Siemens AG 2006
SIPROTEC 4
7UT6 differential protection relay for
transformers, generators, motors and
busbars
7UT612:
7UT613:
7UT633:
7UT635:
Page 2
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
Hardware options
Device
7UT612
7UT613
7UT633
7UT635
7 (7)*
1
--3
4
1
4 lines
11 (6)*
1**
3/1
5
8
1
4 lines
11 (6)*
1**
3/1
21
24
1
Graphic
14 (12)*
2**
-- 29
24
1
Graphic
Page 3
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
Function
ANSI No.
Differential
87T/G/M/L
Restricted Earth fault
87 N
Overcurrent-time, phases
50/51
50N/51N
Overcurrent-time, 3I0
Overcurrent-time, earth
50G/51G
Overcurrent-time, single phase
Negative sequence
46
Overload IEC 60255-8
49
Overload IEC 60354 (hot spot)
49
Overexcitation V/Hz
24
Breaker failure
50BF
External temperature monitoring
38
Lockout
86
Measured value supervision
Trip circuit supervision
74TC
Direct coupling
Operational measured values
Protection Objects
Three-phase transformer
Single-phase transformer
Auto-transformer
Generator / Motor
Busbar, 3-phase (Branch point)
Busbar, 1-phase
Page 4
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
ANSI No.
Transf.
3-phase
Transf.
1-phase
Autotransf.
Gen. /
Motor
Busbar
3-phase
Busbar
1-phase
Differential
87T/G/M/L
87 N
---
---
---
Overcurrent-time, phases
50/51
---
Overcurrent-time, 3I0
50N/51N
---
---
Overcurrent-time, earth
50G/51G
46
---
---
49
---
49
---
24
Breaker failure
50 BF
---
38
Lockout
86
Direct coupling 1
Direct coupling 2
Overexcitation V/Hz
*)
X Function applicable ;
74TC
Page 5
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
Communication features
Front interface
System interface
DIGSI4
WEB Monitor
Optical double-ring
module
IEC60870-5-103
Profibus FMS
Profibus DP
DNP3.0
Modbus
ASCII/RTU
DIGSI4 operation
modem
connection
RTD box
Time Synchronising
IRIG-B (GPS)
DCF77
Page 6
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
General Applications
(1 of 2)
Two winding
transformer
1 or 3 phases
Three winding
transformer
1 or 3 phases
1 C.B. application
with
two winding transformer
7UT613
7UT633
7UT612
7UM62
7UT613
7UT633
Short lines
(2 ends)
Short lines
(3 ends)
1 C.B. application on
HV and LV side with
two winding transformer
7UT635
7UT613
7UT633
7UT612
Page 7
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
General Applications
(2 of 2)
Generator/Motor longitudinal or
transversal differential protection
High-impedance
Restricted Earth Fault Protection
G/
M
3~
7UT612
7UM62
7UT6xx
Unit Protection
(Overall Differential)
IEE input
of the unit
7UT63
5
G
3
~
Page 8
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
M
1
S
1
S
2
M
2
X1
Main
protect.
object
M
3
0105
0112
0113
0120
0124
0127
X4
S
3
M
4
X2
7UT63
5
Further
protected
object
Sides:
S1
High voltage side (HV)
S2
Low voltage side (LV)
S3
Low voltage side (LV)
Measuring locations 3-phase , assigned
M1
assigned to the main protected object (side 1)
M2
assigned to the main protected object (side 2)
M3
assigned to the main protected object (side 3)
Measuring locations 3-phase , non-assigned
M4
not assigned to the main protected object
Protected Object
Differential Protection
REF Protection
DMT/IDMT Phase
DMT/IDMT Earth
DMT 1Phase
3 phase Transformer
Enabled
Enabled
Definite Time only
Definite Time only
Enabled
4
3
3
S1:M1, S2:M2, S3:M3
Side 1 earth
Measurement location 4 earth
not connected
connected/not assigned
1A/5A current input
sensitive current input
not assigned measuring loc. 4
Measuring Location 4
Auxiliary CT IX1
Auxiliary CT IX4
Page 9
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
M
1
S
1
Main
protect.
object
Protected Object
Differential Protection
REF Protection
DMT/IDMT Phase
DMT 1Phase
3 phase Transformer
Enabled
Enabled
Definite Time only
Enabled
X1
CT-Numbers
0211
No. of connected Meas. Loc.
0212
No. of assigned Meas. Loc.
0213
No. of sides
CT-Assign
0222
Assignment at 2 assig.
Meas.Loc./2 sides
0251
Auxiliary CT IX1 is used as
0252
Auxiliary CT IX2 is used as
0253
Auxiliary CT IX3 is used as
0255
Type of auxiliary CT IX3
Transf.
.
0313
Starpoint of Side 1 is
0314
Transf. Winding Connection Side 1
.
0323
Starpoint of Side 2 is
0324
Transf. Winding Connection Side 2
0325
Vector Group Numeral of Side 2
Funct.
0413
REF assigned to
0420
DMT/IDMT Phase assigned to
0427
DMT Phase assigned to
X3
S
2
M
2
7UT6
13
Starpointbilder
X2
Sides:
S1
High voltage side (HV)
S2
Low voltage side (LV)
2
2
2
S1:M1, S2:M2
Side 1 earth
Side 2 earth
connected/not assigned
sensitive current input
Solid Earthed
Y (Wye)
Solid Earthed (!!)
D (Delta)
11
Side 2
Side 1
Auxiliary CT IX3
Setting Group A
Yes (Io- correction Side 1)
No
Page 10
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
RS485 interface
7XV5662-(x)AD10
7XV5662-(x)AD10
Page 11
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
Tripping Characteristic
Reasons for this shape of characteristic
x
IDiff
InO
3.0
2.5
Trip
Slope 2
Total
2.0
Block
1.5
CTerror
1.0
Slope 1
Tapchanger
0.5
IDiff>
0
Magnet.
current
0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
IRest InO
Page 12
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
Tripping Characteristic
(1 of 2)
Tripping Characteristic 7UT6
I Diff
InO
1231 IDiff>>
7
1243A
SLOPE
2
6
45
Block
Trip
4
*
)
3
2
1
1221 IDiff>
0 0
Add-on
Stabilization
1241A
SLOPE
1
1242A
1256A
BASE POINT 1
I-ADD ON STAB
1244A
BASE POINT 2
10
12
14
I Rest
InO
16
flexible adaptation to various transformers, e.g. with tap changer or different Cts
high stability against external faults with Ct saturation
IDiff >>: fast tripping for solid short-circuits within one period
Page 13
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
Page 14
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
I Diff
InO
Criterion:
Supervision of
restraint current
1231 Idiff>>
Start-up characteristic
1221
Idiff>
Steady-state
characteristi
c
Trip
45
5
4
Increase
of pickup
3
2
Block
1
0 0
10
12
14
16
Page 15
Jul-06
Author
I Rest
InO
Siemens AG 2006
Power Transmission and Distribution
The REF can be stetted to 0.1 I/INO (min. 0.05) and is therefore more sensitive as
the Differential Protection (even without load).
Page 16
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
Char. for
= 180
Blockin
g
-0.3
-0.2
-0.1
180 > 90
extended TripArea
Trippin
g
0.
0
+0.1
90 0
basic Trip-Area
calculation of the basic wave and the complex vectors of I0' and I0"
evaluation of the modulus and angle between I0' and I0"
sensitive fault detection starting with 5% transformer nominal current
Page 17
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
CT Requirements
Request:
k ALF k ALF_N
k ALF k ALF_N
(1 of 2)
R
R
R
R
ct
ct
ct
R
R
b
'
b
R
R
b
'
b
IP
I NCtPrim
IP
I NCtPrim
for : T P 100ms
for : T P 100ms
where:
kALF_N = rated Accuracy Limiting Factor
kALF = actual Accuracy Limiting Factor
Rct = secondary winding resistance
Rb = actual resistive burden
Rb = rated resistive burden
IP = max. primary symmetrical short circuit current TP = Primary (Net-) Time constant
ct
7UT6
80m , 2.5 mm2
2000/1A
10P10,
10VA
Rct = 2
50m , 4 mm2
Wind.
1
0.1
Explanation:
5P20: kALF_N = 20
Wind.
2
0.1
11 kV
Page 18
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
CT Requirements
(2 of 2)
Side 2 (LV):
Side 1 (HV):
Nominal transformer current:
SN
38100kVA
InO1
200A
3 U N1
3 110kV
InO 2
I P_1
c InO1
1.1 200A
100%
100% 2200A
uk
10%
R 'b
Sb
I
2
NCtS
15VA
15
1A 2
2l
R Relay
q
k ALF 20
160m 0.0175
2.5mm
mm 2
m 0.1 1.22
2
IP
I NCTprim
c InO 2
1.1 2000A
100%
100% 22000A
uk
10%
1 15
144
1 1.22
k ALF 144 4
I P_2
SN
38100kVA
2000A
3 U N2
3 11kV
R 'b
Sb
I
2
NCtS
10VA
10
1A 2
2l
R Relay
q
k ALF 10
2200A
44 OK!
200A
mm 2
m 0.1 0.54
2
100m 0.0175
4mm
2 10
47.2
2 0.54
k ALF 47.2 4
IP
I NCTprim
22000A
44 OK!
2000A
Page 19
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
(1 of 4)
WEB-Technology
Access to the relay with a WEB Monitor
Help system in
INTRANET /
INTERNET
http://www.siprotec.com
1. Serial connection
Direct or via modem with
a standard DIAL-UP
Network
2. HTML page view in a WEB Monitor
with the IP-address of the relay
http://141.141.255.160
Page 20
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
(2 of 4)
Page 21
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
(3 of 4)
Page 22
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
(4 of 4)
Page 23
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
Page 24
Jul-06
Author
Siemens AG 2006
Power Transmission and Distribution
Comparison of functions/settings
between 7UT51- and 7UT6 relays
7UT635
7UT633
7UT613
7UT612
7UT51
---
--5
--
--0
80
-----------------
X
3
--1
--3
30
X
--X
X
X
--X
X
X
3
X
1
X
3
30
X
X
X
X
X
X
X
X
X
3
X
1
X
3
30
X
X
X
X
X
X
X
X
X
3
X
1
X
3
30
X
--X
X
X
--X
X
---
Page 25
Jul-06