General Input :-
L= 9.30 m
Direction of
Seismic Force
tr= 0.20 m
tw= 0.30 m
HL= 2.20 m
L= 10.0 KN/m3
B= 9.30 m
Rectangular Tank Plan
c= 24.0 KN/m3
fc= 35.0 N/mm2
g= 9.81 m/sec2
Importance factor I
Rc
= 1.00
= 1.00
Ri
= 2.00
SEISMIC ZONE
Z factor
Soil Profile
Soil Profile Type
Na For Zone 4 only
Nv For Zone 4 only
Ca
Cv
Ts =0.40Cv/Ca
2B
0.2
Very Dense
SC
1
1
0.240
0.320
0.533
Hw= 2.95 m
, L / HL = 4.23
= 0.27 WL
,Ww = 815.6 KN
= 519.1 KN
,Wr = 442.4 KN
= 0.71 WL
2-Calculation the Height of center of gravity for impulsive hi & convective hc components:
= 0.825 m
= 1.149 m
3-Calculation the fundamental period of oscillation of the tank for impulsive Ti & convective Tc components:
= 1777.1 KN
= 1.48 m
= 3.05 m
,
= 102802.2 KN/m
= 1.22 m
= 0.26 sec
= 4.32 sec
, = (
)
= 289.7 KN/m
Page 1 of 13
Seismic Loads for Liquid-Containing Rectangular RC Tank, According ACI 350.3-06 , Appendix B Method
Based on 1997 Uniform Building Code
Project :Building :Element:Location:-
Project
Building
Rev1.0
Element
Location
M.A.S.
= 244.7 KN
= 155.7 KN
6-Dynamic force distribution above base per Wall perpendicular to ground motion:
Pi Top
= 1.0 KN/m2
Pi Bottom
= 6.7 KN/m2
Pc Top
= 2.9 KN/m2
Pc Bottom
= 2.2 KN/m2
= 4.3 KN/m2
= 4.3 KN/m2
= 1.0 KN/m2
= 6.7 KN/m2
Wall Inertia Force Pw
Impulsive Force Pi
= 4.3 KN/m2
= 8.1 KN/m2
= 2.9 KN/m2
= 2.2 KN/m2
ConvectiveForce Pc
= 13.2 KN/m2
Total Seismic Force E per Wall
perpendicular to ground motion
Dynamic force distribution above base per Wall perpendicular to ground motion
7- Load Cominations:
Note that, the Calculated Seismic Force E above is based on Strength-level Forces (ultimate loads).
For allowable stresses Design (ASD) Method (service loads), the design seismic forces shall be reduced by a factor of 1.4
ACI 350.3-06, Appendix B, Clause B.5
For Ultimate Strength Design method (factored loads), follow ACI 350-06, Clause 9.2.1 load combinations.
Page 2 of 13
UBC 97 Tables
TABLE 16-ISEISMIC
Zone
1
2A
2B
3
4
Ct Values
0.0853
0.0731
0.0488
Rock
Stiff Soil
Soft Soil
Weak Soil
UBC 97 Tables
TABLE 16-ISEISMIC ZONE FACTOR Z
Z
Zone
0.075
1
0.15
2A
0.2
2B
0.3
3
0.4
4
Ct Values
0.0853 (0.035 in ft)for steel moment-resisting frames
0.0731 (0.030 in ft)for
andRC
eccentrically
moment-resisting
braced frames
frames
0.0488 (0.020 in ft)for all other buildings
TABLE 16-JSOIL PROFILE TYPES
Soil
Profile
Descripti Soil Profile
Type
on
Hard
SA
Rock
SB
Rock
Very
SC
Dense
SD
Stiff Soil
SE
Soft Soil
Weak Soil
SF
0.08
0.15
SC
0.13
0.25
SD
0.18
0.32
SE
0.26
0.5
SF
QSEISMIC COEFFICIENT Ca
Z Seismic Zone Factor
0.2
0.3
0.16
0.24
0.2
0.3
0.24
0.33
0.28
0.36
0.34
0.36
0
0
0.4
0.32
0.4
0.4
0.44
0.36
0
RSEISMIC COEFFICIENT Cv
Z Seismic Zone Factor
0.2
0.3
0.16
0.24
0.4
0.32
0.2
0.3
0.4
0.32
0.45
0.56
0.4
0.54
0.64
0.64
0.84
0.96
Rev0
Rev1.0
4-Nov-14
1- adding calculation for Kc, which can be used for dynamic analysis in Cell H46
2- Correction of Ww Calculation in cell G35 according "Mr. Siwalak Khamnurak" Note, missing multiplying by the wall thk
References
1-ACI 350.3_06 Seismic Design of Liquid-Containing Concrete Structures and Commentary
2-SP-2002 IBC2000 ACI 350.3R-01 Design_of_liquid_containing_concrete_structures_for_earthquake_forcesby Javeed A. Munshi-2
3- Tank Wall Stiffness Calculation K :
a- using ACI 350.3-06, R9.2.4 which developed For fixed-base, free-top cantilever walls, such as in open-top tanks
- on my opinion- the same expression can be used for fixed wall in tank base and hinged at roof slab, as below
b- using analysis model with assuming Lateral Force F= 10 KN (e.g) at C.G of tank to obtain a deflection , thus tank stiffness K = F
for more information see Guidelines for Seismic Design of Liquid Storage Tanks, Example 1/Page 59 which you can download