Você está na página 1de 105

ADAM-5000 Series

I/O Module
User's Manual

2.4 rd Edition
May 2008

I/O Module Introduction


Introduction
This manual introduces the detail specifications functions and
application wiring of each ADAM-5000 I/O modules. To organize
an ADAM-5510 Series Controller, you need to select I/O modules
to interface the main unit with field devices or processes that you
have previously determined. Advantech provides 23 types of
ADAM-5000 I/O modules for various applications so far. Following
table is the I/O modules support list we provided for users choice.

Module

Analog I/O

Name

Specification

Reference

ADAM-5013

3-ch. RTD input

Isolated

ADAM-5017

8-ch. AI

Isolated

ADAM-5017P

8-ch. AI with independent Input

Isolated

ADAM-5017H

8-ch. High-speed AI

Isolated

ADAM-5017UH

8-ch. Ultra High-speed AI

Isolated

ADAM-5018

Isolated

ADAM-5024

7-ch. Thermocouple input


7-ch. Thermocouple input with
independent Input
4-ch. AO

ADAM-5050

7-ch. D I/O

Non-isolated

ADAM-5018P

Digital I/O

Isolated
Isolated

ADAM-5051

16-ch. DI

Non-isolated

ADAM-5051D

16-ch. DI w/LED

Non-isolated

ADAM-5051S

16-ch. Isolated DI w/LED

Isolated

ADAM-5052

8-ch. DI

Isolated

ADAM-5053S

32-ch. Isolated DI

Isolated

ADAM-5055S

16-ch. Isolated DI/O w/LED

Isolated

ADAM-5056

16-ch. DO

Non-isolated

ADAM-5056D

16-ch. DO w/LED

Non-isolated

ADAM-5056S

16-ch. Isolated DO w/LED

Isolated

ADAM-5056SO

16-ch. Iso. DO w/LED (source)

Isolated

ADAM-5057S

32-ch. Isolated DO

Isolated

Table 1: I/O Module Support List

P.2 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Module
Relay Output

Name

Specification

Reference

ADAM-5060

6-ch. Relay output

Isolated

ADAM-5068

8-ch. Relay output

Isolated

ADAM-5069

8-ch. Relay output

Isolated

ADAM-5080

Isolated

Storage

ADAM-5030

4-ch. Counter/Frequency
4-ch/8-ch High Speed
Counter/Frequency
4-port RS232
4-port RS232 with Share
Interrupt
2-port CAN with Isolation
protection
2-slot SD Storage Module

Motion

ADAM-5202

2-port AMONet Master Module

Counter/Frequency

ADAM-5081
ADAM-5090

Serial I/O

ADAM-5091
ADAM-5095

Isolated
Non-isolated
Non-isolated
Isolated

Table 2: I/O Module Support List

ADAM-5000 Series I/O Module Users Manual P.3

I/O Module Introduction


1. Analog Input Modules
Analog input modules use an A/D converter to convert sensor
voltage, current, thermocouple or RTD signals into digital data. The
digital data is then translated into engineering units. The analog
input modules protect your equipment from ground loops and
power surges by providing opto-isolation of the A/D input and
transformer based isolation up to
3,000 VDC.

ADAM-5013 3-channel RTD input module


The ADAM-5013 is a 16-bit, 3-channel RTD input module that
features programmable input ranges on all channels. This module is
an extremely cost-effective solution for industrial measurement and
monitoring applications. Its opto-isolated inputs provide 3,000 VDC
of isolation between the analog input and the module, protecting
the module and peripherals from damage due to high input line
voltage.
Note:

Owing to the conversion time required by the A/D


converter, the initialization time of each ADAM-5013 module
is 5 seconds. Thus the total initialization time will be about 20
seconds if all 4 I/O slots in an ADAM-5000 main unit
contain ADAM-5013 modules.

ADAM-5013

Figure 1: ADAM-5013 module frontal view


P.4 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Application wiring

Figure 2: RTD inputs

ADAM-5000 Series I/O Module Users Manual P.5

I/O Module Introduction


Technical specifications of ADAM-5013
three

Analog input channels

Pt or Ni

Input type

RTD

Pt -100 to 100C a=0.00385


Pt 0 to 100C a=0.00385
Pt 0 to 200C a=0.00385
Pt 0 to 600C a=0.00385
RTD type and temperature range

Pt -100 to 100C a=0.00392


Pt 0 to 100C a=0.00392
Pt 0 to 200C a=0.00392
Pt 0 to 600C a=0.00392
Ni -80 to 100C
Ni 0 to 100C

Isolation voltage
Sampling rate
Input impedance
Bandwidth
Input connections
Accuracy
Zero drift
Span drift
CMR@50/60 Hz

3000 VDC
10 samples/sec (total)
2 M
13.1 Hz @ 50 Hz
15.72 Hz @ 60 Hz
2, 3 or 4 wire
0.1% or better
0.015 C/C
0.01 C/C
150 dB

NMR@50/60 Hz

100 dB

Power consumption

1.2 W

Table 2: Technical specifications of ADAM-5013

P.6 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5013 RTD Input Resistance Calibration
1. Apply power to the module and let it warm up for about 30 minutes.
2. Make sure that the module is correctly installed and is properly
con- figured for the input range you want to calibrate. You can
use the ADAM utility software to help in this.
3. Connect the correct reference self resistance between the screw
terminals of the ADAM-5013 as shown in the following wiring
diagram. Table 2 below shows the correct values of the span and
zero calibration resistances to be connected.
Reference
resistances used can be from a precision resistance decade box or
from discrete resistors with the values 60, 140, 200 and 440 ohms.

Figure 3: Applying calibration resistance


4. First, with the correct zero (offset) calibration resistance connected
as shown above, issue a Zero Calibration command to the module
using the Calibrate option in the ADAM utility software.
5. Second, with the correct span resistance connected as shown
above, issue a Span Calibration command to the module using
the Calibrate option in the ADAM utility software. Note that the
module zero calibration must be completed prior to the span
calibration.
Note:

If the above procedure is ineffective, the user must first issue an


RTD Self Calibration command $aaSi2 to the module and then
complete steps 4 and 5 after self calibration is complete.

ADAM-5000 Series I/O Module Users Manual P.7

I/O Module Introduction


Calibration resistances (ADAM-5013)
Input Range
Code (Hex)

Input Range
Pt, -100 to 100C A = 0.00385

Span
Calibration
Resistance
140 Ohms

Zero
Calibration
Resistance
60 Ohms

20
21

Pt, 0 to 100C A = 0.00385

140 Ohms

60 Ohms

22

Pt, 0 to 200C A = 0.00385

200 Ohms

60 Ohms

23

Pt, 0 to 600C A = 0.00385

440 Ohms

60 Ohms

24

Pt, -100 to 100C A = 0.00392

140 Ohms

60 Ohms

25

Pt, 0 to 100C A = 0.00392

140 Ohms

60 Ohms

26

Pt, 0 to 200C A = 0.00392

200 Ohms

60 Ohms

27

Pt, 0 to 600C A = 0.00392

440 Ohms

60 Ohms

28

Ni, -80 to 100 C

200 Ohms

60 Ohms

29

Ni, 0 to 100C

200 Ohms

60 Ohms

Table 3: Calibration resistances of ADAM-5013

P.8 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5017 8-channel analog input module
The ADAM-5017 is a 16-bit, 8-channel analog differential input
module that provides programmable input ranges on all channels.
It accepts mill volt inputs (150mV, 500mV), voltage inputs (1V, 5V
and 10V) and current input (20 mA, requires 120 ohms resistor).
The module provides data to the host computer in engineering units
(mV, V or mA). This module is an extremely cost-effective solution
for industrial measurement and monitoring applications. Its optoisolated inputs provide 3,000 VDC of isolation between the analog input
and the module, protecting the module and peripherals from damage
due to high input line volt- age. Additionally, the module uses analog
multiplexers with active over- voltage protection. The active
protection circuitry assures that signal fidelity is maintained even
under fault conditions that would destroy other multiplexers. This
module can withstand an input voltage surge of 70 Vp-p with 15 V
supplies. The jumpers of ADAM-5017 are designed for current input.

ADAM-5017

Figure 4: ADAM-5017 module frontal view

ADAM-5000 Series I/O Module Users Manual P.9

I/O Module Introduction


Application wiring

Figure 5: Millivolt and volt input

Figure 6: Process current input


Note:

To keep measurement accuracy please short the channels that


are not in use.

P.10 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Technical specifications of ADAM-5017
Analog Input Channels

Eight differential

Input Type

mV, V, mA

Input Range

150 mV, 500 mV, 1 V, 5 V, 10 V


and 20 mA

Isolation Voltage

3000 VDC

Sampling Rate

10 samples/sec (total)

Analog Input Signal Limit

15 V max.

Max. allowable voltage difference


between two connectors in a
module

15 V max.

Input Impedance

2 Mohms

Bandwidth

13.1 Hz @ 50 Hz, 15.72 Hz @ 60 Hz

Accuracy

0.1% or better

Zero Drift

1.5 V/C

Span Drift

25 PPM/C

CMR @ 50/60 Hz

92 dB min.

Power Requirements

+ 10 to + 30 VDC (non-regulated)

Power Consumption

1.2 W

Table 4: Technical specifications of ADAM-5017

ADAM-5000 Series I/O Module Users Manual P.11

I/O Module Introduction


ADAM-5017P 8-channel analog input module with
independent input range
The ADAM-5017P is a 16-bit, 8-channel analog differential input and
independent configuration module. It accepts mill volt inputs (150mV,
500mV, 0~150mV, 0~500mV, 0~1V, 0~5V, 0~10V, 0~15V), voltage
inputs (1V, 5V, 10V, and 20V) and current input (20 mA,
4~20mA, requires 120 ohms resistor). The module provides data to
the host computer in engineering units (mV, V (supports uni-poloar
and bipolar) or mA). This module is an extremely cost-effective
solution for industrial measurement and monitoring applications. Its
high common mode provides 200 VDC, protecting the module and
peripherals from damage due to high input line volt-age. Additionally,
the module uses analog multiplexers with active over-voltage
protection. The active protection circuitry assures that signal
fidelity is maintained even under fault conditions that would
destroy other multiplexers. This module can withstand an input voltage
surge of 60 VDC.

ADAM-5017P

Figure 7: ADAM-5017P module frontal view

P.12 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction

Application wiring

Figure 8: Millivolt and volt input

Figure 9: Process current input

ADAM-5000 Series I/O Module Users Manual P.13

I/O Module Introduction

Figure 13: Locations of Jumpers


Note:
use.

To maintain measurement accuracy pleases short channels not in

P.14 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Technical specifications of ADAM-5017P
Analog Input Channels

Eight differential and independent

Input Type

mV, V(uni-polar and bipolar), mA

Input Range

150 mV, 500 mV, 1 V, 5 V, 10 V,


0~150mV, 0~500mV, 0~1V, 0~5V, 0~10V,
0~15V and 20 mA, and 4~20mA

High common mode

200 VDC

Sampling Rate

10 samples/sec (total)

Resolution

16 bits

Over Voltage

60 VDC

Input Impedance

20 Mohms Voltage
120 ohms Current

Built-in TVS/ESD protection

yes

Zero Drift

0.1% or better Voltage mode


0.2% or better Current mode
6 V/C

Span Drift

25 PPM/C

CMR @ 50/60 Hz

92 dB min.

Power Consumption

1.25 W (Max)

Accuracy

Table 5: Technical specifications of ADAM-5017P

ADAM-5000 Series I/O Module Users Manual P.15

I/O Module Introduction


ADAM-5017H 8-channel high speed analog input module
The ADAM-5017H is a 12-bit plus sign bit; 8-channel analog differential
input module that provides programmable input ranges on each channel. It
accepts mill volt inputs ( 500 mV, 0-500 mV), voltage inputs (1 V, 0-1
V, 2.5 V, 0-2.5 V, 5 V, 0-5 V, 10 V and 0-10 V) and current inputs (0-20 mA
and 4-20 mA; it was built in a 200 ohms resistor). The module provides
data to the host microprocessor in engineering units (mV, V or mA) or
twos complement format. Its sampling rate depends on the data
format received: up to 100 Hz (total). Each input channel has 3000 VDC
of optical isolation between the outside analog input line and the
module, protecting the module and peripherals from high input line
voltages. Addition- ally, the module uses analog multiplexers with active
over-voltage protection. The active protection circuitry assures that
signal fidelity is maintained even under fault conditions that would
destroy other multiplexers. The analog inputs can withstand a constant
70 Vp-p input with 15V supplies. The jumpers of ADAM-5017H are
designed for current input.

ADAM-5017H

Figure 10: ADAM-5017H module frontal view

P.16 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction

Application wiring

Figure 11: Millivolt and volt input

Figure 12: Process current input

ADAM-5000 Series I/O Module Users Manual P.17

I/O Module Introduction

Figure 13: Locations of Jumpers


Note:
use.

To maintain measurement accuracy pleases short channels not in

P.18 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Technical specifications of ADAM-5017H
Analog Input Channels

8 differential

ADC Resolution

12 bits, plus sign bit

Type of ADC

Successive approximation

Isolation Voltage

3000 VDC
100 Hz

Sampling Rate
Input Impedance

20 Mohms (voltage inputs)


200 ohms (current inputs; built in on the board)

Signal Input Bandwidth

1000 Hz for both voltage inputs and current


inputs

Analog Signal Range

15 V max.

Analog Signal Range for any


two measured Pins
Power Requirements

15 V max.

+10 to +30 VDC (non-regulated)

Power Consumption

1.8 W

Accuracy

0.1% or better

Table 5: Technical specifications of ADAM-5017H

ADAM-5000 Series I/O Module Users Manual P.19

I/O Module Introduction

0 ~ 10
V

0 ~ 11 V

1
LSB

Offset
Error
@ -10
to
+70C
2
LSB

0~5V

0 ~ 5.5 V

1
LSB

0 ~ 2.5
V

0 ~ 2.75 V

0~1V

Input
Range

Voltage
Inputs

Current
Inputs

With
Overranging

Offset
Error @
25C

Gain
Error
@ 25C

Gain Error
@ -10
To
+70C

Offset
Drift

Gain
Drift

Display
Resolution

50
ppm/
C
50
ppm/
C
55
ppm/
C
60
ppm/
C
67
ppm/
C
50
ppm/
C
50
ppm/
C
55
ppm/
C
60
ppm/
C
67
ppm/
C
ppm/
C
ppm/
C

2.7 mV

1
LSB

2 LSB

17
V/C

2
LSB

1.5
LSB

2 LSB

16
V/C

1
LSB

2
LSB

1.5
LSB

2 LSB

20
V/C

0 ~ 1.375
V

1
LSB

2.5
LSB

2
LSB

2.5 LSB

20
V/C

0 ~ 500
mV

0 ~ 687.5
mV

5
LSB

3
LSB

3.5 LSB

20
V/C

10 V

11 V

1
LSB

2
LSB

1
LSB

2 LSB

17
V/C

5V

0 ~ 5.5 V

1
LSB

2
LSB

1.5
LSB

2 LSB

17
V/C

2.5 V

0 ~ 2.75
V

1
LSB

2
LSB

1.5
LSB

2 LSB

20
V/C

1V

0 ~ 1.375
V

1
LSB

2.5
LSB

2
LSB

2.5 LSB

20
V/C

500
mV

0 ~ 687.5
mV

5
LSB

3
LSB

3.5 LSB

20
V/C

1
LSB
1
LSB

1
LSB
1
LSB

1.5
LSB
1.5
LSB

2 LSB

nA/C

2 LSB

nA/C

0 ~ 20
mA
4 ~ 20
mA

22 mA
22 mA

Table 6: ADAM-5017H input signal ranges

P.20 ADAM-5000 Series I/O Module Users Manual

1.3 mV
0.67 mV
0.34 mV
0.16 mV
2.7 mV
1.3 mV
0.67 mV
0.34 mV
0.16 mV

5.3
5.3

I/O Module Introduction


ADAM-5017UH 8-channel Ultra high speed analog input
module
The ADAM-5017UH is a 12-bit plus sign bit, 8-channel analog differential
input module that provides programmable input ranges on each channel. It
accepts voltage inputs (10 V and 0-10 V) and current inputs (0-20 mA and 420 mA). The module provides data to the host microprocessor in
engineering units (mV, V or mA) or twos complement format. Its
sampling rate depends on the data format received: up to 200k Hz (total).
Space is reserved for 125-ohm, 0.1%, 10 ppm resistors (See Figure 9).
Each input channel has 3000 VDC of optical isolation between the
outside analog input line and the module, protecting the module and
peripherals from high input line voltages. Additionally, the module uses
analog multiplexers with active overvoltage protection. The active
protection circuitry assures that signal fidelity is maintained even under
fault conditions that would destroy other multiplexers. The analog
inputs can withstand a constant 70 Vp-p input with 15V supplies. The
jumpers of ADAM-5017UH are designed for current input.

ADAM-5017UH

Figure 11: ADAM-5017UH module frontal view


ADAM-5000 Series I/O Module Users Manual P.21

I/O Module Introduction


Application wiring

Figure 12: Millivolt and volt input

Figure 13: Process current input

P.22 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction

Figure 14: Locations of RC Filter Jumper setting

Figure 15: Locations of RC Filter Jumper setting


Note:

To maintain measurement accuracy please short channels not in


use.

ADAM-5000 Series I/O Module Users Manual P.23

I/O Module Introduction


Technical specifications of ADAM-5017UH
Analog Input Channels

Eight differential

Resolution

12 bits

Input Type

mV, V, mA

Input Range

+0~10V , 10 V , +4~20mA and 20 mA

Isolation Voltage

3000 VDC

Sampling Rate

200k samples/sec (single channel)


50k samples/sec (8 channel)

Analog Input Signal Limit

15 V max.

Max. allowable voltage difference


between two connectors in a
module

15 V max.
20 Mohms (Voltage input)

Input Impedance

120 ( current input )


200kHz

Bandwidth
Accuracy

0.1% or better

Low or high pass filter

Configured by User

CMR @ 50/60 Hz

92 dB min.

Power Requirements

+ 10 to + 30 VDC (non-regulated)

Power Consumption

1.75 W (typical ); 2.2W (max)

Signal Input Bandwidth

200kHz for both voltage and current inputs

Table 7: Technical specifications of ADAM-5017UH

Voltage
Inputs

Input
Range

Offset
Error
@
25C

0 ~ 10 V

1
LSB
1
LSB
1
LSB
1
LSB

10 V
Current
Inputs

0 ~ 20
mA
4 ~ 20
mA

Offset
Error
@ -10
to
+70C
2
LSB
2
LSB
1
LSB
1
LSB

Gain
Error
@
25C
1 LSB
1 LSB
1.5
LSB
1.5
LSB

Gain
Error
@ -10
to
+70C
2
LSB
2
LSB
2
LSB
2
LSB

Display
Resolution

2.7 mV
2.7 mV
5.3
5.3

Table 8: ADAM-5017UH input signal ranges

P.24 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5018 7-channel thermocouple input module
The ADAM-5018 is a 16-bit, 7-channel thermocouple input module that
features programmable input ranges on all channels. It accepts
millivolt inputs (15 mV, 50 mV, 100 mV, 500 mV), voltage inputs (1
V, 2.5 V), current input (20 mA, requires 125 ohms resistor) and
thermocouple input (J, K, T, R, S, E, B).
The module forwards the data to the host computer in engineering units
(mV, V, mA or temperature C). An external CJC on the plug-in terminal is
designed for accurate temperature measurement.

ADAM-5018

Figure 16: ADAM-5018 module frontal view

ADAM-5000 Series I/O Module Users Manual P.25

I/O Module Introduction


Application wiring

Figure 17: Thermocouple input

P.26 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Technical specifications of ADAM-5018
Analog Input Channels
Input Type

Seven differential
mV, V, mA, Thermocouple

Input Range

15 mV, 50 mV, 100 mV, 500 mV, 1 V,


2.5 V and 20 mA

T/C Type and Temperature


Range

J
K
T
E
R
S
B

Isolation Voltage

3000 VDC

Sampling Rate

10 samples/sec (total)

Input Impedance

2 Mohms

Bandwidth

0 to 760 C
0 to 1370 C
-100 to 400 C
0 to 1400 C
500 to 1750 C
500 to 1750 C
500 to 1800 C

13.1 Hz @ 50 Hz, 15.72 Hz @ 60 Hz

Accuracy

0.1% or better

Zero Drift

0.3 V/C

Span Drift

25 PPM/C

CMR @ 50/60 Hz

92 dB min.

Power Consumption

1.2 W

Table 9: Technical specifications of ADAM-5018

ADAM-5000 Series I/O Module Users Manual P.27

I/O Module Introduction


ADAM-5018P 7-channel thermocouple input module

The ADAM-5018P is a 16-bit, 8-channel Thermocouple


Independent input module that provides programmable input
ranges on all channels. It accepts Various Thermocouple
inputs (Type J, K, T, E, R, S, B) and provides data to the
host computer in engineering units (oC) In order to satisfy
various temperature requirements in one module, each
analog channel is allowed to configure an individual range
for several applications.
ADAM-5018P

Figure 18: ADAM-5018P module frontal view

P.28 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Application wiring

Figure 19: Thermocouple input

Technical specifications of ADAM-5018P


Analog Input Channels
Input Type

Seven differential & independent thermocouple


mV, V, mA, Thermocouple

Input Range

15 mV, 50 mV, 100 mV, 500 mV, 1 V,


2.5 V and 20 mA

T/C Type and Temperature


Range

J
K
T
E
R
S
B

Isolation Voltage

3000 VDC

Sampling Rate

10 samples/sec (Selected by Utility)

Input Impedance

20 Mohms (Voltage input)

0 to 760 C
0 to 1370 C
-100 to 400 C
0 to 1400 C
500 to 1750 C
500 to 1750 C
500 to 1800 C

120 ( current input )


Bandwidth

13.1 Hz @ 50 Hz, 15.72 Hz @ 60 Hz

Accuracy

0.1% or better

Zero Drift

6 V/C

Span Drift

25 PPM/C

CMR @ 50/60 Hz

92 dB min.

Power Consumption

0.5 W

Table 10: Technical specifications of ADAM-5018P

ADAM-5000 Series I/O Module Users Manual P.29

I/O Module Introduction


2. Analog Output Modules
ADAM-5024 4-channel analog output module
The ADAM-5024 is a 4-channel analog output module. It receives
its digital input through the RS-485 interface of the ADAM-5510
system module from the host computer. The format of the data is
engineering units. It then uses the D/A converter controlled by the
system module to convert the digital data into output signals.
You can specify slew rates and start up currents through the
configuration software. The analog output can also be configured
as current or voltage through the software utility. The module
protects your equipment from ground loops and power surges by
providing opto-isolation of the D/A output and transformer based
isolation up to 500 VDC.

Slew rate
The slew rate is defined as the slope indicated the ascending or
descending rate per second of the analog output from the present to
the required.

ADAM-5024

Figure20: ADAM-5024 module frontal view

P.30 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Application wiring

Figure 21: Analog output

Technical specifications of ADAM-5024


Analog Output Channels

Four

Output Type

V, mA

Output Range

0-20mA, 4-20mA, 0-10V

Isolation Voltage

3000 Vdc

Output Impedance

0.5 Ohms

Accuracy

0.1% of FSR for current output 0.2% of


FSR for voltage output

Zero Drift

Voltage output: 30 V/C Current output:


0.2 A/C

Resolution

0.015% of FSR

Span Temperature Coefficient

25 PPM/C

Programmable Output Slope

0.125-128.0 mA/sec 0.0625-64.0 V/sec

Current Load Resistor

0-500 Ohms (source)

Power Consumption

2.5W (Max.)

Table 11: Technical specifications of ADAM-5024

ADAM-5000 Series I/O Module Users Manual P.31

I/O Module Introduction


3. Analog I/O Modules Calibration
Analog input/output modules are calibrated when you receive
them. However, calibration is sometimes required. No screwdriver is
necessary because calibration is done in software with calibration
parameters stored in the ADAM-5000 analog I/O modules onboard
EEPROM.
The ADAM-5000 system comes with the ADAM utility software
that supports calibration of analog input and analog output.
Besides the calibration that is carried out through software, the
modules incorporate automatic Zero Calibration and automatic Span
Calibration at boot up or reset.

Analog input module calibration


Modules: ADAM-5017, 5017H, 5018
1. Apply power to the ADAM-5000 system that the analog input
module is plugged into and let it warm up for about 30 minutes
2. Assure that the module is correctly installed and is properly
configured for the input range you want to calibrate. You can do
this by using the ADAM utility software.
3. Use a precision voltage source to apply a span calibration voltage
to the modules V0+ and V0- terminals. (See Table 12 for
reference voltages for each range.)

Figure 22: Applying calibration voltage

P.32 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


4. Execute the Zero Calibration command (also called the Offset
Calibration command).

Figure 23: Zero calibration


5. Execute the Span Calibration command. This can be done with the
ADAM utility software.

Figure 24: Span calibration


ADAM-5000 Series I/O Module Users Manual P.33

I/O Module Introduction


6. CJC Calibration (only for T/C input module)

Figure 25: Cold junction calibration


* Note: Zero calibration and span calibration must be completed
before CJC calibration. To calibrate CJC, the thermocouple
attached to ADAM-5018 and a standard thermometer
should be used to measure a standard known temperature,
such as the freezing point of pure water. The amount of
offset between the ADAM-5018 and the standard
thermometer is then used in the ADAM utility to complete
CJC calibration.

P.34 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Calibration voltage (ADAM-5017/5018)
Module

Input Range Code


(Hex)

Input Range

Span Calibration
Voltage

5018

00h

15 mV

+15 mV

01h

50 mV

+50 mV

02h

100 mV

+100 mV

03h

500 mV

+500 mV

04h

1 mV

+1 V

5017

05h

2.5 V

+2.5 V

06h
0Eh

20 mV

+20 mA (1)
+50 mV

J thermocouple 0 to
1370C

0Fh

K thermocouple 0 to
1370C

+50 mV

10h

T thermocouple -100 to
400C

+22 mV

11h

E thermocouple 0 to
1000C

+80 mV

12h

R thermocouple 500 to
1750C

+22 mV

13h

S thermocouple 500 to
1800C

+22 mV

14h

B thermocouple 500 to
1800C

+152 mV

07h
08h

Not used
C10 V

+10 V

09h

5 V

+5 V

0Ah

1 V

+1 V

0Bh

500 mV

+500 mV

0Ch

150 mV

+150 mV

0Dh

20 mA

+20 mV (1)

Table 12: Calibration voltage of ADAM-5017/5018

ADAM-5000 Series I/O Module Users Manual P.35

I/O Module Introduction


Calibration voltage (ADAM-5017H)
Module

5017H

Input Range Code


(Hex)

Input Range

Span Calibration Voltage

00h

10 V

+10 V

01h

0 ~ 10 V

+10 V

02h

5 V

+5 V

03h

0~5V

+5 V

04h

2.5 V

+2.5 V

05h

0 ~ 2.5 V

+2.5 V

06h

1 V

+1 V

07h

0~1V

+1 V

08h

500 mV

+500 mV

09h

0 ~ 500 mV

+500 mV

0ah

4 ~ 20 mA

*(1)

0bh

0 ~ 20 mA

*(1)

Table 13: Calibration voltage of ADAM-5017H


Note: You can substitute 2.5 V for 20 mA if you remove the current conversion
resistor for that channel. However, the calibration accuracy will be limited
to 0.1% due to the resistor's tolerance.

P.36 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Calibration voltage (ADAM-5018P)
Module

Input Range Code


(Hex)

Input Range

Span Calibration
Voltage

00h

15 mV

+15 mV

01h

50 mV

+50 mV

02h

100 mV

+100 mV

03h

500 mV

+500 mV

04h

1 mV

+1 V

05h

2.5 V

+2.5 V

06h

20 mV

+20 mA (1)

4 ~ 20 mA

+16 mA (1)
+50 mV

07h
0Eh
5018P

J thermocouple
0 to 1370C

0Fh

K thermocouple
0 to 1370C

+50 mV

10h

T thermocouple
-100 to 400C

+22 mV

11h

E thermocouple
0 to 1000C

+80 mV

12h

R thermocouple
500 to 1750C

+22 mV

13h

S thermocouple
500 to 1800C

+22 mV

14h

B thermocouple
500 to 1800C

+152 mV

Table 14: Calibration voltage of ADAM-5018P

ADAM-5000 Series I/O Module Users Manual P.37

I/O Module Introduction


Calibration voltage (ADAM-5017UH)
Module

5017H

Input Range Code


(Hex)

Input Range

Span Calibration Voltage

08h

10 V

+10 V

48h

0 ~ 10 V

+10 V

46h

0 ~ 20 mA

*(1)

07h

4 ~ 20 mA

*(1)

Table 15: Calibration voltage of ADAM-5017UH


Note: You can substitute 2.5 V for 20 mA if you remove the current
conversion resistor for that channel. However, the calibration
accuracy will be limited to 0.1% due to the resistor's tolerance.

P.38 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction

Analog output module calibration


The output current of analog output modules can be calibrated by using
a low calibration value and a high calibration value. The analog output
modules can be configured for one of two ranges: 0-20 mA and 4-20 mA.
Since the low limit of the 0-20 mA range (0 mA) is internally an absolute
reference (no power or immeasurably small power), just two levels are
needed for calibration: 4 mA and 20 mA.
1. Apply power to the ADAM-5000 system including the analog output
module for about 30 minutes.
2. Assure that the module is correctly installed and that its configuration
is according to your specifications and that it matches the output range
you want to calibrate. You can do this by using the ADAM utility
software.
3. Connect either a 5-digit mA meter or voltmeter with a shunt resistor
(250 ohms, .01 % and 10 ppm) to the screw terminals of the module.

Figure 26: Output module calibration

ADAM-5000 Series I/O Module Users Manual P.39

I/O Module Introduction


4. Issue the Analog Data Out command to the module with an
output value of 4 mA.
5. Check the actual output value at the modules terminals. If this
does not equal 4 mA, use the "Trim" option in the "Calibrate"
submenu to change the actual output. Trim the module until the
mA meter indicates exactly 4 mA, or in case of a voltage meter with
shunt resistor, the meter indicates exactly 1 V. (When calibrating for
20 mA using a voltage meter and shunt resistor, the correct
voltage should be 5 V.)
6. Issue the 4 mA Calibration command to indicate that the output
is calibrated and to store the calibration parameters in the
module's EEPROM.
7. Execute an Analog Data Out command with an output value
of 20 mA. The module's output will be approximately 20 mA.
8. Execute the Trim Calibration command as often as necessary until
the output current is equal to exactly 20 mA.
9. Execute the 20 mA Calibration command to indicate that the
present output is exactly 20 mA. The analog output module
will store its calibration parameters in the unit's EEPROM.

P.40 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


4. Digital Input/Output Modules
ADAM-5050 16-channel universal digital I/O module
The ADAM-5050 features sixteen digital input/output channels.
Each channel can be independently configured to be an input or
an output channel by the setting of its DIP switch. The digital
outputs are open collector transistor switches that can be
controlled from the ADAM-5000. The switches can also be used to
control solid-state relays, which in turn can control heaters, pumps
and power equipment. The ADAM-5000 can use the modules digital
inputs to determine the state of limit or safety switches, or to receive
remote digital signals.
Warning!

A channel may be destroyed if it is subjected


to an input signal while it is configured to be
an output channel.

Figure 27: Dip switch setting for digital I/O channel

ADAM-5050

Figure 28: ADAM-5050 module frontal view

ADAM-5000 Series I/O Module Users Manual P.41

I/O Module Introduction


Application wiring

Figure 29: Dry contact signal input (ADAM-5050)

Figure 30: Wet contact signal input (ADAM-5050)

Figure 31: Digital output used with SSR (ADAM-5050/5056)

P.42 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Technical specifications of ADAM-5050
Points

16

Channel Setting

Bitwise selectable by DIP switch

Digital Input

Dry Contact Logic Level 0: close


to GND Logic Level 1: open Wet
Contact Logic Level 0: +2 V max
Logic Level 1: +4 V to 30 V

Digital Output

Open collector to 30 V, 100mA


max load

Power Dissipation

450 mW

Power Consumption

0.4 W

Table 16: Technical specifications of ADAM-5050

ADAM-5000 Series I/O Module Users Manual P.43

I/O Module Introduction


ADAM-5051(D) 16-channel digital input module
The ADAM-5051 provides sixteen digital input channels. The ADAM5510 can use the modules digital inputs to determine the state of limit or
safety switches or to receive remote digital signals.

ADAM-5051/5051 D

Figure 32: ADAM-5051 module frontal view

Application wiring

Figure 33: TTL input (ADAM-5051/5051D)

P.44 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction

Figure 34: Contact closure input (ADAM-5051/5051D)

Technical specifications of ADAM-5051/5051D


Points

16

Digital input

Logic level 0: + 1 V max


Logic level 1: + 3.5 to 30 V Pull up
current: 0.5 mA
10 k resistor to + 5 V

Power consumption

0.3 W

Indicator

ADAM-5051 D only
Table 17: Technical specifications of ADAM-5051

ADAM-5000 Series I/O Module Users Manual P.45

I/O Module Introduction


ADAM-5051S 16-channel Isolated Digital Input Module
with LED
The ADAM-5051S provides 16 isolated digital input channels for critical
environments need individual channel isolating protection. Different from
other ADAM-5000 I/O modules, ADAM-5051S designed with 21 pins
plug terminal.

ADAM-5051S

Figure 35: ADAM-5051S module front view

Application Wiring

Figure 36: ADAM-5051S module wiring diagram

P.46 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Technical specification of ADAM-5051S
Point

16(4-channel/group)

Digital Input

Logic Level 0: + 3 V max Logic


Level 1: + 10 to 50 V

Optical Isolation
Opto-isolator response time
Over-voltage Protection

2500 VDC
25 s

Power Consumption

70 VDC
0.8 W

LED Indicator

On when active

I/O Connector Type

21-pin plug-terminal

Table 18: Technical specification of ADAM-5051S

ADAM-5000 Series I/O Module Users Manual P.47

I/O Module Introduction


ADAM-5052 8-channel isolated digital input module
The ADAM-5052 provides eight fully independent isolated
channels. All have 5000 VRMS isolation to prevent ground loop
effects and to pre- vent damage from power surges on the input lines.

ADAM-5052

Figure 37: ADAM-5052 module frontal view

Application wiring

Figure 38: Isolation digital input (ADAM-5052)

P.48 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Technical specifications of ADAM-5052
Points

8 Differential

Digital input

Logic level 0: + 1 V max


Logic level 1: + 3.5 to 30 V
Isolation voltage: 5000 V RMS
Resistance: 3 k/ 0.5 W

Power consumption

0.4 W

Table 19: Technical specifications of ADAM-5052

ADAM-5000 Series I/O Module Users Manual P.49

I/O Module Introduction


ADAM-5053S 32-channel Isolated Digital Input Module
The ADAM-5053S provides 32 isolated digital input channels for
critical environments need individual channel isolating protection.
Different from other ADAM-5000 I/O modules, ADAM-5053S
designed with 40-pin flat cable wiring terminal.

ADAM-5053S

Technical specification of ADAM-5053S


Point

32

Digital Input

Logic Level 0: + 5 V max Logic Level


1: 19 to 35 V

Optical Isolation
Opto-isolator response time
Over-voltage Protection

2500 VDC
25 s

Power Consumption

35 VDC
1 W (max.)

I/O Connector Type

40-pin flat cable wiring terminal

P.50 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Application Wiring

ADAM-5000 Series I/O Module Users Manual P.51

I/O Module Introduction


ADAM-5055S 16-channel Isolated Digital I/O Module with
LED
The ADAM-5056S provides 8 isolated digital input and 8 isolated
output channels for critical environments need individual channel
isolating protection. Different from other ADAM-5000 I/O modules,
ADAM-5055S designed with 21 pins plug terminal.

ADAM-5055S

Figure 39: ADAM-5055S module front vie

Application Wiring

Figure 40: ADAM-5055S module wiring diagram

P.52 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Technical specification of ADAM-5055S
Points

16

Digital Output

8 (8-channel/group)

Open collector to 40 V

200 mA max

Optical Isolation

2500 VDC
25 s

Opto-isolator response time


Supply Voltage
Digital Input

5 ~ 40 VDC
8(4-channel/group) Dry Contact
Logic Level 0: close to GND Logic
Level 1: open Wet Contact Logic
Level 0: + 3 V max Logic Level 1:
+ 10 to 50 V

Dry Contact & Wet contact

Selectable

Optical Isolation

2500 VDC
25 s

Opto-isolator response time


Over-voltage Protect

load per channel

Power Consumption

70 VDC
0.68 W

LED Indicator

On when active

I/O Connector Type

21-pin plug-terminal

Table 20: Technical specification of ADAM-5055S

ADAM-5000 Series I/O Module Users Manual P.53

I/O Module Introduction


Jumper Setting
Below is the jumper setting for both JP1 & JP2.
JP1(DI0~DI3)
JP2(DI4~DI7)

Wet Contact

Dry Contact

Dry Contact wiring

Note: Be sure to adjust the jumper to the right place.

P.54 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5056(D) 16-channel digital output module w/LED
The ADAM-5056 features sixteen digital output channels. The
digital outputs are open-collector transistor switches that you can
control from the ADAM-5000 main unit. You also can use the
switches to control solid-state relays.

ADAM-5056

Figure 41: ADAM-5056 module frontal view

Application wiring

Figure 42: Digital output used with SSR (ADAM-5050/5056)

ADAM-5000 Series I/O Module Users Manual P.55

I/O Module Introduction


Technical specifications of ADAM-5056
There are 16-point digital input and 16-point digital output modules in
the ADAM-5000 series. The addition of these solid state digital I/O
devices allows these modules to control or monitor the interfaces
between high power DC or AC lines and TTL logic signals. A
command from the host converts these signals into logic levels
suitable for the solid-state I/O devices.
Points

16

Digital output

Open collector to 30 V 100 mA


max load

Power dissipation

450 mW

Power consumption

0.25 W

Table 21: Technical specifications of ADAM-5056

P.56 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5056S 16-channel Isolated Digital Output Module
with LED
The ADAM-5056S provides 16 isolated digital output channels for critical
environments need individual channel isolating protection. Different from
other ADAM-5000 I/O modules, ADAM-5056S designed with 21 pins
plug terminal.

ADAM-5056S

Figure 43: ADAM-5056S module front view

Application wiring

Figure 44: ADAM-5056S module wiring diagram

ADAM-5000 Series I/O Module Users Manual P.57

I/O Module Introduction


Technical Specification of ADAM-5056S
Points

16(8-channel/group)

Digital Output

Open collector to 40 V 200 mA


max load per channel

Optical Isolation
Opto-isolator response time
Supply Voltage

2500 VDC
25 s

Power consumption

5 ~ 40 VDC
0.6 W

LED Indicator

On when active

I/O Connector Type

21-pin plug-terminal

Table 22: Technical specification of ADAM-5055S

P.58 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5056SO 16-channel Isolated Digital Output
Module with LED
The ADAM-5056SO provides 16 channels source type isolated digital
output for critical environments need individual channel isolating
protection. Addition to the source output wiring, all of the specification
and command sets are the same with ADAM-5056S.
ADAM-5056SO

Figure 45: ADAM-5056SO module front view


Application wiring

Figure 46: ADAM-5056SO module wiring diagram

ADAM-5000 Series I/O Module Users Manual P.59

I/O Module Introduction


Technical Specification of ADAM-5056SO

Points

16(8-channel/group)

Digital Output

Open collector to 40 V 200 mA max load per channel

Optical Isolation

2500 VDC

Opto-isolator response
time

25 us

Supply Voltage

5 ~ 40 VDC

Power consumption

0.6 W

LED Indicator

On when active

I/O Connector Type

21-pin plug-terminal

Table 23: Technical specification of ADAM-5056SO

P.60 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5057S 32-channel Isolated Digital Output Module
The ADAM-5057S provides 32 isolated digital output channels for
critical environments need individual channel isolating protection.
Different from other ADAM-5000 I/O modules, ADAM-5057S
designed with 40-pin flat cable wiring terminal.

ADAM-5057S

Technical specification of ADAM-5057S


Points

32

Digital Output

Contact with ADAM-3920R

Optical Isolation

2500 VDC
10 A 250VAC, 10 A 30VDC

Contact Rating
Power Input
Power consumption

+24 VDC
1 W (max.)

Relay Type

SPST (Form A)

I/O Connector Type

40-pin flat cable wiring terminal

Application wiring
ADAM-5000 Series I/O Module Users Manual P.61

I/O Module Introduction

Note: Please be noted that the Cable, PCL-10220 & Wiring Board,
ADAM-3920R are additional option.

Pin Assignments for ADAM-3920R

P.62 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


5. Relay Output Modules
ADAM-5060 relay output module
The ADAM-5060 relay output module is a low-cost alternative to
SSR modules. It provides 6 relay channels, two of Form A and four of
Form C.

ADAM-5060

Figure 47: ADAM-5060 module frontal view

Application wiring

Figure 48: Relay output

ADAM-5000 Series I/O Module Users Manual P.63

I/O Module Introduction


Technical specifications of ADAM-5060
Points

6, two Form A and four Form C

Contact rating

AC: 125 V @ 0.6A; 250 V @ 0.3 A


DC: 30 V @ 2 A; 110 V @ 0.6 A

Breakdown voltage

500 VAC(50/60 Hz)

Relay on time (typical)

3 ms

Relay off time (typical)

1 ms

Total switching time

10 ms

Insulation resistance

1000 M min. @ 500 VDC

Power consumption

0.7 W

Table 24: Technical specifications of ADAM-5060

P.64 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5068 relay output module
The ADAM-5068 relay output module provides 8 relay channels of
Form A. Switches can be used to control the solid-state relays.

ADAM-5068

Figure 49: ADAM-5068 module frontal view

Application wiring

Figure 50: Relay output

ADAM-5000 Series I/O Module Users Manual P.65

I/O Module Introduction


Technical specifications of ADAM-5068

Points
Contact Rating

8 Form A
AC: 120 V @ 0.5 A DC: 30 V @ 1 A

Breakdown Voltage
Relay On Time (typical)

500 VAC(50/60 Hz)


7 msec.

Relay Off Time (typical)

3 msec.

Total Switching Time

10 msec.

Power Consumption

2.0 W

Table 25: Technical specifications of ADAM-5068

P.66 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5069 relay output module
The ADAM-5069 relay output module provides 8 relay
channels of Form A. Switches can be used to control the
relays. Considered to user friendly, the ADAM-5069 also built
with LED indicator for status reading easily. And it also
provides a choice to clear or keep output status when reset by
adjusting a jumper.

Specification

Number of Output Channel: 8 Form A


Contact Rating: AC:250V@5A
DC:30V@5A

Breakdown Voltage : 750 VAC (50/60 Hz)


Insulation Resistance: 1000M@500VDC

LED Indicator: On: Active


Off: Non-active
Power Consumption: 0.25W(typical) 2.2W(Max)
Isolation Resistance: 4000 VRMS
Relay response Time: ON :5 ms
Off :5.6 ms
Clear or Keep Relay Status when reset (selectable by jumper)

ADAM-5000 Series I/O Module Users Manual P.67

I/O Module Introduction

Figure 51: the wiring of ADAM-5069 module frontal view

P.68 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


6. Counter/Frequency Module
Overview
Compatible ADAM-5000 Series Main Units
ADAM-5080 is a 4-channel counter/frequency module designed to
be implemented within the following Advantech ADAM-5000
series main units:
ADAM-5000/485
ADAM-5510
ADAM-5511
ADAM-5510M
ADAM-5510E
ADAM-5510/TCP
ADAM-5510E/TCP
Please make sure that the ADAM-5080
counter/frequency module is properly inserted into the
compatible main units.

ADAM-5080 4-channel Counter/Frequency Module


With ADAM-5080 4-Channel Counter/Frequency Module, users
can select either counter or frequency mode for data output.
ADAM-5080 offers users a variety of very flexible and versatile
applications such as below:

Counter Mode or Frequency Mode


If you want to measure the number of input signals for totalizer
function, you may use counter mode to measure quantities such as
movement and flow quantity. Alternatively, you can also select
frequency mode to calculate the instantaneous differential of
quantities such as rotating speed, frequency or flow rate, and present
them in specific engineering formats.

Up/Down or Bi-direction Function


When operating in counter mode, you can choose either the
Up/Down function or the Bi-direction function for different
application purposes. The counter will count up or down according
to your applications. This counting function helps users obtain the
most accurate data.

ADAM-5000 Series I/O Module Users Manual P.69

I/O Module Introduction


Alarm Setting Function
While in counter mode, you can set alarm status--Disable and Latch. If
you want to disable it, you can select Disable. If Latch status is selected,
it means the Alarm status will be "latched" whenever the alarm is being
triggered. Once the alarm status being "latched," it will thereafter stay in
that triggered state. Users will have to issue a "Clear Alarm Status"
command to return the "latched" alarm status back to normal. Users can
designate the high-limit value and low-limit value to regulate your
alarm behavior through the utility program.

Digital Output Mapping


Users can either run the utility program or issue a "Set Alarm
Connection" command to designate a specific digital output module
for the alarm signal to be sent through.

ADAM-5080 Module Diagram

Figure 52: ADAM-5080 Module

P.70 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5080 Application Wiring

Figure 53: Isolated Input Level

Figure 54: TTL Input Level

ADAM-5000 Series I/O Module Users Manual P.71

I/O Module Introduction


ADAM-5080 Counter/Frequency Mode Selection
Users can select Bi-direction, Up/Down Counter or Frequency option
as shown in Figure 44.

Figure 55: Counter / Frequency Mode


Note:

All four channels of ADAM-5080 will operate simultaneously


in the mode you have selected. i.e. If you switch the ADAM5080 to Counter Mode, all four channels will operate in Counter
Mode.

Features -- Counter Mode


Up/Down Counting
The Up/Down Counter Function offers two types of counting:
Up Counting (increasingly) and Down Counting (decreasingly).
Up Counting: when C0A+ and C0A- sense any input signals, the
counter counts up.
Down Counting: when C0B+ and C0B- sense any input signals, the
counter counts down. On receiving Up and Down signal
simultaneously, the counter will not perform each specific counting
accordingly, but will remain at the previous counting value, since
these simultaneous signals won't have any effect on counting
values.

P.72 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction

Figure 56: Wiring for Up/Down Counting


Note:

If you need only one type of counting, connect C0A+ and C0Afor Up Counting only; or connect C0B+ and C0B- for Down
Counting only.

Bi-direction Counting
For implementing Bi-direction Counting, you need to connect
C0B+/D+ and C0B-/D- to implement the control function for Up/Down
Counting. Up Counting: when the input signal is within logic level "1",
the counter value increases.

Figure 57: Wiring for Bi-direction Counting


Down Counting: when the input signal is within logic level "0", the
counter value decreases.
Note:

If users select TTL mode and don't connect C0B+ C0B-,


the counter value will increase. If users select Isolated
mode and don't connect C0B+ C0B-, the counter value will
decrease.

ADAM-5000 Series I/O Module Users Manual P.73

I/O Module Introduction


Features -- Frequency Mode
If users want to select frequency mode, they can only utilize Up
Counting type, and can only connect to C0A+ and C0A-.

Figure 58: Wiring for Frequency Mode

Features -- Alarm Setting


According to your application purposes, you can run the utility program
to set different limit values for High/Low Alarm.

Figure 59: Setting Alarm Limit

P.74 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Setting Initial Counter Value
In order to utilize the alarm function, users have to set a high-alarm limit
value and/or a low alarm limit value, and a initial value to fulfill the
requirements for a basic alarm setting.

Figure 60: Sending Alarm Signal (recommended settings)

Figure 61: Sending Alarm Signal (settings not recommended)

Overflow Value
Overflow value is the number of times the counter value exceeds the
Max/Min values you specified. When the counter value exceeds Maximum value, the overflow value increases; when the counter value goes
under Minimum value, the overflow value decreases. Besides, when the
counter value runs beyond the range of Max/Min value, it will continue
counting from the initial value. Furthermore, if users want to check the
counter value to see if it is higher or lower than the Max/Min value, they
can use the "ReadOverflowFlag" library to gain readout of the overflow value.

ADAM-5000 Series I/O Module Users Manual P.75

I/O Module Introduction


Getting the Totalizer Value
If users want to get the actual counter value, a formula such as follows
can facilitate an easy calculation from the initial counter value, overflow
value and current counter value:

Vtol = {|Vini - Vmin (or Vmax) |+ 1} x |Vvf| + |Vini - Vcur|


Vtol : totalizer value
Vini : initial counter value
Vmin : min. counter value = 0 (fixed value)
Vmax : max. counter value = 2 = 4,294,967,295 (fixed value)
Vvf : overflow value
Vcur : current counter value
32

Example:
If the initial value =10, overflow value =4, min. value = 0, current
counter value = 3, the totalizer value could be calculated as
Totalizer value = {|10 - 0| + 1} x| 4 |+ |10 -3| = 51

P.76 ADAM-5000 Series I/O Module Users Manual

Features--Digital Output Mapping


If users want to use Digital Output function, ADAM utility is
available for setting specifically which module, channel or slot to
receive the alarm signals.

Figure62: Digital Output Mapping


1:
2:
3:
4:

High Alarm State--Set Alarm state to "Latch" or "Disable".


High Alarm Limit--Set Alarm limit from 0 to 4,294,967,295.
High Alarm Output Mode--Enable or Disable D.O. Mapping.
High Alarm Output Slot--Users can select D.O Modules such
as ADAM-5050, ADAM-5055, ADAM-5056, ADAM-5060, ADAM5068 for the alarm signal to be sent through.

5: High Alarm Output Channel--Select Alarm Output Channel


6: Clear Latch Alarm--Users can select "Enable" or "Disable"
option. When selecting "Enable", the latch will be relieved and the
alarm state will return to normal. Once the alarm state returns to
normal, the Clear Latch Alarm will return to "Disable".

I/O Module Introduction


TTL/Isolated Input Level
According to your need, you can select either TTL or Isolated Input
Level by setting the configuration for the jumpers. Select the proper
jumper settings for either TTL or Isolated Input according to Figure 53.
Please note that you must configure all six jumpers to the correct configuration for proper function.

Figure 63: Jumper Location on the ADAM-5080 Module

Figure 64: TTL/Isolated Input Level Selecting

P.78 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5080 Technical Specifications
Channel

Input Frequency

0.3 ~ 1000 Hz max. (Frequency


mode) 5000 Hz max. (Counter mode)

Input Level

Isolated or TTL level

Minimum Pulse Width

500 sec. (Frequency mode) 100


sec. (Counter mode)

Minimum Input Current

2mA (Isolated)

Isolated Input Level

Logic Level 0 : +1 VMAX


Logic Level 1 : + 3.5 V to 30 V

TTL Input Level

Logic Level 0 : 0 V to 0.8 V Logic


Level 1 : 2.3 to 5 V

Isolated Voltage

1000 VRMS

Mode

Counter (Up/Down, Bi-direction)


Frequency

Programmable Digital Noise


Filter

8 ~ 65000 sec

Table 26: ADAM-5080 technical specifications

ADAM-5000 Series I/O Module Users Manual P.79

I/O Module Introduction


ADAM-5081 4-ch/8-ch High Speed Counter/Frequency
Mode Selection
Users can select Bi-direction, Up/Down Counter or Frequency option
as shown in Figure 55.
Note: this high speed module can support ADAM-5550 Series,
ADAM-5000/485,ADAM-5000E, ADAM-5000/TCP and ADAM5510M(TCP).

Figure 55: Counter / Frequency Mode


Note:

All four channels of ADAM-5081 will operate simultaneously


in the mode you have selected. i.e. If you switch the ADAM5081 to Counter Mode, all four channels will operate in Counter
Mode.

Features -- Counter Mode


Up/Down Counting
The Up/Down Counter Function offers two types of counting:
Up Counting (increasingly) and Down Counting (decreasingly).
Up Counting: when C0A+ and C0A- sense any input signals, the
counter counts up.
Down Counting: when C0B+ and C0B- sense any input signals, the
counter counts down. On receiving Up and Down signal
simultaneously, the counter will not perform each specific counting
accordingly, but will remain at the previous counting value, since
these simultaneous signals won't have any effect on counting
values.

P.80 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction

Figure 56: Wiring for Up/Down Counting


Note:

If you need only one type of counting, connect C0A+ and C0Afor Up Counting only; or connect C0B+ and C0B- for Down
Counting only.

Bi-direction Counting
For implementing Bi-direction Counting, you need to connect
C0B+/D+ and C0B-/D- to implement the control function for Up/Down
Counting. Up Counting: when the input signal is within logic level "1",
the counter value increases.

Figure 57: Wiring for Bi-direction Counting


Down Counting: when the input signal is within logic level "0", the
counter value decreases.
Note:

If users select TTL mode and don't connect C0B+ C0B-,


the counter value will increase. If users select Isolated
mode and don't connect C0B+ C0B-, the counter value will
decrease.
ADAM-5000 Series I/O Module Users Manual P.81

I/O Module Introduction


Features -- Frequency Mode
If users want to select frequency mode, they can only utilize Up
Counting type, and can only connect to C0A+ and C0A-.

Figure 58: Wiring for Frequency Mode

Features -- Alarm Setting


According to your application purposes, you can run the utility program
to set different limit values for High/Low Alarm.

P.82 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction

Figure 59: Setting Alarm Limit

Setting Initial Counter Value


In order to utilize the alarm function, users have to set a high-alarm limit
value and/or a low alarm limit value, and an initial value to fulfill the
requirements for a basic alarm setting.

Figure 60: Sending Alarm Signal (recommended settings)

ADAM-5000 Series I/O Module Users Manual P.83

I/O Module Introduction

Figure 61: Sending Alarm Signal (settings not recommended)

Overflow Value
Overflow value is the number of times the counter value exceeds the
Max/Min values you specified. When the counter value exceeds Maximum value, the overflow value increases; when the counter value goes
under Minimum value, the overflow value decreases. Besides, when the
counter value runs beyond the range of Max/Min value, it will continue
counting from the initial value. Furthermore, if users want to check the
counter value to see if it is higher or lower than the Max/Min value, they
can use the "ReadOverflowFlag" library to gain readout of the overflow value.

Getting the Totalizer Value


If users want to get the actual counter value, a formula such as follows
can facilitate an easy calculation from the initial counter value, overflow
value and current counter value:

Vtol = {|Vini - Vmin (or Vmax) |+ 1} x |Vvf| + |Vini - Vcur|


Vtol : totalizer value
Vini : initial counter value
Vmin : min. counter value = 0 (fixed value)
Vmax : max. counter value = 2 = 4,294,967,295 (fixed value)
Vvf : overflow value
Vcur : current counter value
32

Example:
If the initial value =10, overflow value =4, min. value = 0, current
counter value = 3, the totalizer value could be calculated as
Totalizer value = {|10 - 0| + 1} x| 4 |+ |10 -3| = 51

P.84 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Features--Digital Output Mapping
If users want to use Digital Output function, ADAM utility is
available for setting specifically which module, channel or slot to
receive the alarm signals.

Figure62: Digital Output Mapping


1:
2:
3:
4:

High Alarm State--Set Alarm state to "Latch" or "Disable".


High Alarm Limit--Set Alarm limit from 0 to 4,294,967,295.
High Alarm Output Mode--Enable or Disable D.O. Mapping.
High Alarm Output Slot--Users can select D.O Modules such
as ADAM-5050, ADAM-5055, ADAM-5056, ADAM-5060, ADAM5068 for the alarm signal to be sent through.

5: High Alarm Output Channel--Select Alarm Output Channel


6: Clear Latch Alarm--Users can select "Enable" or "Disable"
option. When selecting "Enable", the latch will be relieved and the
alarm state will return to normal. Once the alarm state returns to
normal, the Clear Latch Alarm will return to "Disable".

P.85 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


TTL/Isolated Input Level
According to your need, you can select either TTL or Isolated Input
Level by setting the configuration for the jumpers. Select the proper
jumper settings for either TTL or Isolated Input according to Figure 63.
Please note that you must configure all six jumpers to the correct configuration for proper function.

Figure 63: Jumper Location on the ADAM-5081 Module

P.86 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5081 Technical Specifications
Channel

Input Frequency

5 Hz~1 MHz max. (Frequency mode)


1 MHz max. (Counter mode)

Input Level

Isolated or TTL level

Minimum Pulse Width

1 sec. (Frequency mode)


1 sec. (Counter mode)

Minimum Input Current

2mA (Isolated)

Isolated Input Level

Logic Level 0 : +3 VMAX


Logic Level 1 : + 10 V to 30 V

TTL Input Level

Logic Level 0 : 0 V to 0.8 V


Logic Level 1 : 2.3 to 5 V

Isolated Voltage

2500 VRMS

Mode

Counter (Up/Down, Bi-direction, up,


A/B Phase) Frequency

Programmable Digital Noise


Filter

1 ~ 65000 sec

Table 27: ADAM-5081 technical specifications

P.87 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction

Output

P.88 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


7. Serial Module
Overview
Compatible ADAM-5000 Series Main Units
The ADAM-5090 is a 4-port RS-232 communication module to be
implemented with the following Advantech ADAM-5000 series main
units: ADAM-5510 (with library Version V1.10 or above)
ADAM-5511 (with library Version V1.10 or above)

ADAM-5090 4-port RS-232 Communication Module


Bi-direction Communication
The ADAM-5090 is equipped with four RS-232 ports, which
makes it especially suitable for bi-direction communication. It can
simultaneously read data from other third-party devices such as Bar
Code and PLC as long as these devices are equipped with a RS-232
interface. Furthermore, the ADAM-5090 can issue commands to
control other devices. It is fully integrated with the ADAM-5000,
ADAM-5500 and ADAM-4000 series, and transmits data to each
other through the RS-232 port. The whole integrated system is an
intelligent stand-alone system and can connect and issue
commands to control devices such as printers and PLCs in remote
factory location.
The ADAM-5090 transmits and receives data by polling
communication, and each port can receive up to 128 bytes in the
FIFO. For continuous data longer than 128 bytes, please refer to
Table 20 for Baud Rate setting to avoid data loss.
Baud Rate
(bps)
Polling
interval (ms)

115200

57600

38400

19200

9600

11.11

22.22

33.33

66.66

133.33

4800

2400

266.66

533.33

Table 27: Baud Rate setting reference table

P.89 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Communication Backup Function
With the ADAM-5090 you can implement dual communication
channels between your PC and the ADAM system. Even when one
of the two communication channels is down, your system can still
function through the alternative communication channel. This dual
communication channels can be implemented by application software.

ADAM-5090 Module Diagram

Figure 65: ADAM-5090 Module

ADAM-5090 Application Wiring

Figure 66: ADAM-5090 Application Wiring

P.90 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


PIN Mapping
PIN Name

RJ-48

DB9

/DCD

RX

TX

/DTR

GND

/DSR

/RTS

/CTS

RI or +5V

GND

10

Table 28: Pin Mapping

ADAM-5090 Technical Specification


Function

Provides communication ports for the ADAM5510 to integrate other devices with
communication function into your system

Electrical Interface

4 ports (RS-232)

Communication Rates

4800, 9600, 19200, 38400, 115200bps

FIFO

128 bytes/per UART (Tx/Rx)

Indicator

Tx (Orange), Rx (Green)

Power Required

100mA @ 5VDC Default in RI mode (*)

Table 29: ADAM-5090 technical specifications

User can define the communication ports with 5VDC output


by switching the jumper, and the maximum current output is
400mA.

P.91 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


I/O Slots and I/O Ports Numbering
The ADAM-5090 module provides four RS-232 ports for
communication with target devices. The ports are numbered 1
through 4. For programming, the definition of port number depends
on the slot number and port number. For example, the second port on
the ADAM-5090 in slot 1 is defined to port 12.

Jumper Settings
This section tells you how to set the jumpers to configure your
ADAM-5090 module. There are four jumpers on the PC Board. User
can choose RI signal or 5V output for each port by setting these
jumpers (system default is RI signal).
The following figure shows the location of the jumpers:

Figure 67: Jumper locations on the CPU card

Figure 68: Jumper Settings

P.92 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


LED Status of the ADAM-5090 Module
There are two LEDs for each port on the front panel of the ADAM-5090
to display specific communication status:
a. Green LED (RX): Data Receiving Status; the LED indicator is on when
the port is receiving data.
b. Orange LED (TX): Data Transmitting Status; the LED indicator is on
when the port is transmitting data.

Configure Your ADAM-5090 Module


This section explains how to configure an ADAM-5090 module before
implementing it into your application.
Quick Start
Step 1: Get your host PC ready, and run the ADAM-5510 Utility
Software.
Step 2: Install the ADAM-5090 Module and power on your ADAM5510 main unit.
Step 3: Download the executable program to the main unit
Step 4: Monitor the ADAM-5090 Modules current status from the PC
through the utility software.
A basic example program for the ADAM-5090
main ()
{
//Install the port you would like to use. Here we install slot 0,
port 1.
port_install(1);
// Here we install slot 2, port 2.
port_install(22);
//Select working port. Here we select slot 0, port 1.
port_select(1);
//Set port data format.
//Here we set the data format of port 1 as lengh:8; parity:0;stop_bit:1.
(N81)
port_set_format(1,8,0,1);

//Set port speed. Here we set communication speed of port 1 as 115200


bps.
//(L is necessary)

P.93 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


port_set_speed(1,115200L);

//Enable Port FIFO. Here we enable 128 byte FIFO for port1.
port_enable_fifo(1);

//After these above settings are enabled, you can apply any
other function library to implement your program.
}

A receive-and-transmit example program for the ADAM-5090


main()
{
int err_value, char character port_installed(1)
:
:
port_enable_fifo(1);

//check whether error has been received or not


err_value=port_rx_error(1);

//if error detected, print out the message


if(err_value)
{
printf(\n Rx Error, The LSR Value=%02X, Err_value);
}
//check whether FIFO receives data or not; if data received, read a
character
if(port_rx_ready(1))
{
character=port_rx(1);
}
//check whether FIFO is empty or not, if empty, send a character
if(port_tx_empty(1));
{
port_tx(1, character)
}
}

P.94 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5091 4-port RS-232 Communication Module with
share interrupt (Only for ADAM-5550 Series)
Bi-direction Communication
The ADAM-5091 is equipped with four RS-232 ports with share
interrupt, which makes it especially suitable for bi-direction
communication. It can simultaneously read data from other thirdparty devices such as Bar Code and PLC as long as these devices
are equipped with a RS-232 interface. Furthermore, the ADAM-5091
can issue commands to control other devices. It is fully integrated with
the ADAM-5550, and transmits data to each other through the RS232 port. The whole integrated system is an intelligent stand-alone
system and can connect and issue commands to control devices
such as printers and PLCs in remote factory location.
The ADAM-5091 transmits and receives data by sharing interrupt
communication, and each port can receive up to 128 bytes in the
FIFO. For continuous data longer than 128 bytes, please refer to
Table 27 for Baud Rate setting to avoid data loss.
Baud Rate
(bps)
Polling
interval (ms)

115200

57600

38400

19200

9600

4800

2400

11.1

22.2

33.3

66.66

133.33

266.66

533.33

Table 27: Baud Rate setting reference table


Communication Backup Function
With the ADAM-5091 you can implement dual communication
channels between your PC and the ADAM system. Even when one
of the two communication channels is down, your system can still
function through the alternative communication channel. This dual
communication channels can be implemented by application software.

P.95 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5091 Module Diagram

Figure 65: ADAM-5091 Module

ADAM-5091 Application Wiring

Figure 66: ADAM-5091 Application Wiring

P.96 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction

PIN Mapping
PIN Name

RJ-48

DB9

/DCD

RX

TX

/DTR

GND

/DSR

/RTS

/CTS

RI or +5V

GND

10

Table 28: Pin Mapping

ADAM-5091 Technical Specification


Function

Provides communication ports for the ADAM5550 to integrate other devices with
communication function into your system

Electrical Interface

4 ports RS-232

Communication Rates

4800, 9600, 19200, 38400, 115200bps

FIFO

128 bytes/per UART (Tx/Rx)

Indicator

Tx (Green), Rx (Red)

Power Required

100mA @ 5VDC Default in RI mode (*)

Table 29: ADAM-5091 technical specifications

User can define the communication ports with 5VDC output


by switching the jumper, and the maximum current output is
400mA.

P.97 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


I/O Slots and I/O Ports Numbering

The ADAM-5091 module provides four RS-232 ports for


communication with target devices. For more information about the
number of slot and COM port, you may refer to the section of "ADAM5091 COM port configuration" in ADAM-5550KW series Manual.

LED Status of the ADAM-5091 Module


There are two LEDs for each port on the front panel of the ADAM-5091
to display specific communication status:
a. Red LED (RX): Data Receiving Status; the LED indicator is on when the
port is receiving data.
b. Green LED (TX): Data Transmitting Status; the LED indicator is on
when the port is transmitting data.

P.98 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


ADAM-5095 2-port CAN Serial Communication Module with
isolation protection (Only for B version of ADAM-5550 Series)
ADAM-5095 is a special purpose communication module that offers the
connectivity of the Controller Area Network (CAN). With its built-in CAN
controllers, the ADAM-5095 provides bus arbitration and error detection
with an automatic transmission repeat function. This drastically reduces the
chance of data loss and ensures system reliability. The on-board CAN
controllers are located at different positions in the memory, and you can run
both CAN controllers independently at the same time. With highcompatibility, the ADAM-5095 can be used in diverse systems.

ADAM-5095 Diagram

Specification
General
1. Connector: 2 DB9-M
2. LED Indicator: Tx(Yellow), Rx(Green) For Each Port
3. Power Consumption: 1W (max.)
Communication
1. CAN Controller: SJA-1000
2. CAN Transceiver: 82C250
3. Protocol: CAN2.0 A/B
4. Signal Support: CAN-H, CAN-L
5. Speed: 1Mbps
Protection
1. Isolation Protection: 1000VDC

P.99 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


CAN Serial Port Pin Assignment
Pin

Table 1: CAN Serial Port Pin Assignment ( CAN1 ~ CAN2 )


CAN Signal
Definition

Termination Resistor Setting


Terminal resistors are factory installed to allow for impedance matching.
These resistors can be enabled by utilizing SW1 and SW2 for each port
(shown below). The value of the resistor should equal the characteristic
impedance of the signal wires (approximately 120 ohms). The following
figure shows resistor placements.
Enable Termination Resistor for CAN1 and CAN2 Ports ( SW1 and SW2 )

I/O Slots and I/O Ports Numbering

Therere two PCI slots on the version B of ADAM-5550 series. If only


one ADAM-5095 module is used, no mater which PCI slot is plugged,
the port number shown in the Utility would be CAN1 and CAN2. If two
ADAM-5095 modules are used, the port number shown in the Utility
would be CAN1 and CAN2 for the first PCI slot and CAN3 and CAN4
for the second PCI slot.

P.100 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


CAN Serial Port Wiring
The CAN standard supports half-duplex communication. This means that
just two wires are used to transmit and receive data.

Wiring connections are as follows:


Pin
7
3
2

Table 2: ADAM-5095 DTE Pin Wiring


ADAM-5095 DTE(DB9-M) Pin
DTE Pin Signal
Signal
CAN-H
CAN-H
GND
GND
CAN-L
CAN-L

Maximum Bit Rate vs. Bus Length


For a Controller Area Network, the maximum possible bus length depends on
the bit rate. The bit rate can always be slower than the maximum possible
speed for a given bus length. Conversely, the bus length can be shorter than
the maximum possible bus length for a given transmission speed.
Table 3: Maximum Bit rate vs. Bus Length
Bit Rate
Bus Length
1M bps
25m
800k bps
50m
500k bps
100m
250k bps
250m
125k bps
500m
50k bps
1000m
20k bps
2500m
10k bps
5000m

P.101 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


8. Storage Module
Overview
Compatible ADAM-5000 Series Main Units
The ADAM-5030 is a 2-slot SD storage module to be implemented
with the following Advantech ADAM-5000 series main units:
ADAM-5550KW

ADAM-5030 SD storage module


The ADAM-5030 storage module provides 2 slot of SD cards. When
you insert the SD card into the ADAM-5030, please remove the
name plate first. Please be careful to remove it. If you remove it
with great exertion, it may be damaged.

ADAM-5030 Diagram

Figure 69: ADAM-5030 module frontal view

P.102 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


Technical specifications of ADAM-5030
USB Type

USB Rev 2.0 (Compliant)

USB Number

Storage Type

SD (Secure Digital Card)

Storage Number
Operating Temperature
Certification
Power Consumption
Max Storage

2
0~60 (32~140)
CE
3 W (Max)
1G (Max) x 2

Format

FAT16

Surge Protection

10kW

Hot Swap

Yes

Table 30: Technical specifications of ADAM-5030

P.103 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction


9. Motion Module
Overview
Compatible ADAM-5550 Series Main Units
The ADAM-5202 is a 4-port AMONet Master module to be
implemented with the following Advantech ADAM-5000 series main
units:
ADAM-5550KW (Only)

ADAM-5202 4-port AMONet Master Module


The ADAM-5202 provides 4-port AMONet Master Module. When you
insert the SD card into the ADAM-5202, please remove the name
plate first. Please be careful to remove it. If you remove it with
great exertion, it may be damaged.

ADAM-5202 Diagram

Figure 70: ADAM-5202 module frontal view

P.104 ADAM-5000 Series I/O Module Users Manual

I/O Module Introduction

Technical specifications of ADAM-5202


Certifications

CE

Power Consumption

0.5 W (Max.)

Connectors

RJ-45

LED Indictors

Active, Error (Each Port)

Number of Rings

Transmission Speed
Serial Interface

2.5, 5, 10 or 20 Mbps with automatic data flow


control
Half duplex RS-485 with transformer isolation

Cable Type

CAT5 UTP/STP Ethernet cable

Surge Protection

10 kV

Communication

Max. 100 m (20 Mbps/32 slave modules) 50 m (20


Mbps/64 slave modules) Distance
Slave 2 Rings with Max. 128 (1 Ring with 64
slaves) Module Number
0 ~ 50 C (32 ~ 122 F)

Communication
Operating Temperature

Table 31: Technical specifications of ADAM-5202

P.105 ADAM-5000 Series I/O Module Users Manual