Você está na página 1de 14

MEMORIA DESCRIPTIVA

INSTALACIONES ELECTRICAS

1. NOMBRE DEL PROYECTO ................................................................................................................ 3


2. UBICACIN DEL PROYECTO ............................................................................................................ 3
3. GENERALIDADES ............................................................................................................................... 3
4. ALCANCE DEL PROYECTO ............................................................................................................... 3
5. DESCRIPCION DEL PROYECTO ....................................................................................................... 4
7. DEMANDA DE POTENCIA. ................................................................................................................. 6
8. CDIGO Y REGLAMENTOS .............................................................................................................14
9. PRUEBAS 14

1. NOMBRE DEL PROYECTO


Complejo Residencial Juvenil de Reinsercin Educativa y Deportiva Ollantaytambo.

2. UBICACIN DEL PROYECTO


Regin

Lima

Provincia

Lima

Distrito

Ate Vitarte

Zona

04

Sub Zona

Ubicacin

Avenida Alfonso Ugarte y Jr. El Progreso.

3. GENERALIDADES
El presente proyecto comprende el desarrollo de las Instalaciones Elctricas a nivel de redes
exteriores, alimentadores a los tableros de distribucin, e instalaciones de interiores de los
diferentes mdulos, a nivel de ejecucin en obra, del Complejo Residencial Juvenil de
Reinsercin Educativa y Deportiva Ollantaytambo.

4. ALCANCE DEL PROYECTO


El proyecto de Instalaciones Elctricas comprende lo siguiente:

Diseo de las Redes exteriores (alimentadores a los Tableros General y de


Distribucin e iluminacin exterior y interior).

Instalaciones de interiores (Iluminacin, tomacorrientes y fuerza) de los mdulos y/o


locales.

El proyecto comprende el diseo de las Instalaciones Elctricas de interiores y exteriores a


nivel de ejecucin de obra de: Iluminacin, tomacorrientes, alimentadores a los diferentes
equipos, como son: equipos de cmputo, electrobombas, etc.

5. DESCRIPCION DEL PROYECTO


Suministro de energa
Para el presente Proyecto, Complejo Residencial Juvenil, contar con un suministro trifsico
380 V. La empresa contratista deber solicitar con debida anticipacin (al inicio de obra) la
Factibilidad de Suministro de la nueva potencia contratada de acuerdo al presente estudio.
En caso de ser diferentes el sistema de tensin proyectado y el sistema de tensin de la
empresa concesionaria, se informar inmediatamente al proyectista para adecuar o
modificar el tablero y alimentador.
Instalaciones de interiores
Estas se refieren generalmente instalaciones elctricas en los mdulos que comprenden
circuitos de iluminacin, tomacorrientes, esquemas de los tableros de distribucin con
interruptores termo-magnticos e interruptores diferenciales de 30 mA de sensibilidad
Los artefactos de iluminacin a utilizarse son

LUMINARIA FAGERHULT 566896. 40 w.

LUMINARIA FAGERHULT 29551 2x28 w.

LUMINARIA FAGERHULT 35219 2x54 w.

LUMINARIA FAGERHULT 29553 2x 35w.

LUMINARIA FAGERHULT 64416 79 w.

LUMINARIA FAGERHULT 29510 80 w.

LUMINARIA FAGERHULT 56890 22 w.

LUMINARIA FAGERHULT 56892 60 w.

LUMINARIA FAGERHULT 56931 40 w.

Cada circuito de iluminacin interior llevar lnea de proteccin a tierra y estar protegido
con su respectivo interruptor diferencial.
Los tomacorrientes sern del tipo universal, dobles con lnea a tierra a 220V. Cada circuito
de tomacorriente llevar su respectivo interruptor diferencial.

Red de iluminacin exterior


Estas se refieren generalmente instalaciones elctricas en el exterior que comprenden
circuitos de iluminacin, esquemas de los tableros de distribucin con interruptores termomagnticos e interruptores diferenciales de 30 mA de sensibilidad.
Los artefactos de iluminacin a utilizarse son:

INCA 400 w.

INCA 250 w.

7. DEMANDA DE POTENCIA.
Tablero General TG

TABLERO
T-G

DESCRIPCION
Sub tablero ST-1
Sub tablero ST-2
Sub tablero ST-3
Sub tablero ST-4
Sub tablero ST-5
Sub tablero ST-6
Sub tablero ST-7
Sub tablero ST-8
Sub tablero ST-9
Sub tablero ST-10
Sub tablero ST-11
Sub tablero ST-12
Sub tablero ST-13
Sub tablero ST-14
Sub tablero ST-15
Sub tablero ST-16
Sub tablero ST-17

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda

3,813.94
1,776.86
1,421.58
2,384.08
3,376.58
3,972.93
409.82
5,340.88
5,076.72
11,675.00
5,119.51
4,286.33
1,302.94
1,600.01
11,682.74
20,950.00
3,128.00

w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w
w

3,813.94
1,776.86
1,421.58
2,384.08
3,376.58
3,972.93
409.82
5,340.88
5,076.72
11,675.00
5,119.51
4,286.33
1,302.94
1,600.01
11,682.74
20,950.00
3,128.00

1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00

3,813.94
1,776.86
1,421.58
2,384.08
3,376.58
3,972.93
409.82
5,340.88
5,076.72
11,675.00
5,119.51
4,286.33
1,302.94
1,600.01
11,682.74
20,950.00
3,128.00

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

87,317.92

3 x 150mm + 1 x 150 mm (N)

147.40

Id=In*1.25 If=In*1.5
Amp
Amp
184.25

221.10

IT
Amp
250.00

ID
250 A sensibilidad 30 mA
Caja Moldeada

Subtablero ST-1 Sala de Exposiciones


TABLERO

DESCRIPCION

ST-1
Sala de exposiciones
SALA DE EXPOSICIONES Sala de preparacin
Hall - Sala de espera
Oficio
Ludoteca
Secamanos
Emergencia
Iluminacin en la entrada
SS.HH

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
1.00
1.00
1.00
1.00
2.00
8.00
2.00
1.00

104.34
17.90
90.29
2.40
57.20

32.15

carga basica
carga basica
carga basica
carga basica
carga basica
Maxima demanda
Maxima demanda
Maxima demanda
carga basica

8.89
4.09
8.05
9.01
3.78
2,750.00
30.00
150.00
9.01

w/m
w/m
w/m
w/m
w/m
w
w
w
w/m

927.58
73.21
726.83
21.62
216.22
5,500.00
240.00
300.00
289.67

0.75
0.75
0.75
0.75
0.75
0.35
0.50
0.50
0.50

695.69
54.91
545.13
16.22
162.16
1,925.00
120.00
150.00
144.84

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

3,813.94

3 x25mm + 1 x 25mm(N) + 1 x 10mm(LT)

6.44

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

1,776.86

3 x 6mm + 1 x 6mm(N) + 1 x 6mm(LT)

3.00

Id=In*1.25 If=In*1.5
Amp
Amp
8.05

9.66

IT
Amp

ID

16.00

16 A sensibilidad 30 mA

IT
Amp

ID

16.00

16 A sensibilidad 30 mA

Subtablero ST-2 Boleteria

TABLERO
ST-2
BOLETERIA

DESCRIPCION
Sala de boletera
Computadoras
Impresoras
Secamanos
Iluminacin en la entrada
SS.HH

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
5.00
1.00
1.00
2.00
1.00

12.45

2.10

carga basica
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
carga basica

8.05
200.00
150.00
2,750.00
150.00
9.01

w/m
w
w
w
w
w/m

100.22
1,000.00
150.00
2,750.00
300.00
18.92

0.75
0.50
0.50
0.35
0.50
0.75

75.17
500.00
75.00
962.50
150.00
14.19

Id=In*1.25 If=In*1.5
Amp
Amp
3.75

4.50

Subtablero ST-3 Bao A


TABLERO
ST-3
BAO A

DESCRIPCION
Baos
Secamanos
Iluminacin en la entrada
Emergencia

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
1.00
2.00
2.00

41.30

carga basica
Maxima demanda
Maxima demanda
Maxima demanda

9.01
2,750.00
150.00
30.00

w/m
w
w
w

372.11
2,750.00
300.00
60.00

0.75
0.35
0.50
0.50

279.08
962.50
150.00
30.00

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

1,421.58

3 x 10mm + 1 x 10mm(N) + 1 x 10mm(LT)

2.40

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

2,384.08

3 x 25mm + 1 x 25mm(N) + 1 x 10mm(LT)

4.02

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

3,376.58

3 x 16mm + 1 x 16mm(N) + 1 x 10mm(LT)

5.70

Id=In*1.25 If=In*1.5
Amp
Amp
3.00

3.60

IT
Amp

ID

16.00

16 A sensibilidad 30 mA

IT
Amp

ID

16.00

16 A sensibilidad 30 mA

IT
Amp

ID

16.00

16 A sensibilidad 30 mA

Subtablero ST-4 Bao A1

TABLERO
ST-4
BAO A 1

DESCRIPCION
Baos
Secamanos
Iluminacin en la entrada
Emergencia

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
2.00
2.00
2.00

41.30

carga basica
Maxima demanda
Maxima demanda
Maxima demanda

9.01
2,750.00
150.00
30.00

w/m
w
w
w

372.11
5,500.00
300.00
60.00

0.75
0.35
0.50
0.50

279.08
1,925.00
150.00
30.00

Id=In*1.25 If=In*1.5
Amp
Amp
5.03

6.04

Subtablero ST-5 Bao B

TABLERO
ST-5
BAO B

DESCRIPCION
Baos
Secamanos
Iluminacin en la entrada
Emergencia

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
3.00
2.00
4.00

41.30

carga basica
Maxima demanda
Maxima demanda
Maxima demanda

9.01
2,750.00
150.00
30.00

w/m
w
w
w

372.11
8,250.00
300.00
120.00

0.75
0.35
0.50
0.50

279.08
2,887.50
150.00
60.00

Id=In*1.25 If=In*1.5
Amp
Amp
7.13

8.55

Subtablero ST-6 Bao C


TABLERO
ST-6
BAO C

DESCRIPCION
Baos
Secamanos
Iluminacin en la entrada
Emergencia

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
3.00
2.00
4.00

129.55

carga basica
Maxima demanda
Maxima demanda
Maxima demanda

9.01
2,750.00
150.00
30.00

w/m
w
w
w

1,167.25
8,250.00
300.00
120.00

0.75
0.35
0.50
0.50

875.43
2,887.50
150.00
60.00

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

3,972.93

3 x 16mm + 1 x 16mm(N) + 1 x 10mm(LT)

6.71

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

409.82

3 x 6mm + 1 x 6mm(N) + 1 x 6mm(LT)

0.69

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

5,340.88

3 x 25mm + 1 x 25mm(N) + 1 x 10mm(LT)

9.02

Id=In*1.25 If=In*1.5
Amp
Amp
8.38

10.06

IT
Amp

ID

16.00

16 A sensibilidad 30 mA

Subtablero ST-7 Bao D

TABLERO
ST-7
BAOD

DESCRIPCION
Baos
Emergencia
Iluminacin en la entrada

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
5.00
2.00

27.35

carga basica
Maxima demanda
Maxima demanda

9.01
30.00
150.00

w/m
w
w

246.42
150.00
300.00

0.75
0.50
0.50

184.82
75.00
150.00

Id=In*1.25 If=In*1.5
Amp
Amp
0.86

1.04

IT
Amp

ID

16.00

16 A sensibilidad 30 mA

Subtablero ST-8 Vestuarios

TABLERO
ST-8
VESTUARIOS

DESCRIPCION
Vestuarios
Secamanos
Iluminacin en la entrada
Emergencia

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
2.00
2.00
15.00

450.00

carga basica
Maxima demanda
Maxima demanda
Maxima demanda

9.01
2,750.00
150.00
30.00

w/m
w
w
w

4,054.50
5,500.00
300.00
450.00

0.75
0.35
0.50
0.50

3,040.88
1,925.00
150.00
225.00

Id=In*1.25 If=In*1.5
Amp
Amp
11.27

13.52

IT
Amp

ID

20.00

20 A sensibilidad 30 mA

Subtablero ST-9 Cuadro de Maquinas

TABLERO

DESCRIPCION

ST-9
Cuarto de maquinas
CUARTO DE MAQUINAS Bomba 1HP para Bombeo
Bomba 1HP
Bomba 2 HP
Bomba 2.5 HP
Iluminacin en la entrada
Emergencia
Hipoclorito

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
1.00
1.00
1.00
4.00
1.00
5.00
3.00

163.00

carga basica
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda

8.68
736.00
736.00
1,472.00
1,840.00
150.00
30.00
500.00

w/m
w
w
w
w
w
w
w

1,414.84
736.00
736.00
1,472.00
7,360.00
150.00
150.00
1,500.00

0.50
0.50
0.35
0.35
0.35
0.35
0.50
0.35

707.42
368.00
257.60
515.20
2,576.00
52.50
75.00
525.00

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

5,076.72

3 x 16mm + 1 x 16mm(N) + 1 x 10mm(LT)

8.57

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

11,675.00

3 x 70mm + 1 x 70mm(N) + 1 x 25mm(LT)

19.71

Id=In*1.25 If=In*1.5
Amp
Amp
10.71

12.86

IT
Amp

ID

20.00

20 A sensibilidad 30 mA

Subtablero ST-10 Restaurante

TABLERO
ST-10
RESTAURANTE

DESCRIPCION
Cocina
Comedor
Lava vajillas industriales
Lavadora
Refrigeradora
Nevera
Secamanos
Emergencia
Bomba 1 HP para Pileta
Iluminacin en la entrada
Baos

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
1.00
1.00
1.00
5.00
1.00
2.00
12.00
1.00
2.00
1.00

51.65
66.70

46.65

carga basica
carga basica
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
carga basica

14.28
2.62
3,500.00
2,000.00
1,390.00
5,000.00
2,750.00
30.00
736.00
150.00
9.01

w/m
w/m
w
w
w
w
w
w
w
w
w/m

737.56
174.75
3,500.00
2,000.00
6,950.00
5,000.00
5,500.00
360.00
736.00
300.00
420.32

0.75
0.75
0.35
0.35
0.50
0.50
0.35
0.50
0.85
0.50
0.50

553.17
131.07
1,225.00
700.00
3,475.00
2,500.00
1,925.00
180.00
625.60
150.00
210.16

Id=In*1.25 If=In*1.5
Amp
Amp
24.64

29.56

IT
Amp

ID

40.00

40 A sensibilidad 30 mA

10

Subtablero ST-11 Bar Terraza


TABLERO
ST-11
BAR TERRAZA

DESCRIPCION
Cocina
Refrigeradora
Nevera
Emergencia
Comedor

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
1.00
1.00
1.00
1.00

23.50

30.70

carga basica
Maxima demanda
Maxima demanda
Maxima demanda
carga basica

14.28
1,390.00
5,000.00
30.00
2.62

w/m
w
w
w
w/m

335.58
1,390.00
5,000.00
30.00
80.43

0.75
0.75
0.75
0.50
0.75

251.69
1,042.50
3,750.00
15.00
60.33

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

5,119.51

3 x 25mm + 1 x 25mm(N) + 1 x 10mm(LT)

8.64

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

4,331.12

3 x 25mm + 1 x 25mm(N) + 1 x 10mm(LT)

7.31

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

1,302.94

3 x 4mm + 1 x 4mm(N) + 1 x 2.5mm(LT)

2.20

Id=In*1.25 If=In*1.5
Amp
Amp
10.80

12.96

IT
Amp

ID

20.00

20 A sensibilidad 30 mA

IT
Amp

ID

20.00

20 A sensibilidad 30 mA

Subtablero ST-12 Bao Anfiteatro

TABLERO
ST-12
BAO AMFITEATRO

DESCRIPCION
Vestuarios
Secamanos
Emergencia
Iluminacin en la entrada
Baos

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
4.00
2.00
2.00
1.00

21.50

13.45

carga basica
Maxima demanda
Maxima demanda
Maxima demanda
carga basica

10.26
2,750.00
30.00
150.00
13.45

w/m
w
w
w
w/m

220.59
11,000.00
60.00
300.00
180.90

0.75
0.35
0.50
0.50
0.75

165.44
3,850.00
30.00
150.00
135.68

Id=In*1.25 If=In*1.5
Amp
Amp
9.14

10.97

Subtablero ST-13 Tpico

TABLERO
ST-13
TOPICO

DESCRIPCION
Sala
Secamanos
Emergencia
Iluminacin en la entrada
Bao

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
1.00
1.00
2.00
1.00

27.50

2.40

carga basica
Maxima demanda
Maxima demanda
Maxima demanda
carga basica

7.72
2,750.00
30.00
150.00
9.01

w/m
w
w
w
w/m

212.30
2,750.00
30.00
300.00
21.62

0.75
0.35
0.50
0.50
0.75

159.23
962.50
15.00
150.00
16.22

Id=In*1.25 If=In*1.5
Amp
Amp
2.75

3.30

IT
Amp

ID

16.00

16 A sensibilidad 30 mA

11

Subtablero ST-14 Administracin

TABLERO
ST-14
ADMINISTRACION

DESCRIPCION
Sala
Computadoras
Impresoras
Secamanos
Emergencia
Iluminacin en la entrada
Bao

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
2.00
1.00
1.00
1.00
2.00
1.00

26.50

2.40

carga basica
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
carga basica

4.09
200.00
150.00
2,750.00
30.00
150.00
9.01

w/m
w
w
w
w
w
w/m

108.39
400.00
150.00
2,750.00
30.00
300.00
21.62

0.75
0.75
0.50
0.35
0.50
0.50
0.75

81.29
300.00
75.00
962.50
15.00
150.00
16.22

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

1,600.01

3 x 6mm + 1 x 6mm(N) + 1 x 6mm(LT)

2.70

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

11,682.74

3 x 50mm + 1 x 50mm(N) + 1 x 16mm(LT)

19.72

Id=In*1.25 If=In*1.5
Amp
Amp
3.38

4.05

IT
Amp

ID

16.00

16 A sensibilidad 30 mA

Subtablero ST-15 Gimnasio

TABLERO
ST-15
GIMNASIO

DESCRIPCION
Sala de deporte
Baos
Cinta de correr 5 Cv
Maquina expendedora
Secamanos
Emergencia
Iluminacin en la entrada
Recepcin

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
1.00
5.00
3.00
2.00
18.00
2.00
1.00

465.10
79.70

149.30

carga basica
carga basica
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
Maxima demanda
carga basica

8.64
9.01
3,680.00
200.00
2,750.00
30.00
150.00
4.09

w/m
w/m
w
w
w
w
w
w/m

4,018.46
718.10
18,400.00
600.00
5,500.00
540.00
300.00
610.64

0.75
0.75
0.30
0.85
0.25
0.50
0.50
0.50

3,013.85
538.57
5,520.00
510.00
1,375.00
270.00
150.00
305.32

Id=In*1.25 If=In*1.5
Amp
Amp
24.65

29.58

IT
Amp

ID

40.00

40 A sensibilidad 30 mA

12

Subtablero ST-16 Alumbrado Pblico

TABLERO
ST-16

DESCRIPCION
Linea 1
Faroles - luminarias
Linea 2
Faroles - luminarias
Linea 3
Faroles - luminarias

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00

Maxima demanda

3,150.00

3,150.00

1.00

3,150.00

1.00

Maxima demanda

5,700.00

5,700.00

1.00

5,700.00

1.00

Maxima demanda

12,100.00

12,100.00

1.00

12,100.00

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

20,950.00

3 x 6mm + 1 x 6mm(N) + 1 x 6mm(LT)

35.37

MAX.
DEM.

CABLE ALIMENTADOR
POR TABLERO

In
Amp

3,128.00

3 x 6mm + 1 x 6mm(N) + 1 x 6mm(LT)

5.28

Id=In*1.25 If=In*1.5
Amp
Amp
44.21

53.05

IT
Amp

ID

60.00

60 A sensibilidad 30 mA

IT
Amp

ID

16.00

16 A sensibilidad 30 mA

Subtablero ST-17 Bombas

TABLERO
ST-17
BOMBAS

DESCRIPCION
Bomba 1HP - Limpieza
Bomba 4HP - Abastecimiento

POTENCIA FACTOR MAX. DEM.


INSTALAD DEM. SUB TOTAL

CANT. AREA(m)
1.00
1.00

Maxima demanda
Maxima demanda

736.00
2,944.00

w
w

736.00
2,944.00

0.85
0.85

625.60
2,502.40

Id=In*1.25 If=In*1.5
Amp
Amp
6.60

7.92

13

8. TOMA DE TIERRA
Se ha previsto instalar varios pozos de puesta a tierra, obteniendo una mejor proteccin
zonificada. Se han instalado pozos de tierra en todos y cada uno de los subtableros adems
del Tablero General, esta lnea de proteccin a tierra proteger a los circuitos derivados de
iluminacin, tomacorriente y maquinaria. La resistencia de puesta a tierra de la instalacin
deber ser 25 ohmios como mximo.

9. CDIGO Y REGLAMENTOS
Todos los trabajos se efectuarn de acuerdo con los requisitos de las secciones aplicables a
los siguientes Cdigos o Reglamentos:

Cdigo Nacional de Electricidad Utilizacin 2006.

Reglamento Nacional de Edificaciones.

Normas de DGE-MEM

Normas IEC y otras aplicables al proyecto

Normas Tcnicas Peruanas: NTP 111.011, NTP 111.022, NTP 111.023

10. PRUEBAS
En la parte elctrica deber realizarse pruebas

de continuidad, tensin, aislamiento,

balanceo de carga, funcionamiento de equipos de iluminacin, funcionamiento de todas las


instalaciones a plena carga, mediciones de la resistencia del pozo de tierra, etc. Todas
estas pruebas y mediciones debern ser certificadas mediante un protocolo de pruebas
con la participacin de profesionales especialistas del caso. Los resultados de las
mediciones debern cumplir con las exigencias mnimas indicados en el Cdigo Nacional de
Electricidad.

14