Você está na página 1de 39

CONTENTS

I. SETTING UP THE SYSTEM ........................................................................................... 1


I.1.THE WALL TYPE DS200 SYSTEM INSTALLATION .............................................................. 1

I.1.A. PREPARATION ...............................................................................................................................1


I.1.B. APPLICATION ................................................................................................................................1
I.1.C. GROUNDING ..................................................................................................................................4
I.1.D. BATTERY CONNECTION................................................................................................................5

I.2.THE CABINET-TYPE DS200 SYSTEM INSTALLATION ........................................................ 5

I.2.A. PREPARATION ...............................................................................................................................5


I.2.B. APPLICATION ................................................................................................................................6
I.2.C. INSTALLATION OF SYSTEMS WITH FOUR OR MORE RACKS .....................................................8
I.2.C.1. CONNECTIONS IN THE MAIN RACK, TO WHICH THE CPU200 CARD HAS BEEN ATTACHED:........... 9
I.2.C.1.1. ATTACHING THE CC EXTRA CARD ONTO THE CPU200 CARD: ..........................................................................9
I.2.C.1.2. INTEGRATION OF THE C MASTER CARD TO THE MAIN RACK:........................................................................10
I.2.C.1.3. CONNECTING THE BPLSPS-FCX CABLE:.........................................................................................................11

I.2.C.2. CONNECTIONS ON THE FOURTH RACK: .............................................................................................12


I.2.C.2.1. INTEGRATION OF THE C SLAVE CARD TO THE MAIN RACK ............................................................................12
I.2.C.2.2. ATTACHING THE CC ENABLE CARD TO THE MAIN RACK: ..............................................................................12
I.2.C.2.3. CONNECTING THE BPLSPS-FCX CABLE:.........................................................................................................12

I.2.D. GROUNDING ................................................................................................................................12


I.2.E. BATTERY CONNECTION ..............................................................................................................14

I.3.INSTALLING POWER SUPPLIES IN THE SYSTEM............................................................ 16

I.3.A. SPS200 AC/DC POWER SUPPLY .................................................................................................16


I.3.B. SPS248 DC/DC POWER SUPPLY ................................................................................................16

I.4.INTEGRATING MODULES TO THE SYSTEM...................................................................... 16

I.4.A.CPU200, REDUNDANT CPU200 & DS200 CPUKON CARDS.......................................................16


I.4.A.1. THE LAN ADAPTOR CARD:....................................................................................................................17

I.4.B. THE UTIL200 UTILITY MODULE ..................................................................................................18


I.4.B.1. nstallng the conference chp on UTIL200...........................................................................................18

I.4.C. CON2/CON3 LINE CONNECTION CARDS...................................................................................19


I.4.D. INSTALLING EXPANSION MODULES .........................................................................................21
I.4.D.1. ATTACHING EX200 MODULES: .............................................................................................................21
I.4.D.2. CABLING OF EX200 MODULES: ............................................................................................................22
I.4.D.2.1. EX200 (0/16) ANALOG EXTENSION MODULE:...................................................................................................22
I.4.D.2.2. EX200 (8/0) ANALOG LINE MODULE: ................................................................................................................23
I.4.D.2.3. EX200 (0/8S0) ISDN BRI EXTENSION MODULE: ...............................................................................................23
I.4.D.2.4. EX200 (1S2/0) ISDN PRI MODULE: ....................................................................................................................24
I.4.D.2.5. EX200 (1R2/0) R2 DIGITAL LINE MODULE: .......................................................................................................24
I.4.D.2.6. EX200 (0/8U) DIGITAL EXTENSION MODULE:...................................................................................................25
I.4.D.2.7. EX200 (0/16U) DIGITAL EXTENSION MODULE:.................................................................................................25
I.4.D.2.8. EX200 (8 T0/S0) ISDN BRI LINE/EXTENSION MODULE: ...................................................................................26
I.4.D.2.9. EX200 (0/8LB) LOCAL BATTERY EXTENSION MODULE:...................................................................................27
I.4.D.2.10. EX200 (4E&M/0) E&M LINE MODULE: ............................................................................................................27

I.4.E. JUMPER SETTINGS ON THE EX200 (8T0/S0)


MODULE........................................................28
I.4.F. JUMPER SETTINGS ON THE EX200 (4E&M/0)
MODULE ......................................................29
I.4.G. INSTALLATION OF THE EVM200L MODULE ..............................................................................31

I.5. THE FINAL PREPARATIONS............................................................................................ 31

II. PUTTING THE SYSTEM ON LINE............................................................................... 33


II.1. SINGLE-RACK, WALL-TYPE SYSTEM............................................................................. 33
II.2. TWO-RACK WALL-TYPE SYSTEM................................................................................... 33
II.3. CABINET-TYPE SYSTEM................................................................................................. 33
II.4. TWO-CABINET SYSTEM.................................................................................................. 34

III. TESTING THE SYSTEM AND TROUBLESHOOTING BASIC PROBLEMS .................. 36

DS200 Installation Guide

I. SETTING UP THE SYSTEM


The DS200 system can be set up in two different structures, namely as wall type and cabinet
type.

I.1.THE WALL TYPE DS200 SYSTEM INSTALLATION


If the DS200 system consists of one or two racks at most, then it can be mounted as wall
type. As for the systems with three or more racks, they definitely have to be mounted as
cabinet type.

I.1.A. PREPARATION
The following requirements should be fulfilled prior to the installation of the exchange:
1- The wall on which the DS200 exchange will be mounted should be firm enough to carry
the weight and it should have a smooth surface.
2- The exchange should be installed in places that are not exposed to direct sunlight, that
are not humid, but that are ventilated, well lit, with an environmental temperature of 045oC. It should not be exposed to effects of dust, vibration, oil and water.
3- Devices that generate high frequency waves (such as welding machines, office equipment
such as computers and telex machines, air conditioners, TV sets) should not be in the
same room if possible, and they should be at least 3 meters away from the exchange,
otherwise.
4- The mains supply should be reserved for the exchange only. The power supply of the
system should be uninterrupted and, if possible, the system should be powered from an
independent and well-grounded source from which no other device is powered.

POWER SUPPLY THAT IS INTERRUPTED FREQUENTLY MAY AFFECT


NORMAL OPERATION OF THE SYSTEM!

5- The spot where the exchange is to be mounted should be at a distance to the main
distribution frame (MDF), so that the MDF can be reached through three-meter line
connection cables. While the distance is being determined, the flexibility of the cables
and the way they will be fixed to the wall should also be considered.
6- A location that can be reached easily should be chosen, considering the installation work
and later maintenance work.
7- Place requirement for the batteries should be considered, as well.

THE AIR VENTS AT THE TOP AND BOTTOM OF THE EXCHANGE MUST
NOT BE BLOCKED BY ANY MEANS. PREVENTING VENTILATION MAY DAMAGE
THE EXCHANGE!

I.1.B. APPLICATION
1- Plot a location that complies with the requirements indicated in the Preparation step
above.
2- By making use of the installation template that comes with the racks, mark the locations
for the wall mount bars carefully that are to be used for hanging the racks on the wall.
V003. 25.06.2002

B-1

DS200 Installation Guide


The lower hole of the wall mount bars should be approximately 130 cm. above the floor. It
is essential to check whether the height of both holes are the same, in order to make
sure the exchange is parallel to the floor.
3- If there are two DS200 racks to be installed, then the lower hole of the wall mount bars,
for the first rack to be installed (That will be the lower rack.), should be 100 cm. above
the floor.
4- Drill the lower wall mount bar hole of the second rack 140 cm. above the floor, vertically
on the same line with the first one. When the installation is over, there will be a 10-cm
gap between the two racks.

Figure 1
5- Drive the anchor plugs into the holes, whose locations have already been checked, and
then screw the wall mount bars. Note that the right and the left side of the wall mount
bars differ. The screws must be fixed enough to burry their heads completely into the
wall.
6- After removing the front cover of the exchange by unscrewing the Allen screws, remove
the bottom cover by sliding it to the front.
7- While removing the bottom cover, watch out for the grounding cables that are between
the cover and the main frame, so that they will not break off. Remove the cables from the
covers together with their tags and keep them safe from any damage during the
installation.
8- Slide the SPS200 to the front and remove it, after loosening its screws. (This is just for
facilitating the installation and not obligatory.)

V003. 25.06.2002

B-2

DS200 Installation Guide


9- Hold the exchange so that the wall mount bar holes at the back of the exchange
correspond to the wall mount bar holders, then push the exchange towards the wall, so
that the holders would carry it. Make sure the holders of both wall mount bars have been
inserted into the holes, and then lower the exchange cautiously. The exchange is fixed 5
mm. below. If it is still not fixed, even though it has been lowered for about one
centimeter, that indicates the holders do not carry it. In that case, try to hang the
exchange once again. In order to make sure that the exchange has been fixed, gently
shake it to check whether the wall mount bars really carry it.
10- In case it is necessary to displace the exchange, just lift it upwards cautiously and pull it
out.

IT IS ESSENTIAL TO MOUNT AND DISMOUNT THE WALL MOUNT BARS


SIMULTANEOUSLY; OR THEY MAY GET DISTORTED.

11- If the second rack will be installed, then remove the top cover of the lower rack and the
bottom cover of the upper rack, in order to attach the cables that will connect the racks
to each other (Caution is needed for the grounding cables, as explained in the seventh
step.) The BPL200 main boards are connected to each other by the BPL200-FC and
BPLSPS-FC connection cables that come with the shipped hardware of the auxiliary rack.
There are three such cables. Two BPL200-FC's (34-pin flat cable) are used for connecting
the BPL200 backplanes and the single BPLSPS-FC (5-wire cable) is used for combining
BPL200-SPS backplanes.

1. BPL200-FC connections
V003. 25.06.2002

2. BPLSPS-FC connection
B-3

DS200 Installation Guide


a) BPL200-AUX

d) BPL200-SPS

b) BPL200-FC

e) BPLSPS-FC

c) BPL200-MAIN

f) BPL200-SPS

Figure 2
12- Replace the covers by coinciding the cables with the corresponding cable slots that are at
the back of the covers.
13- If SPS200 has been removed in order to facilitate the installation, then replace it as will
be explained in detail later.
14- Connect the 230 VAC cable to the corresponding input on SPS200. Before plugging the
other end of the cable in, check the position of the on/off switches and whether the fuses
are defective. The mains on/off switch must be off. Keep in mind that the battery on/off
switch must be set to on after the mains supply is on and it must be set to off before
the power is shut off. (Putting the System on Line is described in Section II.)
Two 2A T-type fuses that are necessary for 230 VAC are in the drawer-type compartment
next to the 230 VAC input.

I.1.C. GROUNDING
Grounding is required for protecting the DS200 exchange from lightning and other sources of
high voltage that may affect through lines or peripheral devices. The 230 VAC power cable of
the exchange has grounding feature, so there is no need for an extra grounding if the
electrical installation of the building has sound grounding.
Although special tools are required for measuring the sufficiency of grounding of the electric
installation of the building precisely, voltages between Neuter-Phase and Neuter-Ground
can be measured for getting a rough idea. The Neuter-Phase voltage should be 180-260 VAC
and the Neuter-Ground voltage should be 1-2 VAC. Those values must be consistent.
Possible voltage leakage in grounding installation may damage your exchange, just like all
other devices that require grounding.

ADDITIONAL GROUNDING MUST BE PROVIDED, IF SOUNDNESS OF


THE GROUNDING OF THE ELECTRIC SYSTEM CANNOT BE GUARANTEED.

Water installation of the building can be used for grounding, provided that the pipes are of
metal and no insulation material has been used at junctions.
Indeed, the most secure grounding method is inserting a copper rod that is 1.5 cm in
diameter with 1.5 m of length, or inserting a copper plate with 1 m2 of area to the ground and
connecting it to the exchange through a copper grounding cable. The cable should be
fastened tightly to the rod or to the plate and precautions should be taken against corrosion.
The cable coming from the grounding plate or grounding installation must be connected to
the ground connection point of the exchange.
If the second rack is to be installed as well, then the ground connection points of the two
racks must be connected to each other tightly with the ground connection cable that comes
with the auxiliary rack.

THE GROUND CONNECTIONS OF THE LOWER AND UPPER COVERS OF


THE EXCHANGE MUST DEFINITELY BE DONE AGAIN WHEN THE COVERS ARE
REMOVED AND THEN REPLACED.

V003. 25.06.2002

B-4

DS200 Installation Guide

A- DS200 Main Rack

B- DS200 Auxiliary Rack

C- The grounding cable

D- The copper grounding plate or rod


Figure 3

I.1.D. BATTERY CONNECTION


Since power failure will impede your exchange to fulfill its normal functions, a battery must
be connected to it, if there is such a possibility. Battery connection is made after SPS200 has
been fixed. The battery switch must be 0 during the connection. There are two clips on
SPS200 for the battery connection. (See The Technical Reference GuideFigure 13). It is
strictly recommended that a 48V 24Ah dry battery group (12V, 24Ah X 4) should be connected
to those clips. The red end must be connected to the + pole of the battery group, and the
black end to the - pole. In order to make the connection, press the springed latch of the
clips, insert the corresponding end of the battery cable into the hole in front, deep enough so
that no naked portion of the cable is left outside, and then release the latch.
Battery connection is provided only for the SPS200 of the main rack, in two-rack systems.
There is no battery connection for the second SPS200.

REVERSE BATTERY CONNECTION MAY DAMAGE YOUR EXCHANGE!

I.2.THE CABINET-TYPE DS200 SYSTEM


INSTALLATION
I.2.A. PREPARATION
The following requirements should be fulfilled prior to the installation of the exchange:
1- The DS200 exchange cabinet should be installed in places that are not exposed to direct
sunlight, that are not humid, but that are ventilated, well lit, with an environmental
temperature of 0-45oC.
2- It should not be exposed to the effects of dust, vibration, oil and water.

V003. 25.06.2002

B-5

DS200 Installation Guide


3- Devices that generate high frequency waves (such as welding machines, office equipment
such as computers and telex machines, air conditioners, TV sets) should not be in the
same room if possible, and they should be at least 3 meters away from the exchange,
otherwise.
4- The mains supply should be reserved for the exchange only. The power supply of the
system should be uninterrupted and, if possible, the system should be powered from a
well-grounded source from which no other device is powered.

FREQUENT POWER FAILURES MAY AFFECT NORMAL OPERATION OF


THE SYSTEM!

5- The spot where the exchange is to be mounted should be chosen considering its position
relative to the main distribution frame (MDF) and length of the cables. The installation
work and later maintenance work should also be considered, so that the covers can be
removed and replaced easily.
6- Since the installation connections will be made at the back of the cabinet, the position of
the cabinet should be arranged accordingly. The lighting at the back has been placed for
facilitating the work.

I.2.B. APPLICATION
1- Take the cabinet to a location as defined in the preparation step.
2- Lock the wheels by pressing the latches so that the exchange will not move.
3- Remove the front cover and the rack stopper screws that prevent the racks to slide.

Figure 4
4- Remove the back and side covers, after unlocking them, by lifting them for approximately
10 cm in a manner so that their paint is not scratched.
5- While removing the covers, watch out for the grounding cables that are between the main
frame and the covers so that they do not break off. Detach the cables, together with their
tags, from the covers and keep them so as to make sure they would not get damaged
during the placement of the exchange into the cabinet.
6- Push the main rack and auxiliary racks one by one until the holes of the removed
stopping screws appear. Then replace the stopping screws so that the racks would not
slide along the slots.

V003. 25.06.2002

B-6

DS200 Installation Guide

Figure 5
7- Open the cable panels from rear in order to facilitate the access.
8- In order to connect the main rack and the auxiliary racks, as well as to make inter-rack
ground connection: First, use the BPL200-FC and BPLSPS-FC connection cables that
come with the auxiliary rack. There are three such cables. Two BPL200-FC's (34-pin flat
cable) are used for connecting the BPL200 backplanes and BPLSPS-FC (5-wire cable) is
used for connecting BPL200-SPS backplanes. In order to connect the backplanes:
a) Primarily, attach one end of each BPL200-FC to the BPL200-MAIN backplane of the
main rack that has been placed to the bottom.
b) Extend the free ends of the BPL200-FC cables to the second rack through the cable
holes corresponding to the upper panel at the back of the first rack and the lower
panel at the back of the second rack. Attach the ends of those two cables to the
BPL200-AUX backplane connector. The cables should be parallel to each other.
Repeat the same procedure to connect the second rack to the third, later. See Figure
2.
V003. 25.06.2002

B-7

DS200 Installation Guide


9) Each rack comes as the power card-backplane connection has been made as factory
default. There are special cables that are used for this purpose. In case it is necessary,
those cables can be detached and the two cards can be separated or they can be
combined again, with those cables.
10) Then, you are supposed to make the power connection among the racks. In order to
connect the BPL200-SPS backplanes:
a) For the connection of the BPL200-SPS backplanes of the first and second racks, first
attach the BPLSPS-FC (5-wire cable) to the inter-rack SPS connector that is on the
BPL200-SPS backplane of the first rack.
b) Then, extend the free end of the cable through the holes of the metal plates that are
at the back of the first and the second racks and then attach it to the inter-rack SPS
connector that is on the BPL200-SPS backplane of the second rack. Repeat the same
procedure for the connection between the second and the third racks. See Figure 2.
11) Attach the 230 VAC cable to the connector on the SPS200. First, make sure that the on/off
switches are off and the fuses are free from any defect. Then, attach the other end of the
cable to one of the plugs next to the mains switch that is at the lower front section of the
cabinet, by extending it through the back of the cabinet.
Two 2A T-type fuses that are necessary for 230 VAC are in the drawer-type compartment
next to the 230 VAC input.

VENTS OVER THE CABINET FANS MUST NOT BE COVERED BY ANY


MEANS DURING OPERATION OF THE SYSTEM. CERTAINLY CHECK
WHETHER THE FANS WORK PROPERLY, AT THE TEMPERATURES OVER
20C.

CAUTION!
The rules that must be obeyed strictly while powering the system on and off are stated as a
special chapter at the end of this guide.
When the system consists of three or more racks, if it is powered on and off by the battery
switches, then those switches are damaged in time, due to the electric arcs. In order to
prevent this situation, a delayed main battery breaker (10 Ampere 250 V Main breaker) is
included in the system. Control of the electricity provided to the racks from the battery is
maintained by this breaker. Detailed information about this is in Chapter II of this guide.

I.2.C. INSTALLATION
MORE RACKS

OF

SYSTEMS

WITH

FOUR

OR

Installation of the DS200 system in configurations with four, five or six racks is indeed a step
that follows the cabinet-type installation of the system.
Except the case of the four-rack cabinet that has been designed for the four-rack systems,
since installation cannot be realized with one cabinet for the systems with more than three
racks, first installation of two cabinets are realized so as to distribute the necessary quantity
of racks to those two cabinets.
The crucial point while installing the two cabinets is that they should be located side by side
and they should not be displaced during and after the installation.

THE CABLES PROVIDING THE CONNECTION BETWEEN THE CABINETS


MAY BE DAMAGED IN CASE OF A DISPLACEMENT.

V003. 25.06.2002

B-8

DS200 Installation Guide


The four-rack cabinet is used, if a system has four racks. In this case, since the entire racks
will fit into that cabinet, single-cabinet installation will suffice. The rack that will fit into the
uppermost rack slot of the cabinet will be of the main rack structure, too, like the first rack.
In two-cabinet systems, the first racks (lowermost) will be main rack and the others will be
auxiliary racks. However, there is CPU200 card only in a single cabinets main rack.
Likewise, there is DS200 CPUKON card in only a single main rack.
The first and the fourth racks are of the main rack structure and the connection between
these two racks is provided with some additional cards and cables. The list of those cards
and cables are below:
1) CC Extra card
2) C Master card
3) C Slave card
4) CC Enable card
5) Two BPL200-FC
6) Five PCM carrier cable
7) BPLSPS-FCX cable
In order to facilitate the connection of the two cabinets, you need to remove the SPS248
power units, UTIL200, DS200 CPUKON and CPU200 cards (redundant CPU200, too, if there is
any.)

I.2.C.1. CONNECTIONS IN THE MAIN RACK, TO WHICH THE


CPU200 CARD HAS BEEN ATTACHED:
I.2.C.1.1. ATTACHING THE CC EXTRA CARD ONTO THE CPU200 CARD:
Attach the card to the 20-pin connector with the code CON402, in a manner as it coincides
with the lower back corner of the CPU200 card that has been indicated with white lines,
through the female connector that is on the CC Extra card.

V003. 25.06.2002

B-9

DS200 Installation Guide

Figure 6
If there will be a redundant CPU200 card in the system, then you should attach another CC
Extra card onto that redundant CPU200 card, too.

I.2.C.1.2. INTEGRATION OF THE C MASTER CARD TO THE MAIN RACK:


The C Master card must be attached to the main rack on which there is CPU200. Structure of
this card is suitable for attaching it to the plastic card slots of DS200 and its size is the same
as that of the CPU200 card. However, there is no 64-pin male connector at the back of the
card for the backplane connection. Instead, it is connected by a BPL200-FC to the inter-rack
connector that is at the lower section on the BPL200 backplane of the main rack, at the same
level with the CPU200.
If, on the other hand, there will not be a redundant CPU200 card in the DS200 system, then
the C Master card is attached to the slot that is reserved for the redundant CPU200 card.
Connect the cables before completely fixing the card in the slot.
The procedure for this:
1) Connect one end of the BPL200-FC to the inter-rack connector that is at the lower edge
of the BPL200-MAIN backplane of the main rack.
2) Connect the other end of the BPL200-FC to the similar connector that is on the C Master
card.
3) Connect the PCM carrier cables to the five RJ45 connectors that are on the C Master
card. The connection order of those cables is essentially important because those cables
will be connected to the second rack in the same order.

V003. 25.06.2002

B-10

DS200 Installation Guide

1- BPL200-FC

4- C Master card

2- PCM cable connectors (RJ45)

5- BPL200-Main

3- PCM carrier cables (The order is important.)

Figure 7
After making the entire cable connections, push the card into the slot completely and make
sure the fixing latches that are on the plastic front cover have been fully fixed on the metal
casing.
If there will be redundant CPU200 card in the system, then you may install the C Master card
in the second general-purpose slot that is on the main rack. (Keep in mind that there must
be an extension card in the first general-purpose slot.) The cable connections are the same
as above.
Then, attach the DS200 CPUKON, UTIL200, CPU200 and redundant CPU200 (if there is any) of
the main rack to their corresponding slots, as will be described in later sections.

I.2.C.1.3. CONNECTING THE BPLSPS-FCX CABLE:


The BPLSPS-FCX cable is structurally the same as the BPLSPS-FC cable, yet it is longer.
Connect one end of that cable to the SPS connector that is at the lower section of the
BPLSPS backplane.
Attach the SPS248 Power Unit to its corresponding slot, as will be described in later
sections.
Finally, extend the free ends of the PCM carrier cables and the BPLSPS-FCX cable out of the
cabinet through the cable channels that are at the lower back of the cabinet. Then, insert
those cables into the second cabinet through the similar opening as that of the first one, and
extend them to the front part of the main rack.

V003. 25.06.2002

B-11

DS200 Installation Guide

I.2.C.2. CONNECTIONS ON THE FOURTH RACK:


The procedure is similar to that for the first rack.

I.2.C.2.1. INTEGRATION OF THE C SLAVE CARD TO THE MAIN RACK


Structure of the C Slave card is the same as that of the C Master card, which is on the first
rack . Besides, the connections are exactly the same.
Since there will not be any CPU200 and redundant CPU200 cards in the second cabinet, you
can place the C Slave card into the redundant CPU200 card slot that is on the main rack of
the second cabinet. You are supposed to connect the corresponding cables before
completely fixing the card in the slot.
The procedure for this:
1) Connect one end of the BPL200-FC to the inter-rack connector that is at the lower edge
of the BPL200-MAIN backplane of the main rack.
2) Connect the other end of the BPL200-FC to the similar connector that is on the C Slave
card.
3) Connect the PCM carrier cables to the five RJ45 connectors that are on the C Slave card.
The connection order of those cables is essentially important because those cables will
be connected to the C Slave card in the same order as they have been connected to the C
Master card in the first cabinet. (See Figure 7)

INCORRECT CONNECTION ORDER OF THE PCM CARRIER CABLES


WOULD PRECLUDE THE OPERATION OF THE SYSTEM.

After making the entire cable connections, push the card into the slot completely and make
sure the fixing latches that are on the plastic front cover have been fully fixed on the metal
casing.

I.2.C.2.2. ATTACHING THE CC ENABLE CARD TO THE MAIN RACK:


The CC Enable card has a structure, which makes it possible to be attached to the BPL200MAIN backplane, thanks to the 64-pin male connector that is located at the back of it.
Attach the CC Enable card to the slot reserved for CPU200 on the main rack.
Then, you should attach the UTIL200 card of the main rack to its corresponding slot.

I.2.C.2.3. CONNECTING THE BPLSPS-FCX CABLE:


Connect free end of the BPLSPS-FCX cable, whose connection with the first cabinet has
already been provided, to the SPS connector that is at the lower section of the BPLSPS
backplane.
Attach the SPS248 Power Unit to its corresponding slot, as will be described in later
sections.
The operation of connecting two cabinets to each other will have been completed after
applying the steps above.

I.2.D. GROUNDING
Grounding is essential for protecting the DS200 Exchange from the effects of lightning or
other sources of high voltage that might affect over lines or peripheral devices.

V003. 25.06.2002

B-12

DS200 Installation Guide


Although special tools are required for measuring the sufficiency of grounding of the electric
installation of the building precisely, voltages between Neuter-Phase and Neuter-Ground
can be measured for getting a rough idea.
The Neuter-Phase voltage should be 180-260 VAC and the Neuter-Ground voltage should be
1-2 VAC. Those values must be consistent. Possible voltage leakage in grounding installation
may damage your exchange, just like all other devices that require grounding.
Water installation of the building can be used for grounding, provided that the pipes are of
metal and no insulation material has been used at junctions. Indeed, the most secure
grounding method is inserting a copper rod that is 1.5 cm in diameter with 1.5 m of length, or
inserting a copper plate with 1 m2 of area to the ground and connecting it to the exchange
through a copper grounding cable. The cable should be fastened tightly to the rod or to the
plate and precautions should be taken against corrosion.
The cable coming from the grounding plate or grounding system must be connected to the
ground connection point of the exchange.
The DS200 Exchange and auxiliary racks are connected to each other tightly at the ground
connection points with the ground connection cable that comes with the shipped hardware.

A- DS200 Main Rack

B- DS200 Auxiliary rack

C- The grounding cable

D- The copper grounding plate or rod


Figure 8

ADDITIONAL GROUNDING MUST BE PROVIDED, IF SOUNDNESS OF


THE GROUNDING OF THE ELECTRIC SYSTEM CANNOT BE GUARANTEED.

For providing the internal inter-rack grounding, first connect the grounding cable and the
grounding screw of the first rack, which is under the rack. Then, connect the grounding
screw that is under the first rack and the grounding screw of the second rack. Repeat the
same operation for the third rack. Afterwards, connect the cabinet grounding screw and the
external grounding system that has been installed for the cabinet, in order to provide
grounding for the entire cabinet.
For the two-cabinet structure, the grounding points of both cabinets must be the same.

V003. 25.06.2002

B-13

DS200 Installation Guide

I.2.E. BATTERY CONNECTION


!
SINCE ANY POWER FAILURE WILL DISRUPT THE EXCHANGE TO
PERFORM ITS NORMAL FUNCTIONS, YOU SHOULD CONNECT BATTERY TO
THE SYSTEM, IF THERE IS SUCH A POSSIBILITY.
!

THE BATTERY BREAKER MUST BE OFF DURING THE CONNECTION


PROCESS.

The system uses dry batteries. The batteries are placed at the bottom of the DS200 cabinet.
The compartment has been designed as large enough to include 38 Ah, dry-type batteries.
The dimensions of the cabinet bottom are about 60x78 cm. The capacity of that space is at
most12 batteries of 24 Ah (width: 17.5 cm, length: 16.6 cm, height: 12.5 cm) or of 38 Ah
(width: 16.5 cm, length: 19.7 cm, height: 17.0 cm). A three-rack system requires at least 4
batteries and there is room in the cabinet for 8 or 12 batteries, as needed.
Placing the batteries close to the back cover facilitates connecting them, as well as their
maintenance.
In order to connect the batteries:
First, connect the batteries that are in the compartment under the exchange serially to each
other. Then, connect the battery output through main breaker to the battery input of the main
rack, which is the lowermost rack. Attach the battery output to the connection clips on the
SPS200 (See the Technical Reference GuideFigure 13), in the manner as the red end being
the + pole, and the black end being the - pole. No battery connection is required for the
other SPSs.

REVERSE BATTERY CONNECTION MAY DAMAGE YOUR EXCHANGE.

In order to complete the connection, press the spring latch of the clips and insert the
corresponding end of the battery cable into the hole in front, deep enough so that no naked
portion of the cable is left outside and then release the latch.
Since the batteries are connected to the 48 VDC-output of the SPS200 in parallel, completely
exhausted batteries may affect normal operation of the system. In that case, you should
charge them from an external source and then re-connect them to the system.

NORMAL OPERATION OF SYSTEMS WITH BATTERIES WOULD BE


AFFECTED BY FAILURES OF 230 VAC MAINS SUPPLY DURING NIGHT TIME
AND HOLIDAYS.

THE SYSTEM AUTOMATICALLY SHUTS DOWN IF THE BATTERY


VOLTAGE DROPS BELOW 34 VDC DURING PROLONGED POWER FAILURES AND
THE BATTERIES DO NOT SWITCH ON UNTIL THE BATTERY VOLTAGE LEVEL
EXCEEDS 46 VDC.

V003. 25.06.2002

B-14

DS200 Installation Guide

1. 230 VAC cable

4. BPL200-FC

2. BPLSPS-FC

5. Grounding screw

3. Grounding wire

6. Battery connection cables

7. Main grounding cable

Figure 9

V003. 25.06.2002

B-15

DS200 Installation Guide

I.3.

INST

I.3.A. SPS200 AC/DC POWER SUPPLY


The SPS200 AC/DC Power Supply, which includes the SPS200CR Power Card, has been
placed in a metal casing.
In order to fix SPS200 in the rack, place the metal rails properly, which are on the power
chassis, in the metal slots that are on rightmost side of the rack. (See the Technical
Reference GuideFigure3). Then, push the SPS200 into the rack until it is firmly fixed to the
connector that is on the BPLSPS-Backplane, which is behind the power rack. Afterwards,
drive the SPS200 fixing screw that is in the upper front part of the rack. (See the Technical
Reference GuideFigure 4).
In case you need to take the SPS200 out of rack, switch the battery and mains off,
respectively, by the ON/OFF switches on the SPS200 module. (See The Technical Reference
GuideFigure 13). Detach the 230 V cable and battery connection cables (if there is any.)
Then, pull the power rack out after loosening the fixing screw that is on the upper front part
of the system rack.

I.3.B. SPS248 DC/DC POWER SUPPLY


SPS248 DC/DC Power Supply, which includes the SPS248CR Power Card and ring
transformer, has been mounted in a metal casing.
Attaching the SPS248 is very similar to that of the SPS200. It is attached to the slot on the
left-hand side of the SPS200. (See The Technical Reference GuideFigure 4).

CAUTION! IN MULTI-RACK DS200 SYSTEMS, THE INTER-RACK


!
POWER CONNECTIONS MUST HAVE BEEN COMPLETED PRIOR TO PLACEMENT
OF SPS248 MODULES.

I.4.

INTEG

In this section, integration of the CPU200, DS200 CPUKON, UTIL200 UTILITY and Expansion
Modules to the system, together with CON2/CON3 Line Connection Cards, have been
explained.

I.4.A.CPU200, REDUNDANT CPU200 & DS200 CPUKON


CARDS
The CPU200 Central Processing Module has been fixed in the corresponding slot, as being
connected to the BPL200-MAIN backplane in the rack. (See The Technical Reference
GuideFigure 11). The DS200 CPUKON Connection Card has been situated in the leftmost
slot of the main rack, as connected to the CPU200 card via the DS200 CPU-FC flat cable. The
DS200 CPUKON card has not been connected to the BPL200-MAIN backplane.
Install the CPU200, DS200 CPUKON and DS200 CPU-FC modules in the main rack as
described below:
1- Make sure that the UTIL200 module of the first rack has not been installed.

V003. 25.06.2002

B-16

DS200 Installation Guide


2- Connect the cables of the accessories to the connectors on the DS200 CPUKON. In order
to do this, extend the cables through the cable hole that is in the lower front rack and
attach them to the corresponding connectors on the DS200 CPUKON card. Then take the
free end of the cable out of the rack by extending it along underneath the rack through
the corresponding path within the cable channel that has been fixed on the back cover.
3- Install DS200 CPUKON card together with DS200 CPU-FC cable. First, attach the DS200
CPU-FC cable to the connector on the DS200 CPUKON card. Then, insert the DS200
CPUKON card so as its back corners fit the channel of the plastic card slot. Afterwards,
extend the free end of the DS200 CPU-FC cable along underneath the UTIL200 connector
on the backplane. As for the final step, when the card is completely placed, fix the DS200
CPUKON card by the fixing latches on the plastic card holder. See the figure below for
the correct usage of the plastic fixing latches.

Figure 10
4- In order to install the CPU200 module, place the back corners of the module into the
channel of the plastic card slot and push it towards the rack. Before you set the module
completely, connect the DS200 CPU-FC cable to CPU200. Then, push the CPU200 module
inside, so as it tightly fits on its corresponding connector on the BPL200-Backplane.
When the module has been completely set, fix it by using fixing latches on the front cover
of the card. (See The Technical Reference GuideFigure 24). See Figure 10 for the
correct usage of the plastic fixing latches.
In case it is necessary to take CPU200 out of the rack, press the card fixing latches on the
front cover of CPU200 toward the tag on the holder and then pull the module cautiously until
DS200 CPU-FC appears. As for the final step, detach DS200 CPU-FC from CPU200 and then
take it out of the rack.
In case it is necessary to take DS200 CPUKON out of the rack, press the card fixing latches
on the front cover of the card toward the tag on the holder and then pull the module
cautiously until DS200 CPU-FC appears. Afterwards, detach DS200 CPU-FC from DS200
CPUKON and take it out of the rack.
If a redundant CPU200 is needed in the system, then install that card in the special slot at the
right-hand side of CPU200, which is reserved for it by following the same installation steps
as for CPU200. Its connection to DS200 CPUKON card is provided by DS200 CPU-FC.

DO NOT EVER REMOVE THE CPU200 CARD DURING THE OPERATION


OF THE EXCHANGE.

I.4.A.1. THE LAN ADAPTOR CARD:

V003. 25.06.2002

B-17

DS200 Installation Guide


The LAN Adaptor card has been designed to be attached to two female sockets, each with 5
pins, which are on the CPUKON card. There are pins on the solder side of the card
corresponding to the female sockets on CPUKON. While the RJ45 socket on the LAN Adaptor
card is facing out of the CPUKON card, attach the pins to the sockets. In addition to that, fix
the LAN Adaptor card to the CPUKON card through lead card holders.
In the figure below the LAN Adaptor card is illustrated as it has been attached onto CPUKON.

Figure 11
After you have attached the LAN Adaptor card onto the DS200 CPUKON card, adjust the
jumpers on the CPUKON card according to the proper configuration. The table below shows
states of the jumpers:
Jumper

State

1, 2

ON

3, 4

OFF

1, 2

OFF

3, 4

ON

Selected output
RS232
LAN Adaptor

After the installation of the card is over, make the network connection through a one-to-one
cable with RJ45 connectors on both sides.

I.4.B. THE UTIL200 UTILITY MODULE


The UTIL200 Utility Module has been set on the related plastic card slot in the rack. (See The
Technical Reference GuideFigure 11 and Figure 12). The UTIL200 module is situated
between the CPU200 and DS200 CPUKON cards in the main rack. The DS200 CPU-FC cable
passes through the back of the UTIL200 module. On the other hand, it is installed in the
leftmost slot in the auxiliary racks.
In order to set UTIL200 into the rack, insert the module so as its back corners fits the plastic
card slot. Then, you should push it towards the inside of the rack so as the connector at the
back of it would fully fit its correspondent on BPL200-MAIN or BPL200-AUX (While you are
attaching the one that is on the main rack, be careful so that the DS200 CPU FC cable
remains behind the card.) When the module has been completely set, fix it by using latches
on the plastic card holder. (See Figure 10).
In case it is necessary to take UTIL200 out of the rack, press the card fixing latches on the
front cover of the card toward the sticker on the holder and then take the module out of the
rack.

I.4.B.1. INSTALLING THE CONFERENCE CHIP ON UTIL200


V003. 25.06.2002

B-18

DS200 Installation Guide


If the chip enabling conferencing with up to 16 participants, which is offered optionally is to
be utilized within the system, then insert this into the socket that is reserved for it on the
UTIL200 card of the first rack. While inserting the chip into the socket, make sure positioning
of the chip is correct.
In case there is an optional conference chip in the system, since this chip needs 32 PCM
channel in order to be functional, you must leave the last two general-purpose slots (The two
general-purpose slots on the rightmost edge of the rack) of the first rack vacant.

WHILE INSERTING THE CONFERENCE CHIP INTO THE UTIL200


CARD, LEAVE THE TWO GENERAL-PURPOSE SLOTS VACANT, WHICH ARE AT
THE RIGHTMOST SIDE ON THE BACKPLANE.

I.4.C. CON2/CON3 LINE CONNECTION CARDS


The CON2 and CON3 line connection cards constitute the connection among telephones,
lines and the extension and line cards of the system. High voltage protection circuits, the
line-busy LED, grounding pins and line connection connectors are all situated on the line
connection cards.
There are four female RJ45 connectors on the CON2 card. The MDF cable with 16 pairs,
which is called CBL-16, is for CON2. The male RJ45s at one end of the CBL-16 cable are
attached to the corresponding female connectors on CON2. Cable pairs at the other end of
the CBL-16 cable should be attached to the related sections on the MDF.
There are two female RJ45 connectors on the CON3 card. The MDF cable with 8 pairs, which
is called CBL-8, is for CON3. The male RJ45s at one end of the CBL-8 cable are attached to
the corresponding female connectors on CON3. Cable pairs at the other end of the CBL-8
cable should be attached to the related sections on the MDF.
The CON2 and CON3 cards are attached to the related expansion card on the side with circuit
elements. Two 20-pin connectors on the component side of the CON2 and CON3 cards are
attached to the corresponding connectors on the component side of the expansion card.
You should connect the cables CBL-8 and CBL-16 correctly in order to experience no
problems while removing the expansion modules from the exchange and replacing them
back. Proper connection of those cables is shown in Figure 12.
It would be proper to extend the cables that go to the line connection connectors alongside
the expansion card connection connector (20-pin, white connector) in order to reduce the
space they occupy. Fixing line connection cables tightly to the expansion card by cable tie so
as their thin sides would touch the card, would provide for a trouble-free installation.

V003. 25.06.2002

B-19

DS200 Installation Guide

1. Ground contact spring

4. Line status LED

7. CBL-8 line cable

2. Line connection connector (RJ45)

5. Card status LED

8. CBL-16 line cable

3. EX200B connection connector

6. Cable tie

Figure 12
While attaching the line connection card to the expansion card, be careful about fully
inserting the connection connectors and fully fitting the line connection card into the clicks
on sides of the plastic cover. Cards that are not completely fitted cause friction with the
cards nearby, as well as they cause the LEDs on the front face not to be seen from outside,
for they would not fit.
The connectors on the line connection cards have been included only to provide for easy
replacement of the card without detaching the cabling, in case protection circuitry on the
card is damaged. While replacing the card, do not detach the cables from that connector. In
order to achieve this, during the first connection, insert the expansion module to its
corresponding place by sliding it in the slot while the cable is still loosely hanging, however,
leave it 6-7 cm before the point it is completely fixed. Then, fix the line connection cable to
the back surface of the exchange while the expansion module is in this position.

V003. 25.06.2002

B-20

DS200 Installation Guide

1. CON2 / CON3 connection card

6. Ground contact spring of rack

2. Ground contact spring of


connection card

7. CBL-8 / CBL-16 line cable

3. EX200B line card

8. Card removing latch

4. Card slot

9. Card fixing click

5. Bottom front section of rack

10. Front card cover

Figure 13

I.4.D. INSTALLING EXPANSION MODULES


This section explains integrations of the entire EX200 extension, line and network connection
modules to the system.

I.4.D.1. ATTACHING EX200 MODULES:


EX200 modules fundamentally consist of the electronic card and the card cover that
maintains connection to chassis. Figure 24 in the Technical Reference Guide shows
fundamental characteristics of a card and a card cover.
There are two points to consider while establishing the configuration of the system:
1) An extension card must be installed in the first general-purpose slot of the first rack.
2) If EX200 (1S2/0) or EX200 (1R2/0) module or modules are to be installed in the system,
then the ones that are to be utilized for data or video transmission must be installed in
the first rack, into the card slots with even numbers. On the other hand, the modules that
are to be utilized for voice transmission can be installed into the even-numbered slots of
any rack.

THE EX200 (1S2/0) OR EX200 (1R2/0) MODULES THAT ARE TO BE


UTILIZED FOR DATA OR VIDEO TRANSMISSION IN THE SYSTEM MUST BE
INSTALLED IN THE FIRST RACK OF THE EXCHANGE.

After considering criteria such as the system configuration, traffic rate (distribution of
extension and line connections to the racks), begin with installing the modules in their
corresponding slots.

Hold the module upright and make sure the corners in the rear fit lower and upper
plastic slot, then push it forward in the slot slowly and cautiously.

V003. 25.06.2002

B-21

DS200 Installation Guide

After more than half of the module has been inserted into the slot, arrange any
cable that is connected to the module.

You need to push a little bit harder so that the connector for backplane connection
fits, which is at the back of the expansion card.

Finally, push the module by gently pressing the latches upward / downward, which
are at the top and bottom of the card cover to fit it to its place.

Check if the card fixing clicks that are over the card cover latches have fit to the
holes on the chassis. Card latches that have not fit appear as in Figure 10.

Before the expansion module contacts with the backplane while it is being pushed into its
slot, the pins that are on and under the connection card provides grounding for the cards by
applying pressure on the ground contact spring. (See Figure 13).
In case it would be necessary to remove the modules following the first installation:

Pull the module by pressing the latches at the top and bottom of the card cover to
disconnect it from the backplane.

Pull the module until the line connection card gets out of the exchange. Be careful
about the cable that has been fixed under the exchange, so that it would not forced
too much by being pulled.

At this point, remove the line connection card from the expansion card and set it
free as connected to the line connection cable. Then do whatever would be
necessary by pulling the module out.

Repeat the steps above in reverse order in order to replace the card. While removing and
replacing the module, pay attention to the facts that line connection cable has been tightly
attached to the chassis, the expansion card and the connection cards are completely in
contact, and the card cover moves in a straight line parallel to slot.

MOVE THE MODULES IN A STRAIGHT LINE WHILE INSERTING OR


REMOVING, WITHOUT TILTING THEM TOWARDS RIGHT-LEFT OR IN
UPWARD-DOWNWARD DIRECTION.

See Figure 10 for the appearance of a card latch that has not fit.

I.4.D.2. CABLING OF EX200 MODULES:


After you have installed the expansion modules in the corresponding slots in the rack,
establish line or extension connections by making use of the cable pairs at the free ends of
CBL-8 or CBL-16 cables, which have properly been taken out of the rack. The following
tables present cabling information related to those connections on module basis.

I.4.D.2.1. EX200 (0/16) ANALOG EXTENSION MODULE:


Pairs in the CBL-16 cable and connected extensions are given in the table below.

V003. 25.06.2002

Pair No

Color & Signal of Pair

Extension No

White (A) Blue (B)

1st Extension

White (A) Orange (B)

2nd Extension

White (A) Green (B)

3rd Extension

White (A) Brown (B)

4th Extension

White (A) Gray (B)

5th Extension
B-22

DS200 Installation Guide


6

Red (A) Blue (B)

6th Extension

Red (A) Orange (B)

7th Extension

Red (A) Green (B)

8th Extension

Red (A) Brown (B)

9th Extension

10

Red (A) Gray (B)

10th Extension

11

Black (A) Blue (B)

11th Extension

12

Black (A) Orange (B)

12th Extension

13

Black (A) Green (B)

13th Extension

14

Black (A) Brown (B)

14th Extension

15

Black (A) Gray (B)

15th Extension

16

Yellow (A) Blue (B)

16th Extension

The order of A and B wires are not important for the connection of the cable mentioned
above to the extension phone.

I.4.D.2.2. EX200 (8/0) ANALOG LINE MODULE:


Pairs in the CBL-8 cable and connected lines are given in the table below.

Pair No

Color & Signal of Pair

Line No

White (A) Blue (B)

1st Line

White (A) Orange (B)

2nd Line

White (A) Green (B)

3rd Line

White (A) Brown (B)

4th Line

White (A) Gray (B)

5th Line

Red (A) Blue (B)

6th Line

Red (A) Orange (B)

7th Line

Red (A) Green (B)

8th Line

The order of A and B wires are not important for the connection of the cable mentioned
above to the lines. The line circuitry automatically detects polarity and takes action
accordingly.

I.4.D.2.3. EX200 (0/8S0) ISDN BRI EXTENSION MODULE:


Pairs in the CBL-16 cable and connected extensions are given in the table below.

V003. 25.06.2002

Pair No

Color & Signal of Pair

White (R1) - Blue (T1)

White (T2) Orange (R2)

White (R1) Green (T1)

White (T2) Brown (R2)

White (R1) Gray (T1)

Red (T2) Blue (R2)

Red (R1) Orange (T1)

Extension No
1st ISDN Extension
2nd ISDN
Extension
3rd ISDN Extension
4th ISDN Extension

B-23

DS200 Installation Guide


8

Red (T2) Green (R2)

Red (R1) Brown (T1)

10

Red (T2) Gray (R2)

11

Black (R1) Blue (T1)

12

Black (T2) Orange (R2)

13

Black (R1) Green (T1)

14

Black (T2) Brown (R2)

15

Black (R1) Gray (T1)

16

Yellow (T2) Blue (R2)

5th ISDN Extension


6th ISDN Extension
7th ISDN Extension
8th ISDN Extension

For the cable above, order of the four wires that are to be used for connection to ISDN
devices is important.
The signals represented as R are the receiving signals of DS200; on the other hand, the
signals represented as T are the transmitting signals. Pay attention to this order for
cabling.
Pin-signal assignments of cabling for the connection between DS200 and Iris ISDN
telephones are given in the table below:
Signal with
respect to Iris

RJ45 pins of the


Iris side

CBL-16 wires of
the DS200 side

Signal with respect


to DS200

T1

R1

R1

T1

R2

T2

T2

R2

I.4.D.2.4. EX200 (1S2/0) ISDN PRI MODULE:


The assignments required for the PRI ISDN line connections of the EX200B (1S2/0) card are
given in the table below.

Signal

D-type Connector Pin No

RJ45 Pin No

R1

R2

T1

T2

For the cable above, order of the four wires that are to be used for the ISDN connection is
important.
Pin assignments of the cable that comes with the EX200 (1S2/0) module are given with
respect to the RJ45 connectors at both ends, in the table below:
RJ45

Signal

RJ45

R1

R2

T1

T2

I.4.D.2.5. EX200 (1R2/0) R2 DIGITAL LINE MODULE:


V003. 25.06.2002

B-24

DS200 Installation Guide


The assignments required for the line connections of the EX200 (1R2/0) card are given in the
table below.

Signal

D-type Connector Pin No

RJ45 Pin No

R1

R2

T1

T2

For the cable above, order of the four wires that are to be used for the R2 connection is
important.
Pin assignments of the cable that comes with the EX200 (1R2/0) module are given with
respect to the RJ45 connectors at both ends, in the table below:
RJ45

Signal

RJ45

R1

R2

T1

T2

I.4.D.2.6. EX200 (0/8U) DIGITAL EXTENSION MODULE:


Pairs in the CBL-8 cable and connected extensions are given in the table below.

Pair No

Color & Signal of Pair

Extension No

White (A) Blue (B)

1st Extension

White (A) Orange (B)

2nd Extension

White (A) Green (B)

3rd Extension

White (A) Brown (B)

4th Extension

White (A) Gray (B)

5th Extension

Red (A) Blue (B)

6th Extension

Red (A) Orange (B)

7th Extension

Red (A) Green (B)

8th Extension

The order of A and B wires are not important for the connection of the cable mentioned
above to the extension phone.

I.4.D.2.7. EX200 (0/16U) DIGITAL EXTENSION MODULE:


Pairs in the CBL-16 cable and connected extensions are given in the table below.

V003. 25.06.2002

Pair No

Color & Signal of Pair

Extension No

White (A) Blue (B)

1st Extension

White (A) Orange (B)

2nd Extension

White (A) Green (B)

3rd Extension

White (A) Brown (B)

4th Extension

White (A) Gray (B)

5th Extension

Red (A) Blue (B)

6th Extension

Red (A) Orange (B)

7th Extension
B-25

DS200 Installation Guide


8

Red (A) Green (B)

8th Extension

Red (A) Brown (B)

9th Extension

10

Red (A) Gray (B)

10th Extension

11

Black (A) Blue (B)

11th Extension

12

Black (A) Orange (B)

12th Extension

13

Black (A) Green (B)

13th Extension

14

Black (A) Brown (B)

14th Extension

15

Black (A) Gray (B)

15th Extension

16

Yellow (A) Blue (B)

16th Extension

The order of A and B wires are not important for the connection of the cable mentioned
above to the extension phone.

I.4.D.2.8. EX200 (8 T0/S0) ISDN BRI LINE/EXTENSION MODULE:


Pairs in the CBL-16 cable and connected extensions are given in the table below.

Pair No

Color & Signal of Pair

White (R1) - Blue (T1)

White (T2) Orange (R2)

White (R1) Green (T1)

White (T2) Brown (R2)

White (R1) Gray (T1)

Red (T2) Blue (R2)

Red (R1) Orange (T1)

Red (T2) Green (R2)

Red (R1) Brown (T1)

10

Red (T2) Gray (R2)

11

Black (R1) Blue (T1)

12

Black (T2) Orange (R2)

13

Black (R1) Green (T1)

14

Black (T2) Brown (R2)

15

Black (R1) Gray (T1)

16

Yellow (T2) Blue (R2)

Line No
1st ISDN line
2nd ISDN line
3rd ISDN line
4th ISDN line
5th ISDN line
6th ISDN line
7th ISDN line
8th ISDN line

For the cable above, order of the four wires that are to be used for connection to ISDN
devices is important.
The signals represented as R are the receiving signals of DS200; on the other hand, the
signals represented as T are the transmitting signals. Pay attention to this order for
cabling.
Pin-signal assignments of cabling for the connection between DS200 and lines extending out
of NT1 (network terminating device) are given in the table below:

V003. 25.06.2002

B-26

DS200 Installation Guide


Signal with respect
to NT1

RJ45 pins of the


NT1 side

CBL-16 wires of
the DS200 side

Signal with respect


to DS200

T1

R1

R1

T1

R2

T2

T2

R2

I.4.D.2.9. EX200 (0/8LB) LOCAL BATTERY EXTENSION MODULE:


Pairs in the CBL-8 cable and connected extensions are given in the table below.

Pair No

Color & Signal of Pair

Line No

White (A) Blue (B)

1st LB Line

White (A) Orange (B)

2nd LB Line

White (A) Green (B)

3rd LB Line

White (A) Brown (B)

4th LB Line

White (A) Gray (B)

5th LB Line

Red (A) Blue (B)

6th LB Line

Red (A) Orange (B)

7th LB Line

Red (A) Green (B)

8th LB Line

The order of A and B wires are not important for the connection of the cable mentioned
above to the extension phone.

I.4.D.2.10. EX200 (4E&M/0) E&M LINE MODULE:


Pairs in the CBL-16 cable and connected extensions are given in the table below.

V003. 25.06.2002

Pair No

Color & Signal of Pair

White (E) - Blue (SG)

White (M) Orange (SB)

White (T) Green (R)

White (T1) Brown (R1)

White (T1) Gray (R1)

Red (T) Blue (R)

Red (M) Orange (SB)

Red (E) Green (SG)

Red (E) Brown (SG)

10

Red (M) Gray (SB)

11

Black (T) Blue (R)

12

Black (T1) Orange (R1)

13

Black (T1) Green (R1)

14

Black (T) Brown (R)

15

Black (M) Gray (SB)

16

Yellow (E) Blue (SG)

Line No

1st E&M Line

2nd E&M Line

3rd E&M Line

4th E&M Line

B-27

DS200 Installation Guide


Connection orders of both signaling and voice transmission wires for cabling E&M lines are
important.
These wires should be connected by being crossed within their own groups.
Those orders are given in the table below for two correspondent exchanges:
RJ45 wire order on
DS200 side

Wire order on the


Signal

opposite side

SG

SB

SB

SG

R1 (R, if it is 2-wire)

T1 (T, if it is 2-wire)

T1

R1

I.4.E. JUMPER SETTINGS ON THE EX200 (8T0/S0)


MODULE
The ISDN BRI lines of the EX200 (8 T0/S0) module can be configured as either external line or
extension. (The software with the version 1.05 does not support the configuration for
extension.) This setting operation is done trough jumpers that exist within the structure of
each line. The list of those settings are given per line in the table below:
Line Number
1st ISDN BRI line
2nd ISDN BRI line
3rd ISDN BRI line
4th ISDN BRI line
5th ISDN BRI line
6th ISDN BRI line
7th ISDN BRI line
8th ISDN BRI line

Positions of the jumpers for extension settings


K4, K5 pins 1,2 and K6, K7 pins 1,2
K8, K9 pins 1,2 and K10, K11 pins 1,2
K12, K13 pins 1,2 and K14, K15 pins 1,2
K16, K17 pins 1,2 and K18, K19 pins 1,2
K20, K21 pins 1,2 and K22, K23 pins 1,2
K24, K25 pins 1,2 and K26, K27 pins 1,2
K28, K29 pins 1,2 and K30, K31 pins 1,2
K32, K33 pins 1,2 and K34, K35 pins 1,2

Line Number
1st ISDN BRI line
2nd ISDN BRI line
3rd ISDN BRI line
4th ISDN BRI line
5th ISDN BRI line
6th ISDN BRI line
7th ISDN BRI line
8th ISDN BRI line

Positions of the jumpers for line settings


K4, K5 pins 2,3 and K6, K7 pins 2,3
K8, K9 pins 2,3 and K10, K11 pins 2,3
K12, K13 pins 2,3 and K14, K15 pins 2,3
K16, K17 pins 2,3 and K18, K19 pins 2,3
K20, K21 pins 2,3 and K22, K23 pins 2,3
K24, K25 pins 2,3 and K26, K27 pins 2,3
K28, K29 pins 2,3 and K30, K31 pins 2,3
K32, K33 pins 2,3 and K34, K35 pins 2,3

V003. 25.06.2002

B-28

DS200 Installation Guide

I.4.F. JUMPER SETTINGS ON THE EX200 (4E&M/0)


MODULE
Since several different configurations are possible for the E&M module, unlike the others,
some configuration settings must be done on it before it is installed in the system. Those
settings are done through jumpers. A list of jumper settings for different configurations is as
follows:
A) FOR THE SIGNALING CHANNEL CONFIGURATION:
Type 1:
TRUNKING SIDE
E&M channel 1: JP1, JP4, JP17, JP19, JP22
E&M channel 2: JP5, JP8, JP31, JP33, JP36
E&M channel 3: JP9, JP12, JP24, JP26, JP29
E&M channel 4: JP13, JP16, JP38, JP40, JP43
SIGNALING SIDE
E&M channel 1: JP2, JP3, JP19, JP21
E&M channel 2: JP6, JP7, JP33, JP35
E&M channel 3: JP10, JP11, JP26, JP28
E&M channel 4: JP14, JP15, JP40, JP42
Type 2:
TRUNKING SIDE
E&M channel 1: JP1, JP4, JP19, JP20
E&M channel 2: JP5, JP8, JP33, JP34
E&M channel 3: JP9, JP12, JP26, JP27
E&M channel 4: JP13, JP16, JP40, JP41
SIGNALING SIDE
E&M channel 1: JP2, JP3, JP21, JP23
E&M channel 2: JP6, JP7, JP35, JP37
E&M channel 3: JP10, JP11, JP28, JP30
E&M channel 4: JP14, JP15, JP42, JP44
Type 3:
TRUNKING SIDE
E&M channel 1: JP1, JP4, JP17, JP19, JP20
E&M channel 2: JP5, JP8, JP31, JP33, JP34
E&M channel 3: JP9, JP12, JP24, JP26, JP27
E&M channel 4: JP13, JP16, JP38, JP40, JP41

V003. 25.06.2002

B-29

DS200 Installation Guide


SIGNALING SIDE
E&M channel 1: JP2, JP3, JP19, JP21, JP23
E&M channel 2: JP6, JP7, JP33, JP35, JP37
E&M channel 3: JP10, JP11, JP26, JP28, JP30
E&M channel 4: JP14, JP15, JP40, JP42, JP44
Type 4:
TRUNKING SIDE
E&M channel 1: JP1, JP4, JP19, JP20
E&M channel 2: JP5, JP8, JP33, JP34
E&M channel 3: JP9, JP12, JP26, JP27
E&M channel 4: JP13, JP16, JP40, JP41
SIGNALING SIDE
E&M channel 1: JP1, JP4, JP18, JP21
E&M channel 2: JP5 JP8, JP32, JP35
E&M channel 3: JP9, JP12, JP25, JP28
E&M channel 4: JP13, JP16, JP39, JP42
Type 5
TRUNKING SIDE
E&M channel 1: JP1, JP4, JP19, JP21
E&M channel 2: JP5, JP8, JP33, JP35
E&M channel 3: JP9, JP12, JP26, JP28
E&M channel 4: JP13, JP16, JP40, JP42
SIGNALING SIDE
E&M channel 1: JP1, JP4, JP19, JP21
E&M channel 2: JP5 JP8, JP33, JP35
E&M channel 3: JP9, JP12, JP26, JP28
E&M channel 4: JP13, JP16, JP40, JP42
B) FOR SPEECH CHANNEL CONNECTION
Two-wire connection
E&M channel 1: JP45, JP46
E&M channel 2: JP48, JP49
E&M channel 3: JP51, JP52
E&M channel 4: JP54, JP55
Four-wire connection
E&M channel 1: JP47
E&M channel 2: JP50
E&M channel 3: JP53
E&M channel 4: JP56
V003. 25.06.2002

B-30

DS200 Installation Guide

I.4.G. INSTALLATION OF THE EVM200L MODULE


Integration of the EVM200L module to the system is the same as that of the EX200 cards.
However, there are two points that differ from the case for the EX200 modules:
1) No cabling is needed for EVM200L installation,
2) EVM-FL Flash ROM Auto Attendant message module or EVM-DL, DRAM voice mail
module can be installed on the EVM200L module in order to increase the capacity of Auto
Attendant or voice mail.
On the EVM200L card, there are two slots in which the EVM-FL card can be installed and
there are four slots in which the EVM-DL card can be installed. Figure 14 shows locations
of those slots on the card:

Figure 14
The EVM-FL or EVM-DL cards can be installed in the slots reserved for them without respect
to any order.
After the installation of EVM-FL or EVM-DL is over, hold the module upright and make sure
the corners in the rear fit lower and upper plastic slot, then push it forward in the slot slowly
and cautiously. You need to push a little bit harder so that the connector for backplane
connection fits, which is at the back of the EVM200L card. In this final step, push the module
by gently pressing the latches upward / downward, which are at the top and bottom of the
card cover and make sure the module fits completely.
Check if the card fixing clicks that are over the card cover latches have fit to the holes on the
chassis. Card latch that has not fit appears as in Figure 10.
In case it would be necessary to remove the module following the first installation, pull the
module by pressing the latches at the top and bottom of the card cover to disconnect it from
the backplane. Then, pull it until it gets out of the exchange.

I.5. THE FINAL PREPARATIONS


Upon completion of all those operations, connect the computer to the system, to which the
ADMIN200 has been loaded. For this, connect one end of the computer cable, which comes
with DS200, to the RS232 output on the DS200 CPUKON card. As for the other end of the
cable, connect it to the related serial port on the computer.
In addition to that, you need to connect an LT200 (-H) or FT20 Feature Telephone set as the
operator telephone in order to watch the tests closely that would be carried out on the
system. For this, plug the two-pin end of the cable, which comes with DS200 with a two-pin
V003. 25.06.2002

B-31

DS200 Installation Guide


connector at one end and with telephone connection box on the other, into one of the KTS
ports that are on the DS200 CPUKON card. Additionally, connect the first extension of the
first EX200 (0/16) card (blue-white pair) to the red and green ends of the connection box that
is at the other end of that cable.
Details about those connections have been explained in the guides of the related telephones
and in the ADMIN200 guide.

V003. 25.06.2002

B-32

DS200 Installation Guide

II. PUTTING THE SYSTEM ON LINE


After all the cards have been installed, the system is ready to be powered.
The methods for properly powering the system have been listed below for different system
configurations:

II.1. SINGLE-RACK, WALL-TYPE SYSTEM


1) Make sure the entire cables in the rack have been connected properly.
2) Check if the mains and battery switches on the SPS200 module are off.
3) Connect the mains cord to the SPS200 module and then plug it into an outlet of the
premise that has been properly grounded.
4) Connect the batteries (if battery connection is to be made) to the battery connectors
of the SPS200 module.
5) Turn on the mains switch on the SPS200 module.
6) Turn on the battery switch on the SPS200 module.

II.2. TWO-RACK WALL-TYPE SYSTEM


1) Make sure the entire inner-rack and inter-rack connections have been made
properly.
2) Check if the mains and battery switches on the entire SPS200 modules are off.
3) Connect the mains cords to the SPS200 modules and then plug them into an outlet of
the premise that has been properly grounded.
4) Connect the batteries (if battery connection is to be made) to the battery connectors
of the first SPS200 module (Note that no connection shall be made to the second
SPS200 module.)
5) Turn on the mains switches on the SPS200 modules.
6) Turn on the battery switch that is on the SPS200 module to which the batteries have
been connected.

II.3. CABINET-TYPE SYSTEM


1) Make sure the entire inner-rack and inter-rack connections have been made
properly.
2) Check, if the primary mains switch, which is on the control panel of the cabinet, is off.
3) Check, if the primary battery switch, which is on the control panel of the cabinet, is
off.
4) Check if the mains and battery switches on the entire SPS200 modules are off.

V003. 25.06.2002

B-33

DS200 Installation Guide


5) Plug the mains cords of the entire SPS200 modules into the mains outlets that are on
the control panel of the cabinet.
6) Plug the mains cord that comes from the mains outlets on the control panel of the
cabinet into an outlet of the premise that has been properly grounded. Since the
primary mains switch is protected with a fuse of 10 A, the mains outlet of the premise
must be protected with a higher-rate fuse.
7) Connect the batteries (if battery connection is to be made) to the battery connection
points on the cabinet.
8) Make the connection from the primary battery switch to the first of the SPS200
battery connectors (Note that the battery connection is not made to the entire SPS200
modules.)
9) Turn on the entire mains switches on the SPS200 modules, beginning with the
SPS200 module in the first rack.
10) Turn on the battery switch that is on the SPS200 module to which the batteries have
been connected.
11) Turn on the primary mains switch that is on the control panel of the cabinet.
12) Turn on the primary battery switch that is on the control panel of the cabinet.
13) Turn on the two fan switches that are on the control panel of the cabinet. The fans
must be working while the system is in operation.

II.4. TWO-CABINET SYSTEM


1) Make sure the inner-rack, inter-rack and inter-cabinet connections have been made
properly.
2) Check if the primary mains switches that are on the control panels of the cabinets are
off.
3) Check if the primary battery switches that are on the control panels of the cabinets
are off.
4) Check if the mains and battery switches on the entire SPS200 modules are off.
5) Plug the mains cords of the entire SPS200 modules into the mains outlets that are on
the control panels of the cabinets.
6) Plug the mains cords that come from the mains outlets on the control panels of the
cabinets into outlets of the premise that have been properly grounded. Since the
primary mains switch is protected with a fuse of 10 A, the mains outlet of the premise
must be protected with a higher-rate fuse.
7) Connect the batteries (if battery connection is to be made) to the primary battery
connection points on the first cabinet.
8) Make the connection from the battery switch to the first of the SPS200 battery
connectors (Note that the battery connection is not made to the entire SPS200
modules and it is made only for one cabinet.)
9) Turn on the entire mains switches on the SPS200 modules, beginning with the
SPS200 module in the first rack.
10) Turn on the battery switch that is on the SPS200 module to which the batteries have
been connected.
11) Turn on the primary mains switch that is on the control panel of the second cabinet.
V003. 25.06.2002

B-34

DS200 Installation Guide


12) Turn on the primary mains switch that is on the control panel of the first cabinet.
13) Turn on the primary battery switch that is on the control panel of the first cabinet.
14) Turn on the fan switches that are on the control panels of the cabinets. The fans must
be working while the system is in operation.
After being powered, the system carries out a series of automatic tests in order to check the
current configuration. Beginning with the card in the rightmost slot, two LEDs that are on the
front plastic panel of each card start to light in a row. This action begins with the bottom
rack.
After the entire LEDs have begun to light, the message connecting appears on LCD screen
of LT200 (-H) or FT20 feature telephone that is connected to the system. Once that message
disappears, the system is ready to operate.

WARNING

1) In order to turn on and off a cabinet-type system, use the


mains and battery switches that are in front of the cabinet.
2) The correct way of powering the system is
batteries on line after turning the system on.

putting

the

3) The correct way of shutting down the system is putting the


batteries off line before turning the system off.

V003. 25.06.2002

B-35

DS200 Installation Guide

III. TESTING THE SYSTEM AND


TROUBLESHOOTING BASIC PROBLEMS
It would be useful to test the fundamental characteristics of the exchange, after it has been
put on line. It would be even more useful to detect some possible errors in advance, if those
tests are done before the line cables are attached to the main distribution frame.
When the system has come on line, it detects the configuration by carrying out an automatic
scan as the first step, as described in the previous section.
Visual test, which is the first test step, should be done after that scan. When the scanning is
over, the LEDs are checked, which are in the fronts of the entire modules that have been
installed in the system. Modules and normal LED actions are as follows:

Module

LED

CPU200

It blinks.

Redundant CPU200

It blinks fast.

CC Enable

It blinks.

UTIL200

It blinks.

Module

Upper LED
LED

Lower LED

It is on

It is on.

EVM200L

It is on.

It blinks.

Module

- 48 VDC LED

+ 5 VDC LED

- 5 VDC LED

SPS248

It is on.

It is on.

It is on.

Module

VOUT

FAULT

MAINS POWER

SPS200 (2)

It is on.

It is off.

It is on.

EX200

(1)

(1) Since EX200 (1S2/0) and EX200 (1R2/0) modules have no CON line connection card, they
do not have LEDs on their front sides, either. LEDs of those modules are on the cards
themselves.
(2) In case there are more than one SPS200 in the system, while the LEDs of one or more
SPS200s are on, the others may be off. This signifies that only the SPS200s with the
LEDs on carry the system load at that moment. The ones with the LEDs off will
automatically come on line in case the load increases.
If anything except the facts indicated in the table and the notes above is observed, it is
probable that there is a problem in the system. If the upper LED of one of the EX200 modules
are not on, then this may indicate that there is a short-circuit in the line cables that are
connected to that module. In such a case, you should check for any short circuit in the cable.
If the FAULT LED on SPS200 is on, then there is an element in the system, which consumes
excessive power. In such a case, turn the system off and check for any mistakes that may
have been made during installation.

V003. 25.06.2002

B-36

DS200 Installation Guide


If you observe problems with LEDs of the CPU200, CC Enable, UTIL200 and SPS248 modules,
then shut down the system and replace the modules whose LEDs are off with new ones. Put
the system on line again, afterwards.
If the lower LED of any of the EX200 or EVM200L cards is off, then it is likely that there is a
problem with that card. In that case:
1) Cut the power to that card through the operator telephone by programming,
2) Replace the card with a new one,
3) Power the new card, again, through the operator telephone by programming.
The programming procedure for that purpose is as follows:
a) Dial 877777 through the operator telephone and wait for the dial tone,
b) Cut the power to the card by dialing 800950, then the slot number of the card and
finally 0. At that point, you are supposed to receive either the dial tone or the error
tone.
c) Remove the card from its slot by disconnecting it from the line connection card and
take it out of the system.
d) Place the new card into the slot by plugging the line connection card.
e) Power the card, again, through the operator telephone, by dialing 800950, then the
slot number of the card and finally 1.
NOTE: In order to power the card again, as explained above, a period of at least 30 seconds
must pass after the power is cut.

Sixth rack

94

80

81

82

83

84

85

86

87

88

89

90

91

92

93

Fifth rack

78

64

65

66

67

68

69

70

71

72

73

74

75

76

77

Fourth rack

SECOND CABINET

The table below illustrates card locations and slot numbers for a 6-rack system:

48

49

50

51

52

53

54

55

56

57

58

59

60

61

V003. 25.06.2002

62

B-37

Third rack

46

32

33

34

35

36

37

38

39

40

41

42

43

44

45

Second rack

30

16

17

18

19

20

21

22

23

24

25

26

27

28

29

First rack

FIRST CABINET

DS200 Installation Guide

14

00

01

02

03

04

05

06

07

08

09

10

11

12

13

UTIL200 cards
EX200 or EVM200 cards
CPU200 card (no slot number)
CC Enable card (no slot number)
After the visual test and the necessary arrangements are completed, it would be useful to
check the system in general simply.
Choosing extensions from various racks randomly and then arranging phone calls among
them by establishing connections would be sufficient to test the fundamental structure of the
system. At this point, it becomes a necessity to have a good command of the numbering plan
of the system. Therefore, it would be wise to run the ADMIN200 program and review the
numbering plan through the Configuration window.
Once the ADMIN200 program runs and the Configuration window opens, numbers of the
lines on a card can be viewed as long as the mouse cursor is placed onto the related card
and the left mouse button is kept pressed.
When the system test is over, shut down the system, make the line connections over the
main distribution pane, complete the entire accessory connections and then put the system
on line again for use.
Afterwards, the related programming must be done preferably through the ADMIN200
program.

!" WARNING
All the programmed parameters must be saved in the nonvolatile memory of the system and then they should be backedup to a PC through ADMIN200.

V003. 25.06.2002

B-38

Você também pode gostar