Theory
Definitions
The Higher Heating Value (HHV) or heat of combustion is the amount of energy which is released in
the process of complete combustion of a weight/volume unit of certain fuel and cooling down all the
combustion products to the ambient temperature.
The Lower heating Value (LHV) is the HHV lowered by the heat of evaporation of all the water
contained in the flue gas.
Thus the LHV is roughly (although not exactly) equal to the amount of energy released in the process
of complete combustion of a weight/volume unit of certain fuel and cooling down the combustion
products to the flue gas dew point. It is utilised to determine energy potential of combusting fossil
fuels, as in industrial practice it is usually impossible or impracticable to cool down flue gas below the
dew point (due to corrosion risk). LHV is also popularly used to determine efficiency of combustion
systems. It should be noted however, that if LHV is used to determine energy input into a system,
which does cool down the exhaust gas below the dew point (like in case of heating boilers fired with
de-sulphurised natural gas), the efficiency calculated as the energy output (water enthalpy increase
divided by fuel energy input) may go beyond 100%. Such a value, while technically correct, has no
physical meaning, yet it may be utilised to compare efficiencies of several different pieces of
equipment.
Units
Typically fuel heating values are denominated in units of energy in reference to units of weight or
normalised volume. Thus most popular heating value units (in Europe) are:
Please remember, that Nm normal cubic metre is a unit defining amount of gas, not its actual
volume. A normal cubic metre is directly linked to certain mass of a gas or to certain amount of its
molecules. Normal cubic metre of a gas is the amount of gas which will have a volume of exactly one
cubic metre in normal conditions. Please note that reference conditions (pressure and temperature)
used to define it may vary according to standards used in different countries. In Poland the reference
conditions (called normal conditions) are: p = 101,325 Pa, T = 273.15 K.
Fuel burner
Cylindrical combustion chamber, located directly above the burner
Water jacket surrounding the combustion chamber
Cooling water inlet with a flow-control valve
Cooling water outlet with a three way valve allowing the discharged water to be directed to
sewerage or to a measurement tank
Exhaust gas outlet
Flue gas condensate outlet.
Exhaust gas
Cooling water at inlet
Cooling water at outlet.
During a measurement the burner is tuned to ensure complete combustion process and then fixed in
the bottom part of the combustion chamber. Water delivered to the calorimeter is flowing through
the external jacket and is subsequently discharged either to sewerage or to a measurement
container. Exhaust gas, cooled down to the ambient temperature by the water flow, is exhausted to
the environment. Water vapour contained in the flue gas is condensing in the process of cooling
down flue gas and is discharged through a special pipe stub installed in the bottom part of the
calorimeter.
The energy released during the combustion process is therefore at first utilised to heat up the gases
inside the combustion chamber (i.e. air and fuel). Then the gases are cooled by water and the energy
is transferred to the cooling water, increasing its temperature. If the flue gas is cooled down to
ambient temperature, then it may be assumed that 100% of released energy is transferred to the
cooling water.
The calorimeter seen as a separate thermodynamic system is an open flow-type system with
following mass inlets and outlets:
Additionally heat may be exchanged between the calorimeters interior and ambient air through the
calorimeter walls.
Therefore we may present the energy balance of the calorimeter as:
m mass flow
h specific enthalpy
H enthalpy
HHV higher heating value of the fuel gas
Q 0 heat flux going OUT of calorimeter (heat exchange with environment)
f fuel
a air
iw inlet cooling water
ow outlet cooling water
c condensate.
As there the water flow through the
calorimeter is continuous and
steady, miw mow mw
HHV
where:
mw mass of cooling water which has passed through the cooling jacket during the
measurement period
C specific heat capacity of water
As in practice water temperatures vary slightly, average values from the whole measurement period
are used.
The fuel LHV is determined according to the definition. This means that it is necessary to collect the
condensate from the flue gas during the measurement period. Then the lower heating value may be
calculated as:
LHV HHV mc r
where:
Mass of the combusted fuel is determined according to indications of the gas flow meter, which
indicates:
Please note that the volume of consumed gas is valid for measured parameters only! It may be
converted to normalised volume (expressed in normal cubic metres) using Clapeyrons equation.
Then a mass of consumed fuel gas may be calculated using its density.
Exercise instruction
During the exercise you will measure LHV and HHV of a 50/50 mixture of propane and butane.
Preparation
Record the ambient temperature
Open the main cooling water valve (red handle)
Check the water inlet temperature
Calculate the desirable outlet water temperature
Open the gas supply valve and ignite the burner
WARNING! DO NOT OPEN THE GAS VALVE AND DO NOT IGNITE THE BURNER UNLESS
SPECIFICALLY ORDERED TO DO SO BY YOUR INSTRUCTOR! FAILURE TO COMPLY WITH THIS
REQUIREMENT IS CONSIDERED A SERIOUS VIOLATION OF HEALTH-AND-SAFETY RULES AND
MAY RESULT WITH A FAILURE TO GET A POSITIVE FINAL GRAD FROM THE COURSE!
Adjust the burner to obtain a smooth blue flame, proving that combustion is complete
Put the burner under the calorimeter. Do not attach it yet
Adjust the fine-control valve installed on the calorimeter to achieve desirable outlet water
temperature
CAUTION. The valve controls the water flow into the calorimeter. The thermometer shows
the temperature of outgoing water flow. This means that the temperature response will be
delayed. Take your time and allow the system to respond to even fine valve movements.
CAUTION. If you set insufficient water flow, then the outgoing water temperature will
rapidly increase. This might lead to destroying the thermometer. If you are unable to
contain temperature increase (i.e. if the temperature exceeds approximately 35C and
keeps growing) immediately remove the burner from the calorimeter and wait for the
temperature to drop. Only afterwards you may try again.
When the desired outgoing water temperature is achieved and stabilised, verify that the
exhaust gas temperature is equal to the ambient temperature. If it is the case, you may start
the main measurement.
Main measurement
During the main measurement you need to record the following parameters at regular intervals (e.g.
30 seconds):
At the time zero, except for recording those parameters, you need to perform two more actions:
Switch a three-way valve on the outgoing water line, so the water is discharged by the stub
pipe into your measurement container
Put a wash-bottle under the drain of the exhaust gas condensate.
The measurement continues until the amount of collected condensate is sufficient to measure it with
reasonable accuracy. Please note that it may be necessary to switch cooling water containers. You
may measure amount of collected water using a scale available at the laboratory.
Upon completion of the measurement: