Você está na página 1de 6

Clearing Up Neutral-to-Ground Voltage Confusion

Because effects from N-G voltage can range from nonexistent to significant, you
must learn to identify true common-mode events
Feb 1, 2007Tom Shaughnessy, PowerCET | Electrical Construction and Maintenance

Power quality questions continue to revolve around one underlying issue related to
electronic equipment: its ability to withstand the effects of electrical interference. If
equipment sensitivity was always well known and defined, then we would have few,
if any, doubts. In this perfect world, we would also know with a high degree of
certainty that a voltage sag of a known amplitude and duration would have either
no effect or a significant impact on equipment. Unfortunately, we seldom are privy
to such information. Therefore, the possible effects of neutral-to-ground (N-G)
voltage are often left up in the air.
When you measure N-G voltage, the measurement yields a simple voltage
differential, which a voltage potential on either the neutral conductor or grounding
conductor may create. Furthermore, this differential may be a simple by-product of
neutral return current or may even be part of a complex common-mode voltage
signal. The effects of these conditions vary greatly.
The simple question What is the effect of N-G voltage? isn't so simple
because it depends upon the magnitude, mode of propagation, timing,
energy/frequency content, and sensitivity of the equipment involved. Let's try to
resolve this important and confusing question.

Voltage drop and the NEC

<b>Fig. 1.</b> Basic single-phase circuit and load. As the load draws current, a voltage drop develops
across the supply and return conductors. N-G voltage measurements at the load will reflect the voltage
drop across the return (neutral) conductor.

Figure 1 shows a simple diagram of a single-phase load connected to a voltage


source. As the load draws current, a voltage drop develops across the supply and
return conductors. N-G voltage measurements at the load will reflect the voltage
drop across the return (neutral) conductor.
The National Electrical Code, in Sec. 210.19(A), FPN No.4, states: Conductors for
branch circuits as defined in Art. 100, sized to prevent a voltage drop exceeding 3%
at the farthest outlet of power, heating, and lighting loads, or combination of such
loads, and where the maximum total voltage drop on both feeders and branch
circuits to the farthest outlet does not exceed 5%, provide reasonable efficiency of
operation. This amounts to a 6V drop in a 120V branch-circuit home run.
Assuming equal losses in the supply and return conductors, then you should see an
N-G voltage of 3V, which is a realistic condition.

Origins of required low N-G voltages


Some equipment installation specifications list extremely small values for
acceptable N-G voltage, such as 0.5V to 1.0V. To meet these stringent requirements,
you would usually install a dedicated transformer at the load, and/or run large gage
wiring directly from the source N-G bond to the load.
Where did these extremely tight N-G voltage specifications come from? There could
be a bit of hyperbole in these specifications, but there are some realistic origins. For
instance, in the early 1980s, some equipment manufacturers installed power supply
and motherboard grounding in configurations that made them extremely
susceptible to earth/ground-referenced offset. In response, a few surge suppressor
manufacturers introduced TVSS products with N-G components and extremely low
transient voltage clamping levels with disastrous consequences in certain cases.
However, over time those design deficiencies were corrected present-day test
requirements usually prevent the wide-scale introduction of such products.

Figure 2 shows the basic diagram of a power supply system. What possible effect
could neutral return losses have upon a system with this configuration? After all,
there are no ground-referenced components on the input to the power supply that a
voltage potential on the neutral conductor could upset. In fact, UL power supply
tests reverse the polarity of voltages applied to a power supply. Consequently, the
power supply must withstand 120V with respect to earth/ground for both normal
and reverse polarities.
The voltage sensing and feedback circuitry also must meet electrical isolation
requirements for safety purposes. The bond between the grounding of the system
and the electronics occurs on the secondary of the high-frequency transformer
inside the power supply or system. If the system is well designed, the effects of lowfrequency voltage potentials appearing on the neutral conductor should have no
adverse effects. In fact, if a power supply has a switched input capability (e.g.,
85VAC to 264VAC), how could any simple N-G potential cause a problem? For
example, suppose the power supply operates from a 208VAC source. Then each
conductor on the input (L1 and L2) will have a 120V potential with respect to
ground.

Determining equipment sensitivity to N-G voltages


Tests performed in the past by PowerCET, Santa Clara, Calif., to determine
sensitivity of equipment to the effects of N-G voltage have never established any
consistent results. In one series of tests, the staff deliberately created N-G voltages
at the input to a mainframe computer and found that N-G voltages as high as
30VAC created no adverse effects.
There are two system configurations that can make equipment very susceptible to
the effects of N-G potential:

If the voltage sensing circuitry on the output of the power supply is


referenced to the chassis of the equipment, but the bond from the DC return to the
chassis is absent, then any small amount of earth/ground-referenced offset
potential may appear as DC bus fluctuation, resulting in equipment malfunction.

A more common problem develops when the power supply and circuit
boards are floated (no intentional connection to chassis), but the device has RS-232
circuitry with internal referencing to ground. Earth/ground-referenced offset
potentials may then cause erratic data transfer. Also, large common-mode
potentials can degrade or damage the chip. The latter problem appears more
frequently at printers and ancillary equipment.

While the industry has focused much attention on power frequency voltages
measured with a voltmeter and involving N-G voltages, a much larger problem
arises when you consider higher frequency N-G voltages that require measurement
with better instrumentation. This poses realistic performance challenges for
electronic equipment.

<b>Fig. 3.</b> Example of true common-mode interference recorded with a power monitor.

Figure 3 shows an example of true common-mode interference, which was


recorded with a power monitor. The red trace is line-to-ground (L-G), and the blue
trace is N-G. The earth/ground-referenced potential is common to both currentcarrying conductors, and the only path for this interference is through
earth/ground-referenced circuitry within equipment powered from that circuit. The
common-mode potential is only about 50V to 70V, but the frequency content of this
potential is fairly high (approximately 20kHz). The negative effects of these
interference signals can range from power supply reset to damaged I/O ports (RS232).
Figure 4 shows another example of a form of true common-mode interference
signal. Here, PowerCET recorded L-N and N-G voltages with a line decoupler and
recorded the resulting current signals in Ethernet cabling with Channels 3 and 4
with high-frequency current probes. The common-mode interference signal drives
interference currents through the Ethernet and associated intersystem cabling.

<b>Fig. 4.</b> True common-mode interference affecting system networks. This signal drives
interference currents through the Ethernet and associated intersystem cabling systems.

If the staff was to measure only from neutral to ground, then the true commonmode nature of these signals would not be apparent. For instance, referring back to
Fig. 1, the impedance of the neutral conductor will support impulse propagation as
loads cycle on and off. The resulting transient voltages, however, are developed
from a relatively high impedance. Therefore, their potential to wreak havoc is
limited. In comparison, common-mode interference signals, as shown in Figs. 3 and
4, not only have more available paths through the system, but their energy and
frequency content may be higher.

<b>Fig. 5.</b> Ground current induced voltage. Current surging through the grounding system of a
facility caused this event.

What about current flowing through earth/ground that is measured as an N-G


signal?Figure 5 shows an event caused by current surging through the grounding
system of a facility. The N-G voltage waveform truncates at 40V peak because the

waveform exceeded the input range of the digital storage oscilloscope. However,
you can follow the slope of the lines and extrapolate that the peak voltage easily
reached and probably exceeded 100V! This event caused hard drive failures and
data loss.

Applying what we've learned


As many power monitor setups do not use L-G connections along with L-N and N-G
connections, you must ferret out true common-mode events. With sole usage of NG connections to detect common-mode events, you may develop a tendency to
ignore low amplitude N-G transients. After all, if recorded transients are always
present at a given level and you can determine no adverse effects, why waste
monitor memory recording those events? Increasing the monitor threshold to avoid
capturing lower level and commonly occurring N-G events may leave the true
common-mode events undetected.
We can sum up our experiences as follows:

N-G voltages less than 3V and developed at power frequencies seldom cause
adverse effects.

Low level N-G transients less than 25V peak and caused by load cycling
usually donot cause adverse effects. However, the potential for adverse effect
will increase as frequency content and amplitude increases.

Higher frequency, true common-mode events can cause adverse effects, but
you may not be able to detect or correctly identify their presence.

Measuring N-G voltages with a multimeter is a valid procedure, and the


measurements you make may help identify wiring problems that cause excessive
voltage drop. Remember, high levels of N-G voltage invariably arise from
grounding/bonding problems.

Você também pode gostar