Product/Technical Bulletin
Issue Date
A350E
0899
System 350
A350E Electronic Cooling Control
Modular Design
Minimum Setpoint
Selections
Plug-together Connectors
and 35 mm DIN Rail
Mounting
Interchangeable
Temperature Sensors
1
www.johnsoncontrols.com
A pplication
The A350E Cooling Control can be used as a
standalone device or in conjunction with other
System 350 plug-together accessory modules to
control a wide variety of single or multiple-stage
equipment. Typical applications include:
beverage/milk coolers
chiller staging
setpoint
differential
minimum setpoint
24V
COM
COM
SEN
Setpoint
Dial
Module
Connector
O peration
IMPORTANT:
Setpoint Adjustment
DIFF
(Differential
Potentiometer)
Minimum
Setpoint Jumper
Relay
LED Indicator
Relay
20F (-7C)
40F (4C)
30F (-1C)
OFF
N.C. COM
N.O.
Relay Output Terminals
Differential Adjustment
(+)
Differential
ON
Setpoint
Temperature
OFF
OFFSET
OFF
ON = Energized
OFF = De-energized
(-)
A dd-On Modules
The S350 Stage Modules, D350 Digital Temperature
Display Module, and Y350R Power Module connect
together and plug into a connector on the right side of
the A350E. The maximum number of add-on modules
is listed in Table 1.
Number of
S350A or
S350C
Modules
(with
1 S350P)
Allowed
Number
of S350A
or S350C
Modules
(with
2 S350Ps)
Allowed
Y350R
External
Class 2
Transformer
Power
Source
D imensions
Mounting Slots
for No. 6 Screws
3/16 (4)
1/2 (13)
2 15/16
(75)
A350E
ON
5 (127)
4 (102)
1 9/16
(40)
2 3/8 (61)
1 3/16
(31)
DIN Rail
Mount
7/16 (11)
Sensor
2 3/8 (61)
1/4 (6)
9 3/4 (248)
3 (76)
7/8
(22)
2 (50)
Conduit 7/8
Hole (22)
Note:
24
VAC
L1
2
Load
Load
Sensor Connection
Shielded cable is not generally required for sensor
wiring on runs of less than 50 ft (15.2 m), but is
recommended for lengths greater than 50 ft (15.2 m).
Connect the shield to the COM sensor terminal on the
A350E. (See Figure 2 for terminal location.) Sensor
A99BA-200, which includes a shielded cable, is
available if needed.
Note:
Wire
Gauge
Sensor Included
A350EA-4C
152
A350EB-1C
No Sensor Included
94
A350EB-1D
No Sensor Included
200
61
A350EB-2C
No Sensor Included
124
38
Feet
Meters
14 AWG
800
244
16 AWG
500
18 AWG
310
20 AWG
22 AWG
Shield (Connect
to COM on A350E.)
A350E
Y350R
S350A
S350A
S350A
Load
Load
Load
D350
24V
COM
COM
SEN
NC
COM
NO
120 VAC
Load
djustments
A
Follow this procedure to set up the A350E for the
heckout Procedure
C
Follow this procedure to verify the A350E control is
desired operation.
(+)
Setpoint
Temperature
Differential
ON
Differential
ON
Differential
ON
Differential
ON
OFF
OFF
OFF
OFFSET
OFFSET
OFFSET
Differential
OFF
OFFSET
OFF
roubleshooting
T
If the control system does not function properly, use
the following procedures to determine the cause of the
problem:
1. Check for proper voltage applied to the A350E.
a. Connect a Digital Voltmeter (DVM) between
the 24V (+) and COM (-) terminals located on
the controls left side terminal block (Figure 2).
ON = Energized
OFF = De-energized
(-)
A350E
Stage 1
S350A
Stage 2
S350A
Stage 4 S350A
S350A
Stage 5
Stage 3
f.
260
120
240
220
100
200
180
80
160
140
60
120
40
100
80
20
60
40
0
20
0
-20
-20
-40
-40
500 700 900 1100 1300 1500 1700 1900 2100
Resistance (Ohms)
Figure 8: Temperature vs. Resistance Chart
3. Check the A350E for proper operation.
Note:
c.
N.O. Relay
Status
On
Closed
Off
Open
Setpoint
Dial Setting
(Ts)* - Differential
(Ts)*
For example:
70F (Ts)
- 5F (Differential)
65F (Setpoint Dial Setting)
O rdering Information
Table 5: System 350 Products
Item
Product Code
Number
A350EA-4C and
A350EA-1C
A350EA-2C
Description
D350AA-1C
D350BA-1C
Fahrenheit scale
Celsius scale
S350AA-1C
S350AB-1C
Fahrenheit Scale
Celsius Scale
S350CC-1C
S350PQ-1C
Power Module
Y350R-1C
Description
Outdoor Enclosure
BOX10A-600R
TE-6001-4
Cover
T-4000-2644
Conduit Adaptor
ADP11A-600R
Immersion Well
WEL11A-601R
BKT287-1R
BKT287-2R
PLT344-1R
WHA29A-600R*
WHA29A-603R
WHA29A-604R
3 ft (0.9 m)
25 ft (7.6 m)
50 ft (15.2 m)
S pecifications
Product
Supply Voltage
Power Consumption
Adjustment Setpoint
Range
Differential Adjustment
Range
SPDT Relay Output
Ambient Temperatures
Humidity
Sensor
Material
Minimum Setpoint
Short Circuit Detection
Agency Listings
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls Application Engineering at (414) 274-5535. Johnson Controls, Inc. shall not be liable for damages
resulting from misapplication or misuse of its products.