what will be cause of busting of CT? We have almost 3-4 incident .Please Tell me .
Like (1)
Comment (9)
Follow
Reply Privately
3 days ago
Comments
kenneth sylvester likes this
9 comments Jump to most recent comment

Ing. Ole
Ing. Ole Knudsen
Experienced Electrical Engineer, looking for new challenges.
Top Contributor
o
o
o
o

Most common cause is if the secondary is not loaded or shorted.


Like
Reply privately
Flag as inappropriate
3 days ago

Ramiah Mudaliar
Ramiah Mudaliar Nambithurai
Chef de service at industries chimigues du senegal
Top Contributor

o
o
o
o

There are two reasons that may cause CT failures in High voltage system.
1. Aging and eventual failure of high voltage insulation
2. Open circuiting of CT secondary during operation
That is why periodic condition monitoring of Switch gears to be done atleast once in two years. Various diagnostic
methods are available which will detect the healthiness of the equipments like CT, PT,Transformers etc
Like
Reply privately
Flag as inappropriate
3 days ago

Mark
Mark Falesch
Owner/GM, Powerserve Inc
o
o
o
o

What type of CTs are you asking about? Bus bar mounted LV/MV CTs or large HV oil-filled CTs?
Like
Reply privately
Flag as inappropriate
2 days ago


Neil
Neil Crandell
Power Systems Team Leader at Oxy

o
o
o
o

Open CT secondary while energized will do it. Have you had maintenance personnel inside the panel lifting wires?
Also, if this is not related to open CT secondary and is happening frequently, maybe there is some other root cause like
ferro-resonance during switching, depending on what your system configuration is.
One needs to look at all the data.
Like
Reply privately
Flag as inappropriate
2 days ago

jayadeep
jayadeep kulkarni
Engineering at NIPRO INDIA CORPORATION PVT LTD
Top Contributor

o
o
o
o

CTs are bus bar type,But CTs are not open in secondary side, and it connected from at least 1.5 year .Is it may be mfg
defect?
Like
Reply privately
Flag as inappropriate
2 days ago

kenneth
kenneth sylvester
ARC FURNACE CONSULTANT at regan inc
o
o
o
o

In my limited experience ,the problem has always been either age,degredation of insular value and lightning strikes.
Like
Reply privately
Flag as inappropriate
2 days ago

Eugene
Eugene Stevens
Electrical Mechanic Supervisor at Los Angeles Department of Water and Power

o
o
o
o

An open secondary is probably your issue. However, it could be an open in the CT itself, before the secondary output
terminals.
Like (1)
Reply privately
Flag as inappropriate
2 days ago
kenneth S. likes this


Mark
Mark Falesch
Owner/GM, Powerserve Inc

o
o
o
o

Following-on to Neil Crandell's very valid points: is it possible that someone has removed or withdrawn a
instrumentation or protective relaying device without properly operating the CT secondary shorting switches or
inserting CT secondary circuit shorting screws in the terminal block?
Like (1)
Reply privately
Flag as inappropriate
2 days ago
kenneth S. likes this

Manoj
Manoj Badave
Manager Plant Engineering at Tata Motors Ltd

o
o
o
o

Dear Jaydeep,
you need to be more specific while posting the queries! Can you pl share more details of the CTs? e.g. Voltage rating,
CT Ratio, metering or protection CT, VA Burden, indoor or outdoor type, mounting etc. All these factors will help to
predict the probable causes of failure. Also the failure details. if it is due to insulation failure or Ferro resonance, it
busts.
pl share more data.
Like
Reply privately
Flag as inappropriate
15 hours ago

PRADIPSINH
PRADIPSINH PARMAR
Deputy Engineer GETCO
There are numerous reason for CT Bursting but most common low IR and high tan delta value of CT....
o
o
o
o

Like
Reply privately
Flag as inappropriate
1 day ago

Raja

Raja Mukherjee
Senior Enginner at M. N. Dastur & Co. (P) Ltd.
When Primary bus is charged, then with CT in secondary circuit with terminals open will cause current i.e. electrons
charged particles will get buildup around the cross section of CT terminals will eventually have no space to stand and
will be converted into heat energy and will explode.
o
o
o
o

Like
Reply privately
Flag as inappropriate
23 hours ago

venugopal
venugopal karanam
Electrical engineer at Karnataka power transmission corporation ltd
withstanding capacity of fault current, i.e. in NP ; STC rating of CT
o
o
o
o

Like
Reply privately
Flag as inappropriate
10 hours ago