Escolar Documentos
Profissional Documentos
Cultura Documentos
REV.
B
KSK-ME-DS-001
SHEET
1 OF 7
Prepare by
Louthfi
GEK
Check by
Timbul W
GEK
Approved by
Nazarudin Rahman
BSP
REV
DATE
DESCRIPTIONS
3O
October
b 2014
PREP'D CHK'D
LTF
TW
30 October 2014
LTF
TW
COMPANY APPROVAL
NR
Date
Revision
Page 2 of 7
Table of Content
Page 3 of 7
Document Number
KSK-ME-DS-001
DATA SHEET
KASIKAN WASH TANK (T-03)
Project Title:
SHEET
4 OF
Mechanical
30-Oct-14
LTF
TW
3-Oct-14
LTF
TW
DATE
BY
CHK.
REV.
DESCRIPTIONS
GENERAL INFORMATION
1
2
Applicable to
Location
: Kasikan GS
Construction
Manufacturer
Purchase
Equipment Name
: WashTank
Serial No.
Item No.
: T-03
No. of Unit
APP.
As Built
OPERATING CONDITIONS
NR
1 (One)
MATERIALS
Liquid Type
A 36
: 0,968
Reinforcing Pad
A 36
Operating Temperature
: 170
Top Angles
A 36
10
: 0.865 "WC
A 106 Gr. B
11
Liquid Overflow
: 15,5
ft
Nozzle Flanges
SA 105
12
: 15
ft
Fittings
13
: 13
ft
As-Bestos, t = 1/8"
14
: 12,5
ft
15
: 9
ft
Internal Pipe
A 106 Gr. B
16
Working Capacity
: 162
bbl
Internal Bolts
N/A
Internal Nuts
N/A
F
(0.031 psig)
17
DESIGN DATA
ASTM A 193 B7
fluorocarbon coated
19
Code Standard
ASTM A 194 2H
fluorocarbon coated
20
: Latest Ed
Supports / Structurals
A 36
21
Diameter (ID)
: 21,5
ft
Name Plate
SS 316
22
Height (H)
: 16
ft
Earthing Lugs 4 ea
SS 304
23
: 170 / 220
24
: 4 "WC
(0.144 psig)
Insulation
N/A
25
: 2 "WC
(0.072 psig)
Center Column
A 106 Gr. B
26
Manway Cover
A 36
27
Shell Design
: 1 Foot Method
Manway Davit
A 53 Gr.B
28
Joint Efficiency
: 0,85
29
Roof Type
A 36
APPURTENANCES
30
Roof Support
31
Rafter Size
32
Roof Slope
: 1 : 16
33
: 25
34
Bottom Slope
: 1 : 120
35
: 40
36
: 2A
37
Hydrotest Pressure
38
: 158
39
: N/A
40
Cathodic Protection
: N/A
41
42
Outside
43
Yes
44
45
46
Column
6" SCH.40
47
48
N/A
15
18
Quantity
1/8
in
UNP- 4 x 2 x 1in
Qty 12
lbf/ft2
Yes
Yes
No
No
Internal Ladder
Yes
No
Yes
No
Wind Girder
Yes
No
Yes
No
Yes
No
Insulation Supports
Yes
No
Lifting Lugs
Yes
No
in
Earthing Lugs
Yes
No
in
No
in
Yes
No
Foundation
Yes
No
Yes
No
mph
Anchor Bolts
5.000
BPD
5.000
BPD
lbf/in2
MINIMUM THICKNESS
49
50
Shell Plate
Yes
No
Stress Relief
Yes
No
Yes
No
Pneumatic Test
Yes
No
Radiography
Full
Yes
No
Yes
No
51
52
Width Course (1 / 2 / 3 )
6 / 6 / 6
ft
Yes
No
53
in
Yes
No
Witness
Non Witness
54
55
Joint Type
Bottom Plate Thickness
3/8
56
Joint Type
57
58
Joint Type
N/A
59
60
Width
61
Observe
in
Radiography
in
62 1.
63 2.
64 3.
4
65 4.
66 5.
67 6.
Magnetic Particle
Dye Penetrant
in
N/A
in
APPLICABLE SPECIFICATIONS & DRAWINGS
Tank Bottom Coating & Cathodic Protection for
Steel Oil Storage Tanks
:
Impact Test
Ultrasonic
Hydrotest
PROTECTIVE COATING
External Coating
Yes
Internal Coating
Yes
Shell Design
Empty
30 270
30.270
lbs
Safety In Designs
Operating
358.684
lbs
Coating Systems
Mechanical Data Sheet For Wash Tank
Hydrotest
381.243
lbs
68 7. KSK-ME-DS-001
WEIGHTS
Document Number
DATA SHEET
KASIKAN WASH TANK (T-03)
KSK-ME-DS-001
Project Title:
5 OF 7
SHEET :
Tank No.
Service Description
: Wash Tank
OPERATING CASE
Fluid
Flammable/Toxic/Corrosive
Operating Pressure
30-Oct-14
LTF
TW
3-Oct-14
LTF
TW
REV.
DESCRIPTIONS
DATE
BY
CHK.
DESIGN
Crude Oil & Produced Water
Operating Temperature
0,031
170
146
Filling rate
USgpm
10
Emptying rate
USgpm
11
Specific gravity
12
Vapour Pressure
13
Viscosity
14
Mass Density
15
146
0,968
psia
cP
0,72
lb/ft
60,38
18,02
Molecular Weight
16
Design Pressure
Min/Max
psig
0.072 / 0.144
17
Design Temperature
Min/Max
170 / 220
18
TANK DATA
19
20
Tank Diameter
ft
21
Tank Height
ft
22
Tank Type
23
Material of Construction
24
Corrosion Allowance
25
Insulation
26
Lining
27
Working Capacity
28
21,5
16
Fixed Supporting Roof
Carbon Steel with External & Internal epoxy coated
0,1250
in
No
No
162
bbl
29
- Overflow
ft
15,50
30
ft
15,00
31
ft
13,00
32
ft
12,50
33
ft
10,00
34
ft
9,00
35
Additional
36
- Mixer
No
37
- Heater
Yes
38
No
39
No
40
- Breather Valve
Yes
41
No
42
- Dogleg
Yes
43
- Level Indicator
No
44
- Spreader Box
Yes
45
- Vortex Breaker
Yes
46
- Gauge Hatch
Yes
47
- Pressure Gauge
No
NOTES
48
49
1)
50
2)
51
52
53
NR
APP.
Document Number
DATA SHEET
KASIKAN WASH TANK (T-03)
KSK-ME-DS-001
Project Title:
6 OF 7
SHEET :
PROCESS
30-Oct-14
LTF
TW
3-Oct-14
LTF
TW
REV.
DESCRIPTIONS
DATE
BY
CHK.
APP.
Mark
Number
Size (in)
N1
150# / RF / SO
Fluids Inlet
N2
150# / RF / SO
N3A
150# / RF / SO
N3B
150# / RF / SO
N4
150# / RF / SO
N5
24
150# / RF / SO
10
N6
150# / RF / WN
Overflow
12
N7
150# / RF / WN
150# / RF / WN
150# / RF / WN
Gauge Hatch
Sample points
N8
13
N9
14
1
1
Service
NR
Remarks
11
N10A-F
3/4
3000# / CPL'G
N11
150# / RF / WN
N12A-D
12
150# / RF / SO
Heater Connection
15
M1
24
API 650
Roof Manway
16
M2
24
API 650
Shell Manway
17
COD
24X36
API 650
N3A
N3B
N9
N4
M1
N5
Handrail
3/4:12
N2
N6
Weir box
(Note 2)
StairWay
Support
16' - 0" H
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
SKETCH
18
N10 A-F
(Note 3)
M2
Internal Pipe
Vortex Breaker
N11
Name Plate
N1
Spreader Box
N8
collection box
COD
1:120
N7
N12A-D
Earth Lugs - 4 Ea
21' - 6" ID
NOTES
1.
2.
3.
4.
5.
6.
7.
Dimension of water seal box (with x length x height) is 40" x 40" x 40".
Weir box 2' height x 1' width with length 1/4 circumferental of tank. Elevation of top weir is15'-0" from bottom plate.
Elevation of sample points are 10'-0", 11'-0", 12'-0", 13'-0", 14'-0" and 15'-0" from bottom plate.
Internal & External coating as per Coating System Data Sheet
Overflow Nozzle is 15'-6" complete with goose neck
Dimension of Spreader Box (with x length x height) is 30" x 40" x 59".
Maintenance Access Base On SID
ATTACHMENT-1
Tank Sizing
TANK SIZING
CV GUMBEL ENGINEERING
KONSULTAN
BASIS OF CALCULATION
Project No.
Project Title
Client
Location
Tag No.
Equip. Name
Case
:
:
:
:
:
:
:
Prepared by
Checked by
Approved by
Revision No.
Revision Date
:
:
:
:
:
LTF
TW
NR
B
30-Oct-14
OBJECTIVES
The objective of this document is to sizing the Water Surge Tank for Ampuh.
CALCULATION METHOD
1. Unit of Measurement :
US Customary
2. The storage tank will be sized/verified for the working capacity as required. The storage tank size will be checked for the holding time,
level settings and response time.
REFERENCES
1. API Standard 650, 10th edition, 1998 "Welded Steel Tanks for Oil Storage"
2. API Standard 650, 11th edition, 2007 "Welded Tanks for Oil Storage"
Bottom Selection and Design
4. TAM 200
5. TAM 400
Roof and Seal Selection and Design
Shell Design
6. TAM 500
Safety In Designs
7. SID-SU-5106-A
Coating Systems
8. COM-SU-5191
9. BE-ZWD1-AMPH-ME-DS-0001
Mechanical Data Sheet For Water Surge Tank
DESIGN BASIS
1. The working volume of the tank is defined as liquid volume stored between LLL and NLL.
2. The Low Liquid Level alarm will be set based on operators response time (3 minutes) before the pump
trip at the low low liquid level.
3. The low low liquid level is based on Table 3.6 of API STANDARD 650 (10th ed. 1998) plus additional height equal to outline diameter
to prevent vortex in the connection point of the outlet of the tank.
4. Surge time (NLL - overflow) of 30 minutes is provided to allow Operator blocking the water surge tank's outlet line during maintenance
while produced water from existing Wash Tank will be continuously filling.
5. Nozzle for inlet and outlet to pump will be sized/verified for following design criteria :
Momentum at Inlet Tank Nozzle shall not exceed 670 lb/ft s2
Velocity a Outlet to pump suction flange shall not exceed 5 ft/s
6. Filling rate is taken from Existing Wash Tank.
ft
ft
hours
bbls
bbls
ft
ft
ft
ft
ft
=
=
=
=
2743
3048
3810
3962
4572
mm
mm
mm
mm
mm
TANK SIZING
CV GUMBEL ENGINEERING
KONSULTAN
:
:
:
:
:
:
:
Prepared by
Checked by
Approved by
Revision No.
Revision Date
:
:
:
:
:
LTF
TW
NR
B
30-Oct-14
CALCULATION
Unit of measurement :
DESIGN DATA
Filling Rate From Existing Wash Tank
Pumping Out by Water Injection Pump
DESIGN CRITERIA
A. Holdup Time
B. Surge Time
(A + B)
Qin
Qout
5.000
5.000
BPD
BPD
=
=
=
20
30
50
minutes
minutes
minutes
=
=
=
=
=
=
3
22
5
20
5
30
minutes
minutes
minutes
minutes
minutes
minutes
21,50
8
=
=
Overflow
Working Volume
145,83
145,83
=
=
15,5 ft
HHLL
15,0 ft
HLL
NLL
=
=
13,0 ft
12,5 ft
LLL
LLLL
=
=
h =
h' =
US Customary
10
9
ft
ft
1,00 ft
1,30 ft
USGPM
USGPM
ft
in
(min. of 1 ft or 5 minutes)
(minimum = h + h')
TANK SIZING
CV GUMBEL ENGINEERING
KONSULTAN
:
:
:
:
:
:
:
Prepared by
Checked by
Approved by
Revision No.
Revision Date
Level Setting
Liquid Level
Parameter from Datum
ft
LLLL
9,0
LLL
10,0
NLL
12,5
HLL
13,0
HHLL
15,0
Overflow
15,5
Overflow to HHLL
HHLL to LLL
HLL to NLL
NLL to LLL
LLL to LLLL
HLL to LLLL
LTF
TW
NR
B
30-Oct-14
Filling Time
Liquid Volume
Remarks
(bbl)
582
647
808
841
970
1002
Parameter
OK
OK
OK
OK
OK
OK
Time
(minutes)
18,62
46,56
9,31
37,25
9,31
55,87
LLLL to LLL
LLL to NLL
NLL to HLL
HLL to HHLL
HHLL to Overflow
NLL to Overflow
Response Time
Parameter
:
:
:
:
:
Time
(minutes)
9,31
37,25
9,31
46,56
18,62
74,49
Parameter
OK
OK
OK
OK
OK
OK
Time
(minutes)
9,31
37,25
9,31
46,56
18,62
74,49
Overflow to HHLL
HHLL to LLL
HLL to NLL
NLL to LLL
LLL to LLLL
HLL to LLLL
Tank Dimension
Parameter
Working Capacity
Nominal Capacity
Height
(ft)
2,50
16,00
NOZZLE SIZING
Design Criteria :
Momentum at Inlet Nozzle
Velocity at Outlet to Pump Nozzle
Parameter
Inlet Nozzle
Outlet to Fire Water Pump Nozzle
Diameter
(ft)
21,50
21,50
Capacity
(bbl)
162
1035
lb/ft s
ft/s
670
5
=
=
NPS
(in)
8
8
Schedule
40
40
Level
LLL - NLL
Bottom - Curf Angel
ID
(in)
7,981
11,938
Nozzle
Criteria
0,94 lb/ft s2
0,42 ft/s
Remarks
OK
OK
ATTACHMENT-2
DESIGNCALCULATION
DOC. NO
PROJECT
OWNER
: KSK-ME-DS-001
: KASIKAN MAINTENANCE PROJECT
: PT. BUMI SIAK PUSAKO
REV
BY
DATE
:
:
:
B
CV GUMBEL ENGINEERING KONSULT
30 Oktober 2014
TABLE OF CONTENTS
PAGE
SHELL PLATE
ROOF PLATE
BOTTOM PLATE
WEIGHT OF WATER
10
SUMMARY OF WEIGHT
11
12
13
14
DEAD LOAD
15
WIND LOAD
Sheet 1 of 8
DOC. NO
PROJECT
OWNER
: KSK-ME-DS-001
: KASIKAN MAINTENANCE PROJECT
: PT. BUMI SIAK PUSAKO
:
:
:
REV
BY
DATE
B
CV GUMBEL ENGINEERING KONSULT
30 Oktober 2014
TAG NUMBER
ROOF (OPEN / CLOSE)
TANK SUPPORT (SELF-SUPPORTED /COLUMN-SUPPORTED / N/A)
TYPE OF ROOF (CONE-ROOF / DOME-ROOF / FLAT-ROOF / FLOAT-ROOF / NA)
=
=
=
=
T-03
COpen
Column-Supported
Cone-Roof
TANK DIAMETER
TANK HEIGHT
MAX. DESIGN LIQUID LEVEL (HHLL)
GROSS CAPACITY
NET CAPACITY
D
Ht
H
Gc
Nc
=
=
=
=
=
21,5
16
15,0
1.035
970
Ft
Ft
Ft
Bbls
Bbls
=
=
=
=
=
RADIUS OF ROOF
rr
15
Deg
=
=
=
=
0,125
0,125
0,125
0,125
inch
inch
inch
inch
=
=
=
=
3,175
3,175
3,175
3,175
mph
psf
=
=
64,374
122,070
=
=
=
1.000,000
9,928
70,000
CORROSION ALLOWANCE
SHELL PLATE
BOTTOM PLATE
ROOF PLATE
STRUCTURAL
EARTHQUAKE
ZONE COEFICIENT ( FOR SEISMIC ZONE 2A )
ESSENSIAL FACTOR
SITE COEFISIEN FACTOR
Z
I
S
=
=
=
0,2
1
1
V
w
=
=
40
25
MATERIAL
:
SHELL PLATE, BOTTOM PLATE, ROOF PLATE
STRUCTURAL
COLUMN
FLANGE
NOZZLE NECK (PIPE NOZ.)
MANHOLE COVER & REINFORCE
=
=
=
=
=
=
mm
mm
mm
mm
km/h
kg/m
ASTM A-36
ASTM A-36
A-106 Gr.B Sch.40
SA-105
SA
105
A-106 Gr.B
ASTM A-36
Pu
0,144 psi
PL
0,027 psi
Tu
220 F
TL
G
P
T
=
=
=
=
(Atmospheric)
mm
mm
mm
M
M
lb/ft2
6.553,200
4.876,800
4.572,000
164
154
170 F
62,4
lb/ft
0,144
psig
158
Deg F
kg/m
mbarg
Deg.C
2. SHELL PLATE
Refference: API 650 TWELFTH, March 2013, clouse 5.6.3.2
Calculation of Thickness by the 1-foot Method
2.6 D (H-1)G
Td
2.6 D (H-1)
Tt =
+ CA
Sd
St
Tc
Td
Tt
=
=
=
D
H
=
=
1/6
1/6
3/89
21,5
16
Inch
Inch
Inch
ft
ft
0,97
(Produced Water)
CA
Sd
=
=
0,13 inch =
23.200 psi ( API 650 Table 5.2b)
St
= Joint Efficiency
3,175
mm
## 160 Mpa
## 171 Mpa
0,85
As per section 5.6.1.1 the required shell thickness shall be the greather of the design shell thickness including any corrosion allowance, or the hydrostatic test shell
thickness, but the shell thickness shall not be less than 3/16 inch (5 mm) for Nominal Tank Diameter < 50 ft.
NO
COURSE
H
Feet
1
2
3
4
5
6
6
12
16
CA
Inch
Td
( Tc + CA )
Inch
0,125
0,125
0,125
0,139
0,155
0,166
Tc
Inch
0,014
0,030
0,041
Inch
0,315
0,236
0,236
mm
Ok
Ok
Ok
8
6
6
WEIGHT
kg
2.363,25
1.772,43
1.181,62
5.317,30
11.722,64
Sheet 2 of 8
DOC. NO
PROJECT
OWNER
: KSK-ME-DS-001
: KASIKAN MAINTENANCE PROJECT
: PT. BUMI SIAK PUSAKO
:
:
:
REV
BY
DATE
B
CV GUMBEL ENGINEERING KONSULT
30 Oktober 2014
Shell No.
1
2
3
Mat'l
Used
A36
A36
A36
Minimum
Yield stress reduction fac
Yield Strength
( App. M )
(psi)
(k)
36000
0,904
36000
0,904
36000
0,904
Product Design
Stress Sd
(psi)
23200
23200
23200
Tensile strength
Ft
(psi)
58000
58000
58000
Corrosion
Allowance CA
(Inc)
0,125
0,125
0,125
Joint Efficiency
(E)
0,85
0,85
0,85
1
2
3
Mat'l
Height
t.min
tsc.
H'
H' max
P' max
used
(inc)
(inc)
(inc)
(inc)
(inc)
(inc)
kPa
0,20
0,20
0,20
0,31
0,24
0,24
196
124
52
1.081,79
768,30
454,81
A36
A36
A36
192
120
48
889,79
648,30
406,81
Pmax
kPa
221,71
161,54
101,37
221,71
161,54
101,37
ROOF PLATE
Weight of roof plate
Wrp
= 0.7854 x (D)^2 x (t/12) x 490.06
Wll
= 0.7854 x D^2 x w
Minimun roof plate thickness (API 650, cl. 5.10.2.2)
Roof plate thickness selected
=
=
D
t
A
w
Wrp
Wll
Wr
=
=
=
=
=
=
=
=
=
=
=
=
=
=
r
h
c
sin
Total H
=
=
=
=
1/5 inch
1/4 inch
21,5
0,250
15
25
3.705
9.076
12.781
0.197 inch
12.5 mm, exclusive of corrosion allowance
3/4
:
21,5 ft
0,06
3,58 o
10,75 ft
0,67 ft
10,77 ft
0,06
16,67 ft
=
=
=
=
=
=
=
=
=
12
feet
inch
degree
lbf/ft2
lbs
lbs
lbs
5,36 m
5 mm
6,00 mm
=
=
6.553 mm
6,00 mm
=
=
=
=
122
1.682
4.121
5.803
=
=
=
Selected =
kg/m
kg
kg
kg
5,24 m
ft
ft
inch
17,2
25,8
1/4
r
D
=
=
3 x 3 x 1/4 inch
0,077 inch3
=
=
>
Top Angel
Refer to API 650 Cl. 5.1.5.9
The tank shell will be supplied with top angle :
L- 2 x 2 x 3/16 Inch
Minimum Size:
L-3 1/7 x 3 1/7 x 1/3 Inch
Selected size :
Weight of top angle Selected
=
3.3
NOT REQUIRED.
Minimum Requirement
Minimum required size (API 650, cl. 5.9.3.2)
Section modulus, Z min
Since Za
3.2
<
20587,48498 mm
442 lb
=
=
=
21 m
9,55 kg/m
201 kg
ft.
where:
Top shell course thickness, t
Nominal tank diameter, D
Wind design speed, V
Sheet 3 of 8
=
=
=
1/4 Inch
21,5 ft
40 mph
mm
DOC. NO
PROJECT
OWNER
: KSK-ME-DS-001
: KASIKAN MAINTENANCE PROJECT
: PT. BUMI SIAK PUSAKO
:
:
:
REV
BY
DATE
B
CV GUMBEL ENGINEERING KONSULT
30 Oktober 2014
4. BOTTOM PLATE
4.1
4.2
4.3
1/4
1/8
3/8
3/8
inch
inch
inch
inch
(exclude CA)
(include CA)
10
=
=
=
feet
inch
lbs
=
=
=
6.703
10
2.770
mm
mm
kg
Selected
4.4
22
3/8
6.101,94
=
=
=
1/4 inch
1/3 inch
0
inch
=
=
=
=
24 inch
239,91 inch
inch
lbs
=
=
==NOT REQUIRED==
=
=
=
=
609,60
6.093,60
10,00
-
mm
mm
mm
kg
Note :
a. Max. hydrostatic test stress
b. Allowance stress for the design
5,1
=
=
=
=
=
=
RAFTER
Refer to API 650 Cl. 5.10.4.4
Max Rafter spaced (outer)
Max Rafter spaced (inner)
=
=
b
Fy
t
p
=
=
=
=
21,5
10,75
16
25
3.705
12.781
ft
ft
ft
lb/sq.ft
lbs
lbs
7
6
35,21
psf
0,244
psi
ft
ft
maximum allowable roof plate span, measured circumferentially from center-to-center of rafters
specified minimum yield strength of roof plate
corroded roof thickness
uniform pressure as determined from load combinations
nmin
Polygon
No
Radius
( ft )
Q'ty of side
polygon
10,75
CIRCLE
Rafter Quantity
min Req'
Selected
10,75
w =
Weight =
Material
Rafter
UNP- 4 x 2 x 1/5
in-lb
Rafter Space
( inch )
3300
Section Modulus
z =
Mmax / f
=
1,45 inch
f = allowable tension for A36
24.000 psi (2/3 x yield stress)
132,53 lb/in
9,33 kg/m )
149,05 lb/in
Total Load =
Recalculating Mmax ;
Mmax =
314.479,44
129,92
16,51 lb/in
in-lb
Material Selected
UNP- 4 x 2 x 1/5
12
z=
13,10
Length (ft)
Qty
10,77
12
Sheet 4 of 8
inch
Weight
lb/ft
6,260
Total Weight
lb
809
67,54
DOC. NO
PROJECT
OWNER
: KSK-ME-DS-001
: KASIKAN MAINTENANCE PROJECT
: PT. BUMI SIAK PUSAKO
REV
BY
DATE
:
:
:
B
CV GUMBEL ENGINEERING KONSULT
30 Oktober 2014
Size (in)
8
8
2
4
24
8
2
8
6
3/4
2
12
24
36
36X48
150# / RF / SO
150# / RF / SO
150# / RF / SO
150# / RF / SO
150# / RF / SO
150# / RF / WN
150# / RF / WN
150# / RF / WN
150# / RF / WN
3000# / CPL'G
150# / RF / WN
150# / RF / SO
API 650
API 650
API 650
Fluids Inlet
Skimmed Oil Flow to Shipping
Siphon Breaker connection
Breather Valve connection
Tank Gauge Connection
Overflow
Drain collection box
Outlet water seal box
Gauge Hatch
Sample points
Temperature Indicator Connec
Heater Connection
Roof Manway
Shell Manway
Clean Out Door
Weight (lbs)
132,56
132,56
56,40
56,40
117,12
132,56
14,10
132,56
39,45
10,58
14,10
78,90
155,78
214,95
1.029,00
2.317,02
Qty
1
1
2
1
1
1
1
1
1
6
1
1
1
1
1
Descriptions
Weight (lbs)
Qty
1
1
0
1
1.709
1.191
1.147
4.046,70
8. WEIGHT OF WATER
Max. Liquid level =
15,50 ft
HHLL =
LLLL =
f luid =
3
=
5.627 ft
W ID = VID x
f luid
15,00 ft
9 ft
62,37 lb/ft3
Weight of Water =
350.973 lb.
f luid =
=
5.446 ft
W ID = VID x
f luid
Weight of Liquid =
328.414 lb.
60,31 lb/ft3
Descriptions
Weight (lbs)
30.270
EMPTY TANK
Shell Plate
Bottom Plate
6.102
Roof Plate
3.705
1.251
2.317
4.047
11.723
1.126
Weight of Water
Empy Tank
381.243
350.973
30.270
OPERATING CONDITION
a
Weight of Liquid
Empy Tank
358.684
328.414
30.270
Kg-m
H1 =
600000
( t D ) (100 v )
3
Kg
H1
0,197 inch
21,5 ft
40 mph
17,88
Kg
1 ft
Height of tank
16 ft
mm
Kg
mm
DOC. NO
PROJECT
OWNER
: KSK-ME-DS-001
: KASIKAN MAINTENANCE PROJECT
: PT. BUMI SIAK PUSAKO
REV
BY
DATE
:
:
:
B
CV GUMBEL ENGINEERING KONSULT
30 Oktober 2014
Kg
= ZI ( C1 Ws Xs + C1 Wr Ht + C1 W1 X1 + C2 W2 X2 )
= ZI ( C1 Ws + C1 Wr + C1 W1 + C2 W2 )
Where,
M
231.197 ft-lb
31.993 mm
32.883 lb
14.929
= Zone coefficient
0,2
C1
0,60
C2
0,28
Ws
11.712 lb
Xs
8,79 ft
Wr
12.781 lb
Ht
16,00 ft
W1
183.912 lb
X1
5,70 ft
W2
141.218 lb
X2
8,70 ft
mm
mm
mm
mm
D =
Ht =
H =
21,5 Ft
16 Ft
15,0 Ft
=
=
=
6.553
4.877
4.572
=
=
=
=
7,50
15,96
344,00
61,93
Y2
Ht
Y1
Y2
A1
A2
Y1
=
=
=
=
0.5 H
H + 1/6 D tg.A
D x Ht
Dx(D tg.A) x 0.5
ft
ft
ft2
ft2
A1 Y1 + A2 Y2
Xs = -------------------A1 + A2
Ws
M
Wt
W LMAX
WL
=
=
=
=
=
11.712
231.197
362,63
416,24
416,24
Xs =
8,791 ft
lbs
ft-lb
lb/ft
lb/ft
lb/ft
mm
WT
= /4 x D x H x g
WT
D/H
= ratio of D/H
kg/mm
==> WT =
328.414 Lb
=> D/H =
1,43
183.912 Lb
141.218 LB
154.207
kg/mm
W1/WT =
W2/WT =
0,56
0,43
==> W1 =
==> W2 =
X1/H =
X2/H =
0,38
0,58
==> X1 =
==> X2 =
Sheet 6 of 8
5,70 Ft
8,70 Ft
=
=
83.496
=
=
1737
2652
64.113
DOC. NO
PROJECT
OWNER
: KSK-ME-DS-001
: KASIKAN MAINTENANCE PROJECT
: PT. BUMI SIAK PUSAKO
:
:
:
REV
BY
DATE
B
CV GUMBEL ENGINEERING KONSULT
30 Oktober 2014
==> C1 =
==> k =
0,6
0,58
T=
2,69
kg/m
If T =< 4.5
C2 = (0.75 x S)/T
0,2788
If T > 4.5
C2 = (1.35 x S)/T
0,1036
RESISTANCE TO OVERTURNING
WL
= 7.9 Tb (Fby.G.H)
Tb
Fby
WL
= Resistance to overturning
7.9 tb ( Fby G H )
0,38
36.000
15
Inch
9,53
Psi
1.701
Ft
4.572
WL =
2.212 lb/ft
#REF!
1.25 GHD =
390 lb/ft
581
Take WL =
390 lb/ft
581
SHELL COMPRESSIVE
Unanchored Tank
Wt
= ( W shi + W rs ) / D =
Factor
`
2
= M / [ D (wt + wL ) ]
Since
(Ws + Wr )
3.14 D
362,63 lb/ft
0,6643 <
1.57
So,
b = (( Wt + WL ) *
b=
Fa =
Fty =
max Fa =
b/1000t (b/12t)
10.012
<
2,2
3.452 lb/ft
) - WL
=
5.142,22
6.681 psi
36.000 psi
18.000 psi
18.000
==TANK IS STABLE==
Z
I
S
=
=
=
M
P
=
=
ZI ( C1 Ws Xs + C1 Wr Ht + C1 W1 X1 + C2 W2 X2 )
ZI ( C1 Ws + C1 Wr + C1 W1 + C2 W2 )
M
P
=
=
=
=
231.197 lb-ft
32.883 lb
=
=
11.723 lb
442 lb
12.781 lb
=
=
=
173,55 lb/ft
6,54 lb/ft
189,23 lb/ft
0,2
1
1
Ws / ( . D )
Wta / ( . D )
Wdls / ( . D )
=
=
p=
As =
31(V/120)2
Fw =
40 mph
2
3,44 lb/ft
p x As
Wind pressure, psf
=
=
252 lbs
Sheet 7 of 8
0,62 Psf
2
405,93 ft
DOC. NO
PROJECT
OWNER
: KSK-ME-DS-001
: KASIKAN MAINTENANCE PROJECT
: PT. BUMI SIAK PUSAKO
Wind Load
proj. (ft2)
Shell
Roof
344
7
REV
BY
DATE
Area (As)
ft
55,04
1,16
1080,71
363,05
Total
W rpe =
W rfe =
W she =
3.705 lb
8.521 lb
11.723 lb
W=
Mw =
M=
23.948 lb
191.587 lbs-ft
171.630 lbs-ft
==TANK IS STABLE==
Since the overturning moment of tank < overturning moment from wind pressure, tank is stable
Sheet 8 of 8
Force (Fw)
lbs
59.482,16
419,55
:
:
:
B
CV GUMBEL ENGINEERING KONSULT
30 Oktober 2014
Moment Arm
ft
7,50
15,96
Moment (M)
(ft - lbs)
Shear Force
lbs
446.116
6.696
59.482,16
419,55
452.812
59.901,71