APPLICATIONS
Ideal circuit monitoring for main feeds, branch circuits, gensets and
equipment
Programmable set-point for alarms and control
FEATURES
Monitoring and Metering
User Interface
EPM 5500P
Standard Features
15
Power Quality
Statistic
PL
5500
PARAMETERS
Phase Voltage
Line Voltage
Current
I1,I2,I3,In,Iavg
Power
P1,P2,P3,Psum
Reactive Power
Apparent Power
Power Factor
PF1,PF2,PF3,PF
Frequency
Frequency
Ep_imp ,Ep_exp ,Ep_t otal,Ep_net
Energy
Reactive Energy
Demand
U_unbl
I_unbl
Monitoring
Voltage THD
Current THD
Harmonics
Harmonics 2nd t
Crest Fact or
TIF
THFF
Current K factor
K Fact or
PL
5500 IO
o 31st
I/O
Relay Output
Pulse Output
Others
Monitoring
Description
Energy
Real Time Measuring
& Demand
FUNCTION
Alarm
COMM
RS485 Port
Year,Month,dat e,Hour ,
minut e, Second
Time
Note:
1. There are two DIs in the model - PL5500.
2. The model PL5500 IO can provide additional 2 DIs, DI power, 2 DOs and 2 Relay outputs. The 2 DOs can serve as Alarm or Pulse
output.
User Interface
Display metering data
Load current
percentage display
Load nature
Energy Level
Time display
Communication Indicator
Energy pulse
output indicator
Digital input
indicator
www.GEMultilin.com
2
EPM 5500P
Options Advanced
Measurement Features
Control Options:
The EPM 5500P includes multiple advanced
measurement features to support power analysis and control through the use of two form A
relays. Two digital outputs can also be used to
provide alarm signals.
Up to nine set points can be programmed with
specified time limits. If a parameter value varies
above or below a given set point for a programmed time interval, then an event with a time
stamp is generated.One digital output (DO) can
also be activated to send a control signal. When
the alarming parameter returns to normal, it will
be time stamped and logged, providing the user
with the duration of the over/under condition.
Any of the following 43 parameters can be
programmed to activate 1 DO and generate
an event.
Frequency
Volts - per phase, per phase average,
phase-phase, phase-phase average
Currents - per phase, average, neutral
Communication
PC software:
The software is used to communicate with the
meter for the setting of EPM5500P energy, alarm
and meter settings. The software tool can be
used for real time monitoring of metered parameters, voltage and current harmonics, alarm
parameters, phase angle parameters and maximum/minimum statistical information with time
stamps.
15
Features
Part Name
1. Enclosure
Description
The EPM 5500P enclosure are made of high
strength anti-combustion engineering plastic
2. Front casing
3. LCD Display
4. Key
8. Installation clip
www.GEMultilin.com
EPM 5500P
Typical Wiring
15
3LN, 3CT
2LN, 2CT
2LN, 1CT
2LL, 3CT
2LL, 2CT
2LL, 1CT
1 Phase 2 Line
www.GEMultilin.com
4
EPM 5500P
1 Phase 3 Line
Dimensions
dimensions in mm
90.00
96.00
43.00
96.00
38.50
55.00
LINE
B C
Input/Output Option
1A FUSE
Terminal
Block
5 I11
Vn V3 V2 V1
A
11
12
13
NC
14
NC
19
20
6 I12
7 I21
9 I31
RS-485
8 I22
EPM 5500P
10 I32
LOAD
22
23
24
RELAY OUTPUTS
31
DIGITAL OUTPUTS
25
34
26
27
35
36
37
Vaux
15
Power supply
86-264VAC 50/60Hz
100-300VDC
33
38
V-
18
EPM 5500P
32
21
30
17
DIGITALINPUTS
R
S4
DIGITALINPUTS
S3
R
R
S1
NC
DIGITAL INPUTS
V+
16
DI
POWER
V+ V29 30
VDI power=15V
Digital input with intermal DI.Power supply.
S2
DIGITAL INPUTS
29
EPM 5500P
DI POWER
28
15
DIGITALINPUTS
DI3+ DI3- DI4+ DI425 26 27 28
S4
POWER
S2
S3
NC
DIGITALINPUTS
DI1+ DI1- DI2+ DI215 16 17 18
S1
12V<Vaux<30V,I<20mA
Digital input with extemal Aux.Power supply.
EPM 5500P
EPM 5500P
R12
32
R13
33
R14
34
38
31
37
Vaux<40V,I<30mA
Alam Output
RELAYOUTPUTS
Vaux
R11
36
DIGITAL OUTPUTS
38
www.GEMultilin.com
35
37
Vaux<40V,I<30mA
Pulse Output
Out
36
DIGITAL OUTPUTS
35
Vaux
EPM 5500P
Vaux
AV
or DC
Intermidiate Relay
EPM 5500P
Max. 500KVAC
20-100VAC with 20% over range
40-230VAC with 20% over range
45~65Hz
2 x Rated voltage ( continued )
2500VAC/1sec ( No cycling )
less than 0.2VA
AC True-RMS
Burden:
Measurement:
CURRENT INPUT
CT Primary:
CT Secondary:
9999Amp AC
5Amps
AC,with 20% over-range;
Min. initial current: 20mA
10A ( Continued ), 100A/1sec ( No Cycling)
< 0.1VA
AC True-RMS
Overload:
Burden:
Measurement:
METERING
Parameter
Voltage
Accuracy
Resolution
(% of full scale)
0.2%
0.1%
Current
Neutral current
Volt. Unbalance
Current unbalance
Power
Reactive Power
Apparent Power
Active Energy
Reactive Energy
Power Factor
Frequency
Power demand
Reactive power demand
Apparent power demand
Volt. THD
Current THD
0.2%
1.0%
1.0%
1.0%
0.5%
0.5%
0.5%
0.5%
0.5%
1.0%
0.2%
0.2%
0.5%
0.5%
2.0%
2.0%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1%
0.1KWh
0.1KVarh
0.01
0.01Hz
0.1%
0.1%
0.1%
0.01%
0.1%
Range
20-100VAC ( PT )
40-230VAC ( D )
1%-120% CT
1%-120%CT
0-200%
0-200%
0-9999MW
0-9999MVar
0-9999MVA
0-99999999.9KWh
0-99999999.9KVarh
0.02-1.00
45-65Hz
0-9999MW
0-9999MVar
0-9999MVA
0-100%
0-100%
COMMUNICATIONS
Type:
Baud Rate:
Protocol:
ENVIRONMENTAL
Humidity:
Temperature:
Dimension (mm):
Weight:
5%-95% non-condensing
o
o
-10 C -+70 C ( operation )
o
o
-40 C -+85 C ( storage )
96x96x72 ( Cut out90x90 )
350g
DIGITAL INPUT ( DI )
Optical Isolated Voltage:
Input Type:
Input resistance:
Input voltage:
Close voltage:
Max input current:
DI Aux Power:
2500VAC RMS
Wet contact
2K Ohm ( Typical )
5~30VDC
> 10VDC
20mA
15VDC/100mA
DIGITAL OUTPUT ( DO )
Output Form :
Optical Isolation:
Max operating voltage:
Max operating current:
Photo-MOS, NO
2500VAC ( RMS )
100VDC
50mA
100-240VAC or 100-300VDC
3W ( Max )
IEC 61010-1
Safety directive
EMC directive
Electrical Environment:
IEC 60255-22-1
High frequency disturbance
IEC 61000-4-2
Electrostatic discharge
IEC 61000-4-3
Radiated, radio-frequency immunity
IEC 61000-4-4
Fast transient disturbance
IEC 61000-4-5
Surge immunity
IEC 61000-4-6
Conducted disturbances immunity
IEC 61000-4-8
Power frequency magnetic field immunity
IEC 61000-4-11
AC supply dips & short interruptions
EN 55011/CISRR 11
Atmospheric Environment:
IEC 60068-2/-1.-2 cold/dry hot
IEC 60068-2-30
Damp heat, cyclic
IEC 60259
IP41 front panel
Mechanical Environment:
IEC 60255-21-1
Vibration
Accuracy:
IEC 62053-21
Class 1
Dimensions:
DIN43700
Note:
1. Directly measured Voltage: Accuracy0.2%;
Calculated Voltage: Accuracy0.5%.
2. Directly measured Current: Accuracy0.2%;
Calculated Current: Accuracy0.5%. See the following
table for the calculated parameters.
15
Calculated parameter
VL-L
V2VL-L
V3-1
I3
Ordering
PL5500
PL5500
0
IO
PT
D
Description
Metering, Max./Min. and Time Tag, Energy,
Demand, THD, Individual Harmonic, CF, THFF, K Factor
2 Digital Inputs
4 Digital Inputs(15VDC Provided by Meter), 2 Form
A Outputs, 2 Digital Outputs for Alarm or Pulse Output
20-100V(From PT)
40-230V(Not From PT)
www.GEMultilin.com
www.GEMultilin.com
6