Session Goals
ABB Group
October 21, 2013 | Slide 2
Harmonics
What?
ABB Group
October 21, 2013 | Slide 3
Harmonics What?
ABB Group
October 21, 2013 | Slide 4
Non-incandescent lighting
Computers
Telecommunications equipment
Copy machines
Battery chargers
ABB Group
October 21, 2013 | Slide 5
ABB Group
October 21, 2013 | Slide 6
Fundamental
5th
0.5
i1 ( t)
i5 ( t)
Components
i7 ( t)
0.5
7th
0.005
0.01
0.015
0.02
0.025
0.03
1.5
0.5
i T( t)
Summation
0.5
1.5
0.005
0.01
0.015
0.02
t
ABB Group
October 21, 2013 | Slide 7
0.025
0.03
Fundamental
5th
7th
ABB Group
October 21, 2013 | Slide 8
11th
13th
Harmonics
Why worry?
ABB Group
October 21, 2013 | Slide 9
ABB Group
October 21, 2013 | Slide 10
Excessive voltage
Overheating of capacitors
ABB Group
October 21, 2013 | Slide 12
(cont.)
Equipment downtime
ABB Group
October 21, 2013 | Slide 13
PCC Example
To other utility customers
PCC2 (Harmonic
Voltage Distortion)
480 V
MV PWM
ABB Group
October 21, 2013 | Slide 14
LV
PWM
LV
PWM
THD = DF =
ABB Group
October 21, 2013 | Slide 15
*100%
ISC
~8
IL
TDD (Total Demand Distortion) equals the THD (Total Harmonic Distortion) of the
nonlinear load multiplied by the ratio of nonlinear load to the total (demand)
load:
(percentages)
NL
TDD = THDNL
TL
Where
ABB Group
October 21, 2013 | Slide 17
TDD
THDNL
NL
TL
=
=
=
=
General
System
Dedicated
System
Notch Depth
10%
20%
50%
THD (Voltage)
3%
5%
10%
16,400
22,800
36,500
Notch Area, Vs
Note: Notch area for other than 480 V systems should be multiplied by V / 480.
ABB Group
October 21, 2013 | Slide 18
<11
11
h<17
17
h<23
23
h<35
35
h
TDD
<20
4.0
2.0
1.5
0.6
0.3
5.0
20<50
7.0
3.5
2.5
1.0
0.5
8.0
50<100
10.0
4.5
4.0
1.5
0.7
12.0
100<1000
12.0
5.5
5.0
2.0
1.0
15.0
Note: All harmonic current levels are in percent with fundamental current IL as the base.
ABB Group
October 21, 2013 | Slide 19
<11
na
na
na
na
h<17
11
2.83
4.95
6.36
7.78
h<23
17
na
na
na
na
h<35
23
0.85
1.41
2.12
2.83
h
35
0.42
0.71
0.99
1.41
ABB Group
October 21, 2013 | Slide 20
<11
1.00
1.75
2.50
3.00
h<17
11
0.50
0.88
1.13
1.38
h<23
17
0.38
0.63
1.00
1.25
h<35
23
0.15
0.25
0.38
0.50
h
35
0.08
0.13
0.18
0.25
Harmonics
Will it be a problem?
ABB Group
October 21, 2013 | Slide 21
ABB Group
October 21, 2013 | Slide 22
THD (Current) on a network with a short circuit ratio <20 (20<50, 50<100,
100<1000) will be acceptable if the % drive load times 45% is <5% (<8%, <12%,
<15%)
E.g. a network with a short circuit ratio of 35 has 15% drive load:
15% x 45% = 6.75% 6.75% < 8% Acceptable
E.g. a network with a short circuit ratio of 65 has 30% drive load:
30% x 45% = 13.5% 13.5% > 12% Not Acceptable
(Rule of thumb for 6-pulse drives with 3%
reactor,, all other loads assumed to be linear)
ABB Group
October 21, 2013 | Slide 23
Harmonics
ABB Group
October 21, 2013 | Slide 24
ABB Group
October 21, 2013 | Slide 25
Reactors (Chokes)
Passive Filters
Harmonic Trap
Hybrid
Active Filters
Stand Alone
Reactors (Chokes)
ABB Group
October 21, 2013 | Slide 26
Different design
techniques
DC Link
Reactor
Reactor Effectiveness
THD (Current) vs. % Reactor
120
%THD (Current)
100
80
60
40
20
0
0
% Reactor
Rsc = 20
ABB Group
October 21, 2013 | Slide 28
Rsc = 60
Rsc = 200
Swinging Chokes
ABB Group
October 21, 2013 | Slide 29
ABB Group
October 21, 2013 | Slide 30
%TDD (Current)
35
30
25
20
15
10
5% Swinging Choke
3% Fixed Choke
0
0%
20%
40%
60%
% Speed
ABB Group
October 21, 2013 | Slide 31
80%
100%
120%
ABB Group
October 21, 2013 | Slide 32
Performance reduced by
line imbalance
Hybrid Filter
ABB Group
October 21, 2013 | Slide 33
Relatively unaffected by
line imbalance
ABB Group
October 21, 2013 | Slide 34
6 pulse rectifier
18 pulse rectifier
DC/AC
DC/AC
12 pulse rectifier
ABB Group
October 21, 2013 | Slide 35
E1Ysec
12 Pulse Configuration
Transformer with delta primary and
delta / wye secondary produces a 30
phase shift between the two
secondaries.
30
E1sec
-5 x 0 = 0
E5sec
E5Ysec
( 0 )
( 180 )
ABB Group
October 21, 2013 | Slide 36
-5 x 30 = -150
E1Ysec
12 Pulse Configuration
Transformer with delta primary and
delta / wye secondary produces a 30
phase shift between the two
secondaries.
30
E1sec
7 x 0 = 0
E7sec
E7Ysec
( 0 )
( 180 )
7 x 30 = 210
ABB Group
October 21, 2013 | Slide 38
DC
Link
L
C
LCL filter
M
Line
inverter
(rectifier)
Motor
inverter
Motor
Active supply
100
Percentage [%]
10
1
0,1
0,01
ABB Group
October 21, 2013 | Slide 40
Diode supply
0,001
0,0001
0
1000
2000
3000
4000
5000
6000
Frequency [Hz]
7000
8000
9000
10000
Impressive Numbers
THD (current) and harmonic components
5
4
3
2
1
0
1
7 13 19 25 31 37 43 49 55 61 67 73 79 85 91 97
20
30
40
50
60
70
80
90
100
RSC
ABB Group
October 21, 2013 | Slide 41
Converter module
Main switch
Main contactor
LCL-filter module
ABB Group
October 21, 2013 | Slide 42
Product offering
ABB Group
October 21, 2013 | Slide 43
20%
12-Pulse
0% Voltage Imbalance Reference Curve
10% Total Network Impedance
18-Pulse
5% Total Network Impedance
(Utility + Multi-Phase Transformer)
15%
18 Pulse with
12 Pulse Performance
18-Pulse
10% Total Network Impedance
(Utility + Multi-Phase Transformer)
10%
ULH
1% Total Network Impedance
5%
ULH
10% Total Network Impedance
0%
0.0%
0.5%
1.0%
1.5%
2.0%
2.5%
Voltage Imbalance
12-Pulse Reference
ABB Group
October 21, 2013 | Slide 44
18-Pulse Direct
18-Pulse Xfmr
3.0%
Harmonic
Reduction
72%
39%
45.8%
33%
54.2%
12%
83.3%
10%
86.1%
Hybrid filter
7%
90.3%
5%
93.1%
4%
94.4%
3.5%
95.1%
Technique
Remember!
Even an 80% THD nonlinear load with a will result in only 8%
TDD if the nonlinear load is 10% and the linear load is 90%.
(80%(10%/(10%+90%))=8%)
ABB Group
October 21, 2013 | Slide 45