Você está na página 1de 150

Installation

Transcoding and Rate Adaption Unit


IMN:TRAU
A30808-X3247-L460-2-7631

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

Important Notice on Product Safety


DANGER - RISK OF ELECTRICAL SHOCK OR DEATH - FOLLOW ALL INSTALLATION
INSTRUCTIONS.
The system complies with the standard EN 60950 / IEC 60950. All equipment connected to the
system must comply with the applicable safety standards.
Hazardous voltages are present at the AC power supply lines in this electrical equipment. Some
components may also have high operating temperatures.
Failure to observe and follow all installation and safety instructions can result in serious
personal injury or property damage.
Therefore, only trained and qualified personnel may install and maintain the system.

The same text in German:


Wichtiger Hinweis zur Produktsicherheit
LEBENSGEFAHR - BEACHTEN SIE ALLE INSTALLATIONSHINWEISE.
Das System entspricht den Anforderungen der EN 60950 / IEC 60950. Alle an das System angeschlossenen Gerte mssen die zutreffenden Sicherheitsbestimmungen erfllen.
In diesen Anlagen stehen die Netzversorgungsleitungen unter gefhrlicher Spannung. Einige
Komponenten knnen auch eine hohe Betriebstemperatur aufweisen.
Nichtbeachtung der Installations- und Sicherheitshinweise kann zu schweren Krperverletzungen oder Sachschden fhren.
Deshalb darf nur geschultes und qualifiziertes Personal das System installieren und warten.

Caution:
This equipment has been tested and found to comply with EN 301489. Its class of conformity is
defined in table A30808-X3247-X910-*-7618, which is shipped with each product. This class also
corresponds to the limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the relevant standards referenced in the manual Guide to Documentation, may
cause harmful interference to radio communications.
For system installations it is strictly required to choose all installation sites according to national and
local requirements concerning construction rules and static load capacities of buildings and roofs.
For all sites, in particular in residential areas it is mandatory to observe all respectively applicable
electromagnetic field / force (EMF) limits. Otherwise harmful personal interference is possible.

Trademarks:
All designations used in this document can be trademarks, the use of which by third parties for their own purposes
could violate the rights of their owners.

Copyright (C) Siemens AG 2003.


Issued by the Information and Communication Mobile Group
Hofmannstrae 51
D-81359 Mnchen
Technical modifications possible.
Technical specifications and features are binding only insofar as
they are specifically and expressly agreed upon in a written contract.

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Reason for Update


Summary:
Second Edition for Release BR 7.0
Details:
Chapter / Section

Reason for Update

1.4.2

New numbering of the TRAU-HC modules in the


TRAU-HC rack

5.3

Expansion and Replacement Procedures of TRAUHC frame into the TRAU-Standard rack

Issue History
Issue

Date of issue

Reason for Update

07/2003

First Edition for New Release BR 7.0

12/2003

Second Edition for Release BR 7.0

A30808-X3247-L460-2-7631

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

This document consists of a total of 150 pages. All pages are issue 2.

Contents
1
1.1
1.2
1.3
1.4
1.4.1
1.4.2
1.5
1.6

General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Purpose of the Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Position in the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Site Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Station Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TRAU Standard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TRAU-HC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable Length between Network Elements . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2
2.1
2.2
2.3
2.4
2.4.1
2.4.2
2.5
2.5.1
2.5.2

2.5.3
2.6
2.6.1
2.6.2

Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Installation Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Equipment Delivery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Equipment Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Rack Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Devices and Boards Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Installation of the TRAU-Standard Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Grounding connections of the TRAU Standard Rack (S30861-C21-X) . . . 33
Grounding collector and fire protection kit for the TRAU-Standard rack
(MK:FGV* - S30861-K106-X) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Fan units (FG Kit - S50201-U32-X) and rack door (FG kit - C50324-A201-B12)
for fire resistance cabinet.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Earthquake Kit for the TRAU-Standard Rack. . . . . . . . . . . . . . . . . . . . . . . 41
Installation of the TRAU-HC Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Earthquake Kit for TRAU-HC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Grounding connections for the TRAU-HC Rack . . . . . . . . . . . . . . . . . . . . . 64

3
3.1
3.2
3.3
3.4

TRAU Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TRAU Rack Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Primary Power Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

65
65
65
66
67

4
4.1
4.1.1
4.1.2
4.2
4.2.1
4.2.2
4.3
4.3.1
4.3.2
4.4

PCM and ALARM connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


Asub/A interface connection of the TRAU Standard rack . . . . . . . . . . . . . .
Coaxial cable connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Balanced cable connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarms connection of the TRAU Standard rack . . . . . . . . . . . . . . . . . . . . .
Remote Alarms connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Internal Alarms connection (W14, W15 connectors). . . . . . . . . . . . . . . . . .
Asub/A interface connection of the TRAU-HC rack . . . . . . . . . . . . . . . . . .
Coaxial cable connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Balanced cable connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarms connection of the TRAU-HC rack . . . . . . . . . . . . . . . . . . . . . . . . . .

69
71
73
75
77
77
81
82
84
86
88

2.5.2.1

A30808-X3247-L460-2-7631

13
13
13
14
14
14
18
21
22

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

4.4.1

Remote Alarms connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

5
5.1
5.2
5.2.1
5.2.2
5.2.3
5.2.4
5.3
5.3.1
5.3.2

System Cabling of the TRAU rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93


TRAU Standard rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
TRAU-HC rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Adapter Board cabling (M:ADAPTBTV1) . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Front-Panel Board cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Internal PCM lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Photographs of the wiring assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
TRAU HC Frame to mount in a TRAU Standard rack . . . . . . . . . . . . . . . . 128
Extra Adapter Board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Replacement and expansion procedure . . . . . . . . . . . . . . . . . . . . . . . . . . 134

Upgrade Procedure of a TRAU frame in a TRAU HC rack . . . . . . . . . . . . 137

Swap from TRAU Standard rack to TRAU HC rack . . . . . . . . . . . . . . . . . . 147

Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Illustrations
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.

A30808-X3247-L460-2-7631

1.1
1.2
1.3
1.4
1.5
1.6
1.7
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10
2.11
2.12
2.13
2.14
2.15
2.16
2.17
2.18
2.19
2.20
2.21
2.22
2.23
2.24
2.25
2.26
2.27
2.28
2.29
2.30
2.31
2.32
2.33
2.34
2.35
2.36

Position of the TRAU in the SBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


Front view of the TRAU Standard rack . . . . . . . . . . . . . . . . . . . . . . . . .
Front view of the TRAU Standard rack in fire resistance cabinet . . . . .
TRAU HC fully equipped . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TRAU-HC frame with two TRAU modules and DC Panel.. . . . . . . . . . .
Interfaces between network elements . . . . . . . . . . . . . . . . . . . . . . . . . .
Maximum attenuations between equipment and HF-DF rack . . . . . . . .
Installation tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TRAU rack unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unpacking of TRAU devices and boards . . . . . . . . . . . . . . . . . . . . . . . .
TRAU rack installation accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TRAU rack details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rack fixing on concrete floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rack fixing on raised floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Grounding kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ground plate assy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Grounding cables kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power cables connection for fans kit . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fan units mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flame-guard door mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Earthquake Kit : floor holes for the TRAU-Standard. . . . . . . . . . . . . . . .
Earthquake kit: front view. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Earthquake kit parts list.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Earthquake kit anchoring screws detail . . . . . . . . . . . . . . . . . . . . . . . . .
Earthquake kit: Internal Plate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TRAU rack details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Minimum space necessary for a single TRAU rack installation . . . . . . .
Minimum space necessary for a back to back TRAU rack installation .
Drilling sketch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rack levelling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rack fixing on concrete floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rack fixing on raised floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Back to back rack fixing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Earthquake kit installation: preliminary operations. . . . . . . . . . . . . . . . .
Earthquake kit: floor holes for TRAU-HC. . . . . . . . . . . . . . . . . . . . . . . .
Earthquake kit: front view. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Earthquake kit: part list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Eathquake kit: Internal Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Anchor Kit S30861-K126-X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Anchoring screw S30861-K126 assembled on M12/50 anchor . . . . . . .
Fastening of the HSL M12/50 anchor . . . . . . . . . . . . . . . . . . . . . . . . . .
Rack fixed on the floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RCAP of the TRAU rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

13
16
17
19
20
21
22
24
26
27
29
31
32
32
33
34
35
38
39
40
42
43
44
45
46
47
49
50
51
52
52
53
54
57
58
59
60
61
61
62
62
63
64

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.

3.1
3.2
4.1
4.2
4.3
4.4
4.5
4.6
4.7
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10

TRAU-Standard power IN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
TRAU-HC power IN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
TRAU Standard top view : Rach Cabling Access Panel (RCAP) . . . . . . 69
TRAU-HC top view : Rach Cabling Access Panel (RCAP) . . . . . . . . . . . 70
Coax Adapter mounted on left side (GW6, LW6) . . . . . . . . . . . . . . . . . . 73
Coax Adapter mounted on right side (AW6, DW6) . . . . . . . . . . . . . . . . . 74
PCM line connections to MDF (to/from BSC and MSC) . . . . . . . . . . . . . 76
Remote Alarm connection to terminal block . . . . . . . . . . . . . . . . . . . . . 80
Coax Adapter mounted on left and right side . . . . . . . . . . . . . . . . . . . . . 84
TRAU Rack - Top view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Rack left side and rack right top side . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Power and ground cables distribution. . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Interconnections list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
TRAU Sub-rack: front view (fuse panel shown in open position) . . . . . . 98
TRAU sub-rack: Fuse Panel Mounting and Cabling . . . . . . . . . . . . . . . . 99
Adapter Board layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Adapter Board layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Adapater Board system block diagram . . . . . . . . . . . . . . . . . . . . . . . . . 102
DC-PANEL system block diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110

Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.

5.11
5.12
5.13
5.14
5.15
5.16
5.17
5.18
5.19
5.20
5.21
5.22
5.23
5.24
5.25
5.26
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9

Remote Alarms cabling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112


PCM lines connectors in DC-Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
PCM lines wirings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Table of the rack wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Rack wiring 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Rack wiring 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Rack wiring 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Rack wiring 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Table of the frame wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Frame wiring 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Frame wiring 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Mechanical layout of the Extra Adapter board . . . . . . . . . . . . . . . . . . . 131
Extra Adapter Board system block diagram . . . . . . . . . . . . . . . . . . . . . 132
New subrack of the TRAU_HC in TRAU_standard rack . . . . . . . . . . . . 133
Examples of replacement and expansion procedures . . . . . . . . . . . . . 135
Examples of replacement and expansion procedures . . . . . . . . . . . . . 135
TRAU frame wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
TRAU FRAME mechanics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
DC PANEL rear. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
TRAU FRAME cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Frame mechanics mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Ground cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
PCM and Signal cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
DC Panel mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.
Fig.

A30808-X3247-L460-2-7631

6.10
6.11
6.12
6.13
6.14
6.15
7.1
7.2

IMN:TRAU

Ground cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote Alarm cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Daisy chain and Signal cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DC Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standard rack drilling sketch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
HC rack drilling sketch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

143
144
144
145
145
146
147
147

IMN:TRAU

10

Installation
Transcoding and Rate Adaption Unit

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Tables
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.
Tab.

A30808-X3247-L460-2-7631

1.1
1.2
1.3
2.1
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
4.13
4.14
4.15
4.16
4.17
4.18
4.19
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
5.11
5.12
5.13
5.14
5.15
5.16
5.17
5.18
6.1
6.2

Board equipping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Coaxial cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Balanced cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Types of anchorage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Left TRAUs PCM lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Right TRAUs PCM lines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
PCM Lines connector pinning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Pinning of the 75ohm PCM on Adapter board . . . . . . . . . . . . . . . . . . . . 74
Pinning of the PCM connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Left TRAUs Remote alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Right TRAUs Remote alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Layout of the pins of connector AW3/DW3/GW3/LW3 . . . . . . . . . . . . . 78
Pinning of the Remote Alarm cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Pin description of the connectors W14 and W15 . . . . . . . . . . . . . . . . . . 81
Left TRAUs PCM lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Right TRAUs PCM lines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
PCM Lines connector pinning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Pinning of the 75ohm PCM on Adapter board . . . . . . . . . . . . . . . . . . . . 85
Pinning of the PCM connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Left TRAUs Remote alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Right TRAUs Remote alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Layout of the pins of connector AW0-AW7 . . . . . . . . . . . . . . . . . . . . . . 89
Pinning of the Remote Alarm cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Connectors position, type and function . . . . . . . . . . . . . . . . . . . . . . . . . 93
Table of the Fuse Panel cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
X25 connector of the Adapter Board . . . . . . . . . . . . . . . . . . . . . . . . . . 103
X23,X24 connectors of the Adapter Board . . . . . . . . . . . . . . . . . . . . . 104
X27 connector of the Adapter Board . . . . . . . . . . . . . . . . . . . . . . . . . . 105
X26 connector of the Adapter Board . . . . . . . . . . . . . . . . . . . . . . . . . . 106
X5,X6 connectors of the Adapter Board . . . . . . . . . . . . . . . . . . . . . . . 108
X1,X2 and X3,X4 connectors of the Adapter Board. . . . . . . . . . . . . . . 108
X7 to X22 connectors of the Adapter Board . . . . . . . . . . . . . . . . . . . . 109
X13,X14 connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
X15,X16 connectors of the Front Panel Board . . . . . . . . . . . . . . . . . . 113
X17 connectos of the Front Panel Board . . . . . . . . . . . . . . . . . . . . . . . 114
X1/X12 connectors of the Front Panel Board . . . . . . . . . . . . . . . . . . . 115
PCM lines connector in the Frame backpanel and in the RCAP . . . . . 119
X3,X4 connectors of the Extra Adapter Board . . . . . . . . . . . . . . . . . . . 128
X5,X6 connectors of the Extra Adapter Board . . . . . . . . . . . . . . . . . . . 129
X1,X2 connectors of the Extra Adapter Board . . . . . . . . . . . . . . . . . . . 129
X7 connector of the Extra Adapter Board . . . . . . . . . . . . . . . . . . . . . . 130
List of Rack Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
List of Frame cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140

11

IMN:TRAU

12

Installation
Transcoding and Rate Adaption Unit

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

1 General
i

i
i

i
1.1

The CE declaration of conformity for the product will be fulfilled if the setup and cabling
is undertaken in accordance with the specification in the manual and the documentation
listed there, such as mounting instructions, cable lists etc. Where necessary, account
should be taken of project-specific documentation. Deviations from the specifications or
independent changes during setup, such as use of cable types with lower screening
values, for example, can lead to the CE requirements being violated. In such cases the
CE declaration of conformity is invalidated and the responsibility passes to the person
who has caused the deviations.
The applicable technical standards and regulations are listed in the Terminology-Guide
to Documentation A30808-X3247-K-52-1-7635.
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in
a commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio communications. Operation of this
equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense.
For the US market the following note applies:- PCM ports are intended to be connected
to a near-placed Listed CSU (Channel Service Unit) providing over voltage protection.

Purpose of the Manual


This document provides the information required for the installation of the Transcoder
and Rate Adaption Unit (TRAU), rack configurated for balanced or coaxial PCM lines.
In accordance with the GSM requirements, a TRAU provides a PCM line interface to the
Base Station Controller (BSC) and four PCM lines to the Mobile Switching Center (MSC)
PCM line to/from BSC can be redundant.

1.2

Position in the System


The following figure gives the position of the TRAU within the BSS.
Um
Interface

BTS
Mobile
Station

BSC
Abis
Interface

TRAU
Asub
Interface

MSC
A
Interface

SBS
Fig. 1.1

A30808-X3247-L460-2-7631

Position of the TRAU in the SBS

13

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

1.3

Site Requirements
Before starting the installation, the construction of the room in which the operation and
maintenance equipment is to be housed must be complete and the room in good condition and dry heaters, if necessary, should be put up in the room.
Doors and windows, if any, must already have been installed and must be lockable.
Openings in wall or ceiling of floor, if required, must be complete.
The floor covering must have been laid.
Room lighting and wall sockets must have been installed.
Heating or air-conditioning systems should be ready for operation.
Walls and ceilings should have been painted.
The room must be clean.
To prevent subsequent accumulation of dust and dirt, the parts and equipment units to
be installed must be unpacked outside the room (if possible).
After that it is advantageous to install the OMS-B equipment, after all other installation
works to create the required infrastructure (power supply, PCM30 lines ...) are complete.

1.4

Station Configuration
The TRAU functionality is mechanically arranged in two variants:
- TRAU rack able to manage up to 480 TCH (Standard configuration)
- TRAU-HC rack able to manage up to 960 TCH (High capacity configuration)

1.4.1

TRAU Standard
The TRAU Standard rack (S30861-C21-X), which is configured according to the ETSI
standard (h=2000mm, l=600mm, p=300mm) (h=78.7,w=23.6,d=11.8) can accommodate up to 4 TRAU subracks equal each other and equipped with the same boards (files
BC, EF, HI and MN). Every subrack includes a fuse and alarm panel (files A, D, G and
L). Files A, D, G and L relate to the backplanes of the TRAU subracks with the connectors for internal and external connections. A lamp panel is equipped in file T. The sensor
of the Open Door Alarm (OPDS) is equipped in file O.
The TRAU rack includes up to 4 subrack (4 TRAU modules)
The subrack (H=420mm (16.5), W=533mm (21), D=249mm (9.8) includes the interfaces to the BSC (BSCI) and the MSC (MSCI) , the transcoders (TRAC) and the cable
connection zone to the RCAP of the rack.
TRAU subrack capacity (depending on PCM line type):
One PCM line with 120 or 96 16kbit/s channels to/from the BSC.
Four PCM lines with 30 or 24 64kbit/s channels to/from the MSC.
This capacity corresponds to 15 or 12 TRXs (full rate) located in the BTS (radio
measures pre-processed in the BTS).

14

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Boards are equipped according to the following Tab. 1.1.


Quantity

Acronym

Slot position

2
2
6

BSCI
MSCI
TRAC

40-44
36-48
18-24-30
52-58-64

PWRS

3-71

Tab. 1.1

Notes
1
1
2

Board equipping

Note 1: Boards in position 44 and 48 are for redundancy purposes.


Note 2: All the TRAC boards of a TRAU subrack are always equipped at the factory, irrespective of the number of channels of the PCM line coming from the BSC. One board (out
of the equipped six) is for redundancy purposes.
The TRAU Fuse and Alarm Panel (TFAP) (H=116mm (4.6), W=533mm (21)), accommodates the fuses through which the primary power is brought to the equipment, the LEDs
displaying the equipment alarms, and the SUB D 15 connector interfacing (V.11) the Local
Maintenance Terminal (LMT).
The rack is equipped with an alarm panel placed at the top of the rack which can be
attained by removing the front cover.
The racks have a door mounted. Therefore a new alarming mechanism is introduced
detecting when the door is left Open (see detail x in Fig. 2.5). The relevant TRAU
Open door alarm is managed by SW and treated as an internal alarm. A sensor is cableconnected to the first TRAU shelf of the rack, indicating when the TRAU door is Open.
The TRAU rack configuration is modular in accordance with the number of the transcoders
to be equipped. The number of the transcoders depends on the number of traffic channels
coming from the BSC.
Every TRAU subrack can be equipped with 5 (+1 redundant) transcoder boards (TRAC).
Every TRAC board handles up to 24 traffic channels.
Fig. 1.2 shows a picture of the TRAU Standard rack fully equipped and Fig. 1.3 with
flame-guard door and fan units in file H.

A30808-X3247-L460-2-7631

15

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

GLOBAL ALARMS

POWER 0
10A
F

LAMP
TEST

CRITICALMAJOR MINOR

POWER 1

LOCAL
TERMINAL

10A
F

BSC
LINK
ALARM

P
W
R
S
0

T
R
A
C
0

T
R
A
C
1

T
R
A
C
2

18

24

30 36 40 44 48 52 58 64

M
S
C
I
0

T
R
A
C
3

T
R
A
C
4

T
R
A
C
5

P
W
R
S
1

LOCAL
TERMINAL

10A
F

LAMP
TEST

BSC
LINK
ALARM

T
R
A
C
0

T
R
A
C
1

T
R
A
C
2

T
R
A
C
5

P
W
R
S
1

18

24

30 36 40 44 48 52 58 64

71

M
S
C
I
0

B
S
C
I
1

B
S
C
I
0

M
S
C
I
1

GLOBAL ALARMS

POWER 0
10A
F

T
R
A
C
3

T
R
A
C
4

LAMP
TEST

LOCAL
TERMINAL

10A
F

BSC
LINK
ALARM

P
W
R
S
0

T
R
A
C
0

T
R
A
C
1

T
R
A
C
2

T
R
A
C
5

P
W
R
S
1

18

24

30 36 40 44 48 52 58 64

71

M
S
C
I
0

B
S
C
I
1

B
S
C
I
0

M
S
C
I
1

GLOBAL ALARMS

POWER 0
10A
F

T
R
A
C
3

T
R
A
C
4

LAMP
TEST

LOCAL
TERMINAL

10A
F

BSC
LINK
ALARM

P
W
R
S
0

T
R
A
C
0

T
R
A
C
1

T
R
A
C
2

T
R
A
C
5

P
W
R
S
1

18

24

30 36 40 44 48 52 58 64

71

M
S
C
I
0

HI

CRITICALMAJOR MINOR

POWER 1

EF

CRITICALMAJOR MINOR

POWER 1

BC

71

CRITICALMAJOR MINOR

POWER 1

M
S
C
I
1

GLOBAL ALARMS

POWER 0
10A
F

P
W
R
S
0

B
S
C
I
1

B
S
C
I
0

B
S
C
I
0

B
S
C
I
1

M
S
C
I
1

T
R
A
C
3

T
R
A
C
4

MN

O
OPDS

Fig. 1.2

16

Front view of the TRAU Standard rack

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

GLOBAL ALARMS

POWER 0
10A
F
POWER 1

LOCAL
TERMINAL

10A
F

P
W
R
S
0
3

T
R
A
C
1

T
R
A
C
2

T
R
A
C
5

P
W
R
S
1

18

24

30 36 40 44 48 52 58 64

71

M
S
C
I
0

B
S
C
I
1

B
S
C
I
0

M
S
C
I
1

GLOBAL ALARMS

POWER 0

T
R
A
C
3

T
R
A
C
4

LOCAL
TERMINAL

10A
F

M
S
C
I
0

BSC
LINK
ALARM

B
S
C
I
1

B
S
C
I
0

M
S
C
I
1

T
R
A
C
3

T
R
A
C
4

T
R
A
C
5

T
R
A
C
0

T
R
A
C
1

T
R
A
C
2

18

24

30 36 40 44 48 52 58 64

GLOBAL ALARMS

POWER 0
10A
F

P
W
R
S
1

POWER 1

LOCAL
TERMINAL

LAMP
TEST

BSC
LINK
ALARM

P
W
R
S
0

T
R
A
C
0

T
R
A
C
1

T
R
A
C
2

18

24

30 36 40 44 48 52 58 64

M
S
C
I
0

B
S
C
I
1

B
S
C
I
0

M
S
C
I
1

GLOBAL ALARMS

POWER 0
10A
F

T
R
A
C
3

T
R
A
C
4

T
R
A
C
5

P
W
R
S
1

LOCAL
TERMINAL

10A
F

LAMP
TEST

BSC
LINK
ALARM

P
W
R
S
0

T
R
A
C
0

T
R
A
C
1

T
R
A
C
2

T
R
A
C
5

P
W
R
S
1

18

24

30 36 40 44 48 52 58 64

71

M
S
C
I
0

B
S
C
I
0

B
S
C
I
1

M
S
C
I
1

T
R
A
C
3

T
R
A
C
4

OPDS

Fig. 1.3

HI

71

CRITICALMAJOR MINOR

POWER 1

EF

71

CRITICALMAJOR MINOR

10A
F

BC

LAMP
TEST

CRITICALMAJOR MINOR

POWER 1

BSC
LINK
ALARM

T
R
A
C
0

10A
F

P
W
R
S
0

LAMP
TEST

CRITICALMAJOR MINOR

MN

Front view of the TRAU Standard rack in fire resistance cabinet

A30808-X3247-L460-2-7631

17

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

1.4.2

TRAU-HC
The new TRAU-HC (S30861-C37/C41-X) rack has the same footprint as that the
previous TRAU Standard rack, mechanical dimensions h=2000, l=600, p=300 (h=78.7,
w=23.6, d=11.8) , but each rack includes up to 4 Frames (8 TRAUs) (Fig. 1.5). Fans
are included for heat dissipation (Fig. 1.4). No power supply card is necessary because
all the cards have a DC/DC converter on board. The weight, fully equipped, is 130 Kg
(286 lb).
The rack is equipped with an alarm panel placed at the top of the rack which can be
attained by removing the front cover
The racks have a door mounted. Therefore a new alarming mechanism is introduced
detecting when the door is left Open (see detail x in Fig. 2.19). The relevant TRAU
Open door alarm is managed by SW and treated as an internal alarm. A sensor is
cable-connected to the first TRAU shelf of the rack, indicating when the TRAU door is
Open.
The new TRAU frame can be mounted on the old rack by using the Extra Adapter Board
(S30861-U725-X) mounted into the DC-Panel. In that case, as the RCAP board is the
same as that of the Standard configuration, the number of channels cannot exeed 480
TCH.
The TRAU rack configuration is modular in accordance with the number of the
transcoders to be equipped. The number of the transcoders depends on the number of
traffic channels coming from the BSC.
Each TRAU module is functionally independent from the other ones and can be
equipped with 5 (+1 redundant) transcoder boards (TRAC). Every TRAC board handles
up to 24 traffic channels.
Fig. 1.4 shows a picture of the TRAU HC fully equipped.
Leds, lamps, signallings and alarms reporting have the same philosophy as that of the
Standard configuration (Fig. 1.4 and Fig. 1.5) except for the Fan-alarm and Door-Open
alarms. The Fan-alarm is reported on the TRAU_Left and the door-open-alarm on the
TRAU_Right. So to manage both the alarms, the presence of two TRAUs at least, within
the same subrack, is necessary.
.

18

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

TRAU 0

TRAU 2

TRAU 3

TRAU 4

TRAU 5

TRAU 6

Fig. 1.4

TRAU 1

TRAU 7

TRAU HC fully equipped

A30808-X3247-L460-2-7631

19

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

DC Panel

TRAU module
Fig. 1.5

20

TRAU-HC frame with two TRAU modules and DC Panel.

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

1.5

IMN:TRAU

Cable Length between Network Elements


Fig. 1.6 shows A, Abis and Asub interfaces; whereas, Tab. 1.2, Tab. 1.3, and Fig. 1.6
show the maximum distances and attenuations allowed between BSS racks (BTS, BSC,
TRAU) and between the BSS (TRAU) and the MSC.

Abis

BTS

BSC

Asub

TRAU

MSC

BSS
Fig. 1.6

Interfaces between network elements

For the US market PCM ports are intended to be connected to a near-placed Listed
CSU (Channel Service Unit) providing over voltage protection.

Coaxial Version
Connection

Max. hop
attenuation

Max. hop
length

6 dB

cable attenuation dependent

Asub

6 dB

cable attenuation dependent

Abis

6 dB

cable attenuation dependent

Tab. 1.2

Coaxial cables

Balanced Version
Connection

Max. hop
length

6 dB

cable attenuation dependent

Asub

6 dB

cable attenuation dependent

Abis

6 dB

cable attenuation dependent

Tab. 1.3

Max. hop
attenuation

Balanced cables

Whenever two equipment elements are connected through High Frequency-Distribution Frames (HF-DF), the maximum attenuation is as follows:

A30808-X3247-L460-2-7631

21

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

1st equipment HF-DF


2nd equipment HF-DF

BSC

TRAU

Fig. 1.7

1.6

6 dB
6 dB

6dB

6dB

HF-DF

HF-DF

Maximum attenuations between equipment and HF-DF rack

Installation Activities
The installation activities for the BSS-TRAU rack consist of the following:
Unpacking the rack and inspecting for visible damages
Positioning the rack as per floor plan and anchoring it to the floor
Grounding the rack
Connecting DC power to the rack
Note: The recommended torque value for the screws of the input terminal block is
from 1.24 to 2.26 N x m (11 to 20 lb x in).
Connecting external cables
Inserting power supply boards and disk units into the rack.

22

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

2 Mechanical Installation
2.1

Installation Tools
The correct rack installation is carried out with the aid of the following tools (see
Fig. 2.1).
Hammer drill (ATF)
Twist drills widia 20mm (0.79) and 9mm (0.35) (PRP)
Poligonal socket wrench (CHT)
Poligonal wrench (CHP)
N3 and N4 screwdrivers (CAT) for cross-slotted screws
N2, N3 and N4 screwdrivers (CA)
Square (SQ)
Plumb line (FP)
Tracer (TR)
Screwdrivers for M3, M6 and M12 hex.socket head screws (CHB)
Electric jigsaw with sawdust vacuum and filter (for raised floors only) (ATS)
Other tools are needed for the electrical connections:
Wire-wrap tool for 0.8 x 1.2mm (0.03x0.05)anchoring pins and 0.5mm (0.02) wire
Power soldering iron for tinned copper braid welding
Soldering iron for electronic circuits
Crimping tool

A30808-X3247-L460-2-7631

23

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

Fig. 2.1

24

Installation tools

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

2.2

IMN:TRAU

Equipment Delivery
Racks, devices, boards, cables as well as all installation material and relevant manuals
are shipped in cartons or in wood boxes. Handle each container with extreme caution to
avoid tipping.
All boxes containing installation material have the following information printed on them
or indicated in label W of Fig. 2.2 and Fig. 2.3:
trade-mark
customer order number
serial number of rack or other equipment
destination
gross and net weight
overall dimensions
symbol or inprint to identify the "Top" or "Bottom"
For transport of the cartons from the unloading area into the construction room use
handling aids (for example: fork-lift truck, goods elevator); a second person is needed
for help.

2.3

Preliminary Checks
Check that the cartons are not damaged. In case of evident damage due to transport,
unpack the equipment in the presence of an insurance company representative and
promptly claim any damage and inform the shipper for specifying the damage.
Check whether the package is actually addressed to the site and complete.
Open it and take the contents out carefully.
After having removed all contents from the packing material, check for deformation to
the devices, of torn or unwelded wiring, of oxidized connectors, as well as deformed
front sides of the units, loose screws, damage to paint work, etc.

2.4

Equipment Unpacking
During the unpacking steps great care must be taken to ensure that the equipment is
not scratched or damaged in any way.
The packing material should be preserved for possible future re-packing.
In case of repacking or in the event that repacking material is supplied by the customer,
special care should be taken to avoid damage during the transport and storage of the
devices.

A30808-X3247-L460-2-7631

25

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

8
1

2
GILE

FRA

3
Fig. 2.2

26

TRAU rack unpacking

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Z
W

3
Z1

Z2

Fig. 2.3

A30808-X3247-L460-2-7631

Unpacking of TRAU devices and boards

27

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

2.4.1

Rack Unpacking
With reference to Fig. 2.2 proceed as follows:
Cut the straps 8 and 9 and remove the container cover 7.
Take out the rack from the box 1 and the relevant wood support 2.
Open the tubular shrink-wrap 5 protecting the rack and take it out.
Remove the 8 dehydrating material bags 6 fixed with adhesive tape.
Remove the protections 3 of rack head and base and lift the rack to vertical position.
Remove the 2 front profiles 4 and the 2 rear profiles 4 protecting the rack edges.

2.4.2

Devices and Boards Unpacking


With reference to Fig. 2.3 proceed as follows:
Cut with a suitable knife the adhesive tape sealing the box 1.
Take the device out.
Remove the shaped profiles in polystyrene foam 4.
Remove the dehydrating material bags 3.
Open the wrap 2 protecting the device/board and withdraw it.
The packing material should be preserved for possible future repacking. To this
purpose, reverse the procedure described above, taking into account the warnings
specified for the packing. In case of repacking or in the event that repacking material is
supplied by the Customer, special care should be taken to avoid damages during transport and storage of the devices.

28

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

2.5

IMN:TRAU

Installation of the TRAU-Standard Rack


The TRAU rack is provided with proper metal eyebolts (G1 G4) for securing the rack
during transport (see Fig. 2.5).
The aluminium protection grid, in the upper part of subracks, is covered during transport
and installation by a fender sheet which is to be removed after installation and which
prevents damages caused by accidental falls of screws or other installation tools.
The Y detail shows the ESD jack (CNB) for wrust (BR) strap connection.
The rack can be anchored onto two types of floor (see Tab. 2.1 as well as Fig. 2.6 and
Fig. 2.7):
Type of
anchorage

Standard floor
(concrete)

Wall anchorage
Stand alone rack
Back to back racks
Tab. 2.1

yes
yes
yes

Raised floor
yes
yes
yes

Types of anchorage

Note: The stand alone rack anchored on raised floor must be also fixed to the wall.
The installation of the TRAU requires the following accessories, available separately
(see Fig. 2.4):
-

Adaption (AD):
Expansion bolts (M8):

for securing the rack to the wall


for fixing the rack to the wall

90 (3.5

70 (2.8

AD
M8
6 (0.2)

Fig. 2.4

A30808-X3247-L460-2-7631

TRAU rack installation accessories

29

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

.For correct positioning of the rack, trace the drilling plan of the floor, whichever this is,
using the plumb line, the square and the tracer. These procedures, relevant to the rack
installation, adjustment and alignment, are valid for all types of rack configurations.
Make sure the leveling feet (P1-P4) of the rack basement do not stretch out the basement level. Place the rack in vertical position, then make the reference pins of the alignment bar, to be aligned with the corresponding holes in the rack basement. Make sure
the alignment bar is fully inside the groove of the rack basement.
Remove the flame guard hex.socket head screws, M12, and washers from the hole for
the expansion bolt M8.
Put the rack in a vertical position so that the holes on the floor coincide with the holes of
the rack basement.
Adjust the leveling feet (P1-P4) of the basement to have the rack coinciding both vertically and horizontally in the correct position.
Screw tightly the hexagonal bolts (M8x10) of the upper anchorage, then the hexagonal
expansion bolts (2xM8x25) of the floor by means of a 13mm (0.5) socket wrench. For
elevated floor, use proper (2x5x30 Din 97/UNI 702) self-thread screws and tighten them
firmly.

30

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Y detail

ESD jack for wrist strap connection

TRAU Open Door

Fig. 2.5

A30808-X3247-L460-2-7631

TRAU rack details

31

IMN:TRAU

32

Installation
Transcoding and Rate Adaption Unit

Fig. 2.6

Rack fixing on concrete floor

Fig. 2.7

Rack fixing on raised floor

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

2.5.1

IMN:TRAU

Grounding connections of the TRAU Standard Rack (S30861-C21-X)


The rack has to be connected to the site specific ground system before to starting the
connection of the power cable. To grounding the rack has to be used the Kit S30861K124-X (see Fig. 2.8 ).

The grounding kit has not to specify when the Fire Resistance kit S30861-K106-X is
used; in this case the grounding kit (C50324-A201-A6) is part of the Fire Resistance kit
itself.
The kit contains the following items:

10+/-1.5

ground plate assy (see Fig. 2.10)


grounding cables
grounding label
bush
cover (see Fig. 2.10, pos. 10)

(0.39+/-0.06)

1.
2.
3.
4.
5.

25+/-1.5
(0.98+/-0.06)

Fig. 2.8

Grounding kit

The ground plate assy (see Fig. 2.10) contains the following items:
1.
2.
3.
4.
5.

A30808-X3247-L460-2-7631

ground plate
washer
contact washer
hexagon nut
screw

33

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

46.5 (1.83)

77.5 (3.05)

Fig. 2.9

Ground plate assy

Mounting instruction of the grounding kit (see Fig. 2.10):


Remove the grounding cable (if it is connected) from the RGB bolt (corresponding
to pos. 2)) on the top of the rack.
Remove yellow ground label 4)
Remove ground connection nut 2), washers and the screws 3).
Place as shown the ground plate 1) and replace nut and washer 2).
Change the screws 3) with the one supplied in the kit (item 5 of Ground plate assy).
Spacing piece 11) supplied with ground plate kit should be used if it is necessary
only to guarantee a correct plate mounting. The ground plate should be parallel to
the rack top plate.
Remove screws 6) and connection cover 5).
Cut label in half and cover the two ground symbol of the ground terminal block as
shown 12).
Place ground cables 7) and 8) supplied by the kit and connect them as shown.
Lock ground cables by the cable tie 9).
Place the new connection cover 10) and fix it by the screws previously removed.

34

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Grounding kit installation

Two bolts for external ground wire connection

Fig. 2.10

Grounding cables kit


To grounding the rack use a 16mmq/5AWG or 25mmq/3AWG PVC Ye/Gr copper wire.
The connection should be connected to a main wire or to a ground bar on the shortest
way.
Mounting procedure of the external ground wire:
Use the nearest ground system on site.
Verify the distance between the connection points of the ground system and the
ground bolts of the rack.
Cut the wires to the required lenght.
Unsheet the wire at the end and crimp a two-hole M6 lug terminal (i.e. Thomas &
Betts type 54852BE blu color for 16mmq/6AWG or 54856BE brown color for
25mmq/3AWG).
Remove hexagon nut 4), contact washer 3) and washer 2) of the ground plate assy.
Connect the prepared wire to the ground plate assy by a two-hole lug terminal.
Replace the hexagon nut 4), contact washer 3) and washer 2).
Tighten the hexagon nut firmly.

A30808-X3247-L460-2-7631

35

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

2.5.2

Grounding collector and fire protection kit for the TRAU-Standard


rack (MK:FGV* - S30861-K106-X)
The FIREPROT-0 (MK:FG) is an optional kit reducing the damage of a fire on the TRAU
rack (S30861-C21-X) and also includes an additional extension of the rack grounding.
Unit part number list:
Grounding kit (C50324-A201-A6).
Fun unit (S50201-U32-X).
FG rack door (C50324-A201-B12).
Four cable tie (H70764-B140-J210).
One label (H60403-C305-K2).

36

The Grounding kit use the same components and the same mounting instructions as
the kit S30861-K124-X (see par. 2.5.1)

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

2.5.2.1

IMN:TRAU

Fan units (FG Kit - S50201-U32-X) and rack door (FG kit - C50324A201-B12) for fire resistance cabinet.
This kit is available only for S30861-C21-X TRAU-Standard rack.
The fan units kit consists of :
Fan motor assembly
Two power supply cables
Mounting instruction with reference to Fig. 2.11 :
Remove grid cover 1) by the screws.
Remove nuts 3) and connect fan units power supply cables 4) and 5).
Cables lug to be connected on the existing ones.
Lock cables by the previously removed nuts 3).
With reference to Fig. 2.12:
Connect power supply cables 4) and 5) coming from Bus Bar PP0 as shown.
Cables must be fixed to the fan unit front panel as shown by cable ties 7) supplied
with the kit.
Insert fan units 6) in the rack and fit it by grid cover screws 2) previously removed.
Place the cables in the left rack space (side of the sub-racks).
With reference to Fig. 2.13
Remove door fixing scews 1) and disconnect door ground cable from door side.
Place new door and connect the door ground cable previously disconnected and fix
the door by the removed scews 1).
Place the label 20) in indicated position.

A30808-X3247-L460-2-7631

37

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

2)
T
H
GLOBAL ALARMS

POWER 0
10A
F
POWER 1

LOCAL
TERMINAL

10A
F

Fig. 2.11

38

P
W
R
S
0

T
R
A
C
0

18 24

T
R
A
C
1

LAMP
TEST

CRITICALMAJOR MINOR

BSC
LINK
ALARM

B
S
C
I
0

T T
R R
A A
C C
4 5

P
W
R
S
1

30 36 40 44 48 52 58 64

71

T
R
A
C
2

M
S
C
I
0

B
S
C
I
1

M
S
C
I
1

R
A
C
3

BC

Power cables connection for fans kit

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

6)

2)

T
H
A
GLOBAL ALARMS

POWER 0
10A
F
POWER 1

LOCAL
TERMINAL

10A
F

P
W
R
S
0

T
R
A
C
0

18 24

5) BLUE
FROM BUS BAR PP0 -V

T
R
A
C
1

LAMP
TEST

CRITICALMAJOR MINOR

BSC
LINK
ALARM

B
S
C
I
0

T T
R R
A A
C C
4 5

P
W
R
S
1

30 36 40 44 48 52 58 64

71

T
R
A
C
2

M
S
C
I
0

B
S
C
I
1

M
S
C
I
1

R
A
C
3

BC

5)
7)

FANS EXISTING CABLE

4) BLACK
FROM BUS BAR PP0 +V

4)

5)
FANS EXISTING CABLE

Fig. 2.12

Fan units mounting

A30808-X3247-L460-2-7631

39

Installation
Transcoding and Rate Adaption Unit

EXISTING LABELS

FGV1 2D-CODE LABEL

IMN:TRAU

Fig. 2.13

40

Flame-guard door mounting

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

2.5.3

IMN:TRAU

Earthquake Kit for the TRAU-Standard Rack.


Earthquake Kit, available separately, allows the TRAU rack to be resistant to earthquake
zone 4 strains, according to the NEBS requirements.

This kit is available only for S30861-C21-X rack starting from issue 06 on.
The kit for TRAU-Standard (MK: EQ4V1 - S30861-K105-X) consists of (Fig. 2.16):
1.
2.
3.
4.

i
!

N2 Internal Plate (C50324-A201-C13)


N4 Anchoring Screws (HSL M12/50)(C50117-A201-B49)
N1 Label (C7322-R6-N1)
N1 Insulating plate (C50117-A201-C389)

The Earthquake Kit allows the TRAU rack to conform with the Bellcore specification and
is mandatory for the U.S. market.
The concrete floor shall have the compressive strength of 30 N/mm2 minimum
With reference to Fig. 2.14, Fig. 2.15 and Fig. 2.16 proceed as follows:
1. Mark floor holes.
2. Drill a 90mm (3.54) deep hole (18 mm (0.71) diameter hole) for each Anchoring
screw.
3. Using an appropriate vacuum, clear the hole with a small diameter hose which can
reach the bottom of the hole.
4. Take off the leveling feet (P1-P4 in Fig. 2.6 and Fig. 2.7) from the rack basement
and, if necessary, extend the hole size to 20 mm (0.79) diameter.
5. Place the TRAU rack. The hole of the rack basement must fit the hole on the floor.
6. Position the Internal Plates over the holes. Be careful not to let any debris fall into
the holes.
7. Insert the anchor into the hole and tap the anchor down with a hammer until the
washer contacts the rack internal plate.
8. Screw down the Anchor HSL M12/50 having 80Nm tightening torque.

A30808-X3247-L460-2-7631

41

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

1+1 INTERNAL PLATE

N4 EXAGONAL-HEAD SCREW
(HSL M12/50) FOR ANCHORAGE

TRAU CABINET

TRAU POSITION
16
(6. 0
3)

300
(11
.8
)
95
(3.
7)

HOLES FROM LODGING


FLOOR

0
30 .8)
(11
0
60 .6)
(23
0
15 )
9
(5.

Fig. 2.14

42

Earthquake Kit : floor holes for the TRAU-Standard.

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

N4 GOLFARE FOR
LIFT THE CABINET

INTERNAL PLATE
HSL M12/50
WASHER

162
(6.37)

84
(3.3)

18
(0.71)

18 (0.71)
FLOOR

Fig. 2.15

A30808-X3247-L460-2-7631

(41 3)

90 (3.5)

18+1

Earthquake kit: front view.

43

IMN:TRAU

Fig. 2.16

44

Installation
Transcoding and Rate Adaption Unit

Earthquake kit parts list.

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

Fig. 2.17

IMN:TRAU

Earthquake kit anchoring screws detail

A30808-X3247-L460-2-7631

45

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

220 mm (8.7)

21 mm
(0.83)

37,5 mm (1.5)

160 mm (6.3)

145 mm (5.7)

275 mm (10.8)

Fig. 2.18

46

Earthquake kit: Internal Plate

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

2.6

IMN:TRAU

Installation of the TRAU-HC Rack


The TRAU rack is provided with two proper metal eyebolts (G1 and G2) on the top for
securing the rack during the transport (see Fig. 2.19.).

If the rack is provided with the earthquake kit take care of the floor flatness/ruoghness.
The foor flatness tolerance must be 6mm/mq max. and the roughness tolerance 5 mm
max

BR
G1
G2

CNB

Fig. 2.19

A30808-X3247-L460-2-7631

Detail Y

TRAU rack details

47

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

The Y detail shows the ESD jack (CNB) for wrust (BR) strap connection.
The rack can be anchored on the concrete floor or raised floor in stand alone or back to
back mode (see Fig. 2.23).
Before starting of rack installation, consult the site documentation to locate the installation point of the TRAU rack, the PCM network termination, the Alarm connection point,
the Power Supply unit; then check the earthing bar and the necessary cable runways.

48

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

2250mm (88.6)

2000mm (78.7)

Minimum
room height

Front

600mm (23.6)
950mm (37.4)

Minumum
100mm (3.9)

300 mm (11.8)

Front

700mm (27.6)
Fig. 2.20

A30808-X3247-L460-2-7631

Minimum space necessary for a single TRAU rack installation

49

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

2000mm (78.7)

Minimum
room height

2250mm (88.6)

Front

Front

600mm (23.6)

300 mm (11.8)
Minimum
100mm (3.9)
1900mm (74.8)

Front

1500mm (59)

Front

600mm (23.6)

950mm (37.4)

Minimum
800mm (31.5)
Fig. 2.21

50

Minimum space necessary for a back to back TRAU rack installation

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

300+0-1.5 (11.8+0-0.01)

transportation holes

145+/-0.25 (5.7+/-0.01)

57
(2.2)

BASEMENT LAYOUT
300+/-0.25 (11.8+/-0.01)

80 (3.15)

45 (1.77)

Installation on concrete floor:


Mark the positions of the drilling holes as per Fig. 2.22.
Drill the floor with 18mm in diameter and a depth of 90mm.
Clean out the drilling holes by vacuuming.
Make sure the levelling feet (P1-P4 - see Fig. 2.23) of the rack basement do not
stretch out the basement level.
Place the rack in vertical position and shift it in the correct position so that the holes
on the floor coincide with the holes of the rack basement.
Adjust the levelling feet (P1-P4 - see Fig. 2.23) of the basement to have the rack
coinciding both vertically and horizontally in the correct position.
Insert (see Fig. 2.24) the anchor (e.g. HILTI HSL M12/25) and washer (e.g. DIN 125
- Internal Diameter=21mm - External Diameter=37mm) into the hole and tap the
anchor down with a hammer until the washer contacts the rack basement.
Screw down the anchor HSL M12/50 having 80Nm tightening torque.

adjustable feet

599+/-1 (23.6+/-0.04)

Fig. 2.22

Drilling sketch

A30808-X3247-L460-2-7631

51

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

Fig. 2.23

Rack levelling

Washer

Anchor

Fig. 2.24

52

Rack fixing on concrete floor

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Installation on raised floor:


Mark the positions of the drilling holes as per Fig. 2.22.
Drill the raised floor with 18mm in diameter
Drill the concrete floor with 18mm in diameter and a depth of 90mm.
Clean out the drilling holes by blowing or sucking.
Make sure the levelling feet (P1-P4 - see Fig. 2.23) of the rack basement do not
stretch out the basement level.
Place the rack in vertical position and shift it in the correct position so that the holes
on the floor coincide with the holes of the rack basement.
Adjust the levelling feet (P1-P4 - see Fig. 2.23) of the basement to have the rack
coinciding both vertically and horizontally in the correct position.
Insert (see Fig. 2.25) the anchor (e.g. HILTI HSA M12/80+300) and washer (e.g.
DIN 125 - Internal Diameter=17mm - External Diameter=30mm) into the hole and
tap the anchor down with a hammer until the washer contacts the rack basement.
Screw down the Anchor HSL M12/80+300 having 50Nm tightening torque.

(Di=0.67 De=1.18)

(3.5)

Fig. 2.25

(D=0.71)

Rack fixing on raised floor

If the distance between the raised and the concrete floor (Ground floor loose stone foundation) is bigger than the lenght of the screw of the anchor (e.g. HILTI M12/300) replace
the screw of the anchor with a threaded rod M12 DIN 975 cutting the same at the right
leght.

A30808-X3247-L460-2-7631

53

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

Racks installed back to back


If two rack are installed back to back it also needs to fix the racks on the top. After having
installed the racks proceed as follows (see Fig. 2.26):
Take the plane washer (dameter 10.5 DIN 934) in the correct position.
Insert the bolt (M10 DIN 933).
Insert the spring washer (diameter 10.5 DIN 127).
Tighten the nut (M10 DIN 934) firmly.

Nut M10 DIN 934

Spring washer diam.10.5 DIN 127


Plane washer Diam.10.5 DIN 433
Bolt M10 DIN 933

Fig. 2.26

54

Back to back rack fixing

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

2.6.1

IMN:TRAU

Earthquake Kit for TRAU-HC.


Earthquake Kit, available separately, allows the TRAU rack to be resistant to earthquake
zone 4 strains, according to NEBS requirements.

!
!

The foor flatness tolerance must be 6mm/mq max. and the roughness tolerance 5 mm
max
The concrete floor shall have the compressive strength of 30 N/mm2 minimum
The kit for TRAU-HC (MK: EQ4V2 - S30861-K121-X) consists of (Fig. 2.30):
1.
2.
3.
4.
5.
6.

N2 Internal Plate (C50324-A201-C39)


N4 Anchoring Screws (V50089-B3-P100)
N1 Label (C7322-R6-N1)
N4 washers (C50324-A201-C40)
N1 Insulating bushes (C50324-A201-C41
N1 Insulating plate (C50324-A201-C42)

For installed TRAU-HC pull out the cards of the down rack and take out the four guiderails on the right side and the four guide-rails on the left side

Mounting Instructions
With reference to Fig. 2.27 Fig. 2.28, Fig. 2.29 and proceed as follow:
1. Pull out the cards of the down rack if they are inserted and take out the three guiderails on the right side and the two guide-rails on the left side (mark their slot position,
so it is easier to reassemble them)
2. Mark floor holes (if the new rack replaces the old standard type you can use the
previous holes by two anchoring screws S30861-K126-X kit (see mounting instruction belove).
3. Drill a 105mm (4.13) deep hole (18 mm (0.71) diameter hole) for each anchoring
screw.
4. Using an appropriate vacuum, clear the hole with a small diameter hose which can
reach the bottom of the hole.
5. Take off the leveling feet (P1-P4 in Fig. 2.23) from the rack basement and, if necessary, extend the hole size to 20 mm (0.79) diameter.
6. Place the insulating plate and the TRAU rack on. The hole of the rack basement
must fit the hole on the floor.
7. Position the Internal Plates over the holes. Be careful not to let any debris fall into
the holes.
8. Insert the anchors into the holes and tap the anchors down with a hammer until the
washer contacts the rack internal plate.
9. Insert on the anchors the insulating bush, theinsulating washer, the washer, and
screw down the Anchor HSL M12/50 having 80Nm tightening torque.

A30808-X3247-L460-2-7631

55

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

Mounting Instructions using the Kit S30861-K126-X.


The kit S30861-K126-X is an optional kit to fix the BT 960 HC rack on the holes of the
previous TRAU rack (S30861-C20-X). It s consist of (refer Fig. 2.32):

Nr.2 complete rod (item1)


Nr.2 ring (item 2)
Nr.2 insulating bush (item 3)
Nr.4 washer (item 4)
Nr.2 Xexagon nut M12 (item 5)
Nr.1 label

With reference to Fig. 2.33 proceed as follows:


1. Insert the washer (item 2) on long threaded part of item 1 and the ring ( item 3) .
Then insert, removed from HILTI HSL-B-TZ M12/50 anchor SIEMENS code
V50089-B3-P100-7625 supplied with the kit S30861-K121-X the S30861-K121-X
kit, the rubbing (item 4), the expansion cone (item 5) and screw the nut cone (item 6)
2. Insert the insulating bush (item 3) on opposite threaded part, insert the washer (item
4) and screw in the nut (item 5)
3. Position the Internal Plates, from S30861-K105-X kit, over the holes. Be careful not
to let any debris fall into the holes andPut the two anchor so assembled in the holes
4. Insert the two so assembled anchor into the rear position hole and tap the anchor
down with a hammer until the washer contacts the rack internal plate.
5. Screw down the anchor HSL M12/50 having 80Nm tightening torque with the M12
pivot frontal direction (Fig. 2.34
6. Place the TRAU rack on. The anchor must fit the rear holes of the rack basement
and the front holes of the rack basement must fit the holes on the floor.
7. Position the Internal Plates over the rack basement. Be careful not to let any debris
fall into the holes.
8. Mount the anchor V50089-B3-P100-7625 supplied with the S30861-K121-X kit on
the front holes.
9. Insert on the rear anchors the insulating bush, theinsulating washer, the washer, and
screw, by using a dynamometer at 80 Nm, the nut M12/50. (Fig. 2.35).

56

After the installation stick 20 code label on rack door in reserved area

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

Fig. 2.27

IMN:TRAU

Earthquake kit installation: preliminary operations

A30808-X3247-L460-2-7631

57

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

1+1 INTERNAL PLATE

N4 EXAGONAL-HEAD SCREW
(HSL M12/50) FOR ANCHORAGE

TRAU CABINET

(10 271
.67
)

TRAU POSITION

(5. 145
71
)

(2. 67.5
66
)

HOLES FROM LODGING


FLOOR

0
30 .8)
(11
0
60 .6)
(23
0
15 )
9
(5.

Fig. 2.28

58

Earthquake kit: floor holes for TRAU-HC.

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

N2 GOLFARE FOR
LIFT THE CABINET

INTERNAL PLATE
HSL M12/50
WASHER

162
(6.37)

84
(3.3)

18
(0.71)

18 (0.71)
FLOOR

105 (4.1)

18+1

Fig. 2.29

A30808-X3247-L460-2-7631

Earthquake kit: front view.

59

IMN:TRAU

Fig. 2.30

60

Installation
Transcoding and Rate Adaption Unit

Earthquake kit: part list

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

145 mm (5.7)

220 mm (8.7)

5 mm(0.02)

37,5 mm (1.5)

145 mm (5.7)
5 mm(0.2)

23 mm (0.91)

275 mm (10.8)

Fig. 2.31

Eathquake kit: Internal Plate

Fig. 2.32

Anchor Kit S30861-K126-X

A30808-X3247-L460-2-7631

61

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

1
2
3
4
5

62

Fig. 2.33

Anchoring screw S30861-K126 assembled on M12/50 anchor

Fig. 2.34

Fastening of the HSL M12/50 anchor

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

Fig. 2.35

IMN:TRAU

Rack fixed on the floor

A30808-X3247-L460-2-7631

63

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

2.6.2

Grounding connections for the TRAU-HC Rack


The rack has to be connected to the site specific ground system before to starting the
connection of the power cable

ground bolts
Fig. 2.36

RCAP of the TRAU rack

To grounding the rack use a 16mm2/5AWG or 25mm2/3AWG PVC Ye/Gr copper wire.
The connection should be connected to a ground collector bar on the shortest way.
Mounting instruction of the grounding of the rack (see Fig. 2.36):
Use the nearest ground system on site.
Verify the distances between the connection point of the ground system and the
ground bolts of the rack.
Cut the wire to the required lenght.
Unsheet the wire at the end and crimp a two-hole M6 lug terminal (i.e. Thomas &
Betts type 54852BE blu color for 16mm2/6AWG or 54856BE brown color for
25mm2/3AWG).
Remove exagonal nut, lock washer and contact washer from the ground bolt.
Connect the prepared wire to the ground bolts by a two-hole lug terminal.
Replace the contact washer, lock washer and hexagonal nut.
Tighten the hexagonal nut firmly.

64

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

3 TRAU Power Supply


3.1

Requirements
The equipment shall be connected to a 48V DC SELV source which is electrically
isolated from the AC source and which is reliably connected to earth.
The BSCIV4, as well as TRACV5 and MSCIV2, can be powered by the on board DC/DC
converter and in this case the Power Supply Module (PWRS) is not equipped. The
equipment and the strap configuration of these modules are described in the TRAU
Maintenance Manual.

3.2

Overview
The TRAU rack has to be connected to a 48 VDC Power Distribution Rack (PDR). For
reasons of reliability, two power suppliers at 48V start from PDR, each one provided with
an individual protection. The two couples of conductors at 48V, are directly connected
to the PP0 and PP1 terminals (max conductor cross-section is 10mm2) located on the
Rack Cabling Access Panel (see Fig. 3.1).
When connecting the power supply cables use different colors, like blue and black (or
brown) and take into account that:
-

PDR side:

Rack side:

The BLACK conductor must be connected to the positive polarity


of the secondary power and then to the protective earth collector;
The BLUE conductor must be connected to the negative polarity
of the secondary power.
The BLACK conductor must be connected to terminal "+"
The BLUE conductor must be connected to terminal "- 48V

The power supply units of the TRAU subsystem operate at a voltage of 48 V


(range:38.4-57.6 V). They provide two output voltages +5,3 V and +12,3 V with a tolerance of +/- 2%.
The power supply units are switched off in an irreversible way if the output voltage
exceeds a protection threshold of +15%; if the output voltage drops below a protection
threshold of -5%, the power supply units are switched off and then automatically
restored when the voltage returns above the threshold value.
Two power supply units, copy 0 and copy 1, are provided for the TRAU subrack.
Each power supply is powered in an independent way and each module is powered by
two independent conductors at -48V.

A30808-X3247-L460-2-7631

65

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

3.3

TRAU Rack Power Requirements


Voltage
-48VDC
Max power consumption for subrack/frame 120W for TRAU Standard
110W fro TRAU HC
Max power consumption for TRAU rack
480W fro TRAU Standard
470W for TRAU HC
Power protection on Alarm and Fuse Panel 2 x 10A fuses for TRAU standard
2 x 4A breakers for TRAU HC
Upstream Protection
Breakers or Fuses (see Note 1)
The TRAU subsystem comprises redundant equipment for reasons of reliability. All the
boards of the TRAU system, except TRAC boards, are duplicated and operate in activehot standby configuration.
The copy 0 of the duplicated boards are powered by the power supply copy 0 and the
copy 1 by the power supply copy 1.
The TRAC boards, having a system redundance N+1, receive a double supply voltage,
from power supplier copy 0 and power supplier copy 1, with decoupling diodes.
Note 1: The choise of the breakers/fuses, to mount upstream (in a Power Distribution
Rack) the TRAU rack, and the cross-section of the conductors, to connect between the
Power Distrinution Rack and the TRAU rack, should be based on the typical parameters
of the installation (Power Station, ohmic resistance of the cabling, max voltage drop
accepted on the TRAU power line, etc.). All these data are known to the Service people
and are should be taken in order to have the right coordination of the protections.
In a general way it is possible:
to use an automatic breaker supplied by SIEMENS S.p.A. as an example of its characteristics: Nominal Current=20A; Single pole; Curve C; Type 5SY4 or 5SY6
connect the TRAU rack from a Power Distribution Rack to a distance of 30m (100ft),
using a 10mm2 (7AWG) conductors cross-section

66

For markets requiring UL compliance use UL-Listed automatic breaker

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

3.4

IMN:TRAU

Primary Power Connection


Installation of the DC wires (see Fig. 3.1) is as follows:
Verify the distance between the connection points of the Power Distribution Rack
system and the terminals (on the RCAP) of the power entry of the TRAU rack.
Cut the wires to the required lenght.
TRAU rack side: unsheet the wires about 10mm (0.4)
PDR side: installation dependent
Remove the cover of the Power Line entry on the RCAP.
Insert the wires into holes.
Connect the prepared wire as follows: BLUE wire to Terminal -48V; BLACK
(BROWN) wires to terminal +48V.
Check the correct polarity of the connection from the TRAU rack and the DC output
of the PDR.
Replace the cover of the Power Line entry.

terminals for power line connection


power1
power 0

cover

power 0 power1
power line entry

Fig. 3.1

TRAU-Standard power IN

A30808-X3247-L460-2-7631

67

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

terminals for power line connection


power 0 power 1
cover

power line entry


Fig. 3.2

68

TRAU-HC power IN

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

4 PCM and ALARM connection


This chapter provides the information required for installing the external cables between
the TRAU rack (RCAP Fig. 4.1 and Fig. 4.2) and the infrastructure equipment on site.
The rack cannot function without the following cable connections:
an external -48VDC power supply.
ground connection
Abis interface
optional:
remote alarms interface
Note: For what concerns interconnecting cables and cable assemblies used for external
interconnection between parts of equipment or between components of system, the
following directives apply to all countries that operate according to UL or CB certificate:
For external cables longer than 3,5 m (approximately 10 ft), the following must be
used: Listed CL-2 or Listed Communication Cable (DUZX), type CM or CMR, rated
150 Vac, 75C.
For external cables less than 3,5 m (approximately 10 ft) the following can be used:
Listed or constructed of materials rated minimum FT-1 or VW-1.
Furthermore each detachable external interconnecting non-Listed cable with terminations must be identified by a tag or a non-permanent label reporting the logo
"Siemens AG" and the "cables identifying designation"; marking applied on the cable
at any location or locations.
Two types of cables can be used for the Asub/A interface (PCM lines):
coaxial cables (using an Adapter inserted on SUB-D37 connectors)
balanced cables

Fig. 4.1

TRAU Standard top view : Rach Cabling Access Panel (RCAP)

A30808-X3247-L460-2-7631

69

IMN:TRAU

Fig. 4.2

70

Installation
Transcoding and Rate Adaption Unit

TRAU-HC top view : Rach Cabling Access Panel (RCAP)

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

4.1

IMN:TRAU

Asub/A interface connection of the TRAU Standard rack


The Asub/A connection provides the communication links to the MSC equipment and to
BSC equipment. The connection can be performed either coaxial cable or balanced
cable. The Abis interface is terminated with the Overvoltage Protection (OVPT) that
protects the boards inside the rack against overvoltage (residual voltage <1kV). The
connector (SUB-D37) of the OVPTis mounted on the RCAP of the rack (see Fig. 4.1).

Use only coaxial cable for 75ohm wiring, e.g. INTERCOND 13-RJC19A12R-C1
(12x0.4/1.9) and relative 1.0/2.3 coaxial connector, e.g. COMPEL 350.064.050 or
INTERCOND 11-RK23/4 (single coaxial) and relative 1.0/2.3 coaxial connector, e.g.
COMPEL 350.064.054.
Use onlybalanced cable 100/120ohm, e.g. INTERCOND 13-TDH26P12R-C1
12x2xAWG26 twisted shielded pairs (with drain wire) plus total braided shield and relative SUB-D 37 connector.

The Tab. 4.1 and Tab. 4.2 gives the corresponding of the PCM connection between the
TRAU subrack, the TRAU module and the connector of the RCAP rack.
TRAU Subrack

TRAU Module

RCAP Connector

LINK 3 (GW6)

LINK 4 (LW6)

Tab. 4.1

Left TRAUs PCM lines

TRAU Subrack

TRAU Module

RCAP Connector

LINK 1 (AW6)

LINK 2 (DW3)

Tab. 4.2

A30808-X3247-L460-2-7631

Right TRAUs PCM lines

71

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

The pinning of any PCM connector on the RCAP of the rack is shown in Tab. 4.3. The
wire color is referred to the rack internal cable and is corresponding to the table CEIUNEL 00724.
PIN
CONNECTOR #

WIRE
COLOR

1/20

PCM 0 Input

(from BSC)

BLUE/WHITE

2/21

PCM 0 Output

(to BSC)

ORANGE/WHITE

GROUND

4/22

PCM 1 Input

(from BSC)

GREEN/WHITE

5/23

PCM 1 Output

(to BSC)

BROWN/WHITE

6/24

PCM 0 Input

(from MSC)

GREY/WHITE

7/25

PCM 0 Output

(to MSC)

BLUE/RED

26

GROUND

8/27

PCM 1 Input

(from MSC)

ORANGE/RED

9/28

PCM 1 Output

(to MSC)

GREEN/RED

10

GROUND

11/29

PCM 2 Input

(from MSC)

BROWN/RED

12/30

PCM 2 Output

(to MSC)

GREY/RED

13/31

PCM 3 Input

(from MSC)

BLUE/BLACK

14/32

PCM 3 Output

(to MSC)

ORANGE/BLACK

33

GROUND

SHIELD

15/34

---------------

Not connected

16/35

---------------

Not connected

17

GROUND

SHIELD

18/36

---------------

Not connected

19/37

---------------

Not connected

Tab. 4.3

72

PCM
LINE

SHIELD

SHIELD

SHIELD

PCM Lines connector pinning

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

4.1.1

IMN:TRAU

Coaxial cable connection


For Asub/A cabling 75ohm impedance use coaxial cable and relative 1.0/2.3 coaxial
connector.

To assembly the coaxial cable and relative connector, please refer to the assembling
procedures of the connector Supplier
The Asub/A interface should be connected by a coax Adapter C39117-A343-A48 (see
Fig. 4.3, Fig. 4.4, Tab. 4.4)
TX cables
to BSC side

TX cables
to MSC side

Not Used

1
0

RX cables
to BSC side

Fig. 4.3

A30808-X3247-L460-2-7631

RX cables
to MSC side

Not Used

Coax Adapter mounted on left side (GW6, LW6)

73

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

RX cables
to BSC side

RX cables
to MSC side

Not used

Not Used

Fig. 4.4

TX cables
to MSC side

TX cables
to BSC side

Coax Adapter mounted on right side (AW6, DW6)

Preparation of the coaxial cable TRAU rack side


Cut the cable to the required lenght.
Unsheet the cable as per connector assembling procedures.
Fix a 1.0/2.3 female connector (e.g. ROSENBERGER 34S101-341H3 for the cable
2YCCY 0.4/2.5) for any PCM-Input and Output line at the end to be connected to the
coax Adapter.
Connect the prepared cable to the matching connectors.
Use a torque spanner for 1.0/2.3 connector (35 N/cm).
Signal

Coax connector

Signal

Coax connector

PCM 0 Input

RX 0 (BSC side)

PCM 0 Input

RX 0 (MSC side)

PCM 0 Output

TX 0 (BSC side)

PCM 0 Output

TX 0 (MSC side)

PCM 1 Input

RX 1 (BSC side)

PCM 1 Input

RX 1 (MSC side)

PCM 1 Output

TX 1 (BSC side)

PCM 1 Output

TX 1 (MSC side)

PCM 2 Input

RX 2 (MSC side)

PCM 2 Output

TX 2 (MSC side)

PCM 3 Input

RX 3 (MSC side)

PCM 3 Output

TX 3 (MSC side)

Tab. 4.4

Pinning of the 75ohm PCM on Adapter board

Preparation of the coaxial cable on Installation side


The connector type to be used is a site installation dependet; the choise of the right
connector and possible terminals block to mount on a Main Distribution Frame (MDF) is
Service people care.

74

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

4.1.2

IMN:TRAU

Balanced cable connection


For Asub/A cabling 100/120ohm impedance use a balanced cable twisted shielded pairs
(with drain wire) plus total braided shield and relative SUB-D 37 Male connector.

The outer diameter of the PCM cable must not exceed 15mm (0.59)
The pinning of the PCM signal is reported in the Tab. 4.5
Pin connector

PCM line

1/20

PCM 0 Input (BSC) - RXP0/RXN0

2/21

PCM 0 Output (BSC) - TXP0/TXN0

GND

4/22

PCM 1 Input (BSC) - RXP1/RXN1

5/23

PCM 1 Output (BSC) - TXP1/TXN1

6/24

PCM 0 Input (MSC) - RXP0/RXN0

7/25

PCM 0 Output (MSC) - TXP0/TXN0

26

GND

8/27

PCM 1 Input (MSC) - RXP1/RXN1

9/28

PCM 1 Output (MSC) -TXP1/TXN1

10

GND

11/29

PCM 2 Input (MSC) - RXP2/RXN2

12/30

PCM 2 Output (MSC) - TXP2/TXN2

13/31

PCM 3 Input (MSC) - RXP3/RXN3

14/32

PCM 3 Output (MSC) - TXP3/TXN3

33

GND

15/34

Not connected

16/35

Not connected

17

GND

18/36

Not connected

19/37

Not connected

Tab. 4.5

Pinning of the PCM connector

Preparation of the balanced cable TRAU rack side

A30808-X3247-L460-2-7631

75

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

Cut the cable to the required lenght.


Remove external jacket about 70 mm (2.7)
Free all pairs from respective shields about 55 mm (2.1) (dont cut the drain wire).
Connect the pairs as per Tab. 4.5 (connect to GND the drain wire of the pairs) using
a SUB-D37 Male (e.g. CANNON ZDC37PA191).
Close the connector with a shielded cap with screws M3 (e.g. FCT FMK4GK201+2FRS1Y5-K190-M3). Be careful: the outer shield of the cable must be in
contact with the cable clamping of the said cap.

Preparation of the balanced cable on Installation side


The connector type to be used is a site installation dependet; the choise of the right
connector is Service people care. The following Fig. 4.5 shows a possible termination
on a 6x30 terminal block of the Main Distribution Frame (MDF).
The wires color is the same color of the wires of the internal cable and is corresponding
to the table CEI-UNEL 00724.

Fig. 4.5

76

PCM line connections to MDF (to/from BSC and MSC)

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

4.2
4.2.1

IMN:TRAU

Alarms connection of the TRAU Standard rack


Remote Alarms connection
This connection is used to send the TRAU alarms to a remote location. The connectors
of the TRAU RCAP are associated to the TRAU subrack, TRAU module according the
following Tab. 4.6 and Tab. 4.7.
TRAU Subrack

TRAU Module

RCAP Connector

GW3

LW3

Tab. 4.6

Left TRAUs Remote alarms

TRAU Subrack

TRAU Mdule

RCAP Connector

AW3

DW3

Tab. 4.7

Right TRAUs Remote alarms

For Remote alarms cabling use a 13x2x0.4 (13x2xAWG24/26) twisted pairs plus total
braided shield and relative SUB-D 25 Male connector.

i
i

The outer diameter of the Remote Alarms cable must not exceed 12mm (0.47)
The maximum lenght between the remote alarms connector and the output device
should be calculated taking into account that the nominal loading of each relay contact
is 0,3A/48VDC.
The alarm signals are associated to as many relay contacts to send the following alarm
conditions:
BSC link alarm
Spare alarm
Spare alarm
OR of BS-MS-INT
Global alarm: Major
Global alarm: Minor
Global alarm: Critical
OR of MJ-MN-CR

A30808-X3247-L460-2-7631

(BS)
(MS)
(INT)
(OR2)
(MJ)
(MN)
(CR)
(OR1)

77

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

Tab. 4.8 shows the layout of the pins of the connector AW3/DW3/GW3/LW3, situated
on the RCAP.The wire color is referred to the internal cable and is corresponding to the
table CEI-UNEL 00724.
Alarm Type
BSC LINK ALARM

SPARE ALARM

SPARE ALARM

OR OF BS-MSINT ALARMS

Signal Name

Pin Number

Wire Color

BS-BK

01

WHT

BS-CM

02

BLU

BS-MK

03

WHT

MS-BK

04

ORN

MS-CM

05

WHT

MS-MK

06

GRN

INT-BK

07

WHT

INT-CM

08

BRN

INT-MK

09

WHT

OR2-BK

10

GRY

OR2-CM

11

RED

OR2-MK

12

BLU

13
GLOBAL ALARM:
MAJOR
GLOBAL ALARM:
MINOR
GLOBAL ALARM:
CRITICAL
OR OF MJ_MN_CR
ALARMS

Tab. 4.8

78

MJ-BK

14

RED

MJ-CM

15

ORN

MJ-MK

16

RED

MN-BK

17

GRN

MN-CM

18

RED

MN-MK

19

BRN

CR-BK

20

RED

CR-CM

21

GRY

CR-MK

22

BLK

OR1-BK

23

BLU

OR1-CM

24

BLK

OR1-MK

25

ORN

Layout of the pins of connector AW3/DW3/GW3/LW3

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

In general, the condition of each type of alarm is notified through a relay contact in the
following way:
no alarm:

contact RELAY-COMMON/RELAY-BREAK
contact RELAY-COMMON/RELAY-MAKE

closed
open

alarm state:

contact RELAY-COMMON/RELAY-BREAK
contact RELAY-COMMON/RELAY-MAKE

open
closed

Where RELAY-COMMON indicates the common point of the contact (CM), RELAYBREAK indicates the break point (no alarm) of the contact (BK), and RELAY-MAKE indicates the make point (alarm) of the contact (MK).
Preparation of the Remote Alarm cable TRAU rack side
Cut the cable to the required lenght.
Remove external jacket about 70 mm (2.7)
Cut the outer shield leaving about 10mm (0.4) to permit its contact with the
campling of the cap.
Connect the pairs as per Tab. 4.9 (the wire color is referred to the internal cable and
is corresponding to the table CEI-UNEL 00724) using a SUB-D25 Male (e.g.
CANNON ZDB25PA191).
Close the connector with a shielded cap with screws M3 (e.g. FCT FMK3GK201+2FRS1Y5-K190-M3). Be careful: the outer shield of the cable must be in
contact with the cable clamping of the said cap.

Pair Color

Signal

Connector Pin

WHT/BLU

BSBK/MJBK

1/14

WHT/ORG

BSCM/MJCM

2/15

WHT/GRN

BSMK/MJMK

3/16

WHT/BRN

MSBK/MNBK

4/17

WHT/GRY

MSCM/MNCM

5/18

RED/BLU

MSMK/MNMK

6/19

WHT/GRY

INTBK/CRBK

7/20

RED/GRN

INTCM/CRCM

8/21

RED/BRN

INTMK/CRMK

9/22

RED/GRY

OR2BK/OR1BK

10/23

BLK/BLU

OR2CM/OR1CM

11/24

BLK/ORG

OR2MK/OR1MK

12/25

BLK/GRN

----------------

Not connected

Tab. 4.9

A30808-X3247-L460-2-7631

Pinning of the Remote Alarm cable

79

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

Preparation of the Remote Alarm cable on Installation side


The connector type to be used is a site installation dependet; the choise of the right
connector is Service people care. The following Fig. 4.6 shows a possible termination
on a 6x30 terminal block of the Main Distribution Frame (MDF).
The wires color is the same color of the wires of the internal cable and is corresponding
to the table CEI-UNEL 00724.
The left part (*) of the MDF block in Fig. 4.6 can be used for alarms from BSC, when the
BSC and the TRAU racks are co-located.
All these alarm signals can be connected to output devices such as lamps, bells, horns,
taking into account that the nominal loading of each relay contact is 0,3A/48VDC; only
security voltages (60VDC max or 42,4Vpk max) can be connected to these circuits.

Fig. 4.6

80

The cable shield must be grounded at Installation (e.g. MDF) side

Remote Alarm connection to terminal block

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

4.2.2

IMN:TRAU

Internal Alarms connection (W14, W15 connectors)


The internal alarms are connected between the connectors W14, W15 of the TRAU
subracks and the connector PM2 of the TRAU Rack Cabling Access Panel. The
Tab. 4.10 shows the pinning of the connectors W14 and W15.
Pin

signal name

description

BSB

BSC link alarm

MSB

not used

INTB

Open door alarm

4-9

CM2,CM1

- 48 V

not used

MJB

major alarm

CRB

critical alarm

MNB

minor alarm

10 - 11 GND
Tab. 4.10

ground

Pin description of the connectors W14 and W15

In the last lower subrack on the connector W14 takes place the Open door sensor cable.
The two wires of the sensor are connected to pin number 3 and to ground (by the cableclamp of the shielded cap).
During an upgrade of a subrack needs to:
disconnect the cable connected to connector W14 on the last subrack equipped.
mount the new subrack.
reconnect the cable disconneted from connector W14 on the new subrack.
connect the cable V7440-A32-R32 (item of the new subrack) between the connector
W15 of the new subrack and the connector W14 of the last equipped subrack.

For references see Fig. 5.4 and Fig. 5.5 of the Chap. 5.

A30808-X3247-L460-2-7631

81

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

4.3

Asub/A interface connection of the TRAU-HC rack


The Asub/A connection provides the communication links to the MSC equipment and to
BSC equipment. The connection can be performed either coaxial cable or balanced
cable. The Asub/A interface is terminated with the Overvoltage Protection (OVPT) that
protects the boards inside the rack against overvoltage (residual voltage <1kV). The
connector (SUB-D37) of the OVPTis mounted on the RCAP of the rack (see Fig. 4.1).

Use only coaxial cable for 75ohm wiring, e.g. INTERCOND 13-RJC19A12R-C1
(12x0.4/1.9) and relative 1.0/2.3 coaxial connector, e.g. COMPEL 350.064.050 or
INTERCOND 11-RK23/4 (single coaxial) and relative 1.0/2.3 coaxial connector, e.g.
COMPEL 350.064.054.
Use onlybalanced cable 100/120ohm, e.g. INTERCOND 13-TDH26P12R-C1
(12x2x0.4) 12x2xAWG26 twisted shielded pairs (with drain wire) plus total braided
shield and relative SUB-D 37 connector.

The Tab. 4.11 and Tab. 4.12 gives the corresponding of the PCM connection between
the TRAU frame, the TRAU module and the connector of the RCAP rack.
TRAU Frame

TRAU Module

LINK 0 (PCM 0)

LINK 2 (PCM 2)

LINK 4 (PCM 4)

LINK 6 (PCM 6)

Tab. 4.11

Left TRAUs PCM lines

TRAU Frame

TRAU Module

RCAP Connector

LINK 1 (PCM 1)

LINK 3 (PCM 3)

LINK 5 (PVM 5)

LINK 7 (PCM 7)

Tab. 4.12

82

RCAP Connector

Right TRAUs PCM lines

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

The pinning of any PCM connector on the RCAP of the rack is shown in Tab. 4.3.
PIN
CONNECTOR #

PCM
LINE

1/20

PCM 0 Input

(from BSC)

2/21

PCM 0 Output

(to BSC)

GROUND

4/22

PCM 1 Input

(from BSC)

5/23

PCM 1 Output

(to BSC)

6/24

PCM 0 Input

(from MSC)

7/25

PCM 0 Output

(to MSC)

26

GROUND

8/27

PCM 1 Input

(from MSC)

9/28

PCM 1 Output

(to MSC)

10

GROUND

11/29

PCM 2 Input

(from MSC)

12/30

PCM 2 Output

(to MSC)

13/31

PCM 3 Input

(from MSC)

14/32

PCM 3 Output

(to MSC)

33

GROUND

15/34

---------------

16/35

---------------

17

GROUND

18/36

---------------

19/37

---------------

Tab. 4.13

A30808-X3247-L460-2-7631

PCM Lines connector pinning

83

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

4.3.1

Coaxial cable connection


For Asub/A cabling 75ohm impedance use coaxial cable and relative 1.0/2.3 coaxial
connector.

To assembly the coaxial cable and relative connector, please refer to the assembling
procedures of the connector Supplier
The Asub/A interface should be connected by a coax Adapter S30861-Q472-X (see
Fig. 4.7, Tab. 4.14)
TX cables
to BSC side

TX cables
to MSC side

1
0

RX cables
to BSC side

Fig. 4.7

RX cables
to MSC side

Coax Adapter mounted on left and right side

Preparation of the coaxial cable TRAU rack side


Cut the cable to the required lenght.
Unsheet the cable as per connector assembling procedures.
Fix a 1.0/2.3 female connector (e.g. ROSENBERGER 34S101-341H3 for the cable
2YCCY 0.4/2.5) for any PCM-Input and Output line at the end to be connected to the
coax Adapter.
Connect the prepared cable to the matching connectors.
Use a torque spanner for 1.0/2.3 connector (35 N/cm).

84

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Signal

Coax connector

Signal

Coax connector

PCM 0 Input

RX 0 (BSC side)

PCM 0 Input

RX 0 (MSC side)

PCM 0 Output

TX 0 (BSC side)

PCM 0 Output

TX 0 (MSC side)

PCM 1 Input

RX 1 (BSC side)

PCM 1 Input

RX 1 (MSC side)

PCM 1 Output

TX 1 (BSC side)

PCM 1 Output

TX 1 (MSC side)

PCM 2 Input

RX 2 (MSC side)

PCM 2 Output

TX 2 (MSC side)

PCM 3 Input

RX 3 (MSC side)

PCM 3 Output

TX 3 (MSC side)

Tab. 4.14

Pinning of the 75ohm PCM on Adapter board

Preparation of the coaxial cable on Installation side


The connector type to be used is a site installation dependet; the choise of the right
connector and possible terminals block to mount on a Main Distribution Frame (MDF) is
Service people care.

A30808-X3247-L460-2-7631

85

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

4.3.2

Balanced cable connection


For Asub/A cabling 100/120ohm impedance use a balanced twisted shielded pairs (with
drain wire) plus total braided shield and relative SUB-D 37 Male connector.

The outer diameter of the PCM cable must not exceed 15mm (0.59)
The pinning of the PCM signal is reported in the Tab. 4.15
Pin connector
1/20

PCM 0 Input (BSC) - RXP0/RXN0

2/21

PCM 0 Output (BSC) - TXP0/TXN0

GND

4/22

PCM 1 Input (BSC) - RXP1/RXN1

5/23

PCM 1 Output (BSC) - TXP1/TXN1

6/24

PCM 0 Input (MSC) - RXP0/RXN0

7/25

PCM 0 Output (MSC) - TXP0/TXN0

26

GND

8/27

PCM 1 Input (MSC) - RXP1/RXN1

9/28

PCM 1 Output (MSC) -TXP1/TXN1

10

GND

11/29

PCM 2 Input (MSC) - RXP2/RXN2

12/30

PCM 2 Output (MSC) - TXP2/TXN2

13/31

PCM 3 Input (MSC) - RXP3/RXN3

14/32

PCM 3 Output (MSC) - TXP3/TXN3

33

GND

15/34

Not connected

16/35

Not connected

17

GND

18/36

Not connected

19/37

Not connected

Tab. 4.15

86

PCM line

Pinning of the PCM connector

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Preparation of the balanced cable TRAU rack side


Cut the cable to the required lenght.
Remove external jacket about 70 mm (2.7)
Free all pairs from respective shields about 55 mm (2.1) (dont cut the drain wire).
Connect the pairs as per Tab. 4.15 (connect to GND the drain wire of the pairs)
using a SUB-D37 Male (e.g. CANNON ZDC37PA191).
Close the connector with a shielded cap with screws M3 (e.g. FCT FMK4GK201+2FRS1Y5-K190-M3). Be careful: the outer shield of the cable must be in
contact with the cable clamping of the said cap.
Preparation of the balanced cable on Installation side
The connector type to be used is a site installation dependet; the choise of the right
connector and the arrangement on a possible terminal block to mount on a Main Distributor Frame (MDF) is Service people care.

A30808-X3247-L460-2-7631

87

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

4.4
4.4.1

Alarms connection of the TRAU-HC rack


Remote Alarms connection
This connection is used to send the TRAU alarms to a remote location. The connectors
of the TRAU RCAP are associated to the TRAU frame, TRAU module according the
following Tab. 4.16 and Tab. 4.17.
TRAU Frame

TRAU Module

RCAP Connector

AW0

AW2

AW4

AW6

Tab. 4.16

Left TRAUs Remote alarms

TRAU Frame

TRAU Module

RCAP Connector

AW1

AW3

AW5

AW7

Tab. 4.17

Right TRAUs Remote alarms

For Remote alarms cabling use a 2x13x0.4 (2x13xAWG24/26) twisted pairs plus total
braided shield and relative SUB-D 25 Male connector.

i
i

The outer diameter of the PCM cable must not exceed 12mm (0.47)
The maximum lenght between the remote alarms connector and the output device
should be calculated taking into account that the nominal loading of each relay contact
is 0,3A/48VDC.
The alarm signals are associated to as many relay contacts to send the following alarm
conditions:
BSC link alarm
Spare alarm
Spare alarm
OR of BS-MS-INT
Global alarm: Major
Global alarm: Minor
Global alarm: Critical
OR of MJ-MN-CR

88

(BS)
(MS)
(INT)
(OR2)
(MJ)
(MN)
(CR)
(OR1)

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Tab. 4.18 shows the layout of the pins of the connector AW0-AW7, situated on the
RCAP.
Alarm Type
BSC LINK ALARM

SPARE ALARM

SPARE ALARM

OR OF BS-MSINT ALARMS

Signal Name

Pin Number

BS-BK

01

BS-CM

02

BS-MK

03

MS-BK

04

MS-CM

05

MS-MK

06

INT-BK

07

INT-CM

08

INT-MK

09

OR2-BK

10

OR2-CM

11

OR2-MK

12
13

GLOBAL ALARM:
MAJOR
GLOBAL ALARM:
MINOR
GLOBAL ALARM:
CRITICAL
OR OF MJ_MN_CR
ALARMS

Tab. 4.18

A30808-X3247-L460-2-7631

MJ-BK

14

MJ-CM

15

MJ-MK

16

MN-BK

17

MN-CM

18

MN-MK

19

CR-BK

20

CR-CM

21

CR-MK

22

OR1-BK

23

OR1-CM

24

OR1-MK

25

Layout of the pins of connector AW0-AW7

89

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

In general, the condition of each type of alarm is notified through a relay contact in the
following way:
no alarm:

contact RELAY-COMMON/RELAY-BREAK
contact RELAY-COMMON/RELAY-MAKE

closed
open

alarm state:

contact RELAY-COMMON/RELAY-BREAK
contact RELAY-COMMON/RELAY-MAKE

open
closed

Where RELAY-COMMON indicates the common point of the contact (CM), RELAYBREAK indicates the break point (no alarm) of the contact (BK), and RELAY-MAKE indicates the make point (alarm) of the contact (MK).
Preparation of the Remote Alarm cable TRAU rack side
Cut the cable to the required lenght.
Remove external jacket about 70 mm (2.7)
Cut the outer shield leaving about 10mm (0.4) to permit its contact with the
campling of the cap.
Connect the pairs as per Tab. 4.19 (the wire color is referred to the internal cable
and is corresponding to the table CEI-UNEL 00724) using a SUB-D25 Male (e.g.
CANNON ZDB25PA191).
Close the connector with a shielded cap with screws M3 (e.g. FCT FMK3GK201+2FRS1Y5-K190-M3). Be careful: the outer shield of the cable must be in
contact with the cable clamping of the said cap.

Pair Color

Connector Pin

WHT/BLU

BSBK/MJBK

1/14

WHT/ORG

BSCM/MJCM

2/15

WHT/GRN

BSMK/MJMK

3/16

WHT/BRN

MSBK/MNBK

4/17

WHT/GRY

MSCM/MNCM

5/18

RED/BLU

MSMK/MNMK

6/19

WHT/GRY

INTBK/CRBK

7/20

RED/GRN

INTCM/CRCM

8/21

RED/BRN

INTMK/CRMK

9/22

RED/GRY

OR2BK/OR1BK

10/23

BLK/BLU

OR2CM/OR1CM

11/24

BLK/ORG

OR2MK/OR1MK

12/25

BLK/GRN

----------------

Not connected

Tab. 4.19

90

Signal

Pinning of the Remote Alarm cable

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Preparation of the Remote Alarm cable on Installation side


The connector type to be used is a site installation dependet; the choise of the right
connector and the arrangement on a possible terminal block on a Main Distributor
Frame (MDF) is Service people care.
All these alarm signals can be connected to output devices such as lamps, bells, horns,
taking into account that the nominal loading of each relay contact is 0,3A/48VDC; only
security voltages (60VDC max or 42,4Vpk max) can be connected to these circuits.

The cable shield must be grounded at Installation (e.g. MDF) side

A30808-X3247-L460-2-7631

91

IMN:TRAU

92

Installation
Transcoding and Rate Adaption Unit

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

5 System Cabling of the TRAU rack


This chapter reports an overview of the internal cabling of the TRAU rack

5.1

TRAU Standard rack


The following Tab. 5.1 shows the function and the type of connector positioned on the
Rack Cabling Access Panel .

Connector position

Type

Function

PP0 PP1

TERMINALS

Power supply Connected to PDR

AW3

SUB D 25 Female

TRAU 0 alarms to remote location

DW3

SUB D 25 Female

TRAU 1 alarms to remote location

GW3

SUB D 25 Female

TRAU 2 alarms to remote location

LW3

SUB D 25 Female

TRAU 3 alarms to remote location

PM2

SUB D 9 Female

Rack Lamp alarms (connected together)

AW6

SUB D 37 Female

PCM line connections to BSC and MSC for


TRAU-0

DW6

SUB D 37 Female

PCM line connections to BSC and MSC for


TRAU-1

GW6

SUB D 37 Female

PCM line connections to BSC and MSC for


TRAU-2

LW6

SUB D 37 Female

PCM digital connections to BSC and MSC for


TRAU-3

Tab. 5.1

Connectors position, type and function

A30808-X3247-L460-2-7631

93

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

The Fig. 5.1 shows the position of the connectors on the RCAP of the rack

Fig. 5.1

94

TRAU Rack - Top view

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

The Fig. 5.2 shows a side view of the rack with the subrack power supply connection
(bus-bar) and the connection of the cables on the RCAP

Rack right top side

Rack left side


Fig. 5.2

Rack left side and rack right top side

A30808-X3247-L460-2-7631

95

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

The Fig. 5.3 shows a front view of the rack with the subrack power supply connection
(bus-bar and filter) and ground connection.

Fig. 5.3

96

Power and ground cables distribution

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

The Fig. 5.4 shows the list of the cabling of the TRAU rack.

Fig. 5.4

Interconnections list

A30808-X3247-L460-2-7631

97

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

Notes on interconnection list


3 - This cable is a part of the F:TRAUE (Expansion frame). Here listed for mounting
reference only.
4 - this cable is fitted by rack supplier. Here listed for mounting reference only.
5 - Side 1 of the Open sensor cable (57) has to be terminated to W14 connector of TRAU
module equipped in lower position; secure cable along vertical duct using provided
cable ties (ref. 58 and 59).
The Fig. 5.5 shows the connectors of the Fuse Pane in open position.

48VA

Rem-Alm
to TOP(AW3)
to Fuse Panel
(J1)
(J2)

to top(AW6)
PCM lines

from Door-Open sensor


to W14 upper subrack
or to PM2 on RCAP

48VB

from PM3
temp.
sensors

Fig. 5.5

98

TRAU Sub-rack: front view (fuse panel shown in open position)

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

The Fig. 5.5 shows the cabling of the Fuse Panel.

Fig. 5.6

TRAU sub-rack: Fuse Panel Mounting and Cabling

Mounting
Reference

From
File

Connector

To
File

Connector

55

W5

Fuse Pan. J1

56

W4

Fuse Pan. J2

58

W1

Fuse Pan. J4

58

W16

Fuse Pan. J5

60

GNDF

Fuse Pan. GNDF

Tab. 5.2

A30808-X3247-L460-2-7631

Table of the Fuse Panel cabling

99

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

5.2

TRAU-HC rack
This chapter reports an overview of the internal cabling of the TRAU rack.
The chapter is developped in the following four blocks:
1.
2.
3.
4.

5.2.1

Adapter Board cabling


DC-Panel cabling
PCM lines cabling
Photographs of the wiring assembly

Adapter Board cabling (M:ADAPTBTV1)


Adapter Board card (S30861-Q476-X) takes place on the top of the rack (see Fig. 5.7,
Fig. 5.8 and Fig. 5.9) and has the following functions :

48 V power supply from EMI-Filter to all DC-Panel,Lamp Panel,Fan unit and


Temperature Monitor
Thermal alarms from Temperature Monitor
Fan alarm from Fan unit
Open door alarm from open door sensor
Board alarms from all TRAU cards to Lamp Panel

Fig. 5.7

100

Adapter Board layout

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

Fig. 5.8

IMN:TRAU

Adapter Board layout

A30808-X3247-L460-2-7631

101

IMN:TRAU

Fig. 5.9

102

Installation
Transcoding and Rate Adaption Unit

Adapater Board system block diagram

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

LIST OF THE CONNECTORS AND CABLES OF THE ADAPTER BOARD (refer Fig. 5.9).

X25 connector
The X25 connector is used to send board alarms and to power Lamp Panel at the top of the rack
(PM2 connector).
Connector code is D Subminiature right-angle solder termination 9p.
pin

Signal

Description

N.C.

N.C.

N.C

VAB

+ 48 V

-VAB

- 48 V

MJ

Major alarm

MN

Minor alarm

Critical Critical alarm

-VAB

Tab. 5.3

not connected

- 48 V

X25 connector of the Adapter Board

RCAP-LAMP PANEL CABLE

A30808-X3247-L460-2-7631

103

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

X23-X24 Connectors
The faston X23-X24 are used to receive open door alarm that is a contact from a sensor.
The type is a faston pressfit.
pin

Signal

Description

X23

OPEND

Open door

X24

GND

ground

Tab. 5.4

X23,X24 connectors of the Adapter Board

OPEN DOOR SENSOR CABLE

104

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

X27 connector
The X27 connector is used to receive fan alarm from FAN unit.
The type is D Subminiature pressfit termination 15p.
pin

Signal

N.C.

N.C.

N.C

GND

TRAU_FANAL

N.C.

N.C.

N.C.

N.C.

10

N.C.

11

GND

12

N.C.

13

N.C.

14

N.C.

15

N.C.

Tab. 5.5

Description

Fan alarm

X27 connector of the Adapter Board

FAN UNIT ALARM CABLE

A30808-X3247-L460-2-7631

105

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

X26 connector
The X26 connector is used for DAISY CHAIN that connects the sub-racks with the
following signals:
TRAU alarms (MJ,MN,MCR,EXT) that are in logical OR between the sub-racks.
POWER OFF A and B alarms.
OPEND alarm.
FAN alarm,.
The type is 20pin, 2x10 pressfit termination.
Daisy chain is constituited with a crimped flat cable.
pin

Description

TEST_PWOFFA Test thermal alarm A

PWOFFA

TEST_PWOFFB Test thermal alarm B

PWOFFB

Thermal alarm B

- VAB

- 48 V

OPEND

Open door alarm

MN

Minor alarm

GND

N.C.

10

FAN

11

N.C.

12

MN

13

N.C.

14

MJ

15

N.C.

16

MCR

17

N.C.

18

EXT

19

N.C.

20

GND

Tab. 5.6

106

Signal

Thermal alarm A

Fan alarm

Minor alarm

Major alarm

Critical alarm

External BSCI alarm

X26 connector of the Adapter Board

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

DAISY CHAIN CABLE

(169)

A30808-X3247-L460-2-7631

107

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

X5-X6 connector
The faston X5-X6 are used to feed Fan unit.
The type is a faston pressfit.
pin5

Signal

Description

X5

+ VAB

+ 48 V

X6

- VAB

- 48 V

Tab. 5.7

X5,X6 connectors of the Adapter Board

DC-FAN UNIT CABLE

X1-X2 and X3-X4 connectors


The faston X1-X2 and X3-X4 are used to receive power supply from EMI-Filter.
The type is a faston pressfit.
pin

Signal

Description

48A

+ 48 V battery A

- 48A

- 48 V battery A

48B

+ 48 V battery B

- 48B

- 48 V battery B

Tab. 5.8

X1,X2 and X3,X4 connectors of the Adapter Board

DC-MAIN CABLES

108

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

X7 to X22 connector
The faston X7 to X22 are used to feed TRAU frames.
The type is a faston pressfit.
Ref.

frame

Signal

X7

+ 48 A

X8

- 48 A

X9

+ 48 B

X10

- 48 B

X11

+ 48 A

X12

- 48 A

X13

+ 48 B

X14

- 48 B

X15

+ 48 A

X16

- 48 A

X17

+ 48 B

X18

- 48 B

X19

+ 48 A

X20

- 48 A

X21

+ 48 B

X22

- 48 B

Tab. 5.9

X7 to X22 connectors of the Adapter Board

DC-MAIN TO DC-PANEL CABLES

A30808-X3247-L460-2-7631

109

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

5.2.2

Front-Panel Board cabling

Fig. 5.10

110

daisy chain

daisy chain

-48A

to/from backpanel
to backpanel
to top rack
-48A -48B

DC PANEL 0

-48B

daisy chain

ADAPTER-BOARD

daisy chain

daisy chain

The Front Panel Board (S50201-Q54-X) is positioned in the DC-Panel in a TRAU subrack that includes two TRAU unit and provides the following functions:
to display the TRAU alarms (4 leds for each TRAU)
to connect the TRAU via LMT connector
to exchange alarms to other units via DAISY CHAIN
to remote the alarms on the top rack connectors (AW)
to switch off the 48 V power supply in the frame by two 4A magnetothermic breakers.

DC-PANEL system block diagram.

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

LIST OF THE CONNECTORS AND CABLES OF THE FRONT-PANEL BOARD (refer


Fig. 5.10).
X13-X14 connectors
The X13-X14 connectors are used to send alarms (REM-AL-L/R) of the TRAULeft/Right to the top rack (AW connectors) :
The type is 26pin, 2x13 pressfit termination.
pin

Signal

BSBK_L/R

BSCM_L/R

BSMK_L/R

N.C.

N.C.

N.C.

N.C.

N.C.

N.C.

10

OR2BK_L/R

11

OR2CM_L/R

12

OR2MK_L/R

13

N.C.

14

MJBK_L/R

15

MJCM_L/R

16

MJMK_L/R

17

MNBK-L/R

18

MNCM_L/R

19

MNMK_L/R

20

CRBK_L/R

21

CRCM_L/R

22

CRMK_L/R

23

OR1BK_L/R

24

OR1CM_L/R

25

OR1MK_L/R

Tab. 5.10

A30808-X3247-L460-2-7631

Description
BSC link alarm

OR alarm pin 1 to 9

Global alarm : Major

Global alarm : Minor

Global alarm : Critical

OR alarm pin 14 to 22

X13,X14 connectors

111

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

REMOTE ALARM CABLE (from DC-Panel: Rem-AL_L/R to RCAP:AW0/(AW7)

Fig. 5.11

112

Remote Alarms cabling

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

X15-X16 connectors
The LMT connectors X15-X16 are used to have a serial interface of both the TRAU_L/R.
The type is D Subminiature straight pressfit termination 15p.
Refer to V11 interface for the signals description.
pin

Signal

pin

Signal

T(B)

T(A)

10

C(B)

C(A)

11

R(B)

R(A)

12

I(B)

I(A)

13

S(B)

S(A)

14

B(B)

B(A)

15

N.C.

Tab. 5.11

X15,X16 connectors of the Front Panel Board

X18 connector
The X18 connector is the DA-CH (DAISY CHAIN) connector.
The pin description is the same as in the Adapter Board (see Tab. 5.6)

A30808-X3247-L460-2-7631

113

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

X17 connector
The X17 connector is the LMT+ALM_L/R used for the following signals:
Two LMT serial interfaces for the Trau Left and Right side.
Alarm from Backplane : major,minor,critical,external.
Alarms to Backplane : power-off,open-door,fan.
Power signal from Backplane : +5VA and +5VB.
The type is 64pin, 2x32 pressfit termination.
Description

pin

pin

GND

GND

T(A)

T(B)

C(A)

C(B)

R(A)

R(B)

I(A)

10

I(B)

S(A)

11

12

S(B)

B(A)

13

14

B(B)

15

16

GND

17

18

GND

PWOFF
A0

19

20

PWOFF
B1

N.C.

21

22

N.C.

Open door alarm to BSCI-0 of


TRAU left

OPEND0 23
_L

24

OPEND1 Open door alarm to BSCI-1


_L
of TRAU left

Fan alarm to BSCI_0 of TRAU


right

FANAL0
_R

25

26

FANAL1
_R

N.C.

27

28

N.C.

Minor alarm TRAU_Right

MN_R

29

30

N.C.

Major alarm TRAU_Right

MJ_R

31

32

MCR_R

GND

33

34

GND

5VA TRAU_Left

+5VA_L

35

36

+5VB_L

5VB TRAU_Left

Minor alarm TRAU_Left

MJ_L

37

38

EXT_L

External alarm Trau_Left

Major alarm TRAU_Left

MN_L

39

40

EXT_R

External alarm Trau_Right

MCR_L

41

42

GND

+5VA_R

43

44

+5VB_R

GND

45

46

N.C.

T(A)

47

48

T(B)

C(A)

49

50

C(B)

V11 interface for LMT-TRAU-Left


side

Thermal alarm to BSC_0

5VA TRAU_Right

V11 interface for LMT-TRAURight side

Tab. 5.12

114

Signal

Signal

Description

V11 interface for LMT-TRAULeft side

Thermal alarm to BSC_1

Fan alarm to BSCI_1 of


TRAU right

Critical alarm TRAU_Right

5VB TRAU_Right

V11 interface for LMT-TRAURight side

X17 connectos of the Front Panel Board

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Description

Tab. 5.12

Signal

pin

pin

Signal

R(A)

51

52

R(B)

I(A)

53

54

I(B)

S(A)

55

56

S(B)

B(A)

57

58

B(B)

59

60

N.C.

61

62

N.C.

GND

63

64

GND

Description

X17 connectos of the Front Panel Board

LMT+ALM CABLE

X1/X12 connectors (48 V power cabling)


Ref

Signal

X5

- 48A_UP

X6

+ 48A_UP

X11

- 48B_UP

X12

+ 48B_UP

X10

- 48B_UP

X4

- 48A_UP

X7

- 48B

X1

- 48A

X8

- 48B

X9

+ 48B

X2

- 48A

X3

+ 48A

X20

GND

Tab. 5.13

A30808-X3247-L460-2-7631

Description
main power A from Adapter board

main power B from Adapter board

to breakers

from breakers

PWR-B to Backplane

PWR-A to Backplane

X1/X12 connectors of the Front Panel Board

115

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

DC-CABLES TO BACKPLANE

DC-CABLES TO BREAKERS

GROUND CABLES

116

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

X19 connector
The X19 connector fits the new version TRAUV2 sub-rack (S30861-B248-X) on the
TRAU-Standard rack (S30861-C21-X).
For the pin description see the X7 connector in the Extra Adapter Board (Chap. 5.3).

A30808-X3247-L460-2-7631

117

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

5.2.3

Internal PCM lines


From the Backplane of each FRAME thera are two connectors to connect the PCM lines
of the TRAU_L/R (left and right) towards and from BSC/MSC.

PCM connector of the TRAU_L

Fig. 5.12

118

PCM connector of the TRAU_R

PCM lines connectors in DC-Panel

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

PCM LINES CABLES

pin

signal

stream

1-20

PCM 0 input

from BSC

2-21

PCM 0 output

to BSC

GND

4-22

PCM 1 input

from BSC

5-23

PCM 1 output

to BSC

6-24

PCM 0 input

from MSC

7-25

PCM 0 output

to MSC

26

GND

8-27

PCM 1 input

from MSC

9-28

PCM 1 output

to MSC

10

GND

11-29

PCM 2input

from MSC

12-30

PCM 2 output

to MSC

13-31

PCM 3 input

from MSC

14-32

PCM 3 output

to MSC

33

GND

15-34

N.C.

16-35

N.C.

17

GND

18-36

N.C.

19-37

N.C.

Tab. 5.14

A30808-X3247-L460-2-7631

PCM lines connector in the Frame backpanel and in the RCAP

119

IMN:TRAU

Fig. 5.13

120

Installation
Transcoding and Rate Adaption Unit

PCM lines wirings

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

5.2.4

IMN:TRAU

Photographs of the wiring assembly


This chapter reports the cable routing tables and the photographs of the rack wiring.

Fig. 5.14

Table of the rack wiring

A30808-X3247-L460-2-7631

121

IMN:TRAU

Fig. 5.15

122

Installation
Transcoding and Rate Adaption Unit

Rack wiring 1

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

Fig. 5.16

IMN:TRAU

Rack wiring 2

A30808-X3247-L460-2-7631

123

Fig. 5.17

124

FRAME 3

FRAME 2

FRAME 1

Installation
Transcoding and Rate Adaption Unit

FRAME 0

IMN:TRAU

Rack wiring 3

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

14/0

TRAU FRAME 0

IMN:TRAU

14/0

4/0A
4/0B

12/0
12/0
18

14/1

TRAU FRAME 1

14/1

4/1A
4/1B

12/1
12/1
18
14/2

14/2

TRAU FRAME 2
4/2A
4/2B
12/2
12/2
18
14/3

14/3

TRAU FRAME 3
4/3A
4/3B
12/3
12/3
18
Fig. 5.18

Rack wiring 4

A30808-X3247-L460-2-7631

125

IMN:TRAU

Table of the frame wiring

126

GROUND CABLE

POWER CABLES

SIGNAL CABLE

Fig. 5.19

Installation
Transcoding and Rate Adaption Unit

A30808-X3247-L460-2-7631

Frame wiring 1

Fig. 5.21

Frame wiring 2

PCM CABLES

DAISY CHAIN CABLES

Fig. 5.20

A30808-X3247-L460-2-7631

POWER CABLES

IMN:TRAU

REMOTE ALARM CABLES

Installation
Transcoding and Rate Adaption Unit

127

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

5.3

TRAU HC Frame to mount in a TRAU Standard rack


It is possible to mount a TRAU HC Frame (S30861-B248-X) in a TRAU Standard rack
(S30861-C21-X) by an Extra Adapter Board (S30861-U725-X).

5.3.1

Extra Adapter Board


The Extra Adapter Board is mounted on the Front-Panel-Board (S50201-Q54-X) in the
DC-Panel.
It provides the following function:
to receive - 48VA and - 48VB from the bar of the rack and to power supply the Frame
to distribute the Power-off alarm to the Frame
to interface the signalling with the other TRAU Frames via DAISY-CHAIN.

LIST OF THE CONNECTORS AND CABLES


X3-X4 connectors
The X3-X4 are used to receive Power-off alarms from the top of the rack.
The type is D subminiature pressfit termination 9 p.
pin
1

PWOFFA Thermal alarm A

N.C.

PWOFFB Thermal alarm B

4,5,6,7,8,9

N.C.

Tab. 5.15

128

signal

description

X3,X4 connectors of the Extra Adapter Board

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

X5-X6 connectors
The X5-X6 are used to receive and to distribuite the Daisy-Chain alarms and feed the
power to the top board (RCAP).
The type is D subminiature pressfit termination 9 p.
pin

signal

description

N.C

GND

OPEND

Open-door alarm

+ VAB

+ 48 V

5-9

- VAB

- 48 V

MJ

Major alarm

MN

Minor alarm

MCR

Critical alarm

Tab. 5.16

X5,X6 connectors of the Extra Adapter Board

X1-X2 connectors
The X1-X2 are used to receive Power supply (X1 from A and X2 from B source).
The type is power D subminiature pressfit termination 3 p.
pin

signal

- VA/B

GND

+ VA/B

Tab. 5.17

A30808-X3247-L460-2-7631

description
- 48 V

+ 48 V

X1,X2 connectors of the Extra Adapter Board

129

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

X7 connectors
The X7 is used to interface Extra Adapter board to the Frame via front Panel board. .
The type is SMT solder terrmination 36 p.
description

pin

pin

signal

description

+48 VA

+ VA

+ VA

+48 VA

+48 VA

+ VA

+ VA

+48 VA

- 48 VA

- VA

- VA

- 48 VA

- 48 VA

- VA

- VA

- 48 VA

+ 48 VB

+ VB

10

+ VB

+ 48 VB

+ 48 VB

+ VB

11

12

+ VB

+ 48 VB

- 48 VB

- VB

13

14

- VB

- 48 VB

- 48 VB

- VB

15

16

- VB

- 48 VB

GND

17

18

GND

FAN

19

20

PWOFFA Thermal alarm A

GND

21

22

PWOFFB Thermal alarm B

OPEND

23

24

GND

External BSCI alarm (link) EXT

25

26

MCR

Critical alarm

Major alarm

MJ

27

28

MN

Minor Alarm

N.C.

29

30

N.C.

N.C.

31

32

N.C.

N.C.

33

34

N.C.

N.C.

35

36

N.C.

Fan alarm

Open-door alarm

Tab. 5.18

130

signal

X7 connector of the Extra Adapter Board

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

The Extra Adapter Board is designed using pressfit connector apart from X7 (Fig. 5.22)
that is a SMT solder termination 36 p. This connector needs to connect this board to
Front Panel Board (on this board there is the same connector) via a pin strip (V50500C1-A8). Before inserting the finger of the X7 connector in the Front Panel Board
connector (DA-CH), tighten the four screws on the Extra Adapter Board to fasten it on
the Front Panel Board.

holes for fastening screws

X3

X4

X5
X1

X6

X2
X7

Fig. 5.22

Mechanical layout of the Extra Adapter board

A30808-X3247-L460-2-7631

131

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

AW6

DW6

AW3
S50201-X8-A20
new cables
DW3
new cable for expansion subrack

PM2

PM3

GW6

LW6

GW3

LW3

to old type TRAU subrack

Fig. 5.23

132

Extra Adapter Board system block diagram

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

Fig. 5.24

IMN:TRAU

New subrack of the TRAU_HC in TRAU_standard rack

A30808-X3247-L460-2-7631

133

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

5.3.2

Replacement and expansion procedure


It is possible, in each frame, to replace a TRAU-Standard module with a TRAU-HC
module using the TRAU-HC shelf, but if there is another TRAU in service in the shelf
below it is allowed to equip only one TRAU (the first on the left side) because of TRAUs
cables numbering. If there is no TRAU in the shelf belove it is possible to equip both
TRAUs of the TRAU-HC frame, provided the number of TRAUs do not exceed four.
In the figure belove there are some examples of the replace/expansion of TRAU module
starting from TRAU-Standard rack with 1, 2 or 3 TRAUs.
0

add one
TRAU

add one
TRAU

0 1
add one
TRAU

2 3

TRAU-Standard rack
with only one TRAU equipped
0
replace with TRAU-HC

add one TRAU


0

0
add one
TRAU

0
2

add one
TRAU

1
3

0
1

add one
TRAU

TRAU-Standard rack
with two TRAUs equipped

1
2

add one
TRAU

1
2 3

0
1

replace shelf number zero


with TRAU-HC shelf
add one TRAU
0

0
1
2

134

add one
TRAU

1
2 3

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

Fig. 5.25

IMN:TRAU

Examples of replacement and expansion procedures

0
1

add one
TRAU

1
2

2
3
replace shelf number zero
TRAU-Standard rack
with three TRAUs equipped

add one
TRAU

replace shelf
1
number one

1
2

replace shelf number two


0

0
1

add one
TRAU

Fig. 5.26

1
2 3

Examples of replacement and expansion procedures

A30808-X3247-L460-2-7631

135

IMN:TRAU

136

Installation
Transcoding and Rate Adaption Unit

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

6 Upgrade Procedure of a TRAU frame in a


TRAU HC rack
In the following is showed the Upgrade Procedure of a TRAU frame in a site with TRAU
rack already installed and working.
The upgrade procedure is referred to one frame only; each frame should be installed in
the same way.
TRAU rack with a frame missing and cables of the Racl Cabling kit.

Fig. 6.1

TRAU frame wiring

A30808-X3247-L460-2-7631

137

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

List of the Rack Cabling kit (S30861-K117-X).


Code Number

Function Designation

S50201-X8-A11 PCM cable

S50201-X8-A9

S50201-X8-A3

Remote Alarm cable

Power cable

S50201-X8-A15 Daisy chain cable

Cable
Number

Connected To

14/0

Frame 0/X27 (PCM 0) -SX

14/0

Frame 0/X25 (PCM 1) -DX

14/1

Frame 1/X27 (PCM 0) -SX

14/1

Frame 1/X25 (PCM 1) -DX

14/2

Frame 2/X27 (PCM 0) -SX

14/2

Frame 2/X25 (PCM 1) -DX

14/3

Frame 3/X27 (PCM 0) -SX

14/3

Frame 3/X25 (PCM 1) -DX

12/0

DC Panel 0/REM AL: - SX

12/0

DC Panel 0/REM AL: - DX

12/1

DC Panel 1/REM AL: - SX

12/1

DC Panel 1/REM AL: - DX

12/2

DC Panel 2/REM AL: - SX

12/2

DC Panel 2/REM AL: - DX

12/3

DC Panel 3/REM AL: - SX

12/3

DC Panel 3/REM AL: - DX

4/0A

DC Panle 0/PWRA (IN)

4/0B

DC Panel 0/PWRB (IN)

4/1A

DC Panle 1/PWRA (IN)

4/1B

DC Panel 1/PWRB (IN)

4/2A

DC Panle 2/PWRA (IN)

4/2B

DC Panel 2/PWRB (IN)

4/3A

DC Panle 3/PWRA (IN)

4/3B

DC Panel 3/PWRB (IN)

-----

DC Panel 0/Daisy chain


DC Panel 1/Daisy chain
DC Panel 2/Daisy chain
DC Panel 3/Daisy chain

Tab. 6.1

138

List of Rack Cabling

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

TRAU FRAME (S30861-B248-X)


Mechanics (S30861-B250-X)

Fig. 6.2

TRAU FRAME mechanics

DC PANEL (S30861-D26-X)

Fig. 6.3

DC PANEL rear

A30808-X3247-L460-2-7631

139

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

FRAME cabling kit

Fig. 6.4

Code Number

TRAU FRAME cabling

Function Designation

From

To

S50201-X8-A6

Ground cable

DC Panel/GND

TRAU Frame/X28 (GND)

S50201-X8-A16

Power cable

DC Panel/PWRA (OUT)

TRAU Frame/X21-X22 (VBA)

S50201-X8-A16

Power cable

DC Panel/PWRB (OUT)

TRAU Frame/X23-X24 (VBB)

S50201-X8-A17

Signal cable

DC Panel/LMT+ALARM

TRAU Frame/X26 (LMT+ALM)

Tab. 6.2

140

List of Frame cabling

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Upgrade procedure
1 - Mount the frame mechanics

4xScrews
Frame-Mechanics

Fig. 6.5

Frame mechanics mounting

2 - Connect ground cable (backplane side)

Fig. 6.6

Ground cable

A30808-X3247-L460-2-7631

141

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

3 - Connect PCM cables and Signal cable (backplane side)

Fig. 6.7

PCM and Signal cables

4- Connect power cables (backplane side)

Fig. 6.8

142

Power cables

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

5 - Mount the DC panel

4xScrews
DC-Panel

Fig. 6.9

DC Panel mounting

Make sure that the two breakers of the DC panel are off.

6- Connect Ground cable (DC Panel side)

Fig. 6.10

Ground cable

A30808-X3247-L460-2-7631

143

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

7 - Connect Power cables (DC Panel side)

Fig. 6.11

Power cables

8 - Connect Power cables (DC Panel side)

Fig. 6.12

144

Power cables

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

9 - Connect Remote Alarm cables

Fig. 6.13

Remote Alarm cables

10 - Connect Signa cable (DC Panel side) and Daisy chain cable

Fig. 6.14

Daisy chain and Signal cables

A30808-X3247-L460-2-7631

145

IMN:TRAU

Installation
Transcoding and Rate Adaption Unit

12 - Close the DC Panel

Fig. 6.15

146

DC Panel

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

7 Swap from TRAU Standard rack to TRAU HC


rack
To swap the standard rack to HC rack proceed as follows:
Disconnect all cables (first of all: POWER SUPPLY) from the rack and position them
in a zone where dont trouble.
Take off the standard rack (according the site remove the expansion bolt used for
fixing the basement, the expansion bolt used for fixing the rack to the wall, the Adaption used for securing the rack to the wall - see Chap. 2.5).
Install the HC rack according the Chap. 2.6.
Reconnect all cables according the site documentation and, if occur, according the
Chap. 3 (TRAU Power Supply) and Chap. 4 (External Cabling Activities).

Basement layout

300 (11.8)

160 (6.3)

80 (3.15)45 (1.77)

300 (11.8)

599 (23.6)

Standard rack drilling sketch

300 mm (11.8)

300 mm (11.8)

145 (5.7)

80 (3.15) 45 (1.77)

Basement layout

57 (2.2)

Fig. 7.1

599 (23.6)

Fig. 7.2

A30808-X3247-L460-2-7631

HC rack drilling sketch

147

IMN:TRAU

148

Installation
Transcoding and Rate Adaption Unit

A30808-X3247-L460-2-7631

Installation
Transcoding and Rate Adaption Unit

IMN:TRAU

Abbreviations

GSM Interface between TRAU and MSC

Abis

GSM Interface between BTS and BSC

Asub

GSM Interface between BSC and TRAU

BSC

Base Station Controller

BSS

Base Station System

BTS

Base Transceiver Station

CSU

Channel Service Unit

DC

Direct Current

ETSI

European Telecommunication Standards


Institute

GND

Ground

HF-DF

High Frequency-Distribution Frames

LMT

Local Maintenance Terminal

MDF

Main Distribution Frame

MSC

Mobile Switching Center

PCM

Pulse Code Modulation

TFAP

TRAU Fuse and Alarm Panel

TRAC

Transcoder and Rate Adaption Board

TRX

Transceiver

A30808-X3247-L460-2-7631

,,,,,

149

IMN:TRAU

150

Installation
Transcoding and Rate Adaption Unit

A30808-X3247-L460-2-7631

Você também pode gostar