Você está na página 1de 84

IG-159-GB

General Instructions

version 07

ekorRP
PROTECTION, METERING AND
CONTROL UNITS
LIB
20.09.2012

Transformer
Substations

Secondary Distribution
Switchgear

Primary Distribution
Switchgear

Protection and
Automation

Low Voltage
Boards

Distribution
Transformers

Legal Deposit: 1457/2012

CAUTION!
When MV equipment is operating, certain components are live, other parts may be in movement and some may reach high
temperatures. Therefore, the use of this equipment poses electrical, mechanical and thermal risks.
In order to ensure an acceptable level of protection for people and property, and in compliance with applicable environmental
recommendations, Ormazabal designs and manufactures its products according to the principle of integrated safety, based on
the following criteria:

Elimination of hazards wherever possible.

Where elimination of hazards is neither technically nor economically feasible, appropriate protection functions are
incorporated in the equipment.

Communication about remaining risks to facilitate the design of operating procedures which prevent such risks,
training for the personnel in charge of the equipment, and the use of suitable personal protection equipment.

Use of recyclable materials and establishment of procedures for the disposal of equipment and components so
that once the end of their service lives is reached, they are duly processed in accordance, as far as possible, with
the environmental restrictions established by the competent authorities.

Consequently, the equipment to which the present manual refers complies with the requirements of section 11.2 of the
forthcoming IEC standard 62271-1. It must therefore only be operated by appropriately qualified and supervised personnel, in
accordance with the requirements of standard EN 50110-1 on the safety of electrical installations and standard EN 50110-2 on
activities in or near electrical installations. Personnel must be fully familiar with the instructions and warnings contained in this
manual and in other recommendations of a more general nature which are applicable to the situation according to current
legislation.
The above must be carefully observed, as the correct and safe operation of this equipment depends not only on its design but
also on general circumstances which are in general beyond the control and responsibility of the manufacturer. More specifically:

The equipment must be handled and transported appropriately from the factory to the place of installation.

All intermediate storage should occur in conditions which do not alter or damage the characteristics of the
equipment or its essential components.

Service conditions must be compatible with the equipment rating.

The equipment must be operated strictly in accordance with the instructions given in the manual, and the
applicable operating and safety principles must be clearly understood.

Maintenance should be performed properly, taking into account the actual service and environmental conditions
in the place of installation.

The manufacturer declines all liability for any significant indirect damages resulting from violation of the guarantee, under any
jurisdiction, including loss of income, stoppages and costs resulting from repair or replacement of parts.
Guarantee
The manufacturer guarantees this product against any defect in materials and operation during the contractual period. In the
event that defects are detected, the manufacturer may opt either to repair or replace the equipment. Improper handling of this
equipment and its repair by the user shall constitute a violation of the guarantee.
Registered Trademarks and Copyrights
All registered trademarks cited in this document are the property of their respective owners. The intellectual property of this
manual belongs to the manufacturer.

In view of the constant evolution in standards and design, the characteristics of the elements contained in this manual are
subject to change without prior notification.
The validity of these characteristics, as well as the availability of components, are subject to confirmation by Ormazabals Technical
- Commercial Department.

IG-159-GB
version 07

20.08.2012 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

CONTENTS
1.

GENERAL DESCRIPTION ............................................................................................ 5


1.1. GENERAL FUNCTIONAL CHARACTERISTICS ......................................................... 6
1.2. PARTS OF THE UNIT.................................................................................................. 7
1.3. COMMUNICATIONS AND PROGRAMMING SOFTWARE ....................................... 11

2.

APPLICATIONS .......................................................................................................... 13
2.1. TRANSFORMER PROTECTION ............................................................................... 13
2.2. GENERAL PROTECTION ......................................................................................... 14
2.3. LINE PROTECTION................................................................................................... 15

3.

PROTECTION FUNCTIONS ....................................................................................... 16


3.1. OVERCURRENT ....................................................................................................... 16
3.2. THERMOMETER (EXTERNAL TRIP) ....................................................................... 19
3.3. EARTH ULTRASENSITIVE DEVICE ......................................................................... 19

4.

METERING FUNCTIONS ............................................................................................ 21


4.1. CURRENT.................................................................................................................. 21

5.

SENSORS ................................................................................................................... 21
5.1. CURRENT SENSORS ............................................................................................... 21

6.

TECHNICAL CHARACTERISTICS ............................................................................. 26


6.1. RATED VALUES ........................................................................................................ 26
6.2. MECHANICAL DESIGN ............................................................................................. 26
6.3. INSULATION TESTS ................................................................................................. 26
6.4. ELECTROMAGNETIC COMPATIBILITY ................................................................... 26
6.5. CLIMATIC TESTS ...................................................................................................... 27
6.6. MECHANICAL TESTS ............................................................................................... 27
6.7. POWER TESTS ......................................................................................................... 27
6.8. CE CONFORMITY ..................................................................................................... 27

7.

PROTECTION, METERING AND CONTROL MODELS ............................................ 28


7.1. DESCRIPTION OF MODELS vs. FUNCTIONS ......................................................... 28
7.2. RELAY CONFIGURATOR ......................................................................................... 30
7.3. ekorRPT UNITS ......................................................................................................... 31
7.4. ekorRPG UNITS......................................................................................................... 42

Page 3 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

8.

SETTING AND HANDLING MENUS ........................................................................... 51


8.1. KEYPAD AND ALPHANUMERIC DISPLAY .............................................................. 51
8.2. DISPLAY .................................................................................................................... 52
8.3. PARAMETER SETTING ............................................................................................ 54
8.4. TRIP RECOGNITION ................................................................................................. 59
8.5. ERROR CODES ......................................................................................................... 60
8.6. MENU MAP (QUICK ACCESS) ................................................................................. 61

9.

MODBUS PROTOCOL FOR ekorRP RANGE UNITS ................................................ 64


9.1. READ / WRITE FUNCTIONS ..................................................................................... 65
9.2. PASSWORD-PROTECTED REGISTER WRITING ................................................... 66
9.3. CRC GENERATION ................................................................................................... 66
9.4. REGISTER MAP ........................................................................................................ 67

10.

ANNEX A ..................................................................................................................... 71

11.

ANNEX B ..................................................................................................................... 77

Page 4 of 84

IG-159-GB
version 07
20.08.2012

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.08.2012 84

1. GENERAL DESCRIPTION
The ekorRP range of protection, metering and control units brings together an entire family
of different equipment, which depending on the model, may incorporate protection functions
as well as other functions such as local control, remote control, electrical parameter
metering, automation, etc., related to the current and future automation, control and
protection needs of Transformer and Switching Substations.
Its use in Ormazabals CGMCOSMOS, CGM-CGC and CGM.3 cubicle systems allows the
configuration of customised products for meeting the diverse needs of the different
installations.
The ekorRP protection, metering and control units have been designed to meet the national
and international standard requirements and recommendations that are applied to each of
the parts that make up the unit:
EN 60255, EN 61000, EN 62271-200, EN 60068,
EN 60044, IEC 60255, IEC 61000, IEC 62271-200, IEC 60068, IEC 60044

Page 5 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

Designed to be integrated in a cubicle, the ekorRP units also provide the following
advantages over conventional devices:
Reduction in handling of interconnections when installing the cubicle. The only
connection required is limited to MV cables.
Minimisation of the need to install control boxes on the cubicles.
Avoidance of wiring and installation errors; minimisation of commissioning time.
All the units are factory installed, adjusted and checked; each piece of equipment (relay
+ control + sensors) also undergoes a comprehensive check before being installed.
The final unit tests are carried out once the unit is incorporated in the cubicle before
delivery.
They protect a broad power range with the same model (e.g.: ekorRPG from 160 kVA
up to 15 MVA, in CGMCOSMOS system cubicles).

1.1. GENERAL FUNCTIONAL CHARACTERISTICS


All the relays of the ekorRP units include a microprocessor for
processing the signals from the metering sensors. They
process current metering by eradicating the influence of
transient phenomena and calculate the magnitudes needed for
to carry out protection functions. In addition, the efficient
electrical metering values, which provide the instantaneous
value of these installation parameters, are determined.
They are equipped with keypad for local display, setup and
operation of the unit, as well as communication ports to handle
these functions from a computer, whether locally or remotely.
A user-friendly design has been employed, so that the use of
the various menus is intuitive.
The current is measured by means of several current sensors
with a high transformation ratio, making it possible for the
same equipment to detect a wide range of power levels.
These transformers or current sensors maintain the accuracy
class in all of their rated range.

Page 6 of 84

IG-159-GB
version 07
20.08.2012

IG-159-GB
version 07

20.08.2012 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

The unit contains an events log where all of the latest trips made by the protection functions
are registered. In addition, the total number of operations is saved as well as the unit's
settings parameters. The local interface uses menus to provide the instantaneous values of
the current metering for each phase and zero-sequence current, as well as the setting
parameters, trip motives, etc. They can also be accessed via the communication ports.
From a maintenance perspective, the ekorRP units have a series of features that reduce the
time and the possibility of errors in the test and service restoration tasks. The main features
include some toroidal-core current transformers with larger diameters and test connections;
accessible and disconnectable terminal blocks for tests using current injection; and built-in
test contacts, even in the basic models.

1.2. PARTS OF THE UNIT


The parts that form the ekorRP protection, metering and control unit include the electronic
relay, current sensors, power supply and test board, selfpowered toruses (only for
selfpowered models) and the bistable trigger.

Page 7 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

Figure 1.2: Example of ekorRPT unit installation in fused protection cubicles

Page 8 of 84

IG-159-GB
version 07
20.08.2012

IG-159-GB
version 07

20.08.2012 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

1.2.1. Electronic Relay


The electronic relay has keys and a display to set and view
the protection, metering and control parameters. It includes
a seal on the SET key to ensure that once the settings
have been made they cannot be changed unless the seal is
broken.
The protection trips are registered on the display with the
following parameters: reason for tripping, fault current
value, tripping time and the time and date the event
occurred. Errors in the unit, such as a switch failure,
incorrect thermometer connection, low battery, etc., are
also shown permanently.
The 'On' LED is activated when the equipment receives
power from an external source or the self-powered
transformers. In this situation, the unit is operational to
perform the protection functions. If the 'On' LED is not
activated, only the unit's parameters can be viewed and/or
adjusted (function exclusively assigned to the relay's internal battery).
The current analog signals are conditioned internally by small and very accurate
transformers that isolate the electronic circuits from the rest of the installation.
The equipment has two communication ports, one on the front used for local configuration
(RS232), and another one on the rear used for remote control (RS485). The standard
communication protocol for all models is MODBUS. Others may be used depending on the
application.

1.2.2. Current Sensors


The current sensors are toroidal-core current
transformers with a 300/1 A or 1000/1 A ratio,
depending on the models. Their range of action is the
same as the switchgear where they are installed. They
are factory-installed in the cubicle bushings, which
significantly simplifies the on-site assembly and
connection. This way, once the MV cables are
connected to the cubicle, the installation protection is
operational. There are no sensor installation errors,
due to earthing grids, polarities, etc. since they are
previously installed and tested at the factory.

Current
sensors

Bushing

The inner diameter of the toroidal-core current


transformers is 82 mm, which means they can be used
in cables of up to 400 mm2 without any problems for performing maintenance testing
afterwards.
If the equipment is selfpowered, the toroidal transformers are equipped with some anchorage
points to place them in the same area as the metering transformers, thus forming a single,

Page 9 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

compact block. These transformers supply 1 W when the primary current is 5 A. This power
is enough to allow the units to function correctly.
All the current sensors have an integrated protection against the opening of secondary
circuits, which prevents overvoltages.

1.2.3. Power Supply and Test Board


The selfpowered equipment's power supply board prepares the selfpowered
transformers' signal and converts it into a DC signal to safely power the equipment. The
transformers permanently feed power from 5 to 630 primary amps to the board.
It also has a 230 Vac input with 10 kV level of insulation. This input is for direct connection to
the Transformer Substation's LVB.
The power supply board of models with auxiliary power supply has an input for
connecting both the AC (24 to 110 Vac) and DC (24 to 125 Vdc) power supply. The board
prepares the signal, converting it into a DC signal
suitable for safely powering the equipment.
Furthermore, both types of board have a built-in
protection trip test circuit as well as connectors for
carrying out current injection functional tests during
maintenance and checking operations. The units also
have a protection device for absorbing the excess
energy produced by the transformers when there are
short-circuits up to 20 kA.

1.2.4. Bistable trigger


The bistable trigger is an electromechanical actuator that is
integrated into the switch driving mechanism. This trigger
acts upon the switch when there is a protection trip. It is
characterised by the low actuation power it requires for
tripping. This energy is received in the form of pulses
lasting 50 ms and with an amplitude of 12 V. When there is
a fault, these pulses are repeated every 400 ms to ensure
that the switch opens.

Page 10 of 84

IG-159-GB
version 07
20.08.2012

IG-159-GB
version 07

20.08.2012 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

1.3. COMMUNICATIONS AND PROGRAMMING SOFTWARE


All the ekorRP units have two serial communication ports. The standard RS232 front port is
used to set the local parameters with the ekorSOFT program[1]. At the rear, there is an
RS485 port which is used for remote control.
The standard communication protocol implemented in all equipment is MODBUS-RTU
(binary) transmission mode, although other specific protocols can be implemented depending
on the application. This protocol has the advantage of greater information density than other
modes, resulting in a higher transmission rate for the same communication speed. Each
message must be transmitted as a continuous string and the silences are used to detect the
end of the message.

[1]

For more information about the ekorSOFT program, consult Ormazabals IG-155 document.

Page 11 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

The ekorSOFT setup program has three main operating modes:


Display: indicates the unit status, including electrical
measurements, current settings, date and time.
User Settings: protection parameter change is enabled.
Event Log: the parameters of the final and penultimate
trip are shown as well as the total number of trips made
by the protection unit.
Minimum system requirements for installing and using the
ekorSOFT software:
Processor: Pentium II
RAM: 32 Mb
Operating System: MS WINDOWS
CD-ROM / DVD
RS-232 serial port

Page 12 of 84

IG-159-GB
version 07
20.08.2012

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.08.2012 84

2. APPLICATIONS
2.1. TRANSFORMER PROTECTION
The distribution transformers require various
protection
functions.
Their
selection
depends primarily on the power and level of
responsibility they have in the installation.
As an example, the protection functions that
must be implemented to protect distribution
transformers with a power rating between
160 kVA and 2 MVA are the following:
50

Instantaneous
phase
overcurrent. Protects against shortcircuits between phases in the primary
circuit, or high value short-circuit
currents between phases on the
secondary side. This function is
performed by the fuses when the
protection cubicle does not include a
circuit-breaker.
51 Phase overload. Protects
against excessive overloads, which
can deteriorate the transformer, or
against short-circuits in several turns
of the primary windings.
50N Instantaneous earth fault. Protects
against phase to earth short-circuits or
secondary winding short-circuits, from the
primary interconnections and windings.
51N Earth Leakage. Protects against highly
resistive faults from the primary to earth or to
the secondary.
49T Thermometer. Protects
excessive transformer temperature.

against

Protection units that include the above mentioned


functions:

Unit
ekorRPT
ekorRPG

System
CGMCOSMOS

Systems
CGM-CGC / CGM.3

Type of cubicle
Fuse-combination
switch

Power ranges to protect

Power ranges to protect

50 kVA...2000 kVA

50 kVA...1250 kVA

Circuit-breaker

50 kVA...15 MVA

50 kVA...25 MVA

See tables 7.3.2 and 7.4.2

Page 13 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07
20.08.2012

2.2. GENERAL PROTECTION


The client supply installations require general
protection to ensure that an installation is
disconnected from the rest of the network in the
event of a fault. In this way, the Utility's supply
line will remain energised and other clients will
remain unaffected. It also protects the client's
installation by disconnecting it from the power
source in the event of a fault.
In this type of protection, all the faults detected
in the substation's main circuit breaker should
be simultaneously detected in the transformer
substations so that they can be cleared before
the line trips (protection selectivity).
50 Instantaneous phase overcurrent. Protects against short-circuits between
phases.
51 Phase overload. Protects against excessive overloads, which can deteriorate the
installation. It is also used as a limiting device to control the supply's maximum power.
50N Instantaneous earth fault. Protects against phase-to-earth short-circuits.
51N Earth leakage. Protects against highly resistive faults between phase and earth.
The following protection units provide the above-mentioned functions:
System
CGMCOSMOS

Systems
CGM-CGC / CGM.3

Unit
ekorRPT

Type of cubicle
Fuse-combination switch

Power ranges to protect


50 kVA...2000 kVA

Power ranges to protect


50 kVA...1250 kVA

ekorRPG

Circuit-breaker

50 kVA...15 MVA

50 kVA...25 MVA

See tables 7.3.2 and 7.4.2

Page 14 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.08.2012 84

2.3. LINE PROTECTION


The purpose of the line protection is to isolate this
part of the network in case of fault, without it
affecting the rest of the lines. Generally, it covers
any fault that originates between the Substation,
or Switching Substation, and the consumption
points.
The types of fault that occur in these areas of the
network primarily depend on the nature of the
line, overhead line or cable and the neutral used.
In networks with overhead lines, most faults are transitory. Hence, many line reclosings are
effective.
On the other hand, in case of phase-to-earth faults in overhead lines, when the ground
resistance is very high, the zero-sequence fault currents have a very low value In these
cases, an ultrasensitive neutral current detection is required.
The underground cables have earth coupling capacities, which causes the single phase
faults to include capacitive currents. This phenomenon makes detection difficult in isolated or
resonant earthed neutral networks and thus requires the use of the directional function.
Line protection is mainly accomplished by the following functions:
50 Instantaneous phase overcurrent. Protects against short-circuits between
phases.
51 Phase overload. Protects against excessive overloads, which can deteriorate the
installation.
50N Instantaneous earth fault. Protects against phase-to-earth short-circuits.
51N Earth leakage. Protects against highly resistive faults between phase and earth.
50Ns Ultrasensitive earth instantaneous overcurrent. Protects against phase to
earth short-circuits of very low value.
51Ns Ultrasensitive earth leakage protection. Protects against highly resistive
faults between phase and earth of very low value.
Unit that includes the above mentioned functions:
CGMCOSMOS / CGM-CGC / CGM.3 systems
Unit
ekorRPG

Type of cubicle
Circuit-breaker

Maximum rated current


630 A

Page 15 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

3. PROTECTION FUNCTIONS
3.1. OVERCURRENT
The units have an overcurrent function for each one of the phases (3 x 50-51) and,
depending on the model, they may have another one for earth (50N-51N). The implemented
protection curves are the ones listed in standard IEC 60255.
Overcurrent functions that can be performed depending on the model:
Overload multicurve protection for phases (51).
Protection of phase-to-earth multicurve faults (51N).
Short-circuit protection (instantaneous) at a defined time between phases (50).
Short-circuit protection (instantaneous) at a defined time between phase and earth
(50N).
Meaning of the curve parameters for phase settings:
t(s) Theoretical tripping time for a fault which evolves with a constant current value.
I Actual current flowing through the phase with the largest amplitude.
In
Rated setting current.
I> Withstand overload increment.
K Curve factor.
I>> Short-circuit current factor (instantaneous).
T>> Short-circuit delay time (instantaneous).
Pick-up current value of NI, VI, and EI curves = 1.1 x In x I>
Pick-up current value of DT curve = 1.0 x In x I>
Instantaneous pick-up current value = In x I> x I>>
In the case of earth settings, the parameters are similar to the phase settings. Each of
them is described below.
to(s) Theoretical tripping time for an earth fault which evolves with a constant
current value I0.
Io Actual current flowing to earth.
In Rated phase setting current.
Io> Withstand earth leakage factor (phase).
Ko Curve factor.
Io>> Short-circuit current factor (instantaneous).
To>> Short-circuit delay time (instantaneous).
Pick-up current value of NI, VI, and EI curves = 1,1 x In x Io>
Pick-up current value of DT curve = 1,0 x In x Io>
Instantaneous pick-up current value = In x Io> x Io>>

Page 16 of 84

IG-159-GB
version 07
20.08.2012

IG-159-GB
version 07

20.08.2012 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

Page 17 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

Page 18 of 84

IG-159-GB
version 07
20.08.2012

IG-159-GB
version 07

20.09.2012 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

3.2. THERMOMETER (EXTERNAL TRIP)


The equipment has an input for connecting volt-free contacts and tripping the switch. This
input is protected against erroneous connections (e.g. 230 Vac) showing an error code on the
display when this anomaly occurs.
The switch trips when the volt-free contact is
closed for at least 200 ms. This prevents
untimely tripping due to external disturbances.
External tripping protection is disabled when
all of the overcurrent protection functions are
disabled (for firmware version 18 or later).
In this situation, the relay will not trip the
switch but a flashing arrow will appear at the
top of the display screen to show that the
external trip contact is closed (see section
8.4).
The purpose of this function is to protect the
transformers' maximum temperature. The trip input is associated to contact of the
thermometer which measures the oil's temperature and when the maximum set value is
reached, its associated contact closes and the switch trips. Unlike conventional coils, it has
the advantage of not having low-voltage network connections with the consequent
overvoltages generated in the control circuits.
This trip input can also be associated to output contacts of remote control terminals, alarms
and auxiliary relays responsible for opening the switch.

3.3. EARTH ULTRASENSITIVE DEVICE


This protection corresponds to a particular type of
overcurrent protections. It is primarily used in
networks with isolated or resonant earthed neutral,
where the phase-to-earth fault current value
depends on the system cable capacity value and
on the point in which the fault occurs. Generally, in
Medium Voltage private installations with short
cable stretches, simply determine a minimum zerosequence current threshold at which the protection
must trip.

0-sequence
toroidal
transformer

Page 19 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

The current flowing to earth is detected using a toroidal-core current transformer which
covers the three phases. In this way, the metering is independent from the phase current,
thus avoiding errors in the phase metering transformers. In general, this type of protection
must be used when the set earth current is less than 10% of the rated phase current (for
example: for a rated phase current of 400 A with earth faults below 40 A).
On the other hand, in the lines, whose cable stretches are usually long, it is necessary to
identify the fault direction. Otherwise, trips can occur due to capacitive currents from other
lines, when there is not any fault in the line.
The available curves are: normally inverse (NI), very inverse (VI), extremely inverse (EI)
and defined time (DT).
The setting parameters are the same as in the earth faults of the overcurrent functions
(section 3.1 Overcurrent), with the exception that factor Io> is replaced with the value
directly in amps Ig. This way, this parameter can be set to very low earth current values,
regardless of the phase setting current.
Pick-up current value of NI, VI, and EI curves = 1.1x Ig
Pick-up current value of DT curve = Ig
Instantaneous pick-up current value = Ig x Io>>

Page 20 of 84

IG-159-GB
version 07
20.09.2012

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

4. METERING FUNCTIONS
4.1. CURRENT
The current values measured by the ekorRP units
correspond to the efficient values of each of the
phases I1, I2 and I3. Eight samples from a halfperiod are used and the mean of five consecutive
values is calculated. This measurement is updated
every second. It offers Class 1 meter accuracy,
from 5 A up to 120% of the current sensors
maximum rated range. The zero-sequence current
measurement Io is performed in the same way as
the phase currents.
Current meters: I1, I2, I3 and Io

5. SENSORS
5.1. CURRENT SENSORS
The electronic current transformers are designed for
optimal adaptation to digital equipment technology,
with a slight modification of the secondary interface.
Therefore, the protection, metering and control
equipment for these sensors operate with the same
algorithms and with the same consistency as
conventional devices.
The low power outputs from the sensors can be
adapted to standard values using external amplifiers.
In this way, you can use conventional equipment or
electronic relays.

Page 21 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07
20.09.2012

Main advantages derived from the use of sensor based systems:


Small volume.The decreased power consumption of these transformers allows their
volume to be drastically reduced.
Improved accuracy. Signal acquisition is much more accurate due to high
transformation ratios.
Wide range. When there are power increases in the installation, the sensors do not
have to be replaced with ones having a greater ratio.
Greater safety. The open-air live parts disappear, increasing personnel safety.
Greater reliability. The full insulation of the whole installation provides greater levels
of protection against external agents.
Easy maintenance. The sensors do not need to be disconnected when the cable or
cubicle is being tested.

5.1.1. Functional Characteristics of Current Sensors


The current sensors are toroidal-core current transformers with a high transformation ratio
and low rated burden. These sensors are encapsulated in self-extinguishing polyurethane
resin.
Phase toroidal current transformers
Ratio
Metering range
Protection
Metering
Burden
Thermal current
Dynamic current
Saturation current
Frequency
Insulation
Outer diameter
Inner diameter
Height
Weight
Polarity
Encapsulation
Thermal class
Reference standard

Page 22 of 84

Range 5-100 A
300 / 1 A
5 A to 100 A Extd. 130%
5P20
Class 1
0,18 VA
20 kA
50 kA
7,800 A
50-60 Hz
0,72 / 3 kV
139 mm
82 mm
38 mm
1.350 kg
S1 blue, S2 brown
Self-extinguishing polyurethane
B (130 C)
IEC 60044-1

Range 15-630 A
1000 / 1 A
15 A to 630 A Extd. 130%
5P20
Class 1
0.2 VA
20 kA
50 kA
26,000 A
50-60 Hz
0,72 / 3 kV
139 mm
82 mm
38 mm
1.650 kg
S1 blue, S2 brown
Self-extinguishing polyurethane
B (130 C)
IEC 60044-1

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

Toroidal power transformers


Ratio
Power supply range
Thermal current
Dynamic current
Power
Frequency
Insulation
Outer dimensions
Inner dimensions
Height
Weight
Polarity
Encapsulation
Thermal class
Phase toroidal
transformer

ekorRPT / ekorRPG
200/1 A with centre tap (100 + 100 A)
5 A to 630 A
20 kA
50 kA
0.4 VA to 5 A
50-60 Hz
0,72 / 3 kV
139 mm
82 mm
38 mm
1.240 kg
S1 blue, S2 brown
Self-extinguishing polyurethane
B (130C)
0-sequence toroidal
transformer

Page 23 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

5.1.2. Vector Sum/Zero-SequenceWiring


The wiring of the aforementioned transformers is performed in two different ways, depending
on whether they have a zero-sequence toroidal current transformer installed or not. As a
general rule, the zero-sequence toroidal transformer is used when the earth fault current is a
below 10% of the phase current rating.
R

Page 24 of 84

DETECTION OF EARTH CURRENT BY VECTOR SUM

IG-159-GB
version 07
20.09.2012

IG-159-GB
version 07

20.09.2012 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

Zero-sequence Toroidal Current Transformers

Ratio
Metering range
Protection
Metering
Burden
Thermal current
Dynamic current
Saturation current
Frequency
Insulation
Outer dimensions
Inner dimensions
Height
Weight
Polarity
Encapsulation
Thermal class
Reference standard

Range 5-100 A

Range 15-630 A

300 / 1 A
0.5 A to 50 A Extd. 130%
5P10
Class 3
0.2 VA
20 kA
50 kA
780 A
50-60 Hz
0,72 / 3 kV
330 x 105 mm
272 x 50 mm
41 mm
0.98 kg
S1 blue, S2 brown
Self-extinguishing polyurethane
B (130 C)
IEC 60044-1

1000 / 1 A
0.5 A to 50 A Extd. 130%
5P10
Class 3
0.2 VA
20 kA
50 kA
780 A
50-60 Hz
0,72 / 3 kV
330 x 105 mm
272 x 50 mm
41 mm
0.98 kg
S1 blue, S2 brown
Self-extinguishing polyurethane
B (130 C)
IEC 60044-1

Page 25 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07
20.09.2012

6. TECHNICAL CHARACTERISTICS
6.1. RATED VALUES
Power supply

Current inputs

Accuracy
Frequency
Output contacts
Temperature
Communications

AC
DC
Selfpowered
Consumption
Primary phase
Earth

Voltage
Current
Switching power
Operating
Storage
Front port

24 Vac...110 Vac+/-30%
24 Vdc...125 Vdc +/-30%
>5 A, 230 Vac +/-30%
< 1 VA
5 A...630 A (depending on model)
0.5 A..0.50 A (depending on
model)
20 kA / 50 kA
0.1
5% (minimum 20 ms)
Class 1 / 5P20
50 Hz; 60 Hz +/-1%
250 Vac
10 A (AC)
500 VA (resistive load)
- 40 C to + 70 C
- 40 C to + 70 C
DB9 RS232

Rear port
Protocol

RS485 (5 kV) RJ45


MODBUS (RTU)

I thermal/dynamic
Impedance
Time delay
Metering / Protection

6.2. MECHANICAL DESIGN


IP rating

Dimensions (h x w x d):
Weight
Wiring

Terminals
In cubicle

IP2X
IP3X
IP4X (according to IEC 60255-27)
IK06 (according to EN 50102)
146 x 47 x 165 mm
0.3 kg
0.5...2.5 mm2

Cable/Termination

6.3. INSULATION TESTS


IEC 60255-5

Insulation resistance
Electric strength
Voltage impulses:

standard
differential

500 VDC: > 10 G


2 kVac; 50 Hz; 1 min
5 kV; 1.2/50 s; 0.5 J
1 kV; 1.2/50 s; 0.5 J

6.4. ELECTROMAGNETIC COMPATIBILITY


IEC 60255-11
IEC 60255-22-1
IEC 60255-22-2
IEC 60255-22-3
IEC 60255-22-4
IEC 60255-22-5

Page 26 of 84

Voltage dips
Ripple
Damped wave 1 MHz
Electrostatic discharges
(IEC 61000-4-2, class IV)
Radiated fields
(IEC 61000-4-3, class III)
Bursts - Fast transients
(IEC 61000-4-4)
Overvoltage pulses
(IEC 61000-4-5)

200 ms
12 %
2.5 kV; 1 kV
8 kV air
6 kV contact
10 V/m
4 kV
4 kV; 2 kV

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

IEC 60255-22-6

Induced radio frequency


signals (IEC 61000-4-6)
Magnetic fields

IEC 61000-4-8
IEC 61000-4-12
IEC 60255-25

Sinusoidal damped wave


Electromagnetic emissions
(EN61000-6-4)

150 kHz..0.80 MHz


100 A/m; 50 Hz constant
1000 A/m; 50 Hz short- time (2 s)
2.5 kV; 1 kV
150 kHz to 30 MHz (conducted)
30 MHz to 1 GHz (radiated)

6.5. CLIMATIC TESTS


IEC 60068-2-1

Slow changes. Cold

IEC 60068-2-2

Slow changes. Heat

IEC 60068-2-78
IEC 60068-2-30

Damp heat, continuous test


Damp heat cycles

- 40 C; 16 hrs.
- 40 C; 16 hrs.
+ 60 C; 16 hrs.
+ 70 C; 16 hrs.
+ 40 C; 93%; 10 days
+ 55 C; 6 cycles

6.6. MECHANICAL TESTS


IEC 60255-21-1
IEC 60255-21-2
IEC 60255-21-3

Sinusoidal vibration. Response


Sinusoidal vibration. Endurance
Impacts. Response
Impact. Endurance
Shock. Endurance
Seismic tests

10 - 150 Hz; 1 g
10 - 150 Hz; 2 g
11 ms; 5 g
11 ms; 15 g
16 ms; 10 g
1 - 38 MHz, 1g vertical,
0.5 g horizontal

6.7. POWER TESTS


IEC 60265
IEC 60265
IEC 60265
IEC 60056

No-load cable making and


breaking
Mainly active load making and
breaking
Earth faults
No-load transformer making and
breaking
Short-circuit making and breaking

24 kV/50 A/ cos = 0.1


24 kV/630 A/ cos = 0,7
24 kV/200 A/50 A
13.2 kV /250 A/1250 kVA
20 kA / 1s

6.8. CE CONFORMITY
This product complies with the European Union directive 2004/108/EC on electromagnetic
compatibility, and with the IEC 60255 international regulations. The ekorRP unit has been designed
and manufactured for use in industrial areas, in accordance with EMC standards. This compliance
results from a test performed according to article 10 of the directive, and included in protocol CE26/08-43-EE-1.

Page 27 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

7. PROTECTION, METERING AND CONTROL MODELS


7.1. DESCRIPTION OF MODELS vs. FUNCTIONS
ekorRPT
Distribution transformer protection unit installed in fuse-combination
switch cubicles. The electronic unit performs all the protection functions
except for the high value polyphase short-circuits that occur in the
transformers primary. It has inputs and outputs for switch monitoring and
control.
The unit can protect a power range from 50 kVA up to 2000 kVA in
CGMCOSMOS system cubicles and from 50 kVA up to 1250 kVA in
CGM-CGC and CGM.3 system cubicles.

ekorRPG
Distribution general protection unit installed in circuit-breaker cubicles.
The main usage applications are: general protection of lines, private
installations, transformers, capacitor stacks, etc.
They can protect a power range from 50 kVA up to 400 kVA (630 kVA for
CGM-CGC and CGM.3 system cubicles), when they include toroidal-core
current transformers from 5 A to 100 A. With 15 A to 630 A toroidal-core
current transformers, they offer a power range between 160 kVA and 15
MVA (25 MVA for CGM-CGC and CGM.3 system cubicles).

Page 28 of 84

IG-159-GB
version 07
20.09.2012

Protection, Metering and Control Units


ekorRP
General
Phase current sensors
Earth (zero-sequence) current sensor
Voltage sensors
Digital Inputs
Digital outputs
Power supply 24 Vdc to 125 Vdc / 24 Vac to 110 Vac
Self powered (> 5 A, + 230 Vac +/- 30%)
Protection
Phase overcurrent (50-51)
Earth leakage overcurrent (50N-51N)
Ultrasensitive earth leakage protection (50Ns-51Ns)
Thermometer (49T)
Communications
MODBUS-RTU
PROCOME
RS-232 configuration port
RS-485 port for remote control
ekorSOFT setup and monitoring program
Indications
Tripping cause indication
Error display
Test
Test blocks for current injection
Output contact for test
Measurements
Current
Presence / Absence of voltage

ekorRPG

20.09.2012 84

ekorRPT

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

3
Op
No
2
2
Op
Op

3
Op
No
2
2
Op
Op

Yes
Op
Op
Yes

Yes
Op
Op
Yes

Yes
No
Yes
Yes
Op

Yes
No
Yes
Yes
Op

Yes
Yes

Yes
Yes

Yes
Yes

Yes
Yes

Yes
No

Yes
No

Op - Optional

Page 29 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

7.2. RELAY CONFIGURATOR


NOTE
Not all combinations resulting from this configurator are possible.
For the availability of other models, please consult Ormazabal's Technical Commercial Department.
To select the ekorRP unit on the basis of the installation characteristics, the following
configurator will be used:
ekorRP

Type:
G For protection cubicle with circuit-breaker
T For fuse protection cubicle
Protection functions:
10 Three phases (3 x 50/51)
20 Three phases and neutral (3 x 50/51 + 50N/51N)
30 Three phases and sensitive neutral (3 x 50/51 + 50Ns/51Ns)
Toroidal-core current transformers:
0 Without toruses
1 Range 5-100 A
2 Range 15-630 A
Power supply:
A Self powered
B Auxiliary power supply (Battery, UPS, etc.)
Example: In the case of a selfpowered relay for a protection cubicle with a circuit-breaker,
with functions 3 x 50/51 + 50Ns/51Ns and toroidal-core current transformers with a range of
5-100 A, the corresponding configurator would be ekorRPG-301A.

Page 30 of 84

IG-159-GB
version 07
20.09.2012

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

7.3. ekorRPT UNITS


7.3.1. Functional description
The ekorRPT protection, metering and control unit is used for the protection of distribution
transformers. It is installed in fuse-combination switch cubicles so the electronic system
performs all the protection functions, except high polyphase short-circuit values, which are
cleared by the fuses.
When an overcurrent that is within the values that the load break switch can open is
detected, the relay acts upon a low power bistable trigger that opens the switch. If the fault
current is greater than the breaking capacity of the load break switch[2], the switch trip is
blocked so that the fuses will blow. On the other hand, the equipment is disconnected and
the fuses do not remain energised.

TRANSFORMER PROTECTION

GENERAL PROTECTION
(MV client supply)

[2 ]

1200 A for CGMCOSMOS-P, 480 A for CGM-CMP-F, 36 kV range, and CGM.3 and 300 A for CGM-CMP-F, 24
kV range.

Page 31 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07
20.09.2012

7.3.2. Technical Characteristics


The ekorRPT unit is used to protect the following transformer power ratings.
CGMCOSMOS System
Line
voltage

( )

[kV]
6,6
10
13,8
15
20

Fuse Rated
Voltage
[kV]
3/7,2
6/12
10/24
10/24
10/24

MINIMUM Transformer Power


Fuse Rating [A]
16
10
16
16
16

[kVA]

MAXIMUM Transformer Power


Fuse Rating [A]
( )

50
100
100
125
160

160
160 ()
100
125 ()
125

[kVA]
1250
1250
1250
1600
2000

442 mm cartridge,
125 A SIBA SSK Fuse

( )

CGM-CGC / CGM.3 System


Line
voltage

( )

[kV]
6,6
10
13,8
15
20
25
30

Fuse Rated
Voltage
[kV]
3/7,2
6/12
10/24
10/24
10/24
24/36
24/36

MINIMUM Transformer Power


Fuse Rating [A]
16
16
10
16
16
25
25

[kVA]
50
100
100
125
160
200
250

MAXIMUM Transformer Power


Fuse Rating [A]
( )

160
125
63
63
63
80 (2)
80 (2)

[kVA]
1000
1250
800
1000
1250
2000
2500

442 mm cartridge
SIBA SSK fuse (check)

(2)

Selection process for the ekorRPT unit protection parameters in CGMCOSMOS-P cubicles:
1. Determine the required fuse rating to protect the transformer in accordance with the fuse
table in Ormazabals document IG-078. The maximum ratings that can be used are 160 A
for voltages up to and including 12 kV, and 125 A for voltages up to and including 24 kV.
2. Calculate the transformer rated current In = S/3xUn.
3. Define the continuous overload level I>. Normal values in transformers of up to 2000 kVA
are 20% for distribution installations and 5% for power generation installations.
4. Select the transitory overload curve. Coordination between relay curves and LV fuses is
performed with the EI type curve.
5. Define the delay time in transitory overload K. This parameter is defined by the
transformers thermal constant. This way, the greater the constant, the longer it takes for
the transformers temperature to increase under an overload condition; and therefore, the
protection trigger can be delayed longer. The usual value for distribution transformers is
K = 0.2, which means that it trips in 2 s if the overload is 300% in the EI curve.
6. Short-circuit level I>>. The maximum value of the transformers magnetisation current
must be determined. The current peak produced when a no-load transformer is
connected, due to the effect of a magnetised nucleus, is several times greater than the
rated current. This peak value, up to 12 times the rated value (10 times for more than

Page 32 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

1000 kVA) has a very high harmonic content, so its fundamental 50 Hz component is
much less. Therefore, a usual setting value for this parameter is between 7 and 10.
7. Instantaneous time delay T>>. This value corresponds with the protection trip time in the
event a short-circuit occurs. It depends on the coordination with other protections and the
usual values are between 0.1 and 0.5 s. If the short-circuit value is high, the fuses will act
in the time determined by their characteristic curve.
8. Determine the current value in case of secondary three-phase short-circuit. This fault
must be cleared by the fuses, and it corresponds with the intersection points maximum
value between the relay and the fuse curves. If the intersection point is greater than the
secondary short-circuit value, the settings must be adjusted to meet this requirement.
To select the ekorRPT unit protection parameters in CGM-CMP-F and CGM.3-P cubicles,
the steps to follow are similar to those proposed in the paragraphs above, except for the first
step. The fuse rating required to protect the transformer is determined according to the fuse
table of Ormazabals documents IG-034 and IG-136 respectively. Please take into
consideration that the minimum protection powers are listed in the table above.
In case of protecting a transformer with following characteristics in CGMCOSMOS cubicle
system:
S = 1250 kVA, Un =15 kV and Uk = 5%
Follow the procedure below for proper coordination between the fuses and the protection
relay:
Fuse selection according to IG-078. 10/24 kV 125 A fuse
Rated current. In = S/3 x Un = 1250 kVA/3 x 15 kV 48 A
Continuous withstand overload 20%. In x I> = 48 A x 1.2 58 A
Extremely Inverse Curve type. E.I.
Transitory overload factor. K =0.2
Short-circuit level. In x I> x I>> = 48 A x 1.2 x 7 404 A
Instantaneous time delay T>> = 0,4 s
Secondary short-circuit. Ics = In x 100/ Uk = 48 A x 100 / 5 960 A

Page 33 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

Figure 7.1: Example for SIBA SSK fuse

The earth unit setting depends on the characteristics of the line where the unit is installed. In
general, the earth fault values are high enough to be detected as overcurrent. Even in
isolated or resonant earthed neutral networks, the fault value in transformer protection
installations is clearly different from the capacitive currents of the lines. This way, the
transformer protection ekorRPT units are used in isolated neutral networks that do not
require the directional function. The values of the setting parameters must guarantee
selectivity with the main switch protections. Given the variety of protection criteria and types
of neutral used in the networks, it does not exist a single parameterisation; each case
requires a specific parameterisation. For transformers up to 2000 kVA, the settings below are
given as a general example. It must be ensured that they properly apply to the protections
upstream (general, line or main switch protections, among others.)

Page 34 of 84

IG-159-GB
version 07
20.09.2012

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

Phase
setting
Setting
of
Earth
( )

Rated Current

Time delayed

Instantaneou
s

I>

I>>

T>>

In=S/3xUn = 48 A

EI

DT

1,2

0,2

0,4

Type of Neutral

Time delayed

Instantaneou
s

Io>

Ko

Solid or impedant

NI

DT

0,2

0,2

0,4

Isolated or
resonant

NI

DT

0.1/Ig=2 A(*)

0,2

0,4

Io>> To>>

* In case a zero-sequence toroidal transformer is used

Page 35 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07
20.09.2012

7.3.3. Installation in a Cubicle


The integral parts of the ekorRPT units are the electronic relay, the power supply and test
board, the bistable trigger and the current sensors.

The electronic relay is fixed to the cubicle driving mechanism using anchors. The front of the
equipment, which contains the components of the user interface, display, keys,
communication ports, etc., is accessible from the outside without the need to remove the
mechanism enclosure. The rear contains the X1 and X2 connectors, as well as the wiring
that connects it to the power supply board.
.

CGM.3-F

Page 36 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

All of the signals that come from the relay go through the board. Hence, the board enables
the unit to be checked. Furthermore, there is a volt-free contact (J3) which is activated
simultaneously with the relay trip. This enables to use conventional current injection
equipment for testing the protection relays.
The selfpowered transformers are also connected to the power supply board using the J7
connector in the selfpowered relays. The signal transformers are connected to the board's J8
connector, the function being to inject current into the secondary in order to test the relay.
The ekorRPT protection, metering and control unit has three connectors (J1, J3 and J4) to
which the user can connect. They are situated on the upper part of the power supply and test
board and their functions are as follows:
Connector

Name

J1

EXT. TRIP

J3

TRIP

J4

V. AUX

Functions
It must be connected to an NO, volt-free
contact. When it is activated, the protection
device trips if an overcurrent protection
function is activated.
This is an NO, volt-free contact which is
activated when the protection device is
tripped. It also works in self powered mode.
Auxiliary power supply input:
230 Vac for selfpowered units and 24 to
125 Vdc or 24 to 110 Vac for those with
auxiliary power supply
(10 kV insulated in relation to the rest of the
equipment, in self powered models).

Normal use
Transformer THERMOMETER.
Protection unit TEST.
Trip SIGNAL for remotelycontrolled installations
Relay power supply (LVB of the
transformer to protect, battery,
etc.).

Page 37 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

7.3.4. ekorRPT Electrical Diagram

NOTE
For more details, please see electrical diagram No. 990042, which shows the electrical
connections between the different parts of the ekorRPG unit and the cubicle.

Page 38 of 84

IG-159-GB
version 07
20.09.2012

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

7.3.5. Installation of Toroidal-core current transformers


The installation of toroidal-core current transformers requires special attention. It is the main
cause of untimely tripping problems, and its improper operation can cause trips that go
undetected during commissioning. Aspects that must be considered in the installation:
The toroidal-core current transformers are installed on the outgoing cables of the
cubicle. The inner diameter is 82 mm, which means that MV cables can easily pass
through the inside.
The earthing screen MUST go through the
toroidal-core current transformer when it
comes out of the part of cable remaining
above the toroidal-core current transformer.
In this case, the braided pair goes through
the inside of the toroidal-core current
transformer before it is connected to the
earthing of the cubicle. The braided pair must
not touch any metal part, such as the cable
support or other areas of the cable
compartment, before it is connected to the
cubicle's earth.

Earth screen: it must pass through


the inside of the toroidal-core

The earthing screen must NOT go through the toroidal-core current transformer when
it comes out of the part of cable remaining under the toroidal-core current transformer.
In this case, the braided pair is connected directly to the earthing collector of the
cubicle. If there is no braided pair for the earthing screen because it is connected at the
other end (as in metering cubicles), the twisted pair should also not go through the
toroidal-core current transformer.

7.3.6. Checking and Maintenance


The ekorRPT protection, metering and control unit is designed to perform the operating test
necessary for both commissioning and regular maintenance checks. Several levels of checks
are available depending on the possibility of interrupting service and accessing the MV
cubicle cable compartment.
Check through the primary: This case corresponds to the tests that are performed on
the equipment when it is completely shut down, since it involves actuating the switchdisconnector and earthing the cubicle outgoing cables. When current is injected
through the toroidal-core current transformers, you must check that the protection
opens the switch within the selected time. In addition, you must make sure that the
tripping indications are correct and that all the events are being recorded in the history
log.
CAUTION
To perform this check, the unit must be powered up. Hence more than 5 A must be
injected, or it must be connected to 230 Vac for self powered relays. As regards those
which have auxiliary power supply, feed the voltage through the board's J4 connector.

Page 39 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

To perform this check, follow the steps indicated below:


-

Open the cubicles switch-disconnector and then earth the output.


Access the cable compartment and pass a test cable through the toroidal-core
current transformers.
Connect the test cable to the current circuit of the tester.
Connect the power supply board's J3 connector to the tester's timer stopper input.
Open the earthing switch and close the switch. Reset the latch and remove the
actuating lever in order to leave the cubicle ready for tripping.
Inject the test currents and verify the tripping times are correct. Check that the
trips are correctly displayed.

For phase trips, the test cable must pass through two toroidal-core current transformers.
The cable must pass through each of them in opposite direction; in other words, if in the
first one current flows up bottom, in the other it must flow bottom up so that the sum of
the two currents equals zero and no earth trip occur.
For earth trips, the test cable is passed through a single toroidal-core current transformer
(zero-sequence or phase toroidal, depending on whether a zero-sequence toroidal is
available or not). Trip tests must be performed for all toroidal-core current transformers
to check the proper operation of the complete unit.
Check through the secondary. In this case, the tests are performed on the equipment
when the cable compartment is not accessible. This occurs because the cubicle
outgoing cables are energised and cannot be connected to earth. In this case, it is not
possible to feed a test cable through the toroidal transformers and current must be
injected from the power supply board. This testing method is much better than using
testing equipment (normally more than 100 A).

To perform this check, follow the steps indicated below:


-

Page 40 of 84

Access the control's upper compartment where the power supply board is located.
Disconnect the bistable trigger.
Disconnect the blue, brown, black and earth cables of the J8 connector,
corresponding to points J8-6, J8-8, J8-10 and J8-1 respectively.
Connect the previously disconnected cables to the earth points N of connector J83. This operation will short-circuit the current transformers' secondary circuitry.

IG-159-GB
version 07
20.09.2012

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

Connect the power supply to the J4 connector: 230 Vac for selfpowered units and
24 to 125 Vdc or 24 to 110 Vac for auxiliary power supply units.
Connect the test cable to the J8 connector, bearing in mind the following ratio
between the connector's points and the phases:
Current through L1 J8-6 and J8-1.
Current through L2 J8-8 and J8-1.
Current through L3 J8-10 and J8-1.
Current through L1 and L2 (without earthing current) - J8-6 and J8-8.
Current through L1 and L3 (without earthing current) - J8-6 and J8-10.
Current through L2 and L3 (without earthing current) - J8-8 and J8-10.
Connect the test cable to the current circuit of the tester.
Connect the power supply board's J3 connector to the tester's timer stopper input.
If the switch can be opened, put it in closed position. Reset the latch and remove
the actuating lever in order to leave the cubicle ready for tripping and connect the
bistable trigger. If the switch cannot be operated, the bistable trigger should
remain disconnected and the checking process should be performed as shown in
next section: Check without switch operation.
Inject the secondary test currents taking into account that the transformation ratio
is 300/1 A. Check that the trip times are correct. Check that the trips are correctly
displayed.

NOTE
It is advisable to perform the CHECK THROUGH THE PRIMARY or the CHECK
THROUGH THE SECONDARY annually to guarantee correct equipment operation.
Check without operating the switch. In many occasions, the protection cubicle
switch cannot be operated and therefore, the maintenance checks are performed
exclusively on the electronic unit. In these cases, the following points shall be
considered:
- Always disconnect the bistable trigger. This way, the relay can trip without acting
upon the opening mechanism.
- Inject the current according to the section above "Check through the secondary".
- The toroidal-core current transformers can be verified if the approximate
consumption is known. The current that circulates through the secondary J8-6
(blue), J8-8 (brown) and J8-10 (black) must correspond to the 300/1 A ratio.
- As regards selfpowered relays, check that the selfpowered transformers provide
the operating power needed by the relay, if the primary current is greater than 5 A.
To do this, check that the voltage in connector J7 (between points 1- blue and 2brown) is greater than 10 Vdc.

Page 41 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

7.4. ekorRPG UNITS


7.4.1. Functional description
The ekorRPG unit is used for the general protection of lines, private installations,
transformers, etc. It is installed in circuit-breaker cubicles - models CGMCOSMOS-V,
CGM-CMP-V and/or CGM.3-V - so that the electronic unit performs all the protection
functions.
When an overcurrent that is within the relay operational value range is detected, this relay
acts upon a low power bistable trigger that opens the circuit-breaker.

Page 42 of 84

IG-159-GB
version 07
20.09.2012

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

7.4.2. Technical Characteristics


The ekorRPG protection unit is used to protect the following power ratings:
CGMCOSMOS / CGM-CGC / CGM.3 systems
Line
voltage
[kV]

(1)

6,6
10
13,8
15
20
25 (1)
30 (1)

ekorRPG with 5-100 A toruses


Min P.
[kVA]
50
100
100
100
160
200
250

ekorRPG with 15-630 A toruses


[kVA]
160
200
315
315
400
630
630

Max P.
[kVA]
5000
7500
10000
12000
15000
20000
25000

For CGM-CGC and CGM.3 system cubicles

Selection process for the ekorRPG unit protection parameters in CGMCOSMOS-V, CGMCMP-V and CGM.3-V cubicles:
1. Determine the system power to be protected and select the ekorRPG model in
accordance with the table above.
2. Calculate the rated current In = S/3xUn.
3. Define the continuous overload level I>. Normal values in transformers of up to 2000 kVA
are 20% for distribution installations and 5% for power generation installations.
4. Select the transitory overload curve. Coordination between relay curves and LV fuses is
performed with the EI type curve.
5. Define the delay time in transitory overload K. This parameter is defined by the
transformers thermal constant. This way, the greater the constant, the longer it takes for
the transformers temperature to increase under an overload condition; and therefore, the
protection trigger can be delayed longer. The normal value for distribution transformers is
K = 0.2, which means that it trips in 2 s if the overload is 300% in the EI curve.
6. Short-circuit level I>>. The maximum value of the transformers magnetisation current
must be determined. The current peak produced when a no-load transformer is
connected, due to the effect of a magnetised nucleus, is several times greater than the
rated current. This peak value, up to 12 times the rated value (10 times for more than
1000 kVA) has a very high harmonic content, so its fundamental 50 Hz component is
much less. So, a normal setting value for this parameter is between 7 and 10. In the case
of general protections for several transformers, this value can be lower.
7. Instantaneous time delay T>>. This value corresponds with the protection trip time in the
event a short-circuit occurs. It depends on the coordination with other protections and the
normal values are between 0.1 and 0.5 s.

Page 43 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07
20.09.2012

In the case of a general protection for two transformers, 1000 kVA each:
S = 2000 kVA, Un =15 kV
The steps to follow for proper setting of the protection relay are the following:
Rated current. In = S / 3 x Un = 2000 kVA / 3 x 15 kV 77 A
Continuous withstand overload 20%. In x I> = 77 A x 1.2 92 A
Extremely Inverse Curve type. E.I.
Transitory overload factor. K =0.2
Short-circuit level. In x I> x I>> = 77 A x 1.2 x 10 924 A
Instantaneous time delay T>> = 0.1 s
The earth unit setting depends on the characteristics of the network where the equipment is
installed. In general, the earth fault values are high enough to be detected as overcurrent. In
the isolated or resonant earthed neutral networks, when the fault value is very low, in other
words, when the earth protection is set to a value below 10% of the rated phase
current, it is recommended that an ultrasensitive earth protection be used.
The values of the setting parameters must guarantee selectivity with the main switch
protections. Given the variety of protection criteria and types of neutral used in the networks,
it does not exist a single parameterisation; each case requires a specific parameterisation.
For transformers up to 2000 kVA, the settings below are given as a general example. It must
be ensured that they properly apply to the protections upstream (general, line or main switch
protections, among others.)

Phase
setting

Setting
of
Earth

( )

Rated
Current

Curve

Instantaneo
us

I>

I>>

T>>

In=S/3xUn =
77 A

EI

DT

1,2

0,2

10

0,1

Type of
Neutral

Curve

Instantaneo
us

Io>

Ko

Io>>

To>>

Solid or
impedant

NI

DT

0,2

0,2

0,1

Isolated or
resonant

NI

DT

0.1 / Ig = 2 A (*)

0,2

0,2

* In case a zero-sequence toroidal transformer is used

Page 44 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

7.4.3. Installation in a Cubicle


The integral parts of the ekorRPG units are the electronic relay, the power supply and test
board and flip-flop trigger and the current sensors.
The electronic relay is fixed to the cubicle driving mechanism using anchors. The front of the
equipment, which contains the components of the user interface, display, keys,
communication ports, etc., is accessible from the outside without the need to remove the
driving mechanism enclosure. The rear contains the X1 and X2 connectors (see section
7.4.4) as well as the wiring that connects it to the power supply board. The signals that are
operational for the user are located on a terminal block that can be short-circuited and
accessed from the upper part of the cubicle. Furthermore, there is a volt-free contact (G3G4) which is simultaneously activated with the relay trip. This enables to use conventional
current injection equipment for testing the protection relays.
The functionality of the terminal block G for connecting the user is described below.
Terminals

Name

G1-G2

V.AUX

G3-G4

TRIP

G5-G6

EXT.TRIP

G7--G12

IP1,IP2,

Functions
Auxiliary power supply input:
230 Vac for selfpowered units and
24 to 125 Vdc or 24 to 110 Vac for
those with auxiliary power supply
(10 kV insulated in relation to the
rest of the equipment, in self
powered models).
This is an NO, volt-free contact
which is activated when the
protection device is tripped. It
also works in self powered mode.
It must be connected to an NO,
volt-free contact. When it is
activated, the protection device
trips if an overcurrent protection
function is enabled.
Short-circuitable
and
disconnectable terminals for
secondary current circuits.

Normal Use
Relay power
transformer's
battery, etc.).

supply (TS
LV
board,

Protection unit TEST.


Trip SIGNAL for remotelycontrolled installations.

Transformer
THERMOMETER.

Current
injection
secondary relay tests.

for

Page 45 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

7.4.4. ekorRPG Electrical Diagram

NOTE
For more details, please see electrical diagram No. 996410, which shows the electrical
connections between the different parts of the ekorRPG unit and the cubicle.

Page 46 of 84

IG-159-GB
version 07
20.09.2012

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

Front and rear view

7.4.5. Installation of Toroidal-core current transformers


In CGMCOSMOS-V, CGM-CMP-V and CGM.3-V cubicles, the current transformers are
installed in the cubicle bushings. Therefore there are no problems with connection errors in
the earthing grid. Additionally, these toroidal-core current transformers are equipped with a
test connection for conducting maintenance operations.
The terminals that can be used with the toroidal-core current transformers mounted in the
bushings are as follows:

Manufactur
er

EUROMOLD

Current
rating [A]
400
630
630
630

12 kV
12 kV
24 kV
24 kV
36 kV
36 kV
Type of
crossType of
crossType of
crossconnecto section connecto section connecto section
r
[mm2]
r
[mm2]
r
[mm2]
400 TE
400 LB
400 TB
440 TB

70-300
50-300
70-300
185-630

K-400TE
K-400LB
K-400TB
K-440TB

25-300
50-300
35-300
185-630

M-400TB
M-440TB

25-240
185-630

For other type of terminals[1], the toroidal-core current transformers must be loosened and
installed directly on the cables, in accordance with the instructions listed in section 7.3.5.

[1]

Consult Ormazabals Technical-Commercial Department.

Page 47 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

7.4.6. Checking and Maintenance


The ekorRPG protection, metering and control unit is designed to perform the operating test
necessary for both commissioning and regular maintenance checks. Several levels of checks
are available depending on the possibility of interrupting service and accessing the MV
cubicle cable compartment.
Check through the primary: In this case the tests are performed on the equipment
when it is completely shut down, since it involves actuating the circuit-breaker and
earthing the cubicle outgoing cables. When current is injected through the toroidal-core
current transformers, you must check that the protection opens the circuit-breaker
within the selected time. In addition, you must make sure that the tripping indications
are correct and that all the events are being recorded in the history log.
CAUTION
To perform this check, the unit must be powered up. Hence more than 5 A must be
injected, or it must be connected to 230 Vac for selfpowered relays. As regards those
which have auxiliary power supply, feed the voltage through the board's J4 connector.
To perform this check, follow the steps indicated below:
-

Open the cubicles circuit-breaker. Close the earthing switch and then close the
circuit-breaker for an effective earthing.
Access the cable compartment and connect the test cable to the test connector
of the toroidal-core current transformers.
Connect the test cable to the current circuit of the tester.
Connect terminals G3-G4 to the tester's timer stopper input.
Open the circuit-breaker. Open the earthing switch and then close the circuitbreaker. To open the circuit-breaker using the protection unit, the earthing switch
must be open.
Inject the test currents and verify the tripping times are correct. Check that the
trips are correctly displayed.

In order to detect phase trips, the test cable must be connected to the test bars of two
toroidal-core current transformers. The current must go through each one in opposite
directions. In other words, if the current flows up bottom in one of the test cables, in the
other it must flow bottom up so that the sum of the two currents is zero and no earth fault
trips occur.
For earth trips, the test cable is connected to a single toroidal-core current transformer
(zero-sequence or phase toroidal transformer, depending on whether a zero-sequence
toroidal is available or not). Trip tests must be performed for all toroidal-core current
transformers to check the proper operation of the complete unit.

Page 48 of 84

IG-159-GB
version 07
20.09.2012

IG-159-GB
version 07

20.09.2012 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

Check through the secondary with circuit-breaker operation:


In this case, the tests are performed
Test Terminal
on the equipment when the cable
block
compartment is not accessible. This
occurs because the cubicle outgoing
cables are energised and cannot be
connected to earth. In this case, the
test cable cannot be connected to the
test connection in the toroidal-core
current transformers and the current
injection is performed through the test
terminal block. This testing method is
also used when the primary current
values being tested are much greater
than
those
produced
by
test
equipment (normally greater than 100 A).

G-7

G12

To perform this check, follow the steps indicated below:


- Access the driving mechanism upper compartment where the checks and test
terminal block is located.
- Disconnect the bistable trigger.
- Short-circuit, and then disconnect current circuit terminals G7, G8, G9, G10, G11
and G12. This procedure short-circuits the current transformer secondaries.
- Connect the power supply to the G1-G2 connector: 230 Vac for selfpowered units
and 24 to 125Vdc or 24 to 110 Vac for auxiliary power supply units.
- Connect the test cable to terminals G7 to G12, taking into account the following
relation between the connector's points and the phases.
Current through L1 G7 and G12.
Current through L2 G8 and G12.
Current through L3 G9 and G12.
Current through L1 and L2 (without earthing current) - G7 and G8.
Current through L1 and L3 (without earthing current) - G7 and G9.
Current through L2 and L3 (without earthing current) - G8 and G9.
- Connect the test cable to the current circuit of the tester.
- Connect the G3-G4 connector to the tester's timer stopper input.
- If the circuit-breaker can be opened, put it in closed position. If the circuit-breaker
cannot be operated, make sure the bistable trigger remains disconnected, and
start the check as explained in the following section "Check without circuit-breaker
operation".
- Inject the secondary test currents taking into account that the transformation ratio
is 300/1 A or 1000/1 A, depending on the model. Verify the tripping times are
correct. Check that the trips are correctly displayed.

Page 49 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

Check through the secondary without circuit-breaker operation: In many


occasions, the protection cubicle circuit-breaker cannot be operated and therefore, the
maintenance checks are performed exclusively on the electronic unit. In theses cases,
the following points shall be considered:
-

Page 50 of 84

Always disconnect the bistable trigger. This way, the relay can trip without acting
upon the opening mechanism.
Inject the current according to the section above "Check through the secondary
with circuit-breaker operation".
The toroidal-core current transformers can be verified if the approximate
consumption is known. The current that circulates through the G7 (blue), G8
(brown) and G9 (black) secondaries must correspond to the ratio of 300/1 A or
1000/1 A.
As regards selfpowered relays, check that the selfpowered transformers provide
the operating power needed by the relay, if the primary current is greater than 5 A.
To do this, check that the voltage in connector J7 (between points 1- blue and 2brown) is greater than 10 Vdc.

IG-159-GB
version 07
20.09.2012

IG-159-GB
version 07

20.09.2012 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

8. SETTING AND HANDLING MENUS


8.1. KEYPAD AND ALPHANUMERIC DISPLAY

As can be seen in the image, the ekorRP protection, metering and control units have a total
of 6 keys:

SET: gives access to the Parameter Setting mode. In addition, the key has a
confirmation function within the various menus of the 'Parameter Setting' mode.
This function is explained in greater detail in this section.

ESC: This key allows the user to return to the main screen ('Display') from any
screen without saving changes made to the settings up to this point. Using this
key, the unit's trip indications can be reset.
Scrolling keys: The Up and Down arrows enable the user to scroll through
the different menus and change values. The 'Right' and 'Left' arrows allow
values in the 'Parameter Setting' menu to be selected for modification, as
detailed later.
Along with the keypad, the relays have an alphanumeric display which makes it easier to use
them. To save energy, the relay has a standby mode (display switched off), which starts to
operate any time the relay does not receive an external signal for 1 minute (pressing of any
key, except the SET key, or communication via RS-232), or for 2 minutes if the user is
modifying the parameters in the Parameter Setting mode. Likewise, if either type of external
signal is received (pressing of the ESC, arrow up, down, left or right keys; or communication
via RS-232) the relay will exit the standby mode and return to its active status, as long as the
relay remains powered.

Page 51 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

8.2. DISPLAY
The 'Display' mode is the normal mode of the relay when in
operation. Its main function is to allow the user to view various unit
parameters which can be summarised in 4 groups:
Current metering
Viewing the setting values
Values of the last and penultimate trip
Current date and time
The Display mode is shown by default in the relay, both when it is
switched on and when it returns from its standby status, or when pressing the ESC key from
any screen. In this operating mode, the Up and Down keys are enabled so that the user
can scroll through the various parameters in the Display mode. The SET key gives access
to the Parameter Setting mode.
The following figure shows an example of several 'Display' mode screens for the
ekorRPunits.

The screens shown in the relay display consist of two data lines. The first indicates the
parameter for the specific screen; the second establishes the value of this parameter.
Additionally, error codes can be indicated in both the display screen and the two data lines
(refer to section 8.5: Error codes). These indications are displayed with the other
indications.
A table with the Display mode parameters sequence is shown below. This table includes
the text that appears on the first line of the relay display, along with an explanation of the
corresponding parameter.

Page 52 of 84

IG-159-GB
version 07
20.09.2012

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

Parameter
I1. A
I2. A
I3. A
I0. A
I>
I 0>
I>>
I 0>>
In. A
I>
K
I>>
T>>
I 0>
K0
I 0>>
T 0>>
H2. A
H2
H2.TM
H2.DT
H2.YE
H2.HR
H2.SE
H1. A
H1
H1.TM
H1.DT
H1.YE
H1.HR
H1.SE
DATE
YEAR
TIME
SEC

Meaning
Phase 1 current metering
Phase 2 current metering
Phase 3 current metering
Zero-sequence current metering
Phase curve type (NI, VI, EI, DT, disabled)
Zero-sequence curve type (NI, VI, EI, DT, disabled)
Instantaneous phase unit enabled/disabled
Instantaneous zero-sequence unit enabled/disabled
Phase full load current
Phase overload factor
Constant Phase multiplier
Phase instantaneous multiplier
Phase instantaneous time delay
Earth leakage factor
Constant Zero-sequence multiplier
Zero-sequence instantaneous multiplier
Zero-sequence instantaneous time delay
Current at last trip
Cause of last trip
Time delay of last trip, from start-up to the trip
Last trip date
Last trip year
Hour and minute of last trip
Last trip second
Penultimate trip current
Penultimate trip cause
Time delay of the penultimate trip, from start up to the trip
Penultimate trip date
Penultimate trip year
Hour and minute of penultimate trip
Penultimate trip second
Current date
Current year
Current time
Current second

Page 53 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

8.3. PARAMETER SETTING


The 'Parameter Setting' menu can be accessed from any screen of the 'Display' menu by
pressing the SET key. The protection remains operational with the initial parameters, until the
user returns to the Display menu by pressing on the SET key again.
As a precautionary measure, the Parameter Setting menu is protected by a password,
which is entered each time the user wishes to access this menu. By default, all of the
ekorRP units have the password 0000. This password can be modified by the user as
explained further on.
This menu allows the user to make changes to various relay parameters.
These parameters can be grouped as follows:
Parameters for the protection and detection functions
Date and time
Communication parameters
Information on the number of trips
Password change
When the relay is in the 'Parameter Setting menu, the indication SET on
the lower middle section of the relay screen allows the user to identify the
menu quickly.

8.3.1. Protection parameters


The ekorRP units include two methods for selecting the setting parameters. manual and
automatic.
The manual method consists of entering each protection parameter one by one.
On the other hand, the automatic method makes the parameter entry easier and quicker for
the user. In this method, the user simply enters 2 pieces of data: Installation transformer
power (Pt), and line voltage (Tr). From these 2 pieces of data, the relay sets the parameters
according to:

In

Pt

(Tr 3 )

The selected full load current value is achieved by always rounding up the value.

Page 54 of 84

IG-159-GB
version 07
20.09.2012

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

The rest of setting values are fixed (see the table below), although the user can change any
of the values selected in the program from the manual mode.
Phase Protection

Earth Protection

Setting

Automatic Value

Setting

Automatic Value

Overload Factor
Curve Type
Constant Multiplier
Short-circuit Factor
Trip Time
Tripping Enabled

120 %
EI
0,2
10(*)
0,1(*)
DT

Earth Leakage Factor


Curve Type
Constant Multiplier
Short-circuit Factor
Trip Time
Tripping Enabled

20 %
NI
0,2
5
0,1(*)
DT

( )

* For protection using the ekorRPT-101, 201 or 301 models with 5-100 A range toruses, the short-circuit factor
is 7 and the instantaneous tripping time is 0.4.

8.3.2. Parameter Setting Menu


When accessing the Parameter Setting
menu through the SET key, the relay
requests a password. The settings
introduction area is accessed once it is
verified that the password is correct. At this
moment, manual configuration (CONF PAR)
or automatic configuration (CONF TRAF)
must be selected. You can change from one
to the other using the right and left keys.
Press the SET key to select the desired
option. The diagram on the right graphically
explains this process.
Once inside any of the two settings entry
areas, the user can move from one
parameter to another using the up and
down keys, the same as in the Display mode. Press the ESC or SET key to exit this menu
and access the Display menu. The ESC key will disregard all setting changes made
previously, whereas the SET key will save all data before continuing.

Page 55 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

To change a setting, proceed as follows:


1. Display the setting to be changed on the screen.
2. Press the Left or Right keys. The data will start to flash.
3. Adjust the value required with the 'Up' and 'Down' keys. If the setting
is numeric, the blinking number can be changed with the 'Left' or
'Right' keys.
4. To exit, press SET (save and exit), or ESC (clear changes and exit).

The password can be modified by first entering the


current password. The process is explained graphically in
the diagram on the right. As shown in this diagram,
password modification consists of four steps.
The two following tables show the protection parameters
in the Parameter Setting menu, along with an
explanation of each of them and the values they can
have. This information is shown for each of the two
setting modes: manual or automatic.

Page 56 of 84

IG-159-GB
version 07
20.09.2012

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

Manual Setting Menu


Parameter

Meaning

I>
I 0>
I>>
I 0>>

Phase curve type / unit disabling


Zero-sequence curve type / Unit disabling
Enabling instantaneous phase unit
Enabling instantaneous earth unit

In. A

Phase full load current

I>
K
I>>
T>>
**I0>
K0
I 0>>
T 0>>
DATE
YEAR
TIME
SEC.
*NPER
*PROT
*BAUD
*PARI
*LEN
*STOP
DT.AD
YE.AD
HR.AD
SE.AD
NTP
NTG
*V.0
PSWV

Phase overload factor


Constant Phase multiplier
Phase instantaneous multiplier
Phase instantaneous time delay
Earth leakage factor
Constant Zero-sequence multiplier
Zero-sequence instantaneous multiplier
Zero-sequence instantaneous time delay
Modify current day (day and month)
Modify the current year
Modify the current time
Modify the current second
Peripheral number
Protocol number
Transmission speed (kbps)
Parity
Word length
Stop bits
Day and month on which the last setting was
made
Year in which the last setting was made
Time at which the last setting was made
Second at which the last setting was made
Number of phase trips
Number of earth trips
Firmware version
Password modification

Range
OFF, NI, VI, EI, DT
OFF, NI, VI, EI, DT
OFF, DT
OFF, DT
192 A for ekorRPX-X01
480 A for ekorRPX-X02
1,00 1,30
0,05 1,6
1 25
0,05 2,5
0,1 0,8
0,05 1,6
1 25
0,05 2,5
1 - 31 / 1 - 12
2000 2059
00:00 - 23:59
0 - 59
0 31
0000[3] MODBUS-0001
1,2; 2,4; 4,8; 9,6; 19,2; 38,4
No, even, odd
7; 8
1; 2
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
0000 - 9999

( )

* Only available for firmware version 18 or later.


**) n the case of zero-sequence toroidal transformer, the range is 0.5 A-In and the
parameter is Ig.
(

[3]

ekorSOFT communication protocol.

Page 57 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07
20.09.2012

Automatic Setting Menu


Parameter

Meaning

tP 0W

Transformer Power (kVA)

Tvol
DATE
YEAR
TIME
SEC.
*NPER
*PROT
*BAUD
*PARI
*LEN
*STOP

Line voltage (kV)


Current day and month
Current year
Current time
Current second
Peripheral number
Protocol number
Transmission speed (kbps)
Parity
Word length
Stop bits
Day and month on which the last setting
was made
Year in which the last setting was made
Time at which the last setting was made
Second at which the last setting was
made
Number of phase trips
Number of earth trips
Number of external trips
Firmware version
Password modification

DT.AD
YE.AD
HR.AD
SE.AD
NTP
NTG
NTE
*V.0
PSWV
( )

* Only available for firmware version 18 or later

[4]

ekorSOFT communication protocol.

Page 58 of 84

Range
50; 100; 160; 200; 250; 315; 400; 500;
630; 800; 1000; 1250; 1600; 2000
6,6; 10; 12; 13,2; 15; 20; 25; 30
1-31/1-12
2000-2059
00:00-23:59
0-59
0-31
[4]
0000 (MODBUS)-0001
1,2;2,4;4,8;9,6;19,2;38,4
No, even, odd
7, 8
1, 2
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
0000-9999

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

8.4. TRIP RECOGNITION


Whenever a trip occurs, the relay immediately accesses the
'Trip recognition" menu. This menu can be easily identified
because a blinking arrow is located on the upper part of the
display, just below the name of the function that has caused
the trip. The ekorRP units signal five possible trip causes
using the upper arrow.
Phase time-delayed trip

I>

Phase instantaneous trip

I>>

Earth time-delayed trip I 0>


Earth instantaneous trip

I 0>>

External trip

Ext

To quit the Trip recognition menu, press the ESC key from any of the menu screens. The
relay recognises that the user has checked the trip and then returns to the first screen of the
Display menu. In any case, the trip data will continue to be available to the user from the
Display menu until two new trips have occurred.
The various screens of the of 'Trip Recognition' menu provide two types of information. The
initial screen shows the current detected at the tripping moment, by phase or earth
depending on the tripped unit. Subsequent Trip Recognition screens display the date and
time of the trip, along with the time elapsed from the unit start up to the trip.
The following table shows the sequence in which the data appear. As in the rest of the
menus, the 'Up' and 'Down' keys are used to scroll throughout the various data.
Parameter
Ix A
Ix TM
Ix DT
Ix YE
Ix HR
Ix SE

Meaning
Current at the tripping moment
Time elapsed from unit start up to the trip
Day and month on which the trip occurred
Year in which the trip occurred
Time at which the trip occurred
Second in which the trip occurred

Where subscript x depends on the cause of the trip:


3 or zero-sequence, respectively.

e1 f,

e2 f,

e3 f or

e0 f, for phase 1, phase 2, phase

Page 59 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07
20.09.2012

8.5. ERROR CODES


The ekorRP units have a series of error codes used to warn the user
regarding the different anomalies that may occur in the system.
The different error codes are identified by a number, just as shown in
the figure on the right. The following error codes may be displayed on
the ekorRP units:

Code shown on
the display
ER 01
ER 03

Page 60 of 84

Meaning
230 Vac in the external trip input (this input is to be connected to a volt-free
contact)
Error when opening switch

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

8.6. MENU MAP (QUICK ACCESS)


DISPLAY

The menu map is a summary table that indicates all the


submenus for the ekorRP units, as well as a brief
explanation of each one.

Phase 1
current

Phase multiplier constant

Last trip date

Phase 2
current

Phase instantaneous
multiplier

Last trip year

Phase 3
current

Phase instantaneous time


delay

Time at last trip

Zero-sequence current
(Io or Ig)

Earth leakage factor

Last trip second

Phase curve type

Constant Earth multiplier

Penultimate trip current

Zero-sequence curve
type

Earth instantaneous
multiplier

Penultimate trip cause

Phase instantaneous
enabling

Earth instantaneous time


delay

Time at penultimate trip

Zero-sequence
instantaneous enabling

Current at last trip

Penultimate trip date

Full load current

Cause of last trip

Penultimate trip year

Overload factor

Time at last trip

Time at penultimate trip

Second penultimate
trip

Page 61 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07
20.09.2012

PARAMETER SETTING

Parameter Configuration
Transformer
configuration

Prompt for
password

Word length

Prompt for old


password

Stop
bit(s)

Prompt for new


password

Date
at last setting

Repeat new
password

Parameter
configuration

Earth leakage
factor

Transmission
speed

Number of
external trips

Phase curve
type

Earth multiplier
constant

Parity

Firmware
version

Zero-sequence
curve type

Earth
instantaneous
multiplier

Word length

Password
modification

Modification
of date

Year
at last setting

Phase
instantaneous
enabling

Earth
instantaneous
time delay

Stop
bit(s)

Prompt for old


password

Modification
of year

Time
at last setting

Current that
caused the trip

Zero-sequence
instantaneous
enabling

Modification
of date

Date
at last setting

Prompt for new


password

Modification
of time

Second
at last setting

Trip time

Full load current

Modification
of year

Year
at last setting

Repeat new
password

Modification
of second

Number of
phase trips

Date
at trip

Overload factor

Modification
of time

Time
at last setting

Peripheral
no.

No. Zerosequence trips

Year
at trip

Constant Phase
multiplier

Modification
of second

Second
at last setting

Protocol
no.

Number of
external trips

Time
at trip

Phase
instantaneous
multiplier

Peripheral
no.

Number of
phase trips

Transmission
speed

Firmware
version

Second
at trip

Phase
instantaneous
time delay

Protocol
no.

No. Zerosequence trips

Parity

Password
modification

Page 62 of 84

Line voltage

Trip
recognition

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

The on-screen representation of the equipment for LAST and PENULTIMATE trips is
detailed below:
Cause of last trip
Time of last trip
Date of last trip
Year of last trip
Time of last trip
Second last trip
Current penultimate trip
Cause penultimate trip
Time penultimate trip
Date penultimate trip
Year penultimate trip
Time penultimate trip
Second penultimate trip

Figure 8.1: View of last and penultimate trips on the menu map

FAULT HISTORY LOG


Hn
Hn A

| amp.

Hn

|Fxy

Hn TM | time
Hn DT | date
Hn YE | year
Hn HR | time
Hn SE | sec.

Last trip (n=2). Penultimate trip (n=1)


Current at the moment of tripping (A = Amps)
Reason for tripping:
x= Trip At phase 1 (R), 2 (S), 3 (T), or (Neutral), Trip External (Ext.)
y= Trip. Time delayed (>) or Instantaneous (>>)
Time elapsed from unit start up to the trip (mSg.)
Day and month on which the trip occurred
Year in which the trip occurred
Time at which the trip occurred
Second in which the trip occurred

Page 63 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07
20.09.2012

9. MODBUS PROTOCOL FOR ekorRP RANGE UNITS


The two communication ports of the relay use the same protocol: MODBUS in RTU
transmission mode (binary). The main advantage of this mode over the ASCII mode is that
the information is packed tighter, allowing a higher data transmission rate at the same
communication speed. Each message must be transmitted as a continuous string, as the
silences are used to detect the end of the message. The minimum duration of the SILENCE
is 3.5 characters.
RTU message frame
Start

Address

Function

Data

CRC

End

Silence

8 BITS

8 BITS

n x 8 BITS

16 BITS

Silence

The MODBUS ADDRESS of the relay (also called peripheral number) is a byte that takes
values between 0 and 31.
The master addresses the slave, indicating its address in the respective field and the slave
answers by indicating its own address. The '0' address is reserved for the 'broadcast' mode
so it can be recognised by all slaves.

Page 64 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

9.1. READ / WRITE FUNCTIONS


In principle, only two functions will be implemented, one for reading and another for writing
data.
Data reading
Question:
Start

Address

Function

Silence

SLAD

Data
ADDR-H

ADDR-L

NDATA-H

NDATA-L

CRC

End

16 BITS

Silence

CRC

End

16 BITS

Silence

Response:
Start

Address

Function

No. of
BYTES

Silence

SLAD

Data
DATA1-H

DATA1-L

.......

where:
SLAD
ADDR-H
ADDR-L

Slave address
High byte of the address for the first register to be read
Low byte of the address for the first register to be read

NDATA-H
NDATA-L
DATA1-H
DATA1-L
N

High byte of the number of registers to be read


Low byte of the number of registers to be read
High byte of the first register requested
Low byte of the first register requested
Total number of data bytes. This will be equal to the number of
registers requested, multiplied by 2.

Data Writing
This makes it possible to write a single register at the address indicated.
Question:
Start

Address

Silence

SLAD

Function
6

Data
ADDR-H

ADDR-L

DATA-H

CRC
DATA-L

16
BITS

End
Silence

Response:
The normal response is an echo of the query received.
where:
SLAD
ADDR-H
ADDR-L
DATA-H
DATA-L

Slave address
High byte of the address for the register to be written.
Low byte of the address for the register to be written.
High byte of the data to be written.
Low byte of the data to be written.

Page 65 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07
20.09.2012

Response in case of error


Start

Address

Function

Error-Code

CRC

End

Silence

SLAD

FUNC_ERR

CODE_ERROR

16 BITS

Silence

where:
SLAD
FUNC_ERR
CODE_ERROR
1
2
3
4
5
6
8

Slave address.
Code of the function requested, with the most significant bit
at 1.
Code of the error occurred.
Error in the number of registers
Wrong address
Incorrect data
attempt made to read a write-only address
session error
EEPROM error
Attempt being made to write in a read-only address

9.2. Password-protected Register Writing


The parameters are protected against writing by the USER PASSWORD.
A write session of password-protected parameters starts by entering the PASSWORD in the
respective address. The write session ends with the update of registers once the respective
PASSWORD has been transmitted again. If the timeout period has elapsed, the process is
aborted and the system returns to normal mode. In normal mode, any attempt to write a
protected registration will result in an error code 2'. The write session is valid for only one
port (the one that entered the PASSWORD has priority).

9.3. CRC GENERATION


The cyclical redundancy check (CRC) field contains two bytes that are added to the end of
the message. The receiver must re-calculate it and compare it with the received value. Both
values must be equal.
The CRC is the remainder obtained when dividing the message by a binary polynomial. The
receiver must divide all bits received (information plus CRC) by the same polynomial used to
calculate the CRC. If the remainder obtained is 0, the information frame is deemed correct.
The polynomial used will be: X15+X13+1

Page 66 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

9.4. REGISTER MAP


USER SETTINGS: USER PASSWORD-PROTECTED WRITING
Field

Address

In

0x0000

CURVE_
CURVE_
PHASE
ZERO-SEQ
PHASE_INST
ZERO-SEQ_INST
PHASE_INST_OVERLOAD (I>)
ZERO-SEQ_CURRENT (Io>)

0x0001

K
PHASE_INST
_OCCUR
PHASE_INST
_TIME

0x0005
0x0006

Ko
ZEROSEQ_INST_OCCUR
ZEROSEQ_INST_TIME

PHASE_TRIP_COUNTER
EARTH_TRIP_COUNTER
EXTERNAL_TRIP_COUNTER
USER_PASSWORD
ZERO-SEQ_CURRENT (Io>)

0x0002
0x0003
0x0004

0x0007

0x0008
0x0009
0x000a
0x000b
0x000c

Contents
from 5 to 100 if RATED_I=0
from 15 to 630 if RATED_I=1
0:OFF; 1:NI; 2:VI; 3:EI; 4:DT
0:OFF, 1:DT;
0:100%; 1:101%; 2:102%,... 30:130%
Vector_sum
0-sequence_toroidal
0:10%;1:11%;
0:0.1; 1:0.2; 2:1.5 A
80%
In
0:0.05; 1:0.06; ... 20:1.6
0:3; 1:4;17:20
050 ms, 1 60 ms 270 ms, 3 80
ms 490 ms, 5 100 ms, 6200
ms...2,5 s
from 0000 to 9999
from 0000 to 9999
from 0000 to 9999
from 0000 to 9999
Vector_sum
0-sequence_toroidal
0:10%;1:11%;
0:0.1; 1:0.2; 2:0.3 A
80%
In

Page 67 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07
20.09.2012

HISTORY LOGS; MEASUREMENTS; INPUTS / OUTPUTS; SOFT VERSION: READ ONLY


Field

Address

YEAR

User Setting Date

MONTH
HOUR
00
PENULT_TRIP

DAY
MINUTE
SECONDS
LAST_TRIP

0x0200
0x0201
0x0202
0x0203
0x0208

Contents
RTC Format
Bit
0
1
2
3
4
5
6

7
PHASE_LAST_TRIP_VALUE
ZERO-SEQ_LAST_TRIP_VALUE

Tripping History log

PHASE_LAST_TRIP_TIME
ZERO-SEQ_LAST_TRIP_TIME
YEAR
MONTH
DAY
HOUR
MINUTE
00
SECONDS
PHASE_PENULT_TRIP_VALUE

ZEROSEQ_PENULT_TRIP_VALUE
PHASE_PENULT_TRIP_TIME
ZEROSEQ_PENULT_TRIP_TIME
YEAR
MONTH
DAY
HOUR
MINUTE
00
SECONDS
Phase current L1
Phase current L2

Current metering

Phase current L3
Zero-sequence current

0x0209
0x020a
0x020b
0x020c
0x020d
0x020e
0x020f
0x0210
0x0211
0x0212
0x0213
0x0214
0x0215
0x0216
0x0217
0x0218
0x0219
0x021a
0x021b
0x021c
0X021d
0X021e
0X021f
0X0220
0X0221
0X0222
0X0223
0X0224

Inputs
Software
version

Page 68 of 84

0x0225
functions

0x0226

Contents
Trip by phase
1: L1, 2: L2, 3: L3
Zero-sequence trip
NOT USED
External trip
Cause of the phase trip.
0: overload,
1: short-circuit
Cause of the zerosequence trip.
0: overload,
1: short-circuit
Double tripping

Current in hundredths of an A
Current in hundredths of an A
Time in hundredths of a s
Time in hundredths of a s
RTC Format
Current in hundredths of an A
Current in hundredths of an A
Time in hundredths of a s
Time in hundredths of a s

RTC Format

Hundredths of on A
Hundredths of on A
Hundredths of on A
Hundredths of on A
Bit 0: Input 1,
Bit 1: Input 2, etc.
from 0 to 99

from A to Z

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

IG-159-GB
version 07

20.09.2012 84

CLOCK

MONTH
HOUR
00

Field

Address

Contents

YEAR

0x0300
0x0301
0x0302
0x0303

from 2000 to 2059


from 1 to 12
from 1 to 31
from 0 to 23
from 0 to 59
0
from 0 to 59

DAY
MINUTE
SECONDS

PASSWORD KEYS: WRITING ONLY


Field

Address

Contents

USER PASSWORD KEY

0x0500

from 0 to 9999

Page 69 of 84

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

NOTES

Page 70 of 84

IG-159-GB
version 07
20.09.2012

10. ANNEX A

BRIEF GUIDE FOR COMMISSIONING THE ekorRPG UNIT


IN CGMCOSMOS-V, CGM-CMP-V & CGM.3-V

IG-159-GB
Annex A
version 07

BRIEF GUIDE FOR COMMISSIONING THE


ekorRPG UNIT

Page 72
of 84

IN CGMCOSMOS-V, CGM-CMP-V & CGM.3-V

20-09-2012

The following steps must be followed for correct commissioning:

1. Verify the power to be protected:


CGMCOSMOS / CGM-CGC / CGM.3 SYSTEMS
Line
voltage
[kV]

(1)

6,6
10
13,8
15
20
25 (1)
30 (1)

ekorRPG with 5-100 A toruses

ekorRPG with 15-630 A toruses

Min P.
[kVA]

[kVA]

Max P.
[kVA]

50
100
100
100
160
200
250

160
200
315
315
400
630
630

5000
7500
10000
12000
15000
20000
25000

for CGM-CGC and CGM.3 system cubicles only

2. Toroidal-core current transformers already installed:


Bushing
Protection and power supply
toroidal-core current transformers
(already installed)
Test flatbar

3. Connect the HV terminals:

Connected terminals (shielded). For


non-shielded or plug-in terminals the
current transformers (CT) must be
installed on the cable.

Connect braid to
earth collector

4. External connections:
Remove the terminal
box cover.
Connect
to
terminal
block:

G1-G2: 230 Vac or 48Vdc


(depending on model A
or B)
G5-G6: external trip
(thermostat)

IG-159-GB
Annex A
version 07

BRIEF GUIDE FOR COMMISSIONING THE


ekorRPG UNIT

Page 73
of 84

IN CGMCOSMOS-V, CGM-CMP-V & CGM.3-V

20-09-2012

5. Set relay:
Automatic mode:
Installation kV and kVA.
Manual mode:
Parameters: I>, I0>, I>>, ...

PHASE
SETTING

Table of settings:

IN

S
(UN 3)

EARTH SETTING

Type of
neutral

Curve
EI
Curve

Instantaneo
us
TD
Instantaneo
us

Solid or
impedant

NI

TD

Isolated or
resonant

NI

TD

I>

I>>

T>>

1,2

0,2

10

0,1

Io>

Ko

Io>>

To>>

0,2

0,2

0,1

0,2

0,2

0,1 /
Ig=2A(*)

( )

* In case a zero-sequence toroidal transformer is used

6. Trip test with current:

Remove earthing switch and close the switch.


Remove 230 Vac (G1- G2) to check that the selfpower supply is
operating (except B models).
Inject test current:
In two phase trip flatbars
In one earth trip flatbar
Repeat for I1, I2 and I3.

IG-159-GB
Annex A
version 07

BRIEF GUIDE FOR COMMISSIONING THE


ekorRPG UNIT

Page 74
of 84

IN CGMCOSMOS-V, CGM-CMP-V & CGM.3-V

20-09-2012

7. External trip test:


Short-circuit
and G6.

the

G5

Check
trip
and
indication EXT.

8. Commissioning:

Check I1 I2 I3.
Check I0 0.
Check 230 Vca connection (if available).

9. What to do in the event of:


ERROR

REASON

POSSIBLE CAUSES

Error 01

Incorrectly connected
thermometer

Thermometer connected to 230 V (with potentialfree contact).

Error 03

Switch Error

Switch mechanical blocking


Relay trip wiring error
Auxiliary contact error

I0 0

I1 I2 I3
I123 > 5 A and LED On
switched off
Relay trip in I0>> when
closing switch
Relay trip in I>> when
closing switch

Relay
will
communicate

not

Grid fault
incorrectly connected or Check that the grid and the secondary circuits are
secondary
circuit
not incorrectly connected
disconnected.
Incorrect
toroidal-core
current
transformer
Unbalance
connection
Check secondary circuits
Incorrectly connected toroidal-core current
Selfpowered
transformer
Incorrectly connected relay wiring
Real fault present.
Time T0 >>
Check if T0 >> sufficient, taking into account
insufficient
toroidal vector sum error.
Real fault present.
I >> insufficient
Check parameter I >>, taking into account
transformer current peak (10 times In ).
Incorrect communication cable connections.
Relay in energy-saving mode. Press a button of
Fault in
relay.
communication
Incorrect
configuration
of
communication
parameters.

IG-159-GB
Annex A
version 07

DISPLAY

BRIEF GUIDE FOR COMMISSIONING THE


ekorRPG UNIT

Page 75
of 84

IN CGMCOSMOS-V, CGM-CMP-V & CGM.3-V

20-09-2012

The menu map is a summary table that indicates all the


submenus for the ekorRP units, as well as a brief
explanation of each one.

Phase 1
current

Phase multiplier constant

Last trip date

Phase 2
current

Phase instantaneous
multiplier

Last trip year

Phase 3
current

Phase instantaneous time


delay

Time at last trip

Zero-sequence current
(Io or Ig)

Earth leakage factor

Last trip second

Phase curve type

Constant Earth multiplier

Penultimate trip current

Zero-sequence curve
type

Earth instantaneous
multiplier

Penultimate trip cause

Phase instantaneous
enabling

Earth instantaneous time


delay

Time at penultimate trip

Zero-sequence
instantaneous enabling

Current at last trip

Penultimate trip date

Full load current

Cause of last trip

Penultimate trip year

Overload factor

Time at last trip

Time at penultimate trip

Second penultimate
trip

IG-159-GB
Annex A
version 07

BRIEF GUIDE FOR COMMISSIONING THE


ekorRPG UNIT

Page 76
of 84

IN CGMCOSMOS-V, CGM-CMP-V & CGM.3-V

20-09-2012

PARAMETER SETTING

Parameter Configuration
Transformer
configuration

Prompt for
password

Word length

Prompt for old


password

Stop
bit(s)

Prompt for new


password

Date
at last setting

Repeat new
password

Parameter
configuration

Earth leakage
factor

Transmission
speed

Number of
external trips

Phase curve
type

Earth multiplier
constant

Parity

Firmware
version

Zero-sequence
curve type

Earth
instantaneous
multiplier

Word length

Password
modification

Modification
of date

Year
at last setting

Phase
instantaneous
enabling

Earth
instantaneous
time delay

Stop
bit(s)

Prompt for old


password

Modification
of year

Time
at last setting

Current that
caused the trip

Zero-sequence
instantaneous
enabling

Modification
of date

Date
at last setting

Prompt for new


password

Modification
of time

Second
at last setting

Trip time

Full load current

Modification
of year

Year
at last setting

Repeat new
password

Modification
of second

Number of
phase trips

Date
at trip

Overload factor

Modification
of time

Time
at last setting

Peripheral
no.

No. Zerosequence trips

Year
at trip

Constant Phase
multiplier

Modification
of second

Second
at last setting

Protocol
no.

Number of
external trips

Time
at trip

Phase
instantaneous
multiplier

Peripheral
no.

Number of
phase trips

Transmission
speed

Firmware
version

Second
at trip

Phase
instantaneous
time delay

Protocol
no.

No. Zerosequence trips

Parity

Password
modification

Line voltage

Trip
recognition

11. ANNEX B

BRIEF GUIDE FOR COMMISSIONING THE ekorRPG UNIT


IN
CGMCOSMOS-V, CGM-CMP-V & CGM.3-V

IG-159-GB
Annex B
version 07

BRIEF GUIDE FOR COMMISSIONING THE


ekorRPG UNIT IN

Page 78
of 84

CGMCOSMOS-V, CGM-CMP-V & CGM.3-V

20-09-2012

The following steps must be followed for correct commissioning:

1. Verify the power to be protected:


CGMCOSMOS SYSTEM
Line
voltage
[kV]
6,6
10
13,8
15
20
( )

Fuse rated MINIMUM transformer power


voltage
[kV]
Fuse rating [A]
[kVA]
3 / 7,2
6/12
10/24
10/24
10/24

16
10
16
16
16

MAXIMUM transformer power


Fuse rating [A]
( )

50
100
100
125
160

160
160 ()
100
125 ()
125

[kVA]
1250
1250
1250
1600
2000

442 mm cartridge
125 A SIBA SSK Fuse

( )

Line
voltage

Fuse Rated
Voltage
[kV]

CGM-CGC / CGM.3 System


MINIMUM Transformer Power MAXIMUM Transformer Power

[kV]
6,6
10
13,8
15
20
25
30

( )

3/7,2
6/12
10/24
10/24
10/24
24/36
24/36

Fuse Rating
[A]

[kVA]

16
16
10
16
16
25
25

50
100
100
125
160
200
250

Fuse Rating
[A]
160 ()
125
63
63
63
80 (2)
80 (2)

442 mm cartridge
SIBA SSK fuse (check)

(2)

2. Toroidal-core current transformers:


Installed on cables.
If the earthing grid originates from:

underneath the toroidal-core


current transformer: do not
pass the grid through it.
above
the
toroidal-core
current transformer: pass the
grid through it. Make sure that
the screen does not touch any
metal part before connecting it
to the cubicle earth collector.

Power
supply board

Protection and
power supply
toroidal-core
current
transformers
Earthing grids
Cables

3. Connect the HV terminals

[kVA]
1000
1250
800
1000
1250
2000
2500

BRIEF GUIDE FOR COMMISSIONING THE


ekorRPG UNIT IN
CGMCOSMOS-V, CGM-CMP-V & CGM.3-V

IG-159-GB
Annex B
version 07

Page 79
of 84
20-09-2012

4. External connections:
Remove the control box
cover.
Connect to the power supply
board:
J1: external trip (thermostat)
J4: 230Vac or 48Vdc
(depending on
model A or B)

5. Set relay:
Automatic mode:
Installation kV and kVA.
Manual mode:
Parameters: I>, I0>, I>>, ...

PHASE
SETTING

Table of settings:
Curve

Instantaneous

I>

I>>

T>>

EI

TD

1,2

0,2

0,4

Type of
neutral

Curve

Instantaneous

Io>

Ko

Io>>

To>>

Solid or
impedant

NI

TD

0,2

0,2

0,4

Isolated or
resonant

NI

TD

0,1

0,2

0,4

EARTH
SETTING

IN

S
(UN 3)

6. Trip test with current:

Remove earthing switch and close the switch.


Remove 230 Vac (J4) to check that the selfpower supply is operating (except B models).
Inject test current:
Insert the cable in two toroidal-core current transformers for phase tripping
Insert the cable in one toroidal-core current transformer for earth tripping
Repeat for I1, I2 and I3.

IG-159-GB
Annex B
version 07

BRIEF GUIDE FOR COMMISSIONING THE


ekorRPG UNIT IN

Page 80
of 84

CGMCOSMOS-V, CGM-CMP-V & CGM.3-V

20-09-2012

7. External trip test:


Short-circuit the J1

Check
trip
indication EXT.

and

8. Commissioning:

Check I1 I2 I3
Check I0 0
Check 230 Vca connection (if available)

9. What to do in the event of:


ERROR

REASON

POSSIBLE CAUSES

Error 01

Incorrectly connected
thermometer

Thermometer connected to 230 V (with potentialfree contact).

Error 03

Switch Error

Switch mechanical blocking


Relay trip wiring error
Auxiliary contact error

I0 0

I1 I2 I3
I123 > 5 A and LED On
switched off
Relay trip in I0>> when
closing switch
Relay trip in I>> when
closing switch

Relay
will
communicate

not

Grid fault
incorrectly connected or Check that the grid and the secondary circuits
secondary circuit
are not incorrectly connected
disconnected
Incorrect toroidal-core current transformer
Unbalance
connection
Check secondary circuits
Incorrectly connected toroidal-core current
Self powered
transformer
Incorrectly connected relay wiring
Real fault present.
Time T0 >>
Check if T0 >> sufficient, taking into account
insufficient
toroidal vector sum error.
Real fault present.
I >> insufficient
Check parameter I >>, taking into account
transformer current peak (10 times In ).
Incorrect communication cable connections.
Relay in energy-saving mode. Press a button of
Fault in
relay.
communication
Incorrect
configuration
of
communication
parameters.

IG-159-GB
Annex B
version 07

DISPLAY

BRIEF GUIDE FOR COMMISSIONING THE


ekorRPG UNIT IN
CGMCOSMOS-V, CGM-CMP-V & CGM.3-V

Page 81
of 84
20-09-2012

The menu map is a summary table that indicates all the


submenus for the ekorRP units, as well as a brief
explanation of each one.

Phase 1
current

Phase multiplier constant

Last trip date

Phase 2
current

Phase instantaneous
multiplier

Last trip year

Phase 3
current

Phase instantaneous time


delay

Time at last trip

Zero-sequence current
(Io or Ig)

Earth leakage factor

Last trip second

Phase curve type

Constant Earth multiplier

Penultimate trip current

Zero-sequence curve
type

Earth instantaneous
multiplier

Penultimate trip cause

Phase instantaneous
enabling

Earth instantaneous time


delay

Time at penultimate trip

Zero-sequence
instantaneous enabling

Current at last trip

Penultimate trip date

Full load current

Cause of last trip

Penultimate trip year

Overload factor

Time at last trip

Time at penultimate trip

Second penultimate
trip

BRIEF GUIDE FOR COMMISSIONING THE


ekorRPG UNIT IN

IG-159-GB
Annex B

CGMCOSMOS-V, CGM-CMP-V & CGM.3-V

version 07

Page 82
of 84
20-08-2012

PARAMETER SETTING

Parameter Configuration
Transformer
configuration

Prompt for
password

Word length

Prompt for old


password

Stop
bit(s)

Prompt for new


password

Date
at last setting

Repeat new
password

Parameter
configuration

Earth leakage
factor

Transmission
speed

Number of
external trips

Phase curve
type

Earth multiplier
constant

Parity

Firmware
version

Zero-sequence
curve type

Earth
instantaneous
multiplier

Word length

Password
modification

Modification
of date

Year
at last setting

Phase
instantaneous
enabling

Earth
instantaneous
time delay

Stop
bit(s)

Prompt for old


password

Modification
of year

Time
at last setting

Current that
caused the trip

Zero-sequence
instantaneous
enabling

Modification
of date

Date
at last setting

Prompt for new


password

Modification
of time

Second
at last setting

Trip time

Full load current

Modification
of year

Year
at last setting

Repeat new
password

Modification
of second

Number of
phase trips

Date
at trip

Overload factor

Modification
of time

Time
at last setting

Peripheral
no.

No. Zerosequence trips

Year
at trip

Constant Phase
multiplier

Modification
of second

Second
at last setting

Protocol
no.

Number of
external trips

Time
at trip

Phase
instantaneous
multiplier

Peripheral
no.

Number of
phase trips

Transmission
speed

Firmware
version

Second
at trip

Phase
instantaneous
time delay

Protocol
no.

No. Zerosequence trips

Parity

Password
modification

Line voltage

Trip
recognition

IG-159-GB
version 07
20.09.2012

GENERAL INSTRUCTIONS FOR


ekorRP
PROTECTION, METERING AND CONTROL UNITS

NOTES

Page 83 of 84

TECHNICAL - COMMERCIAL DEPARTMENT:


www.ormazabal.com

Page 84 of 84

Você também pode gostar