Technical specifications

A.1

General technical specifications

Standards compliance
The S7-1200 automation system design conforms with the following standards and test
specifications. The test criteria for the S7-1200 automation system are based on these
standards and test specifications.
Note that not all S7-1200 models may be certified to these standards, and certification status
may change without notification. It is your responsibility to determine applicable certifications
by referring to the ratings marked on the product. Consult your local Siemens representative
if you need additional information related to the latest listing of exact approvals by part
number.

CE approval
The S7-1200 Automation System satisfies requirements and safety related objectives
according to the EC directives listed below, and conforms to the harmonized European
standards (EN) for the programmable controllers listed in the Official Journals of the
European Community.
EC Directive 2006/95/EC (Low Voltage Directive) "Electrical Equipment Designed for Use
within Certain Voltage Limits"
EN 61131-2:2007 Programmable controllers - Equipment requirements and tests
EC Directive 2004/108/EC (EMC Directive) "Electromagnetic Compatibility"
Emission standard
EN 61000-6-4:2007: Industrial Environment
Immunity standard
EN 61000-6-2:2005: Industrial Environment
EC Directive 94/9/EC (ATEX) "Equipment and Protective Systems Intended for Use in
Potentially Explosive Atmosphere"
EN 60079-15:2005: Type of Protection 'n'
The CE Declaration of Conformity is held on file available to competent authorities at:
Siemens AG
IA AS RD ST PLC Amberg
Werner-von-Siemens-Str. 50
D92224 Amberg
Germany

Easy Book
Manual, 03/2014, A5E02486774-AF

281

Technical specifications
A.1 General technical specifications

cULus approval
Underwriters Laboratories Inc. complying with:
Underwriters Laboratories, Inc.: UL 508 Listed (Industrial Control Equipment)
Canadian Standards Association: CSA C22.2 Number 142 (Process Control Equipment)
Note
The SIMATIC S7-1200 series meets the CSA standard.
The cULus logo indicates that the S7-1200 has been examined and certified by
Underwriters Laboratories (UL) to standards UL 508 and CSA 22.2 No. 142.

FM approval
Factory Mutual Research (FM)
Approval Standard Class Number 3600 and 3611
Approved for use in:
Class I, Division 2, Gas Group A, B, C, D, Temperature Class T3C Ta = 60 C
Class I, Zone 2, IIC, Temperature Class T3 Ta = 60 C
Canadian Class I, Zone 2 Installation per CEC 18-150
IMPORTANT EXCEPTION: See Technical Specifications for the number of inputs or outputs
allowed on simultaneously. Some models are de-rated for Ta = 60 C.
WARNING
Substitution of components can impair the suitability for Class I, Division 2 and Zone 2.
Repair of units should only be performed by an authorized Siemens Service Center.

ATEX approval
ATEX approval applies to DC models only. ATEX approval does not apply to AC and Relay
models.
EN 60079-0:2009: Explosive Atmospheres - General Requirements
EN 60079-15:2010: Electrical Apparatus for Potentially Explosive Atmospheres;
Type of protection 'nA'
II 3 G Ex nA IIC T4 or T3 Gc
Install modules in a suitable enclosure providing a minimum degree of protection of IP54
according to EN 60529, or in a location providing an equivalent degree of protection.
Attached cables and conductors should be rated for the actual temperature measured under
rated conditions.
The installation should ensure that transients are limited to less than 119 V. See Surge
immunity in this section.
IMPORTANT EXCEPTION: See Technical Specifications for the number of inputs or outputs
allowed on simultaneously. Some models are de-rated for Ta = 60 C.

Easy Book

282

Manual, 03/2014, A5E02486774-AF

Technical specifications
A.1 General technical specifications

C-Tick approval
The S7-1200 automation system satisfies requirements of standards to AS/NZS 2064
(Class A).

Korea Certification
The S7-1200 automation system satisfies the requirements of the Korean Certification (KC
Mark). It has been defined as Class A Equipment and is intended for industrial applications
and has not been considered for home use.

Maritime approval
The S7-1200 products are periodically submitted for special agency approvals related to
specific markets and applications. Consult your local Siemens representative if you need
additional information related to the latest listing of exact approvals by part number.
Classification societies:
ABS (American Bureau of Shipping)
BV (Bureau Veritas)
DNV (Det Norske Veritas)
GL (Germanischer Lloyd)
LRS (Lloyds Register of Shipping)
Class NK (Nippon Kaiji Kyokai)
Korean Register of Shipping

Industrial environments
The S7-1200 automation system is designed for use in industrial environments.
Table A- 1

Industrial environments

Application field

Noise emission requirements

Noise immunity requirements

Industrial

EN 61000-6-4:2007

EN 61000-6-2:2005

Easy Book
Manual, 03/2014, A5E02486774-AF

283

Technical specifications
A.1 General technical specifications

Electromagnetic compatibility
Electromagnetic Compatibility (EMC) is the ability of an electrical device to operate as
intended in an electromagnetic environment and to operate without emitting levels of
electromagnetic interference (EMI) that may disturb other electrical devices in the vicinity.
Table A- 2

Immunity per EN 61000-6-2

Electromagnetic compatibility - Immunity per EN 61000-6-2


EN 61000-4-2
Electrostatic discharge

8 kV air discharge to all surfaces


6 kV contact discharge to exposed conductive surfaces

EN 61000-4-3
Radiated, radio-frequency,
electromagnetic field immunity test

80 to 1000 MHz, 10 V/m, 80% AM at 1 kHz


1.4 to 2.0 GHz, 3 V/m, 80% AM at 1 kHz
2.0 to 2.7 GHz, 1 V/m, 80% AM at 1 kHz

EN 61000-4-4
Fast transient bursts

2 kV, 5 kHz with coupling network to AC and DC system power


2 kV, 5 kHz with coupling clamp to I/O

EN 6100-4-5
Surge immunity

AC systems - 2 kV common mode, 1 kV differential mode


DC systems - 2 kV common mode, 1 kV differential mode
For DC systems, refer to Surge immunity below

EN 61000-4-6
Conducted disturbances

150 kHz to 80 MHz, 10 V RMS, 80% AM at 1kHz

EN 61000-4-11
Voltage dips

AC systems
0% for 1 cycle, 40% for 12 cycles and 70% for 30 cycles at 60 Hz

Surge immunity
Wiring systems subject to surges from lightning strike coupling must be equipped with
external protection. One specification for evaluation of protection from lightning type surges
is found in EN 61000-4-5, with operational limits established by EN 61000-6-2. S7-1200 DC
CPUs and signal modules require external protection to maintain safe operation when
subject to surge voltages defined by this standard.
Listed below are some devices that support the needed surge immunity protection. These
devices only provide the protection if they are properly installed according to the
manufacturer's recommendations. Devices manufactured by other vendors with the same or
better specifications can also be used:
Supply Voltage, 24 VDC: DEHN, Inc., Type BVT AD 24, Part Number 918 402
Digital Inputs, 24 VDC: DEHN, Inc., Type DCO RK E 24, Part Number 919 988
Digital Outputs, 24 VDC: DEHN, Inc., Type DCO RK E 24, Part Number 919 988
Analog Inputs: DEHN, Inc., Type BXT ML4 BD12, Part Number 920 342
Analog Outputs: DEHN, Inc., Type DCO RK E 12, Part Number 919 987
Ethernet: DEHN, Inc., Type DPA M CAT6 RJ45S 48, Part Number 929 100
RS-232: DEHN, Inc., Type DCO RK E 12, Part Number 919 987
RS-485: DEHN, Inc., Type BXT ML2 BE HFS 5, Part Number 920 270
Relay Outputs: None required

Easy Book

284

Manual, 03/2014, A5E02486774-AF

Technical specifications
A.1 General technical specifications
Table A- 3

Conducted and radiated emissions per EN 61000-6-4

Electromagnetic compatibility - Conducted and radiated emissions per EN 61000-6-4


Conducted Emissions

0.15 MHz to 0.5 MHz

<79dB (V) quasi-peak; <66 dB (V) average

EN 55011, Class A, Group 1

0.5 MHz to 5 MHz

<73dB (V) quasi-peak; <60 dB (V) average

5 MHz to 30 MHz

<73dB (V) quasi-peak; <60 dB (V) average

Radiated Emissions

30 MHz to 230 MHz

<40dB (V/m) quasi-peak; measured at 10m

EN 55011, Class A, Group 1

230 MHz to 1 GHz

<47dB (V/m) quasi-peak; measured at 10m

Environmental conditions
Table A- 4

Transport and storage

Environmental conditions - Transport and storage


EN 60068-2-2, Test Bb, Dry heat and
EN 60068-2-1, Test Ab, Cold

-40 C to +70 C

EN 60068-2-30, Test Db, Damp heat

25 C to 55 C, 95% humidity

EN 60068-2-14, Test Na, temperature shock

-40 C to +70 C, dwell time 3 hours, 5 cycles

EN 60068-2-32, Free fall

0.3 m, 5 times, product packaging

Atmospheric pressure

1080 to 660h Pa (corresponding to an altitude of -1000 to 3500m)

Table A- 5

Operating conditions

Environmental conditions - Operating


Ambient temperature range
(Inlet Air 25 mm below unit)

-20 C to 60 C horizontal mounting


-20 C to 50 C vertical mounting
95% non-condensing humidity
Unless otherwise specified

Atmospheric pressure

1080 to 795 hPa (corresponding to an altitude of -1000 to 2000m)

Concentration of contaminants

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% non-condensing

EN 60068-2-14, Test Nb, temperature change

5 C to 55 C, 3 C/minute

EN 60068-2-27 Mechanical shock

15 G, 11 ms pulse, 6 shocks in each of 3 axis

EN 60068-2-6 Sinusoidal vibration

DIN rail mount: 3.5 mm from 5-9 Hz, 1G from 9 - 150 Hz


Panel Mount: 7.0 mm from 5-9 Hz, 2G from 9 to 150 Hz
10 sweeps each axis, 1 octave per minute

Easy Book
Manual, 03/2014, A5E02486774-AF

285

Technical specifications
A.1 General technical specifications
Table A- 6

High potential isolation test

High potential isolation test


24 VDC / 5 VDC nominal circuits

520 VDC (type test of optical isolation boundaries)

115 VAC / 230 VAC circuits to ground

1500 VAC

115 VAC / 230 VAC circuits to 115 VAC / 230 VAC


circuits

1500 VAC

115 VAC / 230 VAC circuits to 24 VDC / 5 VDC


circuits

1500 VAC (type test only)

1500 VAC (3000 VAC/4242 VDC type test)

Ethernet port to 24 VDC / 5 VDC circuits and


ground1
1

Ethernet port isolation is designed to limit hazard during short term network faults to hazardous voltages. It does not
conform to safety requirements for routine AC line voltage isolation.

Protection class
Protection Class II according to EN 61131-2 (Protective conductor not required)

Degree of protection
IP20 Mechanical Protection, EN 60529
Protects against finger contact with high voltage as tested by standard probe. External
protection required for dust, dirt, water and foreign objects of < 12.5mm in diameter.

Rated voltages
Table A- 7

Rated voltages

Rated voltage

Tolerance

24 VDC

20.4 VDC to 28.8 VDC

120/230 VAC

85 VAC to 264 VAC, 47 to 63 Hz

Note
When a mechanical contact turns on output power to the S7-1200 CPU, or any digital signal
module, it sends a "1" signal to the digital outputs for approximately 50 microseconds. This
could cause unexpected machine or process operation which could result in death or serious
injury to personnel and/or damage to equipment. You must plan for this, especially if you are
using devices which respond to short duration pulses.

Easy Book

286

Manual, 03/2014, A5E02486774-AF

Technical specifications
A.1 General technical specifications

Reverse voltage protection


Reverse voltage protection circuitry is provided on each terminal pair of +24 VDC power or
user input power for CPUs, signal modules (SMs), and signal boards (SBs). It is still possible
to damage the system by wiring different terminal pairs in opposite polarities.
Some of the 24 VDC power input ports in the S7-1200 system are interconnected, with a
common logic circuit connecting multiple M terminals. For example, the following circuits are
interconnected when designated as "not isolated" in the data sheets: the 24 VDC power
supply of the CPU, the sensor power of the CPU, the power input for the relay coil of an SM,
and the power supply for a non-isolated analog input. All non-isolated M terminals must
connect to the same external reference potential.
WARNING
Connecting non-isolated M terminals to different reference potentials will cause unintended
current flows that may cause damage or unpredictable operation in the PLC and any
connected equipment.
Failure to comply with these guidelines could cause damage or unpredictable operation
which could result in death or severe personal injury and/or property damage.
Always ensure that all non-isolated M terminals in an S7-1200 system are connected to the
same reference potential.

DC Outputs
Short -ircuit protection circuitry is not provided for DC outputs on CPUs, signal modules
(SMs) and signal boards (SBs).

Relay electrical service life


The typical performance data estimated from sample tests is shown below. Actual
performance may vary depending upon your specific application. An external protection
circuit that is adapted to the load will enhance the service life of the contacts. N.C. contacts
have a typical service life of about one-third that of the N.O. contact under inductive and
lamp load conditions.
An external protective circuit will increase the service life of the contacts.

Easy Book
Manual, 03/2014, A5E02486774-AF

287

Technical specifications
A.1 General technical specifications
Table A- 8

Typical performance data

Data for selecting an actuator


Continuous thermal current

2 A max.

Switching capacity and life of the contacts


For ohmic load

Voltage

Current

Number of operating cycles (typical)

24 VDC

2.0 A

0.1 million

24 VDC

1.0 A

0.2 million

24 VDC

0.5 A

1.0 million

48 VAC

1.5 A

1.5 million

60 VAC

1.5 A

1.5 million

120 VAC

2.0 A

1.0 million

120 VAC

1.0 A

1.5 million

120 VAC

0.5 A

2.0 million

230 VAC

2.0 A

1.0 million

230 VAC

1.0 A

1.5 million

230 VAC

0.5 A

12.0 million

For inductive load (according to

Voltage

Current

Number of operating cycles (typical)

IEC 947-5-1 DC13/AC15)

24 VDC

2.0 A

0.05 million

24 VDC

1.0 A

0.1 million

24 VDC

0.5 A

0.5 million

24 VAC

1.5 A

1.0 million

48 VAC

1.5 A

1.0 million

60 VAC

1.5 A

1.0 million

120 VAC

2.0 A

0.7 million

120 VAC

1.0 A

1.0 million

120 VAC

0.5 A

1.5 million

230 VAC

2.0 A

0.7 million

230 VAC

1.0 A

1.0 million

230 VAC

0.5 A

1.5 million

Activating a digital input

Possible

Switching frequency
Mechanical

Max. 10 Hz

At ohmic load

Max. 1 Hz

At inductive load (according to


IEC 947-5-1 DC13/AC15)

Max. 0.5 Hz

At lamp load

Max. 1Hz

Easy Book

288

Manual, 03/2014, A5E02486774-AF

Technical specifications
A.2 CPU modules

A.2

CPU modules
For a more complete list of modules available for S7-1200, refer to the S7-1200 System
Manual or to the customer support web site (http://www.siemens.com/automation/).

Table A- 9

General specifications

General specifications

CPU 1211C

Order
number

Power
dissipation

CPU 1214C

CPU 1215C

CPU 1217C

AC/DC/Relay

6ES7 2111BE400XB0

6ES7 2121BE400XB0

6ES7 2141BG400XB0

6ES7 2151BG400XB0

DC/DC/Relay

6ES7 2111HE400XB0

6ES7 2121HE400XB0

6ES7 2141HG400XB0

6ES7 2151HG400XB0

DC/DC/DC

6ES7 2111AE400XB0

6ES7 2121AE400XB0

6ES7 2141AG400XB0

6ES7 2151AG400XB0

6ES7 2171AG400XB0

Dimensions W x H x D (mm)
Weight

CPU 1212C

90 x 100 x 75

90 x 100 x 75

110 x 100 x 75

130 x 100 x 75

150 x 100 x 75
-

AC/DC/Relay

420 grams

425 grams

475 grams

585 grams

DC/DC/Relay

380 grams

385 grams

435 grams

550 grams

DC/DC/DC

370 grams

370 grams

415 grams

520 grams

530 grams

AC/DC/Relay

10 W

11 W

14 W

14 W

DC/DC/Relay

8W

9W

12 W

12 W

DC/DC/DC

8W

9W

12 W

12 W

12 W

Current available (5 VDC) for


SM and CM bus

750 mA max.

1000 mA max.

1600 mA max.

1600 mA max.

1600 mA max.

Current available (24 VDC)


sensor power

300 mA max.

300 mA max.

400 mA max.

400 mA max.

400 mA max.

Digital input current


consumption (24 VDC)

4 mA/input
used

4 mA/input
used

4 mA/input
used

4 mA/inputs
used

4 mA/input used

Table A- 10

CPU features

CPU features

CPU 1211C

CPU 1212C

CPU 1214C

CPU 1215C

CPU 1217C

User memory

Work memory

30 Kbytes

50 Kbytes

75 Kbytes

100 Kbytes

125 Kbytes

Load memory

1 Mbyte

1 Mbyte

4 Mbytes

4 Mbytes

4 Mbytes

Retentive memory

10 Kbytes

10 Kbytes

10 Kbytes

10 Kbytes

10 Kbytes

On-board digital I/O

6 inputs

8 inputs

14 inputs

14 inputs

14 inputs

See specifications
(Page 302).

4 outputs

6 outputs

10 outputs

10 outputs

10 outputs

On-board analog I/O

2 inputs

2 inputs

2 inputs

2 inputs

2 inputs

2 outputs

2 outputs

See specifications
(Page 311).

Easy Book
Manual, 03/2014, A5E02486774-AF

289

Technical specifications
A.2 CPU modules

CPU features

CPU 1211C

CPU 1212C

CPU 1214C

CPU 1215C

CPU 1217C

Process image size

Inputs

1024 bytes

1024 bytes

1024 bytes

1024 bytes

1024 bytes

Outputs

1024 bytes

1024 bytes

1024 bytes

1024 bytes

1024 bytes

Bit memory (M)

4096 bytes

4096 bytes

8192 bytes

8192 bytes

8192 bytes

Temporary (local) memory

16 Kbytes for startup and program cycle (including associated FBs and FCs)

6 Kbytes for each of the other interrupt priority levels (including FBs and FCs)

SM expansion

None

2 SMs max.

8 SMs max.

8 SMs max.

8 SMs max.

SB, CB, or BB expansion

1 max.

1 max.

1 max.

1 max.

1 max.

CM expansion

3 max.

3 max.

3 max.

3 max.

3 max

Highspeed
counters

Total

Up to 6 configured to use any built-in or SB inputs

1 MHz

--

--

--

--

Ib.2 to Ib.5
(Differential)

100/180 kHz

Ia.0 to Ia.5

Ia.0 to Ia.5

Ia.0 to Ia.5

Ia.0 to Ia.5

Ia.0 to Ia.5

30/120

--

Ia.6 to Ia.7

Ia.6 to Ib.5

Ia.6 to Ib.5

Ia.6 to Ib.1

Pulse
outputs2

kHz

Total

Up to 4 configured to use any built-in or SB outputs

1 MHz

--

--

--

--

Qa.0 to Qa.3
(Differential)

100 kHz

Qa.0 to Qa.3

Qa.0 to Qa.3

Qa.0to Qa.3

Qa.0 to Qa.3

Qa.4 to Qb.1

30 kHz

--

Qa.4 to Qa.5

Qa.4 to Qb.1

Qa.4 to Qb.1

--

Pulse catch inputs

14

14

14

Time delay interrupts

4 total with 1 ms
resolution

4 total with 1 ms
resolution

4 total with 1 ms
resolution

4 total with 1 ms
resolution

4 total with 1 ms
resolution

Cyclic interrupts

4 total with 1 ms
resolution

4 total with 1 ms
resolution

4 total with 1 ms
resolution

4 total with 1 ms
resolution

4 total with 1 ms
resolution

Edge interrupts

6 rising and 6
falling

8 rising and 8
falling

12 rising and 12
falling

12 rising and 12
falling

12 rising and 12
falling

With optional SB

10 rising and 10
falling

12 rising and 12
falling

16 rising and 16
falling

16 rising and 16
falling

16 rising and 16
falling

Easy Book

290

Manual, 03/2014, A5E02486774-AF

Technical specifications
A.2 CPU modules

CPU features

CPU 1211C

CPU 1212C

CPU 1214C

CPU 1215C

CPU 1217C

Real time clock


+/- 60
seconds/
month

+/- 60
seconds/
month

+/- 60
seconds/
month

+/- 60
seconds/
month

Accuracy

Retention time
(maintenance-free
Super Capacitor)

+/- 60
seconds/
month

20 days
typ./12 days
min. at 40 C

20 days
typ./12 days
min. at 40 C

20 days
typ./12 days
min. at 40 C

20 days
typ./12 days
min. at 40 C

20 days
typ./12 days
min. at 40 C

Execution speed

Boolean

0.08 s/
instruction

0.08 s/
instruction

0.08 s /
instruction

0.08 s/
instruction

0.08 s/
instruction

Move Word

1.7s/
instruction

1.7 s/
instruction

1.7s/
instruction

1.7s/
instruction

1.7 s/
instruction

Real Math

2.3 s/
instruction

2.3 s/
instruction

2.3 s/
instruction

2.3 s/
instruction

2.3 s/
instruction

The slower speed is applicable when the HSC is configured for quadrature mode of operation.

For CPU models with relay outputs, you must install a digital signal board (SB) to use the pulse outputs.

Table A- 11

Communication

Technical data

CPU 1211C, CPU 1212C, CPU 1214C

CPU 1215C, CPU 1217C

Communication

1 Ethernet port

2 Ethernet ports

Data rates

Isolation (external signal


to PLC logic)

Cable type

Devices

10/100 Mb/s

10/100 Mb/s

Transformer isolated, 1500 VDC

Transformer isolated, 1500 VDC

CAT5e shielded

CAT5e shielded

4 HMI

4 HMI

1 PG

1 PG

Ethernet connections1

8 (active or passive)

8 (active or passive)

CPU-to-CPU
S7 connections (GET/PUT)

8 (client)

8 (client)

3 (server)

3 (server)

Open User Communication connections (active or passive): TSEND_C, TRCV_C, TCON, TDISCON, TSEND, and
TRCV.

Easy Book
Manual, 03/2014, A5E02486774-AF

291

Technical specifications
A.2 CPU modules

Table A- 12

Wiring diagram for CPU 1214C AC/DC/Relay

CPU 1214C AC/DC/Relay

24 VDC Sensor Power Out. For


additional noise immunity, connect "M"
to chassis ground even if not using
sensor supply.

For sinking inputs, connect "-" to "M"


(shown). For sourcing inputs, connect
"+" to "M".

Note 1: X11 connectors must be gold. See


the S7-1200 System Manual, Appendix C,
Spare Parts for order number.
Note 2: Either the L1 or N (L2) terminal can
be connected to a voltage source up to
240 VAC. The N terminal can be
considered L2 and is not required to be
grounded. No polarization is required for L1
and N (L2) terminals.

Easy Book

292

Manual, 03/2014, A5E02486774-AF

Technical specifications
A.3 Digital I/O modules
Table A- 13

Wiring diagram for CPU 1214C DC/DC/DC

CPU 1214C DC/DC/DC

24 VDC Sensor Power Out. For


additional noise immunity, connect "M"
to chassis ground even if not using
sensor supply.

For sinking inputs, connect "-" to "M"


(shown). For sourcing inputs, connect
"+" to "M".

Note 1: X11 connectors must be gold. See


the S7-1200 System Manual, Appendix C,
Spare Parts for order number.

A.3

Digital I/O modules


For a more complete list of modules available for S7-1200, refer to the S7-1200 System
Manual or to the customer support web site (http://www.siemens.com/automation/).

A.3.1
Table A- 14

SB 1221, SB 1222, and SB 1223 digital input/output (DI, DQ, and DI/DQ)
SB 1221 digital input (DI) and SB 1222 digital output (DQ) modules

General

SB 1221 4 DI (200 kHz)

Order number

SB 1222 4 DQ (200 kHz)

24 VDC: 6ES7 221-3BD30-0XB0

24 VDC: 6ES7 222-1BD30-0XB0

5 VDC: 6ES7 221-3AD30-0XB0

5 VDC: 6ES7 222-1AD30-0XB0

Dimensions W x H x D (mm)

38 x 62 x 21

38 x 62 x 21

Weight

35 grams

35 grams

Power dissipation

24 VDC: 1.5 W

5 VDC: 1.0 W

Current
consumption

SM Bus

40 mA

24 VDC

24 VDC: 7 mA / input + 20 mA

5 VDC: 15 mA / input + 15 mA

Inputs/outputs

4 inputs (source)

0.5 W
35 mA
15 mA
4 outputs (solid state - MOSFET)

Easy Book
Manual, 03/2014, A5E02486774-AF

293

Technical specifications
A.3 Digital I/O modules
Table A- 15

SB 1223 combination digital input/output (DI / DQ) modules

General

SB 1223 DI / DQ (200 kHz)

Order number

24 VDC: 6ES7 223-3BD30-0XB0

5 VDC: 6ES7 223-3AD30-0XB0

SB 1223 2 DI / 2 DQ
24 VDC: 6ES7 223-0BD30-0XB0

Dimensions W x H x D (mm)

38 x 62 x 21

38 x 62 x 21

Weight

35 grams

40 grams

Power dissipation

24 VDC: 1.0 W

5 VDC: 0.5 W

Current
consumption

SM Bus

35 mA

24 VDC

24 VDC: 7 mA / input + 20 mA

5 VDC: 15 mA / input + 15 mA

Inputs/outputs

24 VDC: 1.0 W
50 mA
4 mA / input used

2 inputs (source)

2 inputs (IEC Type 1 sink)

2 outputs (solid state - MOSFET)

2 outputs (solid state - MOSFET)

Note
The high-speed (200 kHz) SBs utilize "sourcing" inputs. The standard SB (20 kHz) utilizes
"sinking" inputs. Refer to the specifications for the digital inputs and outputs (Page 302).
The high-speed (200 kHz) outputs (SB 1222 and SB 1223) can be either sourcing or sinking.
For sourcing outputs, connect "Load" to "-" (shown). For sinking outputs, connect "Load" to
"+". Because both sinking and sourcing configurations are supported by the same circuitry,
the active state of a sourcing load is opposite that of a sinking load. A source output exhibits
positive logic (Q bit and LED are ON when the load has current flow), while a sink output
exhibits negative logic (Q bit and LED are OFF when the load has current flow). If the
module is plugged in with no user program, the default for this module is 0V, which means
that a sinking load will be turned ON.

Easy Book

294

Manual, 03/2014, A5E02486774-AF

Você também pode gostar