Anchor design

W-FAZ/A4 M12
Project description
Position
AS PER SITE CONDITION BALCONY CW BRACKETS
User name: Vijay kumar
Login name: Vijay kumar
[2 from 7] Page 2
Project data
Description AS PER SITE CONDITION BALCONY CW BRACKETS
Construction project
selected anchor
W-FAZ/A4 M12
Material: A4
Approval: ETA-99/0011
Depth of drilled hole: 90 mm
Nominal drill bit diameter: 12 mm
Clearancehole in connecting part: <= 14 mm
Geometry
Baseplate dimensions:
b = 400 mm
d = 150 mm
sy1 = 100 mm
sy2 = 150 mm
sy3 = 150 mm
sz1 = 100 mm
sz2 = 25 mm
sz3 = 25 mm
Eccentricity:
ey = 0 mm
ez = 0 mm
Component thickness:
d = 150 mm
Material:
Anchorage material: Concrete tension zone (cracked concrete)
Building material class: C35/45
Reinforcement: Without edge reinforcement
Adolf Wrth GmbH & Co. KG
Postfach 74650 Knzelsau
Tel.: +49 (0)7940 15-0 Fax: +49 (0)7940 15-1000 V. 6.1.0.35
Project description
Position
AS PER SITE CONDITION BALCONY CW BRACKETS
User name: Vijay kumar
Login name: Vijay kumar
[3 from 7] Page 3
Load
Load acts on the attached profile
maximum long term respectively short term temperature: 20C/20C
Adolf Wrth GmbH & Co. KG
Postfach 74650 Knzelsau
Tel.: +49 (0)7940 15-0 Fax: +49 (0)7940 15-1000 V. 6.1.0.35
Project description
Position
AS PER SITE CONDITION BALCONY CW BRACKETS
User name: Vijay kumar
Login name: Vijay kumar
[4 from 7] Page 4
Anchor bending
The following prerequisites are fulfilled:
- Fixture made of metal
- Fixture in full contact with the anchorage material
- Fixture in full contact with the anchor
- Clearance hole diameter maintained
Stress resultants
Md Vd Nd Nr.:
Adolf Wrth GmbH & Co. KG
Postfach 74650 Knzelsau
Tel.: +49 (0)7940 15-0 Fax: +49 (0)7940 15-1000 V. 6.1.0.35
Project description
Position
AS PER SITE CONDITION BALCONY CW BRACKETS
User name: Vijay kumar
Login name: Vijay kumar
[5 from 7] Page 5
1 6.41 kN 3.08 kN 0.00 Nm
2 6.41 kN 3.08 kN 0.00 Nm
3 6.41 kN 3.08 kN 0.00 Nm
4 6.41 kN 3.08 kN 0.00 Nm
Thickness of the baseplate
Building material class: S 235 J... (ST 37)
resultant point of load application relative to the middle of the baseplate:
Tension force: (x/y) = 0.00/ 0.00 mm
required baseplate thickness: 10 mm
controlling loading: Stress verification
Static verification
The calculation is done according " Guideline for European technical approval of metal
anchors for use in concrete;
Annex C: Design methods for anchorages" Design procedure A
Design value of the actions
European Technical Approval
European Technical Approval
Utilization ratio under tension loading
Use of total capacity in the case of steel failure:
Design value of the actions
European Technical Approval
European Technical Approval
European Technical Approval
Utilization ratio under tension loading
Use of total capacity in the case of pullout:
Design value of the actions
ETAG 001 - Annex C 5.2.2.4b
ETAG 001 - Annex C (5.2b)
ETAG 001 - Annex C (5.2c)
Use of total capacity in the case of concrete failure:
Adolf Wrth GmbH & Co. KG
Postfach 74650 Knzelsau
Tel.: +49 (0)7940 15-0 Fax: +49 (0)7940 15-1000 V. 6.1.0.35
Project description
Position
AS PER SITE CONDITION BALCONY CW BRACKETS
User name: Vijay kumar
Login name: Vijay kumar
[6 from 7] Page 6
ETAG 001 - Annex C (5.2d)
ETAG 001 - Annex C (5.2e)
ETAG 001 - Annex C (5.2)
ETAG 001 - Annex C (5.2a)
European Technical Approval
Utilization ratio under tension loading
Use of total capacity in the case of splitting:
Reinforcement is present that will limit the crack width to wk ~ 0,3 mm when the splitting forces are
taken into account.
Design value of the actions
European Technical Approval
European Technical Approval
Utilization ratio under shear loading
Use of total capacity in the case of steel failure under shear load:
Design value of the actions
ETAG 001 - Annex C (5.2a)
ETAG 001 - Annex C 5.2.2.4b
ETAG 001 - Annex C (5.2b)
ETAG 001 - Annex C (5.2c)
ETAG 001 - Annex C (5.2d)
ETAG 001 - Annex C (5.2e)
ETAG 001 - Annex C 5.2.2.4
European Technical Approval
ETAG 001 - Annex C (5.6)
European Technical Approval
Utilization ratio under shear loading
Use of total capacity in the case of pryout:
Design value of the actions
ETAG 001 - Annex C 5.2.2.4b
ETAG 001 - Annex C (5.2b)
ETAG 001 - Annex C (5.2c)
ETAG 001 - Annex C (5.2d)
Use of total capacity in the case of pryout (Single anchor):
Adolf Wrth GmbH & Co. KG
Postfach 74650 Knzelsau
Tel.: +49 (0)7940 15-0 Fax: +49 (0)7940 15-1000 V. 6.1.0.35
Project description
Position
AS PER SITE CONDITION BALCONY CW BRACKETS
User name: Vijay kumar
Login name: Vijay kumar
[7 from 7] Page 7
ETAG 001 - Annex C (5.2e)
European Technical Approval
ETAG 001 - Annex C (5.6)
ETAG 001 - Annex C 5.2.2.4
European Technical Approval
Utilization ratio under shear loading
Use of total capacity in the case of interaction for combined tension and shear loading
The anchor is suitable for the selected system.
This is a preliminary design only! Please confirm result with your civil engineer!
Comment:
The reinforcement required to take up the splitting forces generated by the anchors must be verified.
Notes about the calculations:
The following documents are referenced for the verification of the anchor load-bearing capacity:
- Anchor approval
The following assumptions are made for the calculations:
- The selected building material class has been verified
- all of the anchors in a group are of the same type and size
- The baseplate remains plane during loading
The verification of the local transfer of loads into the anchorage material has been performed. The transfer
of these loads to the rest of the structure must be shown.
The design is based on numerous anchor-specific values. If the selected anchor is substituted for another
or if the input values are changed, the design must be repeated. The requirements and provisions of the
European Technical Approval must be met.