Escolar Documentos
Profissional Documentos
Cultura Documentos
LATERAL LOADING
Problem 1
Free edge
Simple supports
h
Determine the required thickness of a single leaf wall supported as shown above using the
following criteria:
Characteristic wind load
= 0.45 kN/m2
= 4.5 m
= 4.5 m
= 7.3 N/mm2
m = 3.0
f = 1.2
Flexural Design
The design bending moment per unit height of the wall is given by the following expression for a
2 way panel assumed to crack vertically
m = W k f L2
(ii)
(iii)
support conditions
(i)
= 0.25
= 0.15
= 0.6
= 0.35
= 0.45
. Orthogonal ratio to include allowance for self weight. According to clause 32.4.2,
fkb = fkx + mgd, where gd is determined half way down the wall
gd = 0.5 x 4.5 x 1200 x 9.81 x 10-6 x 0.9 = 0.024
nb - f for max criteria = 0.9
f
f
kb
kp
f = 1.2,
L=4.5
f kx
m
kp
M =
=
0.903
0.0806 x 1.2 x 4.52
In addition no dimension shall exceed 50 tef. since h and L both = 4.5 then
t
4.5x 1033
90 mm
50
4.5m
45o
4.5m
2.734
= 0.608 kN / m
4.5
fv
mv
mv
0.398
= 0.16 N/ mm 2
2.5
Solution - Problem 2
1. = 0.3/0.9 = 0.33. Assuming worst flexural strength s for clay units.
2. Aspect ratio h/L = 5.625/4.5 = 1.25
3. Support conditions Simple
Using BS5628:Part 1, Table 8A, for h/L = 1.25, = 0.095 + 2/5(0.097 0.095) = 0.0958
And using the transformation technique, {enhance moment coefficient by window ht/ panel ht}
Window ht hw = 1.0m, panel ht hp = 5.625
Therefore, hw/hp = 1.0/5.625 = 0.18
Modification to moment coefficients due to line loads = 1 + 0.18 = 1.18
Hence modified = 0.095 x 1.18 = 0.113
Now Wk = 0.7kN/m2,
f = 1.2,
L = 4.5m
5.625m
1.25m 1.0m
4.5m
Solution - Problem 3
Using the transformation method indicated in the notes, then fixity to edges is reduced by a
quarter = 0.25, i.e. = 0.75 {Use the notation : = 1.0 for full fixity, = 0.0 for simple
support}
Hence the bending moment coefficient is determined from 8E and 8I. In order to transform, we
reduce the panel fixity to a value intermediate between full fixity and simple support. i.e We
assume partial fixity.
Now = 0.25/0.75 = 0.33 (Table 3)
h/L = 4/4 = 1.0
For the pinned edge condition, Table E ( = 0), then = 0.066 (by linear interpolation)
For the pinned edge condition, Table I ( = 1), then = 0.033 (by linear interpolation)
So including effect fro transformation, = 0.75, = 0.041
Hence m = 0.041 x 0.60 x 1.2 x 42 = 0.47kNm/m
Hence trequired = [(0.47 x 3.0 x 6 x 106)/(0.75 x 1000)]0.5 = 106mm
Solution - Problem 4
Outer leaf.
No information given on water absorption of bricks, so take WA > 12 which gives the worst case.
For brick fkb = 0.3,
fkp = 0.9,
Consider wall as simply supported at base, built in up the sides and include self weight.
Self weight stress at mid height = 0.5 x 3.375 x 1700 x 9.81 x 10-6 x 0.9 = 0.025N/mm2
Orthogonal ratio including self weight = [0.3 + (0.025 x 3.0)]/0.9 = 0.417
Therefore bending moment coefficient (Table 8c) for an aspect ratio = 3.375/4.5 = 0.75,
= 0.044 (by interpolation)
Consider thickness as 103mm,
Design moment capacity of wall M
= [fkp x Z]/m
= [fkpbt2]/(6m) = {0.9 x 1000 x 1032]/[3.0 x 6 x 106]
= 0.531kNm per m
Applied design moment m = WkfL2 and setting this as equal to the design moment capacity of
the wall :
Wk = M/[fL2] = 0.531/[0.044 x 1.2 x 4.52] = 0.499kN/m2
Total characteristic wind pressure = 0.6kN/m2 therefore, excess force to be carried by inner leaf :
is 0.6 0.499 = 0.101kN/m2
Design of inner leaf.
Try 3.6N/mm2 blocks, 100m thick. Aspect ratio of panel = 1.25
Consider self weight as 1000kg/m3,
Then self weight stress at mid height = 0.025 x 1000/1700 = 0.015N/mm2
Modified orthogonal strength ratio = [0.25 + 0.015 x 3.0]/0.45 = 0.66
Now considering simple support to all s=edges then from BS5628 par 1 Table 8A,
= 0.066 + 4/10(0.069 0.066) = 0.0672 (by interpolation)
Thickness is 100mm so
M = [0.45 x 1000 x 1002]/(3.0 x 6 x 106) = 0.25kNm
There fore characteristic wind force that can be carried
Wk = 0.25/[0.0672 x 1.2 x 4.52] = 0.153kN/m2
Total capacity of cavity wall is acceptable.
It should be noted that the wall panel could be shown to carry a greater wind force since some
degree of fixity could be allowed at the base of both walls. In addition, if mortar jointing were
used between the inner blockwall and the columns, then some degree of fixity might effectively be
taken at the support due to arching action in the wall. In the example, the total wind load was
determined based on the assumption that both leaves attain their ultimate strength simultaneously
as inferred by the first paragraph to clause 32.4.5 of BS5628 : Part 1. If, however, the wind load
were shared between the two leaves, in proportion to their design moments of resistance, as
previously given then the stress in the leaves would be as follows:
Mbrick = 0.532, Mblock = 0.250 kNm per m
Thus Wk would be shared in the ratio :
0.531/0.781 x 0.6 = 0.41 kN/m2 to brick
And