Você está na página 1de 38

CONTRACT NO:

1-14-3040/59

CLIENT: SHELL EASTERN PETROLEUM (PTE) Ltd.,


PROJECT TITLE:

SEPC-MEG

DISCIPLINE:

Civil Engineering

CALCULATION NO: 3041-8310-CA-0130


SAFETY CALCULATION:
COMPUTER PROGRAM:
EXCEL

CALCULATION CLASS: 1

YES
DSN: 9317
Page 1 of 28

SUBJECT
MAIN PIPE RACK SUBSTRUCTURE DESIGN

DRAWING NO'S.
3041-8310-43-0015
3041-8310-43-0016
3041-8310-43-0017

RA AREA MAIN E-W PIPE RACK FOUNDATION LAYOUT.


RB AREA MAIN E-W PIPE RACK FOUNDATION LAYOUT.
RC AREA MAIN E-W PIPE RACK FOUNDATION LAYOUT.

REFERENCE DATA

DESIGN BASIS
SS CP 65 : Part 1 : 1999
BS 6399- Part-2 : 1997
3041-8310-SP-3002
2721-8310-RP-0002
DEP 34.00.01.30

Code of practice for structural use of concrete (Incorporating


Erratum No.1, September 2000)
Loading for Buildings - Part 2 Code of practice for wind loads
Civil/Structural Engineering Guide
Preliminary Interpretative Report for Shell Houdini Project -Rev. 1
Gen. Technical specification - Minimum specification for Design
and Engineering

REMARKS

REV
A1

DATE
2-Apr-07

DESCRIPTION
Issued for Authority Approval

ORIGINATOR

CHECKER

S.L. NARAYANA

V. PREMA

APPROVER

CONTRACT NO: 1-14-3040/59

CALCULATION NO.: 3041-8310-CA-0130

PAGE 2 OF 28

CALCULATION AMENDMENT SHEET

SECTION
NO.

PAGE NO.

AMENDMENT
NO.

REMARKS

SECTION NO.

PAGE NO.

REV: A1

AMENDMENT
NO.

REMARKS

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

Originator Checker
SLN

VPP

CONTENTS
Cl. No

Sheet No.

Items
COVER SHEET

AMENDMENT SHEET

ENGINEER'S & CHECKER'S STANDARD CERTIFICATION

CONTENTS

1.0

SCOPE

2.0

DESCRIPTION

3.0

DESIGN INFORMATION

4.0

ANALYSIS METHODOLOGY

5.0

PILE CAPACITY

6.0

DESIGN PHILOSOPHY

7.0

POCKET DESIGN

10

8.0

GROUND BEAM -1, DESIGN

18

9.0

ANCHOR BOLT DESIGN

20

10.0

BASE PLATE DESIGN

21

11.0

PLINTH DESIGN

23

12.0

GROUND BEAM - 6, DESIGN

26

ENGINEER'S & CHECKER'S STANDARD CERTIFICATION

28

APPENDIX - A

POKCET DESIGN FOR ERECTION MOMENTS

A1 TO A3

APPENDIX - B

DRAWINGS

B1 TO B4

OF 28
Approver

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

1.0

Sheet No :

OF 28

Originator Checker
SLN

Approver

VPP

SCOPE
This document covers the substructure design for main pipe rack (excluding standard pile caps). Design
of standard pile caps are covered in Doc. No. 3041-8310-CA-3001.

2.0

DESCRIPTION
Main pipe rack columns are precast concrete members except stair case columns. Stair case columns are
steel members and which are supported on plinth with base plate and anchor bolts. Stair case column pile
caps are connected with ground beams for sharing of lateral forces. Ground beams are also provided
along longitudinal(E-W) direction of pipe rack at braced bay locations for sharing of longitudinal forces
from superstructure.

3.0

DESIGN INFORMATION

3.1

DESIGN CODES & SPECIFICATIONS


a) SS CP 4 : 2003

Code of practice for foundations

b) SS CP 65 : Part 1: 1999

Code of practice for structural use of concrete


(Incorporating Erratum No.1, September 2000)

c) BS 8110 -1: 1997

Part 1:Code of practice for design and


construction (Incorporating Amendments Nos:
1, 2 and 3)

d) BS 6399 -1: 1996

:
:

Loading for buildings


Part 1 : Code of practice for Dead & Imposed
Loads

e) BS 6399 -2 : 1997

:
:

Loading for buildings


Part 2 : Code of practice for Wind Loads

f) BS 5950-1 : 2000

Structural use of Steelwork in building.


Part 1: Code of practice for design Rolled and
welded sections(incorporating corrigendum No:1)

g) SS CP 73 : 1998

Code of practice for Design of concrete


structures for retaining aqueous liquids

h) Singapore Building Control Regulations (S 148/1989, Fourth, fifth & Sixth)


i) Singapore Civil Defence Force
3.2

Code of Practice for Fire Precautions in


Buildings, 1997 - (Fire Safety Bureau)

MATERIALS
a) Structural Steel
(i)

Steel Section
(Grade S275 JR)

BS EN 10210 for Hollow Section (hot-finished)


BS EN 10025 for other non-alloy steel

(ii)

Chequered floor plate

Grade S275 JR

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

Originator Checker
SLN

VPP

(iii)

High Tensile Bolts

Grade 8.8

(iv)

Anchor Bolts

Grade 4.6

(v)

Ordinary Bolts

BS 4190 for grade 4.6 and 8.8 bolts

b) Reinforced Concrete
2

(i)

Concrete grade
(below grade level)

fcu = 40 N/mm

(ii)

Concrete grade
(above grade level)

fcu = 40 N/mm

(iii)

High tensile re-bar

fy = 460 N/mm

(iv)

Mild steel re-bar

fy = 250 N/mm2

fcu = 60 N/mm2

c) Precast Reinforced Concrete Piles


Concrete grade (piles)
3.3

GENERAL LOADING CONDITION


a) Dead loads
(i)

Fireproofing concrete

24 kN/m3

(ii)

Steel

77 kN/m3

(iii)

Water

10 kN/m3

(iv)

Platform

1.0 kN/m2

(v)

Soil

18 kN/m3

OF 28
Approver

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

OF 28

Originator Checker
SLN

Approver

VPP

b) Imposed Loads
Unless otherwise stated in the calculation, imposed loads shall be based on the following.
Item
Floor Area Usage
Imposed Load
2
1
1 Operating and service areas
5.0 kN/m (See Note ) or single point load of 7.5
2
2 Access platforms, walkways and tower
2.0 kN/m or single point load of 3.0 kN
2
platforms
3 Roof
areas accessible for inspection and
1.5 kN/m or single point load of 2.0 kN
2
repairstairs
4 Plant
3.0 kN/m
2
5 Exit or public stairs
5.0 kN/m
2
6 Storage areas, light
5.0 kN/m
2
7 Storage areas, heavy
10.0 kN/m
(To be determined considering the intended
2
1
of the area)
8 use
Compressor/generator
platforms
10.0 kN/m (See Note )
2
1
9 Exchanger head platform areas or similar
5.0 kN/m (See Note )
10 equipment
Hand railing, horizontal
1 kN point load at any one point
11 Ladder, moving concentrated load
2.5 kN
12 Piping load(excluding empty weight of pipe)
a) Piping less than 300 mm diameter
0.7 kN/m2 (Operating condition)
2

b) Pipes larger than 300 mm diameter

1.5 kN/m (Test condition)


Concentrated loads in their actual
locations.

Note1 :- This live load applies only to platforms and floor slabs in areas where the possibility exists of
the flooring or slab being subjected to a concentrated load from either equipment parts or heavy tools.

c) Wind Loading
Wind loading shall be in accordance with BS 6399-2: 1997 & Shell DEP 34.00.01.30 GEN
Ground roughness category: Country.
As per cl. 8.3.7 of
3041-8310-SP-3002
The site wind speed to be taken equals basic wind speed as specified in Cl. 8.3.7 of 3041-8310-SP-3002
Wind loads for Buildings and Structures
Design wind pressure shall be determined for an hourly wind speed of 65Km/hr (18.06 m/s) for terrain
category 3. Structure is designed for 10 second gust factor.
All structures shall be designed for 10 second gust.
3.4

GROUND WATER TABLE


The ground water level is approximately 1.5m below 5.4m ACD

As per cl. 3.14.4 of


3041-8820-SP-0001

3.5

STRUCTURAL SUMMARY
The scope of this submission consists of main pipe rack substructure design .

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

3.6

Sheet No :

OF 28

Originator Checker
SLN

Approver

VPP

COMPUTER PROGRAM USED


Analysis
STAAD. Pro is capable of performing two and three dimensional analysis of structures consisting of
beam, truss, and thin Plate/shell elements. Specific applications include trusses, frames with or without
shear wall stiffening, plate and shell systems, elastically supported beams and plates, as well as a broad
range of other types of structures.
Bandwidth Reduction
The time of execution for a given STAAD.Pro run is dependent upon the bandwidth of the stiffness
matrix as determined by the joint and member numbering scheme used in the input file. STAAD.Pro
has the capability of rearranging this numbering system internally so as to minimize the time and disk
space required for execution, while maintaining a level of ease and flexibility for the user in generation
of these data.
Structural Steel Sections
STAAD.Pro contains a complete listing of standard sections. This enables the program internally to
pick up properties for analysis and design based on a simple designation in the member property
portion of input.
Generation of Joints & Members
Joints and members may be easily generated in a linear or set fashion to minimize the amount of
required input.
Offset Connections
Members, not directly connected at the geometric point of incidence, can be designated as such so
that secondary forces due to these eccentricities will be taken into account during analysis.
Spring Supports
Supports having a spring constant in any translational or rotational direction may be specified.
Loads
A variety of load types may be specified including joint, member (uniform, concentrated or linearly
varying), temperature, support displacement, area, prestressing and moving loads. In addition, the
program has the capability of calculating the self weight

Load Combination
Factored load combinations of primary loads facilitate data input and implementation of code
requirements.
Parameters for Steel Design
A variety of different design parameters such as K, F Y and Cb are available for design purposes.
These parameters have standard default values which may be changed by the user as desired.
Code Checking
Complete code checking of members may be performed according to the AISC, (Working Strength &
LRFD), AASHTO or British Codes of Practice.
Member Selection
Member selection, based on least weight criteria or design parameters such as member depth or
section profile, may be made from STAAD.Pro's internal tables or user created tables. This capability
can significantly reduce the amount of time and expense in design work.

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

OF 28

Originator Checker
SLN

Approver

VPP

Save/Restore Feature
STAAD.Pro can save the latest stiffness matrix from a run in a designated file to be reactivated at a
later point of time for additional analysis.
3.7

REFERENCE
a) Pile Design and Construction Practice. Fourth edition; By: M.J.Tomlinson
b) Foundation Analysis and Design. Fourth edition; By: Joseph E. Bowles.

4.0

ANALYSIS METHODOLOGY

4.1

ASSUMPTIONS
The following points are assumed for the strength design of pile caps.
1. One typical cast in situ pocket is designed by considering maximum reactions from all areas of the pipe
rack.
2. Top of pocket is 400mm below the H.P.P.

5.0

PILE CAPACITY
The following pile capacities are considered for the design of foundations under working conditions.
Pile Diameter
(mm)
500

6.0

Vertical Load
Capacity (kN)
1000

Uplift Capacity (kN)


200

Lateral Load Capacity(kN)


50

DESIGN PHILOSOPHY
Main pipe rack sub structure is designed by considering maximum forces from all the areas of the pipe
rack. The pile caps, ground beams, column pockets and plinths are designed by using SS CP 65 : part1:
1999. BS 5950 : part 1 is used for designing stair case. Pocket plinth for precast column is designed for
maximum support reactions from the super structure and also pocket design is checked for erection
moments which is covered in Appendix-A.

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

7.0 POCKET DESIGN


INPUT DATA:
Characteristic strength of concrete
Characteristic strength of steel

Sheet No :

Bc
Dc
Cb
Ct
H
D
c

REACTIONS:
Maximum reaction

100

800

SLN

541.66 kN
85.963 kN

100

Ref. Node No: 11, L/C 267,


RB area staad Model

300

1000

50

50

ELEVATION ALONG Z - DIRECTION

300

100

500

100

300

1000

50

Approver

VPP

= 500 mm
= 800 mm
50 mm
=
= 100 mm
= 1000 mm
= 300 mm
75 mm
=

Fx =
Fz =
300

Originator Checker

OF 28

40 N/mm2
460 N/mm2

fcu =
fy =

Pre cast column width


Pre cast column depth
Clearance at bottom
Clearance at top
Depth of pocket
Width of pocket at top
Clear cover to the reinforcement

10

50

ELEVATION ALONG X - DIRECTION

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

W1 =
=
=
W2 =
=
=

Uniform force along Z direction due to Fx

Uniform force along X direction due to Fz

11

Originator Checker
SLN

VPP

Fx/(Dc+2Ct)
541.664/((800+2*100)/1000)
541.66 kN/m
Fz/(Bc+2Ct)
85.963/((500+2*100)/1000)
122.80 kN/m

BENDING MOMENT CALCULATIONS:


with reference to the Reinforced Concrete Designer's hand book (Reynolds & Steedman) the bending
moment in the " beam" b/w the side walls can be assessed, treating the pocket as a Box culvert.

X- DIRECTION:
hs

B
Z

hw

hw
kN/m

541.664

q1

hs

D
l

Center to center distance B/W walls along


X- direction

Center to center distance B/W walls along


Z- direction

k1
k3
k5
q1

Bending moment at B & D

=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=

Bc+Ct+Ct+D/2+D/2
500+100+100+300/2+300/2
1000 mm
Dc+Ct+Ct+D/2+D/2
800+100+100+300/2+300/2
1300 mm
(l/h)(hs/hw)3
(1000/1300)*(300/300)^3
0.77
k+1
1.77
k+3
3.77
2k+3
4.54
W 1(Dc+2Ct)/h+D
541.664*(800+2*100)/(1300+300)
338.54 kN/m
q1h2k/12k1k3
338.54*(1.3)^2*0.77/(12*1.77*3.77)

OF 28
Approver

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

Mbd =
Mca =
=
=
Mx =
=
=

Bending moment at A & C

Free span moment

5.50

12

Originator Checker
SLN

VPP

kN.m

Mbdk5/k
5.50*4.54/0.77
32.45
kN.m
q1h2/8
338.54*(1.3)^2/8
71.52
kN.m

Z - DIRECTION:
q2
hs
A

B
Z
122.80

kN/m

hw
h

hw

Bending moment at C & D

Bending moment at A & B

Free span moment

hs

D
l

k =
=
=
k1 =
=
k3 =
=
k5 =
=
q2 =
=
=
Mcd =
=
=
Mab =
=
=
Mz =
=
=

(h/l)(hw/hs)3
(1300/1000)*(300/300)^3
1.3
k+1
2.30
k+3
4.3
2k+3
5.6
W 2(Bc+2Ct)/h+D
(122.80*(500+2*100))/(1000+300)
66.13 kN/m
q2*l2*k/12*k1*k3
66.13*(1)^2*1.30/(12*2.30*4.30)
0.72
kN.m
Mcdk5/k
0.72*5.60/1.30
3.12 kN.m
q2*l2/8
66.13*(1)^2/8
8.27 kN.m

OF 28
Approver

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

13

Originator Checker
SLN

OF 28
Approver

VPP

COMBINED BENDING MOMENTS ( X & Z DIRECTIONS):


1.Bending moment at A

2.Bending moment at B

3.Bending moment at C

4.Bending moment at D

5.Span moment mid span AB

6.Span moment mid span AC

Maximum design moment


Effective depth of wall

Breadth of wall considered

MA =
=
=
MB =
=
=
MC =
=
=
MD =
=
=
MAB =
=
=
MAC =
=
=
M =
d =
=
=
b =
=
=
k =

Mca+Mab
32.45+3.12
35.57
kN.m
Mbd+Mab
5.50+3.12
8.62
kN.m
Mca+Mcd
32.45+0.72
33.17
kN.m
Mbd+Mcd
5.50+0.72
6.22
kN.m
Mz-(MA+MB)/2
8.27-(35.57+8.62)/2
-13.83 kN.m
Mx-(MA+MC)/2
71.52-(35.57+33.17)/2
37.15 kN.m
37.15 kN.m
D-c-f/2
300-75-20/2
215
mm
0.45H
0.45*1000
450
mm
M/bd2fcu
As per SS CP 65: Part 1:
1999 cl. 3.4.4.4.

= 37.15*10^6/(450*215^2*40)
= 0.045
k' ( Redistribution not exceed 10%)
= 0.156
k<k', Hence compression reinforcement is not required.
Depth of lever arm

z =
=
=
zmax =
=
Hence, z
=
A
Area of steel required
sb =
=
=
Minimum % of steel
=
Asb min =
Minimum area of steel
=
Area of steel required for 450mm width
=
Hence, area of steel required per 'm' width
=

(0.5+(0.25-k/0.9))d,but not greater than 0.95d


(0.5+SQRT(0.25-0.045/0.9))*215
203.75 mm
0.95d
204.25 mm
203.75 mm
M/0.87fyz
37.15*10^6/(0.87*460*203.74584232665)
455.57 mm2
As per SS CP 65: Part 1:
0.40 %
0.4*450*300/100 1999 Table 3.27
540.00 mm2
540.00 mm2
1200
mm2

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

14

Originator Checker
SLN

OF 28
Approver

VPP

DIRECT TENSION:
Since the beam is spanning between the side walls, the UDL on the beam puts tension in the side
walls.
Tension force
Tension force in X- direction

F = Max. of forces in X & Z direction.


Fx = W 1*(Dc+2Ct)/2
= 541.66*(800+2*100)/(2*1000)
= 270.83 kN
Fz = W 2*(Bc+2Ct)/2
Tension force in Z- direction
= 122.80*(500+2*100)/(2*1000)
42.98 kN
=
Maximum tension force
F = 270.83 kN
Ast = F/0.87fy
Area of tension reinforcement
= 270.83*10^3/(0.87*460)
= 676.74 mm2
Area of steel required for 450mm width
= 1503.9 mm2
Hence, area of steel required per 'm' width
As = Asb+ 0.5 Ast
Horizontal reinforcement required per face
= 1200+0.5*1503.87
= 1951.9 mm2
20
Diameter of bar
mm
f =
Required spacing
= 160.95 mm
150
Provided spacing
=
mm
A
2094.4 mm2
Area of steel provided
s prov =
Provide 20mm dia @ 150mm c/c as horizontal reinf. on both faces.
SIDE WALLS:
Walls AB & CD

H-0.45H/2

F1

Force in the walls AB & CD

Moment in the walls due to F1

Effective depth of wall

F1 =
=
=
M1 =
=
=
d1 =
=
=

W 1*(Dc+2Ct)/2
541.66*(800+2*100)/(2*1000)
270.83 kN
F1*(H-0.45H/2)
270.83*((1000-(0.45*1000)/2)/1000)
209.89 kN.m
Bc+2*Ct+2D-c-f-f/2
(500+2*100+2*300)-75-20-20/2
1195.00 mm

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

k = M1/bd12fcu

15

Originator Checker
SLN

OF 28
Approver

VPP

As per SS CP 65: Part 1:


1999 cl. 3.4.4.4.

= 209.89*10^6/(300*1195^2*40)
= 0.0122
k' ( Redistribution not exceed 10%)
= 0.156
k<k', Hence compression reinforcement is not required.
Depth of lever arm

Area of steel required

Minimum % of steel
Minimum area of steel

Diameter of bar
No. of bars required
No. of bars provided

z = (0.5+(0.25-k/0.9))d,but not greater than 0.95d


= (0.5+SQRT(0.25-0.012/0.9))*1195
= 1178.5 mm
zmax = 0.95d1
= 0.95*1195
= 1135.3 mm
Hence, z
= 1135.3 mm
As1 = M1/0.87fyz
= 209.89*10^6/(0.87*460*1135.25)
= 461.99 mm2
= 0.40 %
Asmin = 0.4*D*Bc+2*Ct+2D/100
= 0.4*300*(500+2*100+2*300)/100
= 1560.00 mm2
f = 25 mm
= 3.18
4
=
Provide 4-25dia , vertical bars at corners.

SIDE WALLS:
Walls AC & BD

H-0.45H/2

F2

Force in the walls AC & BD

Moment in the walls due to F2

Effective depth of wall

F2 =
=
=
M2 =
=
=
d2 =
=
=

W 2*(Bc+2Ct)/2
122.80*(500+2*100)/(2*1000)
42.98 kN
F2*(H-0.45H/2)
42.98*((1000-(0.45*1000)/2)/1000)
33.31 kN.m
Dc+2*Ct+2D-c-f-f/2
(800+2*100+2*300)-75-20-20/2
1495.00 mm

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

k = M2/bd22fcu

16

Originator Checker
SLN

OF 28
Approver

VPP

As per SS CP 65: Part 1:


1999 cl. 3.4.4.4.

= 33.31*10^6/(300*1495^2*40)
0.001
=
k' ( Redistribution not exceed 10%)
= 0.156
k<k', Hence compression reinforcement is not required.
Depth of lever arm

Area of steel required

Minimum % of steel
Minimum area of steel

Diameter of bar
No. of bars required
No. of bars provided

DISTRIBUTION STEEL:

z = (0.5+(0.25-k/0.9))d,but not greater than 0.95d


= (0.5+SQRT(0.25-0.001/0.9))*1495
= 1492.9 mm
zmax = 0.95d
= 0.95*1495
= 1420.3 mm
Hence, z
= 1420.3 mm
As2 = M2/0.87fyz
= 33.31*10^6/(0.87*460*1420.25)
= 58.606 mm2
= 0.40 %
Asmin = 0.4*D*Dc+2*Ct+2D/100
= 0.4*300*(800+2*100+2*300)/100
= 1920.00 mm2
f = 25 mm
= 3.91
4
=
Provide 4-25dia , vertical bars at corners.
As per SS CP 65: Part 1:
1999 cl. 3.4.4.4.

Distribution of steel

= 0.25% of concrete area


= 0.25*300*1000/100
= 750
mm2
fs = 16
Diameter of bar provided
mm
Required spacing
= 268.08 mm
Provided spacing
= 150
mm
Provide 16 dia @ 150mm c/c as vertical reinforcement on both faces.
CHECK FOR SHEAR:
Considering shear in upper zone of pocket with following dimensions.
Breadth of section considered
b = Depth of wall section is considered.
= 1000
mm
Top width of wall is considered.
Depth of section
D = 300
mm
Effective depth of section
d = D-c-f/2
= 300-75-20/2
= 215
mm
Maximum reaction
V = Max. of F1 & F2
= 270.83 kN
As per SS CP 65: Part 1:
Design shear stress
v = V/bd
1999 cl. 3.4.5.2
= 270.83*10^3/(1000*215)
= 1.26 N/mm2
vc = 0.84{100As/bd}1/3(400/d)1/4/gm
Design concrete shear stress
100As/bd should not be greater than 3.
400/d should not be taken as less than 1.
If fcu is greater than 30N/mm2, vc may be

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

17

Originator Checker
SLN

OF 28
Approver

VPP

multiplied by (fcu/30)1/3, the value of fcu should


not greater than 40N/mm2
100As/bd
= 0.97 < 3 So, 100As/bd = 0.97
400/d
= 1.86 > 1 So, 400/d
= 1.86
= {[0.84*0.97^(1/3)*1.86^(1/4]/1.25}*(40/30)^(1/3)
0.86 N/mm2
=
v > v c, Hence, Provide Shear reinforcement.
Providing diagonal bars to resist the shear.
Asv = bvsv(v-vc)/0.87fy
Vb = Asb(0.87fy)(Cosa + sin acot b)d-d'/Sb
Vb = (v-vc)*bd
= (1.26-0.86)*300*215/1000
26.02 kN
=
Diameter of diagonal bars
Area of diagonal bar
Required spacing
Provided spacing of diagonal bars

=
=
=
=

13
132.73
173.54
150

mm
mm2
mm
mm

Hence provide 13mm diameter bars@150mm c/c as diagonal bars.

13mm dia@150mm c/c

20mm dia @150mm c/c

16mm dia @ 150mm c/c

v v
v

4-25mm dia bars at four


corners.

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

8.0 GROUND BEAM -1, DESIGN


INPUT DATA:
fcu =
40 N/mm2
Characteristic strength of concrete
fy = 460 N/mm2
Characteristic strength of steel
1.5
gf =
Average factored dead+live factor
75 mm
Cover to the reinforcement
C =
Max. axial force
F = 604.17 kN
Summation of forces near braced bay -RB area staad Model
Area of steel required to resist axial force

Diameter of bar provided at top and bottom


No. of bars provided at top and bottom
Provided area of steel

18

OF 28

Originator Checker
SLN

Approver

VPP

Ref page 26 of 27,


3041-8310-CA-0017

Asc reqd. = gfF/0.87fy


= 1.5*604.17*10^3/(0.87*460)
= 2264.5 mm2
f = 32 mm
6 No.s
=
Asc prov. = 6*3.14*32^2/4
= 4825.5 mm2

BEAM SIZE:

Designing the beam as a column member, assuming the member sizes.


Width of member
Depth of member
Ultimate axial load

b = 400 mm
D = 600 mm
N = 0.4fcuAc+0.75Ascfy

As per SS CP 65: Part 1:


1999 cl. 3.8.4.3, equation -38

= 0.4*40*(400*6004825.49)+0.75*4825.49*460)/1000
= 5427.6 kN >
Hence Safe.

604.17

kN

CHECKING FOR SELF WEIGHT & SOIL WEIGHT:


Length of member
Unit weight of concrete
Self weight of member
Moment due to self weight

Depth of soil above ground beam

l = 7.0 m
wc = 24 kN/m3
W 1 = 0.4*0.6*24
= 5.76 kN/m
M1 = W 1l2/8
= 5.76*7^2/8
= 35.28
kN.m
Ds = 1.45 m
H.P.P - Top of pile cap-50mm,
100.000-98.600-0.050

Unit weight of soil


Weight on member due to soil
Moment due to soil weight

Total moment

g = 18 kN/m3
W 2 = 0.4*1.45*18
= 10.4 kN/m
M2 = W 2l2/8
= 10.44*7^2/8
= 63.9 kN.m
M = M1+M2
= 35.28+63.95
= 99.2 kN.m

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

19

Originator Checker
SLN

OF 28
Approver

VPP

Reinforcement required to resist moment:


99.23 kN.m
M =
d = D-c-f/2
= 600-75-32/2
= 509 mm
b = 400 mm
k = M/bd2fcu

Maximum design moment


Effective depth of member

Breadth of beam considered

As per SS CP 65: Part 1:


1999 cl. 3.4.4.4.

= 99.23*10^6/(400*509^2*40)
= 0.024
k' ( Redistribution not exceed 10%)
= 0.156
k<k', Hence compression reinforcement is not required.
Depth of lever arm

z = (0.5+(0.25-k/0.9))d,but not greater than 0.95d


= (0.5+SQRT(0.25-0.024/0.9))*509
= 495.08 mm
zmax = 0.95d
= 483.55 mm
Hence, z
= 483.55 mm
Asb = M/0.87fyz
= 99.23*10^6/(0.87*460*483.55)
= 512.75 mm2
= 0.13 %
As per SS CP 65: Part 1:
Asb min = 0.13*400*600/100 1999 Table 3.27
= 312.00 mm2
= 512.75 mm2
= 512.75 mm2

Area of steel required

Minimum % of steel
Minimum area of steel

Hence, area of steel required


Area of steel required from self weight & axial force = 2264.51+512.75
= 2777.25 mm2
Provided steel
= 4825.5 mm2
GB-1 is O.K.

H.P.P
400

1000

G.B.
50

P.C.

FOSTER WHEELER
SUBJECT
PROJECT
CONTRACT NO
SAFET CALC
CALC NO

20

OF

28

SEPC-MEG

Rev.

Date

Originator

Checker

Approver

1-14-3040/59

A1

2-Apr-2007

SLN

VPP

MAIN PIPE RACK SUBSTRUCTURE DESIGN

Page No

YES
3041-8310-CA-0130

9.0

ANCHOR BOLT DESIGN


For anchor bolt design, unfactored loads are considered.
Critical Load cases
L/C
Fx
Fy
Fz
Node
113
3.136
407.346
76.986 Maximum Fz
300
162
-0.988
-145.387
-48.864 Minimum Fy
300
Case 1: Node no.300 load case 113 (Maximum Fz)
Assume diameter of bolt
24 mm
=
2
=
Tensile area of bolt
361.91 mm
Number of anchor bolts
=
4
2
Cl. 15.2 of 3041-8310-SP-3003
Permissible shear stress of bolt
=
80 N/mm
2
Permissible tensile stress of Bolt =0.8*ft
=
120 N/mm
for Grade 4.6 bolts.
2
2
Resultant Shear on Bolts
= sqrt(Fx +Fz )/No. of Bolts
=
19.26 kN
2
Shear stress per bolt
=
53.22 N/mm
< 80, O.K
Case 2: Node no.300 load case 162 (Minimum Fy)
Assume diameter of bar
24 mm
=
2
=
Tensile area of bolt
361.91 mm
Number of anchor bolts
=
4
2
Cl. 15.2 of 3041-8310-SP-3003
Permissible shear stress of bolt
=
80 N/mm
2
Permissible tensile stress of bolt =0.8*ft
=
120 N/mm
for Grade 4.6 bolts.
2
2
Resultant shear on bolts
= sqrt(Fx +Fz )/No. of Bolts
12.22 kN
2
Shear stress per bolt
=
33.76 N/mm
< 80, O.K
Tensile force per bolt
=
36.35 kN
2
Tensile stress per bolt
=
100.43 N/mm
< 120, O.K
Interaction ratio
=
1.26
<1.4, O.K
Anchor bolt projection

P = t+b+(n+0.5)d+ (50mm for bolts > 36mm dia


meter to allow for taper)
where
t
b
n
d
0.5

=
Thickness of grout
= Thickness of base plate
= Number of bolts
= Diameter of bolt
= Allowance for one washer and a small projection beyond
the nuts.
=
25+25+(1+0.5)*24
mm
= 86

Use 4 No. Anchor Bolts, Type : A242/2

FOSTER WHEELER
MIAN PIPE RACK SUBSTRUCTURE DESIGN
SUBJECT
21
Page No
SEPC-MEG
PROJECT
Originator
Rev.
Date
1-14-3040/59
CONTRACT NO
A1
02.04.07
SLN
YES
SAFET CALC
3041-8310-CA-0130
CALC NO
10.0 BASE PLATE DESIGN
Designed for Maximum force in FY & FZ Direction
(STAIR CASE COLUMNS)
(Based on STAAD Output, Load case 213, Node # 300)
For base plate design, factored loads are considered.

28
Approver

VPP

P
e

M2
A2

H2
B2

M1
H1

1
A2

t
B1

A1

fc

OF
Checker

FT

A1

Fc
y

2
PLAN

ELEVATION

Ultimate loads (kN & kNm)

P
488.816

H1
3.764

H2
92.384

M1
0

M2
0

Eqv. moment
M2'
0.00

Resultant
Hor. load
92.46

A2
50

B2
300

Plate
t
25

Column
depth breadth Flange
209.6
205.8
14.2

Eccentricity
( mm )
0.00

Geometry (mm)

A1
50

B1
300

W eb
9.4

Bolt (each side)


No. **
Dia
Ten. Area
2
24
706
** Provide no. on either
side of axis

Design parameters
Conc.
grade
40

Allow. Bearing (pb)


on conc (MPa)
16

Modular ratio
15.00

Allowable stress in bolt (MPa)


Tensile (pt)
Shear (ps)
192
160

2-2

Allow. stress (pyp)


in .base pl. (MPa)
235

Results
Tensile stress (ft) Shear stress (fs)
in bolts (MPa)
in bolts (MPa)
0.00
65.48

Interaction
ratio
0.41

Bearing stress (fc)


on conc.(MPa)
3.06

Bending stress in
base plate.(MPa)
1.51
< Pyp
O.K.

< pt

< ps

< 1.4

< or = pb

O.K.

O.K.

O.K.

O.K.

Note
1. Equivalent moment is computed as per cl. 3.8.4.5 of BS 8110: Part 1 : 1985
2. Analysis is as per Design in Structural Steel ..... J. E. Lothers.
Eqn. =

y =

mm

c = 10.14 mm (BS 5950 : cl 4.13.2.1)

FOSTER WHEELER
SUBJECT
PROJECT
CONTRACT NO
SAFET CALC
CALC NO

MAIN PIPE RACK SUB STRUCTURE DESIGN

22

OF

28

Rev.

Date

Originator

Checker

Approver

A1

27.03.07

SLN

PREMA

Page No

SEPC-MEG
1-14-3040/59
YES
3041-8310-CA-0130

Design with gussets (mm)


Check for overall section

Height

Section is checked here

64.06 mm

1 no. of stiffener

Stiffeners
No.
2

Thk.
12

2 no. of stiffeners
3

Sec. mod. (mm )

Stress in base

Stress in gst.

Btm.
Top
1602642 486728

plate.(MPa)
3.46

plate.(MPa)
11.38

Moment of
Height
250

Inertia (mm )
102669271

Check for individual panel.


Uniform pressure of
is assumed.

(See note below.)


3.06

MPa below the base

1
Corner Panel

(Two adjacent edges are supported.)

b
'a' is always smaller side of the panel.

2
a

(mm)

(mm)

85.10

95.20

a/b
0.89

Stress at 1

Stress at 2

(MPa)

(MPa)

68.54
< Pyp, --- O.K.

Interior Panel

67.41
< Pyp, --- O.K.

(Three edges are supported.)

a
1
b
2

a
(mm)

b
(mm)

a/b

Stress at 1
(MPa)

Stress at 2
(MPa)

Stress at 3
(MPa)

102.90

95.20

1.08

17.13
< Pyp, --- O.K.

13.09
< Pyp, --- O.K.

26.67
< Pyp, --- O.K.

Note

Design coefficients are taken from ROARK's Formulas for Stress and Strains
.... W arren C Yong.

FOSTER WHEELER
SUBJECT
PROJECT
CONTRACT NO
SAFET CALC

MAIN PIPE RACK SUBSTRUCTURE DESIGN

CALC NO

3041-8310-CA-0130

22

OF

28

Rev.

Date

Originator

Checker

Approver

A1

02.04.07

SLN

VPP

Page No

SEPC-MEG
1-14-3040/59
YES

CHECK WELD
PROVIDE 10 mm FILLET WELD
Input Data

d1

b1

B=
D=
T1 =
t2 =

205.8
209.6
14.2
9.4

mm
mm
mm
mm

r=

15.2

mm

b1 =

83

mm

d1 =

165

mm

t2
B

r
T1

Weld Size =
8
mm
Weld Length W L= 2*B+2*d1+4*b1
= 2*205.8+2*165+4*83
= 1073.6 mm
Force on weld Due to P=FP= = P / W L=

488.816/1073.6

Force on weld due to H1,F H1=H1/W L =


Force on weld due to H2=F H2=H2/W L =

3.764/1073.6
92.384/1073.6

=
=

Resltant Force on weld = sqrt(FP2+FH12+FH22) =

Weld Capacity

= 0.7*220*8/1000
=
Table 37 of BS 5950-1:2000

0.455 kN/mm
0.004 kN/mm
0.086 kN/mm

Sqrt(0.455^2+0.004^2+0.086^2)
0.463 kN/mm
=

1.232 kN/mm O.K

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

11.0 PLINTH DESIGN


INPUT DATA:
Characteristic strength of concrete
Characteristic strength of steel
Length of pedestal
Breadth of pedestal
Height of pedestal
Unit weight of concrete
Clear cover to reinforcement
Dia. of longitudinal bar
Dia. of horizontal reinforcement
LOADS ON PLINTH:
Downward force
Lateral forces

Sheet No :

23

Originator Checker
SLN

OF 28
Approver

VPP

fcu
fy
l
b
H
wc
c
f
ft

=
=
=
=
=
=
=
=
=

40
460
600
600
1000
24
75
20
10

N/mm2
N/mm2
mm
mm
mm
kN/m3
mm
mm
mm

Fy = 488.816 kN
Fx =
3.764 kN
Fz = 92.384 kN

X
l

Ref. Node No:300,L/C 253,


RA-1 area staad Model

Moments
Mx =
Mz =

0
0

kN.m
kN.m

MOMENTS DUE TO ECCENTRICTY


=

20

mm

Minimum eccentricity

Momnet due to eccentricity

Me = Fy*e
= 488.816*0.02
9.78 kN.m
=

As per SS CP 65: Part 1:


1999, Cl. 3.8.2.4

DESIGN FORCES & MOMENTS


Self. Weight of plinth

Total Downward force

Moment about X - axis

Moment about Z - axis

SLENDERNESS RATIO:
Effective length of pedestal

Effective width of pedestal

wp =
=
=
Pu =
=
=
MX =
=
=
MZ =
=
=

l*b*H*wc
0.6*0.6*1*24
8.64 kN
Fy+wp
488.82+8.64
497.46 kN
Fz*H+Mx or Me
92.38*1+0
92.38 kN.m
Fx*H+Mz or Me
9.78
9.78 kN.m

l'

l-c-f/2
600-75-20/2
515.00 mm
b-c-f/2
600-75-20/2

=
=
=
b' =
=

Whichever is maximum

515.00 mm

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

Slenderness ratio

24

Originator Checker
SLN

OF 28
Approver

VPP

= l '/ b'
= 515/515
= 1.00

Bi- AXIAL MOMENT CHECK


Mx/l' Mz/b', Mx' = MX + b(l'/h')MZ
Mx/l' <Mz/b', Mz' = MZ + b(b'/l')MX

Equation 40
Equation 41

P/BLfcu
b

= 497.46*10^3/(600*600*40)
= 0.035
= 0.956
As per SS CP 65: Part 1:
1999 Table. 3.24

MX/l'

= 92.38/0.515
= 179.39 kN
= 9.78/0.515
= 18.98 kN
Mx' = 101.73 kNm
Mu = 101.73 kNm

MZ/b'

Hence, ultimate design moment


REINFORCEMENT :
Longitudinal bars:
Mu/bl2
Pu/bl
b'/b

=
=
=

0.47
1.38
0.86

N/mm2
N/mm2
As per BS 8110-3 : 1985
From chart No: 37

Reinforcement required is very less, Hence provide minimum % of reinforcement.


Minimum % of steel

As per SS CP 65: Part 1:

0.4

1999 Table. 3.27

Area of steel required


Diameter of bar provided
No. of bars required
Provided No. of bars
Provided area of steel

Asc

= 0.4*600*600/100
= 1440.00 mm2
f = 20 mm
= 4.58 No.S
= 8 No.s
= 2513.3 mm2
Hence Provide 8 No.s of 20 dia. bars.

Lateral Ties:
As per SS CP 65: Part 1:

a. 1/4th of the dia. of longitudinal bar


b. 6mm
Diameter of tie - bars, maximum of a & b
Provided diameter of bar
Spacing required for tie bars
Provided spacing for ties

mm

= 6
= 10

mm

ft

1999 cl. 3.12.7

= 12 times longitunal bar.


= 120 mm
= 100 mm

Hence provide 10mm ties at 100mm c/c.

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

25

Originator Checker
SLN

OF 28
Approver

VPP

CHECK FOR SHEAR REINFORCEMENT :


As per SS CP 65: Part 1:
1999 cl. 3.8.4.6

N = 0.4fcuAc + 0.75Ascfy
=
= 6586.9 kN
Mu/N = 15.44 mm
300 mm
0.6b =
Mu/N < 0.6b
Hence O.K.

Ultimate axial load on column

8-20dia bars

600

10 dia ties @100mm c/c

600

Note: In the above figure, X is the distance between anchor bolt and plinth main reinforcement bar, it is
less than E/3( E is Anchorbolt embedment length), hence no need to provide the tensile vertical hairpin
reinforcement to transfer tensile forces from anchor bolt to main reinforcement.

Providing plinth - P2 for the stair case columns which is covered in Dwg. No: 3041-8310-39-3011,
plinth typical details.

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

12.0 GROUND BEAM - 6, DESIGN


INPUT DATA:
Characteristic strength of concrete
Characteristic strength of steel

fcu =
fy =

40 N/mm2
460 N/mm2

Cover to the reinforcement


Max. axial force

C =
F =

75 mm
76.987

26

Originator Checker
SLN

OF 28
Approver

VPP

Ref. Node No: 300, L/C 11,


RA-1 area staad Model

Area of steel required to resist axial force

Diameter of bar provided at top and bottom


No. of bars provided at top and bottom
Provided area of steel

Asc reqd. = 1.5F/0.87fy


= 1.5*76.987*10^3/(0.87*460)
= 288.56 mm2
f = 16 mm
6 No.s
=
Asc prov. = 6*3.14*16^2/4
= 1206.4 mm2

BEAM SIZE:

Designing the beam as a column member, assuming the member sizes.


Width of member
Depth of member
Ultimate axial load

b = 300 mm
D = 400 mm
N = 0.4fcuAc+0.75Ascfy

As per SS CP 65: Part 1:


1999 cl. 3.8.4.3, equation -38

= 0.4*40*(300*4001206.37)+0.75*1206.37*460)/1000
= 2316.9 kN >
Hence Safe.

76.987

kN

CHECKING FOR SELF WEIGHT & SOIL WEIGHT:


Length of member
Unit weight of concrete
Self weight of member
Moment to due to self weight

Depth of soil above ground beam


Unit weight of soil
weight on member due to soil
Moment due to soil weight

Total moment

l = 6.0 m
wc = 24 kN/m3
W 1 = 0.3*0.4*24
= 2.88 kN/m
M1 = W 1l2/8
= 2.88*6^2/8
= 12.96
kN.m
Ds = 1.45 m
100.000-98.600
g = 18 kN/m3
W 2 = 0.3*1.45*18
= 7.83 kN/m
M2 = W 2l2/8
= 7.83*6^2/8
= 35.2 mm
M = M1+M2
= 12.96+35.24
= 48.2 kN.m

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

27

Originator Checker
SLN

OF 28
Approver

VPP

Reinforcement required to resist moment:


48.20 kN.m
M =
d = D-c-f/2
= 400-75-16/2
= 317 mm
b = 300 mm
k = M/bd2fcu

Maximum design moment


Effective depth of member

Breadth of wall considered

As per SS CP 65: Part 1:


1999 cl. 3.4.4.4.

= 48.20*10^6/(300*317^2*40)
= 0.040
k' ( Redistribution not exceed 10%)
= 0.156
k<k', Hence compression reinforcement is not required.
Depth of lever arm

z = (0.5+(0.25-k/0.9))d,but not greater than 0.95d


= (0.5+SQRT(0.25-0.040/0.9))*317
= 302.23 mm
zmax = 0.95d
= 301.15 mm
Hence, z
= 301.15 mm
Asb = M/0.87fyz
Area of steel required
= 48.20*10^6/(0.87*460*301.15)
= 399.89 mm2
Minimum % of steel
= 0.13 %
As per SS CP 65: Part 1:
Asb min = 0.13*300*400/100 1999 Table 3.27
Minimum area of steel
= 156.00 mm2
399.89 mm2
=
399.89 mm2
Hence, area of steel required
=
Area of steel required from self weight & axial force = 288.56+399.89
= 688.45 mm2
Provided steel
= 1206.4 mm2
GB-6 is O.K.

H.P.P
400

1000

G.B.
50

PLINTH

FOSTER WHEELER
SUBJECT :

MAIN PIPE RACK SUBSTRUCTURE DESIGN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Originator Checker

APPENDIX - A
POCKET DESIGN FOR ERECTION MOMENTS.

SLN

VPP

Approver

FOSTER WHEELER
SUBJECT :

DESIGN OF POCKET FOR P.C. COLUMN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

INPUT DATA:
Characteristic strength of concrete
Characteristic strength of steel
Pre cast column width
Pre cast column depth
Clearance at bottom
Clearance at top
Depth of pocket
Width of pocket at top
Clear cover to the reinforcement

Sheet No :

fcu
fy
Bc
Dc
Cb
Ct
H
D
c

A1

Originator Checker
SLN

OF A9
Approver

VPP

40 N/mm2
=
= 460 N/mm2
= 500 mm
= 800 mm
50 mm
=
= 100 mm
= 1000 mm
= 300 mm
75 mm
=

1% of factored self.
Wt. of beam

Longitudinal Direction - X

Transverse Direction-Z

Main transverse

Wind load

P.C. Column

Figure :3

Figure :1

Figure :2

I) Checking of precast pocket for erection stage:


i) Due to wind load: [Figure :1]

During erection stage precast columns will be free standing cantilever and will be subjected to wind
loads as shown in figure :1.

As shown in figure :3, column size is more along transverse direction(Z), hence wind load along
longitudinal direction(X) is considered on the column.
Column size
Wind pressure
External building coefficient

Cpe

=
=
=

500
0.689
2

800

mm

kN/m2
As per BS 6399-2:1997
Table 20

Height of column considered


Wind load on the column
Moment due to wind load on column

Hence, factored moment about Z-axis


Factored shear force due to long. wind load

l = 12 m
w = 0.8*0.689*2
1.10 kN/m
=
Mw = wl2/2
= 1.10*12^2/2
79.37 kN.m
=
Mz = 1.5*79.37
= 119.06 kN.m
Fx = g*w*l
= 1.5*1.10*12
= 19.843 kN

FOSTER WHEELER
SUBJECT :

DESIGN OF POCKET FOR P.C. COLUMN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

A2

Originator Checker
SLN

OF A9
Approver

VPP

ii) Other Forces: [Figure :2]


To resist the erection forces due to practical imperfections such as lack of verticality and incidental
loading, 1% of factored dead load of main transverse beam at EL. +112.00 is considered as horizontal
force in the pocket as shown in figure :2.
As per BS 5950-1:2000, Cl. 2.4.2.3
450
750
mm
=
x
= 12 m
= 1.5*1*0.45*0.75*24*12/100
1.46 kN
=
Fz =
1.46 kN
Mx = 1.46*12
17.50 kN.m
=

Size of main transverse beam at EL. +112.00


Length of main transverse beam
1% of factored self weight of beam
Hence, shear force in the transverse direction
Moment about X-axis
300

100

800

100

300

2/3H

1000

Mx

w4

w3

w3

50

Reaction due to moment

50

ELEVATION ALONG Z - DIRECTION [FOR ERECTION LOAD]


300

100

500

100

300

2/3H

1000

Mz

w2

w1

w1

Reaction due to moment

50

50

ELEVATION ALONG X - DIRECTION [FOR WIND LOAD]

ALONG Z-AXIS
Uniform force due to moment about Z axis

Uniform force along Z direction due to Fx

Total UDL on pocket along Z- direction

w1 =
=
=
w2 =
=
=
W1 =
=
=

(Mz/2/3H)/(Dc+2Ct)
{119.06/[(2/3*1000)/1000]/[(800+2*100)/1000]}
178.589 kN/m
Fx/(Dc+2Ct)
19.8432/((800+2*100)/1000)
19.843 kN/m
w1+w2
178.589+19.843
198.432 kN/m

FOSTER WHEELER
SUBJECT :

DESIGN OF POCKET FOR P.C. COLUMN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

ALONG X-AXIS
Uniform force due to moment about X-axis

Sheet No :

w3 =
=
=
w4 =
=
=
W2 =
=
=

Uniform force along X direction due to Fz

Total UDL on pocket along X- direction

A3

Originator Checker
SLN

(Mx/2/3H)/(Bc+2Ct)
{17.50/[(2/3*1000)/1000]/[(500+2*100)/1000]}
37.49 kN/m
Fz/(Bc+2Ct)
1.46/((500+2*100)/1000)
2.08 kN/m
w3+w4
37.49+2.08
39.57 kN/m

moment in the " beam" b/w the side walls can be assessed, treating the pocket as a Box culvert.

X- DIRECTION:
hs

Z
hw

hw

198.432 kN/m

q1

hs

D
l

Center to center distance B/W walls along


X- direction

Center to center distance B/W walls along


Z- direction

k1
k3
k5
q1

=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=

Approver

VPP

BENDING MOMENT CALCULATIONS:


with reference to the Reinforced Concrete Designer's hand book (Reynolds & Steedman) the bending

OF A9

Bc+Ct+Ct+D/2+D/2
500+100+100+300/2+300/2
1000 mm
Dc+Ct+Ct+D/2+D/2
800+100+100+300/2+300/2
1300 mm
(l/h)(hs/hw)3
(1000/1300)*(300/300)^3
0.77
k+1
1.77
k+3
3.77
2k+3
4.54
W 1(Dc+2Ct)/h+D
198.432*(800+2*100)/(1300+300)
124.02 kN/m

FOSTER WHEELER
SUBJECT :

DESIGN OF POCKET FOR P.C. COLUMN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

A4

Originator Checker
SLN

VPP

= q1h2k/12k1k3
= 124.02*(1.3)^2*0.77/(12*1.77*3.77)
Mbd = 2.01
kN.m
Mca = Mbdk5/k
= 2.01*4.54/0.77
= 11.89
kN.m
Mx = q1h2/8
= 124.02*(1.3)^2/8
= 26.20
kN.m

Bending moment at B & D

Bending moment at A & C

Free span moment

Z - DIRECTION:
q2
hs
A

B
Z
39.57

hw

hw

kN/m

Bending moment at C & D

Bending moment at A & B

Free span moment

hs

D
l
k =
=
=
k1 =
=
k3 =
=
k5 =
=
q2 =
=
=
Mcd =
=
=
Mab =
=
=
Mz =
=
=

(h/l)(hw/hs)3
(1300/1000)*(300/300)^3
1.3
k+1
2.30
k+3
4.3
2k+3
5.6
W 2(Bc+2Ct)/h+D
(39.574*(500+2*100))/(1000+300)
21.31 kN/m
q2*l2*k/12*k1*k3
21.31*(1)^2*1.30/(12*2.30*4.30)
0.23
kN.m
Mcdk5/k
0.23*5.60/1.30
1.01 kN.m
q2*l2/8
21.31*(1)^2/8
2.66 kN.m

OF A9
Approver

FOSTER WHEELER
SUBJECT :

DESIGN OF POCKET FOR P.C. COLUMN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

A5

Originator Checker
SLN

OF A9
Approver

VPP

COMBINED BENDING MOMENTS ( X & Z DIRECTIONS):


MA =
=
=
MB =
=
=
MC =
=
=
MD =
=
=
MAB =
=
=
MAC =
=
=
M =
d =
=
=
b =
=
=
k =

1.Bending moment at A

2.Bending moment at B

3.Bending moment at C

4.Bending moment at D

5.Span moment mid span AB

6.Span moment mid span AC

Maximum design moment


Effective depth of wall

Breadth of wall considered

Mca+Mab
11.89+1.01
12.89
kN.m
Mbd+Mab
2.01+1.01
3.02
kN.m
Mca+Mcd
11.89+0.23
12.12
kN.m
Mbd+Mcd
2.01+0.23
2.25
kN.m
Mz-(MA+MB)/2
2.66-(12.89+3.02)/2
-5.29 kN.m
Mx-(MA+MC)/2
26.20-(12.89+12.12)/2
13.69 kN.m
13.69 kN.m
D-c-f/2
300-75-20/2
215
mm
0.45H
0.45*1000
450
mm
M/bd2fcu
As per SS CP 65: Part 1:
1999 cl. 3.4.4.4.

= 13.69*10^6/(450*215^2*40)
= 0.016
= 0.156

k' ( Redistribution not exceed 10%)

k<k', Hence compression reinforcement is not required.


Depth of lever arm

z = (0.5+(0.25-k/0.9))d,but not greater than 0.95d


= (0.5+SQRT(0.25-0.016/0.9))*215
= 210.99 mm
zmax = 0.95d
= 204.25 mm
Hence, z
= 204.25 mm

Area of steel required

Minimum %age of steel


Minimum area of steel
Area of steel required for 450mm width
Hence, area of steel required per 'm' width

Asb =
=
=
=
Asb min =
=
=
=

M/0.87fyz
13.69*10^6/(0.87*460*204.25)
167.52 mm2
0.40 %
As per SS CP 65: Part 1:
0.4*450*300/100 1999 Table 3.27
540.00 mm2
540.00 mm2
1200
mm2

FOSTER WHEELER
SUBJECT :

DESIGN OF POCKET FOR P.C. COLUMN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

A6

Originator Checker
SLN

OF A9
Approver

VPP

DIRECT TENSION:
Since the beam is spanning between the side walls, the UDL on the beam puts tension in the side
walls.
Tension force
Tension force in X- direction

Tension force in Z- direction

Maximum tension force


Area of tension reinforcement
Area of steel required for 450mm width
Hence, area of steel required per 'm' width
Horizontal reinforcement required per face

F = Max. of forces in X & Z direction.


Fx = W 1*(Dc+2Ct)/2
= 198.43*(800+2*100)/(2*1000)
99.22 kN
=
Fz = W 2*(Bc+2Ct)/2
= 39.57*(500+2*100)/(2*1000)
13.85 kN
=
99.22 kN
F =
Ast = F/0.87fy
= 99.22*10^3/(0.87*460)
= 247.92 mm2
= 550.92 mm2
As = Asb+ 0.5 Ast
= 1200+0.5*550.92
= 1475.5 mm2

f =

Diameter of bar
Required spacing
Provided spacing
Area of steel provided

As prov

=
=
=

20
212.92
200
1570.8

mm
mm
mm
mm2

Provide 20mm dia @ 200mm c/c as horizontal reinf. on both faces.


SIDE WALLS:
Walls AB & CD

H-0.45H/2

F1

Force in the walls due to UDL & moment

Force due to moment

Moment in the walls due to F1 & F2

Effective depth of wall

F2

F1 =
=
=
F2 =
=
=
M1 =
=
=
d1 =
=
=

W 1*(Dc+2Ct)/2
198.43*(800+2*100)/(2*1000)
99.22 kN
w1*(Dc+2Ct)/2
178.59*(800+2*100)/(2*1000)
89.29 kN
F1*(H-0.45H/2)-(F2*0.45H/2)
99.22*((1000-(0.45*1000)/2)/1000)89.2944*(0.45*1000/2)/1000
56.80 kN.m
Bc+2*Ct+2D-c-f-f/2
(500+2*100+2*300)-75-20-20/2
1195.00 mm

FOSTER WHEELER
SUBJECT :

DESIGN OF POCKET FOR P.C. COLUMN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

k = M1/bd12fcu

A7

Originator Checker
SLN

OF A9
Approver

VPP

As per SS CP 65: Part 1:


1999 cl. 3.4.4.4.

= 56.80*10^6/(300*1195^2*40)
= 0.0033
k' ( Redistribution not exceed 10%)
= 0.156
k<k', Hence compression reinforcement is not required.
Depth of lever arm

Area of steel required

Minimum %age of steel


Minimum area of steel

Diameter of bar
No. of bars required
No. of bars provided

z = (0.5+(0.25-k/0.9))d,but not greater than 0.95d


= (0.5+SQRT(0.25-0.003/0.9))*1195
= 1190.6 mm
zmax = 0.95d1
= 0.95*1195
= 1135.3 mm
Hence, z
= 1135.3 mm
As1 = M1/0.87fyz
= 56.80*10^6/(0.87*460*1135.25)
= 125.02 mm2
= 0.40 %
Asmin = 0.4*D*Bc+2*Ct+2D/100
= 0.4*300*(500+2*100+2*300)/100
= 1560.00 mm2
f = 25 mm
= 3.18
4
=
Provide 4-25dia , vertical bars at corners.

SIDE WALLS:
Walls AC & BD

H-0.45H/2

F3

Force in the walls due to UDL & moment

Force due to moment

Moment in the walls due to F2

Effective depth of wall

0.45H/2

F4

F3 =
=
=
F4 =
=
=
M2 =
=
=
d2 =
=
=

W 2*(Bc+2Ct)/2
39.57*(500+2*100)/(2*1000)
13.85 kN
w3*(Bc+2Ct)/2
37.49*(500+2*100)/(2*1000)
13.12 kN
F3*(H-0.45H/2)-F4*0.45H/2
13.85*((1000-(0.45*1000)/2)/1000)13.122*((0.45*1000/2)/1000)
7.78 kN.m
Dc+2*Ct+2D-c-f-f/2
(800+2*100+2*300)-75-20-20/2
1495.00 mm

FOSTER WHEELER
SUBJECT :

DESIGN OF POCKET FOR P.C. COLUMN

PROJECT:

SEPC-MEG

Rev

Date

CONTRACT NO :

1 - 14 - 3040/ 59

A1

2-Apr-07

SAFETY CALC.

YES

CALC. NO

3041-8310-CA-0130

Sheet No :

k = M2/bd22fcu

A8

Originator Checker
SLN

OF A9
Approver

VPP

As per SS CP 65: Part 1:


1999 cl. 3.4.4.4.

= 7.78*10^6/(300*1495^2*40)
0.000
=
k' ( Redistribution not exceed 10%)
= 0.156
k<k', Hence compression reinforcement is not required.
Depth of lever arm
z = (0.5+(0.25-k/0.9))d,but not greater than 0.95d
= (0.5+SQRT(0.25-0.000/0.9))*1495
= 1494.5 mm
zmax = 0.95d
= 0.95*1495
= 1420.3 mm
Hence, z
= 1420.3 mm
As2 = M2/0.87fyz
Area of steel required
= 7.78*10^6/(0.87*460*1420.25)
= 13.692 mm2
Minimum %age of steel
= 0.40 %
Asmin = 0.4*D*Dc+2*Ct+2D/100
Minimum area of steel
= 0.4*300*(800+2*100+2*300)/100
= 1920.00 mm2
Diameter of bar
f = 25 mm
No. of bars required
= 3.91
4
No. of bars provided
=

DISTRIBUTION STEEL:

Provide 4-25dia , vertical bars at corners.


As per SS CP 65: Part 1:
1999 cl. 3.4.4.4.

Distribution of steel

Diameter of bar provided


Required spacing
Provided spacing

=
=
=
fs =
=
=

0.25% of concrete area


0.25*300*1000/100
750
mm2
16
mm
268.08 mm
200
mm

Provide 16 dia @ 200mm c/c as vertical reinforcement on both faces.


CHECK FOR SHEAR:
Considering shear in upper zone of pocket with following dimensions.
Breadth of section considered
b = Depth of wall section is considered.
= 1000
mm
Top width of wall is considered.
Depth of section
D = 300
mm
Effective depth of section
d = D-c-f/2
= 300-75-20/2
= 215
mm
Maximum reaction
V = Max. of F1 & F3
As per SS CP 65: Part 1:
99.22 kN
1999 cl. 3.4.5.2
=
Design shear stress
v = V/bd
= 99.22*10^3/(1000*215)
= 0.46 N/mm2
vc = 0.84{100As/bd}1/3(400/d)1/4/gm
Design concrete shear stress
100As/bd should not be greater than 3.
400/d should not be taken as less than 1.
If fcu is greater than 30N/mm2, vc may be
multiplied by (fcu/30)1/3, the value of fcu should
not greater than 40N/mm2