Escolar Documentos
Profissional Documentos
Cultura Documentos
GRID
Technical Institute
This document is the exclusive property of Alstom Grid and shall not be
transmitted by any means, copied, reproduced or modified without the prior
written consent of Alstom Grid Technical Institute. All rights reserved.
F1
F2
F3
Fuses
Total
Operating
Time
Fuse A
Fuse B
Tripping Methods
51
Trip Coil
IF
AC series trip
IF'
+
51
-
Sensitive
Trip
Coil
IF
IF'
51
IF
DC
BATTERY
No trip if DC fails
10
SHUNT
TRIP COIL
51
No Volt
Release
Trip Coil
11
IF
51
No Volt
Release
Trip Coil
12
Overcurrent Protection
13
Operating Speed
Instantaneous
Time delayed
Discrimination
Current setting
Time setting
Current and time
Cost
14
50
IF2
50
IIF1
Problem
15
TOP
IS
(Relay Current Setting)
16
Applied Current
51
51
0.9 sec
0.5 sec
Problem
17
IS
(Relay Current Setting)
Applied Current
18
Single characteristic
Consider 2 ph & EF or 3 ph plus
additional EF relay
19
I>1
I>2
Time
I>3
I>4
Current
21
Co-ordination
22
R2
R1
IF1
T
IS2 IS1
23
Maximum
Fault
Level
10
C
B
0.1
0.01
Current (A)
24
FLB
FLC
FLD
t =
0.14
(I0.02 -1)
VI
t =
13.5
(I2 -1)
EI
t =
LTI t =
80
(I2 -1)
100
Operating Time (s)
SI
10
LTI
SI
1
VI
120
(I - 1)
EI
0.1
1
10
100
25
26
1000
100
10
0.1
1
10
100
Current (Multiples of Is)
27
R1
R2
IF1
28
GRADING
MARGIN
29
R2
R1
Traditional
breaker op time relay overshoot allow. For errors safety margin Total
Calculate using formula
30
0.1
0.05
0.15
0.1
0.4s
ts = safety margin
31
32
Tf
Tr
I FMAX
1.175Tr
Allowance for CT
and relay error
0.1
CB
or
Tf = 2Tr + 0.33s
33
0.1
Safety margin
0.6Tf
Allowance for
fuse error (fast)
100
10
0.1
1
34
10
100
Current (Multiples of Is)
Overcurrent Protection
Time Multiplier Setting - Calculation
35
200/5
100/5
I
FMAX
= 1400 Amp
B
Is = 5 Amp
A
Is = 5 Amp; TMS = 0.05, SI
200/5
100/5
I
FMAX
= 1400 Amp
B
Is = 5 Amp
A
Is = 5 Amp; TMS = 0.05, SI
100/5
I
FMAX
= 1400 Amp
B
Is = 5 Amp
A
Is = 5 Amp; TMS = 0.05, SI
Overcurrent Protection
LV Protection Co-ordination
11kV
MCGG
CB
350MVA
2 x 1.5MVA
11kV/433V
5.1%
CTZ61
ACB
ACB
1
2
3
4
F
40
Relay 1
Relay 2
Relay 3
Relay 4
Fuse
CTZ61
(Open)
2
1
MCCB
27MVA
Fuse
Load
20MVA
Overcurrent Protection
LV Protection Co-ordination
1000S
100S
TX damage
10S
Very
inverse
1.0S
0.1S
0.01S
0. 1kA
41
10kA
1000kA
Overcurrent Protection
LV Protection Co-ordination
11kV
KCGG 142
CB
350MVA
2 x 1.5MVA
11kV/433V
5.1%
KCEG 142
ACB
ACB
1
2
3
4
F
Relay 1
Relay 2
Relay 3
Relay 4
Fuse
3
2
1
MCCB
27MVA
Fuse
Load
42
(Open)
K
20MVA
Overcurrent Protection
LV Protection Co-ordination
1000S
100S
Long time
inverse
TX damage
10S
1.0S
0.1S
0.01S
0. 1kA
43
10kA
1000kA
Blocking Schemes
44
System Grading
Downstream protection must grade with the utility incomer at the maximum
(1)
(2)
fault level
First
11kV Supply
Metering CB
(Utility)
Attempt
Compromised
Grading
1.0s
1.0s
0.7s
1.0s
0.4s
0.7s
0.1s
0.7s
??s
0.4s
??s
0.4s
??s
0.1s
Load
Load
45
Load
Manufacturers
Technical
Update
Oct
2010 > Non-Directional
Overcurrent
and Earth Fault
Protection
Incomer
BLOCK for IF1
IF2
IF1
46
Manufacturers
Technical
Update
Oct
2010 > Non-Directional
Overcurrent
and Earth Fault
Protection
IEC61850 Architecture
Agile with
IEC61850
47
Manufacturers
Technical
Update
Oct
2010 > Non-Directional
Overcurrent
and Earth Fault
Protection
Delta/Star Transformers
48
Overcurrent Protection
Transformer Protection - 2-1-1 Fault Current
Turns Ratio
= 3 :1
A phase-phase fault
on one side of
transformer produces
2-1-1 distribution on
other side
Use an overcurrent
element in each
phase (cover the 2x
phase)
2 & EF relays can
be used provided
fault current > 4x
setting
49
Iline
Idelta
0.866 If3
Overcurrent Protection
Transformer Protection - 2-1-1 Fault Current
Turns
Ratio =
3 :1
Iline
Idelta
0.866 If3
50
Overcurrent Protection
Transformer Protection - 2-1-1 Fault Current
51
51
HV
LV
Grade HV relay
with respect to
2-1-1 for -
fault
Not only at max
fault level
86.6%If3
51
If3
52
Overcurrent Protection
Instantaneous Protection
53
Overcurrent Protection
Instantaneous OC on Transformer Feeders
HV1
LV
TIME
HV2
HV1
Reduces op times
required of upstream
relays
LV
IF(LV)
IF(HV)
CURRENT
1.3IF(LV)
54
Overcurrent Protection:
Transient Overreach
Ability to ignore DC offset
Overcurrent Protection:
Transient Overreach
I
2
I1
56
Overcurrent Protection:
Partial Differential Protection
Zoned busbar
protection using
overcurrent relays
67
67
51
51
57
51
Overcurrent Protection:
Interlocked OC Protection
58
Earthfault Protection
59
Overcurrent Protection
Earth Fault Protection
60
Overcurrent Protection
Earth Fault Relay Connection - 3 Wire System
E/F
OC
OC
OC
61
E/F
OC
OC
Economise using 2x OC
relays
Overcurrent Protection
Earth Fault Relay Connection - 4 Wire System
E/F
OC
OC
OC
62
E/F
OC
OC
OC
Independent of neutral
current but must use 3 OC
relays for phase to neutral
faults
Overcurrent Protection
Earth Fault Relays Current Setting
Solid earth
Resistance earth
63
Overcurrent Protection
Sensitive Earth Fault Relays
A
B
C
Settings down to
0.2% possible
E/F
Isolated/high
impedance earth networks
For low settings cannot use residual connection, use
dedicated CT
Advisable to use core balance CT
CT ratio related to earth fault current not line current
Overcurrent Protection
Core Balance CT Connections
OPERATION
NO OPERATION
INSULATION
CABLE GLAND
CABLE
BOX
E/F
CABLE GLAND/SHEATH
EARTH CONNECTION