Corrosion
In general there are two types of boilers, low pressure and high pressure:
A) Low pressure boilers will be found heating water or steam to be circulated around a building for heating
purposes via radiators. These systems are "closed circuit" types and require little or no "make" water to top
them up. Mostly low pressure boilers operate below 10 psi.
B) High pressure boilers will be found in industry, generating steam for a variety of uses, locomotion via a
steam engine, or for end use of steam in laundries, rubber product manufacturing, wood pulp products,
food manufacture etc. These boilers operate at over 10 psi and all require constant "make up" water as
some of the steam is used.
Boiler feedwater ("BFW") may either be the same as the makeup water, or may consist of returned steam
condensate, or (as in most cases) will be a mixture of both.
The relative amounts of makeup and condensate may vary. A typical figure is 5% makeup with 95%
condensate, but this depends on how the steam plant is operated and how much of the steam is
condensed and recovered for recirculation.
In order to be non-scaling, the BFW must be a softened or demineralised water . In order to be noncorrosive to the carbon-steel or low-alloy steel components from which boilers are usually constructed, the
water must be thoroughly deaerated. This is partially achieved by thermomechanical means (use of
deaeration heating tanks), while the last traces of dissolved oxygen are removed by chemical agents
("oxygen scavengers").
Oxygen scavengers include both volatile products (e.g., hydrazine, or other organic products like
carbohydrazine, hydroquinone, diethylhydroxyethanol, methylethylketoxime, etc.) and non-volatile salts
(normally: sodium sulphite, Na2SO3, or a derivative thereof). The latter salts often contain catalysing
compounds to increase of rate of reaction with dissolved oxygen (e.g., cobaltous chloride).
Oxygen Scavengers
While the oxygen scavenging salts tend to react rapidly with oxygen, even at lower temperatures, their
reaction products result in increased levels of total dissolved solids in the boiler feedwater.
To minimize this disadvantage, the salt should be fed to the storage tank of the deaerating heater and care
should be taken that no precipitates are introduced into the boiler feed.
As rule of thumb, one typically feeds 10 parts of sodium sulphite per part of oxygen (to compensate for
reaction with atmospheric oxygen and for impurities in the sodium sulphate).
Volatile oxygen scavengers are normally employed for higher pressure systems (e.g., above 1000 psig).
These materials may react directly with oxygen and or directly with carbon steel boiler surfaces to form
gamma iron oxide or magnetite. The formation of such "oxygen-impervious" oxide films precludes
excessive corrosion.
Except for the common hydrazine (N2H4), most other volatile organic oxygen scavengers are sold under
some proprietary name. The use of hydrazine in boiler feedwater is very common and very well
documented. Because hydrazine typically does not react with oxygen at a rapid rate at lower temperatures,
it may not be the preferred oxygen scavenger for low temperature boiler feedwater systems. In addition,
hydrazine is seriously toxic and great care should be taken in its handling. Food production sites should
consider seriously the potential consequences of using highly poisonous chemicals.
Scaling
As water is heated and converted into steam, contaminants brought into a boiler with makeup water are left
behind. The boiler functions as a distillation unit, taking pure water out as steam, and leaving behind
concentrated minerals and other contaminants in the boiler. Scale forms as a result of the precipitation of
normally soluble solids that become insoluble as temperature increases. Some examples of boiler scale are
calcium carbonate, calcium sulphate, and calcium silicate.
Corrosion
Corrosion is a general term that indicates the conversion of a metal into a soluble compound. In the case of
boiler metal, corrosion is the conversion of steel into rust. In a boiler, two types of corrosion are prevalent:
1.)
Oxygen pitting corrosion, seen on the tubes and in the preboiler section.
2.)
Corrosion of either type can lead to failure of critical parts of the boiler system, deposition of corrosion
products in critical heat exchange areas, and overall efficiency loss.
Carryover
Carryover is caused by either priming or foaming. Priming is the sudden violent eruption of boiler water,
which is carried along with steam out of the boiler, usually caused by mechanical conditions. Priming can
cause deposits in and around the main steam header valve in a short period of time. Foaming causes
carryover by forming a stable froth on the boiler water, which is then carried out with the steam. Over a
period of time, deposits due to foaming can completely plug a steam or condensate line.
Caustic Gouging
Caustic gouging occurs when NaOH concentrates under porous boiler water deposits. An example of such
deposition would be iron, which tends to be porous. Essentially, what occurs is that boiler water is present
in the deposit. As steam escapes, the NaOH concentration increases dramatically, dissolving the protective
magnetite and boiler tube metal.
In addition to the gouging of the boiler tubes you may also notice a white substance (sodium carbonate)
outlining the edges of the original deposit.
There are other failure mechanisms such as caustic and hydrogen embrittlement, stress corrosion cracking
and steam blanketing. In this tip we have dealt with those we feel are the most prevalent. If you believe that
you have a failure that does not fit into one of the categories we discussed please feel free to contact our
staff. Finally, for a complete analysis and understanding of a failure, a sample should be sent to an
independent metallurgical lab.