Escolar Documentos
Profissional Documentos
Cultura Documentos
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
Caution:
This equipment has been tested and found to comply with EN 301489. Its class of conformity is
defined in table A30808-X3247-X910-*-7618, which is shipped with each product. This class also
corresponds to the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the relevant standards referenced in the manual Guide to Documentation, may
cause harmful interference to radio communications.
For system installations it is strictly required to choose all installation sites according to national and
local requirements concerning construction rules and static load capacities of buildings and roofs.
For all sites, in particular in residential areas it is mandatory to observe all respectively applicable
electromagnetic field / force (EMF) limits. Otherwise harmful personal interference is possible.
Trademarks:
All designations used in this document can be trademarks, the use of which by third parties for their own purposes
could violate the rights of their owners.
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
1.4.2
5.3
Expansion and Replacement Procedures of TRAUHC frame into the TRAU-Standard rack
Issue History
Issue
Date of issue
07/2003
12/2003
A30808-X3247-L460-2-7631
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
This document consists of a total of 150 pages. All pages are issue 2.
Contents
1
1.1
1.2
1.3
1.4
1.4.1
1.4.2
1.5
1.6
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Purpose of the Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Position in the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Site Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Station Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TRAU Standard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TRAU-HC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable Length between Network Elements . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
2.1
2.2
2.3
2.4
2.4.1
2.4.2
2.5
2.5.1
2.5.2
2.5.3
2.6
2.6.1
2.6.2
Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Installation Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Equipment Delivery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Equipment Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Rack Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Devices and Boards Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Installation of the TRAU-Standard Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Grounding connections of the TRAU Standard Rack (S30861-C21-X) . . . 33
Grounding collector and fire protection kit for the TRAU-Standard rack
(MK:FGV* - S30861-K106-X) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Fan units (FG Kit - S50201-U32-X) and rack door (FG kit - C50324-A201-B12)
for fire resistance cabinet.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Earthquake Kit for the TRAU-Standard Rack. . . . . . . . . . . . . . . . . . . . . . . 41
Installation of the TRAU-HC Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Earthquake Kit for TRAU-HC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Grounding connections for the TRAU-HC Rack . . . . . . . . . . . . . . . . . . . . . 64
3
3.1
3.2
3.3
3.4
65
65
65
66
67
4
4.1
4.1.1
4.1.2
4.2
4.2.1
4.2.2
4.3
4.3.1
4.3.2
4.4
69
71
73
75
77
77
81
82
84
86
88
2.5.2.1
A30808-X3247-L460-2-7631
13
13
13
14
14
14
18
21
22
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
4.4.1
5
5.1
5.2
5.2.1
5.2.2
5.2.3
5.2.4
5.3
5.3.1
5.3.2
Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Illustrations
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
A30808-X3247-L460-2-7631
1.1
1.2
1.3
1.4
1.5
1.6
1.7
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
2.11
2.12
2.13
2.14
2.15
2.16
2.17
2.18
2.19
2.20
2.21
2.22
2.23
2.24
2.25
2.26
2.27
2.28
2.29
2.30
2.31
2.32
2.33
2.34
2.35
2.36
13
16
17
19
20
21
22
24
26
27
29
31
32
32
33
34
35
38
39
40
42
43
44
45
46
47
49
50
51
52
52
53
54
57
58
59
60
61
61
62
62
63
64
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
3.1
3.2
4.1
4.2
4.3
4.4
4.5
4.6
4.7
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
TRAU-Standard power IN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
TRAU-HC power IN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
TRAU Standard top view : Rach Cabling Access Panel (RCAP) . . . . . . 69
TRAU-HC top view : Rach Cabling Access Panel (RCAP) . . . . . . . . . . . 70
Coax Adapter mounted on left side (GW6, LW6) . . . . . . . . . . . . . . . . . . 73
Coax Adapter mounted on right side (AW6, DW6) . . . . . . . . . . . . . . . . . 74
PCM line connections to MDF (to/from BSC and MSC) . . . . . . . . . . . . . 76
Remote Alarm connection to terminal block . . . . . . . . . . . . . . . . . . . . . 80
Coax Adapter mounted on left and right side . . . . . . . . . . . . . . . . . . . . . 84
TRAU Rack - Top view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Rack left side and rack right top side . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Power and ground cables distribution. . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Interconnections list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
TRAU Sub-rack: front view (fuse panel shown in open position) . . . . . . 98
TRAU sub-rack: Fuse Panel Mounting and Cabling . . . . . . . . . . . . . . . . 99
Adapter Board layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Adapter Board layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Adapater Board system block diagram . . . . . . . . . . . . . . . . . . . . . . . . . 102
DC-PANEL system block diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
5.11
5.12
5.13
5.14
5.15
5.16
5.17
5.18
5.19
5.20
5.21
5.22
5.23
5.24
5.25
5.26
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
A30808-X3247-L460-2-7631
6.10
6.11
6.12
6.13
6.14
6.15
7.1
7.2
IMN:TRAU
Ground cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Alarm cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Daisy chain and Signal cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DC Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standard rack drilling sketch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HC rack drilling sketch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
143
144
144
145
145
146
147
147
IMN:TRAU
10
Installation
Transcoding and Rate Adaption Unit
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Tables
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
A30808-X3247-L460-2-7631
1.1
1.2
1.3
2.1
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
4.13
4.14
4.15
4.16
4.17
4.18
4.19
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
5.11
5.12
5.13
5.14
5.15
5.16
5.17
5.18
6.1
6.2
Board equipping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Coaxial cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Balanced cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Types of anchorage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Left TRAUs PCM lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Right TRAUs PCM lines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
PCM Lines connector pinning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Pinning of the 75ohm PCM on Adapter board . . . . . . . . . . . . . . . . . . . . 74
Pinning of the PCM connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Left TRAUs Remote alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Right TRAUs Remote alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Layout of the pins of connector AW3/DW3/GW3/LW3 . . . . . . . . . . . . . 78
Pinning of the Remote Alarm cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Pin description of the connectors W14 and W15 . . . . . . . . . . . . . . . . . . 81
Left TRAUs PCM lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Right TRAUs PCM lines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
PCM Lines connector pinning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Pinning of the 75ohm PCM on Adapter board . . . . . . . . . . . . . . . . . . . . 85
Pinning of the PCM connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Left TRAUs Remote alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Right TRAUs Remote alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Layout of the pins of connector AW0-AW7 . . . . . . . . . . . . . . . . . . . . . . 89
Pinning of the Remote Alarm cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Connectors position, type and function . . . . . . . . . . . . . . . . . . . . . . . . . 93
Table of the Fuse Panel cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
X25 connector of the Adapter Board . . . . . . . . . . . . . . . . . . . . . . . . . . 103
X23,X24 connectors of the Adapter Board . . . . . . . . . . . . . . . . . . . . . 104
X27 connector of the Adapter Board . . . . . . . . . . . . . . . . . . . . . . . . . . 105
X26 connector of the Adapter Board . . . . . . . . . . . . . . . . . . . . . . . . . . 106
X5,X6 connectors of the Adapter Board . . . . . . . . . . . . . . . . . . . . . . . 108
X1,X2 and X3,X4 connectors of the Adapter Board. . . . . . . . . . . . . . . 108
X7 to X22 connectors of the Adapter Board . . . . . . . . . . . . . . . . . . . . 109
X13,X14 connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
X15,X16 connectors of the Front Panel Board . . . . . . . . . . . . . . . . . . 113
X17 connectos of the Front Panel Board . . . . . . . . . . . . . . . . . . . . . . . 114
X1/X12 connectors of the Front Panel Board . . . . . . . . . . . . . . . . . . . 115
PCM lines connector in the Frame backpanel and in the RCAP . . . . . 119
X3,X4 connectors of the Extra Adapter Board . . . . . . . . . . . . . . . . . . . 128
X5,X6 connectors of the Extra Adapter Board . . . . . . . . . . . . . . . . . . . 129
X1,X2 connectors of the Extra Adapter Board . . . . . . . . . . . . . . . . . . . 129
X7 connector of the Extra Adapter Board . . . . . . . . . . . . . . . . . . . . . . 130
List of Rack Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
List of Frame cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
11
IMN:TRAU
12
Installation
Transcoding and Rate Adaption Unit
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
1 General
i
i
i
i
1.1
The CE declaration of conformity for the product will be fulfilled if the setup and cabling
is undertaken in accordance with the specification in the manual and the documentation
listed there, such as mounting instructions, cable lists etc. Where necessary, account
should be taken of project-specific documentation. Deviations from the specifications or
independent changes during setup, such as use of cable types with lower screening
values, for example, can lead to the CE requirements being violated. In such cases the
CE declaration of conformity is invalidated and the responsibility passes to the person
who has caused the deviations.
The applicable technical standards and regulations are listed in the Terminology-Guide
to Documentation A30808-X3247-K-52-1-7635.
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in
a commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
For the US market the following note applies:- PCM ports are intended to be connected
to a near-placed Listed CSU (Channel Service Unit) providing over voltage protection.
1.2
BTS
Mobile
Station
BSC
Abis
Interface
TRAU
Asub
Interface
MSC
A
Interface
SBS
Fig. 1.1
A30808-X3247-L460-2-7631
13
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
1.3
Site Requirements
Before starting the installation, the construction of the room in which the operation and
maintenance equipment is to be housed must be complete and the room in good condition and dry heaters, if necessary, should be put up in the room.
Doors and windows, if any, must already have been installed and must be lockable.
Openings in wall or ceiling of floor, if required, must be complete.
The floor covering must have been laid.
Room lighting and wall sockets must have been installed.
Heating or air-conditioning systems should be ready for operation.
Walls and ceilings should have been painted.
The room must be clean.
To prevent subsequent accumulation of dust and dirt, the parts and equipment units to
be installed must be unpacked outside the room (if possible).
After that it is advantageous to install the OMS-B equipment, after all other installation
works to create the required infrastructure (power supply, PCM30 lines ...) are complete.
1.4
Station Configuration
The TRAU functionality is mechanically arranged in two variants:
- TRAU rack able to manage up to 480 TCH (Standard configuration)
- TRAU-HC rack able to manage up to 960 TCH (High capacity configuration)
1.4.1
TRAU Standard
The TRAU Standard rack (S30861-C21-X), which is configured according to the ETSI
standard (h=2000mm, l=600mm, p=300mm) (h=78.7,w=23.6,d=11.8) can accommodate up to 4 TRAU subracks equal each other and equipped with the same boards (files
BC, EF, HI and MN). Every subrack includes a fuse and alarm panel (files A, D, G and
L). Files A, D, G and L relate to the backplanes of the TRAU subracks with the connectors for internal and external connections. A lamp panel is equipped in file T. The sensor
of the Open Door Alarm (OPDS) is equipped in file O.
The TRAU rack includes up to 4 subrack (4 TRAU modules)
The subrack (H=420mm (16.5), W=533mm (21), D=249mm (9.8) includes the interfaces to the BSC (BSCI) and the MSC (MSCI) , the transcoders (TRAC) and the cable
connection zone to the RCAP of the rack.
TRAU subrack capacity (depending on PCM line type):
One PCM line with 120 or 96 16kbit/s channels to/from the BSC.
Four PCM lines with 30 or 24 64kbit/s channels to/from the MSC.
This capacity corresponds to 15 or 12 TRXs (full rate) located in the BTS (radio
measures pre-processed in the BTS).
14
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Acronym
Slot position
2
2
6
BSCI
MSCI
TRAC
40-44
36-48
18-24-30
52-58-64
PWRS
3-71
Tab. 1.1
Notes
1
1
2
Board equipping
A30808-X3247-L460-2-7631
15
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
GLOBAL ALARMS
POWER 0
10A
F
LAMP
TEST
CRITICALMAJOR MINOR
POWER 1
LOCAL
TERMINAL
10A
F
BSC
LINK
ALARM
P
W
R
S
0
T
R
A
C
0
T
R
A
C
1
T
R
A
C
2
18
24
30 36 40 44 48 52 58 64
M
S
C
I
0
T
R
A
C
3
T
R
A
C
4
T
R
A
C
5
P
W
R
S
1
LOCAL
TERMINAL
10A
F
LAMP
TEST
BSC
LINK
ALARM
T
R
A
C
0
T
R
A
C
1
T
R
A
C
2
T
R
A
C
5
P
W
R
S
1
18
24
30 36 40 44 48 52 58 64
71
M
S
C
I
0
B
S
C
I
1
B
S
C
I
0
M
S
C
I
1
GLOBAL ALARMS
POWER 0
10A
F
T
R
A
C
3
T
R
A
C
4
LAMP
TEST
LOCAL
TERMINAL
10A
F
BSC
LINK
ALARM
P
W
R
S
0
T
R
A
C
0
T
R
A
C
1
T
R
A
C
2
T
R
A
C
5
P
W
R
S
1
18
24
30 36 40 44 48 52 58 64
71
M
S
C
I
0
B
S
C
I
1
B
S
C
I
0
M
S
C
I
1
GLOBAL ALARMS
POWER 0
10A
F
T
R
A
C
3
T
R
A
C
4
LAMP
TEST
LOCAL
TERMINAL
10A
F
BSC
LINK
ALARM
P
W
R
S
0
T
R
A
C
0
T
R
A
C
1
T
R
A
C
2
T
R
A
C
5
P
W
R
S
1
18
24
30 36 40 44 48 52 58 64
71
M
S
C
I
0
HI
CRITICALMAJOR MINOR
POWER 1
EF
CRITICALMAJOR MINOR
POWER 1
BC
71
CRITICALMAJOR MINOR
POWER 1
M
S
C
I
1
GLOBAL ALARMS
POWER 0
10A
F
P
W
R
S
0
B
S
C
I
1
B
S
C
I
0
B
S
C
I
0
B
S
C
I
1
M
S
C
I
1
T
R
A
C
3
T
R
A
C
4
MN
O
OPDS
Fig. 1.2
16
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
GLOBAL ALARMS
POWER 0
10A
F
POWER 1
LOCAL
TERMINAL
10A
F
P
W
R
S
0
3
T
R
A
C
1
T
R
A
C
2
T
R
A
C
5
P
W
R
S
1
18
24
30 36 40 44 48 52 58 64
71
M
S
C
I
0
B
S
C
I
1
B
S
C
I
0
M
S
C
I
1
GLOBAL ALARMS
POWER 0
T
R
A
C
3
T
R
A
C
4
LOCAL
TERMINAL
10A
F
M
S
C
I
0
BSC
LINK
ALARM
B
S
C
I
1
B
S
C
I
0
M
S
C
I
1
T
R
A
C
3
T
R
A
C
4
T
R
A
C
5
T
R
A
C
0
T
R
A
C
1
T
R
A
C
2
18
24
30 36 40 44 48 52 58 64
GLOBAL ALARMS
POWER 0
10A
F
P
W
R
S
1
POWER 1
LOCAL
TERMINAL
LAMP
TEST
BSC
LINK
ALARM
P
W
R
S
0
T
R
A
C
0
T
R
A
C
1
T
R
A
C
2
18
24
30 36 40 44 48 52 58 64
M
S
C
I
0
B
S
C
I
1
B
S
C
I
0
M
S
C
I
1
GLOBAL ALARMS
POWER 0
10A
F
T
R
A
C
3
T
R
A
C
4
T
R
A
C
5
P
W
R
S
1
LOCAL
TERMINAL
10A
F
LAMP
TEST
BSC
LINK
ALARM
P
W
R
S
0
T
R
A
C
0
T
R
A
C
1
T
R
A
C
2
T
R
A
C
5
P
W
R
S
1
18
24
30 36 40 44 48 52 58 64
71
M
S
C
I
0
B
S
C
I
0
B
S
C
I
1
M
S
C
I
1
T
R
A
C
3
T
R
A
C
4
OPDS
Fig. 1.3
HI
71
CRITICALMAJOR MINOR
POWER 1
EF
71
CRITICALMAJOR MINOR
10A
F
BC
LAMP
TEST
CRITICALMAJOR MINOR
POWER 1
BSC
LINK
ALARM
T
R
A
C
0
10A
F
P
W
R
S
0
LAMP
TEST
CRITICALMAJOR MINOR
MN
A30808-X3247-L460-2-7631
17
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
1.4.2
TRAU-HC
The new TRAU-HC (S30861-C37/C41-X) rack has the same footprint as that the
previous TRAU Standard rack, mechanical dimensions h=2000, l=600, p=300 (h=78.7,
w=23.6, d=11.8) , but each rack includes up to 4 Frames (8 TRAUs) (Fig. 1.5). Fans
are included for heat dissipation (Fig. 1.4). No power supply card is necessary because
all the cards have a DC/DC converter on board. The weight, fully equipped, is 130 Kg
(286 lb).
The rack is equipped with an alarm panel placed at the top of the rack which can be
attained by removing the front cover
The racks have a door mounted. Therefore a new alarming mechanism is introduced
detecting when the door is left Open (see detail x in Fig. 2.19). The relevant TRAU
Open door alarm is managed by SW and treated as an internal alarm. A sensor is
cable-connected to the first TRAU shelf of the rack, indicating when the TRAU door is
Open.
The new TRAU frame can be mounted on the old rack by using the Extra Adapter Board
(S30861-U725-X) mounted into the DC-Panel. In that case, as the RCAP board is the
same as that of the Standard configuration, the number of channels cannot exeed 480
TCH.
The TRAU rack configuration is modular in accordance with the number of the
transcoders to be equipped. The number of the transcoders depends on the number of
traffic channels coming from the BSC.
Each TRAU module is functionally independent from the other ones and can be
equipped with 5 (+1 redundant) transcoder boards (TRAC). Every TRAC board handles
up to 24 traffic channels.
Fig. 1.4 shows a picture of the TRAU HC fully equipped.
Leds, lamps, signallings and alarms reporting have the same philosophy as that of the
Standard configuration (Fig. 1.4 and Fig. 1.5) except for the Fan-alarm and Door-Open
alarms. The Fan-alarm is reported on the TRAU_Left and the door-open-alarm on the
TRAU_Right. So to manage both the alarms, the presence of two TRAUs at least, within
the same subrack, is necessary.
.
18
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
TRAU 0
TRAU 2
TRAU 3
TRAU 4
TRAU 5
TRAU 6
Fig. 1.4
TRAU 1
TRAU 7
A30808-X3247-L460-2-7631
19
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
DC Panel
TRAU module
Fig. 1.5
20
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
1.5
IMN:TRAU
Abis
BTS
BSC
Asub
TRAU
MSC
BSS
Fig. 1.6
For the US market PCM ports are intended to be connected to a near-placed Listed
CSU (Channel Service Unit) providing over voltage protection.
Coaxial Version
Connection
Max. hop
attenuation
Max. hop
length
6 dB
Asub
6 dB
Abis
6 dB
Tab. 1.2
Coaxial cables
Balanced Version
Connection
Max. hop
length
6 dB
Asub
6 dB
Abis
6 dB
Tab. 1.3
Max. hop
attenuation
Balanced cables
Whenever two equipment elements are connected through High Frequency-Distribution Frames (HF-DF), the maximum attenuation is as follows:
A30808-X3247-L460-2-7631
21
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
BSC
TRAU
Fig. 1.7
1.6
6 dB
6 dB
6dB
6dB
HF-DF
HF-DF
Installation Activities
The installation activities for the BSS-TRAU rack consist of the following:
Unpacking the rack and inspecting for visible damages
Positioning the rack as per floor plan and anchoring it to the floor
Grounding the rack
Connecting DC power to the rack
Note: The recommended torque value for the screws of the input terminal block is
from 1.24 to 2.26 N x m (11 to 20 lb x in).
Connecting external cables
Inserting power supply boards and disk units into the rack.
22
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
2 Mechanical Installation
2.1
Installation Tools
The correct rack installation is carried out with the aid of the following tools (see
Fig. 2.1).
Hammer drill (ATF)
Twist drills widia 20mm (0.79) and 9mm (0.35) (PRP)
Poligonal socket wrench (CHT)
Poligonal wrench (CHP)
N3 and N4 screwdrivers (CAT) for cross-slotted screws
N2, N3 and N4 screwdrivers (CA)
Square (SQ)
Plumb line (FP)
Tracer (TR)
Screwdrivers for M3, M6 and M12 hex.socket head screws (CHB)
Electric jigsaw with sawdust vacuum and filter (for raised floors only) (ATS)
Other tools are needed for the electrical connections:
Wire-wrap tool for 0.8 x 1.2mm (0.03x0.05)anchoring pins and 0.5mm (0.02) wire
Power soldering iron for tinned copper braid welding
Soldering iron for electronic circuits
Crimping tool
A30808-X3247-L460-2-7631
23
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
Fig. 2.1
24
Installation tools
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
2.2
IMN:TRAU
Equipment Delivery
Racks, devices, boards, cables as well as all installation material and relevant manuals
are shipped in cartons or in wood boxes. Handle each container with extreme caution to
avoid tipping.
All boxes containing installation material have the following information printed on them
or indicated in label W of Fig. 2.2 and Fig. 2.3:
trade-mark
customer order number
serial number of rack or other equipment
destination
gross and net weight
overall dimensions
symbol or inprint to identify the "Top" or "Bottom"
For transport of the cartons from the unloading area into the construction room use
handling aids (for example: fork-lift truck, goods elevator); a second person is needed
for help.
2.3
Preliminary Checks
Check that the cartons are not damaged. In case of evident damage due to transport,
unpack the equipment in the presence of an insurance company representative and
promptly claim any damage and inform the shipper for specifying the damage.
Check whether the package is actually addressed to the site and complete.
Open it and take the contents out carefully.
After having removed all contents from the packing material, check for deformation to
the devices, of torn or unwelded wiring, of oxidized connectors, as well as deformed
front sides of the units, loose screws, damage to paint work, etc.
2.4
Equipment Unpacking
During the unpacking steps great care must be taken to ensure that the equipment is
not scratched or damaged in any way.
The packing material should be preserved for possible future re-packing.
In case of repacking or in the event that repacking material is supplied by the customer,
special care should be taken to avoid damage during the transport and storage of the
devices.
A30808-X3247-L460-2-7631
25
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
8
1
2
GILE
FRA
3
Fig. 2.2
26
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Z
W
3
Z1
Z2
Fig. 2.3
A30808-X3247-L460-2-7631
27
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
2.4.1
Rack Unpacking
With reference to Fig. 2.2 proceed as follows:
Cut the straps 8 and 9 and remove the container cover 7.
Take out the rack from the box 1 and the relevant wood support 2.
Open the tubular shrink-wrap 5 protecting the rack and take it out.
Remove the 8 dehydrating material bags 6 fixed with adhesive tape.
Remove the protections 3 of rack head and base and lift the rack to vertical position.
Remove the 2 front profiles 4 and the 2 rear profiles 4 protecting the rack edges.
2.4.2
28
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
2.5
IMN:TRAU
Standard floor
(concrete)
Wall anchorage
Stand alone rack
Back to back racks
Tab. 2.1
yes
yes
yes
Raised floor
yes
yes
yes
Types of anchorage
Note: The stand alone rack anchored on raised floor must be also fixed to the wall.
The installation of the TRAU requires the following accessories, available separately
(see Fig. 2.4):
-
Adaption (AD):
Expansion bolts (M8):
90 (3.5
70 (2.8
AD
M8
6 (0.2)
Fig. 2.4
A30808-X3247-L460-2-7631
29
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
.For correct positioning of the rack, trace the drilling plan of the floor, whichever this is,
using the plumb line, the square and the tracer. These procedures, relevant to the rack
installation, adjustment and alignment, are valid for all types of rack configurations.
Make sure the leveling feet (P1-P4) of the rack basement do not stretch out the basement level. Place the rack in vertical position, then make the reference pins of the alignment bar, to be aligned with the corresponding holes in the rack basement. Make sure
the alignment bar is fully inside the groove of the rack basement.
Remove the flame guard hex.socket head screws, M12, and washers from the hole for
the expansion bolt M8.
Put the rack in a vertical position so that the holes on the floor coincide with the holes of
the rack basement.
Adjust the leveling feet (P1-P4) of the basement to have the rack coinciding both vertically and horizontally in the correct position.
Screw tightly the hexagonal bolts (M8x10) of the upper anchorage, then the hexagonal
expansion bolts (2xM8x25) of the floor by means of a 13mm (0.5) socket wrench. For
elevated floor, use proper (2x5x30 Din 97/UNI 702) self-thread screws and tighten them
firmly.
30
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Y detail
Fig. 2.5
A30808-X3247-L460-2-7631
31
IMN:TRAU
32
Installation
Transcoding and Rate Adaption Unit
Fig. 2.6
Fig. 2.7
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
2.5.1
IMN:TRAU
The grounding kit has not to specify when the Fire Resistance kit S30861-K106-X is
used; in this case the grounding kit (C50324-A201-A6) is part of the Fire Resistance kit
itself.
The kit contains the following items:
10+/-1.5
(0.39+/-0.06)
1.
2.
3.
4.
5.
25+/-1.5
(0.98+/-0.06)
Fig. 2.8
Grounding kit
The ground plate assy (see Fig. 2.10) contains the following items:
1.
2.
3.
4.
5.
A30808-X3247-L460-2-7631
ground plate
washer
contact washer
hexagon nut
screw
33
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
46.5 (1.83)
77.5 (3.05)
Fig. 2.9
34
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Fig. 2.10
A30808-X3247-L460-2-7631
35
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
2.5.2
36
The Grounding kit use the same components and the same mounting instructions as
the kit S30861-K124-X (see par. 2.5.1)
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
2.5.2.1
IMN:TRAU
Fan units (FG Kit - S50201-U32-X) and rack door (FG kit - C50324A201-B12) for fire resistance cabinet.
This kit is available only for S30861-C21-X TRAU-Standard rack.
The fan units kit consists of :
Fan motor assembly
Two power supply cables
Mounting instruction with reference to Fig. 2.11 :
Remove grid cover 1) by the screws.
Remove nuts 3) and connect fan units power supply cables 4) and 5).
Cables lug to be connected on the existing ones.
Lock cables by the previously removed nuts 3).
With reference to Fig. 2.12:
Connect power supply cables 4) and 5) coming from Bus Bar PP0 as shown.
Cables must be fixed to the fan unit front panel as shown by cable ties 7) supplied
with the kit.
Insert fan units 6) in the rack and fit it by grid cover screws 2) previously removed.
Place the cables in the left rack space (side of the sub-racks).
With reference to Fig. 2.13
Remove door fixing scews 1) and disconnect door ground cable from door side.
Place new door and connect the door ground cable previously disconnected and fix
the door by the removed scews 1).
Place the label 20) in indicated position.
A30808-X3247-L460-2-7631
37
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
2)
T
H
GLOBAL ALARMS
POWER 0
10A
F
POWER 1
LOCAL
TERMINAL
10A
F
Fig. 2.11
38
P
W
R
S
0
T
R
A
C
0
18 24
T
R
A
C
1
LAMP
TEST
CRITICALMAJOR MINOR
BSC
LINK
ALARM
B
S
C
I
0
T T
R R
A A
C C
4 5
P
W
R
S
1
30 36 40 44 48 52 58 64
71
T
R
A
C
2
M
S
C
I
0
B
S
C
I
1
M
S
C
I
1
R
A
C
3
BC
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
6)
2)
T
H
A
GLOBAL ALARMS
POWER 0
10A
F
POWER 1
LOCAL
TERMINAL
10A
F
P
W
R
S
0
T
R
A
C
0
18 24
5) BLUE
FROM BUS BAR PP0 -V
T
R
A
C
1
LAMP
TEST
CRITICALMAJOR MINOR
BSC
LINK
ALARM
B
S
C
I
0
T T
R R
A A
C C
4 5
P
W
R
S
1
30 36 40 44 48 52 58 64
71
T
R
A
C
2
M
S
C
I
0
B
S
C
I
1
M
S
C
I
1
R
A
C
3
BC
5)
7)
4) BLACK
FROM BUS BAR PP0 +V
4)
5)
FANS EXISTING CABLE
Fig. 2.12
A30808-X3247-L460-2-7631
39
Installation
Transcoding and Rate Adaption Unit
EXISTING LABELS
IMN:TRAU
Fig. 2.13
40
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
2.5.3
IMN:TRAU
This kit is available only for S30861-C21-X rack starting from issue 06 on.
The kit for TRAU-Standard (MK: EQ4V1 - S30861-K105-X) consists of (Fig. 2.16):
1.
2.
3.
4.
i
!
The Earthquake Kit allows the TRAU rack to conform with the Bellcore specification and
is mandatory for the U.S. market.
The concrete floor shall have the compressive strength of 30 N/mm2 minimum
With reference to Fig. 2.14, Fig. 2.15 and Fig. 2.16 proceed as follows:
1. Mark floor holes.
2. Drill a 90mm (3.54) deep hole (18 mm (0.71) diameter hole) for each Anchoring
screw.
3. Using an appropriate vacuum, clear the hole with a small diameter hose which can
reach the bottom of the hole.
4. Take off the leveling feet (P1-P4 in Fig. 2.6 and Fig. 2.7) from the rack basement
and, if necessary, extend the hole size to 20 mm (0.79) diameter.
5. Place the TRAU rack. The hole of the rack basement must fit the hole on the floor.
6. Position the Internal Plates over the holes. Be careful not to let any debris fall into
the holes.
7. Insert the anchor into the hole and tap the anchor down with a hammer until the
washer contacts the rack internal plate.
8. Screw down the Anchor HSL M12/50 having 80Nm tightening torque.
A30808-X3247-L460-2-7631
41
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
N4 EXAGONAL-HEAD SCREW
(HSL M12/50) FOR ANCHORAGE
TRAU CABINET
TRAU POSITION
16
(6. 0
3)
300
(11
.8
)
95
(3.
7)
0
30 .8)
(11
0
60 .6)
(23
0
15 )
9
(5.
Fig. 2.14
42
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
N4 GOLFARE FOR
LIFT THE CABINET
INTERNAL PLATE
HSL M12/50
WASHER
162
(6.37)
84
(3.3)
18
(0.71)
18 (0.71)
FLOOR
Fig. 2.15
A30808-X3247-L460-2-7631
(41 3)
90 (3.5)
18+1
43
IMN:TRAU
Fig. 2.16
44
Installation
Transcoding and Rate Adaption Unit
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
Fig. 2.17
IMN:TRAU
A30808-X3247-L460-2-7631
45
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
220 mm (8.7)
21 mm
(0.83)
37,5 mm (1.5)
160 mm (6.3)
145 mm (5.7)
275 mm (10.8)
Fig. 2.18
46
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
2.6
IMN:TRAU
If the rack is provided with the earthquake kit take care of the floor flatness/ruoghness.
The foor flatness tolerance must be 6mm/mq max. and the roughness tolerance 5 mm
max
BR
G1
G2
CNB
Fig. 2.19
A30808-X3247-L460-2-7631
Detail Y
47
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
The Y detail shows the ESD jack (CNB) for wrust (BR) strap connection.
The rack can be anchored on the concrete floor or raised floor in stand alone or back to
back mode (see Fig. 2.23).
Before starting of rack installation, consult the site documentation to locate the installation point of the TRAU rack, the PCM network termination, the Alarm connection point,
the Power Supply unit; then check the earthing bar and the necessary cable runways.
48
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
2250mm (88.6)
2000mm (78.7)
Minimum
room height
Front
600mm (23.6)
950mm (37.4)
Minumum
100mm (3.9)
300 mm (11.8)
Front
700mm (27.6)
Fig. 2.20
A30808-X3247-L460-2-7631
49
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
2000mm (78.7)
Minimum
room height
2250mm (88.6)
Front
Front
600mm (23.6)
300 mm (11.8)
Minimum
100mm (3.9)
1900mm (74.8)
Front
1500mm (59)
Front
600mm (23.6)
950mm (37.4)
Minimum
800mm (31.5)
Fig. 2.21
50
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
300+0-1.5 (11.8+0-0.01)
transportation holes
145+/-0.25 (5.7+/-0.01)
57
(2.2)
BASEMENT LAYOUT
300+/-0.25 (11.8+/-0.01)
80 (3.15)
45 (1.77)
adjustable feet
599+/-1 (23.6+/-0.04)
Fig. 2.22
Drilling sketch
A30808-X3247-L460-2-7631
51
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
Fig. 2.23
Rack levelling
Washer
Anchor
Fig. 2.24
52
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
(Di=0.67 De=1.18)
(3.5)
Fig. 2.25
(D=0.71)
If the distance between the raised and the concrete floor (Ground floor loose stone foundation) is bigger than the lenght of the screw of the anchor (e.g. HILTI M12/300) replace
the screw of the anchor with a threaded rod M12 DIN 975 cutting the same at the right
leght.
A30808-X3247-L460-2-7631
53
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
Fig. 2.26
54
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
2.6.1
IMN:TRAU
!
!
The foor flatness tolerance must be 6mm/mq max. and the roughness tolerance 5 mm
max
The concrete floor shall have the compressive strength of 30 N/mm2 minimum
The kit for TRAU-HC (MK: EQ4V2 - S30861-K121-X) consists of (Fig. 2.30):
1.
2.
3.
4.
5.
6.
For installed TRAU-HC pull out the cards of the down rack and take out the four guiderails on the right side and the four guide-rails on the left side
Mounting Instructions
With reference to Fig. 2.27 Fig. 2.28, Fig. 2.29 and proceed as follow:
1. Pull out the cards of the down rack if they are inserted and take out the three guiderails on the right side and the two guide-rails on the left side (mark their slot position,
so it is easier to reassemble them)
2. Mark floor holes (if the new rack replaces the old standard type you can use the
previous holes by two anchoring screws S30861-K126-X kit (see mounting instruction belove).
3. Drill a 105mm (4.13) deep hole (18 mm (0.71) diameter hole) for each anchoring
screw.
4. Using an appropriate vacuum, clear the hole with a small diameter hose which can
reach the bottom of the hole.
5. Take off the leveling feet (P1-P4 in Fig. 2.23) from the rack basement and, if necessary, extend the hole size to 20 mm (0.79) diameter.
6. Place the insulating plate and the TRAU rack on. The hole of the rack basement
must fit the hole on the floor.
7. Position the Internal Plates over the holes. Be careful not to let any debris fall into
the holes.
8. Insert the anchors into the holes and tap the anchors down with a hammer until the
washer contacts the rack internal plate.
9. Insert on the anchors the insulating bush, theinsulating washer, the washer, and
screw down the Anchor HSL M12/50 having 80Nm tightening torque.
A30808-X3247-L460-2-7631
55
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
56
After the installation stick 20 code label on rack door in reserved area
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
Fig. 2.27
IMN:TRAU
A30808-X3247-L460-2-7631
57
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
N4 EXAGONAL-HEAD SCREW
(HSL M12/50) FOR ANCHORAGE
TRAU CABINET
(10 271
.67
)
TRAU POSITION
(5. 145
71
)
(2. 67.5
66
)
0
30 .8)
(11
0
60 .6)
(23
0
15 )
9
(5.
Fig. 2.28
58
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
N2 GOLFARE FOR
LIFT THE CABINET
INTERNAL PLATE
HSL M12/50
WASHER
162
(6.37)
84
(3.3)
18
(0.71)
18 (0.71)
FLOOR
105 (4.1)
18+1
Fig. 2.29
A30808-X3247-L460-2-7631
59
IMN:TRAU
Fig. 2.30
60
Installation
Transcoding and Rate Adaption Unit
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
145 mm (5.7)
220 mm (8.7)
5 mm(0.02)
37,5 mm (1.5)
145 mm (5.7)
5 mm(0.2)
23 mm (0.91)
275 mm (10.8)
Fig. 2.31
Fig. 2.32
A30808-X3247-L460-2-7631
61
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
1
2
3
4
5
62
Fig. 2.33
Fig. 2.34
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
Fig. 2.35
IMN:TRAU
A30808-X3247-L460-2-7631
63
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
2.6.2
ground bolts
Fig. 2.36
To grounding the rack use a 16mm2/5AWG or 25mm2/3AWG PVC Ye/Gr copper wire.
The connection should be connected to a ground collector bar on the shortest way.
Mounting instruction of the grounding of the rack (see Fig. 2.36):
Use the nearest ground system on site.
Verify the distances between the connection point of the ground system and the
ground bolts of the rack.
Cut the wire to the required lenght.
Unsheet the wire at the end and crimp a two-hole M6 lug terminal (i.e. Thomas &
Betts type 54852BE blu color for 16mm2/6AWG or 54856BE brown color for
25mm2/3AWG).
Remove exagonal nut, lock washer and contact washer from the ground bolt.
Connect the prepared wire to the ground bolts by a two-hole lug terminal.
Replace the contact washer, lock washer and hexagonal nut.
Tighten the hexagonal nut firmly.
64
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Requirements
The equipment shall be connected to a 48V DC SELV source which is electrically
isolated from the AC source and which is reliably connected to earth.
The BSCIV4, as well as TRACV5 and MSCIV2, can be powered by the on board DC/DC
converter and in this case the Power Supply Module (PWRS) is not equipped. The
equipment and the strap configuration of these modules are described in the TRAU
Maintenance Manual.
3.2
Overview
The TRAU rack has to be connected to a 48 VDC Power Distribution Rack (PDR). For
reasons of reliability, two power suppliers at 48V start from PDR, each one provided with
an individual protection. The two couples of conductors at 48V, are directly connected
to the PP0 and PP1 terminals (max conductor cross-section is 10mm2) located on the
Rack Cabling Access Panel (see Fig. 3.1).
When connecting the power supply cables use different colors, like blue and black (or
brown) and take into account that:
-
PDR side:
Rack side:
A30808-X3247-L460-2-7631
65
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
3.3
66
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
3.4
IMN:TRAU
cover
power 0 power1
power line entry
Fig. 3.1
TRAU-Standard power IN
A30808-X3247-L460-2-7631
67
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
68
TRAU-HC power IN
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Fig. 4.1
A30808-X3247-L460-2-7631
69
IMN:TRAU
Fig. 4.2
70
Installation
Transcoding and Rate Adaption Unit
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
4.1
IMN:TRAU
Use only coaxial cable for 75ohm wiring, e.g. INTERCOND 13-RJC19A12R-C1
(12x0.4/1.9) and relative 1.0/2.3 coaxial connector, e.g. COMPEL 350.064.050 or
INTERCOND 11-RK23/4 (single coaxial) and relative 1.0/2.3 coaxial connector, e.g.
COMPEL 350.064.054.
Use onlybalanced cable 100/120ohm, e.g. INTERCOND 13-TDH26P12R-C1
12x2xAWG26 twisted shielded pairs (with drain wire) plus total braided shield and relative SUB-D 37 connector.
The Tab. 4.1 and Tab. 4.2 gives the corresponding of the PCM connection between the
TRAU subrack, the TRAU module and the connector of the RCAP rack.
TRAU Subrack
TRAU Module
RCAP Connector
LINK 3 (GW6)
LINK 4 (LW6)
Tab. 4.1
TRAU Subrack
TRAU Module
RCAP Connector
LINK 1 (AW6)
LINK 2 (DW3)
Tab. 4.2
A30808-X3247-L460-2-7631
71
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
The pinning of any PCM connector on the RCAP of the rack is shown in Tab. 4.3. The
wire color is referred to the rack internal cable and is corresponding to the table CEIUNEL 00724.
PIN
CONNECTOR #
WIRE
COLOR
1/20
PCM 0 Input
(from BSC)
BLUE/WHITE
2/21
PCM 0 Output
(to BSC)
ORANGE/WHITE
GROUND
4/22
PCM 1 Input
(from BSC)
GREEN/WHITE
5/23
PCM 1 Output
(to BSC)
BROWN/WHITE
6/24
PCM 0 Input
(from MSC)
GREY/WHITE
7/25
PCM 0 Output
(to MSC)
BLUE/RED
26
GROUND
8/27
PCM 1 Input
(from MSC)
ORANGE/RED
9/28
PCM 1 Output
(to MSC)
GREEN/RED
10
GROUND
11/29
PCM 2 Input
(from MSC)
BROWN/RED
12/30
PCM 2 Output
(to MSC)
GREY/RED
13/31
PCM 3 Input
(from MSC)
BLUE/BLACK
14/32
PCM 3 Output
(to MSC)
ORANGE/BLACK
33
GROUND
SHIELD
15/34
---------------
Not connected
16/35
---------------
Not connected
17
GROUND
SHIELD
18/36
---------------
Not connected
19/37
---------------
Not connected
Tab. 4.3
72
PCM
LINE
SHIELD
SHIELD
SHIELD
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
4.1.1
IMN:TRAU
To assembly the coaxial cable and relative connector, please refer to the assembling
procedures of the connector Supplier
The Asub/A interface should be connected by a coax Adapter C39117-A343-A48 (see
Fig. 4.3, Fig. 4.4, Tab. 4.4)
TX cables
to BSC side
TX cables
to MSC side
Not Used
1
0
RX cables
to BSC side
Fig. 4.3
A30808-X3247-L460-2-7631
RX cables
to MSC side
Not Used
73
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
RX cables
to BSC side
RX cables
to MSC side
Not used
Not Used
Fig. 4.4
TX cables
to MSC side
TX cables
to BSC side
Coax connector
Signal
Coax connector
PCM 0 Input
RX 0 (BSC side)
PCM 0 Input
RX 0 (MSC side)
PCM 0 Output
TX 0 (BSC side)
PCM 0 Output
TX 0 (MSC side)
PCM 1 Input
RX 1 (BSC side)
PCM 1 Input
RX 1 (MSC side)
PCM 1 Output
TX 1 (BSC side)
PCM 1 Output
TX 1 (MSC side)
PCM 2 Input
RX 2 (MSC side)
PCM 2 Output
TX 2 (MSC side)
PCM 3 Input
RX 3 (MSC side)
PCM 3 Output
TX 3 (MSC side)
Tab. 4.4
74
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
4.1.2
IMN:TRAU
The outer diameter of the PCM cable must not exceed 15mm (0.59)
The pinning of the PCM signal is reported in the Tab. 4.5
Pin connector
PCM line
1/20
2/21
GND
4/22
5/23
6/24
7/25
26
GND
8/27
9/28
10
GND
11/29
12/30
13/31
14/32
33
GND
15/34
Not connected
16/35
Not connected
17
GND
18/36
Not connected
19/37
Not connected
Tab. 4.5
A30808-X3247-L460-2-7631
75
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
Fig. 4.5
76
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
4.2
4.2.1
IMN:TRAU
TRAU Module
RCAP Connector
GW3
LW3
Tab. 4.6
TRAU Subrack
TRAU Mdule
RCAP Connector
AW3
DW3
Tab. 4.7
For Remote alarms cabling use a 13x2x0.4 (13x2xAWG24/26) twisted pairs plus total
braided shield and relative SUB-D 25 Male connector.
i
i
The outer diameter of the Remote Alarms cable must not exceed 12mm (0.47)
The maximum lenght between the remote alarms connector and the output device
should be calculated taking into account that the nominal loading of each relay contact
is 0,3A/48VDC.
The alarm signals are associated to as many relay contacts to send the following alarm
conditions:
BSC link alarm
Spare alarm
Spare alarm
OR of BS-MS-INT
Global alarm: Major
Global alarm: Minor
Global alarm: Critical
OR of MJ-MN-CR
A30808-X3247-L460-2-7631
(BS)
(MS)
(INT)
(OR2)
(MJ)
(MN)
(CR)
(OR1)
77
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
Tab. 4.8 shows the layout of the pins of the connector AW3/DW3/GW3/LW3, situated
on the RCAP.The wire color is referred to the internal cable and is corresponding to the
table CEI-UNEL 00724.
Alarm Type
BSC LINK ALARM
SPARE ALARM
SPARE ALARM
OR OF BS-MSINT ALARMS
Signal Name
Pin Number
Wire Color
BS-BK
01
WHT
BS-CM
02
BLU
BS-MK
03
WHT
MS-BK
04
ORN
MS-CM
05
WHT
MS-MK
06
GRN
INT-BK
07
WHT
INT-CM
08
BRN
INT-MK
09
WHT
OR2-BK
10
GRY
OR2-CM
11
RED
OR2-MK
12
BLU
13
GLOBAL ALARM:
MAJOR
GLOBAL ALARM:
MINOR
GLOBAL ALARM:
CRITICAL
OR OF MJ_MN_CR
ALARMS
Tab. 4.8
78
MJ-BK
14
RED
MJ-CM
15
ORN
MJ-MK
16
RED
MN-BK
17
GRN
MN-CM
18
RED
MN-MK
19
BRN
CR-BK
20
RED
CR-CM
21
GRY
CR-MK
22
BLK
OR1-BK
23
BLU
OR1-CM
24
BLK
OR1-MK
25
ORN
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
In general, the condition of each type of alarm is notified through a relay contact in the
following way:
no alarm:
contact RELAY-COMMON/RELAY-BREAK
contact RELAY-COMMON/RELAY-MAKE
closed
open
alarm state:
contact RELAY-COMMON/RELAY-BREAK
contact RELAY-COMMON/RELAY-MAKE
open
closed
Where RELAY-COMMON indicates the common point of the contact (CM), RELAYBREAK indicates the break point (no alarm) of the contact (BK), and RELAY-MAKE indicates the make point (alarm) of the contact (MK).
Preparation of the Remote Alarm cable TRAU rack side
Cut the cable to the required lenght.
Remove external jacket about 70 mm (2.7)
Cut the outer shield leaving about 10mm (0.4) to permit its contact with the
campling of the cap.
Connect the pairs as per Tab. 4.9 (the wire color is referred to the internal cable and
is corresponding to the table CEI-UNEL 00724) using a SUB-D25 Male (e.g.
CANNON ZDB25PA191).
Close the connector with a shielded cap with screws M3 (e.g. FCT FMK3GK201+2FRS1Y5-K190-M3). Be careful: the outer shield of the cable must be in
contact with the cable clamping of the said cap.
Pair Color
Signal
Connector Pin
WHT/BLU
BSBK/MJBK
1/14
WHT/ORG
BSCM/MJCM
2/15
WHT/GRN
BSMK/MJMK
3/16
WHT/BRN
MSBK/MNBK
4/17
WHT/GRY
MSCM/MNCM
5/18
RED/BLU
MSMK/MNMK
6/19
WHT/GRY
INTBK/CRBK
7/20
RED/GRN
INTCM/CRCM
8/21
RED/BRN
INTMK/CRMK
9/22
RED/GRY
OR2BK/OR1BK
10/23
BLK/BLU
OR2CM/OR1CM
11/24
BLK/ORG
OR2MK/OR1MK
12/25
BLK/GRN
----------------
Not connected
Tab. 4.9
A30808-X3247-L460-2-7631
79
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
Fig. 4.6
80
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
4.2.2
IMN:TRAU
signal name
description
BSB
MSB
not used
INTB
4-9
CM2,CM1
- 48 V
not used
MJB
major alarm
CRB
critical alarm
MNB
minor alarm
10 - 11 GND
Tab. 4.10
ground
In the last lower subrack on the connector W14 takes place the Open door sensor cable.
The two wires of the sensor are connected to pin number 3 and to ground (by the cableclamp of the shielded cap).
During an upgrade of a subrack needs to:
disconnect the cable connected to connector W14 on the last subrack equipped.
mount the new subrack.
reconnect the cable disconneted from connector W14 on the new subrack.
connect the cable V7440-A32-R32 (item of the new subrack) between the connector
W15 of the new subrack and the connector W14 of the last equipped subrack.
For references see Fig. 5.4 and Fig. 5.5 of the Chap. 5.
A30808-X3247-L460-2-7631
81
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
4.3
Use only coaxial cable for 75ohm wiring, e.g. INTERCOND 13-RJC19A12R-C1
(12x0.4/1.9) and relative 1.0/2.3 coaxial connector, e.g. COMPEL 350.064.050 or
INTERCOND 11-RK23/4 (single coaxial) and relative 1.0/2.3 coaxial connector, e.g.
COMPEL 350.064.054.
Use onlybalanced cable 100/120ohm, e.g. INTERCOND 13-TDH26P12R-C1
(12x2x0.4) 12x2xAWG26 twisted shielded pairs (with drain wire) plus total braided
shield and relative SUB-D 37 connector.
The Tab. 4.11 and Tab. 4.12 gives the corresponding of the PCM connection between
the TRAU frame, the TRAU module and the connector of the RCAP rack.
TRAU Frame
TRAU Module
LINK 0 (PCM 0)
LINK 2 (PCM 2)
LINK 4 (PCM 4)
LINK 6 (PCM 6)
Tab. 4.11
TRAU Frame
TRAU Module
RCAP Connector
LINK 1 (PCM 1)
LINK 3 (PCM 3)
LINK 5 (PVM 5)
LINK 7 (PCM 7)
Tab. 4.12
82
RCAP Connector
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
The pinning of any PCM connector on the RCAP of the rack is shown in Tab. 4.3.
PIN
CONNECTOR #
PCM
LINE
1/20
PCM 0 Input
(from BSC)
2/21
PCM 0 Output
(to BSC)
GROUND
4/22
PCM 1 Input
(from BSC)
5/23
PCM 1 Output
(to BSC)
6/24
PCM 0 Input
(from MSC)
7/25
PCM 0 Output
(to MSC)
26
GROUND
8/27
PCM 1 Input
(from MSC)
9/28
PCM 1 Output
(to MSC)
10
GROUND
11/29
PCM 2 Input
(from MSC)
12/30
PCM 2 Output
(to MSC)
13/31
PCM 3 Input
(from MSC)
14/32
PCM 3 Output
(to MSC)
33
GROUND
15/34
---------------
16/35
---------------
17
GROUND
18/36
---------------
19/37
---------------
Tab. 4.13
A30808-X3247-L460-2-7631
83
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
4.3.1
To assembly the coaxial cable and relative connector, please refer to the assembling
procedures of the connector Supplier
The Asub/A interface should be connected by a coax Adapter S30861-Q472-X (see
Fig. 4.7, Tab. 4.14)
TX cables
to BSC side
TX cables
to MSC side
1
0
RX cables
to BSC side
Fig. 4.7
RX cables
to MSC side
84
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Signal
Coax connector
Signal
Coax connector
PCM 0 Input
RX 0 (BSC side)
PCM 0 Input
RX 0 (MSC side)
PCM 0 Output
TX 0 (BSC side)
PCM 0 Output
TX 0 (MSC side)
PCM 1 Input
RX 1 (BSC side)
PCM 1 Input
RX 1 (MSC side)
PCM 1 Output
TX 1 (BSC side)
PCM 1 Output
TX 1 (MSC side)
PCM 2 Input
RX 2 (MSC side)
PCM 2 Output
TX 2 (MSC side)
PCM 3 Input
RX 3 (MSC side)
PCM 3 Output
TX 3 (MSC side)
Tab. 4.14
A30808-X3247-L460-2-7631
85
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
4.3.2
The outer diameter of the PCM cable must not exceed 15mm (0.59)
The pinning of the PCM signal is reported in the Tab. 4.15
Pin connector
1/20
2/21
GND
4/22
5/23
6/24
7/25
26
GND
8/27
9/28
10
GND
11/29
12/30
13/31
14/32
33
GND
15/34
Not connected
16/35
Not connected
17
GND
18/36
Not connected
19/37
Not connected
Tab. 4.15
86
PCM line
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
A30808-X3247-L460-2-7631
87
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
4.4
4.4.1
TRAU Module
RCAP Connector
AW0
AW2
AW4
AW6
Tab. 4.16
TRAU Frame
TRAU Module
RCAP Connector
AW1
AW3
AW5
AW7
Tab. 4.17
For Remote alarms cabling use a 2x13x0.4 (2x13xAWG24/26) twisted pairs plus total
braided shield and relative SUB-D 25 Male connector.
i
i
The outer diameter of the PCM cable must not exceed 12mm (0.47)
The maximum lenght between the remote alarms connector and the output device
should be calculated taking into account that the nominal loading of each relay contact
is 0,3A/48VDC.
The alarm signals are associated to as many relay contacts to send the following alarm
conditions:
BSC link alarm
Spare alarm
Spare alarm
OR of BS-MS-INT
Global alarm: Major
Global alarm: Minor
Global alarm: Critical
OR of MJ-MN-CR
88
(BS)
(MS)
(INT)
(OR2)
(MJ)
(MN)
(CR)
(OR1)
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Tab. 4.18 shows the layout of the pins of the connector AW0-AW7, situated on the
RCAP.
Alarm Type
BSC LINK ALARM
SPARE ALARM
SPARE ALARM
OR OF BS-MSINT ALARMS
Signal Name
Pin Number
BS-BK
01
BS-CM
02
BS-MK
03
MS-BK
04
MS-CM
05
MS-MK
06
INT-BK
07
INT-CM
08
INT-MK
09
OR2-BK
10
OR2-CM
11
OR2-MK
12
13
GLOBAL ALARM:
MAJOR
GLOBAL ALARM:
MINOR
GLOBAL ALARM:
CRITICAL
OR OF MJ_MN_CR
ALARMS
Tab. 4.18
A30808-X3247-L460-2-7631
MJ-BK
14
MJ-CM
15
MJ-MK
16
MN-BK
17
MN-CM
18
MN-MK
19
CR-BK
20
CR-CM
21
CR-MK
22
OR1-BK
23
OR1-CM
24
OR1-MK
25
89
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
In general, the condition of each type of alarm is notified through a relay contact in the
following way:
no alarm:
contact RELAY-COMMON/RELAY-BREAK
contact RELAY-COMMON/RELAY-MAKE
closed
open
alarm state:
contact RELAY-COMMON/RELAY-BREAK
contact RELAY-COMMON/RELAY-MAKE
open
closed
Where RELAY-COMMON indicates the common point of the contact (CM), RELAYBREAK indicates the break point (no alarm) of the contact (BK), and RELAY-MAKE indicates the make point (alarm) of the contact (MK).
Preparation of the Remote Alarm cable TRAU rack side
Cut the cable to the required lenght.
Remove external jacket about 70 mm (2.7)
Cut the outer shield leaving about 10mm (0.4) to permit its contact with the
campling of the cap.
Connect the pairs as per Tab. 4.19 (the wire color is referred to the internal cable
and is corresponding to the table CEI-UNEL 00724) using a SUB-D25 Male (e.g.
CANNON ZDB25PA191).
Close the connector with a shielded cap with screws M3 (e.g. FCT FMK3GK201+2FRS1Y5-K190-M3). Be careful: the outer shield of the cable must be in
contact with the cable clamping of the said cap.
Pair Color
Connector Pin
WHT/BLU
BSBK/MJBK
1/14
WHT/ORG
BSCM/MJCM
2/15
WHT/GRN
BSMK/MJMK
3/16
WHT/BRN
MSBK/MNBK
4/17
WHT/GRY
MSCM/MNCM
5/18
RED/BLU
MSMK/MNMK
6/19
WHT/GRY
INTBK/CRBK
7/20
RED/GRN
INTCM/CRCM
8/21
RED/BRN
INTMK/CRMK
9/22
RED/GRY
OR2BK/OR1BK
10/23
BLK/BLU
OR2CM/OR1CM
11/24
BLK/ORG
OR2MK/OR1MK
12/25
BLK/GRN
----------------
Not connected
Tab. 4.19
90
Signal
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
A30808-X3247-L460-2-7631
91
IMN:TRAU
92
Installation
Transcoding and Rate Adaption Unit
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
5.1
Connector position
Type
Function
PP0 PP1
TERMINALS
AW3
SUB D 25 Female
DW3
SUB D 25 Female
GW3
SUB D 25 Female
LW3
SUB D 25 Female
PM2
SUB D 9 Female
AW6
SUB D 37 Female
DW6
SUB D 37 Female
GW6
SUB D 37 Female
LW6
SUB D 37 Female
Tab. 5.1
A30808-X3247-L460-2-7631
93
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
The Fig. 5.1 shows the position of the connectors on the RCAP of the rack
Fig. 5.1
94
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
The Fig. 5.2 shows a side view of the rack with the subrack power supply connection
(bus-bar) and the connection of the cables on the RCAP
A30808-X3247-L460-2-7631
95
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
The Fig. 5.3 shows a front view of the rack with the subrack power supply connection
(bus-bar and filter) and ground connection.
Fig. 5.3
96
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
The Fig. 5.4 shows the list of the cabling of the TRAU rack.
Fig. 5.4
Interconnections list
A30808-X3247-L460-2-7631
97
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
48VA
Rem-Alm
to TOP(AW3)
to Fuse Panel
(J1)
(J2)
to top(AW6)
PCM lines
48VB
from PM3
temp.
sensors
Fig. 5.5
98
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Fig. 5.6
Mounting
Reference
From
File
Connector
To
File
Connector
55
W5
Fuse Pan. J1
56
W4
Fuse Pan. J2
58
W1
Fuse Pan. J4
58
W16
Fuse Pan. J5
60
GNDF
Tab. 5.2
A30808-X3247-L460-2-7631
99
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
5.2
TRAU-HC rack
This chapter reports an overview of the internal cabling of the TRAU rack.
The chapter is developped in the following four blocks:
1.
2.
3.
4.
5.2.1
Fig. 5.7
100
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
Fig. 5.8
IMN:TRAU
A30808-X3247-L460-2-7631
101
IMN:TRAU
Fig. 5.9
102
Installation
Transcoding and Rate Adaption Unit
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
LIST OF THE CONNECTORS AND CABLES OF THE ADAPTER BOARD (refer Fig. 5.9).
X25 connector
The X25 connector is used to send board alarms and to power Lamp Panel at the top of the rack
(PM2 connector).
Connector code is D Subminiature right-angle solder termination 9p.
pin
Signal
Description
N.C.
N.C.
N.C
VAB
+ 48 V
-VAB
- 48 V
MJ
Major alarm
MN
Minor alarm
-VAB
Tab. 5.3
not connected
- 48 V
A30808-X3247-L460-2-7631
103
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
X23-X24 Connectors
The faston X23-X24 are used to receive open door alarm that is a contact from a sensor.
The type is a faston pressfit.
pin
Signal
Description
X23
OPEND
Open door
X24
GND
ground
Tab. 5.4
104
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
X27 connector
The X27 connector is used to receive fan alarm from FAN unit.
The type is D Subminiature pressfit termination 15p.
pin
Signal
N.C.
N.C.
N.C
GND
TRAU_FANAL
N.C.
N.C.
N.C.
N.C.
10
N.C.
11
GND
12
N.C.
13
N.C.
14
N.C.
15
N.C.
Tab. 5.5
Description
Fan alarm
A30808-X3247-L460-2-7631
105
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
X26 connector
The X26 connector is used for DAISY CHAIN that connects the sub-racks with the
following signals:
TRAU alarms (MJ,MN,MCR,EXT) that are in logical OR between the sub-racks.
POWER OFF A and B alarms.
OPEND alarm.
FAN alarm,.
The type is 20pin, 2x10 pressfit termination.
Daisy chain is constituited with a crimped flat cable.
pin
Description
PWOFFA
PWOFFB
Thermal alarm B
- VAB
- 48 V
OPEND
MN
Minor alarm
GND
N.C.
10
FAN
11
N.C.
12
MN
13
N.C.
14
MJ
15
N.C.
16
MCR
17
N.C.
18
EXT
19
N.C.
20
GND
Tab. 5.6
106
Signal
Thermal alarm A
Fan alarm
Minor alarm
Major alarm
Critical alarm
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
(169)
A30808-X3247-L460-2-7631
107
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
X5-X6 connector
The faston X5-X6 are used to feed Fan unit.
The type is a faston pressfit.
pin5
Signal
Description
X5
+ VAB
+ 48 V
X6
- VAB
- 48 V
Tab. 5.7
Signal
Description
48A
+ 48 V battery A
- 48A
- 48 V battery A
48B
+ 48 V battery B
- 48B
- 48 V battery B
Tab. 5.8
DC-MAIN CABLES
108
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
X7 to X22 connector
The faston X7 to X22 are used to feed TRAU frames.
The type is a faston pressfit.
Ref.
frame
Signal
X7
+ 48 A
X8
- 48 A
X9
+ 48 B
X10
- 48 B
X11
+ 48 A
X12
- 48 A
X13
+ 48 B
X14
- 48 B
X15
+ 48 A
X16
- 48 A
X17
+ 48 B
X18
- 48 B
X19
+ 48 A
X20
- 48 A
X21
+ 48 B
X22
- 48 B
Tab. 5.9
A30808-X3247-L460-2-7631
109
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
5.2.2
Fig. 5.10
110
daisy chain
daisy chain
-48A
to/from backpanel
to backpanel
to top rack
-48A -48B
DC PANEL 0
-48B
daisy chain
ADAPTER-BOARD
daisy chain
daisy chain
The Front Panel Board (S50201-Q54-X) is positioned in the DC-Panel in a TRAU subrack that includes two TRAU unit and provides the following functions:
to display the TRAU alarms (4 leds for each TRAU)
to connect the TRAU via LMT connector
to exchange alarms to other units via DAISY CHAIN
to remote the alarms on the top rack connectors (AW)
to switch off the 48 V power supply in the frame by two 4A magnetothermic breakers.
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Signal
BSBK_L/R
BSCM_L/R
BSMK_L/R
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
10
OR2BK_L/R
11
OR2CM_L/R
12
OR2MK_L/R
13
N.C.
14
MJBK_L/R
15
MJCM_L/R
16
MJMK_L/R
17
MNBK-L/R
18
MNCM_L/R
19
MNMK_L/R
20
CRBK_L/R
21
CRCM_L/R
22
CRMK_L/R
23
OR1BK_L/R
24
OR1CM_L/R
25
OR1MK_L/R
Tab. 5.10
A30808-X3247-L460-2-7631
Description
BSC link alarm
OR alarm pin 1 to 9
OR alarm pin 14 to 22
X13,X14 connectors
111
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
Fig. 5.11
112
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
X15-X16 connectors
The LMT connectors X15-X16 are used to have a serial interface of both the TRAU_L/R.
The type is D Subminiature straight pressfit termination 15p.
Refer to V11 interface for the signals description.
pin
Signal
pin
Signal
T(B)
T(A)
10
C(B)
C(A)
11
R(B)
R(A)
12
I(B)
I(A)
13
S(B)
S(A)
14
B(B)
B(A)
15
N.C.
Tab. 5.11
X18 connector
The X18 connector is the DA-CH (DAISY CHAIN) connector.
The pin description is the same as in the Adapter Board (see Tab. 5.6)
A30808-X3247-L460-2-7631
113
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
X17 connector
The X17 connector is the LMT+ALM_L/R used for the following signals:
Two LMT serial interfaces for the Trau Left and Right side.
Alarm from Backplane : major,minor,critical,external.
Alarms to Backplane : power-off,open-door,fan.
Power signal from Backplane : +5VA and +5VB.
The type is 64pin, 2x32 pressfit termination.
Description
pin
pin
GND
GND
T(A)
T(B)
C(A)
C(B)
R(A)
R(B)
I(A)
10
I(B)
S(A)
11
12
S(B)
B(A)
13
14
B(B)
15
16
GND
17
18
GND
PWOFF
A0
19
20
PWOFF
B1
N.C.
21
22
N.C.
OPEND0 23
_L
24
FANAL0
_R
25
26
FANAL1
_R
N.C.
27
28
N.C.
MN_R
29
30
N.C.
MJ_R
31
32
MCR_R
GND
33
34
GND
5VA TRAU_Left
+5VA_L
35
36
+5VB_L
5VB TRAU_Left
MJ_L
37
38
EXT_L
MN_L
39
40
EXT_R
MCR_L
41
42
GND
+5VA_R
43
44
+5VB_R
GND
45
46
N.C.
T(A)
47
48
T(B)
C(A)
49
50
C(B)
5VA TRAU_Right
Tab. 5.12
114
Signal
Signal
Description
5VB TRAU_Right
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Description
Tab. 5.12
Signal
pin
pin
Signal
R(A)
51
52
R(B)
I(A)
53
54
I(B)
S(A)
55
56
S(B)
B(A)
57
58
B(B)
59
60
N.C.
61
62
N.C.
GND
63
64
GND
Description
LMT+ALM CABLE
Signal
X5
- 48A_UP
X6
+ 48A_UP
X11
- 48B_UP
X12
+ 48B_UP
X10
- 48B_UP
X4
- 48A_UP
X7
- 48B
X1
- 48A
X8
- 48B
X9
+ 48B
X2
- 48A
X3
+ 48A
X20
GND
Tab. 5.13
A30808-X3247-L460-2-7631
Description
main power A from Adapter board
to breakers
from breakers
PWR-B to Backplane
PWR-A to Backplane
115
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
DC-CABLES TO BACKPLANE
DC-CABLES TO BREAKERS
GROUND CABLES
116
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
X19 connector
The X19 connector fits the new version TRAUV2 sub-rack (S30861-B248-X) on the
TRAU-Standard rack (S30861-C21-X).
For the pin description see the X7 connector in the Extra Adapter Board (Chap. 5.3).
A30808-X3247-L460-2-7631
117
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
5.2.3
Fig. 5.12
118
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
pin
signal
stream
1-20
PCM 0 input
from BSC
2-21
PCM 0 output
to BSC
GND
4-22
PCM 1 input
from BSC
5-23
PCM 1 output
to BSC
6-24
PCM 0 input
from MSC
7-25
PCM 0 output
to MSC
26
GND
8-27
PCM 1 input
from MSC
9-28
PCM 1 output
to MSC
10
GND
11-29
PCM 2input
from MSC
12-30
PCM 2 output
to MSC
13-31
PCM 3 input
from MSC
14-32
PCM 3 output
to MSC
33
GND
15-34
N.C.
16-35
N.C.
17
GND
18-36
N.C.
19-37
N.C.
Tab. 5.14
A30808-X3247-L460-2-7631
119
IMN:TRAU
Fig. 5.13
120
Installation
Transcoding and Rate Adaption Unit
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
5.2.4
IMN:TRAU
Fig. 5.14
A30808-X3247-L460-2-7631
121
IMN:TRAU
Fig. 5.15
122
Installation
Transcoding and Rate Adaption Unit
Rack wiring 1
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
Fig. 5.16
IMN:TRAU
Rack wiring 2
A30808-X3247-L460-2-7631
123
Fig. 5.17
124
FRAME 3
FRAME 2
FRAME 1
Installation
Transcoding and Rate Adaption Unit
FRAME 0
IMN:TRAU
Rack wiring 3
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
14/0
TRAU FRAME 0
IMN:TRAU
14/0
4/0A
4/0B
12/0
12/0
18
14/1
TRAU FRAME 1
14/1
4/1A
4/1B
12/1
12/1
18
14/2
14/2
TRAU FRAME 2
4/2A
4/2B
12/2
12/2
18
14/3
14/3
TRAU FRAME 3
4/3A
4/3B
12/3
12/3
18
Fig. 5.18
Rack wiring 4
A30808-X3247-L460-2-7631
125
IMN:TRAU
126
GROUND CABLE
POWER CABLES
SIGNAL CABLE
Fig. 5.19
Installation
Transcoding and Rate Adaption Unit
A30808-X3247-L460-2-7631
Frame wiring 1
Fig. 5.21
Frame wiring 2
PCM CABLES
Fig. 5.20
A30808-X3247-L460-2-7631
POWER CABLES
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
127
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
5.3
5.3.1
N.C.
4,5,6,7,8,9
N.C.
Tab. 5.15
128
signal
description
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
X5-X6 connectors
The X5-X6 are used to receive and to distribuite the Daisy-Chain alarms and feed the
power to the top board (RCAP).
The type is D subminiature pressfit termination 9 p.
pin
signal
description
N.C
GND
OPEND
Open-door alarm
+ VAB
+ 48 V
5-9
- VAB
- 48 V
MJ
Major alarm
MN
Minor alarm
MCR
Critical alarm
Tab. 5.16
X1-X2 connectors
The X1-X2 are used to receive Power supply (X1 from A and X2 from B source).
The type is power D subminiature pressfit termination 3 p.
pin
signal
- VA/B
GND
+ VA/B
Tab. 5.17
A30808-X3247-L460-2-7631
description
- 48 V
+ 48 V
129
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
X7 connectors
The X7 is used to interface Extra Adapter board to the Frame via front Panel board. .
The type is SMT solder terrmination 36 p.
description
pin
pin
signal
description
+48 VA
+ VA
+ VA
+48 VA
+48 VA
+ VA
+ VA
+48 VA
- 48 VA
- VA
- VA
- 48 VA
- 48 VA
- VA
- VA
- 48 VA
+ 48 VB
+ VB
10
+ VB
+ 48 VB
+ 48 VB
+ VB
11
12
+ VB
+ 48 VB
- 48 VB
- VB
13
14
- VB
- 48 VB
- 48 VB
- VB
15
16
- VB
- 48 VB
GND
17
18
GND
FAN
19
20
GND
21
22
OPEND
23
24
GND
25
26
MCR
Critical alarm
Major alarm
MJ
27
28
MN
Minor Alarm
N.C.
29
30
N.C.
N.C.
31
32
N.C.
N.C.
33
34
N.C.
N.C.
35
36
N.C.
Fan alarm
Open-door alarm
Tab. 5.18
130
signal
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
The Extra Adapter Board is designed using pressfit connector apart from X7 (Fig. 5.22)
that is a SMT solder termination 36 p. This connector needs to connect this board to
Front Panel Board (on this board there is the same connector) via a pin strip (V50500C1-A8). Before inserting the finger of the X7 connector in the Front Panel Board
connector (DA-CH), tighten the four screws on the Extra Adapter Board to fasten it on
the Front Panel Board.
X3
X4
X5
X1
X6
X2
X7
Fig. 5.22
A30808-X3247-L460-2-7631
131
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
AW6
DW6
AW3
S50201-X8-A20
new cables
DW3
new cable for expansion subrack
PM2
PM3
GW6
LW6
GW3
LW3
Fig. 5.23
132
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
Fig. 5.24
IMN:TRAU
A30808-X3247-L460-2-7631
133
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
5.3.2
add one
TRAU
add one
TRAU
0 1
add one
TRAU
2 3
TRAU-Standard rack
with only one TRAU equipped
0
replace with TRAU-HC
0
add one
TRAU
0
2
add one
TRAU
1
3
0
1
add one
TRAU
TRAU-Standard rack
with two TRAUs equipped
1
2
add one
TRAU
1
2 3
0
1
0
1
2
134
add one
TRAU
1
2 3
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
Fig. 5.25
IMN:TRAU
0
1
add one
TRAU
1
2
2
3
replace shelf number zero
TRAU-Standard rack
with three TRAUs equipped
add one
TRAU
replace shelf
1
number one
1
2
0
1
add one
TRAU
Fig. 5.26
1
2 3
A30808-X3247-L460-2-7631
135
IMN:TRAU
136
Installation
Transcoding and Rate Adaption Unit
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Fig. 6.1
A30808-X3247-L460-2-7631
137
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
Function Designation
S50201-X8-A9
S50201-X8-A3
Power cable
Cable
Number
Connected To
14/0
14/0
14/1
14/1
14/2
14/2
14/3
14/3
12/0
12/0
12/1
12/1
12/2
12/2
12/3
12/3
4/0A
4/0B
4/1A
4/1B
4/2A
4/2B
4/3A
4/3B
-----
Tab. 6.1
138
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Fig. 6.2
DC PANEL (S30861-D26-X)
Fig. 6.3
DC PANEL rear
A30808-X3247-L460-2-7631
139
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
Fig. 6.4
Code Number
Function Designation
From
To
S50201-X8-A6
Ground cable
DC Panel/GND
S50201-X8-A16
Power cable
DC Panel/PWRA (OUT)
S50201-X8-A16
Power cable
DC Panel/PWRB (OUT)
S50201-X8-A17
Signal cable
DC Panel/LMT+ALARM
Tab. 6.2
140
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Upgrade procedure
1 - Mount the frame mechanics
4xScrews
Frame-Mechanics
Fig. 6.5
Fig. 6.6
Ground cable
A30808-X3247-L460-2-7631
141
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
Fig. 6.7
Fig. 6.8
142
Power cables
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
4xScrews
DC-Panel
Fig. 6.9
DC Panel mounting
Make sure that the two breakers of the DC panel are off.
Fig. 6.10
Ground cable
A30808-X3247-L460-2-7631
143
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
Fig. 6.11
Power cables
Fig. 6.12
144
Power cables
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Fig. 6.13
10 - Connect Signa cable (DC Panel side) and Daisy chain cable
Fig. 6.14
A30808-X3247-L460-2-7631
145
IMN:TRAU
Installation
Transcoding and Rate Adaption Unit
Fig. 6.15
146
DC Panel
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Basement layout
300 (11.8)
160 (6.3)
80 (3.15)45 (1.77)
300 (11.8)
599 (23.6)
300 mm (11.8)
300 mm (11.8)
145 (5.7)
80 (3.15) 45 (1.77)
Basement layout
57 (2.2)
Fig. 7.1
599 (23.6)
Fig. 7.2
A30808-X3247-L460-2-7631
147
IMN:TRAU
148
Installation
Transcoding and Rate Adaption Unit
A30808-X3247-L460-2-7631
Installation
Transcoding and Rate Adaption Unit
IMN:TRAU
Abbreviations
Abis
Asub
BSC
BSS
BTS
CSU
DC
Direct Current
ETSI
GND
Ground
HF-DF
LMT
MDF
MSC
PCM
TFAP
TRAC
TRX
Transceiver
A30808-X3247-L460-2-7631
,,,,,
149
IMN:TRAU
150
Installation
Transcoding and Rate Adaption Unit
A30808-X3247-L460-2-7631