Você está na página 1de 6

Air System Sizing Summary for DUCT SPLIT System

Project Name: JIZAN


Prepared by: asd

11/06/2014
05:10

Air System Information


Air System Name ...................... DUCT SPLIT System
Equipment Class ....................................... SPLT AHU
Air System Type ............................................ CAV/RH

Number of zones .......................................................... 8


Floor Area ............................................................ 8183.0 ft
Location ......................................... JIZAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 46.1
Total coil load ..................................................... 553.7
Sensible coil load ................................................ 393.0
Coil CFM at Jul 1500 ......................................... 21832
Max block CFM ................................................. 21832
Sum of peak zone CFM ..................................... 21832
Sensible heat ratio .............................................. 0.710
ft/Ton ................................................................. 177.3
BTU/(hr-ft) ........................................................... 67.7
Water flow @ 10.0 F rise ..................................... N/A

Tons
MBH
MBH
CFM
CFM
CFM

Load occurs at .................................................. Jul 1500


OA DB / WB .................................................. 120.0 / 87.0
Entering DB / WB ........................................... 81.7 / 71.3
Leaving DB / WB ........................................... 65.0 / 64.0
Coil ADP .................................................................. 63.1
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 67
Design supply temp. ................................................ 65.0
Zone T-stat Check ................................................. 0 of 8
Max zone temperature deviation ................................ 1.2

F
F
F
F
%
F
OK
F

Supply Fan Sizing Data


Actual max CFM ................................................ 21832 CFM
Standard CFM ................................................... 21801 CFM
Actual max CFM/ft ............................................... 2.67 CFM/ft

Fan motor BHP ........................................................ 0.00 BHP


Fan motor kW .......................................................... 0.00 kW
Fan static ................................................................. 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 2250 CFM
CFM/ft ................................................................. 0.27 CFM/ft

Hourly Analysis Program v4.61

CFM/person ........................................................... 12.78 CFM/person

Page 1 of 6

Zone Sizing Summary for DUCT SPLIT System


Project Name: JIZAN
Prepared by: asd

11/06/2014
05:10

Air System Information


Air System Name ...................... DUCT SPLIT System
Equipment Class ....................................... SPLT AHU
Air System Type ............................................ CAV/RH

Number of zones .......................................................... 8


Floor Area ............................................................ 8183.0 ft
Location ......................................... JIZAN, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ...................... Sum of space airflow rates
Space CFM .................. Individual peak space loads

Calculation Months ....................................... Jan to Dec


Sizing Data ................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8

Maximum
Cooling
Sensible
(MBH)
25.3
23.6
28.8
28.8
29.6
29.6
29.6
40.1

Design
Air
Flow
(CFM)
2342
2184
2671
2671
2747
2747
2747
3720

Minimum
Air
Flow
(CFM)
2342
2184
2671
2671
2747
2747
2747
3720

Time
of
Peak
Load
Jul 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1700

Maximum
Heating
Load
(MBH)
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.4

Reheat
Coil
Load
(MBH)
0.0
11.8
14.5
14.5
14.9
14.9
14.9
20.5

Reheat
Coil
Water
gpm
@ 20.0 F
-

Zone
Htg
Coil
Load
(MBH)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

Zone
Htg
Water
gpm
@ 20.0 F
-

Mixing
Box Fan
Airflow
(CFM)
0
0
0
0
0
0
0
0

Zone
Floor
Area
(ft)
1100.0
905.0
905.0
905.0
906.0
906.0
906.0
1650.0

Zone
CFM/ft
2.13
2.41
2.95
2.95
3.03
3.03
3.03
2.25

Zone Terminal Sizing Data

Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8

Space Loads and Airflows

Zone Name /
Space Name
Zone 1
SERVER
STORE
CONTROL
Zone 2
DEBRIEFING
OFFICE
Zone 3
SIMULATION 1
SIMULATION 2
STUDENT AREA 1
CONTROL 1
CONTROL 2
Zone 4
SIMULATION 3
SIMULATION 4
STUDENT AREA 2
CONTROL 3
CONTROL 4
Zone 5
Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

1
1
1

8.8
10.1
6.4

Jul 1600
Jul 1600
Jul 1600

817
936
589

0.1
0.0
0.0

255.0
655.0
190.0

3.20
1.43
3.10

1
1

18.6
4.9

Jul 1600
Jul 1500

1729
455

0.1
0.0

750.0
155.0

2.31
2.93

1
1
1
1
1

9.3
7.0
7.0
2.7
2.7

Jul 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1600

864
651
653
252
252

0.0
0.0
0.0
0.0
0.0

255.0
255.0
285.0
55.0
55.0

3.39
2.55
2.29
4.57
4.57

1
1
1
1
1

9.3
7.0
7.0
2.7
2.7

Jul 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1600

864
651
653
252
252

0.0
0.0
0.0
0.0
0.0

255.0
255.0
285.0
55.0
55.0

3.39
2.55
2.29
4.57
4.57

Page 2 of 6

Zone Sizing Summary for DUCT SPLIT System


Project Name: JIZAN
Prepared by: asd

Zone Name /
Space Name
ROOM 1
ROOM 2
ROOM 3
ROOM 4
ROOM 5
AREA 1
Zone 6
ROOM 6
ROOM 7
ROOM 8
ROOM 9
ROOM 10
AREA 2
Zone 7
ROOM 11
ROOM 12
ROOM 13
ROOM 14
ROOM 15
AREA 3
Zone 8
CORRIDOR

Hourly Analysis Program v4.61

11/06/2014
05:10

Mult.
1
1
1
1
1
1

Cooling
Sensible
(MBH)
3.6
4.2
5.8
5.8
4.2
6.2

Time
of
Load
Jul 1700
Jul 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1600

Air
Flow
(CFM)
333
387
534
534
387
573

Heating
Load
(MBH)
0.0
0.0
0.0
0.0
0.0
0.0

Floor
Area
(ft)
110.0
128.0
145.0
145.0
128.0
250.0

Space
CFM/ft
3.03
3.02
3.68
3.68
3.02
2.29

1
1
1
1
1
1

3.6
4.2
5.8
5.8
4.2
6.2

Jul 1700
Jul 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1600

333
387
534
534
387
573

0.0
0.0
0.0
0.0
0.0
0.0

110.0
128.0
145.0
145.0
128.0
250.0

3.03
3.02
3.68
3.68
3.02
2.29

1
1
1
1
1
1

4.2
5.8
5.8
4.2
3.6
6.2

Jul 1600
Jul 1600
Jul 1600
Jul 1600
Jul 1700
Jul 1600

387
534
534
387
333
573

0.0
0.0
0.0
0.0
0.0
0.0

128.0
145.0
145.0
128.0
110.0
250.0

3.02
3.68
3.68
3.02
3.03
2.29

40.1

Jul 1700

3720

0.4

1650.0

2.25

Page 3 of 6

Air System Design Load Summary for DUCT SPLIT System


Project Name: JIZAN
Prepared by: asd

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Terminal Reheat Coils
>> Total Conditioning
Key:

Hourly Analysis Program v4.61

11/06/2014
05:10

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 120.0 F / 87.0 F
HEATING OA DB / WB 69.0 F / 59.0 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
0 ft
0
0 ft
2760 ft
39876
2760 ft
805
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
7748 ft
0
7748 ft
0
0 ft
0
0 ft
0
0 ft
0
0 ft
0
16366 W
45199
0
0
100 W
278
0
0
12800 W
39961
0
0
176
32855
36080
0
0
0
76195
51302
0
0
0
0
0
0
0% / 0%
0
0
0%
0
0
234365
87382
805
0
289420
87382
-4347
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
21832 CFM
0
21832 CFM
0
2250 CFM
103612
73404
2250 CFM
-1120
0
21832 CFM
0
21832 CFM
0
0
0
0%
0
0%
0
393031
160786
-5467
0
393031
160718
-84430
0
0
78963
393031
160718
-5467
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 4 of 6

System Psychrometrics for DUCT SPLIT System


Project Name: JIZAN
Prepared by: asd

11/06/2014
05:10

July DESIGN COOLING DAY, 1500


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
120.0
81.7
65.0
65.0
65.0
77.3
77.3

Specific
Humidity
(lb/lb)
0.02028
0.01410
0.01255
0.01255
0.01255
0.01339
0.01339

Airflow
(CFM)
2250
21832
21832
21832
21832
21832
21832

CO2 Level
(ppm)
400
848
848
848
848
900
900

Sensible
Heat
(BTU/hr)
103612
393031
0
289420
0

Latent
Heat
(BTU/hr)
73404
160718
87382
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.078 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4739.9 BTU/(hr-CFM)
Site Altitude = 39.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8

Hourly Analysis Program v4.61

Zone
Sensible
Load
(BTU/hr)
25227
23462
28753
28753
29532
29532
29532
39572

T-stat
Mode
Cooling
Cooling
Cooling
Cooling
Cooling
Cooling
Cooling
Cooling

Zone
Cond
(BTU/hr)
30952
28943
35256
35256
35985
35985
35985
51058

Zone
Temp
(F)
77.3
77.3
77.2
77.2
77.1
77.1
77.1
77.7

Zone
Airflow
(CFM)
2342
2184
2671
2671
2747
2747
2747
3720

CO2
Level
(ppm)
837
924
906
906
932
932
932
848

Terminal
Heating
Coil
(BTU/hr)
0
0
0
0
0
0
0
0

Zone
Heating
Unit
(BTU/hr)
0
0
0
0
0
0
0
0

Page 5 of 6

System Psychrometrics for DUCT SPLIT System


Project Name: JIZAN
Prepared by: asd

11/06/2014
05:10

WINTER DESIGN HEATING


TABLE 1:

SYSTEM DATA

Component
Ventilation Air
Vent - Return Mixing
Central Cooling Coil
Supply Fan
Cold Supply Duct
Zone Air
Return Plenum

Location
Inlet
Outlet
Outlet
Outlet
Outlet
Outlet

Dry-Bulb
Temp
(F)
69.0
68.6
65.0
65.0
65.0
68.5
68.5

Specific
Humidity
(lb/lb)
0.00836
0.00836
0.00836
0.00836
0.00836
0.00836
0.00836

Airflow
(CFM)
2250
21832
21832
21832
21832
21832
21832

CO2 Level
(ppm)
400
478
478
478
478
487
487

Sensible
Heat
(BTU/hr)
1120
84430
0
4347
0

Latent
Heat
(BTU/hr)
0
0
0
-

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.078 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4739.9 BTU/(hr-CFM)
Site Altitude = 39.0 ft

TABLE 2:

ZONE DATA

Zone Name
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8

Hourly Analysis Program v4.61

Zone
Sensible
Load
(BTU/hr)
-60
-60
-58
-58
-58
-58
-58
-394

T-stat
Mode
Deadband
Heating
Heating
Heating
Heating
Heating
Heating
Heating

Zone
Cond
(BTU/hr)
1735
307
368
368
367
367
367
467

Zone
Temp
(F)
65.7
68.9
68.9
68.9
68.9
68.9
68.9
68.9

Zone
Airflow
(CFM)
2342
2184
2671
2671
2747
2747
2747
3720

CO2
Level
(ppm)
487
487
487
487
487
487
487
487

Terminal
Heating
Coil
(BTU/hr)
0
8833
10808
10808
11124
11124
11124
15141

Zone
Heating
Unit
(BTU/hr)
0
0
0
0
0
0
0
0

Page 6 of 6

Você também pode gostar