Escolar Documentos
Profissional Documentos
Cultura Documentos
General Instructions
version 07
ekorRP
PROTECTION, METERING AND
CONTROL UNITS
LIB
20.09.2012
Transformer
Substations
Secondary Distribution
Switchgear
Primary Distribution
Switchgear
Protection and
Automation
Low Voltage
Boards
Distribution
Transformers
CAUTION!
When MV equipment is operating, certain components are live, other parts may be in movement and some may reach high
temperatures. Therefore, the use of this equipment poses electrical, mechanical and thermal risks.
In order to ensure an acceptable level of protection for people and property, and in compliance with applicable environmental
recommendations, Ormazabal designs and manufactures its products according to the principle of integrated safety, based on
the following criteria:
Where elimination of hazards is neither technically nor economically feasible, appropriate protection functions are
incorporated in the equipment.
Communication about remaining risks to facilitate the design of operating procedures which prevent such risks,
training for the personnel in charge of the equipment, and the use of suitable personal protection equipment.
Use of recyclable materials and establishment of procedures for the disposal of equipment and components so
that once the end of their service lives is reached, they are duly processed in accordance, as far as possible, with
the environmental restrictions established by the competent authorities.
Consequently, the equipment to which the present manual refers complies with the requirements of section 11.2 of the
forthcoming IEC standard 62271-1. It must therefore only be operated by appropriately qualified and supervised personnel, in
accordance with the requirements of standard EN 50110-1 on the safety of electrical installations and standard EN 50110-2 on
activities in or near electrical installations. Personnel must be fully familiar with the instructions and warnings contained in this
manual and in other recommendations of a more general nature which are applicable to the situation according to current
legislation.
The above must be carefully observed, as the correct and safe operation of this equipment depends not only on its design but
also on general circumstances which are in general beyond the control and responsibility of the manufacturer. More specifically:
The equipment must be handled and transported appropriately from the factory to the place of installation.
All intermediate storage should occur in conditions which do not alter or damage the characteristics of the
equipment or its essential components.
The equipment must be operated strictly in accordance with the instructions given in the manual, and the
applicable operating and safety principles must be clearly understood.
Maintenance should be performed properly, taking into account the actual service and environmental conditions
in the place of installation.
The manufacturer declines all liability for any significant indirect damages resulting from violation of the guarantee, under any
jurisdiction, including loss of income, stoppages and costs resulting from repair or replacement of parts.
Guarantee
The manufacturer guarantees this product against any defect in materials and operation during the contractual period. In the
event that defects are detected, the manufacturer may opt either to repair or replace the equipment. Improper handling of this
equipment and its repair by the user shall constitute a violation of the guarantee.
Registered Trademarks and Copyrights
All registered trademarks cited in this document are the property of their respective owners. The intellectual property of this
manual belongs to the manufacturer.
In view of the constant evolution in standards and design, the characteristics of the elements contained in this manual are
subject to change without prior notification.
The validity of these characteristics, as well as the availability of components, are subject to confirmation by Ormazabals Technical
- Commercial Department.
IG-159-GB
version 07
20.08.2012 84
CONTENTS
1.
2.
APPLICATIONS .......................................................................................................... 13
2.1. TRANSFORMER PROTECTION ............................................................................... 13
2.2. GENERAL PROTECTION ......................................................................................... 14
2.3. LINE PROTECTION................................................................................................... 15
3.
4.
5.
SENSORS ................................................................................................................... 21
5.1. CURRENT SENSORS ............................................................................................... 21
6.
7.
Page 3 of 84
8.
9.
10.
ANNEX A ..................................................................................................................... 71
11.
ANNEX B ..................................................................................................................... 77
Page 4 of 84
IG-159-GB
version 07
20.08.2012
IG-159-GB
version 07
20.08.2012 84
1. GENERAL DESCRIPTION
The ekorRP range of protection, metering and control units brings together an entire family
of different equipment, which depending on the model, may incorporate protection functions
as well as other functions such as local control, remote control, electrical parameter
metering, automation, etc., related to the current and future automation, control and
protection needs of Transformer and Switching Substations.
Its use in Ormazabals CGMCOSMOS, CGM-CGC and CGM.3 cubicle systems allows the
configuration of customised products for meeting the diverse needs of the different
installations.
The ekorRP protection, metering and control units have been designed to meet the national
and international standard requirements and recommendations that are applied to each of
the parts that make up the unit:
EN 60255, EN 61000, EN 62271-200, EN 60068,
EN 60044, IEC 60255, IEC 61000, IEC 62271-200, IEC 60068, IEC 60044
Page 5 of 84
Designed to be integrated in a cubicle, the ekorRP units also provide the following
advantages over conventional devices:
Reduction in handling of interconnections when installing the cubicle. The only
connection required is limited to MV cables.
Minimisation of the need to install control boxes on the cubicles.
Avoidance of wiring and installation errors; minimisation of commissioning time.
All the units are factory installed, adjusted and checked; each piece of equipment (relay
+ control + sensors) also undergoes a comprehensive check before being installed.
The final unit tests are carried out once the unit is incorporated in the cubicle before
delivery.
They protect a broad power range with the same model (e.g.: ekorRPG from 160 kVA
up to 15 MVA, in CGMCOSMOS system cubicles).
Page 6 of 84
IG-159-GB
version 07
20.08.2012
IG-159-GB
version 07
20.08.2012 84
The unit contains an events log where all of the latest trips made by the protection functions
are registered. In addition, the total number of operations is saved as well as the unit's
settings parameters. The local interface uses menus to provide the instantaneous values of
the current metering for each phase and zero-sequence current, as well as the setting
parameters, trip motives, etc. They can also be accessed via the communication ports.
From a maintenance perspective, the ekorRP units have a series of features that reduce the
time and the possibility of errors in the test and service restoration tasks. The main features
include some toroidal-core current transformers with larger diameters and test connections;
accessible and disconnectable terminal blocks for tests using current injection; and built-in
test contacts, even in the basic models.
Page 7 of 84
Page 8 of 84
IG-159-GB
version 07
20.08.2012
IG-159-GB
version 07
20.08.2012 84
Current
sensors
Bushing
Page 9 of 84
compact block. These transformers supply 1 W when the primary current is 5 A. This power
is enough to allow the units to function correctly.
All the current sensors have an integrated protection against the opening of secondary
circuits, which prevents overvoltages.
Page 10 of 84
IG-159-GB
version 07
20.08.2012
IG-159-GB
version 07
20.08.2012 84
[1]
For more information about the ekorSOFT program, consult Ormazabals IG-155 document.
Page 11 of 84
Page 12 of 84
IG-159-GB
version 07
20.08.2012
IG-159-GB
version 07
20.08.2012 84
2. APPLICATIONS
2.1. TRANSFORMER PROTECTION
The distribution transformers require various
protection
functions.
Their
selection
depends primarily on the power and level of
responsibility they have in the installation.
As an example, the protection functions that
must be implemented to protect distribution
transformers with a power rating between
160 kVA and 2 MVA are the following:
50
Instantaneous
phase
overcurrent. Protects against shortcircuits between phases in the primary
circuit, or high value short-circuit
currents between phases on the
secondary side. This function is
performed by the fuses when the
protection cubicle does not include a
circuit-breaker.
51 Phase overload. Protects
against excessive overloads, which
can deteriorate the transformer, or
against short-circuits in several turns
of the primary windings.
50N Instantaneous earth fault. Protects
against phase to earth short-circuits or
secondary winding short-circuits, from the
primary interconnections and windings.
51N Earth Leakage. Protects against highly
resistive faults from the primary to earth or to
the secondary.
49T Thermometer. Protects
excessive transformer temperature.
against
Unit
ekorRPT
ekorRPG
System
CGMCOSMOS
Systems
CGM-CGC / CGM.3
Type of cubicle
Fuse-combination
switch
50 kVA...2000 kVA
50 kVA...1250 kVA
Circuit-breaker
50 kVA...15 MVA
50 kVA...25 MVA
Page 13 of 84
IG-159-GB
version 07
20.08.2012
Systems
CGM-CGC / CGM.3
Unit
ekorRPT
Type of cubicle
Fuse-combination switch
ekorRPG
Circuit-breaker
50 kVA...15 MVA
50 kVA...25 MVA
Page 14 of 84
IG-159-GB
version 07
20.08.2012 84
Type of cubicle
Circuit-breaker
Page 15 of 84
3. PROTECTION FUNCTIONS
3.1. OVERCURRENT
The units have an overcurrent function for each one of the phases (3 x 50-51) and,
depending on the model, they may have another one for earth (50N-51N). The implemented
protection curves are the ones listed in standard IEC 60255.
Overcurrent functions that can be performed depending on the model:
Overload multicurve protection for phases (51).
Protection of phase-to-earth multicurve faults (51N).
Short-circuit protection (instantaneous) at a defined time between phases (50).
Short-circuit protection (instantaneous) at a defined time between phase and earth
(50N).
Meaning of the curve parameters for phase settings:
t(s) Theoretical tripping time for a fault which evolves with a constant current value.
I Actual current flowing through the phase with the largest amplitude.
In
Rated setting current.
I> Withstand overload increment.
K Curve factor.
I>> Short-circuit current factor (instantaneous).
T>> Short-circuit delay time (instantaneous).
Pick-up current value of NI, VI, and EI curves = 1.1 x In x I>
Pick-up current value of DT curve = 1.0 x In x I>
Instantaneous pick-up current value = In x I> x I>>
In the case of earth settings, the parameters are similar to the phase settings. Each of
them is described below.
to(s) Theoretical tripping time for an earth fault which evolves with a constant
current value I0.
Io Actual current flowing to earth.
In Rated phase setting current.
Io> Withstand earth leakage factor (phase).
Ko Curve factor.
Io>> Short-circuit current factor (instantaneous).
To>> Short-circuit delay time (instantaneous).
Pick-up current value of NI, VI, and EI curves = 1,1 x In x Io>
Pick-up current value of DT curve = 1,0 x In x Io>
Instantaneous pick-up current value = In x Io> x Io>>
Page 16 of 84
IG-159-GB
version 07
20.08.2012
IG-159-GB
version 07
20.08.2012 84
Page 17 of 84
Page 18 of 84
IG-159-GB
version 07
20.08.2012
IG-159-GB
version 07
20.09.2012 84
0-sequence
toroidal
transformer
Page 19 of 84
The current flowing to earth is detected using a toroidal-core current transformer which
covers the three phases. In this way, the metering is independent from the phase current,
thus avoiding errors in the phase metering transformers. In general, this type of protection
must be used when the set earth current is less than 10% of the rated phase current (for
example: for a rated phase current of 400 A with earth faults below 40 A).
On the other hand, in the lines, whose cable stretches are usually long, it is necessary to
identify the fault direction. Otherwise, trips can occur due to capacitive currents from other
lines, when there is not any fault in the line.
The available curves are: normally inverse (NI), very inverse (VI), extremely inverse (EI)
and defined time (DT).
The setting parameters are the same as in the earth faults of the overcurrent functions
(section 3.1 Overcurrent), with the exception that factor Io> is replaced with the value
directly in amps Ig. This way, this parameter can be set to very low earth current values,
regardless of the phase setting current.
Pick-up current value of NI, VI, and EI curves = 1.1x Ig
Pick-up current value of DT curve = Ig
Instantaneous pick-up current value = Ig x Io>>
Page 20 of 84
IG-159-GB
version 07
20.09.2012
IG-159-GB
version 07
20.09.2012 84
4. METERING FUNCTIONS
4.1. CURRENT
The current values measured by the ekorRP units
correspond to the efficient values of each of the
phases I1, I2 and I3. Eight samples from a halfperiod are used and the mean of five consecutive
values is calculated. This measurement is updated
every second. It offers Class 1 meter accuracy,
from 5 A up to 120% of the current sensors
maximum rated range. The zero-sequence current
measurement Io is performed in the same way as
the phase currents.
Current meters: I1, I2, I3 and Io
5. SENSORS
5.1. CURRENT SENSORS
The electronic current transformers are designed for
optimal adaptation to digital equipment technology,
with a slight modification of the secondary interface.
Therefore, the protection, metering and control
equipment for these sensors operate with the same
algorithms and with the same consistency as
conventional devices.
The low power outputs from the sensors can be
adapted to standard values using external amplifiers.
In this way, you can use conventional equipment or
electronic relays.
Page 21 of 84
IG-159-GB
version 07
20.09.2012
Page 22 of 84
Range 5-100 A
300 / 1 A
5 A to 100 A Extd. 130%
5P20
Class 1
0,18 VA
20 kA
50 kA
7,800 A
50-60 Hz
0,72 / 3 kV
139 mm
82 mm
38 mm
1.350 kg
S1 blue, S2 brown
Self-extinguishing polyurethane
B (130 C)
IEC 60044-1
Range 15-630 A
1000 / 1 A
15 A to 630 A Extd. 130%
5P20
Class 1
0.2 VA
20 kA
50 kA
26,000 A
50-60 Hz
0,72 / 3 kV
139 mm
82 mm
38 mm
1.650 kg
S1 blue, S2 brown
Self-extinguishing polyurethane
B (130 C)
IEC 60044-1
IG-159-GB
version 07
20.09.2012 84
ekorRPT / ekorRPG
200/1 A with centre tap (100 + 100 A)
5 A to 630 A
20 kA
50 kA
0.4 VA to 5 A
50-60 Hz
0,72 / 3 kV
139 mm
82 mm
38 mm
1.240 kg
S1 blue, S2 brown
Self-extinguishing polyurethane
B (130C)
0-sequence toroidal
transformer
Page 23 of 84
Page 24 of 84
IG-159-GB
version 07
20.09.2012
IG-159-GB
version 07
20.09.2012 84
Ratio
Metering range
Protection
Metering
Burden
Thermal current
Dynamic current
Saturation current
Frequency
Insulation
Outer dimensions
Inner dimensions
Height
Weight
Polarity
Encapsulation
Thermal class
Reference standard
Range 5-100 A
Range 15-630 A
300 / 1 A
0.5 A to 50 A Extd. 130%
5P10
Class 3
0.2 VA
20 kA
50 kA
780 A
50-60 Hz
0,72 / 3 kV
330 x 105 mm
272 x 50 mm
41 mm
0.98 kg
S1 blue, S2 brown
Self-extinguishing polyurethane
B (130 C)
IEC 60044-1
1000 / 1 A
0.5 A to 50 A Extd. 130%
5P10
Class 3
0.2 VA
20 kA
50 kA
780 A
50-60 Hz
0,72 / 3 kV
330 x 105 mm
272 x 50 mm
41 mm
0.98 kg
S1 blue, S2 brown
Self-extinguishing polyurethane
B (130 C)
IEC 60044-1
Page 25 of 84
IG-159-GB
version 07
20.09.2012
6. TECHNICAL CHARACTERISTICS
6.1. RATED VALUES
Power supply
Current inputs
Accuracy
Frequency
Output contacts
Temperature
Communications
AC
DC
Selfpowered
Consumption
Primary phase
Earth
Voltage
Current
Switching power
Operating
Storage
Front port
24 Vac...110 Vac+/-30%
24 Vdc...125 Vdc +/-30%
>5 A, 230 Vac +/-30%
< 1 VA
5 A...630 A (depending on model)
0.5 A..0.50 A (depending on
model)
20 kA / 50 kA
0.1
5% (minimum 20 ms)
Class 1 / 5P20
50 Hz; 60 Hz +/-1%
250 Vac
10 A (AC)
500 VA (resistive load)
- 40 C to + 70 C
- 40 C to + 70 C
DB9 RS232
Rear port
Protocol
I thermal/dynamic
Impedance
Time delay
Metering / Protection
Dimensions (h x w x d):
Weight
Wiring
Terminals
In cubicle
IP2X
IP3X
IP4X (according to IEC 60255-27)
IK06 (according to EN 50102)
146 x 47 x 165 mm
0.3 kg
0.5...2.5 mm2
Cable/Termination
Insulation resistance
Electric strength
Voltage impulses:
standard
differential
Page 26 of 84
Voltage dips
Ripple
Damped wave 1 MHz
Electrostatic discharges
(IEC 61000-4-2, class IV)
Radiated fields
(IEC 61000-4-3, class III)
Bursts - Fast transients
(IEC 61000-4-4)
Overvoltage pulses
(IEC 61000-4-5)
200 ms
12 %
2.5 kV; 1 kV
8 kV air
6 kV contact
10 V/m
4 kV
4 kV; 2 kV
IG-159-GB
version 07
20.09.2012 84
IEC 60255-22-6
IEC 61000-4-8
IEC 61000-4-12
IEC 60255-25
IEC 60068-2-2
IEC 60068-2-78
IEC 60068-2-30
- 40 C; 16 hrs.
- 40 C; 16 hrs.
+ 60 C; 16 hrs.
+ 70 C; 16 hrs.
+ 40 C; 93%; 10 days
+ 55 C; 6 cycles
10 - 150 Hz; 1 g
10 - 150 Hz; 2 g
11 ms; 5 g
11 ms; 15 g
16 ms; 10 g
1 - 38 MHz, 1g vertical,
0.5 g horizontal
6.8. CE CONFORMITY
This product complies with the European Union directive 2004/108/EC on electromagnetic
compatibility, and with the IEC 60255 international regulations. The ekorRP unit has been designed
and manufactured for use in industrial areas, in accordance with EMC standards. This compliance
results from a test performed according to article 10 of the directive, and included in protocol CE26/08-43-EE-1.
Page 27 of 84
ekorRPG
Distribution general protection unit installed in circuit-breaker cubicles.
The main usage applications are: general protection of lines, private
installations, transformers, capacitor stacks, etc.
They can protect a power range from 50 kVA up to 400 kVA (630 kVA for
CGM-CGC and CGM.3 system cubicles), when they include toroidal-core
current transformers from 5 A to 100 A. With 15 A to 630 A toroidal-core
current transformers, they offer a power range between 160 kVA and 15
MVA (25 MVA for CGM-CGC and CGM.3 system cubicles).
Page 28 of 84
IG-159-GB
version 07
20.09.2012
ekorRPG
20.09.2012 84
ekorRPT
IG-159-GB
version 07
3
Op
No
2
2
Op
Op
3
Op
No
2
2
Op
Op
Yes
Op
Op
Yes
Yes
Op
Op
Yes
Yes
No
Yes
Yes
Op
Yes
No
Yes
Yes
Op
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
Op - Optional
Page 29 of 84
Type:
G For protection cubicle with circuit-breaker
T For fuse protection cubicle
Protection functions:
10 Three phases (3 x 50/51)
20 Three phases and neutral (3 x 50/51 + 50N/51N)
30 Three phases and sensitive neutral (3 x 50/51 + 50Ns/51Ns)
Toroidal-core current transformers:
0 Without toruses
1 Range 5-100 A
2 Range 15-630 A
Power supply:
A Self powered
B Auxiliary power supply (Battery, UPS, etc.)
Example: In the case of a selfpowered relay for a protection cubicle with a circuit-breaker,
with functions 3 x 50/51 + 50Ns/51Ns and toroidal-core current transformers with a range of
5-100 A, the corresponding configurator would be ekorRPG-301A.
Page 30 of 84
IG-159-GB
version 07
20.09.2012
IG-159-GB
version 07
20.09.2012 84
TRANSFORMER PROTECTION
GENERAL PROTECTION
(MV client supply)
[2 ]
1200 A for CGMCOSMOS-P, 480 A for CGM-CMP-F, 36 kV range, and CGM.3 and 300 A for CGM-CMP-F, 24
kV range.
Page 31 of 84
IG-159-GB
version 07
20.09.2012
( )
[kV]
6,6
10
13,8
15
20
Fuse Rated
Voltage
[kV]
3/7,2
6/12
10/24
10/24
10/24
[kVA]
50
100
100
125
160
160
160 ()
100
125 ()
125
[kVA]
1250
1250
1250
1600
2000
442 mm cartridge,
125 A SIBA SSK Fuse
( )
( )
[kV]
6,6
10
13,8
15
20
25
30
Fuse Rated
Voltage
[kV]
3/7,2
6/12
10/24
10/24
10/24
24/36
24/36
[kVA]
50
100
100
125
160
200
250
160
125
63
63
63
80 (2)
80 (2)
[kVA]
1000
1250
800
1000
1250
2000
2500
442 mm cartridge
SIBA SSK fuse (check)
(2)
Selection process for the ekorRPT unit protection parameters in CGMCOSMOS-P cubicles:
1. Determine the required fuse rating to protect the transformer in accordance with the fuse
table in Ormazabals document IG-078. The maximum ratings that can be used are 160 A
for voltages up to and including 12 kV, and 125 A for voltages up to and including 24 kV.
2. Calculate the transformer rated current In = S/3xUn.
3. Define the continuous overload level I>. Normal values in transformers of up to 2000 kVA
are 20% for distribution installations and 5% for power generation installations.
4. Select the transitory overload curve. Coordination between relay curves and LV fuses is
performed with the EI type curve.
5. Define the delay time in transitory overload K. This parameter is defined by the
transformers thermal constant. This way, the greater the constant, the longer it takes for
the transformers temperature to increase under an overload condition; and therefore, the
protection trigger can be delayed longer. The usual value for distribution transformers is
K = 0.2, which means that it trips in 2 s if the overload is 300% in the EI curve.
6. Short-circuit level I>>. The maximum value of the transformers magnetisation current
must be determined. The current peak produced when a no-load transformer is
connected, due to the effect of a magnetised nucleus, is several times greater than the
rated current. This peak value, up to 12 times the rated value (10 times for more than
Page 32 of 84
IG-159-GB
version 07
20.09.2012 84
1000 kVA) has a very high harmonic content, so its fundamental 50 Hz component is
much less. Therefore, a usual setting value for this parameter is between 7 and 10.
7. Instantaneous time delay T>>. This value corresponds with the protection trip time in the
event a short-circuit occurs. It depends on the coordination with other protections and the
usual values are between 0.1 and 0.5 s. If the short-circuit value is high, the fuses will act
in the time determined by their characteristic curve.
8. Determine the current value in case of secondary three-phase short-circuit. This fault
must be cleared by the fuses, and it corresponds with the intersection points maximum
value between the relay and the fuse curves. If the intersection point is greater than the
secondary short-circuit value, the settings must be adjusted to meet this requirement.
To select the ekorRPT unit protection parameters in CGM-CMP-F and CGM.3-P cubicles,
the steps to follow are similar to those proposed in the paragraphs above, except for the first
step. The fuse rating required to protect the transformer is determined according to the fuse
table of Ormazabals documents IG-034 and IG-136 respectively. Please take into
consideration that the minimum protection powers are listed in the table above.
In case of protecting a transformer with following characteristics in CGMCOSMOS cubicle
system:
S = 1250 kVA, Un =15 kV and Uk = 5%
Follow the procedure below for proper coordination between the fuses and the protection
relay:
Fuse selection according to IG-078. 10/24 kV 125 A fuse
Rated current. In = S/3 x Un = 1250 kVA/3 x 15 kV 48 A
Continuous withstand overload 20%. In x I> = 48 A x 1.2 58 A
Extremely Inverse Curve type. E.I.
Transitory overload factor. K =0.2
Short-circuit level. In x I> x I>> = 48 A x 1.2 x 7 404 A
Instantaneous time delay T>> = 0,4 s
Secondary short-circuit. Ics = In x 100/ Uk = 48 A x 100 / 5 960 A
Page 33 of 84
The earth unit setting depends on the characteristics of the line where the unit is installed. In
general, the earth fault values are high enough to be detected as overcurrent. Even in
isolated or resonant earthed neutral networks, the fault value in transformer protection
installations is clearly different from the capacitive currents of the lines. This way, the
transformer protection ekorRPT units are used in isolated neutral networks that do not
require the directional function. The values of the setting parameters must guarantee
selectivity with the main switch protections. Given the variety of protection criteria and types
of neutral used in the networks, it does not exist a single parameterisation; each case
requires a specific parameterisation. For transformers up to 2000 kVA, the settings below are
given as a general example. It must be ensured that they properly apply to the protections
upstream (general, line or main switch protections, among others.)
Page 34 of 84
IG-159-GB
version 07
20.09.2012
IG-159-GB
version 07
20.09.2012 84
Phase
setting
Setting
of
Earth
( )
Rated Current
Time delayed
Instantaneou
s
I>
I>>
T>>
In=S/3xUn = 48 A
EI
DT
1,2
0,2
0,4
Type of Neutral
Time delayed
Instantaneou
s
Io>
Ko
Solid or impedant
NI
DT
0,2
0,2
0,4
Isolated or
resonant
NI
DT
0.1/Ig=2 A(*)
0,2
0,4
Io>> To>>
Page 35 of 84
IG-159-GB
version 07
20.09.2012
The electronic relay is fixed to the cubicle driving mechanism using anchors. The front of the
equipment, which contains the components of the user interface, display, keys,
communication ports, etc., is accessible from the outside without the need to remove the
mechanism enclosure. The rear contains the X1 and X2 connectors, as well as the wiring
that connects it to the power supply board.
.
CGM.3-F
Page 36 of 84
IG-159-GB
version 07
20.09.2012 84
All of the signals that come from the relay go through the board. Hence, the board enables
the unit to be checked. Furthermore, there is a volt-free contact (J3) which is activated
simultaneously with the relay trip. This enables to use conventional current injection
equipment for testing the protection relays.
The selfpowered transformers are also connected to the power supply board using the J7
connector in the selfpowered relays. The signal transformers are connected to the board's J8
connector, the function being to inject current into the secondary in order to test the relay.
The ekorRPT protection, metering and control unit has three connectors (J1, J3 and J4) to
which the user can connect. They are situated on the upper part of the power supply and test
board and their functions are as follows:
Connector
Name
J1
EXT. TRIP
J3
TRIP
J4
V. AUX
Functions
It must be connected to an NO, volt-free
contact. When it is activated, the protection
device trips if an overcurrent protection
function is activated.
This is an NO, volt-free contact which is
activated when the protection device is
tripped. It also works in self powered mode.
Auxiliary power supply input:
230 Vac for selfpowered units and 24 to
125 Vdc or 24 to 110 Vac for those with
auxiliary power supply
(10 kV insulated in relation to the rest of the
equipment, in self powered models).
Normal use
Transformer THERMOMETER.
Protection unit TEST.
Trip SIGNAL for remotelycontrolled installations
Relay power supply (LVB of the
transformer to protect, battery,
etc.).
Page 37 of 84
NOTE
For more details, please see electrical diagram No. 990042, which shows the electrical
connections between the different parts of the ekorRPG unit and the cubicle.
Page 38 of 84
IG-159-GB
version 07
20.09.2012
IG-159-GB
version 07
20.09.2012 84
The earthing screen must NOT go through the toroidal-core current transformer when
it comes out of the part of cable remaining under the toroidal-core current transformer.
In this case, the braided pair is connected directly to the earthing collector of the
cubicle. If there is no braided pair for the earthing screen because it is connected at the
other end (as in metering cubicles), the twisted pair should also not go through the
toroidal-core current transformer.
Page 39 of 84
For phase trips, the test cable must pass through two toroidal-core current transformers.
The cable must pass through each of them in opposite direction; in other words, if in the
first one current flows up bottom, in the other it must flow bottom up so that the sum of
the two currents equals zero and no earth trip occur.
For earth trips, the test cable is passed through a single toroidal-core current transformer
(zero-sequence or phase toroidal, depending on whether a zero-sequence toroidal is
available or not). Trip tests must be performed for all toroidal-core current transformers
to check the proper operation of the complete unit.
Check through the secondary. In this case, the tests are performed on the equipment
when the cable compartment is not accessible. This occurs because the cubicle
outgoing cables are energised and cannot be connected to earth. In this case, it is not
possible to feed a test cable through the toroidal transformers and current must be
injected from the power supply board. This testing method is much better than using
testing equipment (normally more than 100 A).
Page 40 of 84
Access the control's upper compartment where the power supply board is located.
Disconnect the bistable trigger.
Disconnect the blue, brown, black and earth cables of the J8 connector,
corresponding to points J8-6, J8-8, J8-10 and J8-1 respectively.
Connect the previously disconnected cables to the earth points N of connector J83. This operation will short-circuit the current transformers' secondary circuitry.
IG-159-GB
version 07
20.09.2012
IG-159-GB
version 07
20.09.2012 84
Connect the power supply to the J4 connector: 230 Vac for selfpowered units and
24 to 125 Vdc or 24 to 110 Vac for auxiliary power supply units.
Connect the test cable to the J8 connector, bearing in mind the following ratio
between the connector's points and the phases:
Current through L1 J8-6 and J8-1.
Current through L2 J8-8 and J8-1.
Current through L3 J8-10 and J8-1.
Current through L1 and L2 (without earthing current) - J8-6 and J8-8.
Current through L1 and L3 (without earthing current) - J8-6 and J8-10.
Current through L2 and L3 (without earthing current) - J8-8 and J8-10.
Connect the test cable to the current circuit of the tester.
Connect the power supply board's J3 connector to the tester's timer stopper input.
If the switch can be opened, put it in closed position. Reset the latch and remove
the actuating lever in order to leave the cubicle ready for tripping and connect the
bistable trigger. If the switch cannot be operated, the bistable trigger should
remain disconnected and the checking process should be performed as shown in
next section: Check without switch operation.
Inject the secondary test currents taking into account that the transformation ratio
is 300/1 A. Check that the trip times are correct. Check that the trips are correctly
displayed.
NOTE
It is advisable to perform the CHECK THROUGH THE PRIMARY or the CHECK
THROUGH THE SECONDARY annually to guarantee correct equipment operation.
Check without operating the switch. In many occasions, the protection cubicle
switch cannot be operated and therefore, the maintenance checks are performed
exclusively on the electronic unit. In these cases, the following points shall be
considered:
- Always disconnect the bistable trigger. This way, the relay can trip without acting
upon the opening mechanism.
- Inject the current according to the section above "Check through the secondary".
- The toroidal-core current transformers can be verified if the approximate
consumption is known. The current that circulates through the secondary J8-6
(blue), J8-8 (brown) and J8-10 (black) must correspond to the 300/1 A ratio.
- As regards selfpowered relays, check that the selfpowered transformers provide
the operating power needed by the relay, if the primary current is greater than 5 A.
To do this, check that the voltage in connector J7 (between points 1- blue and 2brown) is greater than 10 Vdc.
Page 41 of 84
Page 42 of 84
IG-159-GB
version 07
20.09.2012
IG-159-GB
version 07
20.09.2012 84
(1)
6,6
10
13,8
15
20
25 (1)
30 (1)
Max P.
[kVA]
5000
7500
10000
12000
15000
20000
25000
Selection process for the ekorRPG unit protection parameters in CGMCOSMOS-V, CGMCMP-V and CGM.3-V cubicles:
1. Determine the system power to be protected and select the ekorRPG model in
accordance with the table above.
2. Calculate the rated current In = S/3xUn.
3. Define the continuous overload level I>. Normal values in transformers of up to 2000 kVA
are 20% for distribution installations and 5% for power generation installations.
4. Select the transitory overload curve. Coordination between relay curves and LV fuses is
performed with the EI type curve.
5. Define the delay time in transitory overload K. This parameter is defined by the
transformers thermal constant. This way, the greater the constant, the longer it takes for
the transformers temperature to increase under an overload condition; and therefore, the
protection trigger can be delayed longer. The normal value for distribution transformers is
K = 0.2, which means that it trips in 2 s if the overload is 300% in the EI curve.
6. Short-circuit level I>>. The maximum value of the transformers magnetisation current
must be determined. The current peak produced when a no-load transformer is
connected, due to the effect of a magnetised nucleus, is several times greater than the
rated current. This peak value, up to 12 times the rated value (10 times for more than
1000 kVA) has a very high harmonic content, so its fundamental 50 Hz component is
much less. So, a normal setting value for this parameter is between 7 and 10. In the case
of general protections for several transformers, this value can be lower.
7. Instantaneous time delay T>>. This value corresponds with the protection trip time in the
event a short-circuit occurs. It depends on the coordination with other protections and the
normal values are between 0.1 and 0.5 s.
Page 43 of 84
IG-159-GB
version 07
20.09.2012
In the case of a general protection for two transformers, 1000 kVA each:
S = 2000 kVA, Un =15 kV
The steps to follow for proper setting of the protection relay are the following:
Rated current. In = S / 3 x Un = 2000 kVA / 3 x 15 kV 77 A
Continuous withstand overload 20%. In x I> = 77 A x 1.2 92 A
Extremely Inverse Curve type. E.I.
Transitory overload factor. K =0.2
Short-circuit level. In x I> x I>> = 77 A x 1.2 x 10 924 A
Instantaneous time delay T>> = 0.1 s
The earth unit setting depends on the characteristics of the network where the equipment is
installed. In general, the earth fault values are high enough to be detected as overcurrent. In
the isolated or resonant earthed neutral networks, when the fault value is very low, in other
words, when the earth protection is set to a value below 10% of the rated phase
current, it is recommended that an ultrasensitive earth protection be used.
The values of the setting parameters must guarantee selectivity with the main switch
protections. Given the variety of protection criteria and types of neutral used in the networks,
it does not exist a single parameterisation; each case requires a specific parameterisation.
For transformers up to 2000 kVA, the settings below are given as a general example. It must
be ensured that they properly apply to the protections upstream (general, line or main switch
protections, among others.)
Phase
setting
Setting
of
Earth
( )
Rated
Current
Curve
Instantaneo
us
I>
I>>
T>>
In=S/3xUn =
77 A
EI
DT
1,2
0,2
10
0,1
Type of
Neutral
Curve
Instantaneo
us
Io>
Ko
Io>>
To>>
Solid or
impedant
NI
DT
0,2
0,2
0,1
Isolated or
resonant
NI
DT
0.1 / Ig = 2 A (*)
0,2
0,2
Page 44 of 84
IG-159-GB
version 07
20.09.2012 84
Name
G1-G2
V.AUX
G3-G4
TRIP
G5-G6
EXT.TRIP
G7--G12
IP1,IP2,
Functions
Auxiliary power supply input:
230 Vac for selfpowered units and
24 to 125 Vdc or 24 to 110 Vac for
those with auxiliary power supply
(10 kV insulated in relation to the
rest of the equipment, in self
powered models).
This is an NO, volt-free contact
which is activated when the
protection device is tripped. It
also works in self powered mode.
It must be connected to an NO,
volt-free contact. When it is
activated, the protection device
trips if an overcurrent protection
function is enabled.
Short-circuitable
and
disconnectable terminals for
secondary current circuits.
Normal Use
Relay power
transformer's
battery, etc.).
supply (TS
LV
board,
Transformer
THERMOMETER.
Current
injection
secondary relay tests.
for
Page 45 of 84
NOTE
For more details, please see electrical diagram No. 996410, which shows the electrical
connections between the different parts of the ekorRPG unit and the cubicle.
Page 46 of 84
IG-159-GB
version 07
20.09.2012
IG-159-GB
version 07
20.09.2012 84
Manufactur
er
EUROMOLD
Current
rating [A]
400
630
630
630
12 kV
12 kV
24 kV
24 kV
36 kV
36 kV
Type of
crossType of
crossType of
crossconnecto section connecto section connecto section
r
[mm2]
r
[mm2]
r
[mm2]
400 TE
400 LB
400 TB
440 TB
70-300
50-300
70-300
185-630
K-400TE
K-400LB
K-400TB
K-440TB
25-300
50-300
35-300
185-630
M-400TB
M-440TB
25-240
185-630
For other type of terminals[1], the toroidal-core current transformers must be loosened and
installed directly on the cables, in accordance with the instructions listed in section 7.3.5.
[1]
Page 47 of 84
Open the cubicles circuit-breaker. Close the earthing switch and then close the
circuit-breaker for an effective earthing.
Access the cable compartment and connect the test cable to the test connector
of the toroidal-core current transformers.
Connect the test cable to the current circuit of the tester.
Connect terminals G3-G4 to the tester's timer stopper input.
Open the circuit-breaker. Open the earthing switch and then close the circuitbreaker. To open the circuit-breaker using the protection unit, the earthing switch
must be open.
Inject the test currents and verify the tripping times are correct. Check that the
trips are correctly displayed.
In order to detect phase trips, the test cable must be connected to the test bars of two
toroidal-core current transformers. The current must go through each one in opposite
directions. In other words, if the current flows up bottom in one of the test cables, in the
other it must flow bottom up so that the sum of the two currents is zero and no earth fault
trips occur.
For earth trips, the test cable is connected to a single toroidal-core current transformer
(zero-sequence or phase toroidal transformer, depending on whether a zero-sequence
toroidal is available or not). Trip tests must be performed for all toroidal-core current
transformers to check the proper operation of the complete unit.
Page 48 of 84
IG-159-GB
version 07
20.09.2012
IG-159-GB
version 07
20.09.2012 84
G-7
G12
Page 49 of 84
Page 50 of 84
Always disconnect the bistable trigger. This way, the relay can trip without acting
upon the opening mechanism.
Inject the current according to the section above "Check through the secondary
with circuit-breaker operation".
The toroidal-core current transformers can be verified if the approximate
consumption is known. The current that circulates through the G7 (blue), G8
(brown) and G9 (black) secondaries must correspond to the ratio of 300/1 A or
1000/1 A.
As regards selfpowered relays, check that the selfpowered transformers provide
the operating power needed by the relay, if the primary current is greater than 5 A.
To do this, check that the voltage in connector J7 (between points 1- blue and 2brown) is greater than 10 Vdc.
IG-159-GB
version 07
20.09.2012
IG-159-GB
version 07
20.09.2012 84
As can be seen in the image, the ekorRP protection, metering and control units have a total
of 6 keys:
SET: gives access to the Parameter Setting mode. In addition, the key has a
confirmation function within the various menus of the 'Parameter Setting' mode.
This function is explained in greater detail in this section.
ESC: This key allows the user to return to the main screen ('Display') from any
screen without saving changes made to the settings up to this point. Using this
key, the unit's trip indications can be reset.
Scrolling keys: The Up and Down arrows enable the user to scroll through
the different menus and change values. The 'Right' and 'Left' arrows allow
values in the 'Parameter Setting' menu to be selected for modification, as
detailed later.
Along with the keypad, the relays have an alphanumeric display which makes it easier to use
them. To save energy, the relay has a standby mode (display switched off), which starts to
operate any time the relay does not receive an external signal for 1 minute (pressing of any
key, except the SET key, or communication via RS-232), or for 2 minutes if the user is
modifying the parameters in the Parameter Setting mode. Likewise, if either type of external
signal is received (pressing of the ESC, arrow up, down, left or right keys; or communication
via RS-232) the relay will exit the standby mode and return to its active status, as long as the
relay remains powered.
Page 51 of 84
8.2. DISPLAY
The 'Display' mode is the normal mode of the relay when in
operation. Its main function is to allow the user to view various unit
parameters which can be summarised in 4 groups:
Current metering
Viewing the setting values
Values of the last and penultimate trip
Current date and time
The Display mode is shown by default in the relay, both when it is
switched on and when it returns from its standby status, or when pressing the ESC key from
any screen. In this operating mode, the Up and Down keys are enabled so that the user
can scroll through the various parameters in the Display mode. The SET key gives access
to the Parameter Setting mode.
The following figure shows an example of several 'Display' mode screens for the
ekorRPunits.
The screens shown in the relay display consist of two data lines. The first indicates the
parameter for the specific screen; the second establishes the value of this parameter.
Additionally, error codes can be indicated in both the display screen and the two data lines
(refer to section 8.5: Error codes). These indications are displayed with the other
indications.
A table with the Display mode parameters sequence is shown below. This table includes
the text that appears on the first line of the relay display, along with an explanation of the
corresponding parameter.
Page 52 of 84
IG-159-GB
version 07
20.09.2012
IG-159-GB
version 07
20.09.2012 84
Parameter
I1. A
I2. A
I3. A
I0. A
I>
I 0>
I>>
I 0>>
In. A
I>
K
I>>
T>>
I 0>
K0
I 0>>
T 0>>
H2. A
H2
H2.TM
H2.DT
H2.YE
H2.HR
H2.SE
H1. A
H1
H1.TM
H1.DT
H1.YE
H1.HR
H1.SE
DATE
YEAR
TIME
SEC
Meaning
Phase 1 current metering
Phase 2 current metering
Phase 3 current metering
Zero-sequence current metering
Phase curve type (NI, VI, EI, DT, disabled)
Zero-sequence curve type (NI, VI, EI, DT, disabled)
Instantaneous phase unit enabled/disabled
Instantaneous zero-sequence unit enabled/disabled
Phase full load current
Phase overload factor
Constant Phase multiplier
Phase instantaneous multiplier
Phase instantaneous time delay
Earth leakage factor
Constant Zero-sequence multiplier
Zero-sequence instantaneous multiplier
Zero-sequence instantaneous time delay
Current at last trip
Cause of last trip
Time delay of last trip, from start-up to the trip
Last trip date
Last trip year
Hour and minute of last trip
Last trip second
Penultimate trip current
Penultimate trip cause
Time delay of the penultimate trip, from start up to the trip
Penultimate trip date
Penultimate trip year
Hour and minute of penultimate trip
Penultimate trip second
Current date
Current year
Current time
Current second
Page 53 of 84
In
Pt
(Tr 3 )
The selected full load current value is achieved by always rounding up the value.
Page 54 of 84
IG-159-GB
version 07
20.09.2012
IG-159-GB
version 07
20.09.2012 84
The rest of setting values are fixed (see the table below), although the user can change any
of the values selected in the program from the manual mode.
Phase Protection
Earth Protection
Setting
Automatic Value
Setting
Automatic Value
Overload Factor
Curve Type
Constant Multiplier
Short-circuit Factor
Trip Time
Tripping Enabled
120 %
EI
0,2
10(*)
0,1(*)
DT
20 %
NI
0,2
5
0,1(*)
DT
( )
* For protection using the ekorRPT-101, 201 or 301 models with 5-100 A range toruses, the short-circuit factor
is 7 and the instantaneous tripping time is 0.4.
Page 55 of 84
Page 56 of 84
IG-159-GB
version 07
20.09.2012
IG-159-GB
version 07
20.09.2012 84
Meaning
I>
I 0>
I>>
I 0>>
In. A
I>
K
I>>
T>>
**I0>
K0
I 0>>
T 0>>
DATE
YEAR
TIME
SEC.
*NPER
*PROT
*BAUD
*PARI
*LEN
*STOP
DT.AD
YE.AD
HR.AD
SE.AD
NTP
NTG
*V.0
PSWV
Range
OFF, NI, VI, EI, DT
OFF, NI, VI, EI, DT
OFF, DT
OFF, DT
192 A for ekorRPX-X01
480 A for ekorRPX-X02
1,00 1,30
0,05 1,6
1 25
0,05 2,5
0,1 0,8
0,05 1,6
1 25
0,05 2,5
1 - 31 / 1 - 12
2000 2059
00:00 - 23:59
0 - 59
0 31
0000[3] MODBUS-0001
1,2; 2,4; 4,8; 9,6; 19,2; 38,4
No, even, odd
7; 8
1; 2
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
0000 - 9999
( )
[3]
Page 57 of 84
IG-159-GB
version 07
20.09.2012
Meaning
tP 0W
Tvol
DATE
YEAR
TIME
SEC.
*NPER
*PROT
*BAUD
*PARI
*LEN
*STOP
DT.AD
YE.AD
HR.AD
SE.AD
NTP
NTG
NTE
*V.0
PSWV
( )
[4]
Page 58 of 84
Range
50; 100; 160; 200; 250; 315; 400; 500;
630; 800; 1000; 1250; 1600; 2000
6,6; 10; 12; 13,2; 15; 20; 25; 30
1-31/1-12
2000-2059
00:00-23:59
0-59
0-31
[4]
0000 (MODBUS)-0001
1,2;2,4;4,8;9,6;19,2;38,4
No, even, odd
7, 8
1, 2
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
Cannot be changed
0000-9999
IG-159-GB
version 07
20.09.2012 84
I>
I>>
I 0>>
External trip
Ext
To quit the Trip recognition menu, press the ESC key from any of the menu screens. The
relay recognises that the user has checked the trip and then returns to the first screen of the
Display menu. In any case, the trip data will continue to be available to the user from the
Display menu until two new trips have occurred.
The various screens of the of 'Trip Recognition' menu provide two types of information. The
initial screen shows the current detected at the tripping moment, by phase or earth
depending on the tripped unit. Subsequent Trip Recognition screens display the date and
time of the trip, along with the time elapsed from the unit start up to the trip.
The following table shows the sequence in which the data appear. As in the rest of the
menus, the 'Up' and 'Down' keys are used to scroll throughout the various data.
Parameter
Ix A
Ix TM
Ix DT
Ix YE
Ix HR
Ix SE
Meaning
Current at the tripping moment
Time elapsed from unit start up to the trip
Day and month on which the trip occurred
Year in which the trip occurred
Time at which the trip occurred
Second in which the trip occurred
e1 f,
e2 f,
e3 f or
Page 59 of 84
IG-159-GB
version 07
20.09.2012
Code shown on
the display
ER 01
ER 03
Page 60 of 84
Meaning
230 Vac in the external trip input (this input is to be connected to a volt-free
contact)
Error when opening switch
IG-159-GB
version 07
20.09.2012 84
Phase 1
current
Phase 2
current
Phase instantaneous
multiplier
Phase 3
current
Zero-sequence current
(Io or Ig)
Zero-sequence curve
type
Earth instantaneous
multiplier
Phase instantaneous
enabling
Zero-sequence
instantaneous enabling
Overload factor
Second penultimate
trip
Page 61 of 84
IG-159-GB
version 07
20.09.2012
PARAMETER SETTING
Parameter Configuration
Transformer
configuration
Prompt for
password
Word length
Stop
bit(s)
Date
at last setting
Repeat new
password
Parameter
configuration
Earth leakage
factor
Transmission
speed
Number of
external trips
Phase curve
type
Earth multiplier
constant
Parity
Firmware
version
Zero-sequence
curve type
Earth
instantaneous
multiplier
Word length
Password
modification
Modification
of date
Year
at last setting
Phase
instantaneous
enabling
Earth
instantaneous
time delay
Stop
bit(s)
Modification
of year
Time
at last setting
Current that
caused the trip
Zero-sequence
instantaneous
enabling
Modification
of date
Date
at last setting
Modification
of time
Second
at last setting
Trip time
Modification
of year
Year
at last setting
Repeat new
password
Modification
of second
Number of
phase trips
Date
at trip
Overload factor
Modification
of time
Time
at last setting
Peripheral
no.
Year
at trip
Constant Phase
multiplier
Modification
of second
Second
at last setting
Protocol
no.
Number of
external trips
Time
at trip
Phase
instantaneous
multiplier
Peripheral
no.
Number of
phase trips
Transmission
speed
Firmware
version
Second
at trip
Phase
instantaneous
time delay
Protocol
no.
Parity
Password
modification
Page 62 of 84
Line voltage
Trip
recognition
IG-159-GB
version 07
20.09.2012 84
The on-screen representation of the equipment for LAST and PENULTIMATE trips is
detailed below:
Cause of last trip
Time of last trip
Date of last trip
Year of last trip
Time of last trip
Second last trip
Current penultimate trip
Cause penultimate trip
Time penultimate trip
Date penultimate trip
Year penultimate trip
Time penultimate trip
Second penultimate trip
Figure 8.1: View of last and penultimate trips on the menu map
| amp.
Hn
|Fxy
Hn TM | time
Hn DT | date
Hn YE | year
Hn HR | time
Hn SE | sec.
Page 63 of 84
IG-159-GB
version 07
20.09.2012
Address
Function
Data
CRC
End
Silence
8 BITS
8 BITS
n x 8 BITS
16 BITS
Silence
The MODBUS ADDRESS of the relay (also called peripheral number) is a byte that takes
values between 0 and 31.
The master addresses the slave, indicating its address in the respective field and the slave
answers by indicating its own address. The '0' address is reserved for the 'broadcast' mode
so it can be recognised by all slaves.
Page 64 of 84
IG-159-GB
version 07
20.09.2012 84
Address
Function
Silence
SLAD
Data
ADDR-H
ADDR-L
NDATA-H
NDATA-L
CRC
End
16 BITS
Silence
CRC
End
16 BITS
Silence
Response:
Start
Address
Function
No. of
BYTES
Silence
SLAD
Data
DATA1-H
DATA1-L
.......
where:
SLAD
ADDR-H
ADDR-L
Slave address
High byte of the address for the first register to be read
Low byte of the address for the first register to be read
NDATA-H
NDATA-L
DATA1-H
DATA1-L
N
Data Writing
This makes it possible to write a single register at the address indicated.
Question:
Start
Address
Silence
SLAD
Function
6
Data
ADDR-H
ADDR-L
DATA-H
CRC
DATA-L
16
BITS
End
Silence
Response:
The normal response is an echo of the query received.
where:
SLAD
ADDR-H
ADDR-L
DATA-H
DATA-L
Slave address
High byte of the address for the register to be written.
Low byte of the address for the register to be written.
High byte of the data to be written.
Low byte of the data to be written.
Page 65 of 84
IG-159-GB
version 07
20.09.2012
Address
Function
Error-Code
CRC
End
Silence
SLAD
FUNC_ERR
CODE_ERROR
16 BITS
Silence
where:
SLAD
FUNC_ERR
CODE_ERROR
1
2
3
4
5
6
8
Slave address.
Code of the function requested, with the most significant bit
at 1.
Code of the error occurred.
Error in the number of registers
Wrong address
Incorrect data
attempt made to read a write-only address
session error
EEPROM error
Attempt being made to write in a read-only address
Page 66 of 84
IG-159-GB
version 07
20.09.2012 84
Address
In
0x0000
CURVE_
CURVE_
PHASE
ZERO-SEQ
PHASE_INST
ZERO-SEQ_INST
PHASE_INST_OVERLOAD (I>)
ZERO-SEQ_CURRENT (Io>)
0x0001
K
PHASE_INST
_OCCUR
PHASE_INST
_TIME
0x0005
0x0006
Ko
ZEROSEQ_INST_OCCUR
ZEROSEQ_INST_TIME
PHASE_TRIP_COUNTER
EARTH_TRIP_COUNTER
EXTERNAL_TRIP_COUNTER
USER_PASSWORD
ZERO-SEQ_CURRENT (Io>)
0x0002
0x0003
0x0004
0x0007
0x0008
0x0009
0x000a
0x000b
0x000c
Contents
from 5 to 100 if RATED_I=0
from 15 to 630 if RATED_I=1
0:OFF; 1:NI; 2:VI; 3:EI; 4:DT
0:OFF, 1:DT;
0:100%; 1:101%; 2:102%,... 30:130%
Vector_sum
0-sequence_toroidal
0:10%;1:11%;
0:0.1; 1:0.2; 2:1.5 A
80%
In
0:0.05; 1:0.06; ... 20:1.6
0:3; 1:4;17:20
050 ms, 1 60 ms 270 ms, 3 80
ms 490 ms, 5 100 ms, 6200
ms...2,5 s
from 0000 to 9999
from 0000 to 9999
from 0000 to 9999
from 0000 to 9999
Vector_sum
0-sequence_toroidal
0:10%;1:11%;
0:0.1; 1:0.2; 2:0.3 A
80%
In
Page 67 of 84
IG-159-GB
version 07
20.09.2012
Address
YEAR
MONTH
HOUR
00
PENULT_TRIP
DAY
MINUTE
SECONDS
LAST_TRIP
0x0200
0x0201
0x0202
0x0203
0x0208
Contents
RTC Format
Bit
0
1
2
3
4
5
6
7
PHASE_LAST_TRIP_VALUE
ZERO-SEQ_LAST_TRIP_VALUE
PHASE_LAST_TRIP_TIME
ZERO-SEQ_LAST_TRIP_TIME
YEAR
MONTH
DAY
HOUR
MINUTE
00
SECONDS
PHASE_PENULT_TRIP_VALUE
ZEROSEQ_PENULT_TRIP_VALUE
PHASE_PENULT_TRIP_TIME
ZEROSEQ_PENULT_TRIP_TIME
YEAR
MONTH
DAY
HOUR
MINUTE
00
SECONDS
Phase current L1
Phase current L2
Current metering
Phase current L3
Zero-sequence current
0x0209
0x020a
0x020b
0x020c
0x020d
0x020e
0x020f
0x0210
0x0211
0x0212
0x0213
0x0214
0x0215
0x0216
0x0217
0x0218
0x0219
0x021a
0x021b
0x021c
0X021d
0X021e
0X021f
0X0220
0X0221
0X0222
0X0223
0X0224
Inputs
Software
version
Page 68 of 84
0x0225
functions
0x0226
Contents
Trip by phase
1: L1, 2: L2, 3: L3
Zero-sequence trip
NOT USED
External trip
Cause of the phase trip.
0: overload,
1: short-circuit
Cause of the zerosequence trip.
0: overload,
1: short-circuit
Double tripping
Current in hundredths of an A
Current in hundredths of an A
Time in hundredths of a s
Time in hundredths of a s
RTC Format
Current in hundredths of an A
Current in hundredths of an A
Time in hundredths of a s
Time in hundredths of a s
RTC Format
Hundredths of on A
Hundredths of on A
Hundredths of on A
Hundredths of on A
Bit 0: Input 1,
Bit 1: Input 2, etc.
from 0 to 99
from A to Z
IG-159-GB
version 07
20.09.2012 84
CLOCK
MONTH
HOUR
00
Field
Address
Contents
YEAR
0x0300
0x0301
0x0302
0x0303
DAY
MINUTE
SECONDS
Address
Contents
0x0500
from 0 to 9999
Page 69 of 84
NOTES
Page 70 of 84
IG-159-GB
version 07
20.09.2012
10. ANNEX A
IG-159-GB
Annex A
version 07
Page 72
of 84
20-09-2012
(1)
6,6
10
13,8
15
20
25 (1)
30 (1)
Min P.
[kVA]
[kVA]
Max P.
[kVA]
50
100
100
100
160
200
250
160
200
315
315
400
630
630
5000
7500
10000
12000
15000
20000
25000
Connect braid to
earth collector
4. External connections:
Remove the terminal
box cover.
Connect
to
terminal
block:
IG-159-GB
Annex A
version 07
Page 73
of 84
20-09-2012
5. Set relay:
Automatic mode:
Installation kV and kVA.
Manual mode:
Parameters: I>, I0>, I>>, ...
PHASE
SETTING
Table of settings:
IN
S
(UN 3)
EARTH SETTING
Type of
neutral
Curve
EI
Curve
Instantaneo
us
TD
Instantaneo
us
Solid or
impedant
NI
TD
Isolated or
resonant
NI
TD
I>
I>>
T>>
1,2
0,2
10
0,1
Io>
Ko
Io>>
To>>
0,2
0,2
0,1
0,2
0,2
0,1 /
Ig=2A(*)
( )
IG-159-GB
Annex A
version 07
Page 74
of 84
20-09-2012
the
G5
Check
trip
and
indication EXT.
8. Commissioning:
Check I1 I2 I3.
Check I0 0.
Check 230 Vca connection (if available).
REASON
POSSIBLE CAUSES
Error 01
Incorrectly connected
thermometer
Error 03
Switch Error
I0 0
I1 I2 I3
I123 > 5 A and LED On
switched off
Relay trip in I0>> when
closing switch
Relay trip in I>> when
closing switch
Relay
will
communicate
not
Grid fault
incorrectly connected or Check that the grid and the secondary circuits are
secondary
circuit
not incorrectly connected
disconnected.
Incorrect
toroidal-core
current
transformer
Unbalance
connection
Check secondary circuits
Incorrectly connected toroidal-core current
Selfpowered
transformer
Incorrectly connected relay wiring
Real fault present.
Time T0 >>
Check if T0 >> sufficient, taking into account
insufficient
toroidal vector sum error.
Real fault present.
I >> insufficient
Check parameter I >>, taking into account
transformer current peak (10 times In ).
Incorrect communication cable connections.
Relay in energy-saving mode. Press a button of
Fault in
relay.
communication
Incorrect
configuration
of
communication
parameters.
IG-159-GB
Annex A
version 07
DISPLAY
Page 75
of 84
20-09-2012
Phase 1
current
Phase 2
current
Phase instantaneous
multiplier
Phase 3
current
Zero-sequence current
(Io or Ig)
Zero-sequence curve
type
Earth instantaneous
multiplier
Phase instantaneous
enabling
Zero-sequence
instantaneous enabling
Overload factor
Second penultimate
trip
IG-159-GB
Annex A
version 07
Page 76
of 84
20-09-2012
PARAMETER SETTING
Parameter Configuration
Transformer
configuration
Prompt for
password
Word length
Stop
bit(s)
Date
at last setting
Repeat new
password
Parameter
configuration
Earth leakage
factor
Transmission
speed
Number of
external trips
Phase curve
type
Earth multiplier
constant
Parity
Firmware
version
Zero-sequence
curve type
Earth
instantaneous
multiplier
Word length
Password
modification
Modification
of date
Year
at last setting
Phase
instantaneous
enabling
Earth
instantaneous
time delay
Stop
bit(s)
Modification
of year
Time
at last setting
Current that
caused the trip
Zero-sequence
instantaneous
enabling
Modification
of date
Date
at last setting
Modification
of time
Second
at last setting
Trip time
Modification
of year
Year
at last setting
Repeat new
password
Modification
of second
Number of
phase trips
Date
at trip
Overload factor
Modification
of time
Time
at last setting
Peripheral
no.
Year
at trip
Constant Phase
multiplier
Modification
of second
Second
at last setting
Protocol
no.
Number of
external trips
Time
at trip
Phase
instantaneous
multiplier
Peripheral
no.
Number of
phase trips
Transmission
speed
Firmware
version
Second
at trip
Phase
instantaneous
time delay
Protocol
no.
Parity
Password
modification
Line voltage
Trip
recognition
11. ANNEX B
IG-159-GB
Annex B
version 07
Page 78
of 84
20-09-2012
16
10
16
16
16
50
100
100
125
160
160
160 ()
100
125 ()
125
[kVA]
1250
1250
1250
1600
2000
442 mm cartridge
125 A SIBA SSK Fuse
( )
Line
voltage
Fuse Rated
Voltage
[kV]
[kV]
6,6
10
13,8
15
20
25
30
( )
3/7,2
6/12
10/24
10/24
10/24
24/36
24/36
Fuse Rating
[A]
[kVA]
16
16
10
16
16
25
25
50
100
100
125
160
200
250
Fuse Rating
[A]
160 ()
125
63
63
63
80 (2)
80 (2)
442 mm cartridge
SIBA SSK fuse (check)
(2)
Power
supply board
Protection and
power supply
toroidal-core
current
transformers
Earthing grids
Cables
[kVA]
1000
1250
800
1000
1250
2000
2500
IG-159-GB
Annex B
version 07
Page 79
of 84
20-09-2012
4. External connections:
Remove the control box
cover.
Connect to the power supply
board:
J1: external trip (thermostat)
J4: 230Vac or 48Vdc
(depending on
model A or B)
5. Set relay:
Automatic mode:
Installation kV and kVA.
Manual mode:
Parameters: I>, I0>, I>>, ...
PHASE
SETTING
Table of settings:
Curve
Instantaneous
I>
I>>
T>>
EI
TD
1,2
0,2
0,4
Type of
neutral
Curve
Instantaneous
Io>
Ko
Io>>
To>>
Solid or
impedant
NI
TD
0,2
0,2
0,4
Isolated or
resonant
NI
TD
0,1
0,2
0,4
EARTH
SETTING
IN
S
(UN 3)
IG-159-GB
Annex B
version 07
Page 80
of 84
20-09-2012
Check
trip
indication EXT.
and
8. Commissioning:
Check I1 I2 I3
Check I0 0
Check 230 Vca connection (if available)
REASON
POSSIBLE CAUSES
Error 01
Incorrectly connected
thermometer
Error 03
Switch Error
I0 0
I1 I2 I3
I123 > 5 A and LED On
switched off
Relay trip in I0>> when
closing switch
Relay trip in I>> when
closing switch
Relay
will
communicate
not
Grid fault
incorrectly connected or Check that the grid and the secondary circuits
secondary circuit
are not incorrectly connected
disconnected
Incorrect toroidal-core current transformer
Unbalance
connection
Check secondary circuits
Incorrectly connected toroidal-core current
Self powered
transformer
Incorrectly connected relay wiring
Real fault present.
Time T0 >>
Check if T0 >> sufficient, taking into account
insufficient
toroidal vector sum error.
Real fault present.
I >> insufficient
Check parameter I >>, taking into account
transformer current peak (10 times In ).
Incorrect communication cable connections.
Relay in energy-saving mode. Press a button of
Fault in
relay.
communication
Incorrect
configuration
of
communication
parameters.
IG-159-GB
Annex B
version 07
DISPLAY
Page 81
of 84
20-09-2012
Phase 1
current
Phase 2
current
Phase instantaneous
multiplier
Phase 3
current
Zero-sequence current
(Io or Ig)
Zero-sequence curve
type
Earth instantaneous
multiplier
Phase instantaneous
enabling
Zero-sequence
instantaneous enabling
Overload factor
Second penultimate
trip
IG-159-GB
Annex B
version 07
Page 82
of 84
20-08-2012
PARAMETER SETTING
Parameter Configuration
Transformer
configuration
Prompt for
password
Word length
Stop
bit(s)
Date
at last setting
Repeat new
password
Parameter
configuration
Earth leakage
factor
Transmission
speed
Number of
external trips
Phase curve
type
Earth multiplier
constant
Parity
Firmware
version
Zero-sequence
curve type
Earth
instantaneous
multiplier
Word length
Password
modification
Modification
of date
Year
at last setting
Phase
instantaneous
enabling
Earth
instantaneous
time delay
Stop
bit(s)
Modification
of year
Time
at last setting
Current that
caused the trip
Zero-sequence
instantaneous
enabling
Modification
of date
Date
at last setting
Modification
of time
Second
at last setting
Trip time
Modification
of year
Year
at last setting
Repeat new
password
Modification
of second
Number of
phase trips
Date
at trip
Overload factor
Modification
of time
Time
at last setting
Peripheral
no.
Year
at trip
Constant Phase
multiplier
Modification
of second
Second
at last setting
Protocol
no.
Number of
external trips
Time
at trip
Phase
instantaneous
multiplier
Peripheral
no.
Number of
phase trips
Transmission
speed
Firmware
version
Second
at trip
Phase
instantaneous
time delay
Protocol
no.
Parity
Password
modification
Line voltage
Trip
recognition
IG-159-GB
version 07
20.09.2012
NOTES
Page 83 of 84
Page 84 of 84