Technical documentation

Warm air heater


WS WO

Indirectly fired air heater WS


WS indirectly fired air heater to DIN 4794 for heating oil, natural gas and liqefied gas.

CE ID number:

CE 0085 AR 0130

Calculating approximate heat


demand:

As the case with other heaters, it is always advisable to calculate the heat demand to DIN
4701 exactly when dimensioning indirectly fired air heaters. The heat demand can be approximated with the aid of the diagram below.

Heat demand per 1000 m [kW]

Indoor
temp.

Enclosed space in m x 100

Structure:

Exterior walls: 25 cm masonry or equivalent


Roofing: lightweight concrete or equivalent
Heating in recirculating-air mode

Correction factors:
Add:

Deduct:

For corrugated roffing, not insulated

+ 40 %

For corrugated roofing, thin insulation (20 mm)

+ 20 %

For wooden roof with tar-paper or sheet metal

+ 20 %

For metal exterior wall, not insulated

+ 20 %

For extremely narrow buildings

+ 20 %

For large windows in exterior wall

+ 10 %

For exterior wall 75 % adjoining another building

- 15 %

For exterior wall 50 % adjoining another building

- 10 %

For exterior wall without windows, solid brick

- 30 %

For heated upper storey

- 30 %

For heated annex on each side

- 10 %

Dimensions / Weights WS/WO


WS with fan

vertical

horizontal

vertical

horizontal

WO without fan

Technical data

WS/WO
External dimensions

L mm
B mm
HS mm
HO mm
Air inlet
ES mm
F mm
R mm
U mm
D mm
Air outlet
F mm
T mm
Fire tube
Length appr.
mm
mm
NS mm
NO mm
O mm
Burner connection
J mm
MS mm
MO mm
O mm
Lifting lugs
G mm
KS mm
K1 mm
KO mm
Burner
Tube max. length
mm
Tube min. length
mm
Nozz. spray angie

Weight
WS
kg
WO
kg

40
630
630
1260
800
380
550
40
40
550
550
550
97
1480
1075
615
315
151
715
255
315
600
1230
770
105
70
60
130
90

63
800
700
1410
910
420
620
40
40
720
620
720
92
178
1250
750
350
151
743
243
350
770
1380
880
135
100
60
190
130

100
1100
730
1730
1100
550
650
40
40
1020
650
1020
101
178
1483
853
365
151
945
315
365
1070
1700
1070
170
120
60
240
170

160
1250
910
1950
1250
580
790
60
60
1130
790
1130
88
195
1754
1054
455
186
1029
329
455
1210
1910
1250
1210
210
150
60
400
270

250
1600
1090
2510
1600
790
970
60
60
1480
970
1480
140
245
2250
1340
545
186
1311
401
545
1560
2470
1600
1560
225
150
60
650
400

400
1600
1090
2630
1600
910
970
60
60
1480
970
1480
190
345
2370
1340
545
265
1431
401
545
225
150
60
770
450
3

Type selection WS/WO


Ex. air temp.
-air temp.

Air flow 20C

Ex. air temp.


-air temp.

Air flow 20C

Ex. air temp.


-air temp.

40-1
-2
-3
63-1
-2
-3
100-1
-2
-3
160-1
-2
-3
250-1
-2
-3
-4
400-1
-2
-3

Air flow 20C

WS /
WO

Operating point I Operating point II Operating point III


for fresh air
for mixed air
for recirculated air
approx. 60K
approx. 50 K
approx. 40 K

Heating
capacity

Type

Q
[kW]
20
25
32
32
40
50
50
63
80
80
100
125
130
160
200
250
200
250
320

VI
[m/h]
1000
1250
1600
1600
2000
2500
2500
3200
1600
4000
5000
6300
6300
8000
10000
12500
10000
10000
16000

tA
[K]
176
202
241
190
210
250
190
218
248
220
245
260
193
210
235
252
235
252
252

V II
[m/h]
1250
1600
2000
2000
2500
3200
3200
4000
5000
5000
6300
8000
8000
10000
12500
16000
12500
16000
25000

tA
[K]
167
191
226
176
200
236
175
200
225
206
230
235
178
194
214
236
214
236
240

V III
[m/h]
2000
2500
2500
3200
4000
5000
6300
6300
8000
10000
10000
12500
16000
16000
20000
25000

tA
[K]
178
212
169
190
229
175
210
193
210
220
165
180
195
195
212
221

These air flows are not suitable for fresh air opertaion.

Note:

Flue gas mass flow rate


(kg/h)

Required
boiler draught
with / without
turbulator
[Pa]
3
4
7
4
5
9
5
6
9
4
6
10
4
6
13
17
8
12
18

Heating Natural Natural Liqefied


oil
gas
gas
gas
Flue gas
EL
E
LL
pipe
CO2
13 %
33
42
54
54
67
84
84
105
134
134
167
209
222
267
334
417
334
417
534

CO2
CO2
CO2
9,5 %
9%
11 %
not permissible
45
46
43
57
59
55
not permissible
71
74
69
89
93
86
89
93
86
112
117
108
142
148
137
142
148
137
178
185
172
222
231
214
235
245
227
285
296
274
356
370
343
445
462
429
356
370
343
445
462
429
569
591
549

T: Delivery with turbulator

Maximum suction temperature for WS 40 C


Minimum discharge temperature for WS/WO 40 C
Minimum waste gas temperature in accordance with DIN 4794: 160 C

[mm]
148

178

178

195

245

345

Drive / Sound pressure level for WS


Unit resistance for WO

WS Motor capacity, Fan speed, Sound pressure level


External pressure
Air
Type
volume
m/h
WS 40
1 000
1-3
1 250
1 600
2 000
2 500
WS 63
1 600
1-3
2 000
2 500
3 200
4 000
WS 100
2 500
1-3
3 200
4 000
5 000
6 300
WS 160
4 000
1-3
5 000
6 300
8 000
10 000
WS 250
6 300
1-4
8 000
10 000
12 500
16 000
WS 400
10 000
1-3
12 500
14 000
16 000
18 000
20 000
25 000

free discharge
up to 25 Pa
Lp
Motor Venti
dBA
kW
min-1
0,37-1
49
0,37-1
50
0,37-2
51
0,37-2
52
0,37-3
53

0,55-1
0,55-3
0,55-3
0,37
0,37
0,55
1,1
2,2
0,37
0,55
1,1
1,5
3,0
0,55
1,1
1,5
2,2
5,5
1,5
2,2
2,2
3,0
4,0
5,5
11

490
680
770
1000
1260
435
560
620
800
900
360
400
500
570
800
285
330
410
460
530
580
735

47
49
50
55
58
64
67
69
54
54
58
64
67
61
62
63
64
66
67
68
69
69
70
70
72

Motor
kW
0,37-1
0,37-1
0,37-2
0,37-3
0,37-3

50 Pa
Venti
min-1

0,55-1
0,55-2
0,37
0,37
0,75
1,1
2,2
0,37
0,55
1,1
2,2
3,0
0,55
1,1
1,5
2,2
5,5
1,5
2,2
3,0
3,0
4,0
5,5
11

Lp
dBA
50
51
52
53
55

Motor
kW
0,37-1
0,37-2
0,37-2
0,37-3
0,37-3

100 Pa
Venti
min-1

55
58
64
67
70
54
55
58
64
68
62
63
65
66
67
67
68
69
70
70
71
73

Motor
kW
0,37-1
0,37-2
0,37-2
0,37-3

200 Pa
Venti
min-1

Lp
dBA
56
57
58
59

Motor
kW
0,37-3
0,37-3
0,37-3

300 Pa
Venti
min-1

Lp Motor
dBA kW
57
58
59

0,55-1
53 0,55-2
54 0,55-3
55

0,55-1
52 0,55-2
53 0,55-3

49 0,55-1
51 0,55-2
610
770
900
1000
1400
490
560
700
880
1010
410
450
550
570
870
330
410
460
515
560
640
740

Lp
dBA
52
53
54
59
60

400 Pa
Venti
min-1

54 0,55-3
55 0,55-3
56

Lp
dBA

56
57

0,37
0,55
0,75
1,5

770
880
900
1260

55
59
65
69

0,37
0,55
1,1
1,5

770
880
1120
1260

57
61
66
69

0,55
0,75
1,5
2,2

1000
1120
1260
1430

60
64
66
70

0,75
1,1
1,5
2,2

1120
1410
1420
1430

63
66
67
70

0,55
0,75
1,5
2,2

610
690
800
900

55
57
60
65

0,75
1,1
1,5
2,2

690
800
900
1010

57
62
63
66

1,1
1,5
2,2
3,0

810
910
980
1145

61
64
65
67

1,1
2,2
2,2
3,0

810
1010
1010
1250

64
67
67
68

0,75
1,1
1,5
3,0
5,5
2,2
2,2
3,0
4,0
5,5
5,5
11

500
555
550
710
870
410
460
510
570
600
640
740

65
66
66
67
68
68
69
70
70
71
71
73

1,1
1,5
2,2
3,0
5,5
2,2
3,0
4,0
4,0
5,5
7,5

625
635
715
800
870
510
570
570
635
660
720

67
68
69
70
71
69
70
71
71
72
72

1,5
2,2
3,0
5,5

720
720
800
800

69
70
70
71

1,5
2,2
3,0
5,5

720
800
800
925

70
71
72
73

3,0
4,0
4,0
5,5
7,5
7,5

575
640
650
720
720
730

70
71
71
72
72
73

3,0
4,0
5,5
5,5
7,5
11

640
715
715
720
760
830

70
71
71
72
73
74

WS 40 and WS 63: Operating points are achieved through switch board or by connection to one of the motor steps
Sound pressure level in dB(A) at 2 m distance with free air inlet/outlet.

-1), -2), -3)

The air volume is reduced by about 17 % in the case of duct air filters or 2 filter frames;
suction with filter frame is not permissible!

Unit resistance (Pa)

WO Unit resistance
with flow across
the whole cross section

Air volume at inlet 20C (m/h x 1000)

Fitting options of accessories WS


demonstrated on a vertical unit
21

22

23

H
L

12
13
14

15
16
17

20

24

25
26

18

8
2
8

L
V
11

19

10
9
4
3
2
6
5
7

right

left

top
bottom

front

back

right

left

top
bottom

Warm air heater WS - vertical / horizontal


Air inlet
2 Dummy plate
3 Air intake grille
4 / 5 Duct connection frame
6 Dummy plate
7 Air intake grille
8 Slide-in filter with mat and inspection door
9 Filter frame with mat
10 Duct air filter with mat
11 Damper
Air outlet
12 Air outlet hood
with 2 grilles
13
with 3 grilles
14
with 4 grilles
15 Duct connection hood
broad side
16
narrow side
17 Duct connection frame
Other accessories
18 Set of brackets for horizontal appliance
19 Combustion air intake hood
(switch board at the fronst is not possible)
- Set of lifting lugs for horizontal appliance WS 40 to WS 250
- Cleaning brush
Smoke tubes
20 Smoke tube branche
21 Smoke tube rain protection hood
22 Smoke tube 1000 mm length, pluggable up to WS 250
23 Smoke tube sleeve for WS 400
24 Smoke tube bend 90C with soot door
Electrical accessories
25 Double and safety thermostat
26 Switch board fitted below double and safety thermostat
For any further accessories see Chapter Accessories.

back

WS 100-400

front

WS 40/63

F
F
F
F

B
B
B

R
R
R

L
L
L

Bo
Bo
Bo
-

B
B
B
B
B

R
R
R
R
R

L
L
L
L
L

Bo
Bo
Bo
-

F
F
-

B
-

R
R
-

L
L
-

Bo

F
F
-

B
-

R
R
-

L
L
-

Fitting options of accessories WO


demonstrated on a vertical unit
21

22

23

H
L

R
V

20

15
16
17
1

24

25
26

12
13
14

18

8
2

8
3

L
V
11

19

10
9
4
3
2
6
5
7

10
11
12
13
14
15
16

top
bottom

4
5
6
7
8
9

left

2
3

Warm air heater WS - vertical / horizontal


Air inlet
Dummy plate
Duct connection frame
Air outlet
Air outlet hood
with 2 grilles

with 3 grilles

with 4 grilles
Duct connection hood
broad side

narrow side
Duct connection frame
Other accessories
Combustion air intake hood
Set of lifting lugs for horizontal appliance WS 40 to WS 250
Cleaning brush
Smoke tubes
Smoke tube branche
Smoke tube rain protection hood
Smoke tube 1000 mm length, pluggable up to WS 250
Smoke tube sleeve for WS 400
Smoke tube bend 90C with soot door
Smoke tube insulation (on inquiry)
Electrical accessories
Double and safety thermostat
For any further accessories see chapter accessories.

right

front

WO 40-400

Bo

F
F
-

R
R
-

L
L
-

Accessories - Dimensons WS/WO


Duct connction frame

air inlet lateral/at the rear

WS/WO 40
F
530
E
360
Z
30
H
26
appr. kg
2

63
600
400
30
26
2,5

100
630
530
30
26
2,5

Duct connction frame

air inlet at the bottom

WS/WO 40
F
530
D
530
Z
30
H
26
appr. kg
2

63
600
700
30
26
2,5

100 160 250 400


630 770 950 950
1000 11110 1460 1460
30
30
30
30
26
26
26
26
3,5
4
5
5

clear width clear width -

160
770
560
30
26
3

250
950
770
30
26
3,5

400
950
890
30
26
3,5

Spare filter mats for slide-in and frame filters

WS/WO 40
63
length 1220 1380
height 650 820

100
720
620

160
880
670

250 400
1060 1060
880 1000

Duct air filters with filter mat

WS/WO
E
F
T
Z
appr. kg

40
-

63
-

100
550
650
300
40
30

160
580
790
340
60
50

250
790
970
340
60
65

Spare filter mat for duct air filter

WS/WO
length
height

40
-

63
-

100 160 250 400


1880 2290 3020 3020
535 590 810 925

Damper

WS/WO 40
F
530
E
360
T
120
Z
26
appr. kg
5

63
600
400
120
26
7

100
630
530
120
26
8

WS/WO 40
L
630
B
630
H
200
appr. kg 17

63
800
700
200
22

100 160 250 400


1100 1250 1600 1600
730 910 1090 1090
300 300 420 420
32
53
57
57

Air outlet hood



with 2 grilles
with 3 grilles narrow and/or
with 4 grilles broad side
Grille with
adjustable blades

160
770
560
120
26
13

250
950
770
120
26
15

400
910
970
340
60
72

400
950
890
120
26
23

Accessories - Dimensons WS/WO


Duct connction hood

broad side

WS/WO
L
B
H
E
F
appr. kg

40
630
630
300
220
550
20

63
800
700
300
220
720
24

100 160 250 400


1100 1250 1600 1600
730 910 1090 1090
300 300 420 420
220 180 300 300
1020 1130 1480 1480
32
53
57
57

Duct connction hood

narrow side

WS/WO
L
B
H
E
F
appr. kg

40
630
630
300
220
550
20

63
800
700
300
220
620
24

100 160 250 400


1100 1250 1600 1600
730 910 1090 1090
400 500 700 700
320 380 580 580
650 790 970 970
40
70
90
90

Duct connction frame

air outlet

WS/WO 40
F
530
D
530
Z
30
H
26
appr. kg
2

63
600
700
30
26
2,5

100
630
1000
30
26
3,5

Bracket

Combustion air intake hood


B

250
-

Combustion air intake left or


right, interchangeable

WS/WO
B
L
H
N
O
K
appr. kg

40
630
460
630
315
25
229
33

63
630
460
630
315
25
229
33

100
630
460
630
315
25
229
33

160
800
630
800
270
30
322
45

250 400
1000 100
830 830
1000 1000
300 300
30
30
404 404
68
68

with soot collector

WS/WO
H
T
Z
internal
d
external
D
appr. kg

40
540
300
215

63
590
340
250

100
590
340
250

160
700
400
300

250
900
510
390

400
1080
690
390

150

180

180

200

250

350

146
15

179
18

179
18

199
21

249
29

349
48

O
N
K
L

Burner plate

250 400
950 950
1460 1460
30
30
26
26
5
5

WS/WO 40
63 100 160
D
1300 1450 1650 2000
S
500 500 800 1000
M
450 450 740 900
U
50
50
60
80
K
14
14
14
18
appr. kg 16
18
21
60
(set)

Smoke tube branch

160
770
1110
30
26
4

bored

WS/WO

40/63/100
40/63/100
160/250/400
160/250/400
160/250/400

120
130
130
150
150

150
170
150
170
200

M8
M8
M8
M8
M10

210
210
320
320
320

210
210
320
320
320

400
-

plate
type
A
B
C
D
E

Accessories - Control elements WS/WO


Double and safety thermostat
fitted

2 capillaries 350 mm length for fan, burner and burner safety control with restart locking
divice.
Breaking capacity: 15 A, 230 V, 50 Hz

Terminal box fitted


(for WS 40-400)

for connection of the double and safety thermostat as well as the fan to the terminal box

Room thermostat

in plastic casing for on-surface installation.


Breaking capacity: 10 A at 230 V, 50 Hz, thermal return.
Temperature range + 5 to + 30 C, switch temperature difference 0,5 C.

Room thermostat
industrial version

in plastic casing 150 x 110 x 72 mm for on-surface installation.


Switching capacity 16(4) A at 230 V / 50 Hz
Temperature range 0 - 40 C
Switching differential 0,75 K
Degree of saturation IP 54
Part. No. 27 35 300

Room thermostat clock

Plastic housing, 132 x 82 x 32 mm for socket installation,


daytime and night-time temperatures can be set separately.
Temperature decrease adjustable 2 - 10 K
Switching capacity: 10(4) A at 230 V / 50 Hz
Temperature range 5 - 40 C
Switching differential 0,1 - 3 K
Degree of protection IP 20
Part.No. 27 44 079

Time switch daily and weekly


programm and power reserve

for installation in switch board.


Breaking capacity: 16 A at 230 V, 50 Hz.

Hours run meter


for installation in switch board.

in plastic case, front frame 48 x 48 mm


five-digit meter.
Connection: 230 V, 50 Hz

Servomotor

to control fresh air or return air damper open/shut.


Connection: 230 V, 50 Hz.

10

Switch board WS
Switch board

- Terminal box for single speed function of WS 40 and WS 63


- 3-speed with summer-off-winter switch for WS 40-63
- single-speed with summer-off-winter switch for WS 100-400
- 2-speed with summer-off-winter switch and speed selection switch for WS 100-400
(incl. control for burner 2-stage)

Technical data

Switch board
Type
kW
0,37
WS 40 3-speed
0,55
WS 63 3-speed
0,37
0,55
WS 100-400
0,75
single-speed
1,1
1,5
2,2
3,0
4,0
5,5
7,5
11,0
0,37/0,11
WS 100-400
0,50/0,15
2-speed
separate winding 0,75/0,27
1500/1000 min-1 1,00/0,30
1,50/0,50
2,00/0,70
3,00/0,90
3,80/1,14
5,00/1,70
7,20/2,50
9,00/3,00
0,30/0,06
WS 100-400
0,50/0,10
2-speed
0,70/0,15
Dahlander
1,00/0,22
1500/750 min-1
1,40/0,33
2,00/0,45
2,40/0,55
3,60/0,90
5,00 /1,40
6,10/1,40
9,00/2,20

Switch board accessories:

V/Hz
230/50
230/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50
400/50

direct
A
3,0
6,7
1,15
1,5
1,95
2,8
3,7
5,1
6,8
9,0
11,7
15,6
22,4
1,45/0,65
1,75/0,78
2,70/160
3,40/1,75
4,40/2,40
6,00/3,10
7,50/3,40
1,20/0,54
1,80/0,75
2,35/1,00
3,10/1,40
4,20/2,00
5,30/2,50
6,50/3,00
-

Starting mode
Y-
delayed
A
A
5,2
6,8
9,1
13,0
9,8/4,3
13,5/6,0
18,0/7,9
23,0/9,7
9,70/4,7
12,70/7,5
16,00/7,5
20,50/10,3

Built-in hours run meter


Built-in time switch with daily and weekly program and power reserve
Design for threephase current burner up to 2,2 kW (WS 160-400)
Control for servomotor open/shut

fuse
A
10
16
4
6
6
10
10
16
16
20
20
25
35
6
6
10
10
10
10
16
16
20
25
35
6
10
10
16
16
16
16
16
20
25
35

11

Special design WS/WO


Dismountable units

General:
All dismountable warm air heaters are assembled and then dissassembled in the factory.
Each component is marked to facilitate assembly on site. The casing panels are delivered
together with the necessary bolts.

2 components - on extra price

several compon. - on extra price

WS/WO 40-63
Fan section complete
Upper section not split up
Heating furnace not split up

WS/WO 40-63
Fan section complete
Upper section split up
Heating furnace not split up

WS/WO 100-400
Fan section complete
Upper section with built in heating furnace

WS/WO 100-400
Fan section complete
Upper section split up in the middle
Heating furnace not split up

C
H2

D
H1

H1

Dimensions

WS/WO
External casing

Heating furnace

Weight heating furnace

L mm
B mm
H1 mm
H2 mm
C mm
D mm
E mm
Kg

40
630
630
460
800
777
539

63
800
700
500
910
932
615

100
1100
730
630
1100
1243
638

160
1250
910
700
1250
1388
790

250
1600
1090
910
1600
1755
1004

400
1600
1090
1030
1600
1825
1004

722
50

870
75

925
100

1105
170

1410
330

1410
340

Further dismountable parts:


E.g. heating furnace split up, on inquiry and on extra price.
Assembly:
Install fan section vertically and without torsion, attach heat insulation at the bores
using screws, fix panels ai rtight at the bores using screws.

12

Note WS/WO
Thermostats

for burner control:


Warm air heaters may only be operated with 2 thermostats which switch off the burner
independently.
One thermostat is constructed as monitoring device and the other as safety thermostat with
restart locking device.
for fan control:
After the burner has been switched off, the fan must continue operation until the combustion
chamber has cooled down sufficiently.
Warm air heaters by Wolf fulfill both requirements by means of double and safety thermostats.

Smoke tubes

If smoke tubes are used as steel chimneys, they are subject to approval of the respective
building authorities.

Combustion air intake hood

In special cases, the combustion air must be taken in from outside via an airtight duct
system.
e. g.: in car repair workshops or if the pressure between combustion chamber and installation room differs significantly.
The installations of warm air heaters in garages is only allowed for fresh air operation
(recirculated air operation is not permitted).
Be sure to observe regulations for garages!

Gas-fired units

All types and sizes of units included in this list can also be operated with natural and liquid
petroleum gas. The maximum load may not exceed that of oil-fired units.
The flame image, i. e. the combustion nucleus must have characteristics similar to those of
an oil burner with a 60 nozzle.

13

Assembly/Commissioning - Maintenance
WS/WO

Installation

In accordance with the valid local and general directives on warm air heaters and
the directives of the Brandversicherungskammer.

Foundation

Mglichst auf Betonsockel (Hhe 100-150 mm). Bei betoniertem Boden direkt auf dem
Boden mglich.

Space required

For the installation and possibly exchange of


a) fans with drive
front or right or left
b) thermostats
left or right
c) switch board
left or right
d) burner
front
Cleaning of heating compartments back and front

Flue gas guidance

Horizontal flue gas guidance as short as possible. Observe wall thickness and insulation.

Double and safety thermostat

If the thermostat was not installed and adjusted at the factory, fix to the casing with
bolts at the holes punched out laterally.
The sensor shall be positioned at least 40 mm in air direction behind the heating compartments.
The thermostat shall be adjusted so that: Fan on at 40 C

Fan off at 35 C

Burner off at max. BO C
The safety thermostat shall be adjusted so that it will turn off the burner at 100 C and
will be locked by a restart locking device.

Tasks before starting operation

Tighten bolts, in case they were loosened during transport.


Check V-belt tension, tighten if necessary.
Check direction and axial alignment of fan rotor.
Open air intake and air outlet dampers.
Check oil reserve, control gas pressure, open shut-off valves.
Screw in fuses for burner and fan motor.
Observe operating instructions of the manufacturer of burner and air suction fan.

Controls after starting operation

Check current consumption of the fan motor(s). It must not exceed the rated current as
specified on motor name plate. Adjust overcurrent relay accordingly and carry out operation test by taking out a fuse (only necessary for threephase current).
Measure chimney draught. Perform flue gas analysis.
Attention: Depending on the type of construction of the chimney, the flue gas temperature
must be adjusted so as to prevent damage. Minimum flue gas temperature in accordance
with DIN 4794: 1600 C.
Check sealing of the casing panels, tighten screws if necessary.
Check air volume in units with duct connection.
Switch off warm air heater only via room thermostat or control switch of the burner. Fan
will continue operation for some time and is turned off automatically after the heating
furnace has cooled down. Only then can the main electricity supply be turned off.

Maintenance

Cleaning of the heating furnace:


In the case of oil-fired appliances, at the end of each heating season, if possible, or with the
appearance of a soot layer.
In the case of gas-fired appliances, at intervals of several years.
Cleaning apertures become accessible by taking off front and rear insulating panels.
Seal apertures tightly after cleaning.
Casing, suction grille, discharge grille, fan casing and fan rotor must be cleaned at least
once a year. (Do not use corrosive agents!)
V-belt must be tightened several times during the first year of operation.

14

Wolf GmbH, Postfach 1380, D-84048 Mainburg, Tel.: 087 51 / 74-0, Fax: 087 51 / 74-1600, Internet: www.wolf-heiztechnik.de
Offer/Order No.
Company:

Air outlet

Air inlet

Basic unit

Warm air heater

horizontal
horizontal
vertical
left
right
G = grille
H = hood
o = open
F = filter
F = frame
P = plate
D = damper
Duct connection frame
Slide-in filter with mat and inspection door
Duct air filter with mat
Damper
Manual lever with lock
Filter frame with mat
Dummy plate bottom
Duct connection hood
Air outlet hood
Duct connection hood

Pos.:

Pieces

collective transport
by rail-express
by rail-part load
forwarding agency
collection
Price
Total price

with grille.....................................

Smoke tubes

Set of brackets for horizontal design


Explosion-proof hood as burner casing
Set of lifting lugs for horizontal design
Turbulator

Double and safety thermostat, fitted


Terminal box, fitted
Room thermostat
Room thermostat with on/off switch
Room thermostat clock with daily and weekly programm
Servomotor 230 V open/shut, fitted

Switch board

Ex warehouse

Advide note tel..


Type
Heating cap. (kW) Air vol. (m/h)
ext. Pr (Pa)
........................../.......................................... /........................................../............................../
Motor ......................................V
kW

..................................... A
min-1
Fan
min-1
Motor pulley
Bg.
mm
Fan pulley
Bg.
mm
V-belt length
mm
front back right
left
top bottom
Air inlet
Air outlet

Smoke tube branch with soot collector


Smoke tube rain protection hood
Smoke tube 1000 mm length, pluggable up to WSIWO 250
Smoke tube sleeve from WSIWO 400 on
Smoke tube bend 90 with soot door

Assembly

Date of delivery:
Date of order:
Order No.:
Comm.:
Employee:
Address of delivery:

Electric fittings

Other acces.

Customer No.:

Switch board
Type................................................

with hours run meter

with contactor control for threephase current burner/ampere...................

with time switch with daily/weekly program and power reserve

with actuator control
Wiring complete
Burner plate type
A B C D E
Burner plate special design
Bumer assembly with wiring
Terms of payment:

Total

Other:

Place:
Date:
Check the appropriate boxes of fill in the space provided referred view on the burner

ex factory unpacked
freight / packaging
Total
Signature:

15

Specification
Pos.

Pieces

Single price

Total price

WS 40-63

Warm air heaters by Wolf for oil, natural and liquid petroleum gas, as vertical or horizontal unit.
Heating furnace partially consists of alloyed, heat resistant steel. Cleaning apertures are accessible
from the burner and the smoke tube side. Inspection door is positioned above the burner opening.
External casing consists of galvanized sheet steel with heat insulation.
With fitted double inlet radial fan. Fan has a particularly low noise level, impeller is balanced statically
and dynamically and fitted onto a vibrationfree motor.
Heating capacity
kW....................................
Air volume
m/h.................................
Additional pressure
Pa......................................
Motor capacity
kW....................................
Voltage V........................................
Manufacture Wolf
Type
..........................................

Safety and double thermostat


Terminal box
Switch board , 3-stage, fan operation
Wiring complete
.....................................................................

WS 100-400

Warm air heaters by Wolf for oil, natural and liquid petroleum gas, as vertical or horizontal unit.
Heating furnace partially consists of alloyed, heat resistant steel. Cleaning apertures are accessible
from the burner and the smoke tube side. Inspection door is positioned above the burner opening.
External casing consists of galvanized sheet steel with heat insulation.
With fitted, double inlet radial fan, impeller statically and dynamically balanced, shaft with strong
roller bearing. Motor equipped with tension spindle, drive via pulleys and V-belts.
Heating capacity
kW....................................
Air volume
m/h.................................
Additional pressure
Pa......................................
Motor capacity
kW....................................
Voltage V........................................
Manufacture Wolf
Type
..........................................

Safety and double thermostat


Switch board
Wiring complete
.....................................................................
.....................................................................

W0 40-400

Warm air heaters by Wolf for oil, natural and liquid petroleum gas, as vertical or horizontal unit.
Heating furnace partially consists of alloyed, heat resistant steel. Cleaning apertures are accessible
from the burner and the smoke tube side. Inspection door is positioned above the burner opening.
External casing consists of galvanized sheet steel with heat insulation.
Safety and double thermostat
.....................................................................
.....................................................................

Wolf
GmbH, PO Box 1380, D-84048 Mainburg, Tel.: 087 51 / 74-0, Fax: 087 51 / 74-1600, Internet: www.wolf-heiztechnik.de
16
Part no. 48 00 204

201304
GB
Subject to technical modifications

Heating capacity
kW....................................
Air volume
m/h.................................
Unit ressistance
Pa......................................
Manufacture Wolf
Type
.........................................