Escolar Documentos
Profissional Documentos
Cultura Documentos
QH
E
W net
QL
Hot Region
q2-3
3
2
CONDENSER
Expansion
valve
W 1-2
Compressor
EVAPORATOR
4
q4-1
Source
Cold Region
Condenser
pressure
Condenser
Evaporator
Evaporator
pressure
1
4
w = h1- h2
Q4-1 = h1- h4 S
q1-2 = h3- h2
T
2
Condenser
temperature
Evaporator
temperature
S
The cycle:
1-2 isentropic compression of the vapor, from the evaporating to the condensing
pressures
2 -3 Condensation of the high pressure vapor during which heat is transferred to the high
temperature region.
3 -4 Adiabatic throttling of the condensed vapor from condensing to the evaporating
pressure.
4 -1 Evaporating of the low pressure liquid during which heat is absorbed from the low
temperature source.
CO Pr ef
q 4 1 h1 h 4
w
h 2 h1
EQUIPMENT
RC 713 COMPUTER LINKED REFRIGERATION UNIT (P.A HILTON)
EXPERIMENTAL PROCEDURES
1. start the experiments at a condenser saturation temperature of 20C
2. Enter programmed one and increase the evaporator load to approximately 10%.
3. Return to the main menu and enter programmed two. Select no print out and display these
three parameters, 5. Condensing Temperature; 2. Refrigerant Flow Rate; and 14 Cooling water
Flow Rate.
4. By small adjustment of the cooling water, flow rate the condensing temperature of 20C may
be maintain. The system is stable when all three parameters show generally horizontal lines
(approximately 1 minutes)
5. When the system is stabilized, return to the main menu and select programmed 1 with print out
option (raw and calculated data)
6. Then, increase evaporator load (by 10%) and print out the result. Repeat until evaporator load
is at 80%.
RESULTS
By using data obtained from the experiments, for one set of data, plot the data on the Pressure
enthalpy (p-h) diagrams, and show the calculations of the parameters below using the energy
equation based on enthalpy:
a.
Refrigeration duty
Q 4-1
b.
Compressor work
W 1-2
c.
Heat rejected from condenser Q 2-3
d.
Load 0
Load 15
W 1-2 = mR134 ( h1 h2 )
= 0.06061 (313.4 335.22)
= - 1.32kW
W 1-2 = mR134 ( h1 h2 )
= 0.08199 ( 327.03 341.85)
= - 1.22 kW
Q 2-3 = mH2O ( h3 h2 )
= 0.00865(121.17 335.22)
= -185 kW
Q 2-3 = mH2O ( h3 h2 )
= 0.00856(122.25 341.85)
= -1.88 kW
Load 30
Load 45
W 1-2 = mR134 ( h1 h2 )
= 0.08191 ( 326.84 346.80)
= - 1.63 kW
W 1-2 = mR134 ( h1 h2 )
= 0.08164 ( 328.97 351.01)
= - 1.8 kW
Q 2-3 = mH2O ( h3 h2 )
= 0.00856(123.81 346.80)
= -1.91 kW
Q 2-3 = mH2O ( h3 h2 )
= 0.00837(124.03 351.01)
= -1.9 kW
Load 60
Load 75
Q 4-1 = mR134 (h1 h4)
= 0.08111 (337.90 125.53)
= 11.26 kW
W 1-2 = mR134 ( h1 h2 )
= 0.08111 ( 337.90 357.32)
= - 1.58 kW
Q 2-3 = mH2O ( h3 h2 )
= 0.00856(125.53 357.32)
= -1.98 kW
COPref = h1 h4 = 337.90 125.53
h2 h1 357.32 337.90
= 10.94
Load
0
15
30
45
60
75
Q4-1
(kW)
W 1-2
(kW)
Q 2-3
(kW)
COP ref
8.56 x 10
8.56 x 10
8.56 x 10
8.37 x 10
8.37 x 10
8.56 x 10
11.65
16.79
16.63
16.73
17.08
11.26
-1.32
-1.22
-1.63
-1.8
-1.52
-1.58
-1.85
-1.88
-1.91
-1.9
-1.76
-1.98
8.81
13.82
10.17
9.3
11.26
10.94
Evaporator
Condenser
Refrigerant
Cooling water
temp (C)
exit temp
flow rate
(C)
(kg/s)
60.61 x 10
81.99 x 10
81.91 x 10
81.64 x 10
81.11 x 10
81.11 x 10
10.39
23.69
30.98
38.10
41.90
45.01
44.42
49.87
55.34
59.22
63.10
66.30
DISCUSSIONS
1. Fill in the parameters from one set of experiment data into the refrigeration
system diagram.
Load 60
Qc = -3.76 Watt
3
2
CONDENSER
4
EVAPORATOR
Wc = -1.52 Watt
Qe = 17.08
CONCLUSION
Refrigeration is the device that can work as heat rejecter or heat injector to the
working space. Refrigeration process is based on Reversed Carnot cycle process. In this
process, it will involve in input work (compression), heat rejection (condensation) and
heat absorbed (evaporation).
To determine the Coefficient of Performance of refrigeration system can be
determine by this equation
COP = _Q_ = h1 h4
W
h2 h1
Coefficient of performance of the refrigeration depends on the workability of the
refrigerant and also the load. In this experiment, as the load increase the COP will reduce
and the temperature at the condenser increase. This condition will affect the value of COP
and the workability of the refrigeration system.
The temperature of load supply must equal to the evaporation temperature of the
refrigerant in order to maximize the COP of the refrigerant system. Choosing a suitable
refrigerant also critical. Refrigerant chose must suitable to work on the load applied. The
COP of the refrigerant system also can be increased with maximizing the workability of
compressor (comp).