25
num = [0 0 25]
den [1 4 25];
bode(num,den)
grid;

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 61/86

title (Bode Plot of G(s) = 25 / (S^2+4S+25);

Conclusion: The given system is stable.

STABILITY ANALYSIS OF ROOT LOCUS PLOT PROGRAM

Transfer function = 1/ S
3
+4s
2
+5S
num = [0 0 0 1];
den= [1 4 5 0];
rlocus(num,den)
v = [-3 1 -2 2];
axis (v);
sgrid (0.5,[ ]);
title(Root Locus G(s) = 1 / (S^3+4S^2+5S));

Conclusion: The given system is stable.
MANUAL CALCULATION:









RESULT:
Thus the stability of given Transfer function using Bode/Root locus/ Nyquist plot was
analyzed using MATLAB software.



Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 62/86

EX NO: 11. STUDY THE EFFECT OF P, PI, PID CONTROLLERS USING MATLAB.
DATE:

AIM:
To find the percentage peak overshoot and steady state error of the given P, PI and PID.

APPARATUS REQUIRED:
MATLAB, SIMULINK.

THEORY:
A controller is similar to an amplifier. It is used in closed loop control system to enhance
the system output.
In proportional controller, the output is proportional to the input. K
p
represents the gain
constant of proportional contoller.



Where V
o
= output voltage
V
i
= input voltage
R
f
= feedback resistance
R
i
= input resistance
K
p
= gain constant
The control action of proportional plus integral controller is defined by the equation
V
o
(t) = K
p
V
i
(t) + V
i
(t) (K
p
/ T
i
)
The transfer function of the controller is
T.F = V
o
(s) / V
i
(s) = K
p
(1 + 1 / sT
i
)
Where V
o
= output voltage

V
i
= input voltage
T
i
= integral time constant
K
p
= gain constant
I
F
i
O
P
R
R
V
V
K + = = 1

Kings College of Engineering/ EE1257/

Both K
p
and T
i
are adjustable. The integral time
changed in the values of K
p
affects both the integral parts of the control action. The inverse of
integral time T
i
is called the reset rate.
The reset rate is the number of time per minute that the proport
action is duplicated. Reset rate is measured in terms of reset per minute. The combinations of the
proportional control action, integral control action and derivative combined action has the
advantages of the three individual cont
The transfer function of the controller is given by
V
o
(s) / V
i
(s) = K
p
where V
o
= output voltage
V
i
= input voltage
T
i
= integral time constant
T
d
= derivative time constant
K
p
= gain constant

Example:

Transfer function of the model is

PROPORTIONAL CONTROLLER:
P Transfer Function,



/Electrical Engineering &Control Systems Laboratory
are adjustable. The integral time constant T
i
adjusts integral control action while
affects both the integral parts of the control action. The inverse of
is called the reset rate.
The reset rate is the number of time per minute that the proportional part of the control
action is duplicated. Reset rate is measured in terms of reset per minute. The combinations of the
proportional control action, integral control action and derivative combined action has the
advantages of the three individual control actions.
The transfer function of the controller is given by
p
(1 + 1 / (T
i
+ T
d
))
= output voltage

= integral time constant
= derivative time constant
= gain constant

Transfer function of the model is

PROPORTIONAL CONTROLLER:

Page 63/86
adjusts integral control action while
affects both the integral parts of the control action. The inverse of
ional part of the control
action is duplicated. Reset rate is measured in terms of reset per minute. The combinations of the
proportional control action, integral control action and derivative combined action has the

Kings College of Engineering/ EE1257/


Matlab code:

Proportional Controller Plot:

Improved rise time & steady

PROPORTIONAL INTEGRAL CONTROLLER:

P Transfer Function,



/Electrical Engineering &Control Systems Laboratory



Improved rise time & steady-state error
PROPORTIONAL INTEGRAL CONTROLLER:

Page 64/86

Kings College of Engineering/ EE1257/


Matlab code:

Proportional integral Controller

Eliminated steady
PROPORTIONAL INTEGRAL DERIVATIVE CONTROLLER:

PID Transfer Function,


/Electrical Engineering &Control Systems Laboratory

Plot:

Eliminated steady-state error, decreased over-shoot
PROPORTIONAL INTEGRAL DERIVATIVE CONTROLLER:
Page 65/86


Kings College of Engineering/ EE1257/


Matlab code:

Proportional integral derivative Controller

Eliminated steady






Result:

Thus analyzed of given Transfer function using
software.
/Electrical Engineering &Control Systems Laboratory

Controller Plot:

Eliminated steady-state error, decreased over-shoot
of given Transfer function using P, PI and PID controller
Page 66/86
controller using MATLAB

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 67/86

EX NO: 12. DESIGN OF LEAD AND LAG COMPENSATOR.
DATE:

AIM:
To design and implement suitable compensator for s given linear system to improve the
performance.
APPARATUS REQUIRED:


THEORY:
The control systems are designed to perform specific taskes. When performance
specification are given for single input. Single output linear time invariant systems. Then the
system can be designed by using root locus or frequency response plots.
The first step in design is the adjustment of gain to meet the desired specifications. In
practical system. Adjustment of gain alone will not be sufficient to meet the given specifications.
In many cases, increasing the gain may result poor stability or instability. In such case, it is
necessary to introduce additional devices or component in the system to alter the behavior and to
meet the desired specifications. Such a redesign or addition of a suitable device is called
compensations. A device inserted into the system for the purpose or satisfying the specifications
is called compensator. The compensator behavior introduces pole & zero in open loop transfer
function to modify the performance of the system.
The different types of electrical or electronic compensators used are lead compensator
and lag compensator.
In control systems compensation required in the following situations.
1. When the system is absolutely unstable then compensation is required to stabilize
the system and to meet the desired performance.

S.NO
NAME OF THE
APPARATUS

TYPE

RANGE

QUANTITY





Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 68/86

2. When the system is stable. Compensation is provided to obtain the desired
performance.
LAG COMPENSATOR:
A compensator having the characteristics of a lag network is called a lag compensator. If
a sinusoidal signal is applied to a lag network, then in steady state the output will have a phase
lag with respect input.
Lag compensation result in a improvement in steady state performance but result in
slower response due to reduced bandwidth. The attenuation due to the lag compensator will shift
the gain crossover frequency to a lower frequency point where the phase margin is acceptable.
Thus the lag compensator will reduce the bandwidth of the system and will result in slower
transient response.
Lag compensator is essentially a low pass filter and high frequency noise signals are
attenuated. If the pore introduce by compensator is cancelled by a zero in the system, then lag
compensator increase the order of the system by one.
LEAD COMPENSATOR:
A compensator having the characteristics of a lead network is called a lead compensator.
If sinusoidal signal is applied to a lead network, then in steady state the output will have a phase
lead with respect to input.
The lead compensator increases the bandwidth, which improves the speed of response
and also reduces the amount of overshoot. Lead compensation appreciably improves the transient
response, whereas there is a small change in steady state accuracy. Generally lead compensation
is provided to make an unstable system as a stable system. A lead compensator is basically a
high pass filter and so it amplifies high frequency noise signals. If the pole is introduced by the
compensator is not cancelled by a zero in the system, then lead compensator increases order of
the system by one.

FORMULA:




0
0
x
y
A
B
Gain = =
) / log( 20 A B =
) / ( sin
0
1
A x Phase

=

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 69/86





CIRCUIT DIAGRAM:

Lead Compensator


Lag Compensator

PROCEDURE:
1. Make the connection as per the circuit diagram.
2. Apply the 2V p-p sin wave input and observe the waveform.
3. Very the frequency of the sin wave input and tabulate the values of x
o
and y
o

4. Calculate gain and phase angle.
5. Draw the bode plot.
) / ( sin
0
1
B y

=

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 70/86


TABULATION:
Lead compensator:
Output parameter of lead network:

S.No Phase
shift
Time
period
Frequency Angular
frequency
Output
voltage
Input
voltage
Gain




Value of Lissajious pattern:

S.No X1 X2 Y1 Y2



Lag compensator:
Output parameter of lag network:

S.No Phase
shift
Time
period
Frequency Angular
frequency
Output
voltage
Input
voltage
Gain




Value of Lissajious pattern:

S.No X1 X2 Y1 Y2




Kings College of Engineering/ EE1257/

MODEL GRAPH:
Lag compenstor:

Frequency Vs gain & Phase angle


Lissajous pattern:




/Electrical Engineering &Control Systems Laboratory
Frequency Vs gain & Phase angle:

Page 71/86



Kings College of Engineering/ EE1257/

Lead compensator:
Frequency Vs gain & Phase angle

Lissajous pattern:



Result:
Thus the compensator for a given linear system was designed and implemented suit
to improve the performance.


/Electrical Engineering &Control Systems Laboratory
Frequency Vs gain & Phase angle:

the compensator for a given linear system was designed and implemented suit
Page 72/86

the compensator for a given linear system was designed and implemented suitably

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 73/86

EX NO: 13. TRANSFER FUNCTION OF SEPARATELY EXCITED D.C GENERATOR
DATE:

AIM:
To determine the transfer function of separately excited DC generator.

APPARATUS REQUIRED:
S.No Name of the Equipment Range Type Quantity










PRECAUTION:


Armature rheostat is kept at maximum resistance position for determining the field resistance
R
L.

The rheostat 1 is kept in minimum resistance position and the rheostat 2 is kept at maximum
resistance position for determining the generator constant (Kg).
For determining the field impedance, the variac initially has to be kept at minimum position.
SPST switch be kept open while starting.

PROCEDURE:

The connections have to be made as per the circuit diagram.
Initially the DPST 2 has to kept open.

Kings College of Engineering/ EE1257/

The rheostat1 has to be kept in minimum resistance position and the rheostat 2 is kept in
minimum voltage position.
Close the DPST 1 and start the motor using the
rated speed by using the rheostat 1.
Now close the DPST 2. Increase the field potential by varying the rheostat 2 in steps and note
the voltmeter reading, so that voltmeter finally shows the rated voltage (
Magnetic curve has to be plotted between Eg

To Find R
f
:
Make the connection as per the circuit diagram.
By adjusting the rheostat 1,for various values of resistance, the corresponding values of
voltage and current have to be noted down.
To Find Z
f
:
Make the connection as per the circuit di
By adjusting the variac, the various
CIRCUIT DIAGRAM:

To Find Field Resistance(R
f
):




/Electrical Engineering &Control Systems Laboratory
The rheostat1 has to be kept in minimum resistance position and the rheostat 2 is kept in
Close the DPST 1 and start the motor using the three point starter and bring the motor to
d speed by using the rheostat 1.
DPST 2. Increase the field potential by varying the rheostat 2 in steps and note
the voltmeter reading, so that voltmeter finally shows the rated voltage (i.e.)220V
Magnetic curve has to be plotted between Eg and If.
Make the connection as per the circuit diagram.
By adjusting the rheostat 1,for various values of resistance, the corresponding values of
voltage and current have to be noted down.
Make the connection as per the circuit diagram.
By adjusting the variac, the various values of voltage and current have to be noted down.

Page 74/86
The rheostat1 has to be kept in minimum resistance position and the rheostat 2 is kept in
three point starter and bring the motor to
DPST 2. Increase the field potential by varying the rheostat 2 in steps and note
)220V.
By adjusting the rheostat 1,for various values of resistance, the corresponding values of
values of voltage and current have to be noted down.


Kings College of Engineering/ EE1257/


To Find Impedance Resistance Z





RETARDATION (OR) RUNNING DOWN TEST:







/Electrical Engineering &Control Systems Laboratory
To Find Impedance Resistance Z
f
:
RETARDATION (OR) RUNNING DOWN TEST:
Page 75/86



Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 76/86


TABULATION:



To find R
f


Sl.No I
f
(amp) V
f
(Volt) R
f
(ohm)






Avg R
f
=
To find Z
f


Sl.No
I
f
(amp)
mA
V
f
(Volt) Z
f
= V
f
/ I
f





Avg Z
f
=
To find K
t
l


Sl.No I
f
I
a
S
1
S
2
T( N m) N (rpm)





Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 77/86



MODEL GRAPH:





FORMULA:

R
ac
=R
f
* 1.6

Z
f
=R
ac
+X
f


X
f
=Z
f
- R
ac



L
f
= X
f
/2f
= L
f
/ R
ac

K=Kg/ R
ac


=

Kg (from graph) =

G(S)=K/(1+S)


RESULT:

Thus the transfer function of separately excited dc generator was found as

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 78/86


EX NO: 14. TRANSFER FUNCTION OF ARMATURE AND FIELD CONTROLLER
DC MOTOR.
DATE:

AIM:
To determine the transfer function of the DC shunt motor

APPARATUS REQUIRED:
S.No Name of the Equipment Range Type Quantity








THEORY:
Speed can be controlled by varying (i) flux per pole (ii) resistance of armature circuit and
(iii) applied voltage.
It is known that N E
b
/

If applied voltage is kept, E
b
= V I
a
R
a
will
Remain constant. Then, N 1/ By decreasing the flux speed can be increased and vice versa.
Hence this method is called field control method. The flux of the DC shunt motor can be
changed by changing field current, I
sh
with the help of shunt field rheostat. Since the I
sh
relatively

small, the shunt filed rheostat has to carry only a small current, which means I
sh
2
R loss is small.
This method is very efficient. In non-interpolar machines, speed can be increased by this method
up to the ratio 2: 1. In interpolar machine, a ratio of maximum to minimum speed of 6:1 which is
fairly common.


Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 79/86


FORMULA:
Armature Control

D.C. Shunt motor:

It is DC shunt motor designed to satisfy the requirements of the servomotor. The field
excited by a constant DC supply. If the field current is constant then speed is directly
proportional to armature voltage and torque is directly proportional to armature current.

K
m

Transfer Function =
S (1 + T
m
S)

K
m
= 1 / Avg K
b

T
m
= JR
a
/ K
b
K
t

K
t
= T / I
a

E
b
= V-I
a
R
a


Constant Values
J = 0.039 Kg
2
m
B = 0.030 N / rpm


Field Control

D.C. Shunt motor:

It is DC shunt motor designed to satisfy the requirements of the servomotor. In this motor
the armature is supplied with constant current or voltage. Torque is directly proportional to field
flux controlling the field current controls the torque of the motor.

K
Transfer Function =
Js
2
(1 + s)

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 80/86


K = K
t
/ R
f

= L
f
/ R
f
= V Z
f
2
R
f
2
/ 2f / R
f

= 2N / 60
T = r ( S
1
S
2
) * 9.81 N-m and r = .075m

TRANSFER FUNCTION ARMATURE CONTROL DC SHUNT MOTOR:
PRECAUTIONS:
At starting,
The field rheostat should be kept in minimum resistance position

PROCEDURE :
Finding K
b

1. Keep all switches in OFF position.
2. Initially keep voltage adjustment POT in minimum potential position.
3. Initially keep armature and field voltage adjustment POT in minimum position.
4. Connect the module armature output A and AA to motor armature terminal A and AA
respectively, and field F and FF to motor field terminal F and FF respectively.
5. Switch ON the power switch, S
1
, S
2
.
6. Set the field voltage 50% of the rated value.
7. Set the field current 50% of the rated value.
8. Tight the belt an take down the necessary readings for the table 1 to find the value of
K
b
.
9. Plot the graph Torque as Armature current to find K
t
.
Finding R
a

1. Keep all switches in OFF position.
2. Initially keep voltage adjustment POT in minimum position.
3. Initially keep armature and field voltage adjustment POT in minimum potential position.
4. Connect module armature output A and AA to motor armature terminal A to AA
respectively.
5. Switch ON the power switch and S
1
.

Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 81/86

6. Now armature voltage and armature current are taken by varying the armature POT with
in the rated armature current value.
7. The average resistance value in the table -2 gives the armature resistance.

Table No: 2To find K
b
:

Avg K
b
=


Table No: 2To find R
a
:







Avg R
a
=





Sl.No I
f
I
a
S
1
S
2
N V T E
b
K
b
= E
b
/








Sl.No Volt V
a
Current I
a
R
a
= V
a
/ I
a







Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 82/86

TRANSFER FUNCTION OF FIELD CONTROL D.C. SHUNT MOTOR:

PROCEDURE:
Finding R
f

1. Keep all switches in OFF position.
2. Keep armature field voltage POT in minimum potential position.
3. Initially keep armature and field voltage adjustment POT in minimum potential position.
4. Connect module filed output F and FF to motor filed terminal F and FF respectively.
5. Switch ON the power, S1 and S2.
6. Now filed voltage and filed current are taken by varying the armature POT with in the
rated armature current value.
7. Tabulate the value in the table no 3 average resistance values give the fied resistance.
Finding Z
f

1. Keep all switches in OFF position.
2. Keep armature and field voltage POT in minimum position.
3. Initially keep armature and field voltage adjustment POT in minimum position.
4. Connect module varaic output P and N to motor filed terminal F and FF respectively.
5. Switch on the power note down reading for the various AC supply by adjusting varaic for
the table -4.
Finding K
t
l

1. Keep all switches OFF position.
2. Initially keep voltage adjustment POT in minimum potential position.
3. Initially keep armature and field voltage adjustment POT in minimum position.
4. Connect the module armature output A and AA to motor armature terminal and AA
respectively, and field F and FF to motor field terminal F and FF respectively.
5. Switch ON the power switch, S
1
and S
2
.
6. Set the filed voltage at rated value (48V).
7. Adjust the armature voltage using POT on the armature side till it reaches the 1100 rpm.
8. Tight the belt and take down the necessary reading for the table 5 K
t
l

9. Plot the graph Torque as Field current to find K
t
l



Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 83/86


OBSERVATION TABLE FOR TRANSFER FUNCTION OF FIELD CONTROL DC SERVO
MOTOR:

Table No:3 To find R
f


Sl.No I
f
(amp) V
f
(Volt) R
f
(ohm)






Avg R
f
=

Table No:4 To find Z
f


Sl.No
I
f
(amp)
mA
V
f
(Volt) Z
f
= V
f
/ I
f





Avg Z
f
=







Kings College of Engineering/ EE1257/Electrical Engineering &Control Systems Laboratory Page 84/86

Table No: 5 To find K
t
l


Sl.No I
f
I
a
S
1
S
2
T( N m) N (rpm)







MODEL GRAPH:











MODEL CALCULATION:






I
f

T K
t
l
= T / If

T
Field Current
T
I
a
T

Kt = T / I
a


Armature Current

Kings College of Engineering/ EE1257/

TO FIND ARMATURE RESISTANCE



TO FIND ARMATURE IMPEDANCE:







/Electrical Engineering &Control Systems Laboratory
RESISTANCE:
FIND ARMATURE IMPEDANCE:
Page 85/86



Kings College of Engineering/ EE1257/

TO FIND CONSTANT K
b
:



TO FIND CONSTANT K
T
:

Result:

Thus the transfer function of the armature controlled dc shunt motor was obtained and is given
by..
/Electrical Engineering &Control Systems Laboratory
Thus the transfer function of the armature controlled dc shunt motor was obtained and is given
Page 86/86


Thus the transfer function of the armature controlled dc shunt motor was obtained and is given

Você também pode gostar