ELECTRICAL SERVICES

- The system design and installation shall comply and conform to the
current rules and regulations of:

The Electrical Regulations, Federal of Malaysia 1951 and current


amendments.

Sarawak Electricity Supply Corporation (SESCO)

Director General of Electrical Inspector Peninsular Malaysia

The Fire Services Department (Bomba)

BS7671 (Electrical Wiring Regulation)

MS IEC 60364 (Low Voltage Electrical Installation)

MS1525:2007 (Energy Efficiency and Use of Renewable Energy)


where appropriate

Relevant Malaysian Standards, British Standards, IEC & Electrical


Codes of Practice.

All other Authorities having jurisdiction over the installations

LV ELECTRICAL DISTRUBUTION SCHEME


- All the mechanical equipments, motors, control panels, lighting and small
power distribution panels will be supplied with either
400V/50Hz for 3-phase 4-wire system
230V/50Hz for Single phase 2-wire system
For electrical switch board, low Voltage (400V) switchboards will be
constructed for the electrical supply distribution. Main-switchboard (MSB)
will be located at M&E plant room of LG and sub-switchboards (SB) or
distribution boards (DB) for final distribution at the respective floors where
necessary.
Main Switchboards, MSBs:
Min. Form 3 & IP20
ACB&MCCB, ELR / IDMT&ELR (Earth Leakage protection),
Capacitor Bank (pf > 0.9), Electronic Surge Protector and
Digital Power Meter
Sub-Switchboards, SSBs:
ELR / RCCB
Distribution Boards, DBs:
MCB

In cabling system, vertical electrical distribution for general tap-off branch


to suite application and Horizontal electrical distribution will be through
high (ceiling) level for all the general lighting and small power loads. PVC
or XPLE insulated copper cables in conduits and PVC/SWA/PVC for external
areas.

STANDBY POWER SUPPLY SYSYTEM


- All the lightings and small power under essential supply shall be
connected to the generator set. The loads under essential supply will be
provided according to the following proportions:

Load

Percentage Standby Power

Lighting and power for general


all area

30%

External Lighting

30 %

Security, critical plants & other


life safety systems

100%

Fire Protection system

100%

ALL ACMV

N/A

LIGHTING SYSTEM
-Illumination levels will be selected to comply with MS 1525 Recommendation or to the
Clients requirements. All the T5 fluorescent lamps come with low loss electronic control gear
& ballast. Use of incandescent tungsten, mercury vapor & halogen lamps are discouraged.
The localized lighting switch will be provided for individual areas such as plant rooms,
kitchen, storage room, etc.
Area

Average
Illumination
Level, Lux

Proposed Fitting

Responsibility

Car Park

100

T5 Fluorescent Bare
Channel

M&E

External Compound
& Landscape

20-50

ID / LANSCAPE
CONSULTANT

Plant Rooms / BOH

100

T5 Fluorescent Bare
Channel

M&E

Store

100

T5 Fluorescent Bare
Channel

M&E

House Keepers
Quater

200

Compact Fluorescent
Down Lights

M&E/Arch/ID

Office

150-300

Compact Fluorescent
Down Lights

M&E/Arch/ID

Residence

100

Compact Fluorescent
Down Lights

M&E/Arch ID

Circulation Area

100

Compact Fluorescent
Down Lights

M&E/Arch ID

. -Emergency Lights (EL) included as per local authorities requirement


and where necessary. Also, Illuminated Exit Sign (KELUAR) included in
office area. Provision will be minimal as per architects approved bomba
drawings.

-Local dimming facilities and manual by-pass will also be provided at locations to suit
specific applications.The localized lighting switch will be provided for individual areas such
as plant rooms, kitchen, storage room, etc.

Small Power Distribution


- All small power outlets shall be 13A switched socket radially or ring wired
wherever appropriate. The provision of switched socket outlets in, office,

residence and all other rooms


Owner/Architect/IDs requirements.

will

be

provided

based

on

the

Switched socket outlet/isolator with essential supply capability will be


provided for fridge and other equipment in the kitchen, socket outlets
inside office suites, CCTVs, etc.

LIGHTNING PROCTECTION & EARTHING


-The lightning protection design shall be used Faraday cage type. Test
points for each earthing and down conductor will be provided for future
testing and maintenance.

SECURITY SERVICES
- The CCTV Digital Surveillance System is provided to view, record &
playback multiple camera images captured from different location of the
selection of date and time of the event.
-Intercom system shall include one unit handset

SMATV (SATELLITE MASTER AND TELEVISION )


- The SMATV system shall provide VHF, UHF and IF band from a common
headend equipments including antennae and satellite dish.

TELEPHONE & STRUTURED CABLING