Escolar Documentos
Profissional Documentos
Cultura Documentos
a r t i c l e
i n f o
Article history:
Received 28 May 2012
Received in revised form 18 April 2013
Accepted 20 April 2013
Available online 2 May 2013
Keywords:
Air conditioning
Energy efciency
Refrigeration
a b s t r a c t
The factors that have inuence on the energy consumption of a small air conditioning system that are
worth mentioning are the efciencies of the compressor, evaporator and condenser, the form that the
refrigerant ow is controlled, the fan model used, and climatic conditions. Within the climate issue, an
interesting factor is that the relative humidity when it comes to the effect that it causes, especially in
the performance of the air condenser, which generally is not considered in the projects. This study aims
to evaluate the inuence of humidity on the coefcient of system performance (COP), seeking to quantify
their inuence when it happens. The tests were performed on a testing bench, mounted at the Laboratory
for Energy Efciency (LAMOTRIZ) UNESP-Campus Guaratinguet. In the study, the wet bulb temperature
was ranged, keeping the rotation of the scroll compressor with application of a frequency inverter in its
best performance. The test bench is provided with a supervisory system of data collection that is also able
to control all functions of the bench. In the results, there was a signicant inuence, particularly when
comparing high humidity conditions with low humidity, noting that only over 65% relative humidity is
that signicant changes are observed in the COP of the system.
2013 Elsevier Inc. All rights reserved.
1. Introduction
The importance of energy efciency is fundamental, be for the
world economy, or to avoid rationing of electricity and even blackouts, as occurred in 2001 in Brazil, and also to combat global
warming which is undoubtedly one of the biggest challenges of
this century.
According to the report of the United Nations (UNs) released in
Thailand [1], Brazil needs to perform three actions to contain global warming as: ending the illegal deforestation, investing in clean
energy sources like wind and solar, and apply techniques to reduce
the waste of electricity, or improve energy efciency.
The refrigeration is considered a branch of science which deals
with the processes of heat transfer and conservation to reduce the
temperature of a given volume control below the temperature of
the surroundings [2] and therefore falls within the activities that
allow reducing the energy consumption.
The applications of refrigeration can be divided into ve
categories:
(a) Domestic: covers the manufacture of small refrigerators and
freezers.
Corresponding author.
E-mail addresses: sobrinho@feg.unesp.br (P.M. Sobrinho), celso.tuna@feg.unesp.
br (C.E. Tuna).
0894-1777/$ - see front matter 2013 Elsevier Inc. All rights reserved.
http://dx.doi.org/10.1016/j.expthermusci.2013.04.013
(b) Commercial: covers the design, installation and maintenance of refrigerated facilities used in restaurants, hotels
and places of storage, display and processing of perishable
foods.
(c) Industrial: is varied and can be used in different industries
and manufacturing processes.
(d) Air conditioning: has as target to HVAC environments, aiming at the thermal comfort of its occupants.
(e) Refrigerated transport: includes temperature control in special vehicles.
An air conditioning system is a process that aims to control
simultaneously, in an enclosed environment, purity, humidity,
temperature and movement of the air. It is indispensable in
manufacturing processes that require the control of humidity,
temperature and air purity, such as the manufacture of
pharmaceuticals, color printing, operating environments with
ammable or toxics components, surgery rooms, in workplaces
in order to increase comfort and productivity, in residences,
among others.
In the early eighties, 81% of commercial buildings in the United
States appealed to the use of air conditioning systems to promote
thermal comfort. The estimated installed capacity was approximately 100 million tons of cooling. Of these, 95% use the operating
vapor compression cycle. In some regions of Brazil, air conditioning
accounts for 7% of electricity consumption in residential use. In
P.M. Sobrinho, C.E. Tuna / Experimental Thermal and Fluid Science 49 (2013) 152159
153
Nomenclature
COP
(dh)EVA
(dm/dt)
(dV/dt)
ER
g
he
hs
Hp
HVAC
n
p
Pel
Q
Q_ R
R
S
T
TR
V
These facts can be seen in Fig. 1 and 2 which show the variation
in temperature and relative humidity between a maximum and a
minimum during the year of 2012 in the city of Guaratinguet-SP
[5].
It is observed that the minimum relative humidity in the afternoon, come to be close to 20% in some seasons. During the night,
due to the decrease of temperature, relative humidity increases
to values close to 100%.
These observations indicate that there is a tendency of change
in behavior of the coefcient of performance (COP) of an air conditioning system, because since the conditions for heat exchange
vary, certainly the performance also suffers variation.
3. Refrigeration system by steam compression
The air conditioning by steam compression can be done by the
conditioning of the air through a system composed by a compressor, a condenser, an expansion valve or a capillary tube and an
evaporator.
The steam compression cycle is the most used in practice.
Among its main advantages is the possibility of equipment being
built in small volumes compared to other systems and their high
performance, known in literature as the coefcient of performance
(COP). Due to its portability and low cost is easily found in homes
and businesses.
Before an evaluation of the performance of a refrigeration cycle
can be done, efciency should be dened. However, the index is
not called efciency because this term is usually reserved to describe the ratio between the amount of energy obtained by the
amount of energy expended. This ratio can lead to misinterpretations if applied to a refrigeration system, since the outgoing energy
in the condenser, is generally lost. The concept of the performance
index of a refrigeration cycle is the same as the efciency in the
sense that it represents, as shown in the following equation:
COP
154
P.M. Sobrinho, C.E. Tuna / Experimental Thermal and Fluid Science 49 (2013) 152159
The performance of a refrigeration cycle is denominated coefcient of efcacy or coefcient of performance (COP) and is dened
by the following equation: [6].
COP
useful cooling
useful work
P.M. Sobrinho, C.E. Tuna / Experimental Thermal and Fluid Science 49 (2013) 152159
155
Fig. 3. Variation of the heat transfer coefcient inside a pipe where occurs complete
condensation of the overheated steam.
156
P.M. Sobrinho, C.E. Tuna / Experimental Thermal and Fluid Science 49 (2013) 152159
02 frequency inverters;
01 CLP:
01 meter multifunction, precision: 0.5%;
01 three-phase asynchronous motor 2 poles, 1 hp (1134 W),
220/380 V type high performance;
01 Fan, axial ow 5000 Nm3/h, pressure 24 mmCA, eight blades
distributed symmetrically, design pressure coefcient of 0.18,
about 0.43 cube, outside diameter of 350 mm and the tip clearance of 10 mm, driven directly by an electric motor;
01 differential pressure transducer, pressure range 0300 mm
H2O, accuracy: 0.5%;
P.M. Sobrinho, C.E. Tuna / Experimental Thermal and Fluid Science 49 (2013) 152159
Table 1
Experimental uncertainties (l).
Greatness
Atmospheric pressure
Cross sectional area of the workbench
Power of electric motors
Difference in air pressure
Differential pressure of the refrigerant
Air velocity
Airow
Flow rate of refrigerant
Air temperature
Refrigerant temperature
Specic mass of air
Specic mass of refrigerant
0.5 mmHg
0.0005 m2
3.5 W
0.09 mm H2O
0.09 psi
0.03 m/s
0.03 Nm3/s
0.012 Nm3/s
0.3 C
0.1 C
0.58 kg/m3
0.3 kg/m3
Table 2
Standard deviation (r), variance and average for the motor-fan.
r
S
X
4.2. Methodology
The electrical power, such as compressors and fans, are all directly measured by instruments previously described. The volumetric ow rate of refrigerant of the air conditioning system is
directly measured by a ow meter and the coefcient of performance (COP) of the cycle of vapor compression refrigeration is given by Eq. (3) [24].
ER
Q_ R
_
_
Wcomp:
Wcomp
COP
21.00
447.00
1185.00
0.29
0.08
25.00
1.58
2.50
1338.00
For the system studied, considering all the energy ows involved, the COP is given by Eq. (4) [25].
In the study, the wet bulb temperature was ranged, keeping the
rotation of the scroll compressor by applying a frequency inverter
in its best performance. All tests were performed under conditions
where they were kept constant barometric local pressure
(712 mmHg (95 kPa)), the dry bulb temperature of the air ranged
from 22 C to 27 C, and relative humidity in a range between
40% and 92%.
The air ow system, derived from an axial fan, was kept constant with the engine at 60 Hz, providing an average air ow of
1250 Nm3/h. The test bench is provided with supervisory system
(InduSoft) data collection capable of measuring up to 102 variables
four times per second. Fig. 3 shows the test bench which includes
the air conditioning installation.
4.1. Software used to control the supervisory system
All functions of the bench, even a simple command on and off,
to vary the speed of the engines, the opening of the damper, the
Table 3
Standard deviation (r), variance and average for scroll compressor.
S
X
157
System COP
Cycle COP
0.12
0.0143
2.35
0.82
0.6806
4.79
349.00
121783
1455.86
COP
ER
Q_ R
_
_
_
_
Wcomp: Wfan Wfan:cond: Wtotal
The cooling effect or thermal load, that is the ow of heat absorbed by the refrigerant is calculated from Eq. (5) [26].
ER
dm
dV
1 dV
dhEVA qref
hs he EVA
h h
dt
dt
t dt s e EVA
The variation of enthalpy of the refrigerant is obtained indirectly. For this purpose, measurements are made of temperature
and pressure of the uid before and after the evaporator and then
insert these data into a software called CATT3 (Computer Aided
Thermodynamic Table 3) or in thermodynamic tables to obtain
the values of specic enthalpy [26]. The temperatures and pressures were obtained by instruments described in Section 4.
The specic volume is also obtained in CATT3, analogously to
the enthalpy values.
The electrical power drive of the motor-fan can be expressed by
Eq. (6) [27]. This parameter was determined and compared with
the one that has been measured directly by the instruments of
the bench tests to estimate the total performance of all.
Pel
c Q DptmCar
gtotal
Dpt q g Hp q:
V2
2
158
P.M. Sobrinho, C.E. Tuna / Experimental Thermal and Fluid Science 49 (2013) 152159
p
RT
Based on Holman [29] and Cruz et al. [30] were determined the
uncertainty (l) of each primary measure, i.e., obtained without calculation, directly from the instrument, and from these were calculated the uncertainty of results, all shown in Table 1.
From ten trials, referring to a type of experiment was calculated
the median of the data and generated a single point. This procedure
was repeated until all the results of the experiment were obtained.
The average standard deviation (r) as shown by Eq. (9), and variance, as shown by Eq. (10) were calculated based on Costa Neto
[31]. Table 2 presents the results for the motorfan and Table 3
for the compressor.
s
Pn
2
i1 X i X
r
n 1
Pn
S
2
X
n 1
i1 X i
Fig. 7. Variation of the COP of the system due to the variation of relative humidity
of inlet air.
10
5. Results
According to Stoecker [6], in equipments with air condensation,
the cooling capacity depends mainly on the dry bulb temperature
of ambient air and the air ow through the condenser. As the condensing temperature increases with the increasing of the ambient
temperature, the cooling capacity decreases with the increase of
the evaporation temperature.
However, in the test results obtained and presented in Figs. 6
and 7 it can be noted that the relative humidity also has a signicant inuence on the system, because it has inuence on the heat
transfer coefcient responsible for the performance of the system,
as indicated in the results obtained by Bourabaa et al. [15], Still et
al. [22], and Yoo and Lee [18].
In addition, Figs. 8 and 9 show that the relative humidity inuence on the amount of heat removed from the airow passing
through the evaporator and not on the amount of work done by
the compressor. Fig. 10 shows that the dry bulb temperature of inlet air does not inuence the COP of the system.
Tests were performed from June to November, where it was
possible to characterize the behavior of an air conditioning system
during the winter period, which has a low relative humidity, and
during rains period, where has a high relative humidity. The dry
bulb temperature and wet bulb and relative humidity varied
depending on the environmental conditions of each day of
measurement.
Fig. 8. Variation of the heat removed from air to the variation of relative humidity
of inlet air.
Fig. 9. Variation of the compressor work due to the variation of relative humidity of
inlet air.
Fig. 6. Variation of the COP of the system due to the wet bulb temperature of inlet
air.
Analyzing the results, it can be identied that there is an inuence of humidity on the COP of the system, identifying that for low
air humidity condition the performance of air conditioning system
has a 40% drop in its efciency. When it is considered a wet bulb
temperature at the air inlet, it has the same falling of only 3 C
apart.
This reects that the performance of the air condenser, which
suffers direct inuence of the variation of the lm coefcient as a
function of the relative humidity, is contrary to the behavior of
evaporative condensers, where the increase in wet bulb temperature reduces the efciency of the system [6], because the heat to
P.M. Sobrinho, C.E. Tuna / Experimental Thermal and Fluid Science 49 (2013) 152159
159
References
Fig. 10. Variation of the COP of the system due to the variation of the dry bulb
temperature of inlet air.
6. Conclusion
In this paper an experimental analysis was performed on an air
conditioning system, where was evaluated the inuence of relative
air humidity on system performance, as in the literature, for air
conditioning systems where air condensers are employed, it is
not considered this issue but only the dry bulb temperature in
the analysis of those systems.
In the results obtained in bench, was identied that within the
range 4065% RH does not have large variations in system performance. However, from this value the modifying of the system performance is quite signicant, reaching the range of 70%, for the
cases where the test is performed on rainy days where the RH
was high.
For the case that consider for analysis the wet bulb temperature
in the evaluation of system performance, it was not identied large
variations in the range of 1620 C, however, above this temperature, it was noted that system performance becomes greater.
Considering that in the region and period that the analysis was
performed, it was possible to identify that the RH have some inuence on the system performance, however, as most of the time the
climatic characteristics are not more than 65% of RH, it can conclude
that the consideration of using only the dry bulb temperature to
evaluate the performance of a system cannot be disqualied.
It is suggested as a continuation of this work, that tests should be
carried out during the summer where humidity is still higher, so
that the cycle is completed and it can be possible to raise the performance of an air conditioning system during a whole year. Another
suggestion is to develop an analysis of system performance, by
the installation of an air humidier in front of the condenser fan.