Elevator Planning Guide

tkNorthern Elevator
Developing the future.
tkNorthern Elevator
Global Strength
The world has changed for today's successful building owners,
designers and contractors. Short-term speculation is out of
fashion. Value is once again being recognized. Your decisions
must be rightboth for today and decades to come. This New
World is reflected by the members of ThyssenKrupp Elevator
Worldwide. Individually, we have a heritage of success.
Combined, we are a part of one of the world's largest elevator
companies, with hundreds of thousands of installations to our
credit. Your decisions need to stand the test of time. Choose
the companies of ThyssenKrupp Elevator Worldwide for the
assurance only a company with global strength can offer.
CONTENTS
Global Strength . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
International Engineering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
ThyssenKrupp Northern Elevator Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Gearless Overhead Passenger Elevators (front opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Gearless Overhead Passenger Elevators (front and rear opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Geared Overhead Passenger Elevators (front opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Geared Overhead Passenger Elevators (front and rear opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Geared Overhead Hospital Elevators (front opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Geared Overhead Hospital Elevators (front and rear opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Geared Basement Passenger Elevators (front opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Geared Basement Passenger Elevators (front and rear opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Geared Sidemount Passenger Elevators (front opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Geared Sidemount Passenger Elevators (front and rear opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Twin Post Roped Hydraulic Passenger Elevators (front opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Twin Post Roped Hydraulic Passenger Elevators (front and rear opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Twin Post Roped Hydraulic Hospital Elevators (front opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Twin Post Roped Hydraulic Hospital Elevators (front and rear opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Twin Post Holeless Hydraulic Passenger Elevators (front opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Twin Post Holeless Hydraulic Passenger Elevators (front and rear opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Twin Post Holeless Hydraulic Hospital Elevators (front opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Twin Post Holeless Hydraulic Hospital Elevators (front and rear opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
In Ground Hydraulic Passenger Elevators (front opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
In Ground Hydraulic Passenger Elevators (front and rear opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
In Ground Hydraulic Hospital Elevators (front opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
In Ground Hydraulic Hospital Elevators (front and rear opening) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Passenger Entrances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Seismic Zone 2 or Greater Information Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Work Not Included in the Elevator Contract . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
2
Technology has become a global commodity. The best ideas
can no longer be contained by boundaries or distance. Being
a world class company means being able to bring our clients
the benefits of worldwide engineering excellence.
The members of ThyssenKrupp Elevator Worldwide
manufacture a full line of vertical transportation systems
including:
Hydraulic elevators featuring microprocessor controls.
Environmentally friendly holeless and roped hydraulic
elevators.
Mid-rise geared cable elevators with the most advanced
ACVVVF and DCSCR motor drives in the industry.
High-rise gearless elevators.
Escalators and power walks, including exclusive heavy-duty
designs for transit and outdoor applications.
Handicapped access and other specialty lifts.
STELLAR SERVICE
It is not enough to just be big. Our promise to you reaches
much higher. Simply, our service to our clients must be the
best. That is the pledge of the members of ThyssenKrupp
Elevator Worldwide.
We are committed to preserving a heritage, which recalls the
sources of our successour ability to meet the individual
needs of clientsone at a timeday after day. Count on us to
meet the high standards you set for your projects.
International Engineering
3
ThyssenKrupp Northern Elevator is a full line manufacturer of
vertical transportation equipment. Our factories produce a
complete range of gearless, geared, hydraulic, and specialty
elevators.
GEARLESS ELEVATORS
Designed for a wide range of capacities and speeds from 500
FPM to 700 FPM, our gearless elevators incorporate the most
advanced controller technology available in the industry. Our
Northstar 9000 system, with artificial intelligence based logic
dispatching and closed-loop feedback motion control, expertly
directs the activities of elevator groups of up to 8 cars serving
as many as 72 floors.
GEARED ELEVATORS
Our geared elevator systems are available for capacities from
2100 lbs to 6000 lbs and speeds from 150 FPM to 500 FPM.
We are one of North America's most prominent manufacturers
of high efficiency geared machines, overspeed safeties,
governors and roller guides. Our control systems feature
closed-loop Variable Voltage Variable Frequency (VVVF) drive
systems, microprocessor based logic and the industry's most
complete set of integrated safety features.
HYDRAULIC ELEVATORS
We offer the most complete line of hydraulic elevators in North
America. Pre-engineered and custom elevators for capacities
from 2100 lbs to 6000 lbs and speeds from 50 to 175 FPM are
available. We feature conventional direct-acting designs in both
holed and holeless application, as well as unique roped
holeless hydraulic designs, which extend the application range
for hydraulic systems beyond previous limits.
tkNorthern Elevator Products
4
Gearless elevators are the correct selection wherever building
height or extreme population density dictates the highest level
of elevator performance. Sophisticated motor controls ensure
high operating speeds and minimum floor-to-floor flight times,
without sacrificing passenger comfort and safety. Contact our
sales representatives for guidance in determining whether your
project demands the elite level of service gearless elevators
have to offer.
1. Overhead dimension "F" is based on standard cab heights of 9'-0" [2743 mm].
2. Hoist beam shown is to be provided by owner.
3. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
4. Refer to entrance detail section for required entrance rough openings.
5. Where habitable space is below the hoistway counterweight safeties are required.
Consult your TKNE representative for additional hoistway size requirements.
6. At floors that are not served (express zone), front hoistway wall must be built in
reducing hoistway depth "E" by 3" [76 mm].
7. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator
codes.
8. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see
"Seismic Zone 2 or Greater Information Tables".
**Will not accommodate ambulatory requirements.
Capacity (lbs) 2500 3000 3500 4000
(kg) 1160 1380 1600 1815
Speed (fpm) 500 to 700 500 to 700 500 to 700 500 to 700
(m/s) 2.5 to 3.5 2.5 to 3.5 2.5 to 3.5 2.5 to 3.5
Platform Width "A" (ft) 7'-0" 7'-0" 7'-0" 8'-0"
(mm) 2134 2134 2134 2438
Platform Depth "B" (ft) 5'-2" 5'-8" 6'-4" 6'-4"
(mm) 1575 1727 1930 1930
Opening Width "C" (ft) 3'-6" 3'-6" 3'-6" 4'-0"
(mm) 1067 1067 1067 1219
Type of Entrance SS or CO** SS or CO** SS or CO CO
Hoistway Width "D" (ft) 8'-4" 8'-4" 8'-4" 9'-4"
(mm) 2540 2540 2540 2845
Hoistway Depth "E" (ft) 6'-9" 7'-3" 7'-11" 7'-11"
(mm) 2058 2210 2413 2413
Hoistway Width "DD" (ft) 17'-0" 17'-0" 17'-0" 19'-0"
(mm) 5182 5182 5182 5791
Overhead "F"
500 fpm (ft) 20'-0" 20'-0" 20'-0" 20'-0"
2.50 m/s (mm) 6096 6096 6096 6096
700 fpm (ft) 24'-0" 24'-0" 24'-0" 24'-0"
3.5 m/s (mm) 7315 7315 7315 7315
Pit Depth "G"
500 fpm (ft) 9'-0" 9'-0" 9'-0" 9'-0"
2.50 m/s (mm) 2743 2743 2743 2743
700 fpm (ft) 12'-0" 12'-0" 12'-0" 12'-0"
3.5 m/s (mm) 3658 3658 3658 3658
Elevation
2
"

[
5
1

m
m
]
P
i
t
G
T
r
a
v
e
l
O
v
e
r
h
e
a
d
F
Concrete slab
(Machine Beams Optional)
9
'
-
0
"

[
2
7
4
3

m
m
]
Hoist Beam
7
'
-
0
"

[
2
1
3
4

m
m
]
O
p
e
n
i
n
g
A
EB
Single Slide Doors
D
C
C
Center Opening Doors
A
D
EB
DD
4" [102 mm]
Gearless Overhead Passenger Elevators - Front Opening
5
Elevation
G
P
i
t
T
r
a
v
e
l
Hoist Beam
2
"

[
5
1

m
m
]
O
v
e
r
h
e
a
d
F
Concrete slab
(Machine Beams Optional)
7
'
-
0
"

[
2
1
3
4

m
m
]
O
p
e
n
i
n
g
9
'
-
0
"

[
2
7
4
3

m
m
]
EB
1

1
/
2
"

[
3
8
m
m
]
A
t

R
e
a
r

O
p
n
g
.
L
e
v
e
l

O
n
l
y
Single Slide Doors
D
A
C
Center Opening Doors
1

1
/
2
"

[
3
8
m
m
]
E
B
L
e
v
e
l

O
n
l
y
A
t

R
e
a
r

O
p
n
g
.
C
A
D
4" [102 mm]
DD
E

+

2
"

[
5
1
m
m
]
1. Overhead dimension "F" is based on standard cab heights of 9'-0" [2743 mm].
2. Hoist beam shown is to be provided by owner.
3. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
4. Refer to entrance detail section for required entrance rough openings.
5. Where habitable space is below the hoistway counterweight safeties are required.
Consult your TKNE representative for additional hoistway size requirements.
6. At floors that are not served (express zone), front hoistway wall must be built in
reducing hoistway depth "E" by 3" [76 mm].
7. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator
codes.
8. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see
"Seismic Zone 2 or Greater Information Tables".
**Will not accommodate ambulatory requirements.
Capacity (lbs) 2500 3000 3500 4000
(kg) 1160 1380 1600 1815
Speed (fpm) 500 to 700 500 to 700 500 to 700 500 to 700
(m/s) 2.5 to 3.5 2.5 to 3.5 2.5 to 3.5 2.5 to 3.5
Platform Width "A" (ft) 7'-0" 7'-0" 7'-0" 8'-0"
(mm) 2134 2134 2134 2438
Platform Depth "B" (ft) 5'-9 1/2" 6'-3 1/2" 6'-11 1/2" 6'-11 1/2"
(mm) 1765 1918 2121 2121
Opening Width "C" (ft) 3'-6" 3'-6" 3'-6" 4'-0"
(mm) 1067 1067 1067 1219
Type of Entrance SS or CO** SS or CO** SS or CO CO
Hoistway Width "D" (ft) 9'-4" 9'-4" 9'-4" 10'-4"
(mm) 2845 2845 2845 3150
Hoistway Depth "E" (ft) 6'-7" 7'-1" 7'-9" 7'-9"
(mm) 2007 2159 2362 2362
Hoistway Width "DD" (ft) 18'-0" 18'-0" 18'-0" 20'-0"
(mm) 5486 5486 5486 6096
Overhead "F"
500 fpm (ft) 20'-0" 20'-0" 20'-0" 20'-0"
2.50 m/s (mm) 6096 6096 6096 6096
700 fpm (ft) 24'-0" 24'-0" 24'-0" 24'-0"
3.5 m/s (mm) 7315 7315 7315 7315
Pit Depth "G"
500 fpm (ft) 9'-0" 9'-0" 9'-0" 9'-0"
2.50 m/s (mm) 2743 2743 2743 2743
700 fpm (ft) 12'-0" 12'-0" 12'-0" 12'-0"
3.5 m/s (mm) 3658 3658 3658 3658
Gearless Overhead Passenger Elevators - Front and Rear Opening
6
Geared elevators are used in mid-to high-rise residential,
commercial mid-rise and freight applications. Referred to as
geared traction elevators, they possess relatively fast, smooth
acceleration, energy-saving efficiency and have contract speed
up to 500 fpm [2.5 m/s].
O
v
e
r
h
e
a
d
F
2
"

[
5
1

m
m
]
14'-0" [4267 mm] Mach. Room
Hoist Beam
7
'
-
6
"

[
2
2
8
6

m
m
]
GP
i
t
T
r
a
v
e
l
M
A
X
.

3
2
0

f
t

[
9
7
,
5
3
6

m
m
]
Elevation
Concrete slab
(Machine Beams Optional)
7
'
-
0
"

[
2
1
3
4

m
m
]
O
p
e
n
i
n
g
Single Slide Doors
D
A
EB
C
4" [102 mm]
DD
D
C
E
A
B
Center Opening Doors
1. Overhead dimension "F" is based on standard cab heights of 9'-0" [2743 mm].
2. Hoist beam shown is to be provided by owner.
3. Right hand door shown on simplex elevator arrangement can be left handed (symmetrically
opposite) and is available for use in multiple hoistways.
4. Refer to entrance detail section for required entrance rough openings.
5. Where habitable space is below the hoistway counterweight safeties are required. Consult
your TKNE representative for additional hoistway size requirements.
6. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
7. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see "Seismic
Zone 2 or Greater Information Tables".
*Denotes non-compliant with ADA. **Will not accommodate ambulatory requirements.
Capacity (lbs) 2100 2500 3000 3500 4000
(kg) 950 1160 1380 1600 1815
Speed (fpm) 150 to 500 150 to 500 150 to 500 150 to 500 150 to 500
(m/s) 0.75 to 2.5 0.75 to 2.5 0.75 to 2.5 0.75 to 2.5 0.75 to 2.5
Platform Width "A" (ft) 6'-0" 7'-0" 7'-0" 7'-0" 8'-0"
(mm) 1829 2134 2134 2134 2438
Platform Depth "B" (ft) 5'-2" 5'-2" 5'-8" 6'-4" 6'-4"
(mm) 1575 1575 1727 1930 1930
Opening Width "C" (ft) 3'-0" 3'-6" 3'-6" 3'-6" 4'-0"
(mm) 914 1067 1067 1067 1219
Type of Entrance SS** or CO*
**
SS or CO** SS or CO** SS or CO CO
Hoistway Width "D" (ft) 7'-4" 8'-4" 8'-4" 8'-4" 9'-4"
(mm) 2235 2540 2540 2540 2845
Hoistway Depth "E" (ft) 6'-7" 6'-7" 7'-1" 7'-9" 7'-9"
(mm) 2007 2007 2159 2362 2362
Hoistway Width "DD" (ft) 15'-0" 17'-0" 17'-0" 17'-0" 19'-0"
(mm) 4572 5182 5182 5182 5791
Overhead "F"
150 fpm to 200 fpm (ft) 16'-0" 16'-0" 16'-0" 16'-0" 16'-0"
0.75 m/s to 1.00 m/s (mm) 4877 4877 4877 4877 4877
250 fpm to 350 fpm (ft) 17'-0" 17'-0" 17'-0" 17'-0" 17'-0"
1.25 m/s to 1.75 m/s (mm) 5182 5182 5182 5182 5182
400 fpm (ft) 17'-6" 17'-6" 17'-6" 17'-6" 17'-6"
2.00 m/s (mm) 5334 5334 5334 5334 5334
450 fpm (ft) 18'-6" 18'-6" 18'-6" 18'-6" 18'-6"
2.25 m/s (mm) 5639 5639 5639 5639 5639
500 fpm (ft) 18'-6" 18'-6" 18'-6" 18'-6" 18'-6"
2.50 m/s (mm) 5639 5639 5639 5639 5639
Pit Depth "G"
150 fpm to 400 fpm (ft) 5'-6" 5'-6" 5'-6" 5'-6" 5'-6"
0.75 m/s to 2.00 m/s (mm) 1676 1676 1676 1676 1676
450 fpm (ft) 6'-6" 6'-6" 6'-6" 6'-6" 6'-6"
2.25 m/s (mm) 1981 1981 1981 1981 1981
500 fpm (ft) 6'-6" 6'-6" 6'-6" 6'-6" 6'-6"
2.50 m/s (mm) 1981 1981 1981 1981 1981
Geared Overhead Passenger Elevators - Front Opening
7
Geared elevators with a front and rear door configuration increase
flexibility of the overall elevator design. Through cars assist in
the movement of goods, furniture, and passengers. In addition
different front and rear floor levels can easily be accommodated
in existing buildings.
Elevation
Hoist Beam
2
"

[
5
1

m
m
]
F
O
v
e
r
h
e
a
d
T
r
a
v
e
l
G
P
i
t
Concrete slab
(Machine Beams Optional)
7
'
-
0
"

[
2
1
3
4

m
m
]
O
p
e
n
i
n
g
7
'
-
6
"

[
2
2
8
6

m
m
]
14'-0" [4267 mm] Mach. Room
M
A
X
.

3
2
0

f
t

[
9
7
,
5
3
6

m
m
]
Single Slide Doors
D
A
C
EB
1

1
/
2
"

[
3
8
m
m
]
A
t

R
e
a
r

O
p
n
g
.
L
e
v
e
l

O
n
l
y
Center Opening Doors
E
B
A
t

R
e
a
r

O
p
n
g
.
1

1
/
2
"

[
3
8
m
m
]
L
e
v
e
l

O
n
l
y
4" [102 mm]
A
D
DD
C
1. Overhead dimension "F" is based on standard cab heights of 9'-0" [2743 mm].
2. Hoist beam shown is to be provided by owner.
3. Right hand door shown on simplex elevator arrangement can be left handed (symmetrically
opposite) and is available for use in multiple hoistways.
4. Refer to entrance detail section for required entrance rough openings.
5. Where habitable space is below the hoistway counterweight safeties are required. Consult
your TKNE representative for additional hoistway size requirements.
6. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
7. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see "Seismic
Zone 2 or Greater Information Tables".
*Denotes non-compliant with ADA. **Will not accommodate ambulatory requirements.
Capacity (lbs) 2100 2500 3000 3500 4000
(kg) 950 1160 1380 1600 1815
Speed (fpm) 150 to 500 150 to 500 150 to 500 150 to 500 150 to 500
(m/s) 0.75 to 2.5 0.75 to 2.5 0.75 to 2.5 0.75 to 2.5 0.75 to 2.5
Platform Width "A" (ft) 6'-0" 7'-0" 7'-0" 7'-0" 8'-0"
(mm) 1829 2134 2134 2134 2438
Platform Depth "B" (ft) 5'-9 1/2" 5'-9 1/2" 6'-3 1/2" 6'-11 1/2" 6'-11 1/2"
(mm) 1765 1765 1918 2121 2121
Opening Width "C" (ft) 3'-0" 3'-6" 3'-6" 3'-6" 4'-0"
(mm) 914 1067 1067 1067 1219
Type of Entrance SS** or CO*
**
SS or CO** SS or CO** SS or CO CO
Hoistway Width "D" (ft) 8'-4" 9'-4" 9'-4" 9'-4" 10'-4"
(mm) 2540 2845 2845 2845 3150
Hoistway Depth "E" (ft) 6'-7" 6'-7" 7'-1" 7'-9" 7'-9"
(mm) 2007 2007 2159 2362 2362
Hoistway Width "DD" (ft) 16'-0" 18'-0" 18'-0" 18'-0" 20'-0"
(mm) 4877 5486 5486 5486 6096
Overhead "F"
150 fpm to 200 fpm (ft) 17'-6" 16'-0" 16'-0" 16'-0" 16'-0"
0.75 m/s to 1.00 m/s (mm) 5334 4877 4877 4877 4877
250 fpm to 350 fpm (ft) 18'-0" 17'-0" 17'-0" 17'-0" 17'-0"
1.25 m/s to 1.75 m/s (mm) 5486 5182 5182 5182 5182
400 fpm (ft) 18'-6" 17'-6" 17'-6" 17'-6" 17'-6"
2.00 m/s (mm) 5639 5334 5334 5334 5334
450 fpm (ft) 19'-6" 18'-6" 18'-6" 18'-6" 18'-6"
2.25 m/s (mm) 5944 5639 5639 5639 5639
500 fpm (ft) 19'-6" 18'-6" 18'-6" 18'-6" 18'-6"
2.50 m/s (mm) 5944 5639 5639 5639 5639
Pit Depth "G"
150 fpm to 400 fpm (ft) 5'-6" 5'-6" 5'-6" 5'-6" 5'-6"
0.75 m/s to 2.00 m/s (mm) 1676 1676 1676 1676 1676
450 fpm (ft) 6'-6" 6'-6" 6'-6" 6'-6" 6'-6"
2.25 m/s (mm) 1981 1981 1981 1981 1981
500 fpm (ft) 6'-6" 6'-6" 6'-6" 6'-6" 6'-6"
2.50 m/s (mm) 1981 1981 1981 1981 1981
Geared Overhead Passenger Elevators - Front and Rear Opening
8
Our geared hospital elevators meet the stringent capacity, safety,
and durability demands imposed by high-traffic hospital, nursing
home, and other care facility applications.
Hoist Beam
Elevation
2
"

[
5
1

m
m
]
O
v
e
r
h
e
a
d
T
r
a
v
e
l
M
A
X

2
5
0

f
t

[
7
6
,
2
0
0

m
m
]
P
i
t
G
F
Concrete slab
(Machine Beams Optional)
17'-0" [5182 mm] Mach. Room
7
'
-
0
"

[
2
1
3
4

m
m
]
O
p
e
n
i
n
g
7
'
-
6
"

[
2
2
8
6

m
m
]
A
D
EB
C
2 Speed Opening Doors
5" [127 mm] Max. D
A
DD
EB
C
2 Speed Opening Doors
1. Overhead dimension "F" is based on standard cab heights of 9'-0" [2743 mm].
2. Hoist beam shown is to be provided by owner.
3. Right hand door shown on simplex elevator arrangement can be left handed (symmetrically
opposite) and is available for use in multiple hoistways.
4. Refer to entrance detail section for required entrance rough openings.
5. Where habitable space is below the hoistway counterweight safeties are required. Consult
your TKNE representative for additional hoistway size requirements.
6. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
7. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see "Seismic
Zone 2 or Greater Information Tables".
Capacity (lbs) 3500 4000 4500 5000 6000
(kg) 1600 1815 2040 2270 2720
Speed (fpm) 200 to 500 200 to 450 200 to 400 200 to 350 200 to 350
(m/s) 1.0 to 2.5 1.0 to 2.25 1.0 to 2.0 1.0 to 1.75 1.0 to 1.75
Platform Width "A" (ft) 5'-4" 6'-0" 6'-0" 6'-0" 6'-4"
(mm) 1626 1829 1829 1829 1930
Platform Depth "B" (ft) 8'-4" 8'-4" 8'-10" 9'-6" 10'-4"
(mm) 2540 2540 2692 2896 3150
Opening Width "C" (ft) 3'-10" 4'-0" 4'-0" 4'-0" 4'-6"
(mm) 1168 1219 1219 1219 1372
Type of Entrance 2 speed 2 speed 2 speed 2 speed 2 speed
Hoistway Width "D" (ft) 7'-4" 8'-0" 8'-0" 8'-1" 8'-7"
(mm) 2235 2438 2438 2464 2616
Hoistway Depth "E" (ft) 9'-2" 9'-2" 9'-8" 10'-4" 11'-2"
(mm) 2794 2794 2946 3150 3404
Hoistway Width "DD" (ft) 15'-1" 16'-5" 16'-5" 16'-7" 17'-7"
(mm) 4597 5004 5004 5055 5359
Overhead "F"
150 fpm to 200 fpm (ft) 16'-6" 16'-6" 16'-6" 16'-6" 16'-6"
0.75 m/s to 1.00 m/s (mm) 5029 5029 5029 5029 5029
250 fpm to 350 fpm (ft) 17'-6" 17'-6" 17'-6" 17'-6" 17'-6"
1.25 m/s to 1.75 m/s (mm) 5334 5334 5334 5334 5334
400 fpm (ft) 17'-6" 17'-6" 17'-6"
2.00 m/s (mm) 5334 5334 5334
450 fpm (ft) 19'-0" 19'-0"
2.25 m/s (mm) 5791 5791
500 fpm (ft) 19'-0"
2.50 m/s (mm) 5791
Pit Depth "G"
150 fpm to 400 fpm (ft) 5'-6" 5'-6" 6'-0" 6'-0" 6'-0"
0.75 m/s to 2.00 m/s (mm) 1676 1676 1829 1829 1829
450 fpm (ft) 6'-6" 6'-6"
2.25 m/s (mm) 1981 1981
500 fpm (ft) 6'-6"
2.50 m/s (mm) 1981
Geared Overhead Hospital Elevators - Front Opening
9
Also suited to service/freight use in commercial, hotel, and
residential facilities, the size and shape of these elevators allow
easy movement of bulky hospital beds, test equipment, and other
cargo into and out of the elevator car.
Elevation
G
T
r
a
v
e
l
P
i
t
Hoist Beam
2
"

[
5
1

m
m
]
F
O
v
e
r
h
e
a
d
Concrete slab
(Machine Beams Optional)
7
'
-
0
"

[
2
1
3
4

m
m
]
O
p
e
n
i
n
g
7
'
-
6
"

[
2
2
8
6

m
m
]
17'-0" [5182 mm] Mach. Room
M
A
X

2
5
0

f
t

[
7
6
,
2
0
0

m
m
]
D
A
EB
C
4
"

[
1
0
2

m
m
]

R
e
c
e
s
s
L
e
v
e
l
s

O
n
l
y
A
t

R
e
a
r

O
p
e
n
i
n
g
2 Speed Opening Doors
L
e
v
e
l
s

O
n
l
y
A
t

R
e
a
r

O
p
e
n
i
n
g
4
"

[
1
0
2

m
m
]

R
e
c
e
s
s
EB
A
D
C
5" [127 mm] Max.
DD
2 Speed Opening Doors
1. Overhead dimension "F" is based on standard cab heights of 9'-0" [2743 mm].
2. Hoist beam shown is to be provided by owner.
3. Right hand door shown on simplex elevator arrangement can be left handed (symmetrically
opposite) and is available for use in multiple hoistways.
4. Refer to entrance detail section for required entrance rough openings.
5. Where habitable space is below the hoistway counterweight safeties are required. Consult
your TKNE representative for additional hoistway size requirements.
6. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
7. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see "Seismic
Zone 2 or Greater Information Tables".
Capacity (lbs) 3500 4000 4500 5000 6000
(kg) 1600 1815 2040 2270 2720
Speed (fpm) 200 to 500 200 to 450 200 to 400 200 to 350 200 to 350
(m/s) 1.0 to 2.5 1.0 to 2.25 1.0 to 2.0 1.0 to 1.75 1.0 to 1.75
Platform Width "A" (ft) 5'-4" 6'-0" 6'-0" 6'-0" 6'-4"
(mm) 1626 1829 1829 1829 1930
Platform Depth "B" (ft) 9'-1" 9'-1" 9'-7" 10'-3" 11'-1"
(mm) 2769 2769 2921 3124 3378
Opening Width "C" (ft) 3'-10" 4'-0" 4'-0" 4'-0" 4'-6"
(mm) 1168 1219 1219 1219 1372
Type of Entrance 2 speed 2 speed 2 speed 2 speed 2 speed
Hoistway Width "D" (ft) 7'-4" 8'-0" 8'-0" 8'-1" 8'-7"
(mm) 2235 2438 2438 2464 2616
Hoistway Depth "E" (ft) 10'-0" 10'-0" 10'-6" 11'-2" 12'-0"
(mm) 3048 3048 3200 3404 3658
Hoistway Width "DD" (ft) 15'-1" 16'-5" 16'-5" 16'-7" 17'-7"
(mm) 4597 5004 5004 5055 5359
Overhead "F"
150 fpm to 200 fpm (ft) 16'-6" 16'-6" 16'-6" 16'-6" 16'-6"
0.75 m/s to 1.00 m/s (mm) 5029 5029 5029 5029 5029
250 fpm to 350 fpm (ft) 17'-6" 17'-6" 17'-6" 17'-6" 17'-6"
1.25 m/s to 1.75 m/s (mm) 5334 5334 5334 5334 5334
400 fpm (ft) 17'-6" 17'-6" 17'-6"
2.00 m/s (mm) 5334 5334 5334
450 fpm (ft) 19'-0" 19'-0"
2.25 m/s (mm) 5791 5791
500 fpm (ft) 19'-0"
2.50 m/s (mm) 5791
Pit Depth "G"
150 fpm to 400 fpm (ft) 5'-6" 5'-6" 6'-0" 6'-0" 6'-0"
0.75 m/s to 2.00 m/s (mm) 1676 1676 1829 1829 1829
450 fpm (ft) 6'-6" 6'-6"
2.25 m/s (mm) 1981 1981
500 fpm (ft) 6'-6"
2.50 m/s (mm) 1981
Geared Overhead Hospital Elevators - Front and Rear Opening
10
1. Overhead dimension "F" is based on standard cab heights of 9'-0" [2743 mm].
2. Right hand door shown on simplex elevator arrangement can be left handed (symmetrically
opposite) and is available for use in multiple hoistways.
3. Refer to entrance detail section for required entrance rough openings.
4. Provide 2'-0" x 2'-0" [610mm x 610mm] lockable access door in overhead space for access
to elevator governor for each elevator. Means of access must meet governing code.
5. Furnish in place a permanent protective partition between the hoistway and machine room in
accordance to governing code.
6. Concrete foundation (by others) 3000 psi minimum is to be poured in one operation after
machine anchor frame set in place.
7. Where habitable space is below the hoistway counterweight safeties are required. Consult
your TKNE representative for additional hoistway size requirements.
8. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
9. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see "Seismic
Zone 2 or Greater Information Tables".
*Denotes non-compliant with ADA. **Will not accommodate ambulatory requirements.
Capacity (lbs) 2100 2500 3000 3500 4000
(kg) 950 1160 1380 1600 1815
Speed (fpm) 150 to 350 150 to 350 150 to 350 150 to 350 150 to 350
(m/s) 0.75 to 1.75 0.75 to 1.75 0.75 to 1.75 0.75 to 1.75 0.75 to 1.75
Platform Width "A" (ft) 6'-0" 7'-0" 7'-0" 7'-0" 8'-0"
(mm) 1829 2134 2134 2134 2438
Platform Depth "B" (ft) 5'-2" 5'-2" 5'-8" 6'-4" 6'-4"
(mm) 1575 1575 1727 1930 1930
Opening Width "C" (ft) 3'-0" 3'-6" 3'-6" 3'-6" 4'-0"
(mm) 914 1067 1067 1067 1219
Type of Entrance SS** or CO*
**
SS or CO** SS or CO** SS or CO CO
Hoistway Width "D" (ft) 7'-4" 8'-4" 8'-4" 8'-4" 9'-4"
(mm) 2235 2540 2540 2540 2845
Hoistway Depth "E" (ft) 7'-0" 7'-0" 7'-6" 8'-2" 8'-2"
(mm) 2134 2134 2286 2489 2489
Hoistway Width "DD" (ft) 15'-0" 17'-0" 17'-0" 17'-0" 19'-0"
(mm) 4572 5182 5182 5182 5791
Overhead "F"
150 fpm to 200 fpm (ft) 17'-6" 17'-6" 17'-6" 17'-6" 17'-6"
0.75 m/s to 1.00 m/s (mm) 5334 5334 5334 5334 5334
250 fpm to 350 fpm (ft) 18'-0" 18'-0" 18'-0" 18'-0" 18'-0"
1.25 m/s to 1.75 m/s (mm) 5486 5486 5486 5486 5486
Pit Depth "G"
150 fpm to 350 fpm (ft) 5'-6" 5'-6" 5'-6" 5'-6" 5'-6"
0.75 m/s to 1.75 m/s (mm) 1676 1676 1676 1676 1676
M
A
X
.

1
6
0

f
t

[
4
8
,
7
6
8

m
m
]
T
r
a
v
e
l
See note #6
See note #5
F
o
u
n
d
a
t
i
o
n
C
o
n
c
r
e
t
e
M
I
N

O
p
n
g
.
6
'
-
0
"

[
1
8
2
9

m
m
]
P
i
t
G
O
v
e
r
h
e
a
d
F
Sheave Beams
Elevation
7
'
-
0
"

[
2
1
3
4

m
m
]
O
p
e
n
i
n
g
Governor
Access Door
(see note #4)
B
E
8
'
-
0
"

[
2
4
3
8

m
m
]
M
a
c
h
i
n
e

R
o
o
m
C
Single Slide Doors
A
D
Single Slide Doors
C
A
D
DD
4" [102 mm]
E
B
8
'
-
0
"

[
2
4
3
8

m
m
]
M
a
c
h
i
n
e

R
o
o
m
Geared Basement Passenger Elevators - Front Opening
11
See note #5
Elevation
Beams
Sheave
G
P
i
t
T
r
a
v
e
l
F
O
v
e
r
h
e
a
d
7
'
-
0
"

[
2
1
3
4

m
m
]
O
p
e
n
i
n
g
M
A
X
.

1
6
0

f
t

[
4
8
,
7
6
8

m
m
]
See note #6
Governor
Access Door
(see note #4)
1

1
/
2
"

[
3
8
m
m
]
A
t

R
e
a
r

O
p
n
g
.
L
e
v
e
l

O
n
l
y
B
E
A
D
C
Single Slide Doors
8'-0" [2438 mm]
Machine Room
M
a
c
h
i
n
e

R
o
o
m
7
'
-
0
"

[
2
1
3
4

m
m
]

M
I
N

i
n

C
a
n
a
d
a
9
'
-
0
"

[
2
7
4
3

m
m
]

M
I
N

i
n

U
S
A
E
B
Single Slide Doors
DD
D
A
C
4" [102 mm]
1

1
/
2
"

[
3
8
m
m
]
A
t

R
e
a
r

O
p
n
g
.
L
e
v
e
l

O
n
l
y
M
a
c
h
i
n
e

R
o
o
m
7
'
-
0
"

[
2
1
3
4

m
m
]

M
I
N

i
n

C
a
n
a
d
a
9
'
-
0
"

[
2
7
4
3

m
m
]

M
I
N

i
n

U
S
A
8'-0" [2438 mm]
Machine Room
8'-0" [2438 mm]
Machine Room
1. Overhead dimension "F" is based on standard cab heights of 9'-0" [2743 mm].
2. Right hand door shown on simplex elevator arrangement can be left handed (symmetrically
opposite) and is available for use in multiple hoistways.
3. Refer to entrance detail section for required entrance rough openings.
4. Provide 2'-0" x 2'-0" [610mm x 610mm] lockable access door in overhead space for access
to elevator governor for each elevator. Means of access must meet governing code.
5. Furnish in place a permanent protective partition between the hoistway and machine room in
accordance to governing code.
6. Concrete foundation (by others) 3000 psi minimum is to be poured in one operation after
machine anchor frame set in place.
7. Where habitable space is below the hoistway counterweight safeties are required. Consult
your TKNE representative for additional hoistway size requirements.
8. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
9. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see "Seismic
Zone 2 or Greater Information Tables".
*Denotes non-compliant with ADA. **Will not accommodate ambulatory requirements.
Capacity (lbs) 2100 2500 3000 3500 4000
(kg) 950 1160 1380 1600 1815
Speed (fpm) 150 to 350 150 to 350 150 to 350 150 to 350 150 to 350
(m/s) 0.75 to 1.75 0.75 to 1.75 0.75 to 1.75 0.75 to 1.75 0.75 to 1.75
Platform Width "A" (ft) 6'-0" 7'-0" 7'-0" 7'-0" 8'-0"
(mm) 1829 2134 2134 2134 2438
Platform Depth "B" (ft) 5'-9 1/2" 5'-9 1/2" 6'-3 1/2" 6'-11 1/2" 6'-11 1/2"
(mm) 1765 1765 1918 2121 2121
Opening Width "C" (ft) 3'-0" 3'-6" 3'-6" 3'-6" 4'-0"
(mm) 914 1067 1067 1067 1219
Type of Entrance SS** or CO*
**
SS or CO** SS or CO** SS or CO CO
Hoistway Width "D" (ft) 8'-4" 9'-4" 9'-4" 9'-4" 10'-4"
(mm) 2540 2845 2845 2845 3150
Hoistway Depth "E" (ft) 6'-7" 6'-7" 7'-1" 7'-9" 7'-9"
(mm) 2007 2007 2159 2362 2362
Hoistway Width "DD" (ft) 17'-0" 19'-0" 19'-0" 19'-0" 21'-0"
(mm) 5182 5792 5792 5792 6402
Overhead "F"
150 fpm to 200 fpm (ft) 17'-6" 17'-6" 17'-6" 17'-6" 17'-6"
0.75 m/s to 1.00 m/s (mm) 5334 5334 5334 5334 5334
250 fpm to 350 fpm (ft) 18'-0" 18'-0" 18'-0" 18'-0" 18'-0"
1.25 m/s to 1.75 m/s (mm) 5486 5486 5486 5486 5486
Pit Depth "G"
150 fpm to 350 fpm (ft) 5'-6" 5'-6" 5'-6" 5'-6" 5'-6"
0.75 m/s to 1.75 m/s (mm) 1676 1676 1676 1676 1676
Geared Basement Passenger Elevators - Front and Rear Opening
12
1. Overhead dimension "F" is based on standard cab heights of 9'-0" [2743 mm].
2. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
3. Refer to entrance detail section for required entrance rough openings.
4. Provide 2'-0" x 2'-0" [610mm x 610mm] lockable access door in overhead space for
access to elevator governor for each elevator. Means of access must meet governing code.
5. Furnish in place a permanent protective partition between the hoistway and machine room
in accordance to governing code.
6. Where habitable space is below the hoistway counterweight safeties are required. Consult
your TKNE representative for additional hoistway size requirements.
7. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
8. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see "Seismic
Zone 2 or Greater Information Tables".
*Denotes non-compliant with ADA. **Will not accommodate ambulatory requirements.
Capacity (lbs) 2100 2500 3000 3500 4000
(kg) 950 1160 1380 1600 1815
Speed (fpm) 150 to 500 150 to 500 150 to 500 150 to 500 150 to 450
(m/s) 0.75 to 2.5 0.75 to 2.5 0.75 to 2.5 0.75 to 2.5 0.75 to 2.25
Platform Width "A" (ft) 6'-0" 7'-0" 7'-0" 7'-0" 8'-0"
(mm) 1829 2134 2134 2134 2438
Platform Depth "B" (ft) 5'-2" 5'-2" 5'-8" 6'-4" 6'-4"
(mm) 1575 1575 1727 1930 1930
Opening Width "C" (ft) 3'-0" 3'-6" 3'-6" 3'-6" 4'-0"
(mm) 914 1067 1067 1067 1219
Type of Entrance SS** or CO*
**
SS or CO** SS or CO** SS or CO CO
Hoistway Width "D" (ft) 7'-4" 8'-4" 8'-4" 8'-4" 9'-4"
(mm) 2235 2540 2540 2540 2845
Hoistway Depth "E" (ft) 6'-7" 6'-7" 7'-1" 7'-9" 7'-9"
(mm) 2007 2007 2159 2362 2362
Hoistway Width "DD" (ft) 15'-0" 17'-0" 17'-0" 17'-0" 19'-0"
(mm) 4572 5182 5182 5182 5791
Overhead "F"
150 fpm to 200 fpm (ft) 17'-6" 17'-6" 17'-6" 17'-6" 17'-6"
0.75 m/s to 1.00 m/s (mm) 5334 5334 5334 5334 5334
250 fpm to 350 fpm (ft) 18'-0" 18'-0" 18'-0" 18'-0" 18'-0"
1.25 m/s to 1.75 m/s (mm) 5486 5486 5486 5486 5486
400 fpm (ft) 18'-6" 18'-6" 18'-6" 18'-6" 18'-6"
2.00 m/s (mm) 5639 5639 5639 5639 5639
450 fpm (ft) 19'-6" 19'-6" 19'-6" 19'-6" 19'-6"
2.25 m/s (mm) 5944 5944 5944 5944 5944
500 fpm (ft) 19'-6" 19'-6" 19'-6" 19'-6"
2.50 m/s (mm) 5944 5944 5944 5944
Pit Depth "G"
150 fpm to 400 fpm (ft) 5'-6" 5'-6" 5'-6" 5'-6" 5'-6"
0.75 m/s to 2.00 m/s (mm) 1676 1676 1676 1676 1676
450 fpm (ft) 6'-6" 6'-6" 6'-6" 6'-6" 6'-6"
2.25 m/s (mm) 1981 1981 1981 1981 1981
500 fpm (ft) 6'-6" 6'-6" 6'-6" 6'-6"
2.50 m/s (mm) 1981 1981 1981 1981
M
A
X
.

3
0
0

f
t

[
9
1
,
4
4
0

m
m
]
Elevation
T
r
a
v
e
l
G
P
i
t
See note #5
M
I
N
.

M
a
c
h
i
n
e

R
o
o
m
F
9
'
-
0
"

[
2
7
4
3

m
m
]




3
'
-
0
"
[
9
1
5

m
m
]
O
v
e
r
h
e
a
d
Sheave
Beams
7
'
-
0
"

[
2
1
3
4

m
m
]
O
p
e
n
i
n
g
Governor
Access Door
(see note #4)
Single Slide Doors
D
A
C
B E
Center Opening Doors
A
D
C
B E
DD
4" [102 mm]
Geared Sidemount Passenger Elevators - Front Opening
13
Sheave
Beams
See note #5
Elevation
P
i
t
G
T
r
a
v
e
l
O
v
e
r
h
e
a
d
F
7
'
-
0
"

[
2
1
3
4

m
m
]
O
p
e
n
i
n
g
M
A
X
.

3
0
0

f
t

[
9
1
,
4
4
0

m
m
]
M
I
N
.

M
a
c
h
i
n
e

R
o
o
m
9
'
-
0
"

[
2
7
4
3

m
m
]




3
'
-
0
"
[
9
1
5

m
m
]
Governor
Access Door
(see note #4)
Single Slide Doors
L
e
v
e
l

O
n
l
y
A
t

R
e
a
r

O
p
n
g
.
1

1
/
2
"

[
3
8
m
m
]
B E
A
D
C
Center Opening Doors
E
B
A
t

R
e
a
r

O
p
n
g
.
1

1
/
2
"

[
3
8
m
m
]
L
e
v
e
l

O
n
l
y
A
D
C
4" [102 mm]
DD
1. Overhead dimension "F" is based on standard cab heights of 9'-0" [2743 mm].
2. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
3. Refer to entrance detail section for required entrance rough openings.
4. Provide 2'-0" x 2'-0" [610mm x 610mm] lockable access door in overhead space for
access to elevator governor for each elevator. Means of access must meet governing code.
5. Furnish in place a permanent protective partition between the hoistway and machine room
in accordance to governing code.
6. Where habitable space is below the hoistway counterweight safeties are required. Consult
your TKNE representative for additional hoistway size requirements.
7. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
8. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see "Seismic
Zone 2 or Greater Information Tables".
*Denotes non-compliant with ADA. **Will not accommodate ambulatory requirements.
Capacity (lbs) 2100 2500 3000 3500 4000
(kg) 950 1160 1380 1600 1815
Speed (fpm) 150 to 500 150 to 500 150 to 500 150 to 500 150 to 450
(m/s) 0.75 to 2.5 0.75 to 2.5 0.75 to 2.5 0.75 to 2.5 0.75 to 2.25
Platform Width "A" (ft) 6'-0" 7'-0" 7'-0" 7'-0" 8'-0"
(mm) 1829 2134 2134 2134 2438
Platform Depth "B" (ft) 5'-9 1/2" 5'-9 1/2" 6'-3 1/2" 6'-11 1/2" 6'-11 1/2"
(mm) 1765 1765 1918 2121 2121
Opening Width "C" (ft) 3'-0" 3'-6" 3'-6" 3'-6" 4'-0"
(mm) 914 1067 1067 1067 1219
Type of Entrance SS** or CO*
**
SS or CO** SS or CO** SS or CO CO
Hoistway Width "D" (ft) 8'-4" 9'-4" 9'-4" 9'-4" 10'-4"
(mm) 2540 2845 2845 2845 3150
Hoistway Depth "E" (ft) 6'-7" 6'-7" 7'-1" 7'-9" 7'-9"
(mm) 2007 2007 2159 2362 2362
Hoistway Width "DD" (ft) 16'-0" 18'-0" 18'-0" 18'-0" 20'-0"
(mm) 4877 5486 5486 5486 6096
Overhead "F"
150 fpm to 200 fpm (ft) 17'-6" 17'-6" 17'-6" 17'-6" 17'-6"
0.75 m/s to 1.00 m/s (mm) 5334 5334 5334 5334 5334
250 fpm to 350 fpm (ft) 18'-0" 18'-0" 18'-0" 18'-0" 18'-0"
1.25 m/s to 1.75 m/s (mm) 5486 5486 5486 5486 5486
400 fpm (ft) 18'-6" 18'-6" 18'-6" 18'-6" 18'-6"
2.00 m/s (mm) 5639 5639 5639 5639 5639
450 fpm (ft) 19'-6" 19'-6" 19'-6" 19'-6" 19'-6"
2.25 m/s (mm) 5944 5944 5944 5944 5944
500 fpm (ft) 19'-6" 19'-6" 19'-6" 19'-6"
2.50 m/s (mm) 5944 5944 5944 5944
Pit Depth "G"
150 fpm to 400 fpm (ft) 5'-6" 5'-6" 5'-6" 5'-6" 5'-6"
0.75 m/s to 2.00 m/s (mm) 1676 1676 1676 1676 1676
450 fpm (ft) 6'-6" 6'-6" 6'-6" 6'-6" 6'-6"
2.25 m/s (mm) 1981 1981 1981 1981 1981
500 fpm (ft) 6'-6" 6'-6" 6'-6" 6'-6"
2.50 m/s (mm) 1981 1981 1981 1981
Geared Sidemount Passenger Elevators - Front And Rear Opening
14
Our exclusive roped holeless hydraulic elevators extend the cost
savings of hydraulic elevator use when difficult drilling conditions or
environmental concerns make conventional hydraulic elevator use
impractical. Vertical travel can be extended to levels previously not
achievable with hydraulic elevators.
1. Overhead dimension "F" is based on standard cab heights of 8'-0" [2438 mm].
2. Hoist beam shown is to be provided by owner. It can be made removable.
3. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
4. Refer to entrance detail section for required entrance rough openings.
5. Machine room is to be located at the lowest floor adjacent to the hoistway. If remote
location is unavoidable, considerations for hydraulic and electrical lines must be reviewed
with TKNE representative.
6. Machine room must have a clear unobstructed height of 7'-0" [2134 mm].
7. Machine room size required may be larger than shown depending on pump unit required.
8. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
9. Provide 2'-0" x 2'-0" [610mm x 610mm] lockable access door in overhead space for
access to elevator governor for each elevator. Means of access must meet governing
code.
10. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see
"Seismic Zone 2 or Greater Information Tables".
11. For car travel larger than shown contact your TKNE representative.
*Denotes non-compliant with ADA. **Will not accommodate ambulatory requirements.
Capacity (lbs) 2100 2500 3000 3500 4000
(kg) 950 1160 1380 1600 1815
Speed (fpm) 50 to 175 50 to 175 50 to 175 50 to 175 50 to 175
(m/s) 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88
Platform Width "A" (ft) 6'-0" 7'-0" 7'-0" 7'-0" 8'-0"
(mm) 1829 2134 2134 2134 2438
Platform Depth "B" (ft) 5'-2" 5'-2" 5'-8" 6'-4" 6'-4"
(mm) 1575 1575 1727 1930 1930
Opening Width "C" (ft) 3'-0" 3'-6" 3'-6" 3'-6" 4'-0"
(mm) 914 1067 1067 1067 1219
Type of Entrance SS** or CO*
**
SS or CO** SS or CO** SS or CO CO
Hoistway Width "D" (ft) 8'-0" 9'-0" 9'-0" 9'-0" 10'-0"
(mm) 2438 2743 2743 2743 3048
Hoistway Depth "E" (ft) 5'-9" 5'-9" 6'-4" 6'-11" 6'-11"
(mm) 1753 1753 1930 2108 2108
Hoistway Width "DD" (ft) 16'-4" 18'-4" 18'-4" 18'-4" 20'-4"
(mm) 4978 5588 5588 5588 6198
Overhead "F" (ft) 12'-10" 12'-6" 12'-6" 12'-6" 12'-6"
(mm) 3912 3810 3810 3810 3810
Pit Depth "G" (ft) 5'-0" 5'-0" 5'-0" 5'-0" 5'-0"
(mm) 1524 1524 1524 1524 1524
Elevation
P
i
t
G
Governor
Access Door
(see note #9)
M
A
X

6
5

f
t

[
1
9
8
1
2

m
m
]

S
e
e

n
o
t
e

#
1
1
7
'
-
0
"

[
2
1
3
4

m
m
]
O
p
e
n
i
n
g
T
r
a
v
e
l
F
O
v
e
r
h
e
a
d
Hoist Beam
2
"

[
5
1

m
m
]
D
Center Opening Doors
B E
C
A
4" [102mm]
DD
Single Slide Doors
A
C
B E
Machine Room MIN.
7'-0" [2134mm] for Simplex
14'-0" [4268mm] for Duplex
M
I
N
.

M
a
c
h
i
n
e

R
o
o
m
6
'
-
6
"

[
1
9
8
1

m
m
]
Twin Post Roped Hydraulic Passenger Elevators - Front Opening
15
Hoist Beam
O
p
e
n
i
n
g
7
'
-
0
"

[
2
1
3
4
m
m
]
Elevation
O
v
e
r
h
e
a
d
F
T
r
a
v
e
l
GP
i
t
2
"

[
5
1

m
m
]
M
A
X

6
5

f
t

[
1
9
8
1
2

m
m
]

S
e
e

n
o
t
e

#
1
1
Governor
Access Door
(see note #9)
B E
Single Slide Doors
D
A
C
Machine Room MIN.
7'-0" [2134mm] for Simplex
14'-0" [4268mm] for Duplex
M
I
N
.

M
a
c
h
i
n
e

R
o
o
m
6
'
-
6
"

[
1
9
8
1

m
m
]
E
4" [102 mm]
Center Opening Doors
B
A
D
C
DD
1. Overhead dimension "F" is based on standard cab heights of 8'-0" [2438 mm].
2. Hoist beam shown is to be provided by owner. It can be made removable.
3. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
4. Refer to entrance detail section for required entrance rough openings.
5. Machine room is to be located at the lowest floor adjacent to the hoistway. If remote
location is unavoidable, considerations for hydraulic and electrical lines must be reviewed
with TKNE representative.
6. Machine room must have a clear unobstructed height of 7'-0" [2134 mm].
7. Machine room size required may be larger than shown depending on pump unit required.
8. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
9. Provide 2'-0" x 2'-0" [610mm x 610mm] lockable access door in overhead space for
access to elevator governor for each elevator. Means of access must meet governing
code.
10. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see
"Seismic Zone 2 or Greater Information Tables".
11. For car travel larger than shown contact your TKNE representative.
*Denotes non-compliant with ADA. **Will not accommodate ambulatory requirements.
Capacity (lbs) 2100 2500 3000 3500 4000
(kg) 950 1160 1380 1600 1815
Speed (fpm) 50 to 175 50 to 175 50 to 175 50 to 175 50 to 175
(m/s) 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88
Platform Width "A" (ft) 6'-0" 7'-0" 7'-0" 7'-0" 8'-0"
(mm) 1829 2134 2134 2134 2438
Platform Depth "B" (ft) 5'-9 1/2" 5'-9 1/2" 6'-3 1/2" 6'-11 1/2" 6'-11 1/2"
(mm) 1765 1765 1918 2121 2121
Opening Width "C" (ft) 3'-0" 3'-6" 3'-6" 3'-6" 4'-0"
(mm) 914 1067 1067 1067 1219
Type of Entrance SS** or CO*
**
SS or CO** SS or CO** SS or CO CO
Hoistway Width "D" (ft) 8'-0" 9'-0" 9'-0" 9'-0" 10'-0"
(mm) 2438 2743 2743 2743 3048
Hoistway Depth "E" (ft) 6'-8 1/2" 6'-8 1/2" 7'-2 1/2" 7'-10 1/2" 7'-10 1/2"
(mm) 2045 2045 2197 2400 2400
Hoistway Width "DD" (ft) 16'-4" 18'-4" 18'-4" 18'-4" 20'-4"
(mm) 4978 5588 5588 5588 6198
Overhead "F" (ft) 12'-10" 12'-6" 12'-6" 12'-6" 12'-6"
(mm) 3912 3810 3810 3810 3810
Pit Depth "G" (ft) 5'-0" 5'-0" 5'-0" 5'-0" 5'-0"
(mm) 1524 1524 1524 1524 1524
Twin Post Roped Hydraulic Passenger Elevators - Front And Rear Opening
16
1. Overhead dimension "F" is based on standard cab heights of 8'-0" [2438 mm].
2. Hoist beam shown is to be provided by owner. It can be made removable.
3. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
4. Refer to entrance detail section for required entrance rough openings.
5. Machine room is to be located at the lowest floor adjacent to the hoistway. If remote
location is unavoidable, considerations for hydraulic and electrical lines must be reviewed
with TKNE representative.
6. Machine room must have a clear unobstructed height of 7'-0" [2134 mm].
7. Machine room size required may be larger than shown depending on pump unit required.
8. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
9. Provide 2'-0" x 2'-0" [610mm x 610mm] lockable access door in overhead space for
access to elevator governor for each elevator. Means of access must meet governing
code.
10. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see
"Seismic Zone 2 or Greater Information Tables".
11. For car travel larger than shown contact your TKNE representative.
Capacity (lbs) 3500 4000 4500 5000 6000
(kg) 1600 1815 2040 2270 2720
Speed (fpm) 50 to 175 50 to 175 50 to 175 50 to 175 50 to 150
(m/s) 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.75
Platform Width "A" (ft) 5'-4" 6'-0" 6'-0" 6'-0" 6'-4"
(mm) 1626 1829 1829 1829 1930
Platform Depth "B" (ft) 8'-4" 8'-4" 8'-10" 9'-6" 10'-4"
(mm) 2540 2540 2692 2896 3150
Opening Width "C" (ft) 3'-10" 4'-0" 4'-0" 4'-0" 4'-6"
(mm) 1168 1219 1219 1219 1372
Type of Entrance 2 speed 2 speed 2 speed 2 speed 2 speed
Hoistway Width "D" (ft) 7'-6" 8'-0" 8'-0" 8'-0" 8'-9"
(mm) 2286 2438 2438 2438 2667
Hoistway Depth "E" (ft) 9'-2" 9'-2" 9'-8" 10'-4" 11'-2"
(mm) 2794 2794 2946 3150 3404
Hoistway Width "DD" (ft) 15'-4" 16'-4" 16'-4" 16'-4" 17'-10"
(mm) 4674 4978 4978 4978 5436
Overhead "F" (ft) 12'-6" 12'-6" 12'-6" 12'-6" 12'-6"
(mm) 3810 3810 3810 3810 3810
Pit Depth "G" (ft) 5'-0" 5'-0" 5'-0" 5'-0" 5'-0"
(mm) 1524 1524 1524 1524 1524
P
i
t
G
T
r
a
v
e
l
F
O
v
e
r
h
e
a
d
Elevation
7
'
-
0
"

[
2
1
3
4
m
m
]
O
p
e
n
i
n
g
Hoist Beam
2
"

[
5
1

m
m
]
M
A
X

6
5

f
t

[
1
9
8
1
2

m
m
]

S
e
e

n
o
t
e

#
1
1
Governor
Access Door
(see note #9)
B E
C
A
D
DD
5" [127 mm] Max.
2 Speed Opening Doors
B E
A
D
C
Machine Room MIN.
7'-0" [2134mm] for Simplex
14'-0" [4268mm] for Duplex
6
'
-
6
"

[
1
9
8
1

m
m
]
M
I
N
.

M
a
c
h
i
n
e

R
o
o
m
2 Speed Opening Doors
Twin Post Roped Hydraulic Hospital Elevators - Front Opening
17
1. Overhead dimension "F" is based on standard cab heights of 8'-0" [2438 mm].
2. Hoist beam shown is to be provided by owner. It can be made removable.
3. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
4. Refer to entrance detail section for required entrance rough openings.
5. Machine room is to be located at the lowest floor adjacent to the hoistway. If remote
location is unavoidable, considerations for hydraulic and electrical lines must be reviewed
with TKNE representative.
6. Machine room must have a clear unobstructed height of 7'-0" [2134 mm].
7. Machine room size required may be larger than shown depending on pump unit required.
8. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
9. Provide 2'-0" x 2'-0" [610mm x 610mm] lockable access door in overhead space for
access to elevator governor for each elevator. Means of access must meet governing
code.
10. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see
"Seismic Zone 2 or Greater Information Tables".
11. For car travel larger than shown contact your TKNE representative.
Capacity (lbs) 3500 4000 4500 5000 6000
(kg) 1600 1815 2040 2270 2720
Speed (fpm) 50 to 175 50 to 175 50 to 175 50 to 175 50 to 150
(m/s) 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.75
Platform Width "A" (ft) 5'-4" 6'-0" 6'-0" 6'-0" 6'-4"
(mm) 1626 1829 1829 1829 1930
Platform Depth "B" (ft) 9'-1" 9'-1" 9'-7" 10'-3" 11'-1"
(mm) 2769 2769 2921 3124 3378
Opening Width "C" (ft) 3'-10" 4'-0" 4'-0" 4'-0" 4'-6"
(mm) 1168 1219 1219 1219 1372
Type of Entrance 2 speed 2 speed 2 speed 2 speed 2 speed
Hoistway Width "D" (ft) 7'-6" 8'-0" 8'-0" 8'-0" 8'-9"
(mm) 2286 2438 2438 2438 2667
Hoistway Depth "E" (ft) 10'-4" 10'-4" 10'-10" 11'-6" 12'-4"
(mm) 3150 3150 3302 3505 3759
Hoistway Width "DD" (ft) 15'-4" 16'-4" 16'-4" 16'-4" 17'-10"
(mm) 4674 4978 4978 4978 5436
Overhead "F" (ft) 12'-6" 12'-6" 12'-6" 12'-6" 12'-6"
(mm) 3810 3810 3810 3810 3810
Pit Depth "G" (ft) 5'-0" 5'-0" 5'-0" 5'-0" 5'-0"
(mm) 1524 1524 1524 1524 1524
P
i
t
G
T
r
a
v
e
l
F
O
v
e
r
h
e
a
d
Elevation
7
'
-
0
"

[
2
1
3
4
m
m
]
O
p
e
n
i
n
g
2
"

[
5
1

m
m
]
Hoist Beam
M
A
X

6
5

f
t

[
1
9
8
1
2

m
m
]

S
e
e

n
o
t
e

#
1
1
Governor
Access Door
(see note #9)
EB
A
D
C
Machine Room MIN.
7'-0" [2134mm] for Simplex
14'-0" [4268mm] for Duplex
6
'
-
6
"

[
1
9
8
1

m
m
]
M
I
N
.

M
a
c
h
i
n
e

R
o
o
m
2 Speed Opening Doors
EB
C
D
A
DD
5" [127 mm] Max.
2 Speed Opening Doors
Twin Post Roped Hydraulic Hospital Elevators - Front And Rear Opening
18
For two-stop applications, our direct-acting holeless elevators offer vertical transportation at the lowest
possible cost. These designs are ideal for applications to new or existing buildings, and are especially suited to
fulfilling accessibility access obligations in commercial and governmental buildings. Passenger and hospital
configurations are available.
1. Overhead dimension "F" is the greater of
a) cab height plus 4'-2" [1270 mm] (for cars with guard rail on top add 4") or
b) travel plus 3'-8" [1118 mm] minus pit depth.
2. Pit depth is 4'-0" [1219 mm] (5'-0" [1524 mm] in Ontario, Canada).
3. Hoist beam shown is to be provided by owner. It can be made removable.
4. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
5. Refer to entrance detail section for required entrance rough openings.
6. Machine room is to be located at the lowest floor adjacent to the hoistway. If remote
location is unavoidable, considerations for hydraulic and electrical lines must be reviewed
with TKNE representative.
7. Machine room must have a clear unobstructed height of 7'-0" [2134 mm].
8. Machine room size required may be larger than shown depending on pump unit required.
9. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
10. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see
"Seismic Zone 2 or Greater Information Tables".
11. For car travel up to 20 ft contact your TKNE representative.
*Denotes non-compliant with ADA. **Will not accommodate ambulatory requirements.
Capacity (lbs) 2100 2500 3000 3500 4000
(kg) 950 1160 1380 1600 1815
Speed (fpm) 50 to 150 50 to 150 50 to 150 50 to 150 50 to 150
(m/s) 0.25 to 0.75 0.25 to 0.75 0.25 to 0.75 0.25 to 0.75 0.25 to 0.75
Platform Width "A" (ft) 6'-0" 7'-0" 7'-0" 7'-0" 8'-0"
(mm) 1829 2134 2134 2134 2438
Platform Depth "B" (ft) 5'-2" 5'-2" 5'-8" 6'-4" 6'-4"
(mm) 1575 1575 1727 1930 1930
Opening Width "C" (ft) 3'-0" 3'-6" 3'-6" 3'-6" 4'-0"
(mm) 914 1067 1067 1067 1219
Type of Entrance SS** or CO*
**
SS or CO** SS or CO** SS or CO CO
Hoistway Width "D" (ft) 7'-4" 8'-4" 8'-4" 8'-4" 9'-4"
(mm) 2235 2540 2540 2540 2845
Hoistway Depth "E" (ft) 5'-9" 5'-9" 6'-4" 6'-11" 6'-11"
(mm) 1753 1753 1930 2108 2108
Hoistway Width "DD" (ft) 15'-0" 17'-0" 17'-0" 17'-0" 19'-0"
(mm) 4572 5182 5182 5182 5791
Overhead "F" See note 1
Pit Depth "G" See note 2
Elevation
7
'
-
0
"

[
2
1
3
4

m
m
]
O
p
e
n
i
n
g
F
O
v
e
r
h
e
a
d
Hoist Beam
2
"

[
5
1

m
m
]
T
r
a
v
e
l
M
A
X

1
2
'
-
6
"

[
3
8
1
0

m
m
]

S
e
e

n
o
t
e

#
1
1
GP
i
t
B E
Machine Room MIN.
7'-0" [2134mm] for Simplex
14'-0" [4268mm] for Duplex
C
Single Slide Doors
A
D
M
I
N
.

M
a
c
h
i
n
e

R
o
o
m
6
'
-
6
"

[
1
9
8
1

m
m
]
B E
Center Opening Doors
D
A
DD
4" [102mm]
C
Twin Post Holeless Hydraulic Passenger Elevators - Front Opening
19
1. Overhead dimension "F" is the greater of
a) cab height plus 4'-2" [1270 mm] (for cars with guard rail on top add 4") or
b) travel plus 3'-8" [1118 mm] minus pit depth.
2. Pit depth is 4'-0" [1219 mm] (5'-0" [1524 mm] in Ontario, Canada).
3. Hoist beam shown is to be provided by owner. It can be made removable.
4. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
5. Refer to entrance detail section for required entrance rough openings.
6. Machine room is to be located at the lowest floor adjacent to the hoistway. If remote
location is unavoidable, considerations for hydraulic and electrical lines must be reviewed
with TKNE representative.
7. Machine room must have a clear unobstructed height of 7'-0" [2134 mm].
8. Machine room size required may be larger than shown depending on pump unit required.
9. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
10. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see
"Seismic Zone 2 or Greater Information Tables".
11. For car travel up to 20 ft contact your TKNE representative.
*Denotes non-compliant with ADA. **Will not accommodate ambulatory requirements.
Capacity (lbs) 2100 2500 3000 3500 4000
(kg) 950 1160 1380 1600 1815
Speed (fpm) 50 to 150 50 to 150 50 to 150 50 to 150 50 to 150
(m/s) 0.25 to 0.75 0.25 to 0.75 0.25 to 0.75 0.25 to 0.75 0.25 to 0.75
Platform Width "A" (ft) 6'-0" 7'-0" 7'-0" 7'-0" 8'-0"
(mm) 1829 2134 2134 2134 2438
Platform Depth "B" (ft) 5'-9 1/2" 5'-9 1/2" 6'-3 1/2" 6'-11 1/2" 6'-11 1/2"
(mm) 1765 1765 1918 2121 2121
Opening Width "C" (ft) 3'-0" 3'-6" 3'-6" 3'-6" 4'-0"
(mm) 914 1067 1067 1067 1219
Type of Entrance SS** or CO*
**
SS or CO** SS or CO** SS or CO CO
Hoistway Width "D" (ft) 7'-4" 8'-4" 8'-4" 8'-4" 9'-4"
(mm) 2235 2540 2540 2540 2845
Hoistway Depth "E" (ft) 6'-8 1/2" 6'-8 1/2" 7'-2 1/2" 7'-10 1/2" 7'-10 1/2"
(mm) 2045 2045 2197 2400 2400
Hoistway Width "DD" (ft) 15'-0" 17'-0" 17'-0" 17'-0" 19'-0"
(mm) 4572 5182 5182 5182 5791
Overhead "F" See note 1
Pit Depth "G" See note 2
Elevation
7
'
-
0
"

[
2
1
3
4

m
m
]
O
p
e
n
i
n
g
F
O
v
e
r
h
e
a
d
Hoist Beam
2
"

[
5
1

m
m
]
T
r
a
v
e
l
M
A
X

1
2
'
-
6
"

[
3
8
1
0

m
m
]

S
e
e

n
o
t
e

#
1
1
GP
i
t
Machine Room MIN.
7'-0" [2134mm] for Simplex
14'-0" [4268mm] for Duplex
Single Slide Doors
EB
D
A
C
M
I
N
.

M
a
c
h
i
n
e

R
o
o
m
6
'
-
6
"

[
1
9
8
1

m
m
]
E
B
Center Opening Doors
4" [102 mm] D
A
C
DD
Twin Post Holeless Hydraulic Passenger Elevators - Front And Rear Opening
20
1. Overhead dimension "F" is the greater of
a) cab height plus 4'-2" [1270 mm] (for cars with guard rail on top add 4") or
b) travel plus 3'-8" [1118 mm] minus pit depth.
2. Pit depth is 4'-0" [1219 mm] (5'-0" [1524 mm] in Ontario, Canada).
3. Hoist beam shown is to be provided by owner. It can be made removable.
4. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
5. Refer to entrance detail section for required entrance rough openings.
6. Machine room is to be located at the lowest floor adjacent to the hoistway. If remote
location is unavoidable, considerations for hydraulic and electrical lines must be reviewed
with TKNE representative.
7. Machine room must have a clear unobstructed height of 7'-0" [2134 mm].
8. Machine room size required may be larger than shown depending on pump unit required.
9. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
10. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see
"Seismic Zone 2 or Greater Information Tables".
11. For car travel up to 20 ft contact your TKNE representative.
Capacity (lbs) 3500 4000 4500 5000 6000
(kg) 1600 1815 2040 2270 2720
Speed (fpm) 50 to 150 50 to 150 50 to 150 50 to 150 50 to 150
(m/s) 0.25 to 0.75 0.25 to 0.75 0.25 to 0.75 0.25 to 0.75 0.25 to 0.75
Platform Width "A" (ft) 5'-4" 6'-0" 6'-0" 6'-0" 6'-4"
(mm) 1626 1829 1829 1829 1930
Platform Depth "B" (ft) 8'-4" 8'-4" 8'-10" 9'-6" 10'-4"
(mm) 2540 2540 2692 2896 3150
Opening Width "C" (ft) 3'-10" 4'-0" 4'-0" 4'-0" 4'-6"
(mm) 1168 1219 1219 1219 1372
Type of Entrance 2 speed 2 speed 2 speed 2 speed 2 speed
Hoistway Width "D" (ft) 7'-2" 7'-5" 7'-5" 7'-9" 8'-5"
(mm) 2184 2261 2261 2362 2565
Hoistway Depth "E" (ft) 9'-2" 9'-2" 9'-8" 10'-4" 11'-2"
(mm) 2794 2794 2946 3150 3404
Hoistway Width "DD" (ft) 14'-8" 15'-2" 15'-2" 15'-10" 17'-2"
(mm) 4470 4623 4623 4826 5232
Overhead "F" See note 1
Pit Depth "G" See note 2
O
p
e
n
i
n
g
7
'
-
0
"

[
2
1
3
4

m
m
]
Elevation
M
A
X

1
2
'
-
6
"

[
3
8
1
0

m
m
]

S
e
e

n
o
t
e

#
1
1
P
i
t
G
T
r
a
v
e
l
2
"

[
5
1

m
m
]
Hoist Beam
O
v
e
r
h
e
a
d
F
EB
A
D
C
Machine Room MIN.
7'-0" [2134mm] for Simplex
14'-0" [4268mm] for Duplex
M
I
N
.

M
a
c
h
i
n
e

R
o
o
m
6
'
-
6
"

[
1
9
8
1

m
m
]
2 Speed Opening Doors
EB
C
DD
A
D 5" [127 mm] Max.
2 Speed Opening Doors
Twin Post Holeless Hydraulic Hospital Elevators - Front Opening
21
1. Overhead dimension "F" is the greater of
a) cab height plus 4'-2" [1270 mm] (for cars with guard rail on top add 4") or
b) travel plus 3'-8" [1118 mm] minus pit depth.
2. Pit depth is 4'-0" [1219 mm] (5'-0" [1524 mm] in Ontario, Canada).
3. Hoist beam shown is to be provided by owner. It can be made removable.
4. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
5. Refer to entrance detail section for required entrance rough openings.
6. Machine room is to be located at the lowest floor adjacent to the hoistway. If remote
location is unavoidable, considerations for hydraulic and electrical lines must be reviewed
with TKNE representative.
7. Machine room must have a clear unobstructed height of 7'-0" [2134 mm].
8. Machine room size required may be larger than shown depending on pump unit required.
9. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
10. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see
"Seismic Zone 2 or Greater Information Tables".
11. For car travel up to 20 ft contact your TKNE representative.
Capacity (lbs) 3500 4000 4500 5000 6000
(kg) 1600 1815 2040 2270 2720
Speed (fpm) 50 to 150 50 to 150 50 to 150 50 to 150 50 to 150
(m/s) 0.25 to 0.75 0.25 to 0.75 0.25 to 0.75 0.25 to 0.75 0.25 to 0.75
Platform Width "A" (ft) 5'-4" 6'-0" 6'-0" 6'-0" 6'-4"
(mm) 1626 1829 1829 1829 1930
Platform Depth "B" (ft) 9'-1" 9'-1" 9'-7" 10'-3" 11'-1"
(mm) 2769 2769 2921 3124 3378
Opening Width "C" (ft) 3'-10" 4'-0" 4'-0" 4'-0" 4'-6"
(mm) 1168 1219 1219 1219 1372
Type of Entrance 2 speed 2 speed 2 speed 2 speed 2 speed
Hoistway Width "D" (ft) 7'-2" 7'-5" 7'-5" 7'-9" 8'-5"
(mm) 2184 2261 2261 2362 2565
Hoistway Depth "E" (ft) 10'-4" 10'-4" 10'-10" 11'-6" 12'-4"
(mm) 3150 3150 3302 3505 3759
Hoistway Width "DD" (ft) 14'-8" 15'-2" 15'-2" 15'-10" 17'-2"
(mm) 4470 4623 4623 4826 5232
Overhead "F" See note 1
Pit Depth "G" See note 2
Elevation
2
"

[
5
1

m
m
]
M
A
X

1
2
'
-
6
"

[
3
8
1
0

m
m
]

S
e
e

n
o
t
e

#
1
1
O
p
e
n
i
n
g
7
'
-
0
"

[
2
1
3
4

m
m
]
P
i
t
G
T
r
a
v
e
l
O
v
e
r
h
e
a
d
F
Hoist Beam
EB
A
D
C
Machine Room MIN.
7'-0" [2134mm] for Simplex
14'-0" [4268mm] for Duplex
M
I
N
.

M
a
c
h
i
n
e

R
o
o
m
6
'
-
6
"

[
1
9
8
1

m
m
]
2 Speed Opening Doors
C
DD
D
A
EB
5" [127 mm] Max.
2 Speed Opening Doors
Twin Post Holeless Hydraulic Hospital Elevators - Front And Rear Opening
22
1. Overhead dimension "F" is based on standard cab heights of 8'-0" [2438 mm].
2. Pit depth is 4'-6" [1372 mm] (5'-0" [1524 mm] in Ontario, Canada).
3. Hoist beam shown is to be provided by owner. It can be made removable.
4. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
5. Refer to entrance detail section for required entrance rough openings.
6. Machine room is to be located at the lowest floor adjacent to the hoistway. If remote
location is unavoidable, considerations for hydraulic and electrical lines must be reviewed
with TKNE representative.
7. Machine room must have a clear unobstructed height of 7'-0" [2134 mm].
8. Machine room size required may be larger than shown depending on pump unit required.
9. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
10. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see
"Seismic Zone 2 or Greater Information Tables".
11. For car travel larger than shown contact your TKNE representative.
*Denotes non-compliant with ADA. **Will not accommodate ambulatory requirements.
Capacity (lbs) 2100 2500 3000 3500 4000
(kg) 950 1160 1380 1600 1815
Speed (fpm) 50 to 175 50 to 175 50 to 175 50 to 175 50 to 175
(m/s) 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88
Platform Width "A" (ft) 6'-0" 7'-0" 7'-0" 7'-0" 8'-0"
(mm) 1829 2134 2134 2134 2438
Platform Depth "B" (ft) 5'-2" 5'-2" 5'-8" 6'-4" 6'-4"
(mm) 1575 1575 1727 1930 1930
Opening Width "C" (ft) 3'-0" 3'-6" 3'-6" 3'-6" 4'-0"
(mm) 914 1067 1067 1067 1219
Type of Entrance SS** or CO*
**
SS or CO** SS or CO** SS or CO CO
Hoistway Width "D" (ft) 7'-4" 8'-4" 8'-4" 8'-4" 9'-4"
(mm) 2235 2540 2540 2540 2845
Hoistway Depth "E" (ft) 5'-9" 5'-9" 6'-4" 6'-11" 6'-11"
(mm) 1753 1753 1930 2108 2108
Hoistway Width "DD" (ft) 15'-0" 17'-0" 17'-0" 17'-0" 19'-0"
(mm) 4572 5182 5182 5182 5791
Overhead "F" (ft) 12'-2" 12'-2" 12'-2" 12'-2" 12'-2"
(without top of car guard rail) (mm) 3708 3708 3708 3708 3708
Overhead "F" (ft) 12'-6" 12'-6" 12'-6" 12'-6" 12'-6"
(with top of car guard rail) (mm) 3810 3810 3810 3810 3810
Pit Depth "G" See note 2
7
'
-
0
"

[
2
1
3
4

m
m
]
O
v
e
r
h
e
a
d
O
p
e
n
i
n
g
F
Casing
Elevation
Hoist Beam
2
"

[
5
1

m
m
]
T
r
a
v
e
l
M
A
X

6
0

f
t

[
1
8
,
2
8
8

m
m
]

S
e
e

n
o
t
e

#
1
1
2'-0" [610 mm]
Square Hole
GP
i
t
B E
Machine Room MIN.
7'-0" [2134mm] for Simplex
14'-0" [4268mm] for Duplex
A
Single Slide Doors
D
C
M
I
N
.

M
a
c
h
i
n
e

R
o
o
m
6
'
-
6
"

[
1
9
8
1

m
m
]
B E
Center Opening Doors
C
A
D
DD
4" [102mm]
Hydraulic elevators, because of their top speed of 0.9 m/s, are
normally limited to low-rise applications with a maximum of five to
six stops. Hydraulics are low-rise favorites due to their simplicity, low
maintenance cost and because they do not require a load bearing
hoistway. Hoistway use is optimum, but motor horsepower and
electrical requirements are greater than comparable geared
elevators.
In Ground Hydraulic Passenger Elevators - Front Opening
23
2'-0" [610 mm]
Square Hole
7
'
-
0
"

[
2
1
3
4

m
m
]
O
v
e
r
h
e
a
d
O
p
e
n
i
n
g
F
Casing
Hoist Beam
2
"

[
5
1

m
m
]
T
r
a
v
e
l
Elevation
GP
i
t
M
A
X

6
0

f
t

[
1
8
,
2
8
8

m
m
]

S
e
e

n
o
t
e

#
1
1
Machine Room MIN.
7'-0" [2134mm] for Simplex
14'-0" [4268mm] for Duplex
Single Slide Doors
EB
D
A
C
M
I
N
.

M
a
c
h
i
n
e

R
o
o
m
6
'
-
6
"

[
1
9
8
1

m
m
]
E
B
Center Opening Doors
4" [102 mm] D
A
C
DD
1. Overhead dimension "F" is based on standard cab heights of 8'-0" [2438 mm].
2. Pit depth is 4'-6" [1372 mm] (5'-0" [1524 mm] in Ontario, Canada).
3. Hoist beam shown is to be provided by owner. It can be made removable.
4. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
5. Refer to entrance detail section for required entrance rough openings.
6. Machine room is to be located at the lowest floor adjacent to the hoistway. If remote
location is unavoidable, considerations for hydraulic and electrical lines must be reviewed
with TKNE representative.
7. Machine room must have a clear unobstructed height of 7'-0" [2134 mm].
8. Machine room size required may be larger than shown depending on pump unit required.
9. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
10. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see
"Seismic Zone 2 or Greater Information Tables".
11. For car travel larger than shown contact your TKNE representative.
*Denotes non-compliant with ADA. **Will not accommodate ambulatory requirements.
Capacity (lbs) 2100 2500 3000 3500 4000
(kg) 950 1160 1380 1600 1815
Speed (fpm) 50 to 175 50 to 175 50 to 175 50 to 175 50 to 175
(m/s) 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88
Platform Width "A" (ft) 6'-0" 7'-0" 7'-0" 7'-0" 8'-0"
(mm) 1829 2134 2134 2134 2438
Platform Depth "B" (ft) 5'-9 1/2" 5'-9 1/2" 6'-3 1/2" 6'-11 1/2" 6'-11 1/2"
(mm) 1765 1765 1918 2121 2121
Opening Width "C" (ft) 3'-0" 3'-6" 3'-6" 3'-6" 4'-0"
(mm) 914 1067 1067 1067 1219
Type of Entrance SS** or CO*
**
SS or CO** SS or CO** SS or CO CO
Hoistway Width "D" (ft) 7'-4" 8'-4" 8'-4" 8'-4" 9'-4"
(mm) 2235 2540 2540 2540 2845
Hoistway Depth "E" (ft) 6'-8 1/2" 6'-8 1/2" 7'-2 1/2" 7'-10 1/2" 7'-10 1/2"
(mm) 2045 2045 2197 2400 2400
Hoistway Width "DD" (ft) 15'-0" 17'-0" 17'-0" 17'-0" 19'-0"
(mm) 4572 5182 5182 5182 5791
Overhead "F" (ft) 12'-2" 12'-2" 12'-2" 12'-2" 12'-2"
(without top of car guard rail) (mm) 3708 3708 3708 3708 3708
Overhead "F" (ft) 12'-6" 12'-6" 12'-6" 12'-6" 12'-6"
(with top of car guard rail) (mm) 3810 3810 3810 3810 3810
Pit Depth "G" See note 2
In Ground Hydraulic Passenger Elevators - Front And Rear Opening
24
1. Overhead dimension "F" is based on standard cab heights of 8'-0" [2438 mm].
2. Pit depth is 4'-6" [1372 mm] (5'-0" [1524 mm] in Ontario, Canada).
3. Hoist beam shown is to be provided by owner. It can be made removable.
4. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
5. Refer to entrance detail section for required entrance rough openings.
6. Machine room is to be located at the lowest floor adjacent to the hoistway. If remote
location is unavoidable, considerations for hydraulic and electrical lines must be reviewed
with TKNE representative.
7. Machine room must have a clear unobstructed height of 7'-0" [2134 mm].
8. Machine room size required may be larger than shown depending on pump unit required.
9. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
10. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see
"Seismic Zone 2 or Greater Information Tables".
11. For car travel larger than shown contact your TKNE representative.
Capacity (lbs) 3500 4000 4500 5000 6000
(kg) 1600 1815 2040 2270 2720
Speed (fpm) 50 to 175 50 to 175 50 to 175 50 to 175 50 to 150
(m/s) 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.75
Platform Width "A" (ft) 5'-4" 6'-0" 6'-0" 6'-0" 6'-4"
(mm) 1626 1829 1829 1829 1930
Platform Depth "B" (ft) 8'-4" 8'-4" 8'-10" 9'-6" 10'-4"
(mm) 2540 2540 2692 2896 3150
Opening Width "C" (ft) 3'-10" 4'-0" 4'-0" 4'-0" 4'-6"
(mm) 1168 1219 1219 1219 1372
Type of Entrance 2 speed 2 speed 2 speed 2 speed 2 speed
Hoistway Width "D" (ft) 7'-2" 7'-5" 7'-5" 7'-5" 8'-2"
(mm) 2184 2261 2261 2261 2489
Hoistway Depth "E" (ft) 9'-2" 9'-2" 9'-8" 10'-4" 11'-2"
(mm) 2794 2794 2946 3150 3404
Hoistway Width "DD" (ft) 14'-8" 15'-2" 15'-2" 15'-2" 16'-8"
(mm) 4470 4623 4623 4623 5080
Overhead "F" (ft) 12'-6" 12'-6" 12'-6" 12'-6" 12'-6"
(mm) 3810 3810 3810 3810 3810
Pit Depth "G" See note 2
Casing
Elevation
O
p
e
n
i
n
g
7
'
-
0
"

[
2
1
3
4

m
m
]
2'-0" [610 mm]
Square Hole
P
i
t
G
T
r
a
v
e
l
2
"

[
5
1

m
m
]
Hoist Beam
O
v
e
r
h
e
a
d
F
M
A
X

6
0

f
t

[
1
8
,
2
8
8

m
m
]

S
e
e

n
o
t
e

#
1
1
B E
Machine Room MIN.
7'-0" [2134mm] for Simplex
14'-0" [4268mm] for Duplex D
A
C
M
I
N
.

M
a
c
h
i
n
e

R
o
o
m
6
'
-
6
"

[
1
9
8
1

m
m
]
2 Speed Opening Doors
B E
DD
C
D
A
5" [127 mm] Max.
2 Speed Opening Doors
Hydraulic hospital elevators offer the same spacious cargo
compartments as geared hospital elevators, but are restricted to
lower rise and less demanding traffic applications. Other typical
applications include self-storage facilities, service cars for low-rise
garden hotels and apartments, and ambulatory care facilities.
In Ground Hydraulic Hospital Elevators - Front Opening
25
1. Overhead dimension "F" is based on standard cab heights of 8'-0" [2438 mm].
2. Pit depth is 4'-6" [1372 mm] (5'-0" [1524 mm] in Ontario, Canada).
3. Hoist beam shown is to be provided by owner. It can be made removable.
4. Right hand door shown on simplex elevator arrangement can be left handed
(symmetrically opposite) and is available for use in multiple hoistways.
5. Refer to entrance detail section for required entrance rough openings.
6. Machine room is to be located at the lowest floor adjacent to the hoistway. If remote
location is unavoidable, considerations for hydraulic and electrical lines must be reviewed
with TKNE representative.
7. Machine room must have a clear unobstructed height of 7'-0" [2134 mm].
8. Machine room size required may be larger than shown depending on pump unit required.
9. Dimensional data is in accordance with ASME A17.1 and CAN/CSA B44 elevator codes.
10. For hoistway dimensions and building reactions in Seismic Zone 2 or greater see
"Seismic Zone 2 or Greater Information Tables".
11. For car travel larger than shown contact your TKNE representative.
Capacity (lbs) 3500 4000 4500 5000 6000
(kg) 1600 1815 2040 2270 2720
Speed (fpm) 50 to 175 50 to 175 50 to 175 50 to 175 50 to 150
(m/s) 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.88 0.25 to 0.75
Platform Width "A" (ft) 5'-4" 6'-0" 6'-0" 6'-0" 6'-4"
(mm) 1626 1829 1829 1829 1930
Platform Depth "B" (ft) 9'-1" 9'-1" 9'-7" 10'-3" 11'-1"
(mm) 2769 2769 2921 3124 3378
Opening Width "C" (ft) 3'-10" 4'-0" 4'-0" 4'-0" 4'-6"
(mm) 1168 1219 1219 1219 1372
Type of Entrance 2 speed 2 speed 2 speed 2 speed 2 speed
Hoistway Width "D" (ft) 7'-2" 7'-5" 7'-5" 7'-5" 8'-2"
(mm) 2184 2261 2261 2261 2489
Hoistway Depth "E" (ft) 10'-4" 10'-4" 10'-10" 11'-6" 12'-4"
(mm) 3150 3150 3302 3505 3759
Hoistway Width "DD" (ft) 14'-8" 15'-2" 15'-2" 15'-2" 16'-8"
(mm) 4470 4623 4623 4623 5080
Overhead "F" (ft) 12'-6" 12'-6" 12'-6" 12'-6" 12'-6"
(mm) 3810 3810 3810 3810 3810
Pit Depth "G" See note 2
Elevation
Casing
2
"

[
5
1

m
m
]
O
p
e
n
i
n
g
7
'
-
0
"

[
2
1
3
4

m
m
]
2'-0" [610 mm]
Square Hole
P
i
t
G
T
r
a
v
e
l
Hoist Beam
O
v
e
r
h
e
a
d
F
M
A
X

6
0

f
t

[
1
8
,
2
8
8

m
m
]

S
e
e

n
o
t
e

#
1
1
EB
Machine Room MIN.
7'-0" [2134mm] for Simplex
14'-0" [4268mm] for Duplex D
A
C
M
I
N
.

M
a
c
h
i
n
e

R
o
o
m
6
'
-
6
"

[
1
9
8
1

m
m
]
2 Speed Opening Doors
EB
DD
C
A
D 5" [127 mm] Max.
2 Speed Opening Doors
In Ground Hydraulic Hospital Elevators - Front And Rear Opening
26
Notes:
1. Contact your local representative for entrances requiring
transoms, dry wall construction, and architectural concrete.
2. Entrance frames are not designed to support overhead wall
loads. Suitable supports for these loads must be provided by
others.
3. Finished entrance wall of hoistway not to be built until
doorframes are set.
4. Entrance jambs are available in other types as shown.
5. Consult our local representative for freight elevator entrance
details.
6. Dimensional data is in accordance with the National Code.
Local requirements must be used if more stringent.
Single Slide (SS) A 36" [914] 42" [1067]
B 38 1/2" [978] 44 1/2" [1130]
C 60" [1524] 66" [1676]
Center A 42" [1067] 48" [1220]
Opening (CO) B 25 1/2" [648] 28 1/2" [724]
C 66" [1676] 72" [1829]
Two Speed (TS) A 46" [1168] 48" [1220] 54" [1372]
B 28 1/2" [724] 29 1/2" [750] 32 1/2" [825]
C 70" [1778] 72" [1829] 78" [1981]
Choosing a single slide or center opening elevator entrance with an
appropriate finish will affect your project's appearance, cost and
efficiency. Our unique "N" entrance appears to be a traditional
hollow metal entrance, but its rib construction makes it stronger and
2-hour fire-rated.
Passenger Entrances
27
C-Rough Opening
A-Door Opening
Sill Line
Platform
Hall P/B
Station
Wall
Finish
1

1
/
4
"

[
3
2
]
4

1
/
4
"

[
1
0
8
]
1

1
/
4
"

[
3
2
]
Wall
Finish
4

1
/
4
"

[
1
0
8
]
Hall P/B
Station
Platform
Sill Line
A-Opening
C-Rough Opening
8" [203]
8" [203]
C-Rough Opening
A-Opening
8" [203]
Wall
Finish
Platform
Sill Line
Hall P/B
Station
1

1
/
4
"

[
3
2
]
6

1
/
4
"

[
1
5
9
]
Single Slide
Right Hand shown, Left Hand
available
Center Opening
Two Speed
Right Hand shown, Left Hand
available
1
"

[
2
5
]

S
t
d
.

A
llo
w
a
n
c
e
(
s
in
g
le

s
p
e
e
d

&

c
e
n
t
e
r
o
p
e
n
in
g
)

1

1
/
4
"

[
3
2
]

S
t
d
.
3
/
4
"

[
1
9
]
1" [25] Max.
2x5/8" [16] MIN
1" [25] MIN
1/8" [3] Fire Stop
Wall Finish
(by Others)
Mini Frame Drywall Masonry
ENTRANCE FRAME DETAILS
8
'
-
4
"

[
2
5
4
0
]

M
in
.

F
lo
o
r

t
o

F
lo
o
r

H
e
ig
h
t
1/4" [6]
8
'
-
4
"

[
2
5
4
0
]

R
e
c
e
s
s
e
d

A
r
e
a

f
o
r

R
e
a
r

O
p
n
g
.

o
n
ly
5
"

[
1
2
7
]
1 1/2" [38]
7
'
-
0
"

[
2
1
3
4
]

H
e
ig
h
t
7
'
-
1
0

1
/
2
"

[
2
4
0
0
]

R
o
u
g
h

O
p
e
n
in
g
Section - Single Slide
and Center Opening
Header
Track
Aluminum
Sill
Finished
Floor
Section - Single Slide
and Center Opening
with Recess at Rear
Header
Track
8
'
-
4
"

[
2
5
4
0
]

M
in
.

F
lo
o
r

t
o

F
lo
o
r

H
e
ig
h
t
1/4" [6]
7
'
-
1
0

1
/
2
"

[
2
4
0
0
]

R
o
u
g
h

O
p
e
n
in
g
7
'
-
0
"

[
2
1
3
4
]

H
e
ig
h
t
Finished
Floor
Header
Track
Section - Two Speed
8
'
-
4
"

[
2
5
4
0
]

R
e
c
e
s
s
e
d

A
r
e
a

f
o
r

R
e
a
r

O
p
n
g
.

o
n
ly
5
"

[
1
2
7
]
Header
Track
4" [102]
Section - Two Speed
with Recess at Rear
Note:
This chart is for standard elevators manufactured at ThyssenKrupp Northern and shown on general layouts. Consult engineering for hoistway requirements for
elevators with additional cab interior finishes and/or vertical rail bracket spacing larger than 14 feet.
2100 lb (front opening only) 2" 2" 0" 0" 2" 0" 2" 0"
2100 lb (front & rear opening) 2" 0" 0" 0" 2" 0" 2" 0"
2500 lb (front opening only) 2" 2" 0" 0" 2" 0" 2" 0"
2500 lb (front & rear opening) 2" 0" 0" 0" 2" 0" 2" 0"
3000 lb (front opening only) 2" 2" 0" 0" 2" 0" 2" 0"
3000 lb (front & rear opening) 2" 0" 0" 0" 2" 0" 2" 0"
3500 lb (front opening only) 2" 2" 0" 0" 2" 0" 2" 0"
3500 lb (front & rear opening) 2" 0" 0" 0" 2" 0" 2" 0"
4000 lb (front opening only) 2" 2" 0" 0" 2" 0" 2" 0"
4000 lb (front & rear opening) 2" 0" 0" 0" 2" 0" 2" 0"
3500 lb (front opening only) 3" 0" 0" 0" 1" 0" 1" 0"
3500 lb (front & rear opening) 3" 0" 0" 0" 1" 0" 1" 0"
4000 lb (front opening only) 3" 0" 0" 0" 1" 0" 1" 0"
4000 lb (front & rear opening) 3" 0" 0" 0" 1" 0" 1" 0"
4500 lb (front opening only) 3" 0" 0" 0" 1" 0" 1" 0"
4500 lb (front & rear opening) 3" 0" 0" 0" 1" 0" 1" 0"
5000 lb (front opening only) 4" 0" 0" 0" 0" 0" 3" 0"
5000 lb (front & rear opening) 4" 0" 0" 0" 0" 0" 3" 0"
6000 lb (front opening only) 2" 0" 0" 0" 0" 0" 2" 0"
6000 lb (front & rear opening) 2" 0" 0" 0" 0" 0" 2" 0"
tkNorthern Elevator
Elevators in Seismic Zones 2 and Greater Hoistway Requirements
Add values presented in this chart to standard non-seismic TKNE hoistway sizes.
P
a
s
s
e
n
g
e
r
H
o
s
p
i
t
a
l
Platform
Type
Elevator Capacity &
No. of Openings
Traction Roped Hydro Holeless Hydro In-ground Hydro
add per car
to H/W width
add per car
to H/W depth
add per car
to H/W width
add per car
to H/W depth
add per car
to H/W width
add per car
to H/W depth
add per car
to H/W width
add per car
to H/W depth
Notes:
1) This chart provides approx. seismic guide rail reactions for elevators manufactured at ThyssenKrupp Northern. It covers traction, rope hydraulic and holeless
hydraulic elevators. For in-ground hydraulic elevators rail reactions will be higher and are to be provided by Engineering department.
2) All reactions are in thousands of pounds (KIPS).
2100 1.04 0.52 1.16 0.58 2.07 1.04 2.32 1.16
2500 1.23 0.62 1.38 0.69 2.47 1.23 2.77 1.38
3000 1.32 0.66 1.48 0.74 2.63 1.32 2.96 1.48
3500 1.40 0.70 1.58 0.79 2.80 1.40 3.17 1.58
4000 1.58 0.79 1.78 0.89 3.16 1.58 3.57 1.78
3500 1.38 0.69 1.56 0.78 2.75 1.38 3.11 1.56
4000 1.50 0.75 1.69 0.85 2.99 1.50 3.39 1.69
4500 1.54 0.77 1.76 0.88 3.09 1.54 3.51 1.76
5000 1.64 0.82 1.87 0.94 3.28 1.64 3.74 1.87
6000 1.77 0.89 2.03 1.02 3.54 1.77 4.06 2.03
P
a
s
s
e
n
g
e
r
H
o
s
p
i
t
a
l
Platform
Type
Elevator Capacity (LBS)
Seismic Zone 2 Seismic Zone 3 and greater
R1, car
(KIPS)
R2, car
(KIPS)
R1, cwt
(KIPS)
R2, cwt
(KIPS)
R1, car
(KIPS)
R2, car
(KIPS)
R1, cwt
(KIPS)
R2, cwt
(KIPS)
tkNorthern Elevator
Elevators in Seismic Zones 2 and Greater Guide Rail Reactions
This chart is designed for elevators manufactured at ThyssenKrupp Northern Elevator.
Seismic Zone 2 or Greater Information Tables
28
Work not Involved in the Elevator Contract
Other building trades, under supervision of the General Contractor or his Sub-Contractors, are involved in an elevator
installation. This work by others may vary depending upon local codes, statutes or work practices. Work by others will
normally consist of the following:
GENERAL
Provide a properly framed and enclosed legal hoistway, plumb and to agreed dimensions, including a proper pit with the
necessary ladders, drains, access doors and waterproofing, if required.
Provide suitable machine room with proper clearance for the elevator equipment plus proper lighting, ventilation, heating
and coolingthe room temperature must be maintained within 40F (5C) minimum to 90F (32C) maximum.
Provide the necessary structures to permit safe access to the machine room as defined by ASME A17.1, CSA B44 or
AS-1735 code requirements. Please note with very few exceptions, machine rooms and hoistways should be free of
equipment not essential to elevator operations.
Perform all cutting, filling, patching of walls and floors, plus the removal of all obstructions to permit proper installation of
the elevator. Setting of sleeves and pockets or blockouts for signal fixtures. All painting, except as otherwise specified.
Provide and maintain protective enclosure around hoistway and hoistway openings during the time the elevator is being
installed. Supply and install finished cab flooring.
STRUCTURAL
Construct adequate supports and foundations to carry the loads including impact loads of all equipment. Install the supports
for guide rail brackets and machine beams or overhead sheaves. If adjacent hoistways are used, divider beams at suitable
intervals must be provided for guiderail brackets.
Adequately support the walls above the entrance frames. The entrance frames are not designed to support overhead wall
loads. Provide rough opening min. 12" larger than entrance.
Furnish in the machine room, suitable equipment hoisting beams. Clear room under beams is to be 7ft minimum.
ELECTRICAL
Provide and maintain the proper electric feed to the terminals of each elevator control panel with all necessary main line
switches, circuit-breakers or fused disconnect switches, located at the lock jamb side of the machine room or as per layout
drawings.
Install permanent light fixtures and switches in each pit and machine room. Light switches are to be located on the jamb
side of pit and machine room access. The lighting in machine room should illuminate the front of each controller and be of a
value of not less than 200 lux at floor level. Lighting in pit should be of not less than 200 lux at the pit floor level. In addition,
a duplex receptacle, 15 Amp minimum, should be provided in each pit, machine room and machinery space. Illumination at
sill of every landing is 100 lux.
Furnish and install all fixed conduit, wiring and fittings required to connect remote systems (remote monitoring stations,
telephones, intercommunications, alarms, etc.) with feeders terminating at the elevator controller in each machine room.
Except when the hoistway is enclosed, provide smoke sensors when conditions require at each floor terminating at the
controller in the machine room, a separate smoke sensor shall be provided at the main floor operating independently from
the remaining smoke sensors. Furnish and install seismic switchesif requiredin the machine room.
Work Not Included in the Elevator Contract
tkNorthern Elevator
29
Developing the future.
tkNorthern Elevator
tkNorthern Elevator
Northern Elevator Limited
270 Finchdene Square, Toronto, Ontario, Canada M1X 1A5
Phone: (416) 291-2549 Fax: (416) 291-4654
Sales Department Fax: (416) 291-8348
All photography, illustrations and specifications are based on
information in effect at time of publication approval. TKNE
reserves the right to change specifications or design and to
discontinue items without notice or obligation.
Copyright 2003 ThyssenKrupp Northern Elevator
7231 5/03 Printed in Canada