Escolar Documentos
Profissional Documentos
Cultura Documentos
N-6000
Manual
REV B
DATE 2007-08-08
from a fire.
a variety of reasons:
detectors because:
Barriers such as closed or partially closed doors,
located.
by air outlets.
floor of a building.
regularly.
require
more
frequent
maintenance.
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
Verify that wire sizes are adequate for all initiating and
Several different sources of power can be
understood.
in site-specific software.
circuits.
possible,
make all cable entries from the sides or rear. Before making
operation verified.
Table of Content
Section 1:About This Manual ................................................................................................................. 6
1.1Notes, Cautions & Warnings......................................................................................................... 6
1.2Font Definition .............................................................................................................................. 6
Section 2:System Overview.................................................................................................................... 7
2.1Introduction ................................................................................................................................... 7
2.2Characteristics of the Product........................................................................................................ 7
Section 3:System Configuration & Installation ...................................................................................... 9
3.1Features Main Performances ......................................................................................................... 9
3.2Electrical Specifications ................................................................................................................ 9
3.3System Configuration.................................................................................................................... 9
3.4System Block Diagram................................................................................................................ 10
3.5Installation & Connection ........................................................................................................... 11
3.5.1Enclosures............................................................................................................................ 11
3.5.2Connection Requirements.................................................................................................... 12
3.5.3Connection of Circuit Board Terminals............................................................................... 12
3.5.3.1CPU Diagram ............................................................................................................... 12
3.5.3.2Power Supply Connection ............................................................................................ 15
3.5.3.3NIC-EC......................................................................................................................... 17
3.5.3.4Loop Control Module Connection................................................................................ 19
3.5.3.5MCU-16B Annunciator Control Module Connection .................................................. 21
3.6Equipment Debugging ............................................................................................................ 23
3.6.1Connection Inspection..................................................................................................... 23
3.6.2Power-on Inspection........................................................................................................ 24
3.6.3External Connection ........................................................................................................ 24
3.6.4Important Points .............................................................................................................. 24
3.6.5Inspection Methods for Addressable Device Connections.............................................. 25
Section 4:Operation .............................................................................................................................. 26
4.1LED Indicators and Keys ............................................................................................................ 26
4.1.1Control Panel Display LED Indicators and Keys ................................................................ 26
4.1.2Annunciator Control Module LED Indicators and Keys ..................................................... 29
4.2Power-on ..................................................................................................................................... 30
4.3System Self-test........................................................................................................................... 30
4.4Event Display .............................................................................................................................. 32
4.4.1Trouble Screen..................................................................................................................... 32
4.4.2Fire Alarm Screen................................................................................................................ 33
4.4.3Supervisory Screen .............................................................................................................. 34
4.4.4Point Disabled Screen.......................................................................................................... 35
4.4.5CBE Screen.......................................................................................................................... 36
4.4.6Pre-alarm Screen.................................................................................................................. 36
4.4.7Horn / strobe Screen ............................................................................................................ 37
4.4.8Feedback Screen .................................................................................................................. 37
Warnings: Indicates
1.2Font Definition
Special font styles used in this manual are listed in Table 1-1, Specifications of
Manual Characters:
Font
Bold
Script
Meaning
Key on the control panel
Example
Press the
Silenced
Name of document
key
Signals
3.2Electrical Specifications
y Voltage range
Input voltage: 220 VAC
Output voltage:
3.3System Configuration
y Intelligent control panel: N-6000
y Remote display: LCD-100B, LDM-64B
y Intelligent detectors:
y Intelligent base:
B601
B501
y Intelligent modules:
Isolator: ISO-7
If there are many addressable units in the loop bus, user should install the
shortcut isolator in front of the loop bus. The addressable units are less than 25
units between adjacent two isolators.
All NOTIFIER cabinets are fabricated from 16-gauge steel. The cabinet assembly
consists of two basic parts: a backbox and a locking door. The backbox has been
3.5.2Connection Requirements
y All incoming/outgoing external conduits should use the control panel cabinets
bottom knockout or opening for terminal connections.
y Loop transmission line adopts twisted pair cable, the type and specification are:
RVSP21.5mm2
y Loop resistance (refers to loop resistance between the machine and two leads of
the farthest addressing unit) should be less than 50 .
y Power wiring should use two-color multiple plastic cable, red for male terminal,
black for female terminal. The type and specification are: RV-22.5mm2
Illumination
TB1
TB2
TB3
TB4
24VDCPower
TB5
TB6
TB7
TB8
RPT port
TB9
TB10
J10
J13
J15
Illumination
JP2
JP3
JP5
JP9
ISP program write down jumper, user should cover jumper cap when
ISP upgrade program
JP18
JP19
JP21
JP22
JP23
JP24
Illumination
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
24VDCGreen
LED9
5VDCGreen
LED10
LED11
LED12
LED13
LED15
LED17
LED18
LED19
LED20
LED21
Illumination
TB1
TB2
TB3
TB4
TB5
TB12
TB13
TB14
Illumination
JP1
JP2
JP3
JP4/ JP5
Illumination
LED1
LED2
LED3
LED13
LED19
LED23
LED24
LED25
LED26
LED27
LED28
LED29
LED30
3.5.3.3NIC-EC
When N-6000 connect into N-NET fire alarm network, each control panel must
install a NIC-EC card. Connection terminal, jumper and indicative show as below:
Illumination
TB1
Network port A
TB2
TB3
TB5
Network port A
Table 3-7 NIC-EC Terminal Illumination
Illumination
JP6
JP7
JP8
JP9
LED1
Green
LED2
Green
LED23
Green
Port B information
status
LED24
Yellow
Port B trouble
LED25
Red
LED3
Green
LED4
Green
LED20
Green
Port A information
status
LED21
Yellow
Port A trouble
LED22
Red
LED5
Green
System running
indication
LED6
Yellow
LED7
Red
LED8
Green
LED9
Green
LED10
Green
LED11
Green
J9 signal input
indication
LED12
Green
LED13
Green
J9 signal output
indication
LED14
Green
Function reserve
LED15
Green
Function reserve
LED16
Red
Function reserve
LED17
Green
TB3 port
information
correctly
LED18
Yellow
LED19
Red
LED26
Blue
Function reserve
status
Function
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
1~6bits switch
ON for 1OFF for 0
Composing a 6 bits binary number,
this number infer network card
address. Network card address
range is the number between 0~63.
Network card address must be same
as the connect devices address.
OFF
ON
OFF
ON
Relay mode
OFF
Bus mode
ON
N-NCS
OFF
CPU-6000
Illumination
TB2
TB3
TB4
TB5
J2
Interlink port
J4
Interlink port
Table 3-11 LCM-2 Card Terminal Illumination
Illumination
JP1
JP2
JP4
JP5
Illumination
LED1
LED2
LED3
LED4
LED5
LED6
LED7
LED8
LED9
LED10
LED11
LED12
1~8bits switch
ON for 1OFF for 0
Composing a 8 bits binary number, infer LCM card
address. SW1 setting range is the odd number between
1~29
Table 3-14 LCM-2 Loop Number Setting
Illumination
TB1
TB2
Connect to CPU-6000RS485
J1
Interlink port
J3
Interlink port
Table 3-15 MCU-16B Terminal Illumination
Illumination
JP1
JP2
JP3
JP4
JP5
JP6
Terminal
Illumination
LED1
LED2
LED3
LED4
LED39
LED40
status
function
ON
OFF
ON
1~8bits switch
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
NONE
NONE
NONE
3.6Equipment Debugging
3.6.1Connection Inspection
y Visually inspect the control panel condition
y Visually inspect the external connection ports
y Open the control panel and visually inspect all connections. Confirm connections
are correct, that there are no loose connections, no short circuits, unplugged or
disconnected connectors as well as confirm the power supply does not have
any short circuit trouble.
y Visually inspect the jumpers in the circuit to confirm there are no duplicate
numbers.
3.6.2Power-on Inspection
After you have finished the visual inspection, power-on the battery power supply.
With the battery started a buzzer should be heard and the LCD should temporarily
function normally. Once the control panel enters normal operation status, a buzzer
and LED horn/strobe will indicate a troubled status because main power is not
connected. Power-down and disconnect the battery power supply then connect and
power on the main power supply. Once the control panel enters normal operation
status, a buzzer and LED horn/strobe will indicate a troubled status because the
battery power supply is not connected. At this time, connect the battery power
supply. Soon after the control panel will return to normal operating status.
During normal operation, if both the main and battery power supplies are
connected the power supply status lamp (on the main panel of the control panel)
will maintain normal illumination.
When the main power supply fails because of loss of power, poor power
connection, an over-voltage or under-voltage of 5V and 24V, or a short circuit with
rack earth and communication trouble with the mainframe, the power supply status
lamp (on main panel of the control panel) illumination will stop. Then both a
buzzer and LED horn/strobe will indicate a troubled status while additional
information will be shown on the control panel LCD.
3.6.3External Connection
Look for any short-circuits or disconnections to and from the control panel. Once
everything has been inspected, connect the control panel.
Batch installation -- connecting 10-20 detectors or modules on the loop per time -is highly recommended. After installing the detectors or modules restart the control
panel to ensure the newly installed devices are recognized and installed correctly.
If the control panel gives a trouble signal recheck the circuit and addressable
devices are installed properly. Once the trouble signal has been solved, continue
batch installation and power testing. After all the devices have been installed, the
simulated trouble, fire alarm and CBE event functions maybe tested. Confirm that
the control panel alarms normally, properly links field equipment and accurately
prints corresponding alarm information. Continue testing and adjusting until panel
maintains normal operating status.
3.6.4Important Points
y Avoid touching the circuit board IC chip during installation
y Pay attention to polarity during connection and installation
y Before starting the system, check for short circuits, disconnection or reverse
polarity
y Connectors among leads shall be wielded and inter-line insulation shall be
guaranteed.
Section 4:Operation
4.1LED Indicators and Keys
4.1.1Control Panel Display LED
Indicators and Keys
The N-6000 is an intelligent addressable Fire Alarm Control Panel (FACP) with
advanced features ideal for a variety of applications. The CPU-6000 includes a
front display/keypad enabling localized control panel viewing and programming.
The display/keypad provides an easy-to-use keypad and large LCD (liquid crystal
display) that simplifies the programming process.
The display is 53 characters wide by 20 lines long and displays all programming
screens. These include the events, history, devices as well as other additional
information.
Fields may be entered or changed and commands may be issued using the display
keypad.
LED Indicator
Color
Functions
Fire alarm
Red
Pre-alarm
Red
Trouble
Power
Self-test
Yellow Illuminates when at least one trouble event exists. It will flash
if any of these events are unacknowledged.
Green
CBE
Red
Delay
Red
If the control panel has a delayed control output the LED will
remain illuminated throughout the delay period. It will turn
off upon termination of the delay period.
Signal Silenced
Point Disabled
Yellow Illuminates when at least one device has been disabled. It will
flash until all disabled points have been acknowledged.
Supervisory
CPU Failure
Red
Operation Keys:
A-a: Caps lock key
Space: During programming, change the status of the check box
to and change back to when finished
Backspace : Backspace key
Menu : Press to enter the menu
Help : Help key
PREV / NEXT: Press to skip to the previous/next control screen
The annunciator control module has a total of 32 indicating lamps, 16 keys and 16
feedback signals.
One composite button: Time function key has 3 functions
1Press for about 1 second: LED lamp below the key will illuminate locking the
control key module
2Press for more than 1 second: LED lamp on the right side of the key will
illuminate with manual/automatic allowed
3Press for more than 4 seconds: horn/strobe self-test
No. 1-16 Start Keys:
-Press a key and the corresponding feedback signal a (Lamp 1-16) flash,
means corresponding key has been pressed.
which
4.2Power-on
Connect 220V AC power, and then turn on the main power supply using the switch
inside the cabinet. Power-on Screen is shown in Fig. 4-4:
4.3System Self-test
After the N-6000 has been turned on, it will self-test both the hardware and
software of the system. During the self-test all LED indicating lamps on the left
side of the mainframe panel will flash. Once the self-test has finished a buzzer will
sound and LEDs will temporarily illuminate after which the panel will return to a
normal operation status. Additionally, the system will show the display screen
while the power supply indicating lamp continues to flash.
After a self-test, the system will show the following screen:
The normal system screen is divided into three bars; these include the event
statistics bar, the alarm screen bar and the status bar. The event statistics bar shows
fire alarms, trouble alarms, supervision, CBE and point disabled locations. The
status bar shows the node number, manual/automatic status, transmission
equipment status, main or reserved power supply status, the current date/delay
status of the latest logic zone as well as the current time.
Manual/Automatic Status
System in manual status
System in automatic status
4.4Event Display
Event Order:
First: Fire alarm, CBE, feedback
Second: Supervision
Third: Trouble
Fourth: Point Disabled - disabled
4.4.1Trouble Screen
When the control panel detects a failing power supply or other trouble, it will
execute a series of operations:
A trouble relay will be activated and the control panel will alarm
A system trouble indicating lamp on the control panel display will flash and the
LCD will show a trouble screen
Detailed trouble type will show the exact geographic location and occurrence
time on the LCD
A trouble event will be saved to the native Flash ROM and the printer will print a
record of the trouble event
Press the key or the key on the main panel to review the previous or
next trouble event and press the<key or the>key to page up or down. Press
ACK key on the main panel to acknowledge, and all trouble events will be
shown one by one. Once the alarm has silenced and all trouble events have been
acknowledged, the system trouble indicating lamp on the main panel will return to
its normal illumination.
The most common trouble events include but are not limited to: equipment off-line,
grounding the equipments positive terminal, grounding the equipments negative
terminal, the equipments positive terminal is disconnected, the equipments
negative terminal is disconnected, power supply shows low voltage, power supply
shows high voltage, unmatched load types, low threshold values, database errors.
acknowledged, the system fire alarm indicating lamp on the main panel will return
to its normal illumination.
4.4.3Supervisory Screen
When a point disabled location exists in a loop, each disabled point (detector,
module, and loop) will be shown one by one (see Fig. 4-10). The control panel will
execute a series of operations:
A point disabled indicating lamp on the control panel will flash but the control
panel will not alarm
A point disabled indicating lamp will be illuminated
The point disabled information will be saved to the native Flash and the printer
will print the current point disabled information
Press the key or the key on main panel of the control panel to review
the previous or next point disabled event and press the < key or the > key
to page up or down. Press OK key on main panel of the control panel to
acknowledge all Point disabled information has been shown. Once the alarm has
silenced and all point disabled events have been acknowledged, the point disabled
indicating lamp on the main panel will return to its normal illumination.
4.4.5CBE Screen
4.4.6Pre-alarm Screen
To enter the pre-alarm screen and also query the pre-alarm screen keep pressing the
Fire alarm/Pre-alarmcomposite key on the main panel. The pre-alarm screen is
shown below:
4.4.8Feedback Screen
To enter the supervision/feedback screen and also query the supervision/feedback
screen keep pressing theSupervision/Feedbackcomposite key on the main panel.
The supervision/feedback screen is shown below:
Section 5:Programming
5.1Menu
System Setting
System Management
Modify Password
Main Reset
Setting
LCM
Auto Programming
Point Programming
Setting
DCU
Point Programming
Device Configuration
Setting
MCU
Point Programming
Menu
Setting
Remote Display
Download Labels
Point Programming
General Zone
CBE Programming
Logic Zone
Manual Output
Status Track
Device Control
Status Track
Walk Test
Power Management
History Event
When programming the control panel or reviewing history events, press the
Menu key to view the following screen:
Once a user has entered the correct password, he/she will enter the main menu and
view the following screen. In the main menu screen, he/she can update or change
the system management, device configuration, CBE programming, device control
and history events.
5.2System Management
Under System management the operator has 3 options; (1) System setting, (2)
Modify Password, or (3) Main Reset. The system management screen is shown as
follows:
5.2.1System setting
Under System Setting the following screen will be shown:
Line 1: The node is the control panels address within the network while the label is
a description of the control panel
Line 2: If (YES) is selected for the time server option, then this control panel is
the time master within the network and all other panels will synchronous
accordingly. Click the button time & date to set the time and date of the control
panel
Line 3: Languagedetermines the language of the control panel display. At
present two languages are currently available: Chinese and English
Line 4: Backlightthe duration of time the LED display remains lit. There are four
choices available: Normal Open, Normal Close, Off in 30 Seconds and No Display.
(YES) is
(YES),
(YES),
5.2.2Password modification
Under Password modification, a user can modify his/her password according to
their system status (Admin, Engineer, or Guest). The password modification screen
is shown below:
The N-6000 has 3 different user levels, each level is password protected. The three
levels are (ordered from highest to lowest) Administrator, Engineer and User. Each
level has its own password. The Administrator user can modify any password in
the system (including the Administrator level). The User can only operate on the
4th setting, Device Control and the 5th setting, History event. The Engineer
can operate all five settings in the menu but will be interrupted (exit programming)
when an alarm event occurs. The Administrator can operate all five settings in the
menu and will not be interrupted during an alarm event.
Factory default passwords are as follows: 333333 for Administrator, 222222 for
Engineer and 111111 for User.
After the initial login the user will enter the password modification screen. He/she
can change the password by entering a new password in the Enter new password
dialogue box and then re-entering the new password in the Confirm new
password dialogue box. Once the system has confirmed the two passwords are the
same, the user should press OK to confirm the password change. After the user
has pressed OK the password will be successfully modified, to cancel the
previous operation press the Cancel button.
Note: If an incorrect password is entered, the system will show another dialogue
box requesting the correct password be entered.
5.2.3Main Reset
In the System Setting screen choose Main Reset to reset the system to all
default factory settings.
After the correct Administrator password has been entered, a dialogue box will
prompt to verify the Main Reset choice. Press OK to confirm the reset and
restore default factory settings. Press Cancel to cancel the operation and exit the
screen.
5.3Device Configuration
Choose the Device Configuration screen to adjust the settings of the loop cards,
multi-line control modules, annunciator control modules and repeaters. Screen
shown below:
5.3.1Loop card
In the Device Configuration screen, choose the LCM option to enter the screen
shown below in Fig. 4-23:
5.3.1.1Parameter setting
In the LCM screen, to adjust the settings and program options, choose Setting,
Auto Programming, or Point programming. The screen is shown in Fig. 4-24:
end grounding trouble. If (NO) is chosen, the system will not report positive
end grounding trouble.
There are three function keys, Sync, Save, and Quit in the status bar. The
Sync button allows the operator to download parameter settings (both card level
and point level settings). The Save button saves the changes that have been
selected. The Quit button allows the user to quit without saving the changes.
5.3.1.2Auto Programming
Each loop has 3 status options: Installed, Uninstalled, and Disabled. During normal
installation, the programmer may enter the Auto Programming screen. When
he/she selects a loop number for automatic programming and then presses OK,
the system will verify each device on the selected loop.
Caution: When either a CMX-2 control module or a M500K call point are on
a loop using Auto Programming the control panel will misidentify the CMX-2 as
a CMX-7(C) and misidentify the M500K as an MMX-7. When this happens, the
user should enter 4.5.2.1.3 Point Programming screen (device configuration
LCMpoint programming) to modify the device identity by selecting the proper
equipment type.
5.3.1.3Point Programming
Local Mode: (YES)/ (NO). The factory default setting is (NO). This
option controls both the point and card level settings. By programming
definition the point level setting is the same as the card level setting. If the loop
card and mainframe have a communication failure all selected modules
(degradation mode) will automatically output a fire alarm signal.
Silenceable: (YES)/ (NO). When (YES) is chosen and a horn/strobe
alarm or alarm bell activates, the user can press Signals Silenced on main
panel of the control panel to silence the alarmed equipment. If (NO) is
selected, the user cannot silence the alarmed equipment using the Signals
Silenced button.
Switch Inhibited: (YES)/ (NO). When
output point operation is inhibited.
5.3.2.1Parameter setting
5.3.2.2Point Programming
Point Programming of MCU can access to set the relative module address of keys
and feedback led.
5.3.3Remote Display
In the Remote Display screen, a programmer can access the Setting,
Download Label and Point Programming option screens. One N-6000 fire
alarm control panel can have up to 64 remote displays.
5.3.3.1Parameter setting
5.3.3.2Label Download
system will download relative content for each point in the selected repeater floor
display. If past events have occurred in the selected equipment points, all
previously downloaded contents will also be shown on the remote display. This
allows field operators to update equipment settings for optimal device function.
5.3.3.3Point Programming
Line 1: Displays the remote display number, point number and installation status.
These include: Uninstalled, Normal, and Disabled.
Line 2: Displays the current remote display point description
Line 3: Point MappingEach remote display can have up to 64 points. Each point
must have a specific zone and loop address. After each point has been mapped,
during an event (fire alarm, trouble, etc) the mapped equipments location and
event will be shown on the relative remote display screen.
Press Save to save the current settings. If the user presses Exit without saving,
the following dialogue box will be prompted. At this time the user can also save the
current settings. The user can also exit the current screen to retain previous settings;
the current settings will not be saved.
5.3.4CBE Programming
In the CBE Programming screen programmers can access both the General
Zone and Logic Zone setting screens.
5.3.4.1General Zone
Within the General Zone screen a user can select zones 0-499 to review the
relative logic equation of a particular zone. Use the VFT programming software to
modify the logic equations as necessary.
5.3.4.2Logic Zone
Within the Logic Zone screen a user can select zones 0-999 to review the relative
equation of a particular zone. Use the VFT programming software equation to
modify the logic equations as necessary.
5.3.5Device Control
In the Device Control screen a user can access the Point Output, Status
Tracking, Walking Test, Loop Exercise and Power Supply Management
setting screens.
5.3.5.1Manual Output
Within the Point Output screen a user can set the loop number, address number,
type of equipment, label and the inspection lamp ON/OFF status. Press the
key or the key to review a points status.
Line 1: Displays the current loop number, address and status. These include:
Uninstalled, Normal and Disabled.
Line 2 & Line 3: Displays the current point description and extended description.
Line 4: Displays the current point alarm type. These include: Fire Alarm,
Supervision, Feedback and General Output.
Line 5 & Line 6: Displays the current equipment type and model.
Line 7: Displays the selected output module status. If the user chooses Start and
then presses OK, the point in the current loop will be output by the module; if set
at Close, the point will not be output by the module.
5.3.5.2Status Tracking
Within the Status Track screen a user can set the loop number, address number,
address type as well as monitor the point.
Line 1: Displays the current loop number, loop address and its status. These include:
Uninstalled, Normal and Disabled.
Line 2 & Line 3: Displays the current point description and extended description.
Line 4: Displays the current point alarm type. These include: Fire Alarm,
Supervision, Feedback and General Output.
Line 5 & Line 6: Display the current equipment type and model.
Line 7: Displays the current point status.
5.3.5.3Walk Test
Within the Walk Test screen a user can set the loop number, address number,
address type as well as run a walking test on a particular loop.
Line 1: Displays the loop number, current address and installation status. These
include: Uninstalled, Normal and Disabled.
Line 2 & Line 3: Displays the current point description and extended description.
Line 4: Displays the current point alarm type. These include: Fire Alarm,
Supervision, Feedback and General Output.
Line 5 & Line 6: Displays the current equipment type and model.
After adjusting the systems settings, pressing theLamp inspection/Self-testkey
on main panel will cause the control panel to run a self-test on the current loop.
During this test, both the self-test indicating lamp and the load verification lamp
will be normally illuminated. Press Review the Result to view every address in
the current walk test, the addresses will be displayed on the right hand side of the
walk test interface screen (Fig. 4-50).
5.3.5.4Loop Drill
N-6000 fire alarm control panel uses the MPS-350W power supply. Within the
Power Management screen the user can review the current status of each power
supply.
Line 1: Displays the currently connected power supply type. The MPS-350W is the
primary power supply for the N-6000.
Line 2: Displays the current status and voltage of the main power supply.
Line 3: Displays the current status and voltage of the reserved power supply.
Line 4: Press Discharge to discharge the power supply. Press Stop to stop
discharging. Press Exit to exit the power supply control screen.
5.3.6History Events
Within the History Events screen a user can access the systems history
records/events. This screen is seen below:
Line 1: Displays the type of history event. History event types include but are not
limited to: fire alarm, trouble, supervision, CBE and Isolation. When All Events
is selected, detailed information will be provided for each event. If All Events is
not selected the user must select a particular event to view the additional and
detailed information.
Line 2: Displays the total number of events that can be reviewed.
Line 3: Displays the status of the current event. The operator may obtain detailed
information about the current event including location, type, time of occurrence,
serial number, as well as additional information from the following text box.
Line 4: Press Exit to exit the history event screen.
Pressing theNEXTkey or thePREVkey on main panel of the control panel,
a user can review the detailed description of the next or previous history event.
N-6000 can record and display up to 8000 individual history events.
Section 6:Miscellaneous
6.1Safety Protection Device
The N-6000 has been designed with built-in safety devices to protect both the operator and
control panel in case of improper use and/or installation. These devices include an anti-misplug
terminal which can endure extremely high voltage and current ensuring the safety of both
operators as well as the control panel. Additionally the control panel has current limiting
protection for the power supply, protection circuits for communication devices, and special
grounding terminals provided within the cabinet.
6.3Common Troubles
The N-6000 has advanced features such as self-diagnosis and self-protection; however even
with the advanced technology an occasional trouble signal is unavoidable. Table 5-1 has
additional information regarding common troubles.
Trouble
Main power supply
trouble
Reserved power
supply trouble
Cause analysis
Solution
Re-connect the
power supply
Check connectors
Replace
supply
reserved
AC220V
power
Trouble
Keypad fails
No sound
Inaccurate clock
Cause analysis
Solution
Check connectors
Backlight
improperly
connected
Loudspeaker
improperly
socket
socket
connected
6.5Out-of-box Audit
When opening the control panel box for the first time the user should carry out an out-of-box
audit to ensure the control panel is complete, untouched and undamaged from transportation.
The control panel should include: a CPU, loop card, MCU, POM-8A, MPS-350W,
complement keys and connecting wires, etc.
Open the control panel door to ensure all internal connections are normal and that there are no
loose connections, short circuits and/or disconnected items. Check the power supply status to
ensure it is normal and does not have any short circuits, etc.
Appendix A
Alarm level cross-reference table for the ND682 photoelectric smoke detector:
Alarm level setting
LEVEL 1
0 -2.5
LEVEL 2
2.5 5
LEVEL 3
5 - 7.5
LEVEL 4
7.5 10
LEVEL 5
10 -14
LEVEL 6
14 16
LEVEL 7
16 -18
LEVEL 8
18 20
LEVEL 9
over 20
LEVEL 10
Over 20
LEVEL 1
30 34
LEVEL 2
34 37
LEVEL 3
37 40
LEVEL 4
40 45
LEVEL 5
45 50
LEVEL 6
50 55
LEVEL 7
55 60
LEVEL 8
60 65
LEVEL 9
Over 65
LEVEL 10
Over 65
alarm
(Unit: 0.01%/ft)
LEVEL 1
02
LEVEL 2
23
LEVEL 3
3 10
LEVEL 4
10 50
LEVEL 5
50 100
LEVEL 6
100 150
LEVEL 7
150 200
LEVEL 1Warning
30
LEVEL 2Warning
60
LEVEL 3Trouble
90
Limited Warranty
NOTIFIER warrants its products to be free from defects in materials and
workmanship for eighteen (18) months from the date of manufacture, under
normal use and service. Products are date stamped at time of manufacture.
The sole and exclusive obligation of NOTIFIER is to repair or replace, at its
option, free of charge for parts and labor, any part which is defective in
materials or workmanship under normal use and service. For products not
under NOTIFIER manufacturing datestamp control, the warranty is eighteen
(18) months from date of original purchase by NOTIFIER 's distributor
unless the installation instructions or catalog sets forth a shorter period, in
which case the shorter period shall apply. This warranty is void if the product
is altered, repaired or serviced by anyone other than NOTIFIER or its
authorized distributors or if there is a failure to maintain the products and
systems in which they operate in a proper and workable manner. In case of
defect, secure a Return Material Authorization form from our customer
service department. Return product, transportation prepaid, to NOTIFIER, 12
Clintonville Road, Northford, Connecticut 06472-1653.
This writing constitutes the only warranty made by NOTIFIER with respect to
its products. NOTIFIER does not represent that its products will prevent any
loss by fire or otherwise, or that its products will in all cases provide the
protection for which they are installed or intended. Buyer acknowledges that
NOTIFIER is not an insurer and assumes no risk for loss or damages or the
cost of any inconvenience,
transportation, damage, misuse, abuse, accident or similar incident.
NOTIFIER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF