Escolar Documentos
Profissional Documentos
Cultura Documentos
Revision: 2/06
C o p y r i g h t 1 9 8 8 - 2 0 0 6
C a m p b e l l S c i e n t i f i c , I n c .
1. General .........................................................................1
2. Wiring............................................................................1
3. Programming ...............................................................2
3.1 Measurement.............................................................................................2
3.2 Calculating Sensor Resistance ..................................................................3
3.3 Output - Recording Fraction of Time Wet and Dry..................................3
4. Calibration ....................................................................3
5. Program Example for the CR10X ...............................4
2. Wiring
Figure 1 is a schematic of the 237 Leaf Wetness Sensor. The 237 Sensor uses
a single-ended analog channel, the red lead "HI" can be inserted into either a
HI or LO input.
The black lead "EX" connects to any excitation channel, and the clear lead is
the shield which connects to ground.
The purple lead connects to Analog Ground. Analog Ground is labeled "AG"
on the CR200-series, CR3000,
on the CR510, CR10(X), and CR1000, or
CR5000, CR7, and CR9000(X).
NOTE
3. Programming
This section is for users who write their own datalogger programs. A
datalogger program to measure this sensor can be created using Short Cut.
You do not need to read this section to use Short Cut.
There are three steps involved in programming the datalogger to output results
of leaf wetness with the 237 Sensor. There is the excitation and measurement
of the sensor, the calculation of sensor resistance, and programming for the
desired output.
3.1 Measurement
Except for the CR200-series, the AC Half Bridge instruction (Instruction 5 in
Edlog or BrHalf in CRBasic) is used to read the 237 sensor. The AC Half
Bridge instruction returns the ratio of the measured voltage to the excitation
voltage (Vs/Vx), which is equal to a ratio of sensor resistances as shown below
(refer also to Figure 1).
Vs/Vx = R2/(R2+R1+Rs)
Datalogger
Excitation
Full Scale
Voltage Range
Integration
2500 mV
25 mV
fast
5000 mV
50 mV
fast
Table 1 shows the appropriate excitation voltage, full scale voltage range, and
integration that should be used in Instruction 5 or the BrHalf instruction. Use a
multiplier of 1.0 and an offset of 0 to output Vs/Vx directly.
The CR200-series uses the ExDelSE instruction.
4. Calibration
The resistance of the sensor at the wet/dry transition point should be
determined. A sharp change in resistance occurs in the wet-dry transition on
the uncoated sensor. Coated sensors have a poorly defined transition. The
resistance of the uncoated sensor at the wet/dry transition is normally between
50 and 200 kohms. The coated sensor transition normally occurs from 20
kohms to above 1,000 kohms.
For best results, the leaf wetness sensor should be field calibrated. The
transition point will vary for different areas and vegetation. Place the sensor
among the vegetation whose wetness is to be monitored. Observe the
vegetation until it reaches the desired wetness by natural means. When the
vegetation is at the desired "wetness", note the measured resistance on the
datalogger. This resistance is the transition point.
2: Z=1/X (P42)
*1: 1
*2: 2
Invert VS/VX
X Loc
Z Loc : Res Locv
3: Z=X+F (P34)
*1: 2
2: -101.0
*3: 2
X Loc
F
Z Loc : Res Loc
resulting in VS/VX
4: If time is (P92)
*1: 0
minutes into a
*2: 1440
minute interval
*3: 10
Set high Flag 0 (output)
Every 24 hours
6: Histogram (P75)
*1: 1
Rep
*2: 1
No. of Bins
*3: 1
Closed form
4: 2
Bin Select Value Loc
5: 0000
WV Loc Option
6: 0.0000
Low Limit
*7: 150
High Limit
Output
7: End Table 1
*Parameter entries will vary depending on the program and datalogger channel usage.