Differential Protection SIPROTEC7UT6

Siemens AG 2006

The 7UT6 Family

SIPROTEC 4
7UT6 differential protection relay for
transformers, generators, motors and
busbars

7UT612:
7UT613:
7UT633:
7UT635:

for two end protection objects


for three end protection objects
for three end protection objects
for five end protection objects

(1/3 x 19 housing 7XP20)


(1/2 x 19 housing 7XP20)
(1/1 x 19 housing 7XP20)
(1/1 x 19 housing 7XP20)

Page 2

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Hardware options

Device

7UT612

7UT613

7UT633

7UT635

Current Inputs (normal)


Current Inputs (sensitive)
Voltage Inputs (Uph / UE)
Binary Inputs
Binary Outputs
Life contact
LC Display

7 (7)*
1
--3
4
1
4 lines

11 (6)*
1**
3/1
5
8
1
4 lines

11 (6)*
1**
3/1
21
24
1
Graphic

14 (12)*
2**
-- 29
24
1
Graphic

1A, 5A, (1A, 5A, 0.1A) changeable (jumper position)

** changeable normal or sensitive (jumper position)

Page 3

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Scope of functions and Protection objects

Function

ANSI No.

Differential
87T/G/M/L
Restricted Earth fault
87 N
Overcurrent-time, phases
50/51
50N/51N
Overcurrent-time, 3I0
Overcurrent-time, earth
50G/51G
Overcurrent-time, single phase
Negative sequence
46
Overload IEC 60255-8
49
Overload IEC 60354 (hot spot)
49
Overexcitation V/Hz
24
Breaker failure
50BF
External temperature monitoring
38
Lockout
86
Measured value supervision
Trip circuit supervision
74TC
Direct coupling
Operational measured values

Protection Objects
Three-phase transformer
Single-phase transformer
Auto-transformer
Generator / Motor
Busbar, 3-phase (Branch point)
Busbar, 1-phase

Page 4

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Cross reference - functions and protected objects


Protection functions

ANSI No.

Transf.
3-phase

Transf.
1-phase

Autotransf.

Gen. /
Motor

Busbar
3-phase

Busbar
1-phase

Differential

87T/G/M/L

Restricted Earth Fault

87 N

---

---

---

Overcurrent-time, phases

50/51

---

Overcurrent-time, 3I0

50N/51N

---

---

Overcurrent-time, earth

50G/51G

Overcurrent-time, single phase


Negative sequence

46

---

---

Overload IEC 60255-8

49

---

Overload IEC 60354

49

---

24

Breaker failure

50 BF

---

External temperature monitoring


(thermo-box)

38

Lockout

86

Direct coupling 1

Direct coupling 2

Operational measured values

Overexcitation V/Hz

*)

Measured value supervision


Trip circuit supervision

X Function applicable ;

74TC

--- Function not applicable ;

*) only 7UT613 / 633

Page 5

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Communication features

Flexibility due to plug in modules


Compatibility to international standards
RS232/RS485 electrical
module

Front interface

System interface

DIGSI4
WEB Monitor

Service interface (s)


Fibre-optic module

Optical double-ring
module

IEC60870-5-103
Profibus FMS
Profibus DP
DNP3.0
Modbus
ASCII/RTU

DIGSI4 operation
modem
connection
RTD box
Time Synchronising
IRIG-B (GPS)
DCF77

Page 6

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

General Applications

(1 of 2)

Two winding
transformer
1 or 3 phases

Three winding
transformer
1 or 3 phases

1 C.B. application
with
two winding transformer

7UT613
7UT633
7UT612
7UM62

7UT613
7UT633

Short lines
(2 ends)

Short lines
(3 ends)

1 C.B. application on
HV and LV side with
two winding transformer

7UT635
7UT613
7UT633

7UT612

Page 7

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

General Applications

(2 of 2)

Generator/Motor longitudinal or
transversal differential protection
High-impedance
Restricted Earth Fault Protection

G/
M
3~
7UT612
7UM62

7UT6xx

Unit Protection
(Overall Differential)

IEE input
of the unit

7UT63
5

G
3
~

Page 8

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Terminology of a topology (Example 1)


Device Configuration

M
1
S
1

S
2
M
2

X1

Main
protect.
object


M
3

0105
0112
0113
0120
0124
0127

X4

S
3

M
4
X2

7UT63
5

Further
protected
object

Sides:
S1
High voltage side (HV)
S2
Low voltage side (LV)
S3
Low voltage side (LV)
Measuring locations 3-phase , assigned
M1
assigned to the main protected object (side 1)
M2
assigned to the main protected object (side 2)
M3
assigned to the main protected object (side 3)
Measuring locations 3-phase , non-assigned
M4
not assigned to the main protected object

Protected Object
Differential Protection
REF Protection
DMT/IDMT Phase
DMT/IDMT Earth
DMT 1Phase

3 phase Transformer
Enabled
Enabled
Definite Time only
Definite Time only
Enabled

Power System Data 1


CT-Numbers
0211
No. of connected Meas. Loc.
0212
No. of assigned Meas. Loc.
0213
No. of sides
CT-Assign
0222
Assignment at 3 assig.
Meas.Loc./3 sides
0251
Auxiliary CT IX1 is used as
0252
Auxiliary CT IX2 is used as
0253
Auxiliary CT IX3 is used as
0254
Auxiliary CT IX4 is used as
0255
Type of auxiliary CT IX3
0256
Type of auxiliary CT IX4
Funct.
0413
REF assigned to
0420
DMT/IDMT Phase assigned to
0424
DMT/IDMT Earth assigned to
0427
DMT Phase assigned to

4
3
3
S1:M1, S2:M2, S3:M3
Side 1 earth
Measurement location 4 earth
not connected
connected/not assigned
1A/5A current input
sensitive current input
not assigned measuring loc. 4
Measuring Location 4
Auxiliary CT IX1
Auxiliary CT IX4

Auxiliary measuring locations 1-phase


X1
assigned to the main protected object (side 1)
X2
not assigned to the main protected object
X4
not assigned to the main protected object

Page 9

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Terminology of a topology (Example 2)


Device Configuration
0105
0112
0113
0120
0127

M
1
S
1

Main
protect.
object

Protected Object
Differential Protection
REF Protection
DMT/IDMT Phase
DMT 1Phase

3 phase Transformer
Enabled
Enabled
Definite Time only
Enabled

Power System Data 1

X1

Measuring locations 3-phase , assigned


M1
assigned to the main protected object (side 1)
M2
assigned to the main protected object (side 2)

CT-Numbers
0211
No. of connected Meas. Loc.
0212
No. of assigned Meas. Loc.
0213
No. of sides
CT-Assign
0222
Assignment at 2 assig.
Meas.Loc./2 sides
0251
Auxiliary CT IX1 is used as
0252
Auxiliary CT IX2 is used as
0253
Auxiliary CT IX3 is used as
0255
Type of auxiliary CT IX3
Transf.
.
0313
Starpoint of Side 1 is
0314
Transf. Winding Connection Side 1
.
0323
Starpoint of Side 2 is
0324
Transf. Winding Connection Side 2
0325
Vector Group Numeral of Side 2
Funct.
0413
REF assigned to
0420
DMT/IDMT Phase assigned to
0427
DMT Phase assigned to

Auxiliary measuring locations 1-phase


X1
assigned to the main protected object (side 1)
X2
assigned to the main protected object (side 2)
X3
not assigned to the main protected object

Differential Protection-Settings Group A


1211A Diff-Prot. with meas. Earth Curr. S1
1212A Diff-Prot. with meas. Earth Curr. S2

X3

S
2
M
2

7UT6
13

Starpointbilder
X2

Sides:
S1
High voltage side (HV)
S2
Low voltage side (LV)

2
2
2
S1:M1, S2:M2
Side 1 earth
Side 2 earth
connected/not assigned
sensitive current input
Solid Earthed
Y (Wye)
Solid Earthed (!!)
D (Delta)
11
Side 2
Side 1
Auxiliary CT IX3

Setting Group A
Yes (Io- correction Side 1)
No

Page 10

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Application: Transformer Data Base

RS485 interface

7XV5662-(x)AD10

7XV5662-(x)AD10

Two RTD boxes can be connected to the service interface (RS485)


Monitoring of up to 12 measuring points (6 per RTD box)
each having two thresholds (Alarm stages)

Display of the temperature as measured values


directly at the RTD box (can be used as stand alone device as well)
in the protection relay

Monitoring of threshold values


One dedicated input can be used for the hot spot calculation (oil temp.)
The type of sensor can be selected for each measuring point (Pt100,
Ni100, Ni120)

Page 11

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Tripping Characteristic
Reasons for this shape of characteristic
x

IDiff
InO
3.0

2.5

Trip

Slope 2
Total

2.0

Block

1.5

CTerror

1.0
Slope 1

Tapchanger

0.5
IDiff>
0

Magnet.
current
0

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

IRest InO

Example: Transformer with Tap changer

Page 12

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Tripping Characteristic

(1 of 2)
Tripping Characteristic 7UT6

I Diff
InO

1231 IDiff>>

7
1243A
SLOPE
2

6
45

Block

Trip

4
*
)

3
2
1
1221 IDiff>

0 0

Add-on
Stabilization

1241A
SLOPE
1

1242A
1256A
BASE POINT 1
I-ADD ON STAB
1244A
BASE POINT 2

10

12

14

I Rest
InO

16

*) Slope for Add-on Stabilization:


7UT6 Slope 1 ; 7UT5 Slope 1

flexible adaptation to various transformers, e.g. with tap changer or different Cts
high stability against external faults with Ct saturation
IDiff >>: fast tripping for solid short-circuits within one period

Page 13

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Tripping Characteristic - Pickup of differential function

For triggering of internal tasks, events and fault records the


differential protection function needs a pickup information. This
pickup becomes active, if the differential current or the restraint
current is over an internal threshold
(dotted line). Each external large current leads to a pickup.
Pickup doesnt always mean internal failure!

Page 14

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Tripping Characteristic - Motor Start


Typical for motor start is the starting current and the superimposed dc component with a large
time constant. The two Ct-sets may transform this dc component differently.
The result is a differential current and the risk of an over-function is given.
Detection of motor starting: Increases the pick-up values for a settable time
Tripping Characteristic 7UT6 for Motor start

I Diff
InO

Criterion:
Supervision of
restraint current

1231 Idiff>>

Start-up characteristic

IRest > I-Restr. Startup


(until 2 I/InO)
than the
Start-Factor (max. 2)
is active for the time:
T Start Max
(Duration of dynamical
increasing of pickup)

1221
Idiff>

Steady-state
characteristi
c

Trip

45

5
4

Increase
of pickup

3
2

Block

1
0 0

10

12

14

16

Page 15

Jul-06

Author

I Rest
InO

Siemens AG 2006
Power Transmission and Distribution

Low impedance Restricted Earth Fault (REF) (1 of 2)


The REF measures the Neutral current of the object ( ISP = 3I0 ) and,
depending on the angle () between 3I0 and the also measured sum
of the phase currents
( 3I0 = IL1 + IL2 + IL3 ), decides for internal or external fault.
The sensitivity of the REF is almost independent from the load of the object.
(The sensitivity of the Differential Function especially for high ohm faults will be
reduced by the load due to the slope of its Tripping Characteristic ).

The REF can be stetted to 0.1 I/INO (min. 0.05) and is therefore more sensitive as
the Differential Protection (even without load).

Page 16

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Low impedance Restricted Earth Fault (REF) (2 of 2)


IREF> = Setting value (Trip Threshold)

Tripping Characteristic REF


IREF
IREF

Char. for
= 180

IRest = Restraint current


IREF = 3I0

1) for basic Trip-Area (0 90):


3

= 3I0 and must Ibe /I IREF


>
IREF
Characteristic_1):
REF
REF> = 1
(no restraining current IRest effective)

2) for extended Trip-Area (90 180):


Characteristic_2):
IREF = IREF> +
kIRest
where IRest = (3I0-3I0-3I0+3I0)

Blockin
g
-0.3

-0.2

-0.1

180 > 90
extended TripArea

IRest includes the direction

Trippin
g

0.
0

+0. '' ' +0.


2 3I0 3I0 3

+0.1

90 0
basic Trip-Area

calculation of the basic wave and the complex vectors of I0' and I0"
evaluation of the modulus and angle between I0' and I0"
sensitive fault detection starting with 5% transformer nominal current

Page 17

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

CT Requirements
Request:

k ALF k ALF_N
k ALF k ALF_N

(1 of 2)
R
R
R
R

ct
ct
ct

R
R

b
'
b

R
R

b
'
b

IP
I NCtPrim
IP
I NCtPrim

for : T P 100ms
for : T P 100ms

where:
kALF_N = rated Accuracy Limiting Factor
kALF = actual Accuracy Limiting Factor
Rct = secondary winding resistance
Rb = actual resistive burden
Rb = rated resistive burden
IP = max. primary symmetrical short circuit current TP = Primary (Net-) Time constant
ct

Example: (TP 100ms)


110 kV
200/1A
5P20,15
VA
Rct = 1
38.1 MVA
110/11 kV
uk = 10%

7UT6
80m , 2.5 mm2

2000/1A
10P10,
10VA
Rct = 2

50m , 4 mm2

Wind.
1
0.1

Explanation:
5P20: kALF_N = 20

Wind.
2
0.1

11 kV

Page 18

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

CT Requirements

(2 of 2)
Side 2 (LV):

Side 1 (HV):
Nominal transformer current:

Nominal transformer current:

SN
38100kVA
InO1

200A
3 U N1
3 110kV

InO 2

Maximum through flowing current:

Maximum through flowing current:

I P_1

c InO1
1.1 200A

100%
100% 2200A
uk
10%

where: c = factor for max. possible over voltage


Rb

R 'b

Sb
I

2
NCtS

15VA
15
1A 2

2l
R Relay
q

k ALF 20

160m 0.0175
2.5mm

mm 2
m 0.1 1.22
2

IP
I NCTprim

c InO 2
1.1 2000A
100%
100% 22000A
uk
10%

where: c = factor for max. possible over voltage


Rb

1 15
144
1 1.22

k ALF 144 4

I P_2

SN
38100kVA

2000A
3 U N2
3 11kV

R 'b

Sb
I

2
NCtS

10VA
10
1A 2

2l
R Relay
q

k ALF 10

2200A
44 OK!
200A

mm 2
m 0.1 0.54
2

100m 0.0175
4mm

2 10
47.2
2 0.54

k ALF 47.2 4

IP
I NCTprim

22000A
44 OK!
2000A

Page 19

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Commissioning and operating aids

(1 of 4)

WEB-Technology
Access to the relay with a WEB Monitor
Help system in
INTRANET /
INTERNET
http://www.siprotec.com

The homepage of the relay


is:http://141.141.255.160
IP-address is set with DIGSI
4
on front- or rear service port

1. Serial connection
Direct or via modem with
a standard DIAL-UP
Network
2. HTML page view in a WEB Monitor
with the IP-address of the relay
http://141.141.255.160

WEB server in the relays


firmware
Server sends its HTMLpages
and JAVA-code to the WEB
Monitor
after a DIAL-UP connection

Page 20

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Commissioning and operating aids

(2 of 4)

Transformer YNd11d11, 110/11/11kV, 38.1MVA, IL2S2 wrong polarity

Page 21

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Commissioning and operating aids

(3 of 4)

Transformer YNd11d11, 110/11/11kV, 38.1MVA, IL2S2 wrong polarity

Page 22

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Commissioning and operating aids

(4 of 4)

Page 23

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Benefits for the Customer


Protection relay with flexible adaptation to the transformer/generator/motor or short line. Programming of the device data in the relay.
Reduced amount of wiring by direct connection to the main Cts.
No matching transformers and therefore no wiring errors.
Zero sequence current can be measured (in the 7UT6).
Sensitivity for single-pole faults in the transformer increased by 33% .
Flexible adaptation of the tripping characteristic to various main Cts,
tapped transformers.
Exact discrimination between the short circuit condition and the inrush
condition by on-line analysis of the harmonics. Fast tripping for
high-current faults. Ct saturation detector for external faults.
Thermal monitoring of one transformer winding (including RTD meas.)
Back-up DMTL/IDMTL with reverse blocking for one winding.
Sensitive short circuit protection for faults winding against earth.
External Trip functions
Various commissioning aids.
Common DIGSI 4 software

Page 24

Jul-06

Author

Siemens AG 2006
Power Transmission and Distribution

Comparison of functions/settings
between 7UT51- and 7UT6 relays
7UT635

7UT633

7UT613

7UT612

7UT51

Tripping Characteristic: Base point for slope 1 settable

---

Tripping Characteristic: Increasing of characteristic at start


Tripping Characteristic: minimum setting for add-on stabilization I/InO
Tripping Characteristic: cross block for add-on stabilization
Tripping Characteristic: slope of add-on stabilization / slope 1
Tripping Characteristic: Increasing of characteristic due to DC offset in IDiff
Transformer inrush: Default setting for cross block 2. harmonic [cycles]
Transformer inrush: Default setting for 5. harmonic [%]
Negative sequence current protection
Over excitation protection [V/Hz]
Overload protection IEC 60354 (hot spot)
Single phase busbar differential
High impedance Restricted Earth Fault
Voltage measurements
Temperature monitoring (via Thermo-box / RS 485)
All functions can be enabled at the same time

--5
--
--0
80
-----------------

X
3
--1
--3
30
X
--X
X
X
--X
X

X
3
X
1
X
3
30
X
X
X
X
X
X
X
X

X
3
X
1
X
3
30
X
X
X
X
X
X
X
X

X
3
X
1
X
3
30
X
--X
X
X
--X
X