Você está na página 1de 65

Non-Directional Overcurrent

and Earth Fault Protection

GRID
Technical Institute

This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.

Overcurrent Protection: Purpose of Protection

Detect abnormal conditions


Isolate faulty part of the system
Speed

Fast operation to minimise damage and danger


Discrimination

Isolate only the faulty section


Dependability / reliability
Security / stability
Cost of protection / against cost of potential hazards

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Co-ordination

F1

F2

F3

Co-ordinate protection so that relay nearest to fault


operates first
Minimise system disruption due to the fault

> Non-Directional Overcurrent and Earth Fault Protection

Fuses

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Fuses


Simple

Can provide very fast fault clearance

<10ms for large current


Limit fault energy
Arcing Time
Pre Arc Time

Prospective Fault Current

Total
Operating
Time

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Fuses - disadvantages


Problematic co-ordination

Fuse A

Fuse B

IFA approx 2 x IFB


Limited sensitivity to earth faults
Single phasing
Fixed characteristic

Need replacing following fault clearance


6

> Non-Directional Overcurrent and Earth Fault Protection

Tripping Methods

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Direct Acting AC Trip

51

Trip Coil

IF

AC series trip

common for electromechanical O/C relays

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Direct Acting AC Trip

IF'
+

51
-

Sensitive
Trip
Coil

IF

Capacitor discharge trip

used with static relays where no secure DC supply is


available

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection DC Shunt Trip

IF'

51

IF
DC
BATTERY

Requires secure DC auxiliary

No trip if DC fails
10

> Non-Directional Overcurrent and Earth Fault Protection

SHUNT
TRIP COIL

No Volt Trip Coil: Relay Un-Operated

51

No Volt
Release
Trip Coil

Used for fail-safe tripping on motor feeders

11

> Non-Directional Overcurrent and Earth Fault Protection

No Volt Trip Coil: Relay Operated


IF'

IF

51

No Volt
Release
Trip Coil

Used for fail-safe tripping on motor feeders

12

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection

13

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Principles

Operating Speed

Instantaneous
Time delayed
Discrimination

Current setting

Time setting
Current and time
Cost

Generally cheapest form of protection relay

14

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Instantaneous Relays

50

IF2

50

IIF1

Current settings chosen so that relay closest to fault


operates

Problem

Relies on there being a difference in fault level between the


two relay locations

Cannot discriminate if IF1 = IF2

15

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Definite (Independent)


Time Relays
TIME

TOP

IS
(Relay Current Setting)

16

> Non-Directional Overcurrent and Earth Fault Protection

Applied Current

Overcurrent Protection Definite (Independent)


Time Relays

51

51

0.9 sec

0.5 sec

Operating time is independent of current


Relay closest to fault has shortest operating time

Problem

Longest operating time is at the source where fault level is


highest

17

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection IDMT


TIME

IS
(Relay Current Setting)

Applied Current

Inverse Definite Minimum Time characteristic

18

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Disc Type O/C Relays

Current setting via plug bridge


Time multiplier setting via disc
movement

Single characteristic
Consider 2 ph & EF or 3 ph plus
additional EF relay

19

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Static Relay

Electronic, multi characteristic


Fine settings, wide range
Integral instantaneous elements
20

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Numerical Relay

I>1
I>2
Time

I>3
I>4
Current

Multiple characteristics and stages


Current settings in primary or secondary values
Additional protection elements

21

> Non-Directional Overcurrent and Earth Fault Protection

Co-ordination

22

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Co-ordination Principle

Relay closest to fault


must operate first

R2

R1

Other relays must have


adequate additional
operating time to
prevent them operating

IF1
T

Current setting chosen


to allow FLC

IS2 IS1

23

Maximum
Fault
Level

> Non-Directional Overcurrent and Earth Fault Protection

Consider worst case


conditions, operating
modes and current
flows

Overcurrent Protection Co-ordination Example


E

Operating time (s)

10

C
B
0.1

0.01

Current (A)

24

> Non-Directional Overcurrent and Earth Fault Protection

FLB

FLC

FLD

Overcurrent Protection IEC Characteristics


1000

t =

0.14
(I0.02 -1)

VI

t =

13.5
(I2 -1)

EI

t =

LTI t =

80
(I2 -1)

100
Operating Time (s)

SI

10
LTI
SI

1
VI

120
(I - 1)

EI

0.1
1

10

100

Current (Multiples of Is)

25

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Operating Time Setting Terms Used

Published characteristics are


drawn against a multiple of
current setting or Plug Setting
Multiplier
Therefore characteristics can be
used for any application
regardless of actual relay
current setting
e.g at 10x setting (or PSM of 10)
SI curve op time is 3s

26

> Non-Directional Overcurrent and Earth Fault Protection

1000

Operating Time (s)

Relay operating times can be


calculated using relay
characteristic charts

100

10

0.1
1

10
100
Current (Multiples of Is)

Overcurrent Protection Current Setting

Set just above full load current

allow 10% tolerance


Allow relay to reset if fault is cleared by downstream
device

consider pickup/drop off ratio (reset ratio)


relay must fully reset with full load current flowing

PU/DO for static/numerical = 95%

PU/DO for EM relay = 90%

e.g for numerical relay, Is = 1.1 x IFL/0.95

27

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Current Setting


Current grading

ensure that if upstream relay has started downstream relay has


also started

R1

R2

IF1

Set upstream device current setting greater than downstream relay


e.g. IsR1 = 1.1 x IsR2

28

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Grading Margin


Operating time difference between two devices to ensure
that downstream device will clear fault before upstream
device trips
Must include

breaker opening time

allowance for errors


relay overshoot time
safety margin

GRADING
MARGIN

29

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Grading Margin between relays

R2

R1

Traditional

breaker op time relay overshoot allow. For errors safety margin Total
Calculate using formula

30

> Non-Directional Overcurrent and Earth Fault Protection

0.1
0.05
0.15

0.1
0.4s

Overcurrent Protection Grading Margin between relays


Formula

t = (2Er + Ect) t/100 + tcb + to + ts

Er = relay timing error

Ect = CT measurement error

t = op time of downstream relay

tcb = CB interupting time

to = relay overshoot time

ts = safety margin

Op time of Downstream Relay t = 0.5s

0.375s margin for EM relay, oil CB


0.24s margin for static relay, vacuum CB

31

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Grading Margin relay with fuse

Grading Margin = 0.4Tf + 0.15s over whole characteristic


Assume fuse minimum operating time = 0.01s
Use EI or VI curve to grade with fuse

Current setting of relay should be 3-4 x rating of fuse to


ensure co-ordination

32

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Grading Margin relay with upstream fuse

Tf
Tr
I FMAX

1.175Tr

Allowance for CT
and relay error

0.1
CB

or
Tf = 2Tr + 0.33s
33

> Non-Directional Overcurrent and Earth Fault Protection

0.1
Safety margin

0.6Tf
Allowance for
fuse error (fast)

Overcurrent Protection Time Multiplier Setting

Used to adjust the


operating time of an
inverse characteristic
Not a time setting but a
multiplier
Calculate TMS to give
desired operating time
in accordance with the
grading margin

Operating Time (s)

100

10

0.1
1

34

> Non-Directional Overcurrent and Earth Fault Protection

10
100
Current (Multiples of Is)

Overcurrent Protection
Time Multiplier Setting - Calculation

Calculate relay operating time required, Treq

consider grading margin


fault level
Calculate op time of inverse characteristic with
TMS = 1, T1
TMS = Treq /T1

35

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Co-ordination - Procedure

Calculate required operating current

Calculate required grading margin


Calculate required operating time
Select characteristic
Calculate required TMS
Draw characteristic, check grading over whole
curve

Grading curves should be drawn to a common


voltage base to aid comparison
36

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Co-ordination Example

200/5

100/5
I
FMAX
= 1400 Amp

B
Is = 5 Amp

A
Is = 5 Amp; TMS = 0.05, SI

Grade relay B with relay A


Co-ordinate at max fault level seen by both
relays = 1400A
Assume grading margin of 0.4s
37

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Co-ordination Example

200/5

100/5
I
FMAX
= 1400 Amp

B
Is = 5 Amp

A
Is = 5 Amp; TMS = 0.05, SI

Relay B is set to 200A primary, 5A secondary


Relay A set to 100A If (1400A) = PSM of 14

relay A OP time = t = 0.14 x TMS = 0.14 x 0.05 = 0.13


(I0.02 -1)
(140.02 -1)
Relay B Op time = 0.13 + grading margin = 0.13 + 0.4 = 0.53s
Relay A uses SI curve so relay B should also use SI curve
38

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection Co-ordination Example


200/5

100/5
I
FMAX
= 1400 Amp

B
Is = 5 Amp

A
Is = 5 Amp; TMS = 0.05, SI

Relay B Op time = 0.13 + grading margin = 0.13 + 0.4 = 0.53s


Relay A uses SI curve so relay B should also use SI curve
Relay B set to 200A If (1400A) = PSM of 7
relay B OP time TMS = 1 = 0.14 x TMS =
0.14
= 3.52s
(I0.02 -1)
(70.02 -1)
Required TMS = Required Op time = 0.53 = 0.15
Op time TMS=1
3.52
Set relay B to 200A, TMS = 0.15, SI
39

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection
LV Protection Co-ordination
11kV
MCGG

CB

350MVA

2 x 1.5MVA
11kV/433V
5.1%
CTZ61

ACB
ACB

1
2
3
4
F

40

Relay 1
Relay 2
Relay 3
Relay 4
Fuse

> Non-Directional Overcurrent and Earth Fault Protection

CTZ61

(Open)

2
1

MCCB
27MVA

Fuse
Load

20MVA

Overcurrent Protection
LV Protection Co-ordination
1000S

100S

TX damage

10S
Very
inverse

1.0S

0.1S
0.01S

0. 1kA
41

> Non-Directional Overcurrent and Earth Fault Protection

10kA

1000kA

Overcurrent Protection
LV Protection Co-ordination
11kV
KCGG 142

CB

350MVA

2 x 1.5MVA
11kV/433V
5.1%
KCEG 142

ACB
ACB

1
2
3
4
F

Relay 1
Relay 2
Relay 3
Relay 4
Fuse

3
2
1

> Non-Directional Overcurrent and Earth Fault Protection

MCCB
27MVA

Fuse
Load

42

(Open)

K
20MVA

Overcurrent Protection
LV Protection Co-ordination
1000S
100S

Long time
inverse
TX damage

10S

1.0S
0.1S

0.01S
0. 1kA
43

> Non-Directional Overcurrent and Earth Fault Protection

10kA

1000kA

Blocking Schemes

44

> Non-Directional Overcurrent and Earth Fault Protection

System Grading
Downstream protection must grade with the utility incomer at the maximum
(1)
(2)
fault level
First
11kV Supply

Metering CB
(Utility)

Attempt

Compromised
Grading

1.0s

1.0s

0.7s

1.0s

0.4s

0.7s

0.1s

0.7s

??s

0.4s

??s

0.4s

??s

0.1s

Load

Load
45

Load

Manufacturers
Technical
Update
Oct
2010 > Non-Directional
Overcurrent
and Earth Fault
Protection

Blocking Schemes - Principles (2)


Blocking schemes eliminates grading time and will trip the CB after 100ms has elapsed, scheme
will remove blocking signal should the CB fail to trip

Incomer
BLOCK for IF1

IF2

IF1

46

Ideal application for GOOSE messaging over IEC61850

Manufacturers
Technical
Update
Oct
2010 > Non-Directional
Overcurrent
and Earth Fault
Protection

IEC61850 Architecture

Agile with
IEC61850

47

Manufacturers
Technical
Update
Oct
2010 > Non-Directional
Overcurrent
and Earth Fault
Protection

Delta/Star Transformers

48

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection
Transformer Protection - 2-1-1 Fault Current

Turns Ratio
= 3 :1

A phase-phase fault
on one side of
transformer produces
2-1-1 distribution on
other side
Use an overcurrent
element in each
phase (cover the 2x
phase)
2 & EF relays can
be used provided
fault current > 4x
setting

49

> Non-Directional Overcurrent and Earth Fault Protection

Iline

Idelta

0.866 If3

Overcurrent Protection
Transformer Protection - 2-1-1 Fault Current
Turns
Ratio =
3 :1

Istar = E-/2Xt = 3 E-n/2Xt


Istar = 0.866 E-n/Xt
Istar = 0.866 If3

Iline
Idelta

0.866 If3

Idelta = Istar/3 = If3 /2


Iline = If3

50

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection
Transformer Protection - 2-1-1 Fault Current

51

51

HV

LV

Grade HV relay
with respect to
2-1-1 for -
fault
Not only at max
fault level
86.6%If3

51

> Non-Directional Overcurrent and Earth Fault Protection

If3

Use of High Sets

52

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection
Instantaneous Protection

Fast clearance of faults

ensure good operation factor, If >> Is (5 x ?)


Current setting must be co-ordinated to prevent
overtripping

Used to provide fast tripping on HV side of transformers


Used on feeders with Auto Reclose, prevents transient
faults becoming permanent

AR ensures healthy feeders are re-energised


Consider operation due to DC offset - transient overreach

53

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection
Instantaneous OC on Transformer Feeders

Set HV inst 130% IfLV


HV2

HV1

LV

No operation for LV fault

TIME

HV2

Fast operation for HV fault

HV1

Reduces op times
required of upstream
relays

LV

IF(LV)

IF(HV)

CURRENT

1.3IF(LV)

54

Stable for inrush

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection:
Transient Overreach
Ability to ignore DC offset

Low overreach allows los Inst setting to be used

high operation factor


Immunity to LV transformer faults
55

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection:
Transient Overreach

I
2

I1

I1 = steady state rms pickup

Overreach = (I1 I2)/I2


Typical values

numerical relay = < 5%


Simple EM relay = >60%

56

> Non-Directional Overcurrent and Earth Fault Protection

I2 = rms pickup with fully offset signal

Low overreach allows low


setting high operation
factor
High transient overreach
necessitates high settings
poor sensitivity, slow

Overcurrent Protection:
Partial Differential Protection

Zoned busbar
protection using
overcurrent relays

67

Bus section relay not


required reduced
grading stages

67

51

Time delayed tripping


for busbar fault
51

51

57

> Non-Directional Overcurrent and Earth Fault Protection

51

Overcurrent Protection:
Interlocked OC Protection

Problem due to location of


CTs
Feeder circuit fault seen
outside feeder zone but
inside busbar zone
Fault remains fed from
remote end will be cleared by
remote time delayed
protection
Circuit
Protection
Busbar
Protection

58

> Non-Directional Overcurrent and Earth Fault Protection

Speed up fault clearance with


local Interlocked OC relay
short time delay enabled by
BB protection trip

Earthfault Protection

59

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection
Earth Fault Protection

Earth fault current may be limited


Sensitivity and speed requirements may not be met by
overcurrent relays

Use dedicated EF protection relays


Connect to measure residual (zero sequence) current

Can be set to values less than full load current


Co-ordinate as for OC elements

May not be possible to provide co-ordination with fuses

60

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection
Earth Fault Relay Connection - 3 Wire System

E/F

OC

OC

OC

Combined with OC relays

61

> Non-Directional Overcurrent and Earth Fault Protection

E/F

OC

OC

Economise using 2x OC
relays

Overcurrent Protection
Earth Fault Relay Connection - 4 Wire System

E/F

OC

OC

OC

EF relay setting must be


greater than normal
neutral current

62

> Non-Directional Overcurrent and Earth Fault Protection

E/F

OC

OC

OC

Independent of neutral
current but must use 3 OC
relays for phase to neutral
faults

Overcurrent Protection
Earth Fault Relays Current Setting

Solid earth

30% Ifull load


adequate

Resistance earth

setting w.r.t earth fault level


special considerations for
impedance earthing directional?

63

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection
Sensitive Earth Fault Relays
A
B
C

Settings down to
0.2% possible

E/F

Isolated/high
impedance earth networks
For low settings cannot use residual connection, use
dedicated CT
Advisable to use core balance CT
CT ratio related to earth fault current not line current

Relays tuned to system frequency to reject 3rd harmonic


64

> Non-Directional Overcurrent and Earth Fault Protection

Overcurrent Protection
Core Balance CT Connections

OPERATION

NO OPERATION

INSULATION

Need to take care with core


balance CT and armoured
cables
Sheath acts as earth return
path
Must account for earth
current path in connections
- insulate cable gland
65

> Non-Directional Overcurrent and Earth Fault Protection

CABLE GLAND
CABLE
BOX

E/F

CABLE GLAND/SHEATH
EARTH CONNECTION

Você também pode gostar