Escolar Documentos
Profissional Documentos
Cultura Documentos
1 of 8
http://e4electrical.blogspot.com/
12/17/2014 10:22 AM
2 of 8
http://e4electrical.blogspot.com/
2.Distance Relays
This Relay is used as over current relay in long transmission high
voltage lines. It is accurate than O/C & E/F RELAYS and we can figure
out the exact position of fault.So it is much helpful to locate the fault in
long tx.line.
4. Differential relays
The definition of such a relay is one that operates when the vector
difference of two or more similar electrical quantities exceeds a
predetermined amount.That means in a trans former we know it
primary and secondary voltages so the ratio of Pr. And Sec. Always
constant so if any abnormality occur the ratio will change and relay will
operate.This is also for equipment protection.
5.Master Relay
All the above relays are connected to master relay in a panel board
and it will operate the breaker.
12/17/2014 10:22 AM
3 of 8
http://e4electrical.blogspot.com/
No comments:
Protective scheme
Protective Scheme For Power System
Hi friends now we can see the protective action in a power system.Here i am going to explain you the very
basic protective scheme.Don't think this is all,the power system contain very complex protective schemes
because each and every devices are very costly and dangerous. Here i just illustrate only one P.T and C.T
actually each phase has its own C.T and P.T .
The C.T is always series to the mains and its secondary should be short circuited(ie.always in a closed
circuit).The P.T is always parallel with mains open circuited secondary.In most of the area of power system the
C.T is the protecting device, ie we take the current reference . P.T is mainly for the metering of voltage.I think at
the generating side only the frequency and voltage terms come into protective action.
Both the C.T and P.T has many number of secondary cores for various purposes. Mainly the C.T has
dedicated cores for Metering,Protection,Backup Etc..The cores has some standards also like 5P10,.5s
etc..according to the accuracy and other parameters.The C.T secondary measures in Ampere. it may be 1A to 5A
normally. The P.T secondary measures in voltage, and it is normally 110v AC. we can discuss about C.T and P.T
in the next post.........................THANK YOU
No comments:
12/17/2014 10:22 AM
4 of 8
http://e4electrical.blogspot.com/
L.A 11KV
P.T 33 KV side
12/17/2014 10:22 AM
5 of 8
http://e4electrical.blogspot.com/
No comments:
KVA,KW,KVAR,KWh,Kvar.....
As an electrical engineer we seen a lot as KW,MW,KVA
etc. These are some units related with power and energy. It
varies with the nature of the power and energy. Before that we
can just see what is reactive and real power.
REACTIVE POWER:
The book definition is it is the power absorbed by the inductor
or released by the capacitor. We know in AC circuit only the
inductance and capacitance are present. It may be a line
capacitance or winding inductance.It is the imaginary power
etc.
This reactive power is simply circulating power due to
the phase shift between the source and the loads. This
additional power that appears to be flowing requires the
equipment to be rated higher than that for a system operating
at unity. Obviously these circulating currents while
real..produce no useful work. It is the job of the Electrical
Engineer to correct the load reactance as close as possible to
unity to increase efficiency and reduce operational costs. That
means simply match the capacitance and inductance.
Start now,
Total power KVA = Kilo Volt Amp(v*I)
Real power
KW = Kilo Watt(v*I*cos)
Reactive power KVAR = Kilo Volt Amp Reactance (v*I*sin)
Total power KVA=KW+jKVAR
Power * Time= Energy
Eg:KW*Hour=KWh(unit of electrical energy)
12/17/2014 10:22 AM
6 of 8
http://e4electrical.blogspot.com/
1 comment:
12/17/2014 10:22 AM
7 of 8
http://e4electrical.blogspot.com/
At generator winding.
Actually where we handle the 3 phase supply directly,
we can prefer the star or delta connection. Previous post i
mentioned that only 3 phase loads are motors,so you may
confuse about the transformers, actually transformer is not a
load. It just change the voltage level.
Delta connection is also used to connect the windings of
most three-phase motors because the phase windings are
perfectly balanced and, therefore, do not require a neutral
connection.
Making a star connection has the advantage that two
voltages
become available a line voltage between any two phases,
and a
phase voltage between line and neutral which is connected to
the star point.
1 comment:
3 Phase Concept
12/17/2014 10:22 AM
8 of 8
http://e4electrical.blogspot.com/
No comments:
Home
Older Posts
12/17/2014 10:22 AM