Você está na página 1de 100

IEEE Power & Energy Society

1998

TECHNICAL REPORT

PES-TR7
Formerly TP133

Modeling and Analysis of


System Transients Using
Digital Programs
PREPARED BY THE
IEEE Working Group 15.08.09

IEEE 2013 The Institute of Electrical and Electronic Engineers, Inc.


No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior written permission of the publisher.

THIS PAGE LEFT BLANK INTENTIONALLY

IEEE PES Special Publication

MODELING AND ANALYSIS OF SYSTEM


TRANSIENTS

Prepared By IEEE Working Group 15.08.09


MODELING AND ANALYSIS OF SYSTEM TRANSIENTS USING
DIGITAL PROGRAMS

Working Group Chairman


A. J. F. Keri

(American Electric Power)

Task Forces and Chairmen


K. K. Sen (Siemens), Le Tang (ABB)
R. Iravani (Univ. of Toronto)
A. M. Gole (Univ. of Manitoba),
D. W. Durbak (PTI)
A. F. Imece (ABB)
J.A. Martinez-Velasco (Univ. Politec.
de Catalunya*), D. Povh

1) Power Electronics
2) Slow Transients
3) Switching Transients
4) Fast Front Transients
5) Very Fast Front Transients
(Siemens)
6) Protection and Controls

A.K.S. Chaudhary (Cooper Power


System), R.E. Wilson (WAPA)
T.E. Grebe (Electrotek Concepts, Inc)
J.A. Martinez-Velasco ( * )

7) Bibliography

Editors:
A. M. Gole, J. Martinez-Velasco, A. J. F. Keri

Acknowledgments: The Working group was originated and technically


supported by Dr. B. R. Shperling (New York Power Authority). T.E. Grebe
was also the Secretary of the Working Group. Dr. A. M. Gole had also the
difficult job of organizing Task Force reports into this Special Publication.
Tutorial On
Modeling And Analysis

or System Transients Using Digital Programs

Abstracting is permitted with credit to the source. For other copying, reprint, or republication permission, write to the IEEE
Copyright Manager, IEEE Service Center, 445 Hoes Lane, Piscataway, NJ 08855-1331. All rights reserved. Copyright 1998
by The Institute of Electrical and Electronics Engineers, Inc.

IEEE Catalog Number:

99TP133-0

Additional copies of this publication are available from


IEEE Operations Center
P. O. Box 1331
445 Hoes Lane
Piscataway, NJ 08855-1331 USA
1-800-678-IEEE (IndividuaUMember Orders)
1-800-701-IEEE (Institutional Orders)
1-732-981-0060
1-732-981-9667 (FAX)
email: customer.service@ieee.org

TABLE OF CONTENTS

Introduction

1.

Background

1-1

2.

Power Electronics

2-1

3.

Slow Transients

3-1

4.

Switching Transients

4-1

5.

Fast Front Transients

6.

Very Fast Front Transients

6-1

7.

Protection and Controls

7-1

8.

Bib Ii0 graph y ....................... ..... .......

..

..

..

5 -1

8-1

Modelingand Analysis ofSystem Transients Using


Digital Programs
Introduction
IEEE PES Working Group 15.08.09
A.J.F. Keri (Chairman), A.M. Gole
1. INTRODUCTION

1.4 SWITCHING TRANSIENTS

This documentis written in order to provideguidelines for the modeling of power system apparatus for use in
time - domain solutionof electromagnetic transientphenomenon. This publication has been arranged in the following
eight (8) parts.

The range of frequencies of primary interest in a


switching transients study vary from the fundamental power
frequency up to 10kHz. Switching surge modeling guidelines are presentedincluding modeling of the various power
systemcomponents such as transmission lines, cables, transformers, source equivalents, loads and circuit breakers. In
addition, typicalcase studies are also presented.

Part 1 :Background
Part 2 :PowerElectronics
Part 3:Slow Transients
Part 4 :Switching Transients
Part 5 :Fast Front Transients
Part 6 :Very Fast Front Transients
Part 7 :Protection And Control
Part 8 :Bibliography

1.5 FAST FRONT TRANSIENTS

Modeling guidelines are presented for fast front


transients (i.e., frequency range from 10 kHz up to 1 MHz),
with particularemphasison lightningsurge analysis of overhead lines and substation. Modeling philosophies, simplified mathematical relationships, typical data, and examples
are given for various power system components. A case
study is presented in order to illustrate the overall modeling
procedure.

A general statementof each area is as follows.

1.1 BACKGROUND

This section presents a comprehensive summary of


the background and state of the art for the transientsolutions,
representation of control systems, and modeling of power
systemcomponents.

1.6 VERY FAST FRONT TRANSIENTS

The objective of this section is to provide an explanation of the phenomena of very fast transients, in the frequencyrange of 100 kHz to 50 MHz. This type of transients
typically occur in the gas insulated substations (GIS).
Effects and modeling guidelines for GIS are presented. An
example of a GIS calculationwith detailed input data is provided. A simulation accuracyis verifiedwith field measurements.

1.2 POWERELECTRONICS

The guideline presentsthe basic issuesthat are critical for successfully modeling of power electronics devices
and the interfacebetweenpower electronics and the utility or
industrial system. Modeling aspects are presentedfor simulation of the semiconductor switching devices, power electronics system, snubber treatment, and simulation errors and
control. A number of simulation examples, including
FACTS modeling, are presented.

1.7 PROTECTIONAND CONTROL

General guidelines for modeling of protection systems is presented. Because digital modeling of protection
systemsin the electromagnetic transients programs is a relatively new procedure, this section describes the advantages
and limitations of the protection system modeling. Modeling of instrument transformers, relays - electromechanical,
static and microprocessor based are summarizedand models
are presented.

1.3 SLOW TRANSIENTS

Modeling guidelines are presented for investigations of small signal torsional oscillations, large -signalshaft
transient stresses, turbine -blade vibrations, fast bus transfer,
controller interactions, harmonics interaction, and resonance
phenomena. Sample test systems and simulationresults are
provided.

1.8 BIBLIOGRAPHY
A comprehensive list of references on the subjectare provided.

i-I

Digital Computation of Eelectromagnetic


Transients in Power Systems: Current Status
Juan A. Martinez-Velasco
Departament d'Enginyeria Electrica
Universitat Politecnica de Catalunya, Spain
Abstract- This documentpresentsan introductionto time-domain
solution of electromagnetic transients in power systems using a
digitalcomputerCurrently, the mostwidely usedsimulation tools
tosolve electromagnetic transientsare basedonthetrapezoidalrule
andthe methodofcharacteristics(Bergeron'smethod). Onlyworks
related to this solutionalgorithm are considered in this document
whichcoverstwo maintopics: solution techniques and modeling of
powercomponents.
Keywords : Electromagnetic Transients, Time-domain
Simulation, Trapezoidal Rule, Numerical Oscillations, Control
Systems, Modeling.

1. INTRODUCTION
Transient phenomena in power systems are caused by
switching operations, faults, and other disturbances, such as
lightning strokes. They involve a frequency range from DC to
several MHz. A rough distinction is usually made between
electromechanical transients, traditionally covered by transient
stability studies, and electromagnetic transients. The latter type
of transients can occur on a time scale that goes from
microseconds to several cycles; they are a combination of
travelling waves on lines, cables and buses, and of oscillations
in lumped-element circuits ofgenerators, transformers and other
devices. Some electromechanical transients, such as
subsynchronous resonance, for which detailed machine models
are needed, are usually included in this class of transients.
Several tools have been used over the years to analyze
electromagnetic transients. At early stages, miniature power
system models, known as Transient Network Analyzers (INA),
were used. At present, the digital computer is the most popular
tool, although INAs are still used; in addition, the new
generation of real-time digital systems are probably the most
adequate tool in some applications for which either a very
high-speed or a real-time simulation is required.
Many techniques have been developed to solve electromagnetic
transients using a digital computer. They can be classified into
two main groups : frequency-domain and time-domain

1-1

techniques. The subject of this document is the digital


simulation ofelectromagnetic transients in power systems, using
time-domain techniques. Presently, the most widely used
solution method is based on the application of the trapezoidal
rule and the Bergeron's method, also known as method of
characteristics [1] - [6].
This document has been arranged as follows. Section 2 deals
with the basic solution techniques either already implemented
or proposed for implementation in electromagnetic transients
programs (emtps). It covers not only the algorithms aimed at
solving the transient solution, but procedures to reduce
numerical oscillations produced by the trapezoidal rule,
initialization methods, and procedures to solve the interface
between power networks and control systems.
Section 3 presents a summary of modeling works related to the
most important power components taking into account their
frequency-dependent behaviour.
Due to difficulties for developing power component models
accurate enough for a wide frequency range, much work has
been done to provide modeling guidelines for digital simulation
of every type of transient phenomenon. Section 4 summarizes
the work done in this area and reports about works still in
progress.
Some topics, such as parallel computation or real-time emtpbased simulation of electromagnetic transients, which are
closely related to the main subjects of this document are not
covered here.
A selected bibliography related to topics of each part has been
included at the end of this document.

2. SOLUTION METHODS

2.1 TRANSIENT SOLUTION


The studies to solve travelling wave problems by means of a

digital computer were started in the early 1960's using two


different techniques, the Bewley's lattice diagram [7] and the
Bergeron's method [8]. Thesetechniqueswereapplied to solve
smallnetworks, withlinearandnonlinear lumped- parameter, as
well as distributed-parameter elements. The extension to
multinode networks was made by H.W. Dommel [1]. The
Dommel's scheme combined the Bergeron's method and the
trapezoidal rule into an algorithm capable of solving transients
insingle- andmulti-phasenetworks withlumped anddistributed
parameters. This solution method was the origin of the
ElectroMagnetic Transients Program (EMTP), whose
development was supported by Bonneville Power
Administration (BPA).
Thetrapezoidal ruleis usedto convertthedifferential equations
of the networkcomponents into algebraic equations involving
voltages, currents andpastvalues. Thesealgebraic equations are
assembled using a nodal approach
[ G] [ v ( t)] = [i ( t)] - [ I]
(I)
where [G]
[vet)]
[i(t)]
[I]

is the nodal conductance matrix


is the vectorof node voltages
is the vectorof currentsources
is the vectorof "history" terms.

proposed to cope with nonlinear and time-varying elements


[11]. These modifications were based on a current source
representation, a piecewise-linear representation or the
compensation method. Someof the advantages and drawbacks
shownby these approaches were discussed in [5] and [11].
Using compensation, nonlinear elements are represented as
currentinjections whicharesuperimposed to the solution of the
linearnetwork after this solution has been computed. Figure 1
shows the scheme of the compensation method for a single
nonlinear element.

Linear,
tim e invariant
Netwo rk

I
I

Vk m

I
I
@

Nonlinear

equatio r.~

Vk m

lklll

--+

II

,IT

/'

"-

/~

<

~----<:

<,.....

; UJ ......

'0

i~

:o'

'-.

Netw~~k'

e q u a ti on

' ::l

Figure 1. Principles of the compensation method.

Veryoftenthenetwork contains voltage sources toground, then


the equation is split up into part A with unknown voltages and
part B with knownvoltages
(2)

Oncethe solution of the network withoutthe nonlinearelement


has been computed, its contribution is computed from the
following equation
(3)

and the characteristic of the nonlinear element


v km = f(ikm' dikm/dt, t, ... )

(4)

The resulting conductance matrix is symmetrical and remains


unchanged astheintegration isperformed witha fixed time-step
size.Thesolution ofthetransient processis thenobtained using
triangular factorization. One of the main advantages of this
procedure is that it can be applied to networks of arbitrary size
in a very simple fashion.

vkm(O) in (3) indicates the voltage solution acrossthe nodes "k"


and "m'' without the nonlinear element, while rthev is the
Thevenin equivalent resistance.

Bergeron's method can be efficiently used with lossless and


distortionless lines. However, parameters of actual transmission
systems are frequency-dependent. The first works on
frequency-dependent models were performed for telephone
circuits in the 1920's [9]. The first frequency-dependent
transmission line modeldeveloped for EMTP simulations was
implemented in 1973 [10]. Much effort has been made since
then, and some other frequency-dependent line models have
been developed and implemented, see Section 3.2.

The compensation method can be generalized to networks with


several nonlinear components [12]. However, its application is
limited to only one nonlinear elementper node.

Iterative solution methods, such as the Newton's method, are


usedto solvethis step.

Other solution methods has been proposed to solve this


limitation. A very simple procedure based on a predictorcorrector method has been recently presented [13].
An interface for simulation ofHVDC linksand machines, also

basedon the Dommel's algorithm, was presented in [14].


The original Dommel's scheme could be used to solve linear
networks. However, many power components - transformers,
reactors, surge arresters, circuit breakers - presenta nonlinear
behaviour. Several modifications to the basic method were

1-2

The computation of electromagnetic transients with the


trapezoidal rule is performed in the time-domain. Some other
techniques have been developed to solve network equations

using a time-domain solution (z-transform methods [15], wave


digital filters [16]) or a frequency-domain solution [17]. Some
alternative methodologies taking advantage of the Dommel's
scheme have been recently proposed, they use a hybrid
frequency- and time-domain approach [18], or a state equation
modeling [19].
Programs based on the trapezoidal rule are currently the most
widely used for simulation of electromagnetic transients . This
is due to the simplicity of this integration rule, as well as to its
numerical stability. The trapezoidal rule is an A-stable method
which does not produce run-off instability [20]. However, this
rule suffers from some drawbacks: it uses a fixed time-step size
and can originate sustained numerical oscillations. During the
last twenty years several works have been presented to solve or
minimize most of these drawbacks.
The step size determines the maximum frequency that can be
simulated, therefore users have to know in advance what is the
frequency range ofthe transient simulation to be performed. On
the other hand, both slow and fast transients can occur at the
same time in different nodes. A procedure by which two or
more time step sizes can be used in the trapezoidal integration
was presented in [21].

----~------]

a) Scheme of the rectifier

b) Simulation result without the snubber circuit

2.2 NUMERICAL OSCILLATIONS


In many cases, such as switching operations or transitions
between segments in piecewise-linear inductances , the
trapezoidal rule acts as a differentiator, and introduces sustained
numerical oscillations. Several techniques have been proposed
to control or reduce these numerical oscillations.
One of these techniques uses additional damping to force
oscillations to decay [22]. This damping can be provided by the
integration rule itself or externally, by adding fictitious
resistances in parallel with inductances and in series with
capacitors. This method can have an important effect on the
accuracy of the solution.
Another technique is based on the use of snubber (RC) circuits
in parallel with switches. This option is particularly interesting
in power electronics applications as snubber circuits are very
often placed in parallel with semiconductors to limit
overvoltages across them. Figure 2 shows a very simple case of
a half-wave single-phase rectifier. Plots without and with
snubber circuit in parallel with the diode illustrate this drawback
of the trapezoidal rule, and one possible solution.

1-3

, (..,el

c) Simulation result with the snubbercircuit

Fig. 2. Numerical oscillations and their solution.


Some of the most efficient techniques developed to avoid
numerical oscillations are based on the temporary modification
of the solution method, only when numerical oscillations can
occur, without affecting the rest of the simulation. One ofthese
techniques is based on the CDA (Critical Damping Adjustment)
procedure [23], [24]. During a switching operation, CDA uses
a backward Euler rule and two half-size integration steps. This
method does not require recalculation of the admittance matrix.
Another technique is based on interpolation [25]. Several
approaches have been developed. The procedure presented in
[26] uses two time step sizes and represents switching devices
(power electronics components) by means of characteristic
curves . A modified linear interpolation to solve problems
manifested not only in the network solution, but in the control

system too, has been presented in [27].

2.3 INITIALIZATION
The solution of a transient phenomenon is dependent on the
initial conditions with which the transient is started. Although
some simulations can be performed with zero initial conditions,
for instance some lightning surge studies, there are many
instances for which the simulation must be started from powerfrequency steady-state conditions. Capabilities to obtain the
initial steady-state solution are of great importance in emtps. In
addition, an initialization procedure can be a useful tool on its
own, for instance to calculate resonant voltages due to coupling
effects between parallel transmission lines.
The steady-state solution of linear networks at a single
frequency is a rather simple task, and can be obtained using
nodal admittance equations [5]
[Y]

where [V]
[V]
[I]

[V]

[I]

(5)

is the nodal complex admittance matrix


is the vector of node voltages
is the vector of current sources.

Elements of both [V] and [I] are complex phasor values.


As for the transient solution, this equation is partitioned when
the network contains voltage sources to ground
[YAA ]

[VA]

= [I A] -

[YAB]

[VB]

(6)

However, this task can be very complex in the presence of


nonlinearities. Saturation effects in transformers and shunt
reactors, rectifier loads and HVDC converter stations can
produce steady-state harmonics.
The initial solution with harmonics can be obtained using some
simple approaches. The simplest one is known as "brute force"
approach : the simulation is started without performing any
initial calculation and carried out long enough to let the
transients settle down to steady-state conditions. This approach
can have a reasonable accuracy, but its convergence will be very
slow ifthe network has components with light damping. A more
efficient method is to perform an approximate linear ac
steady-state solution with nonlinear branches disconnected or
represented by linearized models. Some emtps have either a
"snapshot" or a "start again" feature. The state of the system is
saved after a run, so later runs can be started at this point. Using
a "brute force" initialization, the system is started from
standstill, once it reaches the steady-state, a snapshot is taken
and saved.

1-4

A significant effort has been made during the last years to


develop efficient procedures for implementation in emtps and
aimed at calculating ac steady-state initial conditions with the
presence of nonlinear components. The techniques can be
divided into three groups: frequency-domain, time-domain, and
hybrid methods.
One of the first methods, known as Initialization with
Harmonics (IwH), was presented in [28]. This procedure uses
an iterative solution based on the superposition of the steadystate phasor solutions at the fundamental frequency and at the
most important harmonic frequencies, with a representation of
nonlinear inductances as harmonic current sources.
An improved version ofthe IwH method was presented in [29].
This procedure uses a harmonic Norton modeling of nonlinear
branches and a quasi-Newton type method.
Several procedures have been proposed to calculate initial
conditions using time-domain techniques. The search of the
periodic steady-state solution is presented as a two-point
boundary value optimization problem. Techniques developed
during the last years are based on an iterative Newton method.
More recent procedures use a shooting method [30], or a
waveform relaxation technique [31]. The latter paper presents
a procedure with a fast and efficient convergence in networks
with nonlinear power elements and ideal diode-type devices.
Hybrid approaches to calculate initial conditions in nonlinear
networks using both frequency- and time-domain techniques
have also been developed [32].
A different solution method to obtain steady-state solution is
needed when initial operating conditions are specified as power
constraints. An initialization procedure, kown as Multiphase
Harmonic Load Flow (MHLF), was presented in [33] and [34].
In this method, static compensators and other nonlinear
elements, under balanced or unbalanced conditions, are
represented by harmonic Norton equivalent circuits. Further
improvements incorporated a synchronous machine model into
the initialization procedure [35]. A simpler multiphase power
flow solution based on the MHLF procedure was presented in
[36]. If this approach is used for emtp initialization, sources
need to be defmed to drive the transient solution at those nodes
for which load flow models were specified.

2.4 CONTROL SYSTEMS


The development of a section for representation of control
systems in transients programs was initially motivated by
studies of HVDC links. The Transient Analysis of Control
Systems (TACS) option was implemented in the BPA EMTP in

1976 [37]. Although the main goal was the simulation ofHVDC
converters, it soon became obvious that TACS had many other
applications, such as the representation of excitation of
synchronous generators, dynamic arcs in circuit breakers, or
protective relays .
Control systems are represented in TACS by block diagrams
with interconnection between system elements. Control
elements can be transfer functions, FORTRAN algebraic
functions, logical expressions and some special devices. The
solution method used by TACS is also based on the trapezoidal
rule. A control block in the s-domain can be described by the
following relationship

= G(s) U(s)

X(s)

(7)

where U(s) and X(s) are respectively the input and the output in
the Laplace domain, and G(s) a rational transfer function
G ( s)

=K

+Ns+ +Ns m
m

Do + D1 S + + Dns

msn

(8)

Transfer functions are converted into algebraic equations in the


time-domain
' x ( t ) =Kdu(t) +hist(t-~t)

(9)

Components other than transfer functions can be included in a


TACS section, but they are seen as nonlinear blocks and not
directly added into the simultaneous solution of transfer
functions.
When a nonlinear block is inside a closed-loop configuration,
a true simultaneous solution is not possible. The procedure
implemented in the TACS solution is simultaneous only for
linear blocks, that is s-transfer functions, and sequential for
nonlinear blocks. When these blocks are present, the loop is
broken and the system is solved by inserting a time delay. These
delays inside control loops, as well as the delay between the
network and the control system, are the sources of different
effects. Instabilities, inaccuracies and numerical oscillations
produced by delays have been reported.
Although the first release ofTACS was a powerful and flexible
tool, new applications have been demanding other capabilities
than those implemented in the original version. One example are
the new digital controls used in static compensators, HVDC
converters and other FACTS devices. The execution of tasks
only when needed, the simulation of conditional branching
(IF-THEN-ELSE) or the manipulation of vector arrays are
capabilities not available in the first TACS releases.

where K is the gain, while c and d are obtained from the


coefficient of the rational transfer function G(s) [5], [37].

Several works have been performed to overcome main


limitations and minimize problems originated by TACS :

A control system with many linear blocks results in a system of


equations with the following general form

* Improvements to solve internal time delays, initialization


problems and some FORTRAN code limitations, were
implemented and presented in [38].

[Ax)

[x]

+ [Ax)

[u]

(10)

[hist]

The resulting algebraic equations of a control system are by


nature unsymmetrical. Due to this fact, the electric network and
the control system were solved separately in the original TACS
release. The network solution is first advanced, network
variables are next passed to the control section, and then control
equations are solved. Finally, the network receives control
commands. The whole procedure introduces a time-step delay ,
see Figure 3.
NETWORK

solution from
t-tIt to t

"'-"

- -----____.

'-""Z

V;ifJe

voltage and
( de_l~Y
c u r r en t. sources,
" U
lime -varying resistan~:

...'<,

etc.. between t ,ut end t


used

8S

node volt a ge s. branch


--........... currents, etc., between
<,<,
i-At. end t used us input

input to NETWORK in

'

--...~

TACS

* A different and simple solution using filter interposition to


solve inaccuracies caused by the interface time delay was
recently presented in [43].

solution from
t M to t

L
I
-_

* Another approach to overcome these limitations was provided


by MODELS [40]. Initially known as "New TACS" , the
MODELS program was developed to substitute the TACS
program. However, it became obvious that both options
provided alternate approaches, and therefore TACS was
preserved in those emtps in which MODELS was imbedded.
* Several techniques can be used to solve simultaneously power
network and control system equations and avoid problems
related to the interface delay . Two procedures using
compensation have been recently developed [41], [42] .

TACS

* Limitations in FORTRAN code capabilities were solved by


developing an interface between TACS and FORTRAN
subroutines. The interface presented in [39] maintains full
TACS capabilities and takes advantage of the FORTRAN
flexibility to represent digital controls.

next step n-om l to t+At.

Figure 3. Interface between a network and a control system.

1 -5

3. MODELING OF COMPONENTS

3.1 INTRODUCTION
An accurate simulation ofevery transient phenomenon requires
a representation of network components valid for a frequency
range that varies from DC to several MHz. An acceptable
representation of each component throughout this frequency
range is very difficult, and for most components is not
practically possible.

Modeling of power components taking into account the


frequency-dependence ofparameters can be practically made by
developing mathematical models which are accurate enough for
a specific range of frequencies. Each range of frequencies
usually corresponds to some particular transient phenomena.
One of the most accepted classification of frequency ranges is
that proposed by the CIGRE WG 33-02 [184]. According to the
CIGRE document, frequency ranges can be classified as four
groups with some overlapping

* low-frequency oscillations, from 0.1 Hz to 3 kHz


* slow-front surges, from 50/60 Hz to 20 kHz
* fast-front surges, from 10 kHz to 3 MHz
* very-fast-front surges, from 100 kHz to 50 MHz.
This part discusses modeling works for some of the most
important network components - overhead lines, insulated
cables, transformers, arresters, network equivalents, rotating
machines, circuit breakers - taking into account their
frequency-dependent behaviour.

3.2 OVERHEAD LINES


Two types of time-domain models have been developed for
overhead lines and insulated cables :
a) Lumped-parameter models, that represent transmission
systems by lumped elements whose values are calculated
at a single frequency
b) Distributed-parameter models, for which two categories
can be distinguished, constant parameter and frequencydependent parameter models.
The first type of models is adequate for steady-state
calculations, although they can also be used for transient
simulations in the neighbourhood of the frequency at which
parameters were evaluated. The most accurate models for
transient calculations are those which take into account the
distributed nature of parameters and consider their
frequency-dependence.
1-6

A significant number of papers dedicated to analyze the


frequency-dependence behaviour of overhead lines and
insulated cables for digital simulation has been presented during
the last 30 years. And although some efficient models are
presently implemented in the most widely used emtps, new
efforts are being now devoted to the development of more
efficient models.
Some of the first papers presenting frequency-dependent line
models for digital simulation were published during the late
1960's and early 1970's [44], [45]. Most models were aimed at
solving transmission-line equations using a time-domain
solution. Those models were based on the modal theory :
multiphase line equations are decoupled through modal
transformation matrices, so that each mode can be separately
studied as a single-phase line. For unbalanced and untransposed
lines, transformation matrices are frequency dependent.
However, it is possible to obtain a good accuracy using constant
transformation matrices [46], [47].
Several approaches using modal theory have been proposed:
weighting functions [10], recursive convolutions [48] - [50],
state-space formulation [51]. One of the most popular models
was presented in [52]; the paper proposed the solution of a
transmission line model using a modified recursive convolution
and assuming frequency-independent transformation matrices.
The transient solution of this model is based on the rational
function approximation of the propagation and characteristic
admittance functions. The order of the rational functions will
depend on the line geometry, the frequency range and the
desired accuracy. A high accuracy can only be obtained with a
large number of real poles. This can slow down the simulation
of large networks. Low-order fittings have been proposed as a
compromise between the solution accuracy and the model
simplicity [53], [54]. The validity and limitations of constant
transformation matrices, as well as guidelines on how to choose
these matrices, were discussed in [55].
A procedure for representing dissipative multiconductor
transmission lines with frequency-dependent parameters in a
wide frequency range has been recently proposed [56]. The
procedure is aimed at evaluating the correcting terms to be
added to the propagation and characteristic admittance functions
calculated according to the solution presented in [52].
New methods using frequency-dependent transformation
matrices have been recently proposed. They are based on a
Newton-Raphson iteration technique [57], vector fitting and
modal decomposition [58], or polar decomposition [59].
A different solution method based on the superposition
principle and the Hartley transform was presented in [60].

Some recent works have shown that the solution of line


equations can be efficiently performed using a phase-domain
formulation, instead of modal-domain [61] - [68]. Reference
[68] uses a second method which combines modal and phase
domain solutions.
All the previous papers consider transmission line
representations taking into account only conductor geometry.
Some other parts ofa transmission line, such as the towers, have
an important influence on its performance in lightning studies.
The concept of nonuniform transmission lines includes the
effect of towers and grounding resistances, as well as corona
effect [69], [70]. In lightning studies, towers are represented by
a surge impedance with an associated travel time. Literature
related to tower modeling can be found in [71] - [74].

Additional works related to cable modeling and some case


studies are presented in [91] - [93].
As mentioned above, a new trend in the solution of cable
equations taking into account frequency-dependence of
parameters is to carry out calculations in the phase-domain [62],
[63], [64], [67].
A method for simulating electromagnetic wave propagation in
coaxial cables represented by finite sections, taking into account
the frequency dependence of cable parameters, was presented
in [94].

3.4

POWER TRANSFORMERS

An accurate representation of a power transformer over a wide


A source of attenuation and distortion of surges and
overvoltages in overhead lines is corona. An important effort
has been made during the last 20 years to understand this effect
and for its representation in transient studies [75] - [79]. Many
interesting papers dealing with corona representation in digital
simulations have also been published [80] - [86].

frequency range is very difficult, despite of its relatively simple


design. In addition, two alternative transformer models can be
used whether surge transfer from one winding to another is not
of concern, or surge transfer has to be computed.
Representations for both situations were proposed in the
document written by the CIGRE WG 33.02 [184].

3.3

A significant effort on transformer modeling has been made


during the last twenty years. Some modeling approaches for use
in transient programs follow:

INSULATED CABLES

The formulation of insulated cable equations and their solution


are similar to those used with overhead lines. However, the
large variety of cable designs makes very difficult the
development of a single model for representation of every type
of cable.
One of the first works dealing with a general formulation of
impedances and admittances of single-core coaxial and
pipe-type cables was presented in [87]. The cable models could
be used to evaluate matrices and equivalent pi-circuits ofcables
and to obtain steady-state initialization at a single frequency, but
they should be used to perform accurate transient calculations.
The validity of this formulation is restricted, as mentioned
above, to transient calculations in the neighbourhood of the
frequency at which parameters are evaluated. The derivation of
cable impedances and admittances was the subject of some
previous works, see [88] for coaxial cables and [89] for
pipe-type cables.
Reference [90] presented a method to solve cable equations
considering the frequency-dependence ofcable parameters. The
solution of the cable equations is performed in the modal
domain and assumes frequency-dependence of modal
transformation matrices. The model is valid for transient
simulations over a wide frequency range. Recent works have
presented new approaches based on vector fitting and modal
decomposition [58], or polar decomposition [59].

1-7

1) The representation of single- and three-phase n-winding


transformers is made in the form of a branch impedance
or admittance matrix [95]. This approach is generally used
to derive models for low-frequency and slow-front
transients. Transformer parameters are both nonlinear and
frequency-dependent. Major causes of iron core
nonlinearities are saturation and hysteresis; one of the
main causes of frequency-dependence are eddy currents.
This approach cannot include nonlinear effects of iron
cores. They are incorporated by connecting nonlinear
inductances at winding terminals, Many built-in models
currently available in several emtps use this type of
representation; their derivation is made from nameplate
data.
Iron core nonlinearities have been the subjects of many
interesting papers [96] - [102]. The representation of eddy
current effects has been analyzed in [103] - [106].
2) Detailed models incorporating core nonlinearities can also
be derived by using the principle of duality from a
topology based magnetic model [107] - [110]. This
approach is very useful to create models accurate enough
for low-frequency and slow-front transients.
A different approach to obtain the equivalent circuit of a
three-phase five-legged transformer, valid also for

low-frequency and slow-front transients, was proposed in


[111]. A hybrid model based on core topology, and
consisting of electric and magnetic circuits was presented
in [112].
3) Previous approaches do not consider frequency-dependent
parameters, they are not useful to represent a transformer
at high frequencies, although they can be improved if
lumped capacitances are connected across transformer
terminals. Models taking into account frequency-dependent
parameters can be divided into two groups : models with
a detailed description of internal windings [113] and
terminal models, based on the fitting of the elements of a
circuit that represents the transformer as seen from its
terminals [114] - [118].
Reference [119] presents a simplified model based on the
classical T-fonn model; this model is extended to high
freque~cie~ by adding winding capacitances and representing
short-circuit branches by RL frequency-dependent equivalent
networks.
A hybrid model for internal resonance studies, and valid for a
wide frequency range - from a few kHz to a few Mhz -, was
presentedin [120].Themodelis based on a coil-by-coil detailed
model plus intercoil black box models.
Detailed models are needed to obtain internal transient voltage
distribution. These models are reasonably accurate for
insulation design, and generally consist of large networks.
However,theymakesystemmodelsunnecessarylargewhenthe
concern is the response at the transformer terminals, Some
effortshavebeen devotedto obtainreduced transformer models
using eitherlinear or nonlinear techniques [121] - [124].
'
Other models, including saturation, hysteresis, as well as
eddy-currentlosses, have been proposed in [125] - [127]. The
performance of different transformer models, most of them
currentlyimplemented in manyemtps,for the simulationof fast
switchingtransients was analyzed in [128].
Usually models are derived considering the behaviour of the
transformer from its terminals, a method for simulation of
internalfaultsinpowertransformers usingcapabilitiesavailable
in some emtps was presented and validated in [129].

related to modeling of surge arresters can be found in [130],


[131], [132].
MOSAs present a frequency-dependent nonlinear characteristic: the voltage across the arrester is a function ofboth the rate
of rise and th~ magnitude of the current conducted by the
arrester.ModelmgofMOSAs was the subject ofa paper written
by the IEEEWG on Surge Arrester Modeling [133]. The paper
proposes a procedureto obtain the parametersof the equivalent
model from manufacturer's data.
A different model that represents the frequency-dependence
behaviour by means of a nonlinear inductance in series with a
nonlinear resistance was proposed in [134]. An algorithm to
derive parametersof the arrester model from test data was also
included.
Modeling guidelines of gapped silicon-carbide surge arresters
~or digital simulationsof slow-front transients were presented
In [135]. The proposed model is based on current-limiting
arrester design. Recommendations to adapt the model for
lightning studies were also included.
(MOV) models suitable for digital
simulation ofsenes compensatedlines have been the subject of
some recent works [136], [137].

~etal-~xide v~stors

3.6

The simulation of transient phenomena in power systems very


often requires a detailed modeling of just a small part of the
system to be studied. Network equivalents can be used to
represent those parts of the system for which a detailed
modeling is not needed. The goal is to reduce the complexity
and the computation time, while the simulation accuracy is
preserved. Several procedures have been proposed since early
1970's to obtain single- and multi-port network equivalents
[138] - [142].
Most of these procedures are based on the frequency response
of the network to be represented by the equivalent and on the
application of a fitting technique to synthesize either a singleor a multi-port circuit which matches the response of the
network over a wide range of frequencies.
3.7

3.5 SURGE ARRESTERS

basic ~es of surge arresters are now in use : gapped


silicon-carbidearrestersand gaplessmetal-oxide surgearresters
(MOSA). Although many of the arresters still in use are the
?lder type gapped silicon-carbide, the majority of the new
mstalled arresters are the gapless metal-oxide type. Literature
~~o

1-8

NETWORK EQUIVALENTS

ROTATING MACHINES

The need for detailed synchronous generator models in


transients programs was motivated by some serious
su~~~chronous resonance (SSR) incidents in the early 1970's.
~tIhtIe~ were concerned about some problems involving
interactions between synchronous generators and power

systems.
The simulation oftorsional interactions between the mechanical
turbine-generator system and the power system needs a very
detailed representation of the generator and the power system.
Several dynamic three-phase synchronous generator models
were developed and implemented in the BPA EMTP at mid
1970's [143], [144]. All those models were based on the Park's
transformation for solving the electrical equations. They
incorporated a detailed representation of mechanical and
electrical parts, used a sophisticated solution method to solve
machine-power system interface, and included interface to
control systems.
Although its development was raised by SSR problems, those
models could also be used for other studies, such as loss of
synchronism, load rejection or transmission line reclosure.
Magnetic saturation effects were not included at early stages. A
simple and efficient representation of magnetic saturation was
added to one model in the late 1970's [145].
Interests in the analysis and simulation of renewable energy
sources motivated the demand for other machine models. A very
powerful and flexible module, known as Universal Machine
(UM), was implemented in the BPA EMTP in 1980 [146]. The
UM module allowed the representation ofup to twelve different
machine models and expanded the applications ofthe program,
for instance to the simulation of adjustable speed drives. The
first UM release had several limitations that were solved in
subsequent versions [147]. Two interface methods,
compensation and prediction, are currently used with this
module.
All the machine models above mentioned are based on the
transformation of phase-quantities into dqo-quantities. The
matrix of self and mutual inductances becomes then constant.
With models based on compensation methods no more than one
machine connected to the same nodes can be simulated. This
limitation is avoided with a prediction-based interface.
However, with this solution method, the prediction of several
electrical variables is needed. This can originate numerical
instability.
The development of a synchronous generator model using
phase-domain equations instead of Park's transformation to
solve the electrical equations has been recently presented [148].
This solution is numerically stable, as no prediction of any
electrical variable is made, and simplifies the inclusion of
saturation effects. With this approach, the matrix of self and
mutual inductances changes with the rotor position, then the
admittance matrix of the network has to be recalculated at each
time step, which generally increases the simulation time.
1-9

Different techniques to solve machine-power system interface


have also been developed and implemented in other transients
programs [149].
Models currently implemented in all emtps are adequate for
simulation of low frequency transients. They are sufficiently
accurate to analyze the interaction between the machine and the
power system, as well as torsional oscillations in the mechanical
part. However, these models are not adequate for simulation of
fast-front transients. Some switching motor operations can
originatesteep-front surges and cause large turn-to-turn winding
stresses. Lightning surges transferred through transformers are
also a source of high stresses and dielectric failures. Recent
works have proposed computer models for analyzing machine
behaviour in fast-front transients and predicting distribution of
interturn voltages caused by steep-fronted surges [150], [151],
[152]. Some of these models have been represented and
simulated using emtp capabilities [150], [152].
Techniques to develop machine models based on their
frequency response have also been proposed [118], [153].
Most emtp studies are dealing with large three-phase
synchronous and induction machines. The analysis and
simulation of small and special machines were presented in
[154], [155].
The simulation of an induction machine using the existing
synchronous machine models available in some emtps was
detailed in [156].
3.8

CIRCUIT BREAKERS

A circuit breaker opens its contacts when a tripping signal is


sent to it. The separation of the contacts causes the generation
of an electric arc. The phenomenon by which the arc is actually
extinguished is very complicated. Although a large number of
arc models have been proposed, there is no general acceptance
for any of them.
Several approaches can be used to reproduce the arc
interruption phenomenon; the most suitable representations in
a transients program are the so called black-box models [157],
[158]. The aim of a black-box arc model is to describe the
interaction of an arc and a electrical circuit during an
interruption process. They consider the arc as a two-pole, and
determine the transfer function using a chosen mathematical
form and fitting free parameters to measured voltage and current
traces. Rather than internal processes, it is the electrical
behaviour of the arc which is of importance. Several levels of
complexity are possible [159], [160] :
1) The breaker is represented as an ideal switch that opens at

first zero current crossing, after the tripping signal is


given. This model can be used to obtain the voltage across
the breaker, which is to be compared with a pre-specified
transient recovery voltage (TRY) withstand capability for
the breaker. This model cannot reproduce any interaction
between the arc and the system.
2) The arc is represented as a time-varying resistance, whose
variation is determined ahead of time based on the breaker
characteristic. This model can represent the effect of the
arc on the system, but requires advanced knowledge of the
effect of the system on the arc.

Several models can also be used to represent a circuit breaker in


closing operations [5] :
1) The simplest model assumes that the breaker behaves as
an ideal switch whose impedance passes instantaneously
from an infmite value, when open, to a zero value at the
closing time. This performance can be represented at any
part of a power cycle.
A closing operation can produce transient overvoltages
whose maximum peaks depend on several factors, for
instance the network representation on the source side of
the breaker, or the charge trapped on transmission lines in
a reclosing operation. One of the factor which has more
influence on the maximum peak is the instant of closing,
which can be different for every pole of a three-phase
breaker.

3) The most advanced models represent the breaker as a


dynamically varying resistance or conductance. They can
represent both the effect of the arc on the system and the
effect of the system on the arc. No precomputed TRY
curves are required. Most of these models rely on a first

1 dg _ ( 1

g dt

"1[1 i I

g]

P [j i

vi

g]

- 1

Most transient programs allow users to analyze the


influence of this factor and obtain a statistical distribution
of switching overvoltages, usually provided in the form of
an accumulative frequency distribution. Two types of
switches can be represented:

)
(11)

a - The closing time of a switch is systematically varied


from a minimum to a maximum instant in equal
increments of time; this type is known as systematic switch.

order differential equation


where g
is the arc conductance
v
is the arc voltage
i
is the arc current
't ,P are black-box model parameters.
These models are generally developed to determine initial
arc quenching, that is to study the thermal period only,
although some can also be used to determine arc reignition
due to insufficient voltage withstand capability of the
dielectric between breaker contacts. Their most important
application cases are short line fault interruption and
switching of small inductive currents.
Many models for circuit breakers, represented as a dynamic
resistance/conductance, have been proposed. A survey on
black-box modeling of gas (air, SF6) circuit breakers was
presented in [158]. The emtp implementation of three dynamic
arc models, adequate for gas and oil circuit breakers, was
presented in [161]. All those models are useful to represent a
circuit breaker during the thermal period, models for
representation of SF6 breakers during thermal and dielectric
periods were discussed and used [162], [163]. The development
of a user-defined model based on the Newton's method was
proposed in [164]. A new model also based on the Newton's
method and a predictor for calculation ofthe arc resistance was
recently presented [165].
A vacuum circuit breaker has a different performance, its
representation has to consider its statistical properties. Models
for this type of breaker were presented in [166] and [167].

1-10

b - The closing time is randomly varied according to


either a normal (Gaussian) or an uniform distribution; this
type is known as statistical switch. Data required to
represent these switches are the mean closing time, the
standard deviation and the number of switching operations.
When a pre-insertion resistor is used to mitigate switching
overvoltages, the closing time of both main and auxiliary
contacts are statistically determined.
2) The breaker model assumes that there is a closing time
from the moment at which the contacts start to close to the
moment that they finally make. The withstand voltage
decreases as the separation distance between contacts
decreases, an arc will strike before the contacts have
completely closed if the voltage across them exceeds the
withstand voltage of the dielectric medium. Modeling of
the pre-strike effect and its influence on the switching
overvoltages produced during line energization has been
analyzed in [168].
Similar models can be used with other switching devices, for
which a representation for both opening and closing operations
can be needed.
3.9

OTHER COMPONENTS

Capabilities currently available in most emtps make practically

possibleuser-developed modelsof thosecomponents for which


a built-in model has not been implemented. In fact, this is the
case for some componentmodels discussedabove
* a transformermodel for low-frequency transientsbased on
the principle of duality has not been implemented in any
emtp, the capabilities needed to develope such a model
have been used in some papers [107]

there is no built-in model for circuit breakers in most


emtps, but its representation can be made using branches
and control features, available in all emtps [160], [164]

althoughthere is a built-in surge arrestermodel


implemented in all emtps, it is not adequate for lightning
studies; users have to improve this model by taking
advantageof other capabilities.
Semiconductors are usuallyrepresentedas ideal switchesin all
switchingoperations,althoughsometransientsprogramsallow
usersto considerignitionvoltagesandholdingcurrents. As with
other components, capabilities available in some transient
programscan be used to developmore accuraterepresentations
[169], [170].
The list of components for which a built-in model is not
available might also include instrument transformers [171] [175], protective relays [176] - [181], fuses [182], [183]. The
implementation ofmodelsfor instrumenttransformers andsome
types of relays in one emtp was presented in [178].

the probability of insufficient or wrong modeling. In


addition, a very detailed representation of a system will
require very long simulation time. Some experience will
be therefore needed to decide how detailed the system
should be and choose the model for the most important
components.
Presently there are several sources where it is possible to
consult modeling guidelines of power components for timedomaindigital simulations :
1) One of the first document published on this subject was
that produced by the CIGRE WG 33-02 [184]; it covers
the most important power components and proposes the
representation of each component taking into account the
frequency range of the transient phenomena to be
simulated.
2) Modeling guidelines can also be found in the documents
produced by the IEEE Working Group on Modeling and
Analysis of System Transients Using Digital Programs.
The group was created in 1991 and later split up into 6
Task Forces. Followinga different approach to that of the
CIGREWG, each TF was created to produce
documentation on a particulartype of studies : Low Ftapn:y
Transients, SwitchingTransients, Fast Front
Transients, Very Fast Transients, Power Electronics,
Protection and Control. Up to date, several papers have
been presented [185] - [190].
3) Currently, the IEC Working Group 28-04 is dealing with
the same subject. This WG started its tasks in 1996. The
aim is to produce a document on modeling guidelines for
digital calculation of overvoltages.

4. MODELINGGUIDELINES
The followingaspectsareto be consideredin digitalsimulations
of electromagnetic transients [184] :
a) Very often only approximated or estimated values are used
for some parameterswhose influenceon the representation
of a component can be important or very important. In
general, this happens with some basic parameters and
frequency-dependent parametersin simulations of fast and
very fast front transients. In addition, it is important to
take into account that some parameters may change due to
climatic conditions or be dependenton maintenance.
b) In many overvoltages studies it is the maximum peak
which is of interest. This maximum usually occurs during
the first oscillation after the transient phenomenon starts.
Large differences in peak values are mainly due to a poor
representationof losses, while deviations in inductances or
capacitances will lead to time shifting of the peak but not
to importantdifferences betweenthe maximumvalues.
c) The more components the system in study has, the higher
1-11

5. CONCLUSIONS
Time-domain simulations of electromagnetic transients using
digitalcomputers were started in early 1960's.Currently, most
transientsprograms are based on the Dommel'sscheme which
combines the trapezoidalrule and the Bergeron'smethod.
Muchworkhas been doneto solvesomeofthe main drawbacks
and limitations of the originalscheme,i.e solution of nonlinear
networks, elimination of numerical oscillations. In addition, a
significanteffort has been dedicatedto the developmentof new
models, specially frequency-dependent models for the most
importantpower components.
The development of the first tools was mainlymotivatedby the
calculation of overvoltages. Presently most emtps can be used
for simulating a broad spectrum of transient phenomena in
power systems : subsynchronous resonance, power quality

analysis, AC-DC links, FACTS and Custom Power


technologies, electronically-controlled drives.
Due to the wide range oftransient phenomena in power systems
and the complexity of many studies, modeling guidelines are
needed to choose a correct representation of the most critical
components of the system to be simulated. Several works have
been published during the last decade aimed at providing these
guidelines. However, some work is still needed to solve
important limitations, i.e. the representation of some
components is very complex, reliable data are not always
available.

[12]

[13]

[14]

[15]
6. REFERENCES
[1]

[2]

[3]

[4]

[5]

[6]
[7]

[8]

[9]

[10]

[11]

H.W. Dommel, "Digital computer solution of


electromagnetic transients in single- and multi-phase
networks", IEEE Trans. on Power Apparatus and
Systems, vol. 88, no. 2, pp. 734-741, April 1969.
H.W. Dommel and W. Scott Meyer, "Computation of
Electromagnetic Transients", Proc. of IEEE, vol. 62,
no. 7, pp. 983-993, July 1974.
H.W. Dommel, "Techniques for analyzing electromagnetic transients", IEEE Computer Applications in
Power, vol. 10, no. 3, pp. 18-21, July 1997.
"Digital Simulation of Electrical Transient
Phenomena", A. Phadke (ed.), IEEE Tutorial Course,
Course Text 81 EHOI73-5-PWR.
H.W. Dommel, Electromagnetic Transients Program.
Reference Manual (EMTP Theory Book), Bonneville
Power Administration, Portland, 1986.
J.A. Martinez-Velasco (Ed.), Computer Analysis of
Electric Power System Transients, IEEE Press, 1997.
L.O. Barthold and O.K. Carter, "Digital travelingwave solutions. 1 - Single-phase equivalents", AlEE
Trans., vol. 80, pte III, pp. 812-820, December 1961.
W. Frey and P. Althammmer, "The calculation of
transients on lines by means of a digital computer",
Brown Boveri Rev., vol. 48, pp. 334-355, May/June
1961.
J.R. Carson, "Wave propagation in overhead wires
with ground return", Bell Syst. Tech. J., vol. 5, pp.
539-554, 1926.
W. Scott Meyer and H.W. Dommel, "Numerical
modeling of frequency dependent transmission-line
parameters in an electromagnetic transients program",
IEEE Trans. on Power Apparatus and Systems, vol.
93, no. 5, pp. 1401-1409, September/October 1974.
H.W. DommeI, "Nonlinear and time-varying elements
in digital simulation of electromagnetic transients",
IEEE Trans. on Power Apparatus and Systems, vol.
1-12

[16]

[17]

[18]

[19]

[20]

[21]

[22]

[23]

[24]

90, no. 6, pp. 2561-2567, November/December 1971.


H.W. Dommel, "Usefulness and limitations of multiterminal reduced circuits", Proceedings of11th PSCC,
pp. 1155-1160, August 30 - September 3, 1993,
Avignon (France).
T. Noda, K. Yamamoto, N. Nagaoka and A. Ametani,
"A predictor-corrector scheme for solving a nonlinear
circuit", Proceedings of IPST'97, pp. 5-10, June 2226, 1997, Seattle.
D.A. Woodford, A.M. Oole and R.Z. Menzies,
"Digital simulation of de links and ac machines", IEEE
Trans. on Power Apparatus and Systems, vol. 102, no.
6, pp. 1616-1623, June 1983.
W. Derek Humpage, Z-transform Electromagnetic
Transient Analysis in High-Voltage Networks, Peter
Peregrinus Ltd., London, 1982.
M. Roitman and P.S.R. Diniz, "Power system
simulation based on wave digital filters", IEEE Trans.
on Power Delivery, vol. 11, no. 2, pp. 1098-1104,
April 1996.
J.P. Bickford, N. Mullineux and J.R. Reed,
Computation of Power System Transients, Peter
Peregrinus Ltd., London, 1976.
M. D'Amore and M.S. Sarto, "A new efficient
procedure for the transient analysis of dissipative
power networks with nonlinear loads", IEEE Trans. on
Power Delivery, vol. 11, no. 1, pp. 533-539, January
1996.
Y. Kang and J.D. Lavers, "Transient analysis of
electric power systems : Reformulation and theoretical
basis", IEEE Trans. on Power Systems, vol. 11, no. 2,
pp. 754-760, May 1996.
S.C. Tripathy, N.D. Rao and S. Elangovan,
"Comparison of stability properties of numerical
integration methods for switching surges", IEEE Trans.
on Power Apparatus and Systems, vol. 97, no. 6, pp.
2318-2326, November/December 1978.
A. Semlyen and F. de Leon, "Computation of electromagnetic transients using dual or multiple time steps",
IEEE Trans. on Power Systems, vol. 8, no. 3, pp.
1274-1281, August 1993.
F.L. Alvarado, R.H. Lasseter and J.J. Sanchez,
"Testing of trapezoidal integration with damping for
the solution of power transient studies", IEEE Trans.
on Power Apparatus and Systems, vol. 102, no. 12,
pp. 3783-3790, December 1983.
J.R. Marti and J. Lin, "Suppression of numerical
oscillations in the EMTP", IEEE Trans. on Power
Systems, vol. 4, no. 2, pp. 739-747, May 1989.
J. Lin and J.R. Marti, "Implementation of the CDA
procedure in the EMTP", IEEE Trans. on Power
Systems, vol. 5, no. 2, pp. 394-402, May 1990.

[25]

B. Kulicke, "Simulation program NETOMAC :


Difference conductance method for continuous and
discontinuous systems", Siemens Research and
Development Reports, vol. 10, no. 5, pp. 299-302,
1981.
[26] T.L. Maguire and A.M. Gole, "Digital simulation of
flexible topology power electronic apparatus in power
systems", IEEE Trans. on Power Delivery, vol 6, no.
4, pp. 1831-1840, October 1991.
[27] P. Kuffel, K. Kent and G. Irwin, "The implementation
and effectiveness of linear interpolation within digital
simulation", Electrical Power and Energy Systems, vol.
19, no. 4, pp. 221-228, May 1997.
[28] H.W. Dommel, A. Van and S. Wei, "Harmonics from
transformer saturation", IEEE Trans. on Power
Systems, vol. 1, no. 2, pp. 209-215, April 1986.
[29] X. Lombard, J. Masheredjian, S. Lefebvre and C.
Kieny, "Implementation of a new harmonic
initialization method in EMTP", IEEE Trans. on
Power Delivery, vol. 10, no. 3, pp.1343-1352, July
1995.
[30] B.K. Perkins, J.R. Marti and H.W. Dommel,
"Nonlinear elements in the EMTP : Steady-state
initialization", IEEE Trans. on Power Systems, vol. 10,
no. 2, pp. 593-601, May 1995.
[31] Q.Wang and J.R. Marti, "A waveform relaxation
technique for steady state initialization of circuits with
nonlinear elements and ideal diodes", IEEE Trans. on
Power Delivery, vol. 11, no. 3, pp. 1437-1443, July
1996.
[32] G. Murere, S. Lefebvre and X.D. Do, "A generalized
harmonic balance method for EMTP initialization",
IEEE Trans. on Power Delivery, vol. 10, no. 3, pp.
1353-1359, July 1995.
[33] W. Xu, J.R. Marti and H.W. Dommel, "A multiphase
harmonic load flow solution technique", IEEE Trans.
on Power Systems, vol. 6, no. 1, pp. 174-182,
February 1991.
[34] W. Xu, J.R. Marti and H.W. DommeI, "Harmonic
analysis of systems with static compensators", IEEE
Trans. on Power Systems, vol. 6, no. 1, pp. 183-190,
February 1991.
[35] W. Xu, J.R. Marti and H.W. Dommel, "A
synchronous machine model for three-phase harmonic
analysis and EMTP initialization", IEEE Trans. on
Power Systems, vol. 6, no. 4, pp. 1530-1538,
November 1991.
[36] J.J. Allemong, R.J. Bennon and P.W. Selent,
"Multiphase power flow solutions using EMTP and
Newtons method", IEEE Trans. on Power Systems,
vol. 8, no. 4, pp. 1455-1462, November 1993.
[37] L. Dube and H.W. Dommel, "Simulation of control
1-13

systems in an electromagnetic transients program with


TACS", Proc. ofIEEE PICA, pp. 266-271,1977.
[38] R. Lasseter and J. Zhou, "TACS enhancements for the
Electromagnetic Transient Program", IEEE Trans. on
Power Systems, vol. 9, no. 2, pp. 736-742, May 1994.
[39] L.X. Bui, S. Casoria, G. Morin and J. Reeve, "EMTP
TACS-FORTRAN interface development for digital
controls modeling", IEEE Trans. on Power Systems,
vol. 7, no. 1, pp. 314-319, February 1992.
[40] L. Dube and I. Bonfanti, "MODELS : A new
simulation tool in the EMTP", European Transactions
on Electrical Power Engineering, vol. 2, no. 1, pp.
45-50, January/February 1992.
[41] A.E.A. Araujo, H.W. Dommel and J.R. Marti,
"Simultaneous solution of power and control
equations", IEEE Trans. on Power Systems, vol. 8, no.
4, pp. 1483-1489, November 1993.
[42] S. Lefebvre and J. Mahseredjian, "Improved control
systems simulation in the EMTP through
compensation", IEEE Trans. on Power Delivery, vol.
10, no. 4, pp. 1654-1662, April 1995.
[43] X. Cao et al., "Suppression of numerical oscillation
caused by the EMTP-TACS interface using filter
interposition", IEEE Trans. on Power Delivery, vol.
11, no. 4, pp. 2049-2055, October 1996.
[44] A. Budner, "Introduction of frequency-dependent line
parameters into an electromagnetic transients
program", IEEE Trans. on Power Apparatus and
Systems, vol. 89, no. 1, pp. 88-97, January 1970.
[45] J.K. Snelson, "Propagation of travelling waves on
transmission lines - Frequency dependent parameters",
IEEE Trans. on Power Apparatus and Systems, vol.
91, no. 1, pp. 85-91, January/February 1972.
[46] P.C. Magnusson, "Traveling waves on multiconductor open-wire lines. A numerical survey of the
effects of frequency dependence of modal
composition", IEEE Trans. on Power Apparatus and
Systems, vol. 92, no. 3, pp. 999-1008, May/June
1973.
[47] R.G. Wesley and S. Selvavinayagamoorthy,
"Approximate frequency-response values for
transmission line transient analysis", Proc. lEE, vol.
121, no. 4, pp. 281-286, April 1974.
[48] A. Semlyen and A. Dabuleanu, "Fast and accurate
switching transient calculations on transmission lines
with ground return using recursive convolutions",
IEEE Trans. on Power Apparatus and Systems, vol.
94, no. 2, pp. 561-571, MarchlApri I 1975.
[49] A. Ametani, "A highly efficient method for calculating
transmission line transients", IEEE Trans. on Power
Apparatus and Systems, vol. 95, no. 5, pp. 1545-1551,
September/October 1976.

[50]

A. Semlyen, "Contributions to the theory of calculation


of electromagnetic transients on transmission lines with
frequency dependent parameters", IEEE Trans. on
Power Apparatus and Systems, vol. 100, no. 2, pp.
848-856, February 1981.
[51] J.F. Hauer, "State-space modeling of transmission line
dynamics via nonlinear optimization", IEEE Trans. on
Power Apparatus and Systems, vol. 100, no. 12, pp.
4918-4924, December 1981.
[52] J.R. Marti, "Accurate modeling of frequencydependent transmission lines in electromagnetic
transient simulations", IEEE Trans. on Power
Apparatus and Systems, vol. 101, no. 1, pp. 147-155,
January 1982.
[53] L. Marti, "Low-order approximation of transmission
line parameters for frequency-dependent models" ,
IEEE Trans. on Power Apparatus and Systems, vol.
102, no. 11, pp. 3582-3589, November 1983.
[54] A. Oguz Soysal and A. Semlyen, "Reduced order
transmission line modeling for improved efficiency in
the calculation of electromagnetic transients", IEEE
Trans. on Power Systems, vol. 9, no. 3, pp. 14941498, August 1994.
[55] J.R. Marti, H.W. Dommel, L. Marti and V.
Brandwajn, "Approximate transformation matrices for
unbalanced transmission lines", Proc. ofthe 9th Power
Systems Computer Conference, Cascais (Portugal),
1987.
[56] M. D'Amore and M.S. Sarto, "Modelling of lossy
ground parameters in the EMTP for very-fast transient
analysis", Proceedings ofIPST'97, pp. 49-54, June 2226, 1997, Seattle.
[57] L.M. Wedepohl, H.V. Nguyen and G.D. Irwin,
"Frequency-dependent transformation matrices for
untransposed transmission lines using Newton-Raphson
method", IEEE Trans. on Power Systems, vol. 11, no.
3, pp. 1538-1546, August 1996.
[58] B. Gustavsen and A. Semlyen, "Simulation of
transmission line transients using vector fitting and
modal decomposition", IEEE Trans. on Power
Delivery, vol. 13, no. 2, pp. 605-614, April 1998.
[59] B. Gustavsen and A. Semlyen, "Calculation of
transmission line transients using polar decomposition",
IEEE Trans. on Power Delivery, vol. 13, no. 3, pp.
855-862, July 1998.
[60] R. Mahmutcehajic, S. Babic, R. Gacanovic and S.
Carsimamovic, "Digital simulation of electromagnetic
wave propagation in a multiconductor transmission
system using the superposition principle and Hartley
transform", IEEE Trans. on Power Delivery, vol. 8,
no. 3, pp. 1377-1385, July 1993.
[61] A. Oguz Soysal and A. Semlyen, "State equation
1-14

[62]

[63]

[64]

[65]

[66]

[67]

[68]

[69]

[70]

[71]

[72]

approximation of transfer matrices and its application


to the phase domain calculation of electromagnetic
transients", IEEE Trans. on Power Systems, vol. 9, no.
1, pp. 420-428, February 1994.
B. Gustavsen, J. Sletbak and T. Henriksen,
"Calculation of electromagnetic transients in
transmission cables and lines taking frequency
dependent effects accurately into account", IEEE
Trans. on Power Delivery, vol. 10, no. 2, pp.
1076-1084, April 1995.
T. Noda, N. Nagaoka and A. Ametani, "Phase domain
modeling of frequency-dependent transmission lines by
means of an ARMA model", IEEE Trans. on Power
Delivery, vol. 11, no. 1, pp. 401-411, January 1996.
T. Noda, N. Nagaoka and A. Ametani, "Further
improvements to a phase-domain ARMA line model in
terms of convolution, steady-state initialization, and
stability", IEEE Trans. on Power Delivery, vol. 12,
no. 3,1327-1334, July 1997.
F. Castellanos and J.R. Marti, "Full frequencydependent phase-domain transmission line model",
IEEE Trans. on Power Systems, vol. 12, no. 3, pp.
1331-1339, August 1997.
H.V. Nguyen, H.W. Dommel and J.R. Marti, "Direct
phase-domain modeling of frequency-dependent
overhead transmission lines", IEEE Trans. on Power
Delivery, vol. 12, no. 3, 1335-1342, July 1997.
A. Morched, B. Gustavsen and M. Tartibi, "A
universal model for accurate calculation of
electromagnetic transients on overhead lines and
underground cables", Paper presented at the 1997
IEEE PES Summer Meeting, July 20-24, 1997, Berlin.
B. Gustavsen and A. Semlyen, "Combined phase and
modal domain calculation of transmission line
transients based on vector fitting", IEEE Trans. on
Power Delivery, vol. 13, no. 2, pp. 596-604, April
1998.
M.T. Correia de Barros and M.E. Almeida,
"Computation of electromagnetic transients on
nonuniform transmission lines", IEEE Trans. on Power
Delivery, vol. 11, no. 2, pp. 1082- 1091, April 1996.
H.V. Nguyen, H.W. Dommel and J.R. Marti,
"Modeling of single-phase nonuniform transmission
lines in electromagnetic transient simulations", IEEE
Trans. on Power Delivery, vol. 12, no. 2, 916-921,
April 1997.
W.A. Chisholm, Y.L. Chow and K.D. Srivastava,
"Lightning surge response of transmission towers",
IEEE Trans. on Power Apparatus and Systems, vol.
102, no. 9, pp. 3232- 3242, September 1983.
W.A. Chisholm and Y.L. Chow, "Travel time of
transmission towers", IEEE Trans. on Power

[73]

[74]

[75]

[76]

[77]

[78]

[79]

[80]

[81]

[82]

[83]

[84]

Apparatus and Systems, vol. 104, no. 10, pp. 2922


-2928, October 1985.
M. Ishii et aI., "Multistory transmission tower model
for lightning surge analysis", IEEE Trans. on Power
Delivery, vol. 6, no. 3, pp. 1327-1335, July 1991.
T. Yamada et aI., "Experimental evaluation of a DHV
tower model for lightning surge analysis", IEEE Trans.
on Power Delivery, vol. 10, no. 1, pp. 393-402,
January 1995.
M.Mihailescu-Suliciu and 1. Suliciu, "A rate type
constitutive equation for the description of the corona
effect", IEEE Trans. on Power Apparatus and Systems,
vol. 100, no. 8, pp. 3681-3685, August 1981.
X.-R. Li, O.P. Malik and Z.-D. Zhao, "A practical
mathematical model of corona for calculation of
transients on transmission lines", IEEE Trans. on
Power Delivery, vol. 4, no. 2, pp. 1145-1152, April
1989.
M.A. AI-Tai et aI., "The simulation of surge corona
on transmission lines", IEEE Trans. on Power
Delivery, vol. 4, no. 2, pp. 1360-1368, April 1989.
X.-R. Li, O.P. Malik and Z.-D. Zhao, "Computation
of transmission lines transients including corona
effects", IEEE Trans. on Power Delivery, vol. 4, no.
3, pp. 1816-1821, July 1989.
C. de Jesus and M.T. Correia de Barros, "Modelling
of corona dynamics for surge propagation studies",
IEEE Trans. on Power Delivery, vol. 9, no. 3, pp.
1564-1569, July 1994.
K.C. Lee, "Non-linear corona models in an
electromagnetic transients program (EMTP) ", IEEE
Trans. on Power Apparatus and Systems, vol. 102, no.
9, pp. 2936-2942, September 1983.
W.-G. Huang and A. Semlyen, "Computation of
electro- magnetic transients on three-phase transmission
lines with corona and frequency dependent
parameters", IEEE Trans. on Power Delivery, vol. 2,
no. 3, pp. 887-898, July 1987.
P. Sanna Maruvada, D.H. Nguyen and H.
Hamadani-Zadeh, "Studies on modeling corona
attenuation of dynamic overvoltages", IEEE Trans. on
Power Delivery, vol. 4, no. 2, pp. 1441-1449, April
1989.
S. Carneiro Jr. and J.R. Marti, "Evaluation of corona
and line models in electromagnetic transient
simulations", IEEE Trans. on Power Delivery, vol. 6,
no. 1, pp. 334-342, January 1991.
S. Carneiro Jr., H.W. Dommel, J.R. Marti and H.M.
Barros, "An efficient procedure for the implementation
of corona models in electromagnetic transients
programs", IEEE Trans. on Power Delivery, vol. 9,
no. 2, pp. 849-855, April 1994.
1-15

[85]

[86]

[87]

[88]

[89]

[90]

[91]

[92]

[93]

[94]

[95]

[96]

[97]

[98]

J.R. Marti, F. Castellanos and N. Santiago, "Wide


-band corona circuit model for transient simulations",
IEEE Trans. on Power Systems, vol. 4, no. 2, pp.
1003-1013, May 1995.
H.M. Barros, S. Carneiro Jr. and R.M. Azevedo, "An
efficient recursive scheme for the simulation of
overvoltages on multiphase systems under corona",
IEEE Trans. on Power Delivery, vol. 10, no. 3, pp.
1443-1452, July 1995.
A. Ametani, "A general formulation of impedance and
admittance of cables", IEEE Trans. on Power
Apparatus and Systems, vol. 99, no. 3, pp. 902-910,
May/June 1980.
L.A. Wedepohl and D.J. Wilcox, "Transient analysis
of underground power-transmission systems", Proc.
lEE, vol. 120, no. 2, pp. 253-260, February 1973.
G.W. Brown and R.G. Rocamora, "Surge propagation
in three-phase pipe type cables. Part I - Unsaturated
pipe", IEEE Trans. on Power Apparatus and Systems,
vol. 95, no. 1, pp. 88-95, January/February 1976.
L. Marti, "Simulation of transients in underground
cables with frequency-dependent modal transformation
matrices", IEEE Trans. on Power Delivery, vol. 3, no.
3, pp. 1099-1110, July 1988.
A. Ametani, "Wave propagation characteristics of
cables", IEEE Trans. on Power Apparatus and
Systems, vol. 99, no. 2, pp. 499-505, April 1980.
N. Nagaoka and A. Ametani, "Transient calculations
on crossbonded cables", IEEE Trans. on Power
Apparatus and Systems, vol. 102, no. 4, pp. 779-787,
April 1983.
B. Gustavsen and J. Sletbak, "Transient sheath
overvoltages in armoured power cables", IEEE Trans.
on Power Delivery, vol. 11, no. 3, pp. 1594-1600,
July 1996.
R.J. Meredith, "EMTP modeling of electromagnetic
transients in multi-mode coaxial cables by fmite
sections", IEEE Trans. on Power Delivery, vol. 12,
no. 1, pp. 489-496, January 1997.
V. Brandwajn, H.W. Dommel and 1.1. Dommel,
"Matrix representation of three-phase n-winding
transformers for steady-state and transient studies",
IEEE Trans. on Power Apparatus and Systems, vol.
101, no. 6, pp. 1369-1378, June 1982.
W.L.A. Neves and H.W. Dommel, "On modeling iron
core nonlinearities", IEEE Trans. on Power Systems,
vol. 8, no. 2, pp. 417-425, May 1993.
W.L.A. Neves and H.W. Dommel, "Saturation curves
of delta-connected transformers from measurements",
IEEE Trans. on Power Delivery, vol. 10, no. 3, pp.
1432-1437, July 1995.
M. Vakilian and R.C. Degeneff, "A method for

[99]

[100]

[101]

[102]

[103]

[104]

[105]

[106]

[107]

[108]

[109]

[110]

modeling nonlinear core characteristics of transformer


during transients", IEEE Trans. on Power Delivery,
vol. 9, no. 4, pp. 1916-1925, October 1994.
S.N. Talukdar and J.R. Bailey, "Hysteresis models for
system studies", IEEE Trans. on Power Apparatus and
Systems, vol. 95, no. 4, pp. 1429-1434, July/August
1976.
E.P. Dick and W.Watson, "Transformer models for
transient studies based on field measurement", IEEE
Trans. on Power Apparatus and Systems, vol. 100, no.
1, pp. 401-419, January 1981.
J.G. Frame, N. Mohan and T.H. Liu, "Hysteresis
modeling in an electro-magnetic transients program",
IEEE Trans. on Power Apparatus and Systems, vol.
101, no. 9, pp. 3403-3412, September 1982.
F. de Leon and A. Semlyen, "Simple representation of
dynamic hysteresis losses in power transformers",
IEEE Trans. on Power Delivery, vol. 10, no. 1, pp.
315-321, January 1995.
J. Avila-Rosales and F.L. Alvarado, "Nonlinear
frequency dependent transformer model for
electromagnetic transient studies in power systems",
IEEE Trans. on Power Apparatus and Systems, vol.
101, no. 11, pp. 4281-4288, November 1982.
J. Avila-Rosales and A. Semlyen, "Iron core modeling
for electrical transients", IEEE Trans. on Power
Apparatus and Systems, vol. 104, no. 11, pp. 31893194, November 1985.
E.J. Tarasiewicz, A.S. Morched, A. Narang and E.P.
Dick, "Frequency dependent eddy current models for
nonlinear iron cores", IEEE Trans. on Power Systems,
vol. 8, no. 2, pp. 588-597, May 1993.
F. de Leon and A. Semlyen, "Detailed modeling of
eddy current effects for transformer transients", IEEE
Trans. on Power Delivery, vol. 9, no. 2, pp. 11431150, April 1994.
C.M. Arturi, "Transient simulation and analysis of a
three-phase five-limb step-up transformer following an
out-of-phase synchronization", IEEE Trans. on Power
Delivery, vol. 6, no. 1, pp. 196-207, January 1991.
A. Narang and R. H. Brierley, "Topology based
magnetic model for steady-state and transient studies
for three-phase core type transformers", IEEE Trans.
on Power Systems, vol. 9, no. 3, pp. 1337-1349,
August 1994.
X. Chen and S.S. Venkata, "A three-phase threewinding core-type transformer model for low-frequency
transient studies", IEEE Trans. on Power Delivery,
vol. 12, no. 3, 775-782, April 1997.
B.A. Mork, "Five-legged wound-core transformer
model: Derivation, parameters, implementation, and
evaluation", Paper PE-414-PWRD-0-12-1997,
1-16

[111]

[112]

[113]

[114]

[115]

[116]

[117]

[118]

[119]

[120]

[121]

[122]

presented at the 1998 IEEE PES Winter Meeting,


February 1-5, 1998, Tampa.
D.L. Stuehm, B.A. Mork and D.D. Mairs, "Fivelegged core transformer equivalent circuit", IEEE
Trans. on Power Delivery, vol. 4, no. 3, pp.
1786-1793, July 1989.
X. Chen, "A three-phase multi-legged transformer
model in ATP using the directly-formed inverse
inductance matrix", IEEE Trans. on Power Delivery,
vol. 11, no. 3, pp. 1554-1562, July 1996.
R.C. Degeneff "A general method for determining
resonances in transformer windings", IEEE Trans. on
Power Apparatus and Systems, vol. 96, no. 2,
MarchiApril 1977.
R.C. Degeneff, "A method for constructing terminal
models for single-phase n-winding transformers",
Paper No. A 78 539-9, 1978 IEEE PES Summer
Meeting, July 16-21, Los Angeles.
A. Morched, L. Marti and J. Ottevangers, "A high
frequency transformer model for the EMTP", IEEE
Trans. on Power Delivery, vol. 8, no. 3, pp. 16151626, July 1993.
P.T.M. Vaessen, "Transformer model for high
frequencies", IEEE Trans. on Power Delivery, vol. 3,
no. 4, pp. 1761-1768, October 1988.
V. Woivre, J.P. Artaud, A Ahmad and N. Burais,
"Transient overvoltage study and model for shell-type
power transformers", IEEE Trans. on Power Delivery,
vol. 8, no. 1, pp. 212-222, January 1993.
A. Oguz Soysal, "A method for wide frequency range
modeling of power transformers and rotating
machines", IEEE Trans. on Power Delivery, vol. 8,
no. 4, pp. 1802-1810, October 1993.
S. Chimklai and J.R. Marti, "Simplified three-phase
transformer model for electromagnetic transient
studies", IEEE Trans. on Power Delivery, vol. 10, no.
3, pp. 1316-1324, July 1995.
G.B. Gharehpetian, H. Mohseni and K. Moller,
"Hybrid modelling of inhomogeneus transformer
windings for very fast transient overvoltage studies",
IEEE Trans. on Power Delivery, vol. 13, no. 1, pp.
157-163, January 1998.
R.C. Degeneff, M.R. Gutierrez and P.J. McKenny,
"A method for constructing reduced order transformer
models for system studies from detailed lumped
parameter models", IEEE Trans. on Power Delivery,
vol. 7, no. 2, pp. 649-655, April 1992.
M. Gutierrez, R.C. Degeneff P.J. McKennny and
J.M. Schneider, "Linear, lumped parameter
transformer model reduction technique", IEEE Trans.
on Power Delivery, vol. 10, no. 2, pp. 853-861, April
1995.

[123] R.C. Degeneff, M.R. Gutierrez and M. Vakilian,


"Nonlinear, lumped parameter transformer model
reduction technique", IEEE Trans. on Power Delivery,
vol. 10, no. 2, pp. 862-868, April 1995.
[124] R.I. Galarza, J.H. Chow and R.C. Degeneff,
"Transformer model reduction using time and
frequency domain sensitivity techniques", IEEE Trans.
on Power Delivery, vol. 10, no. 2, pp. 1052-1059,
April 1995.
[125] D.N. Ewart, "Digital computer simulation model of a
steel-core transformer", IEEE Trans. on Power
Delivery, vol. 1, no. 3, pp. 174-183, July 1986.
[126] D. Dolinar, J. Pihler and B. Grear, "Dynamic model
of a three-phase power transformer", IEEE Trans. on
Power Delivery, vol. 8, no. 4, pp. 1811-1819, October
1993.
[127] F. de Leon and A. Semlyen, "Complete transformer
model for electromagnetic transients", IEEE Trans. on
Power Delivery, vol. 9, no. 1, pp. 231-239, January
1994.
[128] B.C. Papadias et aI., "Three phase transformer
modelling for fast electromagnetic transient studies",
IEEE Trans. on Power Delivery, vol. 9, no. 2, pp.
1151-1159, April 1994.
[129] P. Bastard, P. Bertrand and M. Meunier, "A
transformer model for winding fault studies", IEEE
Trans. on Power Delivery, vol. 9, no. 2, pp. 690-699,
April 1994.
[130] D.P. Carroll et aI., "A dynamic surge arrester model
for use in power system transient studies", IEEE
Trans. on Power Apparatus and Systems, vol. 91, no.
3, pp. 1057-1066, May/June 1972.
[131] C. Dang, T.M. Parnell and P.J. Price, "The response
of metal oxide surge arresters to steep fronted current
impulses", IEEE Trans. on Power Delivery, vol. 1, no.
1, pp. 157-163, January 1986.
[132] W. Schmidt et aI., "Behaviour of MO-surge-arrester
blocks to fast transients", IEEE Trans. on Power
Delivery, vol. 4, no. 1, pp. 292-300, January 1989.
[133] IEEE Working Group on Surge Arrester Modeling,
"Modeling of metal oxide surge arresters", IEEE
Trans. on Power Delivery, vol. 7, no. 1, pp. 302-309,
January 1992.
[134] I. Kim et al., "Study of ZnO arrester model for steep
front wave", IEEE Trans. on Power Delivery, vol. 11,
no.2,pp.834-841,ApriI1996.
[135] IEEE Working Group of Surge Protective Devices
Committee, "Modeling of current-limiting surge
arresters", IEEE Trans. on Power Apparatus and
Systems, vol. 100, no. 8, pp. 4033-4040, August 1981.
[136] D. L. Goldsworthy, "A linearized model for MOVprotected series capacitors", IEEE Trans. on Power
1-17

Systems, vol. 2, no. 4, pp. 953-958, November 1987.


[137] J.R. Lucas and P.G. McLaren, "A computationally
efficient MOV model for series compensation studies",
IEEE Trans. on Power Delivery, vol. 6, no. 4, pp.
1491-1497, October 1991.
[138] A.S. Morched and V. Brandwajn, "Transmission
network equivalents for electromagnetic transients
studies", IEEE Trans. on Power Apparatus and
Systems, vol. 102, no. 9, pp. 2984- 2994, September
1983.
[139] M. Kizilcay, "Low-order network equivalents for
electromagnetic transients studies", European
Transactions on Electrical Power Engineering, vol. 3,
no. 2, pp. 123-129, March/April 1993.
[140] A. Abur and H. Singh, "Time domain of external
systems for electromagnetic transients programs",
IEEE Trans. on Power Systems, vol. 8, no. 2, pp.
671-679, May 1993.
[141] A.S. Morched, J.H. Ottevangers and L. Marti,
"Multi-port frequency dependent network equivalents
for the EMTP", IEEE Trans. on Power Delivery, vol.
8, no. 3, pp. 1402-1412, July 1993.
[142] H. Singh and A. Abur, "Multiport equivalencing of
external systems for simulation of switching
transients", IEEE Trans. on Power Delivery, vol. 10,
no. 1, pp. 374-382, January 1995.
[143] V. Brandwajn and H.W. Dommel, "A new method for
interfacing generator models with an electromagnetic
transients program", Proc. of IEEE PICA, pp.
260-265, 1977.
[144] G. Gross and M.C. Hall, "Synchronous machine and
torsional dynamics simulation in the computation of
electromagnetic transients", IEEE Trans. on Power
Apparatus and Systems, vol. 97, no. 4, pp. 1074-1086,
July/August 1978.
[145] V. Brandwajn, "Representation of magnetic saturation
in the synchronous machine model in an
electromagnetic transients program", IEEE Trans. on
Power Apparatus and Systems, vol. 99, no. 5, pp.
1996-2002, September/October 1980.
[146] H.K. Lauw and W. Scott Meyer, "Universal machine
modeling for the representation of rotating machinery
in an electromagnetic transients program", IEEE Trans.
on Power Apparatus and Systems, vol. 101, no. 6, pp.
1342-1352, June 1982.
[147] H.K. Lauw, "Interfacing for universal multi-machine
system modeling in an electromagnetic transients
program", IEEE Trans. on Power Apparatus and
Systems, vol. 104, no. 9, pp. 2367-2373, September
1985.
[148] J.R. Marti and K.W. Louie, "A phase-domain
synchronous generator model including saturation

[149]

[150]

[151]

[152]

[153]

[154]

[155]

[156]

[157]

[158]
[159]
[160]

[161]

effects", IEEE Trans. on Power Systems, vol. 12, no.


1, pp. 222-229, February 1997.
A.M. Gole, R.W. Menzies, H.M. Turanli and D.A.
Woodford, "Improved interfacing of electrical machine
models to electromagnetic transients programs", IEEE
Trans. on Power Apparatus and Systems, vol. 103, no.
9,pp. 2446-2451, September 1984.
P.G. McLaren and M.H. Abdel-Rahman, "Modeling
of large AC motor coils for steep-fronted surge
studies", IEEE Trans. on Industry Applications, vol.
24, no. 3, pp. 422-426, May/June 1988.
J.L. Guardado and K.J. Cornick, "A computer model
for calculating steep-fronted surge distribution in
machine windings", IEEE Trans. on Energy
Conversion, vol. 4, no. 1,95-101, March 1989.
A. Narang, B.K. Gupta, E.P. Dick and D.K. Sharma,
"Measurement and analysis of surge distribution in
motor stator windings", IEEE Trans. on Energy
Conversion, vol. 4, no. 1, 126-134, March 1989.
N.J. Bacalao, P. de Arizon and R.O. Sanchez, "A
model for the synchronous machine using frequency
response measurements", IEEE Trans. on Power
Systems, vol. 10, no. 1, pp. 457-464, February 1995.
A. Domijan and Y. Yin, "Single-phase induction
machine simulation using the Electromagnetic
Transients Program: Theory and test cases", IEEE
Trans. on Energy Conversion, vol. 9, no. 3, pp.
535-542, September 1994.
H. Knudsen, "Extended Park's transformation for
2x3-phase synchronous machine and converter phasor
model with representation of harmonics", IEEE Trans.
on Energy Conversion, vol. 10, no. 1, pp. 126-132,
March 1995.
R. Hung and H.W. Dommel, "Synchronous machine
models for simulation of induction motor transients",
IEEE Trans. on Power Systems, vol. 11, no. 2, pp.
833-838, May 1996.
ClORE Working Group 13.01, "Practical application
of arc physics in circuit breakers. Survey of calculation
methods and application guide", Electra, no. 118, pp.
64-79,1988.
CIGRE Working Group 13.01, "Applications of black
box modelling to circuit breakers", Electra, no. 149,
pp. 40-71, August 1993.
EPRI Report EL-4651, "Electromagnetic Transients
Program (EMTP) Workbook II", 1989.
J.A. Martinez-Velasco, "Circuit breaker representation
for TRV calculations", EEUG Meeting 1995,
Hannover, November 13-15, 1995.
V. Phaniraj and A.G. Phadke, "Modeling of circuit
breakers in the electromagnetic transients program",
IEEE Trans. on Power Systems, vol. 3, no. 2, pp.
1-18

799-805, May 1988.


[162] L. van der Sluis, W.R. Rutgers and C.G.A. Koreman,
"A physical arc model for the simulation of current
zero behaviour of high-voltage circuit breakers", IEEE
Trans. on Power Delivery, vol. 7, no. 2, pp.
1016-1022, April 1992.
[163] Z. Ma et aI., "An investigation of transient overvoltage
generation when switching high voltage shunt reactors
by SF6 circuit breaker", IEEE Trans. on Power
Delivery, vol. 13, no. 2, pp. 472-479, April 1998.
[164] J.A. Martinez-Velasco, "Modelling of circuit breaker
using the type-94 component", EEUG Meeting 1995,
Hannover, November 13-15, 1995.
[165] J. Mahseredjian, M. Landry and B. Khodabakhchian,
"The new EMTP breaker arc model", Proceedings of
IPST'97, pp. 245-249, June 22-26, 1997, Seattle.
[166] J. Kosmac and P. Zunko, "A statistical vacuum circuit
breaker model for simulation of transients
overvoltages", IEEE Trans. on Power Delivery, vol.
10, no. 1, pp. 294-300, January 1995.
[167] M.T. Glinkowski, M.R. Gutierrez and D. Braun,
"Voltage escalation and reignition behavior of vacuum
circuit breakers during load shedding", IEEE Trans. on
Power Delivery, vol. 12, no. 1, pp. 219-226, January
1997.
[168] D.A. Woodford and L.M. Wedepohl, "Impact of
circuit breaker pre-strike on transmission line
energization transients", Proceedings of IPST'97, pp.
250-253, June 22-26, 1997, Seattle.
[169] J.A. Martinez-Velasco, R. Abdo and G. Capolino,
"Advanced representation of power semiconductors
using the EMTP", Proceedings of IPST'95, pp. 505510, September 3-7, 1995, Lisbon.
[170] C. Wong, "EMTP modeling of IGBT dynamic
performance for power dissipation estimation", IEEE
Trans. on Industry Applications, vol. 33, no. 1, pp.
64-71, January/February 1997. .
[171] J. Lucas et al., "Improved simulation models for
current and voltage transformers in relay studies",
IEEE Trans. on Power Delivery, vol. 7, no. 1, pp.
152-159, January 1992.
[172] M. Kezunovic et al., "Digital models of coupling
capacitor voltage transformers for protective relay
transient studies", IEEE Trans. on Power Delivery,
vol. 7, no. 4, pp. 1927-1935, October 1992.
[173] M. Kezunovic et al., "Experimental evaluations of
EMTP-based current transformer models for protective
relay transient study", IEEE Trans. on Power Delivery,
vol. 9, no. 1, pp. 405-413, January 1994.
[174] M. Kezunovic et aI., "A new method for the CCVT
performance analysis using field measurements, signal
processing and EMTP modeling", IEEE Trans. on

[175]

[176]

[177]

[178]

[179]

[180]

[181]

[182]

[183]

Power Delivery, vol. 9, no. 4, pp. 1907-1915, October


1994.
M.R. Iravani et aI., "Digital time-domain investigation
of transient behaviour of coupling capacitor voltage
transformer", IEEE Trans. on Power Delivery, vol. 13,
no. 2,pp. 622-629,1\pril 1998.
1\. Domijan and M.V. Emami, "State space relay
modeling and simulation using the Electromagnetic
Transients Program and its Transient Analysis of
Control Systems capability", IEEE Trans. on Energy
Conversion, vol. 5, no. 4, pp. 697-702, December
1990.
R.E. Wilson and J.M. Nordstrom, "EMTP transient
modeling of a distance relay and a comparison with
EMTP laboratory testing", IEEE Trans. on Power
Delivery, vol. 8, no. 3, pp. 984-992, July 1993.
1\.K.S. Chaudhary, K.S. Tam and A.G. Phadke,
"Protection system representation in
the
electromagnetic transients program", IEEE Trans. on
Power Delivery, vol. 9, no. 2, pp. 700-711, April
1994.
M.T. Glinkowski and J. Esztergalyos, "Transient
modeling of electromechanical relays. Part I :
A.rmature type overcurrent relays", IEEE Trans. on
Power Delivery, vol. 11, no. 2, pp. 763-770, April
1996.
M.T. Glinkowski and J. Esztergalyos, "Transient
modeling of electromechanical relays. Part II : Plunger
Type 50 relays", IEEE Trans. on Power Delivery, vol.
11, no. 2, pp. 771-782, April 1996.
J.1\. Martinez-Velasco and L. Kojovic, "1\TP modeling
of electromechanical relays", Proceedings ofIPST'97,
pp. 446-451, June 22-26, 1997, Seattle.
1\. Petit, G. St-Jean and G. Fecteau, "Empirical model
of a current-limiting fuse using EMTP", IEEE Trans.
on Power Delivery, vol. 4, no. 1, pp. 335-341,
January 1989.
L. Kojovic and S. Hassler, "Application of current

1-19

[184]

[185]

[186]

[187]

[188]

[189]

[190]

limiting fuses in distribution systems for improved


power quality and protection", IEEE Trans. on Power
Delivery, vol. 12, no. 2, 791-800, 1\pril1997.
CIGRE Working Group 02 (SC 33), "Guidelines for
Representation of Network Elements when Calculating
Transients", 1990.
IEEE Task Force on Slow Transients (M.R. Iravani,
Chairman), "Modeling and .Analysis Guidelines for
slow transients. Part I : Torsional Oscillations;
Transient Torques; Turbine blade vibrations; Fast bus
transfer", IEEE Trans. on Power Delivery, vol. 10,
no. 4, pp. 1950-1955, October 1995.
IEEE Task Force on Slow Transients (M.R. Iravani,
Chairman), "Modeling and Analysis Guidelines for
slow transients. Part II : Controller Interactions;
Harmonic Interactions", IEEE Trans. on Power
Delivery, vol. 11, no. 3, pp. 1672-1677, July 1995.
IEEE Task Force on Slow Transients (M.R. Iravani,
Chairman), "Modeling And Anlysis Guidelines for
slow transients - Part III : The study of ferroresonance" , 1998 IEEE Summer Power Meeting, July 1216, San Diego.
IEEE TF on Fast Front Transients (A.Imece,
Chairman), "Modeling guidelines for fast transients",
IEEE Trans. on Power Delivery, vol. 11, no. 1,
January 1996.
IEEE TF on Very Fast Transients (D. Povh,
Chairman), "Modeling and analysis guidelines for very
fast transients", IEEE Trans. on Power Delivery, vol.
11, no. 4, October 1996.
IEEE Task Force on Power Electronics (L. Tang,
Chairman), "Guidelines for modeling power electronics
in electric power engineering applications", IEEE
Trans. on Power Delivery, vol. 12, no. 1, pp.
505-514, January 1997.

Modeling Guidelines for Power Electronics in Electric Power


Engineering Applications
Report Prepared by the Power Electronics Task Force
of the IEEE Modeling and Analysis of System Transients Working Group
Contributing Members: K. K. Sen (Co-Chair), L. Tang (Co-Chair), H. W. Do~mel, K. G. ~ehrle, A. M.
Gole, E.W. Gunther, I. Hassan, R. Iravani, A. J. F. Keri R. Lasseter, J. R. Marti, J. A. Martinez, M. F.
McGranaghan, O. B. Nayak, C. Nwankpa, P. F. Ribeiro

ABSTRACT -This paper presents a summary of


guidelines for modeling power electronics in various power
engineering applications. This document is designed for use by
power engineers who need to simulate power electronic devices
and subsystems with digital computer programs. The guideline
emphasizes the basic issues that are critical for successful modeling of power electronics devices and the interface between
power electronics and the utility or industrial system. The modeling considerations addressed in this guideline are generic for
all power electronics modeling independent of the computational tool. However, for the purposes of illustration, the simulation examples presented are based on the EMTP or EMTP
type of programs. The procedures used to implement power
electronics models in these examples are valuable for using
other digital simulation tools.

of the interaction between the power electronic subsystem


and the connected power system. Thus, a model for a power
electronic switching device can be greatly simplified.
Detailed descriptions about the device representation are
presented in the later section of this paper. In the last section
of the paper, the references related to various power electronics simulations are listed.
2. GENERAL CONSIDERATIONS OF POWER
ELECTRONICS MODELING
2.1. Types ofProblems

Power electronics modeling can be divided into


two basic categories, depending on study objectives. The
first category covers all steady state evaluations. The focus
is from the power system response to the harmonics injected
from a power electronics subsystem. Examples of this type
include a study of the steadystate harmonic propagation in a
transmission and distribution system, harmonic frequency
resonance, system voltage and current distortion, filtering
design calculation and performance evaluation, telephone
interference analysis and system losses associated with harmonics. In this type of study, the harmonic current injection
can often be assumed independent of the voltage variations
at a point of common coupling (PCC) which is an electrically dividing point between the utility system and the customer circuit. Therefore, the power electronics subsystem
can greatly be reduced to a shunt circuit equivalent.

1. INTRODUCTION
As a consequence of the advances in power electronics technologies over the last two decades, power electronics applications have quickly spread to all voltage levels,
from EHV transmission to low voltage circuits in end user
facilities. Commonly observed power electronics applications include HVDC terminals, various static var compensation (SVC) systems, high power AC to DC converter for DC
arc furnaces, static phase shifter, isolation switch, load transfer switch, converter/inverter based drive technologies,
active line conditioning, energy storage and instantaneous
backup power systems, renewable energy integration, and
numerous others covered under subjects of Flexible AC
Transmission Systems (FACTS) and Custom Power Systems
(CPS). The need for power electronics modeling and simulation is driven by both existing and new applications.

The second type of power electronics modeling


covers a much more extensive and complex range of practical problems. In many applications, operation of a power
electronics subsystem depends closely upon the operation
state of the connected system. To evaluate the dynamic and
transient performance of a system with power electronics
interfaces, the monitoring and control loops of the system,
including detailed signal processing and power electronics
device firing need to be modeled. Examples of this type of
applications can be a SVC system, a Superconducting Magnetic Energy Storage (SMES), active power conditioning
system and various adjustable speed drives applications.
When modeling these applications, variations of system
parameters need to be used to derive the power electronic
controls so the output of the power electronics subsystem
changes accordingly as demanded. Since a power electron-

Objectives of the simulation include:


verification of an application design
prediction the performance of a system
identification of potential problems
evaluation of possible problem solutions.
The simulation is specially important for a concept validation
and design iteration during new product development.
Power electronics applications are relatively new to
many power system engineers. This guideline provides general procedures to help these engineers to make their own
simulation cases as needed. The theories of power electronics are not discussed. Attention is focused on the simulation
2-1

ics subsystem directly affects overall system operation, a


comprehensive treatment of the supply system and the power
electronics subsystem should be performed.
2.2. Frequency Domain and TIme Domain Simulation
The solution methods are considered from two basic approaches:
1.
2.

frequency domain solution


time domain solution.

Digital computers can only simulate circuit phenomena at discrete frequencies or at discrete intervals of time
(step size M or ~t). This leads to discretization errors. Compared with the time domain calculation, a frequency domain
simulation is more robust because a circuit solution is found
at each individual frequency and these errors are not accumulated. The programs using this solution method often treat
the nonlinearity of a system as known current sources. For a
harmonic evaluation, the frequency domain solution usually
requires less computation time compared with a time domain
solution. However, most available frequency domain solution programs have difficulties in handling the system
dynamics, control interfaces and fast transients. The time
domain solution is based on the integration over a discrete
time interval. The numerical methods applied in different
programs can use either iterative techniques or direct solu tion methods. The solution stability and accuracy achieved
are closely related to the time step size selection. Because
discretization errors can accumulate , the solution may
diverge from the true solution if an improper time step is
selected. The time domain simulation has great advantages
over a frequency domain simulation in handling the system
dynamics, power electronic models , non-linearities and transients .

type programs may be less efficient for detailed power electronics modeling. However, these programs are very attractive for an application oriented power electronics simulation
because these programs offer tremendous capability and flexibility in characterizing various types of power system components , inc lu d in g power electronics switches with
reasonably simplified characteristics. As graphic interfacing
features are gradually incorporated in these programs, a level
of difficulty in using these tools will decrease.
3. MODELING GUIDELINES
3.1. Representation ofPower Electronics Switching Devices
For a power level application, the commonly used
switching devices are power diode , Silicon Controlled Rectifier (SCR), Gate Turn-Off thyristor (GTO) and Insulated
Gate Bipolar Transistor (IGBT). The diode is a two-terminal, uncontrollable device and the rest are three terminal controllable devices.
Representing the reverse recovery characteristic,
leakage current, and forward voltage drop of a diode is often
not necessary for an application study. For an application
simulation, some details of a device characteristic can be
reduced. In many cases, a simplified device model is acceptable. For example, instead of trying to represent a power
electronic diode device using its switching characteristic as
shown on the left in Fig. 1, a simplified or an idealized characteristic, shown by solid and dotted lines respectively on the
right , can be used. In commonly used simulation programs,
the simplified diode model may be available as a built-in
device or it can be realized with a voltage controlled switch.

Real Device
Characteristic

Simulated Device
Characteristic

2.3. Toolsfor Power Electronics Application Simulation

-==---t"- - - v

According to their main functions, commonly used


tools for power electronics related simulations can be classified into three groups:
1. Power electronics simulation tools
2. General transients simulation tools or EMTP type of
programs
3. General harmonics simulation tools or frequency
domain simulation tools .

Cathode

--t<:J-

Anode

Fig. I. Actual and Simplified Switching Characteristic of Power Diode Device

If the idealized power diode model is not available,


its characteristic can be realized using a voltage controlled
unidirectional current flowing switch with a specified conducting voltage threshold, Vs, as shown in Fig. 2.

The tools of the first group may offer the best productivity if a detailed application topology and complicated
operation controls need to be simulated and if the main interest of the study is the power electronics subsystem. These
tools often have difficulties when an extensive utility network needs to be included in the simulation or when the main
interest of the study is overall system dynamics and transients. In such cases, the EMTP type programs are usually
more suitable. The currently available versions of the EMTP
2-2

..

For numerical simulations, if the gating circuit power requirement is excludedfrom the study, there is very little difference
between modelinga GTO, IGBT or any other three-terminal,
controllable, unidirectional current flowing device. The device can all be represented by an simplified switch with gate
tum-on and tum-off controls. The different switchingcharacteristics can be realized by applying different firing controls.
In the simulation, additional errorscan accrue becausethe gating pulses can only be applied at integral time-step multiples,
which may not be the case in reality.The impactof this can be
minimized if the program allows a variable time-step or uses
interpolation [60].

Conducting when v>VS


Fig. 2. An IdealizedPower DiodeRealization

Since an existing diode model does not allow to


specify on-state and off-state resistances, the device can be
realized using two above described switches connected in
parallel (Fig. 3) with the opposite polarities and different
conducting voltage thresholds when loss calculation is of
interest. To include losses, the resistors Rf and Rb can be
inserted in series with the forward and backward current
flowing switches respectively, and a leakage resistor Rl can
be connected crossingthe terminalsof the switch branches.

In an actualpower electronicsapplication, in order to provide


a continuous current flowing path for an inductive load, a reversal diode (free wheeling diode) is used in parallel with a
controllable switching device to form the basic power electronics switching unit. However, several alternatives are
availablefor implementing this basic switchingunit in digital
simulations.

Considering only the terminal equivalent at the connection


point of the application, the simplest model that can be used
to presentone leg of the bridgerectifier or invertercan be constructed with one simplified bi-directional current flowing
switch with gate controls as shown in Fig. 5 (1). This model

..

Rf

.....+-. .R-==:::::::=:::::(-J
Rb

~ ~t--e

Catho~de

Gate

Vsb

X I -----.I

Rl
Fig. 3. Power Diode Characteristic Realization

(1)

The switching characteristics of an actual, a simplified and an idealized SCR are shown in Fig. 4. To represent
the simplified SCR device, the tum-on control is added on
the simplifieddiode model. If the controlis applied continuously, this switch simulates the diode which allows unidirectional current flow when the switch is forward biased.
Delaying the gate pulse allows control over the tum-on
instant of the forward biased switch.

Real Device
Characteristic

Lu

Simulated Device
Characteristic

(2)

(3 )

Fig. 5. Alternatives for Three-terminal Controllable SwitchingDevice Representation

uses the least number of devices for a given power


electronics topology. The problem with this bidirectionalcurrent flowing switch representation is that it fails to correctly
representan operationstate during the idling period. This can
be better explained with an example of a simplified inverter
schemeused in a UPS as shown in Fig.6.

Igl IgO

--::::=~-+-..-.:====..

Vbo

DC
Battery

---=-+-=-----

Cathode~ Anode

AC
Supply

Fig. 6. Simplified InverterScheme in a UPS System

When all the controlled switching devices are


blocked, the DC battery charges through the rectifier bridge

Fig. 4. An Actual and SimplifiedSwitching Characteristic of SCR


Device

2-3

consisting of six reversal diodes. However, if the ideal bidirectional switches are used, while the UPS is idling, the battery will not be charged by the AC supply.

~~

When the idling mode needs to be more realistically


represented, the simple bidirectional device model can be
improved with a parallel reversal diode as shown in Fig. 5
(2) . When the terminal effects as well as the individual
device current carrying conditions are of interest, a further
improvement on the model can be made by adding another
diode as shown in Fig. 5 (3).
It should be noted that for some programs, multiple
switch connections on the same circuit node can lead to a singular system admittance matrix. When using a program with
such restriction, a small series resistor or inductor can be
used to create intermediate nodes and avoid the problem.
To illustrate a power electronic device realization,
an EMTP example of a GTO operation is given below. In this
example , a GTO module is built with a controlled bi-directional current flowing switch (type-13 switch) in series with
a built-in diode device (type-ll switch). Considering the
GTO is often utilized in applications with a reactive power
carrying capability, a reversal diode (free wheeling diode)
has been included. The schematic of the module connection
is shown in Fig. 7. A list of the module file is given in
Appendix A. Note that although it has not been shown in
Fig. 7, some small resistors are used to introduce intermediate nodes between the EMTP switches and snubber elements
are used in this GTO module.

J---=3=- Voltage

Load

~O"'"'---+-...l..-_------'
To Firing Control
Fig. 8. An Example Circuit to Show GTO Simulation.

The GTO gating signal is illustrated in Fig. 9. When


the gating signal is greater than zero , the GTO is turned on
and when the gating signal is equal to zero, the GTO is
turned off. The GTO is initially open . The current flowing
through the GTO and voltage across the load resistor after
t=O are illustrated in Figs. 10 and 11 respectively. By controlling the GTO firing , the average output voltage at the load
terminal can be regulated.

GTO Gating Sqncl

1
,

--,--------,-----..-----1\

"

"

"

type-l l
switch

Fig. 7. An EMTP Realization ofGTO Device

Fig. 10. The Current Flowing through GTO

An example circuit given in Fig. 8 is used to illustrate how this module is used in a circuit simulation. In this
example, the GTO device is used to regulate the voltage at a
resistive load terminal. By controlling the GTO tuning-on
and off, the average voltage across the resistor can be
adjusted.

2-4

]~J I

Fig. 9. The GTO Firing Signal.

type-I 3
switch

GTO

"

I1

Snubber

R ond C

6OO1t---+---I---t-+-+--++-+

Controlloble SWitching Device

100111-----+-,-------1--'---+--'---1----+---1

AC Output
DC Supply

Fig. 11. TheVoltage across a Resistive Load

3.2. Representation ofPower Electronics (PE) Systems


If every individual power electronic switching
device is represented, a system model containingpower electronic applications can easily reach a complicationlevel that
is difficult for implementation. For an example, a HVDC terminal contains tens to hundreds series and parallel SCR
devices in one converter leg for high voltage and MVA ratings. Obviously, if one wants to represent each individual
SCR device in this HVDC system model, one will have to
build a very large model.
Fortunately, (except for some failure mode analyses), for the purposes of most applicationsimulations it is not
necessary to represent all individual devices. Usually, what
needs to be simulated is the terminal characteristics of a
power electronic subsystem and how it interfaces with the
connected system . Thus, the following procedures can be
used to reduce the modeling complexity:
Use one or a few equivalent devices to representseries
and parallel combination of a group of devices
Represent power electronic loads with similar characteristics by an equivalent load
Use the simplest device model which is appropriate for
the application
Represent a power electronic subsystemby equivalent
source injection whenever it is acceptable
Represent only the front end of the drive system when
the major concern is utility interfacing
Include the system dynamic and controls only when necessary
Use modular approach for large scale model development

Fig. 12. Voltage Source Converter Simulation


With these general guidelines, a voltage source converter model for a system dynamic evaluation can be built as
shown in Fig. 12. Irrespective of how many series and parallel GTO devices are used in an actual application, only two
GTO devices are used in each phase of the model to form a
converter leg. In this example, the just discussed GTO module is used as a building block to construct the converter
module.
The GIO firing control signals for the six-step operation is given in Fig. 13. The firing signal for the switching
cells No. 1 through No.6 are shown in this figure by the
traces with the magnitude 1.1 through 1.6 respectively. The
device firing starts when the time reaches one 60 Hz cycle
ending point. When the gating signal is greater than zero, the
corresponding GTO device is turned on. When the gating signal is equal to zero, the device is turned off. The resulting
line-to-neutral and line-to-line output voltages are illustrated
in Figs. 14 and 15, respectively.

GTO Firing SignOI vs. Time

~---;-----, - -

0.'"

o.>f---+--r----l-t-+-+-+-H-t-+-+--'-I
0.00

Fig. 13. The GTO Firing Signal fortheSix Step Converter Operation

2-5

L; n e- : o - G r o i.J ~ C1

600
' 00

....

100

-100

i
,
:

- '00

VOllcge

"

~- i-I

I ii

L-.

-600
JO

'0

Time mS

"

Fig. 18. The Resulting Line-to-Neutral Voltage

Fig. 14. Six Step OperationLine-to-Neutral Voltage

tine-t o- Line Voltage

. . I~-f~==q

~;
I

'

C10'&>"il'JS&-~I~ ej

"

Time (mS)

Fig. 19. The Resulting Line-to-Line Voltage

Fig. 15. Six Step Operation Line-to-Line Voltage

In this guideline, deta iled considerations related to


applying these system reduction are presented. Some important issues addressed are:

For this case, the GTO firing control signal is


derived by comparing the saw tooth carrier signal with a reference signal of a desired frequency of that phase . As shown
in Fig. 16, whenever, the instantaneous value of the reference
signal is greater than that of the carrier signal, the device is
turned on.
PWMFiring Signal Generation

Harmonic cancellation when multiple loads are represented by their lumped equivalent
Existing system distortion.
Appropriate source topology for PE subsystem representation
System unbalance
Effects of a DC link or the inverter side connection on
the front end interface with the power supply system
Current or voltage sharing among the parallel or series
switching devices
Switching loss prediction

3.3.Representation ofPowerSystems

tL

- " JO
. ----c------,;:----~---____;

Fig. 17. The PWMFiringSignal: Reference VoltageFrequency =60


Hz, Carrier Signal Frequency =600 Hz

Similar to the situation in a power electronics subsystem, a power supply system can easily extend to a large
electrical and geographic radius and become too complicated
to model. Therefore, the power system needs to be simplified . The proper level of system reduction depends on the
study objectives.

The simulated line-to-neutral and line-to-line output


voltages are shown in Figs. 17 and 18, respectively. By
changing the magnitude and frequency of the reference signal, the output voltage magnitude and frequency can be
changed. The carrier frequency determines the characteristic
harmonic components of the output voltage.

If the purpose is to characterize the harmonics generated by a particular type of power electronics application,
the power system model can be significantly reduced. When
a pre-existing voltage distortion level at a power electronics
interfacing bus is low, the rest of the power system can be
2-6

satisfactorily represented by one or a set of first orderequivalents connected to the bus at a higher system voltage level.
For an example, if the power electronics application interfaces with the system at the low voltage bus of a step-down
transformer, the equivalent of the system can be placed on
the high voltage bus of the transformer. When a pre-existing
voltage distortionlevel is greater than 2%, one needs an adequate harmonic source to properly represent the background
distortion.
If the objective is to evaluate effects of the power
electronics on a connected utility system, the model shall be
extended to cover all sensitive loads (i.e. rotating machines
and all other major power electronics) within a concerned
electrical radius. Special attention is needed if an unbalancedsystem conditionis involved.
Extensivepower systemmodel is requiredfor a harmonic propagation and resonant study. The main system
components and dominant topology need to be kept in the
power system model. Filter banks, nonlinear passive circuit
components, and all other harmonic injection sources should
be represented. Frequency dependent characteristics of the
systemcomponents might need to be considered.
3.4. Representation ofSystem Controls
The system control is one of the most important
aspectof a power electronics simulation. As illustrated in this
paper, a switching device is greatly simplified. The proper
switching performance of a device is realizedvia appropriate
gate controls. Modelingof power electronic controls consists
of three steps:
1. Monitoring and sampling
2. Signalprocessingand controlreference derivation
3. Device gating signal generation.
Most simulation tools provide some means to
implement system controls. In some later developed programs, the control block diagram and flow-chart structures
are supported for modeling different levels of system controls. Using these tools, a user can define the specified controls in a simulated system with great flexibility. Some key
issues ensuring a correct control modeling is briefly mentioned below. These issues are more thoroughly treatedin the
guideline with illustration examples.
For a time domainsimulation, the highestresolution for
a signal samplingis determined by a selectedtime step.
In general, this presentsno problemfor analog control.
However, for digitalcontrolsimulation, if the selected
time step is too large and if the simulated sampling resolution is significantly differentfrom the real systemsampiing resolution, significant errorscan be introduced and
even lead to instability.
For a time domainsimulation, the computation time
does not reflect the simulatedcontrollogic response
time. User should always rememberto introduce a rea2-7

sonable time delay to match with the limitations of the


control hardware and software.
Whenmodelinga control response, it is importantto
understand the programintroducedtime delay between
the primarysystem and the control interface. For an
example, the controlmodel may introduceone or more
time step delaybecauseof structureand solutionmethod
of the program. This may not cause problemsin some
simulations. However, if the modeled control logic
makesthis time delay caused error to accumulate over a
period of time, it can eventuallyresult in the solution
divergence. The problemcan be correctedin most cases
by reducing the size of the time step or avoidingthe possible accumulation mechanismin the controlmodel.
Differentmethods may be used to synchronize power
electronics gating signalswith required system references. In many cases, a real phase-locked-loop (PLL)
can be greatlysimplifiedto reduce the modeling system
complexity. However, when the system contains significant waveform distortions, either harmonicsor transient
disturbances, a practicalPLL with all signal filters
shouldbe carefully implemented in the control model in
order to accurately predict controlresponse. This is particularly important when the objectiveof the simulation
is to verifycontroldesignand to evaluatethe responseof
a powerelectronic application to primarysystem dynamics.
All power electronic deviceshave their limit in switching frequency. When a load commutation or a standard
PWMtype scheme is simulated, the highest switching
frequency in the simulationis controlledby the system
frequency or by a carrier frequency. Even considering a
variable carrierfrequency, the number of switchingper
fundamental frequency cycle is known and the highest
switching frequency can be made under a physical limit
of the simulateddevice. However, if the device firing is
determined by a simple comparison between the system
controlreference and the systemoutput,a device switching may takeplace in simulation whenevera comparison
difference is detected. Therefore, the switchingfrequencybecomes highly dependenton the time step size,
and the average switching frequency becomes unpredictable. Whenusing this type of firing logic, user should
alwaystake extra measures, such as introducing a hysteresis loop, to ensure that the modeled device is working under its physicalswitchingcapability.
The block diagram for a commonly used phase locked loop
[17,60] is shownin Fig. 20. The systemvoltageat the terminal
of the load is sampled and used to generate the synchronous
reference signal. From Fig. 21 through Fig. 26, the input, intermediate output quantities and output signal are plotted to
showthe each step of this signal processing.

Uref

Va

""

Vb

JOO

Vc

100

DO-PLLC>lACS - DU ~009(Type g)

100

10

'0

Fig. 20 The Block Diagramof a PLL

60

lime (mS)

Fig. 24 DerivedFrequency Reference


DO - PLLO>TACS - IH['AR(Type 9)

+:t fI::: -+
i

/ I /

....-....__....

10

1/

10

Iime (mS)

00

4()

Iime(mS)

i /

"'

Fig. 26 Comparison ofInput and Obtained Syn. Signals

DO-PLLO>lACS -DUMD13(lype g)

The response of this control circuitry to a system


disturbance is illustrated in Fig. 27. A balanced system fault
is placed on and removed from the system, resulting a three
cycle voltage sag.

v ,

-urseo ,

:
o

-i-.:---f-!I----+--------,,-j

0.0500

-0.1000

1/

Fig. 22 DQ Voltage Components

0.1000

0.OO

17

1/

Fig. 25 Output of VCO

Fig. 21 Input three-phase Voltage Signal

0.5 +-1--,---+--+--+L--+-

7f

Ii.

i --f-

.- ._... _...........

!/

10

40

60

Time mS

Fig. 23 Derived Phase Error

80

100

Three phase fault


Rf=0.01 ohms
Tin=0 .025s
Tcl=0.075s
Kpro= 100
Kint =8.3E-3
With above given control parameters, it takes the
PLL about three cycles to be relocked into the system voltage.

2-8

oscillations in which case it is not a concern to the simulation


engineer. Otherwise, some of the measures listed later in this
section may have to be implemented to obtain correct results.
The fmite nature of the simulation time step that the
EMTP type programs use also poses another problem for
power electronic circuit simulation which necessitates the
use of snubber circuits across fast acting power electronic
switches. Note that in some situations the snubber Rand C
values of the actual system mayor may not work in simulations using some programs. In this case, the Rand C values
of the snubbers needed for stable simulation is primarily
dependent on the time step and secondarily on system configuration (capacitors and inductors in the system) and the load
current level. Programs using special features such as variable time steps (very short time steps during switching) or
interpolated switching [59] (simulate the switching very
close to the required instant using linear interpolation
between time steps) do not require fictitious snubber circuits.
Therefore, one of the following measures or their combinations can be taken to prevent numerical inaccuracies in the
simulation:
Select a smaller time step
Use artificial snubber circuits
Introduce a small smoothing reactor for DC links
Introduce proper stray capacitances in the system model

Provide a parallel damping for lumped system.

Fig. 27 The PLL CircuitryResponseto a System Disturbance

If the circuit parameters are changed from the above


given values to the values listed below, for the same system
and fault, one can observe that the same PLL logic can be
relocked into the system voltage within a half cycle period of
the time as shown in Fig. 28.
Three phase fault
Rf=O.OI ohms
Tin=0.025s
Tcl=0.075s

With Modified:
Kpro = 1000
Kint = 8.3E-4

A model for a general, unidirectional conducting,


three terminal, controllable power electronic device with
snubber connections is shown in Fig. 29. An actual snubber
configuration can be different from one application to
another. However, if the purpose of a simulation is not to
design the snubber, a sample snubber configuration shown in
this figure can often provide satisfactory results.

ATRMNL
140.0

GTRMNL

Fig. 28 The PLL Circuitry Responseto a SystemDisturbance

SNUBBR

O----i

Note that this example of PLL logic based on the


three phase to DQ transformation is valid for three-phase balanced application. Also, its performance characteristic is
highly affected by the parameter settings.

SNUBBC

SNUBBC

\...---i

3.5. SnubberTreatment in EMTPtype PE Modeling


CTRMNL

The simulation programs using trapezoidal integration method are inherently prone to spurious oscillations
(also known as chatter) in capacitive and inductive circuits
when subjected to sudden changes such as step change in
voltage, current injection and switching. Some EMTP type
programs take special measures to detect and remove these

Fig. 29 A Sample Snubber Circuit

2-9

3.6.Simulation Errors and Control


AC Supply

Errors in a Power Electronics simulation can come


through the following sources:
1. switching device approximation and system reduction
2. added circuit elements for numerical oscillation control
3. control system simplification
4. time step related truncation
5. program structure and solution method introduced interfacing time delay
6. incorrect system initial conditions
For application simulations, some errors resulting
from the system simplification and measures of numerical
oscillation control are acceptable. The fourth and fifth items
in the list can be controlled by reducing the time step size. A
recommended time step size should not be greater than 1/5 to
1/20 of the period of the highest concerned frequency
cycle. For an example, for an IGBT inverter simulation with
5000Hz PWM switching, a selected time step could be 10
ms. However, if the objective of the simulation is to see the
detailed transient at the terminal of the induction motor
which is fed by the inverter through a section of the cable
with an 1.0 ms travel time, an adequate time step should be
0.2 ms or smaller.

Induct ion
Motor

DC Link

s~
Six Pulse
Diode Rectifier

PWM
Inverter

Fig. 30. Electrical Circuit Configuration of an Adjustable Speed


Drive

The built-in diode models are used to construct the


front end rectifier. The same switching devices with added
open/close controls are used to represent output invert er
IGBTs. The EMTP input data modules are use to build this
example case . Both the output reference frequency and the
PWM carrier frequency are made to be controllable. Modeling of a signal processing and firing pulse generation is illustrated in this example. The motor load of the drive is
represented by its R+jX equivalent branch. The simulated
AC input current, carrier and reference signal for the PWM
control , AC output voltage and current are presented in Fig.
31 through Fig. 33.

Errors caused by incorrect system initial conditions


can be reduced by just letting the simulation run for a period
of time to reach a corrected initial condition. This may take
more computing time , but time is saved in model construction , especially if the program allows to restart. There are
some methods developed which help to accelerate the system
into the correct initial condition quickly.
4. SUMMARY OF DOCUMENTED EXAMPLES

<00

-f\ - J f~

200

.3

-~ w

Summary of simulation examples on PWM Voltage


Source Inverter Adjustable Speed Drive, Voltage notching
caused by operation of Current Source Inverter, HVDC terminal and shunt TSC/TCR compensation, modeling of rotating machines and a comprehensive treatment on the voltage
source inverter based FACTS devices and its modeling techniques using EMTP are presented in this section. The examples can be either a real case study or an exercise for
illustration purposes.

Ii

J;
'\

\0

iO

lime (mS)

I-

vV

_400 1

-0

80

!
100

Fig. 31. Simulated AC Input Current of A PWM-VSI Adjustable


Speed Drive

PWM'vSI>TACS - DlJMC58 yoe 9

4.1. Simulation ofthe Pulse Width Modulation (PWM) Voltage Source Inverter (VSI) AdjustableSpeedDrive (ASD)
The first example is a PWM- VSI AC drive simulation using EMTP. The AC drive (Fig. 30) consisting of a
three-phase diode bridge rectifier, capacitive DC link and
three-phase PWM output inverter. The switching losses of
the drive are a secondary order consideration in the analysis
and the idealized switching characteristics are used.

2-10

Fig. 32. Simulated Carrier and Reference Signals for A PWM- VSI
Adjustable Speed Drive Firing Control

PWMVSI>INVRTA- INVRTB(Type 8)

8:xJ

II II II
i

600,
' 00

slOO

rio
Ig -lOOt
-<00

i'
I

-600

-800

Ii

-0

I
I
60

i
i

Time mS

I,

~I
I
i

144 kV

snon circun ,"wi.

74 MVA

Vvlv 10MVA

....

25 kV Bus

l-

rYjY' 7.87% /

f---80

2 km 266 MCM

100

7.5 MVA

VJ:A:)

t5

I
T
other

5.75% : T

Fig. 33. Simulated AC OutputLine-to-line Voltage of A PWM-VSI


Adjustable SpeedDrive

4.16 kV

10km

!!!

1/0

TTT

harmonic
filters

4.2.Simulation of Voltage Notching Causedby Operation of


Current Source Inverter (CSI) ASD

5,7,11

The second example is based on a case study. The


involved system is illustrated by the one line diagram in Fig.
34 . The 35 kV distribution system is supplied through a 10
MVA transformer from the 144 kV transmission system. The
customer causing the voltage notching problem has a 6000
hp induction motor supplied through a CSI adjustable speed
drive[53] . This drive is at a 4.16 kV bus supplied through a
7.5 MVA transformer. Harmonic filters (5th , 7th , l lth) are
included to control the lower order characteristic harmonics
of the six pulse drive . The actual adjustable speed drive and
motor load were represented to reproduce the notching oscillations observed in the measurements.

ASD
6000 hp

~:.,_Iw, ~ -----.rrrn

4.7%

4.16kV_

u:IV
rrrn

1500 kVA
4 .7%

_",_y,,480 Volt bus


~ TPF Correction

Motor Load
(650 hpj

~O

O.5uF
surge capacitors

Operation of the 6000 hp motor and drive resulted


in significant oscillations on the 25 kV supply system . These
oscillations caused clocks to run fast at the customer with the
6000 hp motor (clocks were fed separately from the 25 kV
system) and failure of surge capacitors on the 800 hp motor
at the customer located on the parallel feeder. The objective
of the simulation is to identify the power quality problem
associated with this 6000 HP CSI ASD operation. The simulation was carried out using EMTP.
The worst notching problems are associated with a
firing angle at about 70% load . The simulated waveform for
the 25 kV bus voltage is shown in Fig. 35. The oscillations at
each commutation point are in good agreement with the measurement results.

loads

capacitors
(160 kvar)

800 hp

Fig. 34. One line diagram for the first example system.

Tim ~

Il"S

_ _ ----l

Fig. 35. Simulated 25 kV systemvoltagewith drive operating.


Fig. 36 illustrates the voltage waveform at the 4.16
kV bus where the 800 hp motor surge capacitors cause magnification of the oscillations. The potential for problems at
this location is quite evident.

2-11

nous condenser (SC) and half-and-half mix of the two


(SVC+SC).

Voltoge 01 4160 Volt Surge Copocitor - Bose Cose

-6000
-8000

Fig. 38 shows the typical results obtained from the


simulation for a permanent DC block. The fixed compensator
case does not control the overvoltage; howe ver, all other
options do. The SVC option is the fastest to respond followed
by the SVC+SC option and lastly the SC option. This simulation setup can be used to conduct almost any type of performance study including a thyristor miss-fire in HVDC valve
group or in the SVC itself.

'~
I - -----:...-------cc----------I

ltl

Fig. 36. Simulated waveform at surge capacitor location (4.16 kV


bus of customer on parallel feeder)

1.6
1.5

4.3. Simulation ofHVDC Terminal and Shunt TSCITCR


Compensation

,-..

Q)
eo 1.3

The third example is an illustration case for modeling of an HYDC system with shunt TscrrCR compensation
at the inverter bus [54]. The simulation example is made
using PSCAD/EMTDC. The schematic system shown in Fig.
37 is a modified version of the GlGRE Benchmark Model for
HYDC Control Studies [55].

Rectifier AC
System

1.2

~u

1.1

0.9

(/)

....
Q)
_ _* 1- - - - - - ,- - - - - - - YG:- - - - - - - - - t:Q) 1.0
>
s::

The inverter short circuit ratio has been reduced


from its original value of 2.5 to 1.5 to make the study more
interesting. The DC link is a 1000MW, 500kV, 12 pulse
monopolar system. There are damped low and high pass filters at each converter terminal to reduce the distortion on the
AC bus. The control scheme for the HYDC system consists
of a rectifier current controller with the gamma controller.
1000MW
500kV
12 Pulse

1.4

;:3

0.8
0.7
0.0

0.1

0.2

0.3

0.4

0.5

0.6

Time (s)
Fig. 38 Inverter AC Voltage Followinga Permanent DC Block

Inverter AC
System

4.4. ModelingofRotatingMachines

Fig. 37. Study System


The SVC system is a -200/+300 MVAr, 12 pulse,
TCR and TSC (two stage) combination connected to the
inverter bus through a step up transformer, The SVC controls
are designed to coordinate the control of TCR and TSC in
such a way that the combined susceptance of the SVC is continuous over its entire operating range. The basic control
mode is voltage control and has as a voltage droop built into
the controls. Several studies to evaluate the recovery to full
power after a contingency were simulated [54]. The performances of several compensation options were compared.
These options included fixed capacitors (FC), SVC, synchro-

Two possible situations can be considered for modeling a rotating machine when simulating a power electronic
system
1. The machine is a component of a larger system where
one or several power electronic devices are operating,
for instance a synchronous machine connected to a
transmission network where FACTS devices are used to
control power flows and improve transient stability.
2. The machine is part of the power electronic system, for
instance an adjustable speed drive.
Similar modeling guidelines for representing rotating machine in both situations can be used, however some
particular considerations can be taken into account in some
cases and studies. Modeling guidelines provided in this document assume that power electronic systems operate at low
frequencies, between DC and 3 kHz. Therefore only the representation of rotating machines for this frequency range is
discussed. Regardless of the application to be simulated a

2-12

detailed modeling for the electrical and the mechanical parts


is usually required, saturation effects should be included, and
capacitance effects can be neglected. Frequency dependent of
electrical parameters, mainly rotor parameters might also be
considered. If frequencies of the transient case to be simulated are higher than 3 kHz, the simulation time is no longer
than a few milliseconds and the machine is not close to any
power electronic system (Le. a synchronous machine connected to a transmission system), the mechanical part can be
usually neglected and the machine can be represented by
means of an ideal source behind its subtransient reactance
and a frequency-dependent resistor; capacitance effects
become important, they can be represented by a parallel
capacitance-to-ground [1].
Other representations should be considered for specific applications
A) An aggregated representation of several
machines can be used to reduce complexity and simulation
time. Ref. [2] resents an aggregated induction model to be
used in power quality studies where short term interruptions
(i.e. sags) are of concern.
B) A very simplified representation for synchronous
and induction machines can be used in harmonic studies
when the machine is not directly connected to the harmonic
source [3].
An important aspect of the simulation of a rotating
machine is the procedure to obtain machine parameters and
the information where these parameters are derived. Electrical parameters of synchronous machines may usually be
obtained in one of the following forms: (1) data supplied
from manufacturer (conventional stability format data, standstill frequency response), (2) data from field tests (on-line
frequency response, load rejection test, other tests) and (3)
computer calculation using the finite-element method [4]. A
good discussion about methods to obtain electrical and also
mechanical parameters can be found in [5]. Data from steady
state and short circuit tests include reactances and time constants, armature resistance as well as saturation effects. Several procedures have been proposed to pass from these data
to electrical parameters which are used in the transient solution of the machine [6-8]. Although these tests and the corresponding procedures can also be used to obtain electrical
parameters of an induction machine, data conversion procedures for this type of machines are performed from different
specifications [9-10].
Frequency response tests have received much attention during the last 25 years. Several methods have been proposed to obtain parameters of d- and q-axis equivalent
circuits; they are based on standstill frequency response
(SSFR) [11-14], and on-line frequency response [15-16].
Some techniques have also been developed to account for
saturation effects [17].

4.5. VoltageSource Inverter Based FACTS Devices and their


Modeling Techniques Using EMTP
This section describes the fundamentals and the
modeling techniques of Voltage Source Inverter-based Flexible Alternating Current Transmission Systems (FACTS)
devices, namely, STATic synchronous COMpensator (STATCOM), Static Synchronous Series Compensator (SSSC), and
Unified Power Flow Controller (UPFC) using an EMTP simulation package. The FACTS model includes all the necessary components - a voltage source inverter with a DC link
capacitor, a magnetic circuit, and a realizable controller. The
UPFC model consists of two solid-state voltage source
inverters which are connected through a common DC link
capacitor. Each inverter is coupled with a transformer at its
output. The first voltage source inverter, known as STATCOM, injects an almost sinusoidal current, of variable magnitude, at the point of connection. The second voltage source
inverter, known as SSSC, injects an almost sinusoidal voltage, of variable magnitude, in series with the transmission
line. When the STATCOM and the SSSC operate as standalone devices, they exchange almost exclusively reactive
power at their terminals. While operating both the inverters
together as a UPFC, the injected voltage in series with the
transmission line can be at any angle with respect to the line
current. The exchanged real power at the terminals of one
inverter with the line flows to the terminals of the other
inverter through the common DC link capacitor. The functionalities of the models have been verified.

4.5.1 VSI Based Facts Devices


Flexible Alternating Current Transmission Systems
(FACTS) devices, namely STATic synchronous COMpensator (STATCOM), Static Synchronous Series Compensator
(SSSC) and Unified Power Flow Controller (UPFC), are
used to control the power flow through an electrical transmission line connecting various generators and loads at its sending and receiving ends. Each of the STATCOM and the SSSC
consists of a solid-state voltage source inverter with several
Gate Tum Off (GTO) thyristor switch-based valves and a DC
link capacitor, a magnetic circuit, and a controller. The number of valves and the various configurations of the magnetic
circuit depend on the desired quality of AC waveforms generated by the FACTS devices. When the STATCOM and the
SSSC operate as stand-alone devices, they exchange almost
exclusively reactive power at their terminals. While operating both the inverters together as a UPFC, the exchanged
power at the terminals of each inverter can be reactive as well
as real. The exchanged line flows to the terminals of the other
inverter through the common DC link capacitor. The objective in this section is to describe each component, such as a
voltage source inverter, a magnetic circuit, and a controller of
FACTS devices and its modeling techniques using an EMTP
simulation package. Since, the emphasis of modeling is
purely on FACTS devices, the power system in which the
FACTS devices are connected to has been modeled in a sim-

2-13

plistic way. A simple transmission line, shown in Fig. 39, has


an inductive reactance, X s' and a voltage source 'Vs' at the
sending end and an inductive reactance, X,., and a voltage
source.P, at the receiving end, respectively. The STATCOM
is connected at BUS 1 of the transmission line as shown in
Fig. 39 . The STATCOM model in EMTP consists of a harmonic neutralized voltage source inverter, VSIl, a magnetic
circuit, MCI, a coupling transformer, TI, a mechanical
switch, MSI , current and voltage sensors, and a controller.
The STATCOM injects an almost sinusoidal current at the
point of connection. This injected current is almost in
quadrature with the line voltage, thereby emulating an inductive reactance or a capacitive reactance at the point of connection. To achieve the bas ic function of a STATCOM, the
inverter is operated by regulating the reactive current flow
through it.

sssc

12=

_v,

~~ii2
~ i;
E",

1DC2

VSI2

ES22
ES2

t.Cl

C9!rtr:'ol~

Fig.40 A StaticSynchronous SeriesCompensator Model in EMTP


The UPFC which is connected to the simple transmission line is shown in Fig . 41. The UPFC model in EMTP
consists of two harmonic neutralized voltage source inverters, VSIl and VSI2, two magnetic circuits, MCI and MC2 ,
two coupling transformers, Tl and T2, four mechanical
switches , MSI, MS2, MS3 , and MS4, two electronic switches,
ES2 and ES22, current and voltage sensors, and a controller.
The voltage source inverters are connected through a common DC link capacitor. In a basic operation of a UPFC, the
STATCOM is operated by regulating the reactive current
flow through it and the SSSC is operated by injecting a voltage in series with the transmission line.

BUS1

ii,

Fig. 39 A StaticSynchronous Compensator Modelin EMTP


UPFC

Fig. 40 shows an SSSC connected in series with the


simple transmission line between BUS 1 and BUS 2. The
SSSC model in EMTP consists of a harmonic neutralized
voltage source inverter, VSI2, a magnetic circuit, MC2, a
coupling transformer, T2, a mechanical switch, MS2, two
electronic switches, ES2 and ES22, current and voltage sensors, and a controller. The SSSC injects an almost sinusoidal
voltage, of variable magnitude, in series with the transmission line. This injected voltage is almost in quadrature with
the line current, thereby emulating an inductive reactance or
a capacitive reactance in series with the transmission line.

12=

_~~ii2
v,
~ i;

ii,

E,.

MS3 -

P.C1

.
'DC2

VSl1 MS4\ISI2

ES22
ES2

t.Cl

CQntr:QI~~

Fig. 41 A UnifiedPowerFlowController Modelin EMTP

4.5.2 DESCRIPTION OF THE INVERTER


Fig. 42 shows a single phase inverter circuit,
referred to as a 3-level "pole," which consists of a positive
valve, A+, a negative valve, A-, and an AC valve, AAC '
When a pole is connected across a series of capacitors which
are charged with a total DC voltage of vDC and the valves are
closed and opened alternately, the pole output voltage, vAD,
at the midpoint of the pole A with respect to the midpoint, 0,

2-14

of the capacitor is a quasi square wave containing a positive


sequence fundamental component and all the odd harmonic
components, such as the zero sequence third, the negative
sequence fifth, and the positive sequence seventh, etc.

3-Levellnverter Pole

O.5voc~

O.5voc ~

At-

A",

1VIC

I>r

AtI>r

c=a:cJ

A",cNJ

aT
aT

Fig. 44 shows two 6-pulse inverters (ABC and DEF)


which are operated from the same DC link capacitor. On the
AC side, they are connected to a 3-phase load (XYZ) through
a magnetic circuit. The poles D, E, and F are operated in such
a way that the pole voltage fundamental phasors

aT

rav

aT

COl

o.5v<t:~
-27t
Vf!(j
1t-l'y
'""'Y

Oy
..{).5v<t: -

1t-"( 1t

VE, 1, Ve,1
and
VF,1 and are 120 apart and the funda mental voltage phasor set of the DEF inverter lags the funda-

mental voltage phasor set of the ABC inverter by 30. The


displacement angle between two consecutive 6-pulse inverters in a multipulse inverter arrangement is 21t/6m, where m is
the total number of 6-pulse inverters used. The configuration
of the magnetic circuit in Fig . 44 is such that if an inverter
the fundamenpole voltage is time shifted by an angle of
tal and all the harmonic components of the pole voltage get a
phase shift by an angle of +e in the positive direction, irrespective of their sequence.

Fig. 42 A 3-Level Inverter "Pole" and its Output Voltage

The amplitude of any odd multiple of fundamental component is

fA 0, n

= n

7/DC ccsn ):

consists of only a fundamental component and odd harmonic components (n) given by the equation (1) where n =6k
1 for k = 1,2,3, etc.

VNO'

-e,

(1)

where y is the "dead" period during which the AC


valve operates in each quarter cycle and the pole output voltage is zero and n =2k + 1 for k =0, 1, 2, 3, etc. For y =0, the
fundamental as well as all the harmonic components have the
highest possible amplitudes.

InverterOEF

-300
3)0

~~F

O.5Va::~

V0,1

VE,1

Vx

r---o:-

f----c:>--

Vy

MAGNETIC

t-

ORCUIT

O.5Va::~

l lJc

Vz

r-

zf--c:>VC,1

VA,1

Fig. 44 A 12-Pulse Harmonic Neutralized Inverter Configuration


with 3-Level poles
Fig. 43 A 6-Pulse Inverter with 3-Level poles and its Output Voltages

Fig. 43 shows three poles A, B, and C which are


connected across the same DC link capacitor and the pole
outputs are connected to a 3-phase load whose neutral point,
N, is not connected to the midpoint of the capacitor. The
poles A, B, and C which form a 6-pulse inverter are operated
in such a way that the pole voltages, VAO' vBO, and Yeo, are
time shifted from one another by one third of the time period
of the pole voltage. Therefore, the fundamental phasors
and
Ve,1 are 120 apart. Since, the zero
sequence components of each pole current have no return
path to the midpoint of the DC link capacitor, the zero
sequence components of each pole voltage, vNO =(vAO + vBO
+ veo)!3, appear between the neutral point and the midpoint
of the DC link capacitor. Therefore, each phase of the load
voltages, VAN =VAO - VNO, VBN =VBO - vNO' and vc =VeoVA, 1, VB, 1

Table 1 shows the time shifted A and D pole voltages, first twenty five harmonic components, final phase
angles after appropriate phase shift. The pole voltages from
the ABC inverter exhibits a 6-pulse harmonic neutralized
waveform with harmonic components n = 6k 1 for k = 1, 2,
3, etc. Similarly, the pole voltages from the DEF inverter
exhibits a 6-pulse harmonic neutralized waveform whose
harmonic components (n 6k 1 for k 1,2, 3, etc .) have
the same magnitudes as the corresponding harmonic components of the ABC inverter's 6-pulse harmonic neutralized
waveform. However, the harmonic components (n 6k 1
for k = 1,3,5, etc.) are in opposite phases while the harmonic
components (n = 6k I for k = 2, 4, 6, etc.) are in phases with
the corresponding harmonic components of the ABC
inverter's 6-pulse harmonic neutralized waveform. Therefore, if all the outputs from each 6-pulse inverter are combined by connecting the corresponding phases in series, a 12pulse harmonic neutralized waveform is obtained. The result-

2-15

component and odd harmonic components (n) where n = 12k


1 for k 1, 2, 3, etc. The presence of 12-pulse harmonic
components in the inverter output voltage may not be acceptable in many applications. Therefore, an inverter with a
higher pulse output voltage should be considered [56-58].

ing output voltage exhibits a fundamental component and


odd harmonic components (n) given by the equation (1)
where n = 12k 1 for k = 1, 2, 3, etc. Note that the output
voltage of a 12-pulse inverter with 3-level poles is referred to
as a 12-pulse waveform when the poles are operated with
dead angle y = o.
Fig. 45 shows a possible configuration of the magnetic circuit which can be used to generate a 12-pulse harmonic neutralized voltage. The ABC 6-pulse inverter voltage
is fed to a Y-Y transformer and the DEF 6-pulse inverter
voltage is fed to a ~- Y transformer. The inverter side A
winding and DE winding will have per tum fundamental
component voltages which are of same magnitude and in
phase and the fifth and the seventh harmonic components
each of which are of same magnitude but in opposite phase.
Therefore, if the line side of the transformer windings are
connected in series, the phase-X voltage will exhibit only a
fundamental component and 12-pulse harmonic components.

4.5.3 MODELING TECHNIQUE


ig. 46 shows the block diagram of the EMTP simulation program layout. Sample EMTP program files are
given in [56-58]. First, some general constants are defined.
Next, the control or the Transient Analysis of Control Systems (TACS) section receives its input signals from the sensors or measuring switches. This section generates the gating
signals for the pole valves "on the fly." The ideal pole voltages are mathematically combined to produce harmonic neutralized inverter voltages, eI, which are fed to the source
section. In an actual simulation case, the gating signals are
used to operate the pole valves of an inverter structure such
as the one shown in Fig. 42.

Note that the inverter side ( winding has J3 times the turns
as the inverter side Y winding has. This is needed in order to
keep the same volts per turn in both windings. The line side
inverter windings can have any turns ratio other than 0.5 to
increase or decrease the output voltage.
n

time shift

5
7
11
13
17
19
23
25

pole A
-5*(0)
+7*(0)
-11*(0)
+13*(0)
-17*(0)
+19*(0)
-23*(0)
+25*(0)

phase
shift
0
0
0
0
0
0
0
0

final
phase
angle
0
0
0
0
0
0
0
0

time shift

phase
shift

poleD
-5*( -1tI6)
+7*(-1tI6)
-11*(-1tI6)

+ I3*(-1tI6)
-17*( -1tI6)
+19*(-1t/6)
-23*(-1t/6)
+25*(-1tI6)

+1t/6
+1t/6
+1t/6
+1tI6
+1tI6
+1t/6
+1t/6
+1t/6

IGeneral

final
phase
angle

Qlnsta1Is

ConboI/TACS

Inverter
Voltages

1t

1t

0
0

Brmch
Transnission Li1e
Tn. ISformeI

1t

1t

0
0

Solrnes
TAC CooboIIed

.1CIepeI1dert

Table 1 Phase Angles of a 12-Pulse Inverter Phasors

Fig. 46 EMTP Modeling Structure

ri

VF
Ve
Vo

Vx
Vy

VA

~t}

VB

~~I

Vz

Vc

Fig.45 A Magnetic Circuitfor a 12-Pulse Harmonic Neutralized Inverter


The 12-pulse inverter configuration, shown in Fig.
45, presents a 3-phase voltage which contains a fundamental

Each valve, located in the switch section, can be


modeled with a number of GTO thyristors connected in
series each having an antiparallel diode and appropriate
snubber circuits. The pole output voltages are fed to a magnetic circuit, located in the branch section, which produces a
3-phase voltage set. In this way, the effects of a nonideal
magnetic circuit, which includes leakage reactance, magnetic
saturation, etc. can be studied. However, in this paper, the
valves and the magnetic circuit are assumed to be ideal. The
voltage, vDC' across the DC link capacitor is maintained by
the power balance equation at both AC and DC sides of the
inverter. This modeling technique gives sufficient insight to
the operation of the power circuit which produces a 3-phase
voltage set. The source section has some independent voltage sources which establish the power flow in a transmission

2-16

line. Next, the controlled and the independent sources are


fed to the branch section which contains the transmission line
and the coupling transformer. The line voltage set, vb at
BUS 1, the inverters' current sets, i l and i2, and the line current, i, are measured by the measuring switches. Finally, the
output section is defmed. In reality, the magnetic circuit can
also serve as the coupling transformer. Therefore, there is no
need for an additional coupling transformer.
The modeling may be done at various levels. For
example, to study the functionality of a FACTS device on an
elaborated power system network, a FACTS device with a
simplified model consisting of sinusoidal voltage sources and
detailed control and protection schemes may be adequate.
For magnetic circuit and valve designers, the primary focus
should be on the modeling of the detailed power circuit. The
modeling techniques described in this section are useful tools
to the FACTS designers.
The various control techniques of FACTS devices
and simulation results are described in the next section. In
each case, an instantaneous 3-phase set ofline voltages, vI> at
BUS 1 is used to calculate the reference angle, which is
phase-locked to the phase a of the line voltage, Via'

A. STATCOM
The controller of a STATCOM is used to operate the
inverter in such a way that the phase angle between the
inverter voltage and the line voltage is dynamically adjusted
so that the STATCOM generates or absorbs desired VAR at
the point of connection [56]. Fig. 47 shows the control block
diagram of the STATCOM. An instantaneous 3-phase

calculated by adding the relative angle, 0., of the inverter


voltage and the phase-lock-loop angle, e. The reference
quadrature component, h q., of the inverter current is defined
to be either positive if the STATCOM is emulating an inductive reactance or negative if it is emulating a capacitive reactance. The DC link capacitor voltage, VDC, is dynamically
adjusted in relationship with the inverter voltage. The control scheme used in this section shows the implementation of
the inner current control loop which regulates the reactive
current flow through the inverter regardless of the line voltage. However, if one is interested in regulating the line voltage, an outer voltage control loop must be implemented. The
outer voltage control loop will automatically determine the
reference reactive current for the inner current control loop
which, in turn, will regulate the line voltage.
Fig. 48 shows the digital simulation results from the
reactive current control operation of a STATCOM. Between
oand 50 ms, the mechanical switch, MSJ, stays open, disconnecting the STATCOM from the transmission line . The DC
link capacitor is precharged. The inverter output 12-pulse
voltage of phase a, el a, and the line voltage of phase a, Via,
are in phase. At 50 ms, MSJ closes and the quadrature cur-

rent demand, h q , of the inverter is set to zero. Since the


inverter current is zero , the inverter voltage of phase a, el a ,
and the line voltage of phase a, Via, have equal amplitudes.

At 125 ms, the quadrature current demand, Ilq , of the


inverter is set to one per unit capacitive, which means the
STATCOM should "see" the system as an inductive reactance and the inverter current of phase a, i la, lags the line
0

voltage of phase a, Via , by almost 90 .

V,A
(PU)

1
I
I
I

V1

I
I
I
I

IL

Gale
PatIem
1...cJge
I

-1-

Fig. 47 Control BlockDiagram ofa Static Synchronous Compensator


set of measured inverter currents, iJ, is decomposed
into its real or direct component, hd, and reactive or quadrature component, h q, respectively. The quadrature component is compared with the desired rference value, h q, and
the error is passed through an error amplifier which produces
a relative angle, 0. , of the inverter voltage with respect to the
line voltage. The phase angle, eJ, of the inverter voltage is

2-17

-1-

Fig. 48 Performance of a Static Synchronous Compensator with a


12-PulseHarmonic Neutralized InverterOperating in Capacitive and
Inductive Modes

The inverter voltage set, el, is greater than the line


voltage set, VI. At 175 ms, the quadrature current demand,
IIq *, of the inverter is set to one per unit inductive, which

means the STATCOM should "see" the system as a capacitive reactance and the inverter current in phase a, i la, leads
the line voltage at phase a, VIa, by almost 90. The inverter
voltage set, el, is less than the line voltage set, VI. At 250
the quadrature current demand, IIq *, of the inverter is set
to one per unit capacitive and the transition takes place in a
subcycle time. The phase angle, a, between the inverter
voltage and the line voltage is dynamically adjusted so that
the inverter maintains proper DC link capacitor voltage.
IDS,

Fig. 49 shows the expanded view of two sections of


Fig. 48. The inverter voltage and current show the presence
of 12-pulse harmonic components.

inverter in such a way that the injected alternating voltage in


series with the transmission line is proportional to the line
current with the emulated reactance being the constant of
proportionality [57]. When an SSSC injects an alternating
voltage leading the line current, it emulates an inductive
reactance in series with the transmission line causing the
power flow as well as the line current to decrease as the level
of compensation increases and the SSSC is considered to be
operating in an inductive mode. When an SSSC injects an
alternating voltage lagging the line current, it emulates a
capacitive reactance in series with the transmission line causing the power flow as well as the line current to increase as
the level of compensation increases and the SSSC is considered to be operating in a capacitive mode. An SSSC controller can also be used for stable reversal of power flow in the
transmission line.

V,A
(pu)

1-

V1

-1-

I
I
I
I
I
I
I
IL

1-

Fig. 50 ControlBlock Diagramof a Static SynchronousSeriesCompensator


250
tine
-1

(ms)

Fig. 49 Waveformsfrom a Static Synchronous Compensator with a


12-PulseHarmonicNeutralizedInverterOperatingin Capacitiveand
Inductive Modes

B. SSSC
An SSSC controller uses a solid-state voltage source
inverter to inject an almost sinusoidal voltage, of variable
magnitude, in series with a transmission line. This injected
voltage is almost in quadrature with the line current. A small
part of the injected voltage which is in phase with the line
current provides the losses in the inverter. Most of the
injected voltage which is in quadrature with the line current
emulates an inductive or a capacitive reactance in series with
the transmission line. This emulated variable reactance,
inserted by the injected voltage source, influences the electric
power flow in the transmission line. If an SSSC is operated
with an energy storage system, the controller becomes an
impedance compensation controller which can compensate
for the transmission line resistance as well as reactance. The
reactance compensation controller is used to operate the

Fig. 50 shows a control block diagram of an SSSC.


An instantaneous 3-phase set of measured line currents, i, is
first decomposed into its real or direct component, Id, and
reactive or quadrature component, I q , and then the amplitude,
I, and the relative angle, 0 in of the line current with respect
to the phase-lock-loop angle, E>, are calculated. The phase
angle, E>;, of the line current is calculated by adding the relative angle, E>ir, of the line current and the phase-lock-loop
angle, 0. The calculated amplitude, I, of the line current
multiplied by the compensating reactance demand, X q*,is the
insertion voltage amplitude demand, Vq *. The phase angle,
0"" of this insertion voltage demand is either 0 i+900 if the
demanding compensating reactance is inductive or 0;-90 if
the demanding compensating reactance is capacitive. The
DC link capacitor voltage is dynamically regulated in relationship with the insertion voltage amplitude demand. The
insertion voltage amplitude demand, Vq * ,and the DC link
capacitor voltage demand, VDC*, are related by the inverter
DC-to-fundamental AC amplitude gain factor (K;nv = 2/n for
a true harmonic netralized voltage source inverter). The DC

2-18

link capacitor voltage demand, VDC *, and the measured DC


voltage, VDC, are compared and the error is passed through an
error amplifier which produces an angle, p. The phase angle,
02, of the inverter voltage is calculated by adding the angle,
p, of the DC voltage regulator and the phase angle, 0\1> of the
insertion voltage demand. The compensating reactance
demand, X q *, is either negative if the SSSC is emulating an
inductive reactance or positive if it is emulating a capacitive
reactance. In another application, the insertion voltage
amplitude demand, Vq * may directly be specified and the
SSSC will inject the desired voltage almost in quadrature
with the line current.
2- V,A,X,P
(PU)

neous DC link capacitor voltage is proportional to the amplitude of the inverter voltage.
Therefore, when an SSSC emulates a reactance in
series with the transmission line, the power flow in the transmission line always decreases if the emulated reactance is
inductive. Also, the power flow always increases if the emulated reactance is capacitive.
Fig. 52 shows the expanded view of the two sections of Fig.
51. The inverter voltage show the presence of 24-pulse harmonic components.

1-~~P

o~~~

/i a

4-

Pq

1-

-1

Qq

X*q
I

-2-

200

400

tiTle
(ms)

600

Fig. 51 Performance of a Static Synchronous Series Compensator


with a 24-Pulse Harmonic Neutralized Inverter Operating in Inductive and Capacitive Modes

Fig. 51 shows the digital simulation results when an


SSSC emulates a reactance in series with the transmission
line. At the beginning of the operation, the mechanical
switch, MS2, and the electronic switch, S22, are open and
the electronic switch, S2, is closed. The inverter, VSI2,
injects no voltage. The DC link capacitor voltage, VDC, is
zero. At 50 ms, an inductive reactance compensation of 0.15
per unit is requested. The inverter output 24-pulse voltage,
0

of phase a leads the line current, i a, by almost 90 . At


175 ms, the inductive reactance demand is increased to 0.3
per unit. As the inductive reactance demand increases, the
line current, i a , and the power flow, Pq and Qq, in the transmission line decrease. At 300 ms, a capacitive reactance
compensation of 0.1 per unit is requested. The inverter volt-

e2a,

age, e2a, lags the line current, ia, by almost 90 . At 450 ms,
the capacitive reactance demand is increased to 0.15 per unit.
As the capacitive reactance demand increases, the line current, i a, and the power flow, Pq and Qq, in the transmission
line increase. In reality, the SSSC would encounter power
losses in the valves and in the magnetic circuit. Therefore,
there will always be a small part of real current component,
lId, flowing into the inverter and the inverter voltage will be

Fig. 52 Waveforms from a Static Synchronous Series Compensator


with a 24-Pulse Harmonic Neutralized Inverter Operating in Inductive and Capacitive Modes

C. UPFC
The stand alone operations of the STATCOM and
the SSSC, as just described, only allow the inverters to
exchange almost exclusively reactive power at their terminals. However, ifboth the inverters are operated from a common DC link capacitor, the injected voltage by the SSSC can
be at any angle with respect to the line current. The real
power exchanged at the terminals of the SSSC appears at the
terminals of the STATCOM through the DC link capacitor.
The STATCOM can still be used to control the reactive current flow through it independently [58]. The current injected
by the STATCOM has two components. First, a real or direct
component, which is in phase with the line voltage, absorbs
or delivers the real power exchanged by the SSSC with the
line. Second, a reactive or quadrature component, which is
in quadrature with the line voltage, emulates an inductive or
a capacitive reactance at the point of connection with the
transmission line.

almost 90 out of phase with the line current. The instanta-

2-19

The SSSC can be operated in many different modes,

such as voltage injection, phase angle shifter emulation, line


impedance emulation, automatic power flow control, etc. In
each mode of operation, the final outcome is such that the
SSSC injects a voltage in series with the transmission line
[58]. In this section, the SSSC is operated in a voltage injection mode. The control block diagram for the SSSC is shown
in Fig. 53.
The desired peak fundamental voltage , Vdq*, at the
output of the inverter and its relative angle, P, with respect to
the reference phase-lock-loop angle are specified. The phase
angle, 0z, of the inverter voltage is calculated by adding the
relative angle, P, of the inverter voltage and the phase-lockloop angle , 0 . The dead angle of each pole is calculated in
accordance with the operation of 24-pulse quasi harmonic
neutralized inverter [58].

Vd:I
vo:; -t------'

P-t--

--,

-1-

ia

Fig. 54 Performance of a Unified PowerFlow Controllerwith a 24PulseQuasi Harmonic Neutralized Inverterwith 3-Level Poles Operatingin a VoltageInjectionMode

At the beginning of the operation, the mechanical


switch, MS2, and the electronic switch, ES22, are open and
the electronic switch, ES2, is closed. The inverter, VSI2,
injects no voltage. The voltage , VIZa, at the terminals of the
coupling transformer, T2, is the voltage across its leakage
reactance. The mechanical switch, MSI , is open, disconnecting the STATCOM from the transmission line. The DC link
capacitor is precharged. At 50 ms , MSI closes and th e

quadrature current demand, Ilq , of the inverter is set to zero.


At 100 ms, a series voltage injection of 0.2 per unit at an
Fig. 53 ControlBlockDiagram ofa StaticSynchronous SeriesCompensator
Fig. 54 shows the digital simulation results from the
voltage injection mode of operation of an SSSC while the
STATCOM is operated to deliver no reactive current.

V,A,P,Q
(pu)

Va:

O t---~::---+-------.:....A'-----~

time

(ms)

angle of 60 0 leading the reference phase-lock-loop angle is


requested. The series inverter output voltage, eza , of phase a
leads the line current, i a , by an angle o. The real power
absorbed by the series inverter appears at the BUS 1 through
the STATCOM. The shunt inverter output voltage, el a , of
phase a is in phase with the current, ;I a, flowing through it.
The power delivered at the receiving end decreases. At 175
ms, the injected voltage request is increased to 0.4 per unit
while maintaining the same angle. As the voltage injection
demand increases, the line current, i a , and the power flow, P,
and Q,., in the transmission line decrease. By injecting a voltage by the SSSC of any magnitude, within the rating of the
inverter, and at any angle with respect to the line current, the
real power, P,., and the reacti ve power, Q,., at the receiving
end of the transmission line can be increased, decreased or
even reversed selectively.
Fig. 55 shows the expanded view of two sections of
Fig. 54. The inverter voltage and current show the presence
of harmonic components.

-1-

2-20

engineering community, the EMTP type of programs are


more commonly used. This results mainly from the great capabilities and flexibility of these programs in handling conventional power system dynamics and electromagnetic
transients beside their capabilities of handling power electronics. With an adequate power electronics device and circuit
simplification, the EMTP type of programs are powerful for
modeling various types of power electronics applications .
Because these programs are based on the time domain solution method, the dynamic interaction between the power electronics and the rest of the system can be easily incorporated in
simulation.

V,A
(PU)

-1ia

1-

-1-

:D)

time
(ms)

Fig.55 Waveforms froma UnifiedPowerFlowController witha 24PulseQuasiHarmonic Neutralized Inverterwith 3-LevelPolesOperatingin a Voltage Injection Mode

4.5.4 SUMMARY
FACTS devices - STATCOM, SSSC, and UPFC,
have been modeled using an EMTP simulation package. The
UPFC consists of two voltage source inverters - one injects
an almost sinusoidal voltage in series with the transmission
line and the other injects an almost sinusoidal current at the
point of connection . The injected voltage can be at any angle
with the line current. The injected current has two parts.
First, the real part , which is in phase with the line voltage,
delivers or absorbs real power to the line that is exchanged by
the injected voltage source plus losses in the UPFC. Second,
the reactive part, which is in quadrature with the line voltage,
emulates an inductive reactance or a capacitive reactance at
the point of connection . The SSSC model has been operated
injecting a voltage in series with the transmission line. The
STATCOM model has been operated regulating the reactive
current flow through it and the transition from one mode of
operation to the other mode takes place in a subcycle time .
The operation of the model is verified with the model connected to a simple transmission line which can easily be
replaced by the utility's existing more complex power system
network.
5. CONCLUSIONS
The appropriate characterization of the power electronics is
very important in power system simulations involving power
electronics operations. In most of these simulations, detailed
representations of the power electronics are not necessary.
Depending on the objective of a study, the involved power
electronics subsystem can be always reduced to some extend
with minimal loss of accuracy.
Numbers of the digital computation tools are capable of simulating power electronics cases. However, in power systems

The important considerations for simulating power electronics applications have been summarized in this guidelines .
Several modeling examples including a comprehensive treatment of voltage source inverter based FACTS device and its
modeling techniques using EMTP type of programs were presented. The procedures used to implement power electronics
models in these examples are valuable for using other digital
simulation tools.

6. REFERENCES
1. CIGRE Working Group 02 (SC 33), "Guidelines for Representation ofNetwork Elements when Calculating Transients", 1990.
2. J. Blanes, A. Quijano, S. Catal n, "Simulation of induction motors behaviour during voltage disturbances using
an aggregated model", European EMTP/ATP Users
Group Meeting, November 9-11,1997, Barcelona.
3. P. F. Ribeiro, "Distribution system and other elements
modeling", Chapter 3 of Tutorial on Harmon ics Modeling and Simulation, IEEE TP-125-0, 1998.
4. "Symposium on Synchronous Machines Modelling for
Power System Studies", IEEE Power Engineering Society, Publication 83THOIOI-6-PWR, 1983.
5. P. M. Anderson, B. 1. Agrawal and J. E. Van Ness, Subsynchronous Resonance in Power Systems, IEEE Press,
1990.
6. "IEEE Guide: Test Procedures for Synchronous Machines", IEEE Std. 115, 1983.
7. F.1. Alvarado and C. Canizares, "Synchronous machine
parameters from sudden-short tests by back-solving",
IEEE Trans. on Energy Conversion, Vol. 4, no. 2, pp.
224-236, June 1989.
8. I. M. Canay, "Modelling of alternating-current machines
having multiple rotor circuits", IEEE Trans. on Energy
Conversion, vol.8, no. 2, pp. 280-296, June 1993.
9. "IEEE Guide: Test procedure for polyphase induction
motors and generators", IEEE Std. 112-1978.
10. G. J. Rogers and D. Shirmohammadi, "Induction machine modelling for electromagnetic transient program",
IEEE Trans. on Energy Conversion, vol. 2, no. 4, pp. 622628, December 1987.
11. "IEEE Standard Procedures for Obtaining Synchronous
Machine Parameters by Standstill Frequency Response
Testing", IEEE Std.l15A, 1987.
12. I. M. Canay, "Determination of the model parameters of
machines from the reactance operators xd(P), xq(P)
(Evaluation of standstill frequency response test)", IEEE
Trans. on Energy Conversion, vol. 8, no. 2, pp. 272-279,
June 1993.

2-21

13. A. Keyhani and H. Tsai, "Identification of high-order


synchronous generator models from SSFR test data", presented at the 1994 IEEE/PES Winter Meeting, Paper no.
94 WM 022-4 EC, New York, January 30-February 3,
1994.
14. J. R. Willis, G. J. Brook and J. S. Edmonds, "Derivation
of induction motor models from standstill frequency response", IEEE Trans. on Energy Conversion, vol. 4, no.
4, pp. 608-615, December 1989.
15. P. L. Dandeno, P. Kundur, A. T. Poray and H. M. Zein
El-din, "Adaptation and validation of turbogenerator
model parameters through on-line frequency response
measurements", IEEE Trans. on Power Apparatus and
Systems, vol. 100, no. 4, pp. 1656-1645, April 1981.
16. P. L. Dandeno, P. Kundur, A. T. Poray andM. E. Coultes,
"Validation of turbogenerator stability models by comparison with power system tests", IEEE Trans. on Power
Apparatus and Systems, vol. 100, no. 4, pp. 1637-1645,
April 1981.
17. F. P. de Mello, L. N. Hannett, J. R. Willis, "Determination of synchronous machine stator and field leakage inductances standstill frequency response tests", IEEE
Trans. on Power Systems, vol. 3, no. 4, pp. 1625-1632,
November 1988.
18. L. Dube, H.W. Dommel, "Simulation of control system
in an Electromagnetic Transient Program with TACS",
IEEE Trans. on Power Industry and Computer Applications, 1977
rs, EMTP Rule Book, EPRIIDCG Version 1.0.
20. D. Goldsworthy, 1. J. Vithayathil, "EMTP model of an
HVDC transmission system", Proceedings of the IEEE
Montech '86 Conference on HVDC Power Transmission,
September 26-0ctober 1, 1986, pp. 39-46
21. L. X. Bui, S. Casoria, G. Morin, "Modeling of digital
controls with EMTP" , CEA Meeting, March 25-29,
1989, Montreal, Canada
22. J. Reeve and S. P. Chen, "Versatile interactive digital
simulator based on EMTP for AC/DC power system transient studies", IEEE Trans. on Power Apparatus and Systems, Vol. 103, No. 12, December 1984, pp. 3625-3633
23. K. G. Fehrle, R. H. Lasseter, "Simulation of control systems and application to HVDC converters", IEEE Tutorial Course 81 EHOI73-PWR on Digital Simulation of
Electrical Transient Phenomena, 1981.
24. L. X. Bui, G. Morin, J. Reeve, "EMTP TACS-FORTRAN interface development for digital controls modeling", 91 SM 417-6 PWRS
25. G. Morin, L. X. Bui, S. Casoria, J. Reeve, "Modeling of
the Hydro-Quebec - New England HVDC system and
digital controls with EMTP", IEEE Trans. on Power Delivery, Vol. 8, No.2, April 1993, pp. 559-566.
26. R. H. Lasseter and S. Y. Lee, "Digital simulation ofstatic
var system transients", IEEE Trans. on Power Apparatus
and Systems, Vol. PAS-I0l, No. 10, pp. 4171-4177, October 1982.
27. A. M. Gole and V. K. Sood, "A static compensator model
for use with electromagnetic transients simulation programs", IEEE Trans. on Power Delivery, Vol. PWRS-5,
No.3, pp. 1398-1407, July 1990
28. A. N. Vasconcelos et. al. "Detailed modeling of an actual
static Var compensator for electromagnetic transients
studies", IEEE Trans. on Power Systems, Vol. PWRS-7,

no. l,pp. 11-19, February 1992


29. S. Y. Lee et aI., "Detailed modeling ofstatic Var compensators using the Electromagnetic Transients Program
(EMTP)", IEEE Trans. on Power Delivery, Vol. 7, no. 2,
pp. 836-847, April 1992
30. S. Lefebvre and L. Gerin-Lajoie, "A static compensator
model for the EMTP", IEEE PES Meeting, San Diego,
July 28-August 1, 1991, Paper 91 SM 461-4 PWRS.
31. L. Dube and I. Bonfanti, "MODELS: A new simulation
tool in the EMTP", European Transactions on Electrical
Power Engineering, Vol. 2, no. 1, pp. 45-50, January/
February 1992.
32. Leuven EMTP Center (ed.), ATP Rule BOQk, 1990.
33. J. A. Martinez, "Simulation of a microprocessor-controlled SVC", 21th European EMTP Meeting, June 5-7,
1992, Crete (Greece).
34. H.W. Dommel, EMTP Reference-Manual (EMIP Theory Book), BPA, 1986.
35. J. A. Martinez, "Simulation of power electronics using
the EMTP, Part I: Power converters, A survey", UPEC'94, September 14-16, 1994, Galway.
36. G. A. Capolino, H. Henao, "ATP simulation for power
electronics and AC drives", 15th European EMTP Users
Group Meeting, Paper 88R-027, October 17-18, 1988,
Leuven.
37. G. A. Capolino, H. Henao, "Simulation of electrical machine drives with EMTP", 18th European EMTP Users
Group Meeting, Paper M7, May 28-29, 1990, Marseille
38. J. A. Martinez, G. A. Capolino, "TACS and MODELS:
Drive simulation languages in a general purpose program", Proc. MCED'91, Marseille, July 1-2, 1991, pp.
RI-RI3.
39. G. A. Capolino, H. Henao, "ATP advanced usage for
electrical drives", EMTP Summer Course, July 5-8,
1993, Leuven.
40. H. Knudsen, "Extended Park's transformation for 2 by 3phase synchronous machine and converter phasor model
with representation of harmonics", IEEE PES Summer
Meeting, Paper 94 SM 350-9 EC, July 24-28, 1994, San
Francisco.
41. M. Mazzucchelli, G. Sciutto, "Digital simulation of AC
electrical drives based on field-oriented control method
using a general purpose program", Proceedings PCIM,
pp.350-364, 1986, Munchen
42. Z. Daboussi, N. Mohan, "Digital simulation of field-oriented control of induction motor drives using EMTP" ,
IEEE Trans. on Energy Conversion, Vol. 3, pp. 667-673,
September 1988.
43. L. Tang, M. McGranaghan, "Modeling an active power
line conditioner for compensation of switching transients", Proceedings of First International Conference on
Power Systems Transients (IPST'95), Lisbon (Portugal),
pp. 403-408.
44. X. Z. Meng, J. G. J. Sloot, H. Rijanto, "Modelling of
semiconductor fuses in EMTP", Proceedings of First International Conference on Power Systems Transients (IPST'95), Lisbon (Portugal), pp. 481-486.
45. J. A. Martinez-Velasco, R. Abdo, G.A. Capolino," Advanced representation ofpower semiconductors using the
EMTP", Proceedings of First International Conference
on Power Systems Transients (IPST'95), Lisbon (Portugal), pp. 505-510.

2-22

46. S. Lefebvre, R. D. Rangel, "Modeling of power electronics devices in EMTP-TACS", Proceedings of First International Conference on Power Systems Transients
(IPST'95), Lisbon (Portugal), pp. 511-516.
47. G. A. Capolino, H. Henao, D. Leduc, V. T. Nguyen
Phuoc, "CAD of field-oriented induction motor drives
using a general purpose program", Proceedings PC1M,
1989, Munchen.
48. E. Bassily, G. A. Capolino, H. Henao, "Simulation ofdiscrete DC drive using sliding mode control", 22nd European EMTP Users Group Meeting, Paper 92R-018,
November 9-10, 1992, Leuven.
49. E. Bassily, G. A. Capolino, H. Henao, "Simulation and
design of brushless motor drive control with fuzzy pi regulator", Proceedings of First European Conference on
Power Systems Transients (EPST'93), Lisbon (portugal),
pp 84-91, June 1993.
50. A. K. Khan, R. Dwyer, M. Mcgranaghan, L. Tang, "Evaluation of Harmonic Impacts from Compact Fluorescent
Lights on Distribution Systems", IEEE PES 95 WM 1057-PWRS.
51. J. A. Martinez, "EMTP simulation of digitally-controlled
static Var system for optimal load compensation", IEEE
PES Summer Meeting, Paper 94 SM 452-3 PWRD, July
24-28, 1994, San Francisco.
52. J. A. Martinez and G. A. Capolino, "EMTP simulation of
power electronics and drives using data modularization",
Proceedings First International Aegean Conference on
Electrical Machines and Power Electronics, Kucadasi
(Turkey), May 27-29, 1992.
53. L. Tang, M. F. McGranaghan, R. A. Ferraro, S. Morganson, b. Hunt, "Voltage notching interaction caused by
large adjustable speed drives on distribution systems with

54.

55.
56.

57.

58.

59.

60.

2-23

low short circuit capacities", IEEE PES 95 SM 388-9PWRD.


O. B. Nayak, A. M. Gole, D. G. Chapman, and J.B.
Davies, "Dynamic performance of static and synchronous compensators at an HVDC inverter bus in a very
weak AC system", IEEE Trans. on Power Systems, Vol.
9, NO.3, August 1994, pp. 1350-1358.
M. Szechtman, T. Wess, C. V. Thio, "First benchmark
model for HVDC control studies", Electra, No. 135,
April 1991.
K. K. Sen, STATCOM - STATic synchronous COMpensator: Theory, Modeling, and Applications, 99WM706,
IEEE PES Winter Meeting, New York, USA, 1999.
K. K. Sen, SSSC - Static Synchronous Series Compensator: Theory, Modeling, and Applications, IEEE Transactions on Power Delivery, vol. 13, No.1, January 1998.
K. K. Sen and E. J. Stacey, UPFC - Unified Power Flow
Controller: Theory, Modeling, and Applications, IEEE
Transactions on Power Delivery, vol. 13, No.4, October
1998.
A.M. Gole ,I.T. Fernando, G.D. Irwin , O.B. Nayak,
"Modeling of Power Electronic Apparatus: Additional
Interpolation Issues", International Conference on Power
System Transients, IPST'97, Seattle, June 22-26, 1997,
Proceedings: pp 23-28.
A.M. Gole, L. Mootoosamy, \ZK. Sood, "Validation and
Analysis of a Grid Control System using d-q-z Transformation for Static Compensator Systems", Canadian Conference on Electrical & Computer Engineering,
Montreal, Sept. 17-20, 1989; Proceedings pp. 745-748.

Modeling Guidelines for Low Frequency Transients


Report Prepared by the Low-Frequency Transients Task Force
of the IEEE Modeling and Analysis of System Transients Working Group
Contributing Members: R. Iravani (Chair), A.K.S. Chandhury,
I.D. Hassan, J.A. Martinez, A.S. Morched,
B.A. Mork, M. Parniani, D. Shirmohammadi, R.A. Walling
Abstract: The objective of this report is to provide guidelines
for modeling and analyses of low-frequency (approximately 5 to
1000 Hz) transients of electric power systems, based on the use
of digital time-domain simulation methods. For the ease of reference, the low-frequency transients are divided in seven distinct phenomena. This report (1) briefly describes the physical
nature of each phenomenon, (2) identities those power system
components/apparatus which either contribute to or are
affected by the phenomenon, (3) provides guidelines for digital
time-domain simulation and analyses of the phenomenon and
(4) provides sample study-system and typical digital timedomain simulation results corresponding to each phenomenon.
A comprehensive list of reference is also included in this report
to provide further in-depth information to the readers.

l.Torsional oscillations (5 to 120Hz)


2.Transient torsional torques(5 to 120Hz)
3.Turbine blade vibrations (90 to 250 Hz)
4.Fastbus transfer(1 to 1000Hz)
5.Controller interactions (10 to 30 Hz)
6.Harmonic interactions and resonances (60 to 600 Hz)
7.Ferroresonance (1 to 1000 Hz)

For each of the above phenomenon this report provides (1) a


brief explanation of the physical phenomenon, (2) modeling
guidelines for time-domain simulation and analyses, and (3)
typical sample systems and simulation results.

Keywords: Low-Frequency Transients, Electromechanical


Transients, Modeling, Time-Domain Analysis, Torsional
Dynamics, Turbine Vibrations, Bus-Transfer, Controller
Interactions, Harmonic Interactions, Ferroresonance

1. INTRODUCTION
This report is intended for practicing power system engineers
who are involved in system analysis, system control, and system planning. To use the report efficiently, adequate understanding of the physical phenomenon of interest and
familiarity with the concepts and techniques of digital computer simulation approaches are necessary.

An interconnected power system can experience undesirable


oscillations and transients as a result of small-signal perturbations, large-signal disturbances, and nonlinear characteristics
of the system components. The oscillations cover a wide frequency range approximately from 0.01 Hz to 50 MHz. Oscillations in the frequency range of 0.01 to 1000 Hz are defmed
in this report as low-frequency (slow) transients. We interchangeably use the terms "slow transients", "low frequency(LF) dynamics", and "LF oscillations" throughout this
report. All the issues relevant to I ow-frequency inter-area
electromechanical oscillations (approximately 0.1 to 1 Hz)
and classical turbine-generator swing modes (approximately
1 to 2.5 Hz) are discussed by other IEEE working groups, and
are not discussed here. A general guideline for representation
of network elements for electromagnetic transient studies
have been previously published [1.1]. The mandate of the
IEEE Low-Frequency Transients Task Force is to provide
modelling guidelines for time-domain analysis ofLF oscillations within the frequency range of 5 to 1000 Hz. Low frequency dynamics are of concern with respect to power system
stability issues and/or temporary overvoltages.

Section 2 of the report deals with low-frequency transients


which involve both electrical and mechanical dynamics, i.e.,
torsional oscillations, transient torsional torques, turbineblade vibrations and fast bus-transfer. Section 3 discusses
low-frequency electrical dynamics, as a result of control systems interactions. Section 4 provides analysis guidelines for
harmonic interactions and resonance phenomena. The phenomenon of ferroresonance is discussed in Section 5.

2. LOW-FREQUENCY ELECTROMECHANICAL
DYNAMICS
This section provides modeling and analysis guidelines for low-frequency dynamics which involve electromechanical oscillations. The phenomena which are covered in
this section are torsional oscillations, transient torques, tur-

phenomena of 60 Hz power systems in the LF range are divided into the following categories:

3-1

bine-blade vibrations, and bus-transfer.

2.1 DEFINITIONS
2.1.1 Torsional Oscillations [2.1, 2.2, 2.3, 2.4, 2.5J
Shaft system of a steam turbine-generator experiences torsional oscillations when one or more of its natural oscillatory
modes, usually at subsynchronous frequencies, are excited.
Sustained or negatively damped torsional oscillations occur
when a turbine-generator shaft system exchanges energy with
an electrical system at the shaft oscillatory modes. This exchange of energy can exist if the electrical system is equipped
with either series capacitors or HVDC converter stations. The
phenomenon of torsional oscillations can also exist as a result
of interaction between the shaft system of a steam turbinegenerator and

the generator excitation systems through either AVR or PSS


control loops,
electronically controlled governor system,
voltage control loop of an electrically close static VAR. compensator (SVC)
large electric arc furnaces.

Although AVR, PSS and governor system can excite torsional


oscillations, the excitation is primarily due to inadequate control design considerations and can be avoided by introducing
filters in the control circuitry. Thus, this report does not consider the generator controls as the main contributors to the
phenomenon of torsional oscillations (Table 1).

The phenomenon of torsional oscillation is referred to as subsynchronous resonance (SSR) when it is a result of interaction
between a shaft system and a series capacitor compensated
transmission line. The problems associated with the phenomenon of small-signal torsional oscillations are:

the natural frequencies of the shaft torsional oscillatory


modes. Usually, the oscillatory mode at the first torsional frequency dominates the shaft transient oscillations. The major
incidents which result in severe shaft stresses are: line-to-line
faults, three-phase faults, fault clearing, automatic reclosures,
and out-of-phase synchronization. The amplitudes of the
shaft transient stresses can be particularly large when the network is equipped with series capacitors.

High amplitude shaft mechanical stress can induce significant


fatigue in the shaft segments and result in noticeable shaft
life-time reduction during each oscillatory cycle. Such oscillations may even result in catastrophic shaft failure. The primary purpose of time-domain investigation of turbinegenerator shaft mechanical stresses is to identify the peak
torques imposed on the shaft segments, after system disturbances. Transient shaft mechanical stresses calculated based
on time-domain simulation methods also can be used to estimate shaft loss of life as a result of system disturbances.

2.1.3 Turbine-Blade Vibrations [2.6]


Frequencies of turbine-blade vibrational modes are
usually within 90 to 250 Hz, and constitute supersynchronous frequency modes. Identification of supersynchronous
frequency modes and their corresponding frequencies is best
carried out by solving elasticity equation of the shaft system
as a continuum, based on the use of finite element methods.
This approach is beyond the scope of this report and usually
carried out by turbine manufacturers.

In this report, the objective is to investigate the impact of


large-signal disturbances on those supersynchronous frequency natural modes which are the reason for turbine-blade vibrations. Thus the required model is tailored to represent
particular supersynchronous modes and not all of them.
The concern with turbine-blade vibrations is fracture
and loss-of-life of the blades due to the fatigue induced in the
blades by repetitive or sustained oscillations. Vibrations of turbine-blades can be excited by large-signal electrical disturbances, e.g. faults, fault clearing, line switching, reclosure, and
out-of-phase synchronization.

i)

Sustained or even negatively damped oscillations which


are considered as small-signal instability problems, and
ii) (loss of life of turbine-generator shaft segment(s) due to the
fatigue induced in the shaft segment(s) as a result of each
oscillatory cycle.

2.1.4 Fast Bus Transfer [2. 7,2.8,2.9]


Motors and other loads in utility and heavy industrial applications are supplied during normal operation from a preferred
power source. An alternate power source is normally provided to supply such motors and other loads during planned shutdowns and upon loss of normal power from the preferred
power source. The process of disconnecting the motors and
other loads from one source and reconnecting to an alternate
source is commonly defmed as "bus transfer". Manual trans-

2.1.2 Transient Torsional Torques [2.1, 2.2, 2.3, 2.4, 2.5]


The shaft segments of turbine-generator units are exposed to
large-amplitude, oscillatory, mechanical stresses as a result of
electric network faults, and planned and unplanned switching
incidents. Frequencies of the shaft mechanical stresses are

3-2

fer means are normally provided to allow transferring the motors and other loads from one power source to the other.
However, upon loss of the preferred power source, the motors
and other loads are automatically transferred to the alternate
power source. This automatic transfer is necessary to allow
uninterrupted operation of the motors and other loads important to personnel safety and process operation. This report
does not address the concept ofbus transfer by means of semiconductor switches [2.23].

The normal and alternate power source connections are always selected such that they are in phase. Therefore, manual
transfers can be accomplished in a make-before-break, i.e.,
the motors and loads are connected to the second power
source before the first power source is disconnected. In this
overlapping transfer, the power supply is not interrupted and
the motors are not subjected to transients. However, during
automatic transfers, the motors may be disconnected from
both power sources for a short duration depending on the type
oftransfer and the associated circuit breakers operating times.
The time during which the motors are disconnected from both
power sources is termed the "dead time". Dead time is usually
between two cycles to 12 cycles. If the relative angle between
the motor residual voltage and the power source voltage becomes large enough at the time of reconnection with significant residual voltage remaining, the resultant voltage

mode which propagates almost through the entire of an interconnected electric network, the phenomena described in Section 2.1 are experienced only within a limited part of the
network. The section of the network which experiences the
phenomenon of interest, and must be represented in adequate
detail for the study of the phenomenon, is referred to as the
"Study Zone" The rest ofthe network is referred to as the "external system" The external system is represented by an
equivalent model. Identification of border nodes of the study
zone for a meshed network requires significant familiarity
with the network, as well as engineering judgment. As of
now, there is no straightforward and systematic approach to
identify the border nodes. One approach involves multiple
harmonic analyses of the system under investigation as
boundaries are extended to identify if new resonant frequencies (at the frequency range of interest) with low dampings exist.

Proper determination of the study zone can exert a major impact on the investigations of torsional dynamics and transient
torques. Comparatively, the impact of the study zone on the
vibrations of turbine blades is less significant. Identification
of the study zone for bus transfer studies is relatively straightforward.

2.2.2 Component Model

between the power source and the motor will produce an inrush current. The inrush current may be significantly largely
than the normal full voltage staging current. Such high inrush
currents cause high winding stresses and transient shaft
torques which can damage the motor and/or the driven equipment.

Table 1 identifies the study zone components and their equivalent models for investigations of slow transient phenomena.
Further explanation ofthe system components are given in the
following sections.

2 2 2 1 Synchronous Generator Electrical System [2 lOJ

The most common bus transfer scheme is the fast bus transfer
scheme. In this scheme, opening of the normal power source
breaker initiates closing of the alternate power source breaker
without intentional time delay. Fast bus transfer operations
result in the motors being disconnected from both power
sources for a duration of as short as two cycles to as long as
12 or more cycles.

Figure 2.1 shows a second-order and a third-order


models of a synchronous machine. Inclusion of the differentialleakage inductance Lfld in the second-order model is
recommended. The differential leakage inductance has
noticeable influence on the damping, and the range of instability of each torsional mode, (with respect to series compensation level), particularly for a salient pole machine.
However, Lfld does not influence the phenomenon of blade
vibrations.

Presently, there are no generic criteria to ensure


acceptable fast bus transfer operations. Therefore, it is necessary to analyze the transient behavior of motors during fast
bus transfer operations. The analysis should be on a case by
case basis to ensure that the motors will not be subjected to
excessive inrush currents and/or shaft transient torques.

Representation of machine electrical system based on


the third-order model, Fig. 2.1, is more accurate. Inclusion of
the differential leakage inductance Lf12d in the third-order
model has the same impact as that of Lfld for the second-order
model. Magnetic saturation of a synchronous machine, both on
d-axis and q-axis, does not have any significant impact on the
phenomenon of small-signal torsional oscillations, but has pro-

2.2 MODELING GUIDELINES


2.2.1 Study Zone
In contrast to an inter-area, electromechanical, oscillatory
3-3

Component

Torsional
Oscillations
Second-Order
Model and
Preferably ThirdOrder Model (d-q-o
Model)
Mass-SpringDashpot Model

Transient
Torques
Third-Order
Model (d-q-o
Model)
Including
Saturation
Mass- SpringDashpot Model

Power
Transformer

Conventional
Low-Frequency
Model including
Saturation
Characteristic

Transmiss ion Line

Turbine-Blade
Vibrations
Third-Order Model
(d-q-o Model)
Including
Saturation

Fast Bus
Transfer
Not
applicable

Not
Applicable

Conventional
Low-Frequency
Model including
Saturation
Characteristic

Detail
Mass-SpringDashpot Model
Conventional
Low-Frequency
Model including
Saturation
Characteristic

Equivalent-a
Model
Ideal Capacitor

Equivalent-a
Model
Ideal Capacitor

Equivalent-a
Model
Ideal Capacitor

Series R-L

Series R-L

Series R-L

Fixed Impedance
Load

Fixed Impedance
Load

Fixed Impedance
Load

Large Motor Load

d-q-o Model of
Electrical System,
Mass-SpringDashpot Model of
Shaft System

Voltage Source
Behind Fixed
Impedance

Voltage Source
Behind Fixed
Impedance

HVDC Converter
Station

Detailed Model of
Converter and
Linearized
(Simplified)
Model of Controls
Detailed Model of
Power Circuitry and
Linearized
(Simplified)
Model of Controls
Ideal Switch
Unimportant

Detailed Models of
Converter and
Controls

Detailed Models of
Converter and
Controls

Detailed Model of
Power Circuitry
and Contro Is

Detailed Model of
Power Circuitry
and Controls

Not
Applicable

Ideal Switch
Unimportant

Ideal Switch
Unimportant

Unimportant

Series Capacitor
Overvoltages
Protection System

Ser ies Capac itor


Overvoltages
Protection System

Ideal Switch
Not
Applicable
Not
Applicable

Synchronous
Generator's
Electrical System

Turbine-Generator
Shaft System

Series/Shunt
Capacitor
Series/Shunt
Reactor
Static Load

SVC

Circuit Breaker
Generator
Controls
Protection System'

Table 1: Component Model

3-4

Conventional
LowFrequency
Model
including
Saturation
C harac terist ic
Not
Applicable
Ideal
Capacitor
Series R-L
Fixed
Impedance
Load
d-q-o Model
of
Electrical
System,
Mass- SpringDashpot
Model of
Shaft System
Not
Applicable

erator unitmust be separately represented.

nounced impact on transient torques andbladevibrations.

In most studies, the power plant under consideration is composed of more than one turbine-generatorunit. If all the turbine-generator units are nominallyidentical,and under almost
equal loading conditions, they can be representedby a single,
equivalent turbine-generator unit. Otherwise, each turbinegeneratorunit must be separately represented.
d-axis

Lt

STATOR

Rlq

q-axis
1.(

LfJd

~q

HP

IP

LPA

LPB

EXC

LId RId

STAToJl:-

HEW
Fig. 2.2. Turbine-generator shaftsystemand its mass-spring-dashpot mode

d-axis

STATOR

FinalStageBlade

Early Stage Blade

t ,

q-axis

Fig. 2.1. Synchronous machine 2nd-order and 3rd-order models

2 2 2 2 Turbine-Generator Mechanical System [2 11, 2 12,

2.lll
Fig. 2.2 shows a six-mass shaft system and its equivalent
mass-spring-dashpot model. The mass-spring-dashpot model
of Fig. 2.2 assumesthat (1) the high-pressure turbine(HP),the
intermediate-pressure turbine (IP), the low-pressure turbines
(LPA and LPB), the generator rotor (G), and the excitor
(EXC) are rigid masses, and (2) each shaft section is composed of a spring constant (Kij) and a cyclic damping (Dij).
The main shortcoming of the model is that neither the shaft
cyclic dampings (Dijis) nor the viscous dampings (Diis) can
be directlymeasured or calculated. Neglectingthe dampings
providesthe most pessimisticdynamicresponse, which is often the objectiveof an investigation. The discussion of [2.11 ]
provides further descriptionof the mass-spring-dashpot model. Figure 2.3 shows a mass-spring-dashpot model of the turbine-generator set of Fig. 2.2 for investigation of turbineblade vibrations. This model representsbladesof turbinesections as lumped masses [2.6].

Fig. 2.3. Mass-spring dashpotmodelof the turbine-generator for turbinebladevibrational studies(mechanical dampingis neglected)

2 2 2 3 power Transfonner

Classical low frequency transformer model with proper connections at both HV and LV sides is adequate for representation of each powertransformerwithin the Study Zone. Figure
2.4 shows the classical model of a single-phase transformer
for simulationof low frequencydynamics. No-load V-I magnetic saturationcharacteristic can be used as a fair approximation of core saturationfor the phenomenaof interest. A threephase transformer model is developed based on proper connections of primary and secondary windings of the singlephase model of Fig. 2.4.

In moststudies, the power plantunder consideration is


composed of more thanoneturbine-generator unit. If all theturbine-generator units are nominally identical, and under almost
equal loading conditions, they can be represented by a single,
equivalent turbine-generator unit. Otherwise, eachturbine-gen-

3-5

L2

R2

Nl:N2

Fig. 2.4. Low frequency modelof a single-phase transformer.

2 2 2 4 Transmission Ijne

Shaft dynamics of a turbine-generator can be excited as a result of interaction between the turbine-generator and either
rectifier current-control or the inverter extinction angle (voltage) control of an HYDC link. Thus, ifboth the rectifier and
the inverter stations are within the study zone, both converter
stations, de line, and the associated controls, with adequate
level of sophistication, must be represented in the system
model.

The Equivalent-pi is an accurate model for representation of a


long or medium length transmission line for the phenomena
under investigation. In many reported studies, the shunt capacitive branches of the line model are also neglected. Shunt
capacitive branches of the line model do not have any major
impact on the
system subsynchronous frequency resonant modes, but their
effect on supersynchronous oscillatory modes can be noticeable. Shunt capacitive branches, particularly in the case of
long lines, have a significant effect on the system steady-state
conditions, e.g. the magnitude of generator power angle.
Therefore, depending on the operating conditions, they may
have a noticeable impact on the dampings of low frequency
oscillatory modes.

Each arm of a six-pulse converter is modelled by an ideal


switch including series and parallel snubber circuits. The
switch represents a group of series/parallel connected diodes
or thyristor valves. The three-phase transformer model of
Section 2.2.2.3 can adequately represent converter transformer of a six-pulse HYDC converter for low frequency studies.
Connection of two six-pulse converter models with proper
transformer models constitutes a 12-pulse HYDC converter
model. The model of each pole of an HYDC converter station
is realized by assembling an adequate number of 12-pulse
converter models. If small-signal dynamics are of concern,
e.g. torsional oscillations, a bipole HYDC link can be approximated by an equivalent monopolar link. Otherwise, e.g. for
investigation of transient torques, bipolar representation is
necessary. Models of smoothing reactors and ac/dc filters are
developed by proper connections of lumped RLC elements.
Multiple -sections is the recommended model of an HYDC
line.

2 2 2 5 Series and Shunt Capacitor Banks

Series capacitors are the main cause of severe shaft torsional


oscillations and their presence in each transmission section is
accurately represented by three lumped, ideal, capacitor
banks. Similar to the shunt capacitive branches of a transmission line, shunt capacitor banks do not have any direct impact
on the shaft dynamics. However, since shunt capacitors alter
the voltage profile of the system, they may noticeable impact
on the dampings of the oscillatory modes depending on the
operating condition. Thus, representation of shunt capacitors
in the system model, particularly under heavy loading conditions, is recommended.

Block diagram of the controls of a bipole Hvdc system for


time-domain simulation is given [2.14]. Further details of the
control blocks are available in Chapter 8 of [2.15].

2 2 2 6 Shunt Reactor

Shunt reactors can have a noticeable impact on the steadystate operating conditions, e.g. voltage profile, which can impact the dampings of the low frequency dynamics. Thus, representation of shunt reactors, particularly under light loading
conditions, is recommended.

When the inverter station is not within the Study Zone, the inverter station and the de line can be represented by an equivalent controlled voltage source, and only the rectifier station
and its controls must be modelled in details. Similarly, the
rectifier station and the de line can be modelled as an equivalent controlled current source and only the inverter station and
its control system be represented in detail, if the rectifier station is not within the Study Zone.

"Fixed Impedance" model is an adequate load representation when turbine-generator shaft dynamics are of concern.
However, if an induction motor load or a synchronous motor
load is comparable to the MVA rating of the turbine-generator
under consideration, fixed impedance representation of the load
may result in erroneous conclusions. Under such conditions, the
load is best represented by either an equivalent induction motor
or an equivalent synchronous motor.

An HYDC installation may have multiple auxiliary controls


for various purposes, e.g. damping inter-area oscillations, frequency control, and reactive power/voltage modulations. It is
recommended to represent such auxiliary controls in the system model to identify their possible adverse impacts on the
torsional oscillatory modes.

Motor loads must be represented in details for fast bus transfer


phenomenon. For these studies, parallel identical motor loads
can be lumped in an equivalent motor load.

2 2 2 9 Static VAr Compensator (SVC)

Field experience and theoretical studies indicate that possible


adverse effect of an SVC on the shaft torsional dynamics are
not as severe when compared with that of an HYDC converter

2 2 2 8 HYDC Converter Station

3-6

station [2.16]. However SVCs have been recognized as effective countermeasures for shaft torsional dynamics. A conventional SVC is composed of thyristor-switched capacitors
(TSCs) and thyristor-controlled reactors (TCRs) [2.17]. During small-signal dynamics, e.g. torsional oscillations, an SVC
can be approximated as fixed capacitors (FCs) and TCRs.thyristor valves in each arm of either the TCR or the TSC are
modelled as two equivalent ideal switches including the parallel snubber branch. The three-phase transformer model of
Section 2.2.2.3 can adequately represent an SVC transformer
for low frequency studies. Controlled reactor, switched capacitor and the SVC filter components are represented in the
time-domain simulation model by proper combinations of
lumped RLC elements. Chapter 9 of [2.15] and reference
[2.18] provide details of the controls of an SVC for time-domain simulation. Similar to an HVDC converter station, an
SVC may be equipped with auxiliary controls, e.g. supplemental SSR damping control. Thus, all the closed-loop controls must be represented in the simulation model to attain a
realistic time-response of an SVC.

nomenon of torsional oscillations. Numerous study results,


using the benchmark model, have been published in the IEEE
PES Transactions [2.1, 2.2, 2.3, 2.4, 2.5].

Time-domain simulation and frequency-domain eigen analysis are widely used as complementary approaches for reciprocal verification of torsional studies.

2.3.2 Transient Torques


The first and the second IEEE benchmark models for SmallSignal torsional studies introduced in Section 2.3.1 also have
been extensively used for transient torque studies. Due to the
nonlinear nature of large-signal torsional oscillations, digital
time-domain simulation is the only approach to investigate
the phenomenon. There are no measurement results regarding
transient torques in the widely circulated technical literature.
Thus, simulation results cannot be readily compared with actual field tests. At this stage, a general verification rule is to
ensure that the simulation results satisfy the well understood
behavioral patterns and immediately after switching incidents.

2 2 2 10 Generator Controls
Conventional generator controls, i.e. automatic voltage regulator (AVR), power system stabilizer (PSS), and governor
system generally do not have major (positive or negative) effects on turbine-generator shaft dynamics. Although there are
reports oftorsional excitation as a result ofPSSs and electronically controlled governors, the adverse effect can be prevented by introducing filters in the control circuitry. Thus, the
dynamics of excitation and governor systems are neglected,
and the input mechanical power and the generator field voltage are considered as constant values for time-domain investigation of shaft dynamics. For those particular cases where
either AVR, PSS or governor may aggravate torsional oscillations [2.1,2.2,2.3,2.4,2.5], they can be represented by their
linearized models in the system model.

2.3.3 Turbine-Blade Vibrations


The radial power system of [2.6] is recommended as the test
system. The system is composed of a multi-mass tubine-generator which is connected to an infinite bus through two parallellines. The system can be used to study blade vibrations
of low-pressure turbine sections. It should be noted that in
contrast to the shaft torsional oscillations (either small-signal
or large-signal), the blade vibrations are not readily quantifiable from time-domain responses. Thus, a frequency spectrum analysis, e.g. FFT should be conducted on the time
response to obtain the relative amplitudes and frequencies of
the blade dominant oscillatory modes.

2 2 2 11 Protection System
A qualitative verification of the simulation results can be obtained based on the comparison ofthe frequencies of the blade
vibrations, deduced from FFT of the simulation results, with
those provided by the turbine manufacturer.

Overvoltage protection system of series capacitor can have a


significant impact on large-signal torsional torques and turbine-blade vibrations following network transients. Thus, for
the simulation of these two phenomena, the series capacitor
overvoltage protection scheme including ZnO varistor and
the associated bypass logic and power circuitry must be represented in the system model.

2.3.4 Bus-Transfer
The simplified system introduced in [2.7], is recommended as
the test system for bus transfer studies. Typical motor load
data for simulation studies are available in [2.19].

2.3 TESTSYSTEMS
2.3.1 Torsional Oscillations
The IEEE Working Group on Subsynchronous Resonance has
introduced two benchmark models for time-domain simulation of turbogenerator torsional oscillations [2.12, 2.13]. The
benchmark models have been extensively used for time-domain as well as frequency-domain investigation of the phe-

Ideally, validating a model of a fast bus transfer operation


should include validating the individual motor models and the
circuit breakers operating times. Individual motor models can
be validated by simulating motor starting and running conditions and comparison of other simulation results to data re3-7

corded during an actual motor instantaneous current, power,


apparent power (VA), and speed. However, since a typical
bus transfermodelmay include 15or moremotors, it maynot
be practical to validate individual motormodels.

enonis thatof multiple SVCs[3.1]. The problemof controller


interactions attracts more attention as the number of power
electronic baseddevices increases.
3.2 STUDYZONE

When two or more interacting controls are identified, the


study zone encompasses those system components which
must be represented with adequate details to investigate the
interaction phenomenon. Sincethe frequencies of interestare
in the subsynchronous frequency range,the studyzone is usually identified based on the criteriaused for the study zone of
torsional oscillations, Section2.2.1.

To establish the dead time and a range of the expected accuracy,it is recommended to performa fastbus transfertestwith
a few motorsconnected and simulating the test conditions using motor models based on the manufacturer supplied data.
Since measuring the transient variations in the motor shaft
torque is a complextask, it is suggested to monitor, simulate
and compare the following parameters:

3.3 DEVICEMODELS

businstantaneous voltage

3.3.1 Generator ElectricalSystem

individual motors instantaneous currents

If a turbine-generator controls system, i.e. governor system,


AVR, PSS, and its torsional mechanical modes do not participate in the interaction phenomenon, then the generatorelectrical system can be modelled as an ideal, fixed-frequency,
three-phase, voltage sourcebehind a three-phase inductance.
Otherwise, the second-order model or the third-order model
for Section2.2.2.1 shouldbe used.

total instantaneous currents through the alternate source circuit


breaker
individual motors instantaneous power andapparent power
motor speed
errors can then be determined by comparison of the test data
with simulation results. A statistical measure of the expected
modelaccuracy may be basedon the methodof the rootof the
sumof the squaresof the individual errors(RSS). The expected error in the actual bus transferanalysis wouldbe less than
the RSS of the errors deriveddue to the largernumberof motors included. References [2.7,2.8, 2.9]provide sometest results which can be used as general guidelines to verify the
pattern of behaviour of the system variables due to the bus
transferphenomenon.

3.3.2 Turbine-Generator Mechanical System

Whenthe generator electrical systemis represented either by


the second-order model or the third-order model, the shaft
system should be represented by the mass-spring-dashpot
modelof Section2.2.2.2. Otherwise, the shaft dynamics and
consequently its oscillatory modes can be ignored.
3.3.3Power Transformer

Appendix A provides further information regarding fast bustransferand typical time-domain simulation results.
3. CONTROL SYSTEM INTERACTIONS
3.1 DEFINITION

Closed-loop controls associated with various power system


apparatus, e.g. SVC controls, HYDC converter controls, controls of adjustable seriescapacitors, generator automatic voltage regulators (AVRs), and generator power system
stabilizers (PSSs) have natural oscillatory modes at frequencies in the subsynchronous frequency range of 1 to 35 Hz.
Depending uponthe "electricaldistance" betweenthe apparatus, the associated closed-loop controls can interact and result
in either unsatisfactory operation of the device(s), sustained
oscillations, or even small-signal instability. Another type of
controller interactions is the interaction between a closedloop control system and a natural oscillatory mode of an apparatus. One practicalcase of controller interaction phenom-

Whena generator is represented by a voltagesourcebehindan


inductance, the generator step-up transformer is represented
by a seriesRL branchin each phase. Otherwise, the low-frequency transformer model of Section 2.2.2.3 should be used
to represent the transformer in the overall system model. In
general, the low-frequency transformer model is an adequate
representation of a power transformer for investigation of
controller interaction phenomenon. The harmonics generated
as a result of transformer saturation have much higher frequencies than those of controller interactions. Thus the saturation does not have any major role in the controller
interaction phenomenon.Transmission Line
Per-phase equivalent- modelis an adequate representation of
a line for investigation of the phenomenon of controlinteractions.
3.3.4Series and Shunt Capacitor Banks

3-8

not within the Study Zone.

Presence of series capacitors in a transmission line can alter


the level of controller interactions or even excite the interaction mode(s) [3.2]. Impacts of parallel (shunt) capacitors on
the controllerinteractionsis significantly less than that of a series capacitor. Both series and shunt capacitors can be adequately represented by three-phase lumped capacitor banks
for investigationof controller interactions.

3.3.8 Static VAR Compensator (SVC)


A conventional SVC, which is composed of thyristor-controlled reactor (TCR) and fixed capacitor (FC), can interact
with an HYDC converterstation or other SVCs through their
closed-loop controls and excite the phenomenonof controller
interaction. An SVC model for control interaction studies
should accurately representthe SVC and its control system in
the frequency range of 5 to about 45 Hz. The steady-state
continuous controlsincludingall the auxiliaryloops, e.g. SVC
voltage controland SSR damping control, must be represented in the simulationmodel. Further details of an SVC smallsignal model are availablein Section 4.3.9.

3.3.5 Shunt Reactor


Similarto shunt capacitors, fixed, shunt inductors do not have
a major impact on controllerinteractions. Nevertheless, shunt
reactorsare adequatelyrepresentedby three-phase lumpedinductancesfor investigationof controllerinteractions.
3.3.6 Loads

3.3.9 GeneratorControls
"Fixed Impedance" modelof loads withinthe studyzoneprovides accurate representation of the loads for investigation of
controllerinteractionphenomenon. Very large load areas can
also be representedby an "infinite bus" with proper phase angle to draw the requiredpower at the fundamental frequency.
The impacts of various load models on the phenomenon of
controller interactions have been neither adequately investigated nor reported in the literature.

Conventional synchronous generator controls, i.e. governor


system, AVR, and PSS are designed to perform corresponding tasks at very low frequencies (0.1 to 2.5 Hz), and are not
the prime cause of controllerinteractions. Thus the dynamics
of the generatorcontrols often can be neglected for the investigation of controller interaction phenomenon. However, if
their presence in the overall system model is required, their
conventional low-frequency, linearized models would suffice.

3.3.7 HVDC ConverterStation


Rectifier or inverter firing angle controls can interact with
other systemcontrollers, e.g. SVC controls,and excitecontrol
interactionphenomenon. Contributionof an HYDC converter stationto the controllerinteractionphenomenon is primarily as a result of the natural oscillatory modes of its control
loop(s) and not due to the harmonics generated by the valve
switchings. If both inverter and rectifier are within the study
zone, both converter stations, the connecting de link, and all
the associatedcontrolsmust be representedin the study model. Furtherdetails on representation of each 12-pulse converter are given in Section 4.3.8.

All the steady-state continuouscontrolsof rectifierand inverter stations, e.g. DC current control, DC voltage control, AC
voltage control or reactive power control,real power control,
and frequency control must be representedin the model. The
control model must adequately represent firing and synchronization schemesused for the convertervalues.

3.3.10HarmonicFilters

Harmonic filters of SVCs are adequately represented by


lumpedRLC circuits. Similarly, ac side and de side harmonic
filters ofHYDC converterstations are representedby lumped
RLC circuits.
3.4 TEST SYSTEM
Fig.3.1 showsthe recommended test system for the investigation of controller interactions [3.1] of multiple SVCs. Depending upon the operating conditions and parameters, the
voltage control loops of the SVCs can interact and exhibit
small-signal instability. Inclusion of control limits in the
model is not necessary since the control interaction constitutes a linearphenomenonand nonlinearities are not involved.
icomp in Fig. 3.1 is the total current of each TCR and the associated capacitor bank. The systems data and initial conditions are given in [3.3, 3.4].

When the inverterstation is not withinthe StudyZone, the inverter station and the dc line can be representedby an equivalent controlled voltage source, and only the rectifier station
and its controls be modelled in detail. Similarly, the rectifier
station and the de line can be modelled as an equivalentcontrolled current sourceand only the inverterstationand its control system be represented in details, if the rectifier station is
3-9

4.2 STUDYZONE
230kV

250km

220km

68kV

180km

Thosesystemapparatus whicheithergenerateor interactwith


the frequencies of interestmustbe representedin adequatedetails,andthey identifythe studyzone. Also transmission lines
which connect the apparatus within the study zone must be
represented with adequate accuracyin the frequency range of
interest in the system model. The remainder of the system
which neither generates nor interacts with the harmonics can
be simplified and represented by its frequency dependent
equivalent model [4.3].

'I

(b)

4.3 DEVICE MODEL


Fig. 3.1. Testsystemsfor investigation of controller interaction phenomena

4.3.1 Generator Electrical Model

3.5 VERIFICATION OF SIMULATION RESULTS

Rotating machines withinthe study zone do not-contribute to


the harmonic interaction phenomenon and can be represented
by equivalent voltagesourcesbehind fixed RL elements.

Small-signal controller interactions also can be investigated


based on the linearizedmodel of the systemunder investigation, using eigen analysis approaches [3.6, 3.7. 3.8]. Both
time-domain simulation and the eigen analysis of controller
interactions are conducted for qualitative comparison of the
results and their mutual verifications.

4. HARMONIC INTERACTION AND RESONANCE


4.1 DEFINITION

Operation of power electronic converters, e.g. an HVDCconverter station,is characterized by generation of currentand!or
voltageharmonics. These harmonics are classified as characteristic and noncharacteristic harmonics. In contrastto characteristic harmonics, amplitudes and orders of
noncharacteristic harmonics cannot be accurately predicted
by conventional analytical techniques, e.g. Fourier analysis.
Time-domain simulation methods provide an alternative approach for the analysis of noncharacteristic harmonics. References [4.1] and [4.2] provide a comprehensive description
of the physicalphenomena resultingin harmonic interactions.

The main concerns with the presenceof noncharacteristic harmonics are (1) harmonic interactions and/or resonance [4.1],
and (2) the interference phenomenon [4.2].

Radio and telephone interference as a result of dc side harmonics of HYDC converters is a well known phenomenon.
Also, secondand third harmonic instability of ac systemsdue
to harmonic modulation characteristic of HYDC converter
has been encountered in the existinginstallations [4.1].

4.3.2 Turbine-Generator Mechanical System

dynamics do not play any noticeable role in the harmonic interaction phenomenon. Thus, the shaft model can be readily
discarded from the overallsystem model.
4.3.3 Power Transformer

Both stray capacitances and magnetic saturation characteristics of powertransformers withinthe study zone can have significant impact on power system harmonics. The magnetic
saturation characteristic has a deterministic impacton the second harmonic instability and can be fairly represented by the
no-load V-I characteristic in the magnetization branch of the
transformer. The winding stray capacitances to the tank have
a noticeable effecton the interference phenomenon[4.2]. The
stray capacitance can be adequately modelled by a single capacitance from the windingterminal to the ground [4.2].
4.3.4 Transmission Lines

Transmission lines withinthe study zone are best represented


as distributed parameterlines including parameter frequency
dependency. However, if the frequency range of interestdoes
not cover high frequencies (more than 300 Hz), each transmissionline can be represented by multiple sections.
4.3.5 Series and Shunt Capacitor Banks

Seriesand shunt capacitors have deterministic impactson series and parallelresonantfrequencies of the system and must
be represented in the overallsystemmodel for harmonicstudies. Both series and shunt capacitors are adequately representedby lumpedthree-phase capacitorbanks.

3-10

capacitors, Fig. 4.1.


Magnetic saturation characteristics of convertertransformers must be includedin the model [4.4].

4.3.6 Shunt Reactor

Similarto series and shunt capacitors, shunt reactors also influence the system natural resonant frequencies and must be
represented in the systemmodel. A shuntreactoris adequately represented by a three-phase lumpedreactorbank.
4.3.7 Loads

"Fixed Impedance" model is a valid representation for loads


withinthe studyzone,unlessthe load is knownto haveparticular resonant frequency or generates particular hannonic(s)
whichcan affect the harmonic phenomenon of interest.
4.3.8 HVDC Converter Station
The HVDe converter station is one of the major
sources for generation of harmonics which cause interference
and/or instability of electrical power networks [4.1]. The
required model of an HVDe converter station for studying interference and harmonic interaction phenomena is the same as the
model described in Section 3.3.8.

cs

4.3.9 Static VAR Compensator (SVC)

StaticVAR compensators have not been reported as a source


of interference phenomenon and harmonic interactions.
However, in the vicinity of HVDC converter stations and
FACTS devices, a static VAR compensator can aggravate
harmonic related issues [4.4]. The required SVC model for
time-domain investigation of harmonic problems is the same
as the modeldescribed in Section3.3.9,exceptfor the following differences:
Snubber circuits of each valve chain must be includedin
the simulation model.
The model of valve firing circuitry must be capable of generating exact firing instants.

Operating point and parametervalues of a SVC can readily


influence series/parallel resonant frequencies of a network
andconsequently tunethe systemfor resonantconditions, e.g.
secondharmonic resonance [4.4]. The above model can also
be used for this class of resonant conditions which normally
occur at noncharacteristic harmonics generated by power
electronic circuits.
4.3.10 Generator Control

Automatic voltage regulator, power system stabilizer, and


governor system do not influence harmonic related problem.
Thus,their modelcan be excluded from the systemmodel for
time-domain harmonic studies.
4.3.11 Harmonic Filters

SVC and HVDC harmonic filters must be modelled as describedin Section3.3.11.


Neutral Filter

4.4 TEST SYSTEM

Fig.4.1. Lumped equivalent of the stray capacitances ofa 12-pulse HVDe


converter and the convertertransformers

Exactparameters of the snubbercircuitsof each valve


chainshouldbe included in the model[4.2]. It shouldbe
noted that in some transients programs, the exactparameters of snubbercircuits cannotbe used. Unrealistic
snubbercircuits are required by theseprograms to avoid
numerical problems.

The HVDC-AC system of Fig. 4.2 is proposedas the test system for the investigation of harmonic interactions phenomena
and the secondharmonic instability issues.

The model used for the valve firing circuitry should generate actual firing instants. Otherwise, the amplitudes and
orders of noncharacteristic harmonics will be noticeably
distorted as a result of improper firing instants [4.4].

Stray capacitances of the converter transformers, valve


structure, and smoothing reactormust be adequately representedin the systemmodel [4.2]. The impactof stray
capacitances can be represented by a set of lumped
3-11

Fig. 4.2. HVDC-AC test systems for time-domain simulation of harmonic


interaction phenomena, and the second harmonic instability

The HVDC link is a 450-kV, 936-km, 2000-MW, 12-pulse,


bipole configuration. Each pole is equippedwith ac side and
de side filters. The inverterneutralis equippedwith a neutral
filter. The rectifierneutralis solidlygrounded closeto the station. Parameters and controlsystemof the ManitobaHydrois
Bipole-2 HVDCsystem[4.5,4.6] are adoptedfor the test system of Fig. 4.2.

Therectifierac system, Fig. 4.2, is composed of an equivalent


26-kV source which is connected to the rectifier ac bus
through a 26/235-kV transformer and a short 230-kV line.
The effective short circuitratio (ESCR) of the rectifierac system is 3.6.

modelling approach of [4.15] are reported in [4.14]. References [4.16,4.17,4.18] provide a comprehensive and fundamental description of the harmonic interactionphenomenon.
However, there are not that many measurements and investigationof the harmonic interaction phenomenon to establisha
method for verification of time-domain simulation studies.
Reference [4.19] introduces an alternative approachbased on
frequency scanning methodfor identification of harmonic instabilities in HVDCsystems. This approachmay be used for
qualitative verification of digital time-domain simulationapproach.

5. FERRORESONANCE
The inverterac system consists of a 230-kV ac source which
is connectedto the inverterstationthrougha 500-kV, 832-km
transmission system. The transmission line is equipped with
240/525-kV y - Y connectedtransformer at the source side.
The ac line is divided in three sections, Fig. 4.2. Each intermediate station is equipped with a 400 MVA capacitorbank
for voltageprofileimprovement. Loads#1, #2, and #3 arerated at 920-MVA, 400-MVA and 360-MVA respectively. The
inverter station is also equipped with an SVC which can adjust its reactive power from 180-MVAR inductive to 510MVAR capacitive. Electrical parameters of the inverter ac
systemare givenin [4.7]. The ESCR of the inverterac side is
2.2.

References [4.8] and [4.9] provide various HVDC/ac benchmarkmodelsthat also can be used for the analyses of harmonic interactions and resonance phenomena. The first HVDC
benchmark model [4.8] proposed by CIGREWG 14-02 also
exhibits second harmonic resonance and can be adopted for
investigation of harmonic instabilityphenomenon. This system is less complicated as compared with that of Fig. 4.2.
Reference [4.10]providesa very simple circuitconfiguration
which exhibits instability due to switching characteristic of
thyristor-controlled reactor (TCR). A set of time-domain
simulations results of the test systems of Fig. 4.2 is given in
[4.4].
4.5 VERIFICATION OF SIMULATION RESULTS

There are several technical papers which deal with analysis


and measurement of noncharacteristic harmonics of HVDC
converter stations [4.2,4.11,4.12,4.13]. The primary concern in these papers is the de side triplen harmonics which
cause interference and not the second harmonic instability
problem. Reference[4.15]providesa modelling approachfor
representation of a six-pulseconverterwithrespectto the second harmonic for eigen analysis. Such eigen analysis approach can be used as an alternative technique for validation
of simulation results. Eigen analysis studies based on the

In this section, ferroresonance is introduced and a general


modeling approach is given. An overview of available literature and contributors to this area is provided. A simple case
of ferroresonance in a single phase transformer is used to illustrate this "phenomenon". Three phase transformer core
structures are discussed. Ferroresonance in three phase
grounded-wye distribution systemsis describedand illustrated with waveform data obtainedfrom laboratorysimulations.
Representation of the study zone is discussed, modelingtechniques are presented, and implementation suggestions are
made. Three case studied are presented. Transformerrepresentation is criticalto performing a valid simulation. The direction of ongoing research is discussed, and the reader is
advisedto monitor the literature for ongoing rapid improvements in transformer modelingtechniques.

5.1 INTRODUCTION TO FERRORESONANCE

Research involving ferroresonance in transformers has been


conducted over the last 80 years. The word ferroresonance
first appears in the literaturein 1920[5.7],althoughpapers on
resonance in transformers appeared as early as 1907 [5.4].
Practical interest was generated in the 1930s when it was
shown that use of series capacitors for voltage regulation
caused ferroresonance in distribution systems [5.9], resulting
in damaging overvoltages.
The firstanalytical workwas doneby Rudenberg in the 1940s
[5.36]. More exacting and detailed work was done later by
Hayashi in the 1950s [5.17]. Subsequent research has been
divided into two main areas: improving the models used to
predict the behavior of the transformers, and studying ferroresonance involving transformers installed in power systems.

3-12

An understanding of the nonlinear parameters describing a


transformer core is prerequisite to dealing with ferroresonance. Swift [5.47] and Jiles [5.20] have provided insight into
transformer core behavior and the separation ofhysteresis and
eddy current losses. Frame [5.15] and others have developed
piecewise-linear methods of modeling the nonlinearities in
saturable inductances.

R~2

~
+

V,_",

Hopkinson [5.19] performed system tests and simulations on


the effect of different switching strategies on the initiation of
ferroresonance in three phase systems. Smith [5.38] categorized the modes of ferroresonance in one type of three phase
distribution transformer based on the magnitude and appearance of the voltage waveforms. Arturi [5.2] and Mork [5.29]
have demonstrated the use of duality transformations to obtain transformer equivalent circuits . Mork [5.27] and Kieny
[5.21] have shown that the theories and experimental techniques of nonlinear dynamics and chaotic systems can be applied to better understand ferroresonance and limitations
inherent in modeling a nonlinear system. Developments in
the near future are expected to be in the areas of developing
improved transformer models and applying nonlinear dynamics to the simulation of ferroresonance.

5.2 FERRORESONANCE IN A SINGLEPHASE TRANSFORMER


In simple terms, ferroresonance is a series "resonance" involving nonlinear inductance and capacitances. It typically
involves the saturable magnetizing inductance of a transformer and a capacitive distribution cable or transmission line connected to the transformer. Its occurrence is more likely in the
absence of adequate damping . A simple case of ferroresonance is presented here as an illustration.
When rated voltage is applied to an unloaded single phase
transformer, only a very small excitation current flows (Fig.
5.1). In this case, the 120-volt winding of a 120-240 volt 1.5
kVA dry-type transformer is energized , resulting in an exciting current, whose peak amplitude is 0.05 per unit. Referring
to the equivalent circuit shown, it is seen that this current consists oftwo components: the magnetizing current and the core
loss current. The magnetizing current, which flows through
the nonlinear magnetizing inductance LM, is required to induce a voltage in the secondary winding of the transformer.
The core loss current, flowing through RC, makes up the eddy
current losses and hysteresis losses in the transformer's steel
core.

R",.

LU

l~l

lEX

~ll

xc

IDEAL

HO

TRANSFOIUlER

1.0
0 .75

0 .5
0 .25

0 .0

>

-0 .2 5
-0.5
-0.7 5

III

Q.

::;

rt.
rt.

:l
0

t=

TIME

Fig. 5.1. Unloaded singlephasetransformer withratedvoltage applied.Solid


waveform is appliedvoltage; dashedwaveform is exciting current

Although usually assumed linear, RC is dependent on voltage


and frequency. The excitation current contains high order odd
harmonics, due to transformer core saturation. RW and LL
are the winding resistance and winding leakage inductance,
respectively . They are assumed to be linear parameters. Their
magnitudes are relatively small compared to LM and RC and
so are usually ignored in no-load situations [5.3,5.24] .
If a capacitor is placed between the voltage source and the unloaded transformer, ferroresonance may occur (Fig. 5.2). An
extremely large exciting current (1.92 per unit peak) is drawn
and the voltage induced on the secondary may be much larger
than rated (1.44 per unit peak) . The high current here is due
to resonance between CS and LM; ferroresonance in most
practical situations results in smaller exciting currents . Any
operating "modes" which result in a significantly distorted
transformer (inductor) voltage waveform are typically referred to as ferroresonance, although the implication of resonance in a classical sense is arguably a misnomer. Even
though the "resonance" occurring does involve a capacitance
and an inductance, there is no defmite resonant frequency,
more than one response is possible for the same set of parameters, and gradual drifts or transients may cause the response
to jump from one steady-state response to another.
High-order odd harmonics are characteristic of the waveforms, whose shapes might be conceptually explained in
terms of the effective natural frequency 1 LMCS as LM goes
in and out of saturation. Steep slopes (fast changes) occur
when LM is saturated, and flat slopes occur when LM is operating in its linear unsaturated region .
Due to nonlinearity, two other ferroresonant operating modes

3-13

are possible, depending on the magnitudes of source voltage


and series capacitance. In this case, all modes are seen to produce periodic voltage waveforms on the transformersecondary [5.26,5.29]. In general, gradualchanges in source voltage
or capacitance will cause state transitions. A reversalto conditions that caused a transitionwill not reverse the transition,
due to nonlinearity ofLM [5.36]. Transientscan also trigger
transition from mode to mode.

In modem terms, these jumps are referred to as bifurcations


[16,27,29,45], and may be better understood by applying the
theory of nonlinear dynamics and chaos. A long-used intuitive explanationof thesejumps, basedon a graphical method,
is given by Rudenberg [5.36]. However, this method is not a
good analyticaltool since it is based only on the fundamental
frequency and neglects harmonics.
Damping added to the circuit will attenuate the ferroresonant voltage and current. Some damping is always
present in the form of resistive source impedance, transformer
losses, and also corona losses in high voltage systems, but most
damping is due to the loadapplied to the secondary of the transformer.

IiI

..f:

Ferroresonance can leadto heatingof transformer, due to high


peak currentsand high core fluxes. High temperatures inside
the transformermay weakenthe insulationand cause a failure
under electrical stresses. In EHV systems, ferroresonance
may result in high overvoltages during the first few cycles, resulting in an insulation coordination problem involving frequencieshigher than the operating frequency of the system.
Because of nonlinearities, analytical solution of the ferroresonant circuit must be done using time domain methods. Typically, a computer-based numerical integration method is
applied using time domain simulation programs such as the
EMTP.

5.3 MAGNETIC BEHAVIOR OF THREE PHASE TRANSFORMERS


It is incorrect to assume that a three phasetransformer
core is magnetically equivalent to three singlephasetransformers, i.e. that the three phases haveno direct magnetic coupling.
Such an assumption can leadto serious errors, especially if one
is investigating a transformer's behavior under transient or
unbalanced conditions.

'l'lUPtEX CoRE (I"ACKED OR -.oUND)

_:>r.

CDRE

roRW

(~ACKED )

~ ~~ 110

- 11:.t

"HELL

-se.e

P'OR

~ACK!lD)

Fig. 5.2. Same transformeras in Fig. 5.1, fed througha 7511F capacitance,operatingin ferroresonance. Solid waveformis terminal voltageof
transformer; dashed waveform is the current.
5-IBdOED WOUND CORE

Damping added to the circuit will attenuate the ferroresonant


voltage and current. Some damping is always present in the
form of resistive source impedance, transformer losses, and
also corona losses in high voltage systems, but most damping
is due to the load applied to the secondary of the transformer.
Therefore, a lightly-loaded or unloaded transformer fed
through a capacitive source impedance is a prime candidate
for ferroresonance.
This elementary type of ferroresonance is similar to that
which occurred in the series capacitor compensated distribution systems of the 1930s. It can also occur, from different
sources of capacitance, in today's single phase distribution
transformers and voltage instrument transformers [5.1,5.18].
It can also occur in series-compensated transmission lines.

I~

Fig. 5.3. Core configurations commonly used in three phase transformers.Only one set of windings is shown.

The only type of core that displays magnetic characteristics


similar to three single phase transformers is the triplex core.
Althoughthe cores share the same tank, they are magnetically
isolated(except for leakage fluxes). Core laminations can be
stacked or wound. Zero sequence fluxes will circulate individually in each core, and tank heating is not a problem. Under normal balanced operation, exciting currents in each
phase are identical, except for their 120 shift in phase angle.
All of the other core conftgurations provide direct flux linkages between phases via the magnetic core. Simply stated, applying a voltage to anyone phase will result in voltages being

3-14

induced in the other phases (only in the adjacent phase(s) in


the case of the five-legged wound core). Further, the degree
of saturation in each limb of the core affects the way flux
flows divide. The apparent reluctance seen by each of the
windings changes depending on the degree of saturation in
each of the limbs of the transformer core. Therefore, exciting
currents vary from phase to phase, even under balanced operation. A brief discussion of each of these core types follows:
Core-form transformers require the least amount of core material to manufacture. Laminations are stacked. Their worst
problem is that unbalanced operation results in zero sequence
fluxes which cannot circulate in the core. These zero sequence fluxes are forced through the insulation surrounding
the core and through the transformer tank. Tank steel is not
laminated like the core is, so eddy currents can heat the tank
and cause damage. Therefore, this type of core should only be
used where load currents are balanced.
The shell-form core provides a magnetic path for zero sequence flux, and is much better-suited for unbalanced operation. Laminations are stacked. There is a large base of
transformers with this type of core (about half of the installed
three phase power transformers in the US).

lines, capacitor banks, coupling capacitances between double


circuit lines or in a temporarily-ungrounded system, and voltage grading capacitors in HV circuit breakers. Other possibilities are generator surge capacitors and SVCs in long
transmission lines. Due to the multitude of transformer winding and core configurations, system connections, various
sources of capacitance, and the nonlinearities involved, the
scenarios under which ferroresonance can occur are seemingly endless [5.5].
System events that may initiate ferroresonance include single
phase switching or fusing, or loss of system grounding. The
ferroresonant circuit in all cases is an applied (or induced)
voltage connected to a capacitance in series with a transformer's magnetizing reactance.
Fig. 5.4 gives three examples offerroresonance occurring in a
network where single phase switching is used. A wye-connected capacitance is paralleled with an unloaded wye-connected transformer, The capacitance could be a capacitor
bank or the shunt capacitance ofthe lines or cables connecting
the transformer to the source. Each phase of the transformer
is represented by jXm, since ferroresonance involves only the
magnetizing reactance.

The four-legged core also provides a magnetic path for zero


sequence flux. This type of core design is not very common.
It is the only type of core whose outer phases do not exhibit
like behavior.

a}

The five-legged stacked core also provides a magnetic path


for zero sequence flux, but has a more symmetric core. This
type of core is often specified where a low-profile is desirable
for shipping or for visual appearance in urban substations.

,; v

s.

---------~-------

The five-legged wound core is made up of four concentrically-laminated cores. The unique feature ofthis core is that only
adjacent phases are directly linked via a magnetic path. Assuming no flux leakage between cores, the two outer winding
assemblies are not magnetically coupled. Tank heating is
minimized, since there are zero sequence flux paths in the
core. Because of its low cost, this type of transformer core is
widely used in distribution systems.

__L

- - - - - .. - - - -

....,

b)

,
1

8.1

-~----~------~--

The winding configuration used does not have any effect on


the transformer core model. Delta, wye, or zig-zag winding
connections are made outside of the model of the core equivalent. However, behavior of the transformer is strongly dependent on the winding configuration.

c)

5.4 FERRORESONANCE IN THREE PHASE SYSTEMS


.. -

Ferroresonance in three phase systems can involve large power transformers, distribution transformers, or instrument
transformers (VTs or CVTs). The general requirements for
ferroresonance are an applied (or induced) source voltage, a
saturable magnetizing inductance of a transformer, a capacitance, and little damping. The capacitance can be in the form
of capacitance of underground cables or long transmission

... - 4 - -

- -

- ,..,

Fig.5.4.Threeexamples offerroresonance in threephasesystems.

If one or two poles of the switch are open and if either the capacitor bank or the transformer have grounded neutrals, then
a series path through capacitance(s) and magnetizing reac-

3-15

tance(s) exists and ferroresonance is possible. Ifboth neutrals


are grounded or both are ungrounded, then no series path exists and there is no clear possibility of ferroresonance. In all
of these cases, the voltage source is the applied system voltage. Ferroresonance is possible for any ofthe core configurations of Fig. 5.3 (even for triplexed or a bank of single phase
transformers).

Depending on the type of transformer core, ferroresonance


may be possible even when there is no obvious series path
from the applied voltage through a capacitance and a magnetizing reactance. This is possible with three phase core types
which provide direct magnetic coupling between phases,
where voltages can be induced in the open phase(s) of the
transformer. To illustrate, a grounded-wye to grounded-wye
transformer typical of modem distribution systems is considered. A recent survey in the US showed that 79% of underground rural distribution systems use this configuration, so
ferroresonance problems in this type of installation are of special interest [5.23,5.25,5.40,5.41]. A simplified schematic of
such a system is shown in Fig. 5.5. The distribution line is
represented by its RLC pi equivalent, with no interphase coupling. Three phase circuit breakers and gang-operated
switches are used at the substation where distribution lines
originate, but single phase switching and interrupting devices
are used outside of the substation.

Whether ferroresonance occurs depends on the type of


switching and interrupting devices, type of transformer, the
load on the secondary of the transformer, and the length and
type of distribution line. A long underground line is much
more capacitive than a short overhead line. However, due to
nonlinearities, increased capacitance does not necessarily
mean an increased likelihood of ferroresonance. Operating
guidelines based on linear extrapolations of capacitance may
not be valid. Also, as mentioned previously, the smaller the
load on the transformer's secondary, the less the system damping is and the more likely ferroresonance will be. Therefore,
a highly capacitive line and little or no load on the transformer
are prerequisites for ferroresonance. Binary loads (either full
load or no load) such as irrigation, are essentially zero most of
the time and cannot be relied upon to damp ferroresonance.
Ferroresonance is rarely seen provided all three source phases
are energized, but may occur when one or two of the source
phases are lost while the transformer is unloaded or lightly
loaded. The loss of one or two phases can easily happen due
to clearing of single phase fusing, operation of single phase
reclosers or sectionalizers, or when energizing or deenergizing using single phase switching procedures.
If one of the three switches of Fig. 5.4 were open, only two
phases of the transformer would be energized. If the transformer is of the triplex design or is a bank of single phase
transformers, the open phase is simply deenergized and the
energized phases draw normal exciting current. (Existence of
capacitor banks or significant phase to phase capacitive coupling could still result in ferroresonance, but that possibility is
not addressed here).
However, if the transformer is of the three-, four- or fivelegged core type, a voltage is induced in the "open" phase.
This induced voltage will "backfeed" the distribution line
back to the open switch. If the shunt capacitance is significant, ferroresonance may occur. The ferroresonance that occurs involves the nonlinear magnetizing reactance of the
transformer's open phase and the shunt capacitance ofthe distribution line and/or transformer winding capacitance. It has
been shown that the ferroresonant circuit is a series combination ofthe shunt cable capacitance and the magnetizing inductance of one of the transformer's wound cores [5.23]. The
equivalent circuit for this transformer is derived later in this
paper.

]I)

Fig. 5.5. Typical distribution systemsupplyinga three phaseloadthrougha


grounded-wye to grounded-wye transformer.

Either overhead lines or underground cables connect transformers to the system. Cables have a relatively large shunt capacitance compared to overhead lines, so this type of
ferroresonance most often involves underground cables, but is
also possible due solely to transformer winding capacitance.
Three phase or single phase transformers can appear at the
end of a distribution line or at any point along the line. Three
phase transformers may have anyone ofthe several core types
discussed in the previous section.

An example of ferroresonant voltage and current waveforms


occurring under this scenario is shown in Fig. 5.6. In this
case, rated voltage was applied to X2 and X3, while Xl was
unenergized and had 9~ attached to simulate a length of underground distribution cable.
Whether in ferroresonance or not, this backfeed situation can
be dangerous, as operating personnel may assume that the
load side of the open switch is deenergized and safe to work
on, when in fact a high voltage is present. Also, it can be seen
that single phase loads connected along this backfed phase

3-16

will continue to be supplied, although with dangerously high


or low voltage levels and with poor power quality.
Therefore, use of single phase interruption and switching
practices in systems containing the five-legged core transformers is the main operating tactic responsible for initiating
ferroresonance . Replacement of all single phase switching
and interrupting devices with three phase devices would eliminate this problem, although economics discourages such
large scale upgrades. An alternate solution would be to replace all five-legged core transformers with single phase
banks or triplex designs wherever there is a small load factor.
System wide operation and design implications of this problem have been more fully addressed in prior work [5.25] .
5.5 NONLINEAR DYNAMICS AND CHAOS APPLIED
TOFERRORESONANCE

Ferroresonant circuits can be analyzed as damped nonlinear


systems driven by sinusoidal forcing function(s) [5.27]. The
nonlinear behavior of ferroresonance falls into two main categories. In the first , the response is a distorted periodic waveform , containing the fundamental and higher-order odd
harmonics of the fundamental frequency. The second type is
characterized by a nonperiodic, or chaotic, response. In both
cases the response's power spectrum contains fundamental
and odd harmonic frequency components. In the chaotic response, however, there are also distributed frequency harmonics and subharmonics. A good conceptual introduction to
chaos and nonlinear dynamics is given by [5.16], and a good
theoretical introduction can be found in [5.45] .
At least 2 different periodic responses are possible for
a single phase transformer [5.26], similar to that ofFig.5.1. Ferroresonance in the above three phase five-legged core distribution transformer can be periodic or nonperiodic. "Lower energy
modes" [5.1] (involving relatively low energy oscillations
between the inductance and capacitance, similar to the waveforms shown in Fig. 5.5) produce periodic voltages on the secondary. Some of the periodic modes of ferroresonance may
contain subharmonics, but still have strong power frequency
components, but take longer than one fundamental cycle to
repeat. This occurs more typically for very large values of C.

Fig. 5.6. Measurement offerroresonance in a three phase grounded-wye to


grounded-wye five-leggedcore transformer. Voltage waveform is solid;current waveform is dashed.

The "higher energy modes" [5.1] offerroresonance involving


relatively large capacitances and little damping can produce a
nonperiodic voltage on the open phase(s). These voltage
waveforms can be quite similar to those ofDuffmg's equation
[5.45] , which describes a nonlinear forced oscillator commonly used to illustrate the behaviors of a nonlinear dynamical
system. Transitions between periodic and nonperiodic modes
occur due to gradual changes in circuit parameters or to transients. And as with Duffing's equation, initial conditions determine the mode that operation stabilizes in after the
transients die down.
The recognition that ferroresonance is a nonlinear and sometimes chaotic process opens up many possibilities. The newly-developed techniques for analysis of nonlinear dynamical
systems and chaos are being evaluated for use with ferroresonance [5.27,5.21]. Use of geometric graphical methods like
phase plane projections and PoincarE sections can be applied
to obtain a better understanding of ferroresonance .

5.6 MODELLING AND ANALYSIS OF FERRORESONANCE


5.6.1 Overview
Ferroresonance has never been well-understood. Therefore,
there is a great deal of misinformation on ferroresonance in
the literature. A good example of this concerns the application of grounded-wye to grounded-wye five-legged core distribution transformers. As recently as 1989, specification of
this type of transformer was recommended to eliminate or
minimize the possibility offerroresonance [5.14,5.35] . This
misinformation is gradually being corrected [5.25 ,5.32], but
engineers must be cautious and continue to update themselves.
Efforts in past years seem focused on refining equivalent circuit models for transformers and performing simulations using a transient circuit analysis program such as EMTP.
Although these programs use fairly robust methods ofnumerical integration, such as the trapezoidal rule , results are only
as good as the models used (and the initial conditions if the
onset offerroresonance is a concern). Simulation results have
a great sensitivity to the model used and errors in nonlinear
model parameters. Unfortunately, determining the model's
nonlinear parameters is probably the biggest modeling difficulty. Three phase transformer modeling has not progressed
as far as single phase modeling. A different model is required
for each type of core, and a different means of determining the
model parameters.
Ideally, use of a correct transformer model would allow an engineer to simulate situations where ferroresonance is likely.
Simulation results could then be used to avoid this problem
when designing a distribution system. Difficulties in determining an adequate model and in simulating every possible

3-17

combination of initialconditionandtransientmakeprediction
less than certain.
5.6.2 The Study Zone

Parts of the system that must be simulatedare the source impedance, the transmission or distribution line(s), the transformer, and any capacitance not already included. Source
representation is not generally critical. Unlessthe sourcecontainsnonlinearities, it is sufficientto use the steady-state thevenin impedance and open-circuit voltage. The distribution
line or transmission line can be assumed to be an RLC coupled pi-equivalent, cascadedfor longer lines. Shunt or series
capacitors may be represented as a standardcapacitance, paralleled with the appropriate dissipation resistance. Stray capacitance may also be incorporated eitherat the comers of an
open-circuited delta transformer winding or midway along
each winding. Other sources of capacitance are transformer
bushings and interwinding capacitances, and possiblybusbar
capacitances.
One of the most critical parts of any ferroresoriance study is
the transformermodel. The transformer containsthe nonlinearities, and modeling results are most sensitive to correct
representation of magnetic saturationand core loss. The rest
of this discussion focuses mainly on how the transformer
shouldbe modeled. Manyare dissatisfied with the transformer modeling capabilities in today'smodeling packages. There
has been much discussionrecently as to what improvements
can be made in modeling techniques [5.6,5.13,5.46].
5.6.3 More on Single Phase Transformer Models And
Parameters

Singlephase transformers are typicallymodeledas shown in


Fig. 5.2. This model is topologically correctonly for the case
wherethe primaryand secondarywindings are not concentricallywound. LL2 is essentially zero for concentric coils. Errors in leakage representation are not significant, however,
unless the core saturates. Obtaining the linear parameters for
this 2-winding transformer may be difficult. Short circuit
tests give total impedance (Rl + R2) + j(XI + X2). A judgement must be made as to how it is dividedbetweenthe primary and secondarywindings.
If the transformerhas three or more windings, the Rs and Xs
for the individual windings of each phase may be separated.
Sometimes one of Xs is negative, but this will not usually
causea problemin the time domaintransientsimulation. This
approach satisfactorily separates the windingresistances, but
may not correctlyaccount for mutual inductive coupling. To
solve this problem, a coupled L representation for the short
circuit inductances is recommended [5.11]. Binary short circuit (shortingtwo windingsat a time while leavingall others
open)tests for all possiblecombinations of windings must be
performedto obtain the inductance matrix. Additional developments are still needed, however, since the core equivalent

cannotbe correctlyincorporated with this representation (the


only place it can be connected is on one of the external transformerterminals).
Model performance depends mainly on the representation of
the nonlinearelements RC and LM. RC has traditionally been
modeledas a linear resistance. Such a core loss representation, if it represents the average losses at the level of excitation being simulated, may in fact yield reasonable results.
Due to eddy currentlosses and hysteresis lossesbeing nonlinear, calculation of a linear core loss resistance RC gives different values for each level of excitation. Using the value of
RC closest to rated voltage may be a good enough estimate.
Past research has shown low sensitivities to fairly large
changes in RC [5.29] for singlephase transformers, but a high
sensitivity for three-phase cores.
LM is typically represented as a piecewiselinear -i characteristic [5.22], or perhaps as a hysteretic inductance
[5.15,5.20,5.33]. The linear value ofLM (below the knee of
the curve) does not much affect the simulation results [5.8],
although great sensitivities are seen for the shape of the knee
and the fmal slope in saturation.
Factorytest data providedby the transformermanufactureris
often insufficient to obtainthe core parameters. Open circuit
tests shouldbe madefor 0.2 to 1.3pu (or higher)insteadof the
typical 0.8 to 1.14pu range. It is importantthat open circuit
testsbe performed for voltagesas high as the conditionsbeing
simulated, or the fmal -i slopeof LM must be guessed. Some
thought should be given to the requirements of test reports
when specifying new transformers.
A method proposedby Dommel [5.11,5.22] is often used to
convertthe RMSV-I opencircuitcharacteristic to the -i characteristic of LM. To successfully use this method, the first
(lowest) level of excitationmust result in sinusoidal current,
or errorswill result in the form of an S-shaped -i curve. Also,
the V-I characteristic must extend as high as the highest voltage that will be encountered in the simulation. An extension
on this method has been proposed to obtain a nonlinear v-i
representation ofRC [5.31], but the resulting flux-linked vs.
lEX loopdoesnot seemto correctlyrepresentthe core losses.
Modem low-loss transformers have comparatively large inter-winding capacitances whichcan affectthe shapeof the excitationcurve [5.47]. This can cause significant errors when
the abovemethodis being used to obtain core parameters. In
thesecases,factory testsmustbe performedto get the -i curve
beforethe coils are placed on the core. A means of removing
the capacitive component of the excitingcurrenthas also been
developed [5.29].
5.6.4 Three Phase Transformer Models And Model Parameters

For three phase transformers, it is possible to make a simplified model by connecting together three of the above single

3-18

phase models. If this is done, a triplex core configuration is


assumed (see Fig . 5.3). A delta-wye transformer of this type
is shown in Fig. 5.7. It is postulated that zero sequence (homopolar) effects are included almost entirely by the leakage
inductance of the delta windings [5.11,5.22].

pr imory : Delto

transformers. Binary short circuit tests involving all windings


of all phases must be performed. Problems can arise for RMS
short circuit data involving windings on different phases,
since the current may be nonsinusoidal. A problem also exists
with connecting the core equivalent. Three single phase core
equivalents are often attached to the windings closest to the
core, and may provide acceptable results in some cases , especially in the case of the three-legged stacked core. Questions
exist as to this method's validity, especially depending on the
type of core being analyzed. The most important question is,
however, what is the topology of the core equivalent? A
method of obtaining topologically correct models is presented
in the next section .

secondary : grounded Wye

PA

R2

L2

SA

5.6.5 Use ofDuality Transformation s to Obtain Equivalent


Circuits
P8

R2

L2

58

R2

L2

5C

PC

Fig. 5.7. Modelofa delta to wye transformerbank madeup of three single


phase transformermodels [22].

If the transformer does not have any delta windings, zero sequence effects may be included by adding a set of delta windings to the model whose total leakage impedance is equal to
the transformer's zero sequence inductance. This may work
for a three-legged core transformer that has an air path for
zero sequence flux, but is highly questionable in the case of
transformers having a saturable zero sequence flux path.
Factory three-phase excitation test reports will not provide the
information needed to get the magnetizing inductances for
this model. Note that standards require the exciting current to
be stated as the "average" value of the RMS exciting currents
of the three phases. Unless it is a triplexed core, this is meaningless, since the currents are not sinusoidal and they are not
the same in every phase . Therefore, the waveforms of the applied voltage and exciting currents in all three phase should be
given by the manufacturer for all levels of applied voltage.
The model might be improved by using a coupled inductance
matrix to model the short circuit characteristics of three phase

This method is based on the duality between magnetic and


electrical circuits. It was originally developed by Cherry
[5.10] in 1949 and SIemon [5.37] in 1953. Using duality
transformations, equivalent circuit derivations reduce to exercises in topology. These methods did not receive much attention at first, presumably since computers were not available.
Researchers have recently begun to use duality to provide
equivalent circuit models which are more topologically correct [5.2,5.29,5.30,5.34,5.39,5.42,5.44]. This approach results in models that include the effects of saturation in each
individual leg of the core, inter-phase magnetic coupling, and
leakage effects. Results are promising, and ongoing work
seems most focused on developing and improving dualitybased models .
To illustrate the method, a duality derivation used to obtain
the model for the five-legged wound core transformer [5.28]
is done here and a case study is presented later in this paper.
A section view of this type oftransformer is shown in Fig. 5.8.
The magnetic flux paths and assumed leakage flux paths are
labeled. In the equivalent magnetic circuit, windings appear
as MMF sources, leakage paths appear as linear reluctances,
and magnetic cores appear as saturable reluctances.

The next step is the duality transformation itself. Using the


symbol to denote the transformation between electrical and
magnetic circuit elements, MMF I (MMF =NI), d /dt V, and
L (L = N2/). In terms of topology, meshes and nodes in the
magnetic circuit transform into nodes and meshes respectively in the electrical circuit. The resulting equivalent circuit is
given in Fig. 5.9.
To make the model practically useful , each current source resulting from the transformation has been replaced with an ideal transformer to provide primary-to-secondary isolation and
coupling to the core, while preserving the overall primary to
secondary turns ratio. Turns ratios are chosen so that core parameters are referenced to the low voltage windings. The portion of the model inside the coupling transformers represents

3-19

the core and leakages. Winding resistance and interconnection of the windings appears external to the coupling transformers . The advantage to this is that the derived core
equivalent can be used independently of winding configuration (delta, wye, zig-zag, etc.). Winding resistance, core losses, and capacitive coupling effects are not obtained directly ,
but can be added to this topologically-correct equivalent electrical circuit.

H1

LUKAGE X1- X!

LAKAcz: Xl-la

The capacitance in this case comes from whatever "stray"


coupling capacitance exists between the delta windings and
earth. Adding a resistive burden to the VT can elim inate the
problem .

X1

LEAICACf: la-X!

Rx

X2

I/J

L[AIC

'Ill"

H3

CDI[

I~

~ ~II~ ~x

~III

X3

xc

HO

~I

...L

Fig. 5.9. Duality derived equivalent circuit with current sources replaced by
ideal coup ling transformers. Winding resistances have also been added
1/2 LlM X1X1

Fig. 5.8. Development of magnetic circuit for grounded-wye togrounded wye five-legged wound core transformer. At top, transformer core sectional
view used as a basis for duality derivation . Leakageflux paths are labeled.
Bold dividing lines mark division in corereluctances. Equivalent magnetic
circuit is shown at bottom.

Tests have been developed to determine the parameters for


this model [5.28].
5.7 CASE STUDIES
5.7.1 Case Study #1: VT Ferroresonance on Floating Systems
It is possible that parts of a power system can be operated for short times without system grounding . One common
example is the no-load energization of the wye side of a wye to
delta power transformer.

The delta side will


load or other source
voltage transformer
power transformer,

"float" with respect to earth, until some


of grounding is connected. If there is a
(VT) connected to the delta side of the
ferroresonance can occur (see figure) .

A recent problem occurring in a 50-kV network in the Hafslund area near Moss, Norway, serves as an excellent example
[5.18]. The clearing of a short circuit removed the only remaining source of grounding on the system. After the fault
was cleared, the only remaining zero sequence impedance
was due to capacitive coupling to earth. After operating in
this way for only 3 minutes , ferroresonance had destroyed 72
of the VTs used for measurement and protective relaying. All
72 of the damaged VTs were from the same manufacturer.
The VTs of two other manufacturers that were also in service
during this time were not damaged.
Fig. 5.10 shows the typical VT arrangement used in this system. The VTs have two low voltage windings. The secondary
is used for measurement and protective relaying purposes.
The burden on that winding has a very high impedance and its
effects can be ignored when considering ferroresonance. It is
the tertiary windings which are shown in Fig. 5.10. These
windings are connected in open delta and loaded with a damping resistance RO. The purpose of this damping resistance is
to damp out ferroresonance, and this design has been com-

3-20

ances were found to be very small compared to the primary


impedances of the VTs, and could be neglected. The zero
sequence impedance ZO consists almost entirely of the stray
capacitance of the floating system, and is therefore very important. Values ofZO varied from 0.6 - j219 to 0.2 - j221 ,depending where in the system. ZO therefore becomes the only system
impedance needed in the model, and the positive sequence voltage sources can be modeled as stiff sources. The core losses of
the VTs were also neglected, their values being much higher
than the damping resistance RO.

monly used for many years.

- ---t--.-.-.-.. -t------.-..I

MAX fLUX

L1111:+ AT Vr.'

&'.

-----------1---------------1-.- i

I
B.O

I----'---~__'__--'----+---'----'-___'_------I-~~.l..---~__'__--'----'

loll

I.~

Fig. 5.10. Typical VT connection in 50-kVNorwegian subtransmission system.

-.

!
i

i
i

"A~1lI iTIZNG

C&J." illiT <AMF'8)

1.1

c.n

Fig. 5.11.Comparison of the saturationcharacteristics of the three VTs.


Notethe much lowersaturationlevel of VT # 1, the ones that were damaged.

Since some of the VTs were damaged and the others weren't,
the VTs of different manufacturers obviously must have different characteristics. The problem at Hafslund therefore
forced a re-evaluation of the specification and application of
voltage transformers. EMTP was used to simulate the system
conditions that caused the VT failures. VT model parameters
were obtained from the manufacturers. Parameters are shown
in Table 2. Saturation characteristics were calculated based
on core material B-H data, core dimensions, and number of
primary turns. Data for the damaged VTs are listed as VT #1.

VA
I

+--a~--..-----------

....

VB
I

(t-+-<J~--+-----..-----B

Vc

The designed flux densities BM at rated voltage vary. As a


more uniform basis of comparison, the flux densities were
converted to flux-linked values (Fig. 5.11). Note that VT #1
will saturate out at lower levels than the other VTs, and one
might guess this to be one of the reasons these failed and the
others didn't. But this can only be confrrmed from simulation
results.

+--a~--+------+-----..--

....

Fig. 5.12.Reducedsystemequivalent, neglecting line impedances and lumping all VTsin each phase into an aggregatejXM.

Rp

Xp

XT

Nl:N3

BMAX

VT#1

32500

25000

0.010

20k:23

l.05T

VT#2

32180

30940

0.010

-36k:42

0.77T

VT#3

75880

48330

0.010

25k:29

0.83T

Table 2: Linear parameters used to model the VTs at Hafslund

Fig. 5.12 shows the reduced equivalent used in the


EMTP model. System positive and negative sequence imped-

Many simulations were run, with various combinations of


VTs and values of RO. It was found that ferroresonance occurred in most cases where RO was set to the 60 value typically used in system design. It was also seen that the high
magnetizing currents drawn by VT #1 while in ferroresonance
caused high loR losses in the windings, which thermally destroyed those VTs. If all of the VTs from manufacturer #1
were replaced with different VTs and ifRO was reduced to 10
, ferroresonance would not occur. It was therefore recommended that the failed VTs be replaced with those of either
VT #2 or VT #3. A decrease in the value of RO standardly
being used was also recommended.

3-21

5.7.2 CaseStudy #2: Ferroresonance in Distribution Systems


This case involvesthe verificationof the 75-kVAfive-legged
wound-core distribution transformermodeldeveloped earlier.
Ferroresonance was staged on the secondary windings in the
laboratory. Balanced 3-phase voltage was applied to the secondary windings, and then one or two phases of the supply
were removed and replaced with various values of shunt capacitance. Scenarios investigated were loss of one source
phase to the centeror an outer winding, and loss of two source
phases to either the two outer windingsor to the center winding and one outer winding [5.27].
Measured waveforms were then compared to EMTP simulations. The transformerequivalentcircuitused was essentially
that of Fig. 5.9. Details of model development and parameter
values are given in [5.29].
Since many ferroresonant modes are possible, bifurcation
simulations were first run. A bifurcationis essentially a jump
from one mode of ferroresonance to another. A simulation
technique was developedto very slowlyrampthe capacitance
[5.12,5.28] and recordjumps from one mode to another. Fig.
5.13 gives one bifurcation diagram for the case where a
ramped capacitance is connectedto unenergized winding Xl
and rated positive sequencevoltage is applied to X2 and X3.
Due to nonlinearities, it is importantto ramp the capacitance
both upward and downward, to ensure that as many ferroresonantmodes are discoveredas possible.

latedare very close for the periods one, two, and three. Period
five is generally correct, with slightly lower than actual peak
amplitudes predicted. The chaotic response predicted is slightly
higher than actual. Themodel useda simplistic linearresistance
to represent the core losses of each core. The model's accuracy
couldbe improved by implementing a more correct (complex)
corelossrepresentation.

5.7.3 CaseStudy #3: Ferroresonance ofAutotransformer


This case is taken from the Ontario Hydro system
where the Cataraqui 230/115-kV autotransformer T2, fedby line
X3H, was experiencing ferroresonance upon deenergization of
lineX3H and the 115-kV bus(Fig. 5.15). The deenergizing circuit breaker was also experiencing a high recovery voltage. It
wasdeduced that capacitive coupling between line X3H and the
still-energized lines X4H and X522A was driving the autotransformer into ferroresonance. Damping resistors were added to
the tertiary of T2, but it was not certain whetherthe resulting
damping was sufficient to limit the duration of ferroresonance
andtherelated recovery voltage.

600

zr400

!
x~

200

II)

-200

If>....i.j~erroresonance:
\

.~

r-;

-...,..

/ t \

.. 1

.....
. ...

..... ..

~":

("' i..

....

> 400

Laboratory
Simulated

22.5uF Connected Xl-XO I

r-,

! ..
. ~J
'c........

I'............1....

['h,

L.

RJ.: \

.:

._-_.: ~

! \\~

-600

Using the bifurcation diagram as a road map, ferroresonance


for capacitances of 5~F, lO~F, 22.5~F, 14.6~F, and 18 ~F
was simulated. This corresponds to waveforms of periods 1,
2, 3, 5, and chaotic (nonperiodic). "Period 3" simply means
that the waveform takes three periods of the forcing function
to repeat -- it contains 1/3harmonics.

234
60-Hz Periods

Fig. 5.14. Period3 ferroresonance, 22.51lF connectedXI

X4H
X3H

hl---6owa""":":,~-:---+--:"=",""",,-++-,,,,
14.26 ml.

.. ....-- 5.15 mi..------..

TO HAWTHORNE SOO TS

X2H

F'E "RROR' E ~O'"ANCt X f.:. J


Bur - )

~ 38uF

LENNOX 230

:.

........................

KINGSTON y .

z:

,!,

.
"0
X"
~

~ :> -288 .8

::>

:i
5.8

1B .8

, "'

15.8

GAROINER TS

........ . "" ~iii


. .

CATARA Q UI I S

HINCHINeROOKE TS

Fig. 5.15. OntarioHydro230-kVsystem. Ferroresonance involvingline


X3Hand connectedtransformerat Cataraqui TransformerStation.

. ~~:~~..

28 .8

CAPACITANCE X I- H (uF)

Fig. 5.14. Samplebifurcationdiagram. Shunt capacitanceon XI is ramped


from 0 to 30 IlF. Blurredareas correspondto chaos.

Fig. 5.14 shows the result of one of the EMTP simulations and compares it to the actual measurements. The model
correctly predicts the existence of all modes of ferroresonance at
the correct values of capacitance. The actual waveforms simu-

SeveralEMTP simulations were run, with Y-connectedresistive loads of zero, 133kW/phase, and 266 kW/phase attached
to the tertiary ofT2. In each case, the 115-kVbreaker ofT2
was assumed to open last. Two double-circuit 230-kV lines,
an existing500-kVline, and a future 500-kVline were included in the corridor, resulting in an 18-phase coupled-circuit
transmission equivalent (Fig. 5.16).

3-22

Fig. 5.17 shows the circuit breaker recovery voltage


for one of the cases.
It is interesting to note that a I33-kW/phase load did an
effective job of damping ferroresonance in T2, but resulted in a
higher recovery voltage than no damping at all. The circuit
breaker was marginally able to handle the recovery voltage
when the load was doubled to 267 kW/phase . Simulations were
also performed for deenergization ofTl, with similar but less
severe behaviors noted. Recommendations were made to add
267 kW/phase loads to both transformers, and add surge arresters to the high and low voltage terminals of both transformers .

!
2.oE+S :..

.. ......

'

.1

............. j

1.oE+S

MIV\~

-ine-s

...

-2.oE+S
-3.oE+S
-4.oE+S

1- .........

O.os

CATARAQJI12 FERRORESONANCE I,
EXTERNAL DAMPING = 133 k!N I phas eJ

--j

...:

...:

v.y...... ..r~ ~~~~~


..
~

...:
~ 402kV peak

'1'
:

zoonms

300.oms

.:
...;

~I ii ..;
100.oms

400.om,

liME

Fig. 5.17. Cataraqui(T2) Autotransformer Ferroresonance. HV terminal


voltageon PhaseC is 2.0 per unit, with 133 kW/phase of damping.

5.8 RECOMMENDATIONS
Is seen that many different types of ferroresonance can and
do occur. Because of the nonlinear nature of ferroresonance,
it is difficult to predict if and where it might next occur. The
power system engineer should be aware, however, that it is
possible for lightly-loaded transformers operating in the presence of source or shunt capacitance to experience ferroresonance. Capacitance can be present in the form of cables, series
or shunt capacitor banks, or even stray capacitances in inadequately-grounded portions of the system.

Fig. 5.16. Sequenceof development of the transmission right-of-way

It is interesting to note that a I 33-kW/phase load did an


effective job of damping ferroresonance in T2, but resulted in a
higher recovery voltage than no damping at all. The circuit
breaker was marginally able to handle the recovery voltage
when the load was doubled to 267 kW/phase. Simulations were
also performed for deenergization ofTl, with similar but less
severe behaviors noted . Recommendations were made to add
267 kW/phase loads to both transformers, and add surge arresters to the high and low voltage terminals of both transformers .

Transient simulations are helpful in confirming or predicting the likelihood of ferroresonance, but only if a correct model is used. Per phase simulations of three phase systems will
not give correct results, due to various possible transformer
core configurations and winding connections. A complete
three phase model must be used. Therefore, the key to transient modeling is use of the proper transformer model. Development and use of acceptable transformer models should be a
priority task.
The development of improved topologically correct models is
a significant advancement, but model performance still depends on improving the way in which the cores are represented. Transformer core configuration must be considered and
saturation characteristics must be accurately known to operating levels well above rated voltage.
At this time, it is seen that modeling of ferroresonance is as
much an art as a science. As such, it is important if possible to
verify the results by checking the simulations against system
measurements. It is highly recommended that anyone active
in this area must continually monitor the literature for improvements in modeling techniques.
6. SUMMARY
This document provides a set of general guidelines for digitalcomputer time-domain simulation oflow-frequency (approximately 5 to 1000Hz) transients of electric power systems.

3-23

The report is intended for practicing engineers who are involved in analysis, control and system planning issues related
to electronic power systems. It is assumed that the reader has
(1) a fair understanding of the physical phenomena and (2) an
adequate knowledge of digital simulation techniques. The
guidelines are provided for seven transient torsional torques,
(3) turbine-blade vibrations, (4) fast bus transfer, (5) controller interactions, (6) harmonic interactions and resonance, and
(7) ferroresonance. For those phenomena which have extensively discussed in the literature, i.e. (1) to (4), general guidelines are provided and the reader is frequently referred to the
technical literature for further in-depth modeling and simulation issues. The emphasis of this document is on phenomena
(5), (6) and particularly (7).

7. REFERENCES

[1.I]CIGRE, "Guidelines For Representation of Network Elements When Calculating Transients", CIGRE Working
Group 33.02, 1990.
[2.1] IEEE Torsional Issues Working Group, "Fourth Supplement To A Bibliography For The Study of Subsynchronous
Resonance Between Rotating Machines and Power Systems",
IEEE Trans., Vol. PWRS-12, No.3, pp. 1276-1282, August
1997.
[2.2] IEEE SSR Working Group, "A Bibliography for the
Study of Subsynchronous Resonance Between Rotating Machines and Power Systems", IEEE Trans., Vol. PAS-95, No.
1, pp. 216-218, Jan. - Feb. 1976.

Transfer Studies", IEEE Trans. on Energy Conversion, Vol.


EC-5, No.3, pp. 470-476, 1990.
[2.9]P.L. Young, W.L. Snider, T.A. Higgins, H.I. Holley,
"Report on Bus Transfer: Part III, Full Scale Testing and
Evaluation", IEEE Trans. on Energy Conversion, Vol. EC-5,
No.3, pp. 477-484, 1990.
[2.10]P.L. Dandeno, M.R. Iravani, "Development and Application of Third-Order Turbogenerator Electrical Stability
Models With Particular Reference To Subsynchronous Resonance Studies", IEEE Trans., Vol. EC-I0, No.1, pp. 78-86,
March 1995.
[2.11]G. Gross, M.C. Hall, "Synchronouos Machine and Torsional Dynamic Simulation in Computation of Electromagnetic Transients", IEEE Trans. on Power Apparatus and
Systems, Vol. PAS-97, No.4, pp. 1074-1086, 1978.
[2.12]IEEE SSR Working Group, "First Benchmark Model
for Computer Simulation of Subsynchronous Resonance",
IEEE Trans. on Power Apparatus and Systems, Vol. PAS-96,
No.5, pp. 1565-1572, 1977.
[2.13]IEEE SSR Working Group, "Second Benchmark Model
for Computer Simulation of Subsynchronous Resonance",
IEEE Trans. on Power Apparatus and Systems, Vol. PAS104, No. 5,pp. 1057-1066, 1985.
[2.14]D.A. Woodford, "Validation of Digital Simulation of
DC Links", IEEE Trans. on Power Apparatus and Systems,
Vol. PAS-I04, No.9, pp. 2588-2595, September 1985.
[2.15]Manitoba HYDC Research Centre, "EMTDC User's
Manual", 1988.

[2.3]IEEE SSR Working Group, "First Supplement to a Bibliography for the Study of Subsynchronous Resonance Between Rotating Machines and Power Systems", IEEE Trans.,
Vol. PAS-98, No.6, pp. 1872-1875, Nov. - Dec. 1979.

[2.16]N. Rostamkolai, et al, "Subsynchronous Torsional Interactions with Static VAR Compensators - Influence of
HYDC", IEEE Trans. on Power Systems, Vol. PWRS-6, No.
1, pp. 255-261, Feb. 1991.

[2.4]IEEE SSR Working Group, "The Second Supplement to


a Bibliography for the Study of Subsynchronous Resonance
Between Rotating Machines and Power Systems", IEEE
Trans., Vol. PAS-I04, No.2, pp. 321-327, Feb. 1985.

[2.17]L. Gyugyi, "Fundamentals of Thyristor-Controlled


Static VAr Compensators in Electric Power System Applications", IEEE Publication 87TH0187-5 PWRS, pp. 8-27,1987.

[2.5]IEEE SSR Working Group, "Third Supplement to a Bibliography for the Study of Subsynchronous Resonance Between Rotating Machines and Power Systems", IEEE Trans.,
Vol. PWRS-6, No.2, pp. 830-834, May 1991.
[2.6]T.P. Tsao, C. Chgn, "Restriction ofTurbine Blade Vibrations in Turbogenerators", lEE Proceedings, Vol. 137, Part C,
No.5, pp. 339-342, 1990.
[2.7]J.D. Gill, "Transfer of Motor Loads, Between Out-ofPhase Sources", IEEE Trans. on Industrial Applications, Vol.
1A-15, No.4, pp. 376-381,1979.
[2.8]T.A. Higgins, P.L. Young, W.L. Snider, H.I. Holley,
"Report on Bus Transfer: Part II, Computer Modelling for

[2.18]A.N. Vasconcelos, et aI, "Detailed Modeling of an Actual Static VAR Compensator for Electromagnetic Transient
Studies", IEEE Trans. on Power Systems, Vol. PWRS-7, No.
1, pp. 11-19, 1992.
[2.19]H.J. Holley, T.A. Higgins, P.L. Young, W.L. Snider,
"A Comparison of Induction Motor Models for Bus Transfer
Studies", IEEE Trans. on Energy Conversion, Vol. EC-5, No.
2, pp. 310-319, 1990.
[2.20]EPRI Report, "Bus Transfer Studies for Utility Motors", EERI EL-4286, Vol. 2, Project 1763-2, October 1986.
[2.21]G.J. Rogers, D. Shirmohammadi, "Induction Machine
Modelling For Electromagnetic Transients Program", IEEE
Trans., Vol. EC-2, No.4, pp. 622-628, December 1987.

3-24

[2.22]R.H. Doherty, "Analysis of Transient Electrical


Torques and Shaft Torques in Induction Motors as a Result of
Power Supply Disturbances", IEEE Trans., Vol. PAS-I0l,
No.8, pp. 2826-2834, August 1982.

No.1, pp. 335-344, January 1996.

[2.23]Y. Pavlyuk, "Application of Static Transfer Switch For


Induction Motor Load Transfer", M.A.Sc. Thesis, University
of Toronto, 1997.

[4.6]D.A. Woodford, "Validation ofDigital Simulation ofDC


Links", IEEE Trans., Vol. PAS-I04, No.9, pp. 2588-2595,
September 1985.

[3.1]A.J.P. Ramos, H. Tyll, "Dynamic Performance of a Radial Weak Power System with Multiple Static VAr Compensators", IEEE Trans., Vol. PWRS-4, pp. 1316-1325,
November 1989.

[4.7]M. El-Marsafaway, "Use of Frequency Scan Techniques


for Subsynchronous Resonance Analysis of a Practical Series
Compensated AC Network", lEE Proceedings, Vol. 135, No.
1, pp. 28-40, 1983.

[3.2]E.V. Larsen, et al, "Basic Aspects of Applying SVCs to


Series Compensated AC Transmission Lines", IEEE Trans.,
Vol. PWRD-5, No.3, pp. 1466-1473, July 1990.

[4.8]M. Szechtman, T. Wess, C.V. Thio, H. Ring, L. Pilotto,


P. Kuffel, "First Benchmark Model for HVDC Control Studies", Electra, No. 135, pp. 54-73, April 1991.

[3.3]IEEE TF Report, "Modelling and Analysis Guidelines


For Slow Transients", IEEE Trans., Vol. PWRD-l1, No.3,
pp. 1672-1677, July 1996.

[4.9]CIGRE Working Group 14.02 of Study Committee 14,


"The CIGRE HVDC Benchmark Model - A New Proposal
with Revised Parameters:, Electra, No. 157, pp. 60-66, December 1994.

[3.4]M. Parniani, "Small-Signal Stability Analysis And Robust Control Design of Static VAR Compensators", Ph.D
Thesis, University of Toronto, 1995.
...[3.5]M. Parniani, M.R. Iravani, "Voltage Control Stability
and Dynamic Interaction Phenomena of Static VAR Compensators", IEEE Trans., Vol. PWRS-I0, No.3, pp. 1592-1597,
August 1995.
[3.6]G. Gross, C.F. Imparato, P.M. Look, "A Tool for Comprehensive Analysis of Power System Dynamic Stability",
IEEE Trans., Vol. PAS-I0l, No.1, pp. 226-234, January
1982.
[3.7]R.M. Hamouda, M.R. !ravani, R. Hackam, "Coordinated
Static VAR Compensators and Power System Stabilizers for
Damping Power System Oscillations", IEEE Trans., Vol.
PWRS-2,pp. 1059-1067, 1987.
[3.8]M. Parniani, M.R. Iravani , "Computer Analysis of
Small-Signal Stability of Power System Including Network
Dynamics", Proceeding lEE, Gen-Trans-Distrib, Vol. 142,
No.6, pp. 613-617, November 1995.
[4.1]A.E. Hammad, "Analysis of Second Harmonic Instability for the Chateauguay HVDC/SVC Scheme", IEEE Trans.,
Vol. PWRD-7, No.1, pp. 410-415, January 1992.
[4.2]E.V. Larsen, M. Lublich, S.C. Kapoor, "Impact of Stray
Capacitance on HVDC Harmonics", IEEE Trans., Vol.
PWRD-4, No.1, pp. 637-645, 1989.
[4.3]A.S. Morched, J.H. Ottevangers, L. Marti, "Multi-Port
Frequency Dependent Network Equivalents for the EMTP",
IEEE Trans., Vol. PWRD-8, No.3, pp. 1402-1412, July 1993.
[4.4]A. Sarshar, M.R. Iravani, J. Li, "Calculation ofNoncharacteristic Harmonics of HVDC Station Using Digital TimeDomain Simulation Method", IEEE Trans., Vol. PWRD-l1,

[4.5]Manitoba HVDC Research Center, "EMTDC User Manual", pp. 12.44-12.50, 1988.

[4.10]L.A.S. Pilotto, J.E.R. Alves, E.H. Watanabe, A.E. Hammad, "A Non-Linear Switching Function Model for Static
VAR Compensators", Proceedings of International Power
Electronics Conference (IPEC), pp. 627-631, Yokohama,
April, 1995.
[4.11]N.L. Shore, G. Andersson, A.P. Canelhas and G. Asplund, "A Three-Pulse Model of DC Side Harmonic Flow in
HVDC Systems", IEEE Trans., Vol. PWRD-4, No.3, pp.
1945-1954, July 1989.
[4.12]D.L. Dickmander, K.J. Peterson, "Analysis of DC Harmonics Using the Three-Pulse Model for the Intermountain
Power Project HVDC Transmission", IEEE Trans., Vol.
PWRD-4, No.2, pp. 1195-1204, April 1989.
[4.13]T.F. Garrity, 1.0. Hassan, K.A. Adamson, J.A.
Donahue, "Measurement of Harmonic Currents and Evaluation of DC Filter Performance of the New England - Hydro
Quebec Phase I HVDC Project", IEEE Trans., Vol. PWRD-4,
No.1, pp. 779-786, January 1989.
[4.14]D.L. Dickmander, S.Y. Lee" G.L. Desilets, M. Granger, "AC/DC Harmonic Interaction in the Presence of GIC for
the Hydro Quebec - New England Phase II HVDC Transmission", IEEE Trans., Vol. PWRD-9, No.1, pp. 68-78, January
1994.
[4.15]H. Stemmler, "HVDC Back-to-back Interties on Weak
AC Systems - Second Harmonic Problems Analysis and Solution", CIGRE Symposium, Paper 300-08, Boston, 1987.
[4.16]R.H. Lasseter, L.J. Bohmann, "Harmonic Interactions
in Thyristor Controlled Reactor Circuits", IEEE Trans., Vol.
PWRD-4, No.3, pp. 1919-1925, July 1989.
[4.17]L.J. Bohmann, R.H. Lasseter, "Stability and Harmonics
in Thyristor Controlled Reactors", IEEE Trans., Vol. PWRD-

3-25

5, No.2, pp. 1175-1181, April 1991.

28-30, 1989.

[4.18]S.G. Jalali, R.H. Lasseter, "A Study of Nonlinear Harmonic Interaction Between a Single Phase Line-Commutated
Converter and a Power System", IEEE Trans., Vol. PWRD-9,
No.3, pp. 1616-1624, July 1994.

[5.14]D.G. Fink and H.W. Beatty, Standard Handbook for


Electrical Engineers, 11th Ed., McGraw-Hill Book Company, New York, NY, copyright 1978.

[4.19]X. Jiang, A.M. Gole, "A Frequency Scanning Method


for the Identification of Harmonic Instabilities in HYDC Systems", IEEE PES paper 95WM222-0 PWRD.
[5.1]R.G. Andrei and B.R. Halley, "Voltage Transformer Ferroresonance from an Energy Standpoint", IEEE Trans. Power
Delivery, vol. 4, no. 3, pp. 1773-1778, July, 1989.
[5.2]C.M. Arturi, "Transient Simulation and Analysis of a
Five-Limb Generator Step-Up Transformer Following an
Out-of-Phase Synchronization", IEEE Trans. Power Delivery, vol. 6, no. 1, pp. 196-207, January 1991.
[5.3]F.R. Bergseth and S.S. Venkata, Introduction to Electric
Energy Devices, Prentice Hall, Inc., Inglewood Cliffs, NJ,
copyright 1987.

[5.15]J.G. Frame, N. Mohan and T. Liu, "Hysteresis Modeling in an Electro-Magnetic Transients Program", IEEE Trans.
PAS, vol. PAS-I0l, no. 9, pp. 3403-3411, September, 1982.
[5.16]J. Gleick, Chaos: Making a New Science, Viking, New
York, NY, copyright 1987.
[5.17]C. Hayashi, Nonlinear Oscillations in Physical Systems, McGraw-Hill Book Company, New York, NY, copyright 1964.
[5.18]T. Henriksen and O. Rervik, "Ferroresonans i 50-kV
Nett til Hafslund", Energiforsyningens Forskningsinstitutt AI
S, Trondheim, Norway, ISBN 82-594-0229-7, EFI TR 3779,
December 19, 1990 (in Norwegian),
[5.19]R.H. Hopkinson, "Ferroresonance During Single-Phase
Switching of3-Phase Distribution Transformer Banks", IEEE
Trans. PAS, vol. PAS-84, no. 4, pp. 289-293, April 1965.

[5.4]J. Bethenod, "Sur le Transformateur et Resonance",


L'Eclairae Electrique, pp. 289-296, November 30, 1907.

[5.20]D.C. Jiles and D.L. Atherton, "Theory ofFerromagnetic


Hysteresis," Elsevier Science Publishers B.V., Journal of
Magnetism and Magnetic Materials, vol. 61. pp. 48-60, January 21, 1986.

[5.5]J.L. Blackburn, Protective Relaying Principles and Applications, Marcel Dekker, Inc., New York, NY, pp. 231-237,
9th printing, copyright 1987.
[5.6]M.H.J. Bollen, "The Search for a General Transformer
Model", 16th European EMTP Users Group Meeting, paper
89-07, pp. 1-20, May 28- 30, 1989.
[5.7]P. Boucherot, "Existence de Deux Regimes en Ferro-resonance", R.G.E., pp. 827-828, December 10, 1920.
[5.8]V. Brenner, "Subharmonic Response of the Ferroresonant Circuit with Coil Hysteresis", AlEE Transactions, vol.
75 I, pp. 450-456, September 1956.
[5.9]J.W. Butler and C. Concordia, "Analysis of Series Capacitor Application Problems", AlEE Trans., vol. 56, pp.
975-988, August, 1937.
[5.10]E.C. Cherry, "The Duality Between Interlinked Electric
and Magnetic Circuits and the Formation of Transformer
Equivalent Circuits," Proceedings of the Physical Society,
Part B, vol. 62, pp. 101-111, 1949.
[5.11]H.W. Dommel with S. Bhattacharya, V. Brandwajn,
H.K. Lauw and L. Marti, EMTP Theory Book, 2nd Ed., Microtran Power System Analysis Corporation, Vancouver, BC,
May 1992.
[5.12]L. Dube and B.A. Mork, "Variable Capacitances and
Inductance in ATP," EMTP News, vol. 5, no. 1, pp. 33-36,
March 1992.
[5.13]G. Empereur, "Miscellaneous - Transformers", 16th
European EMTP Users Group Meeting, Paper 89-09, May

[5.21]Kieny, "Application of Bifurcation Theory in Studying


and Understanding the Global Behavior of a Resonant Electric Power Circuit," IEEE PES Summer Meeting, SM 265-9
PWRD, July 1990.
[5.22]K.U. Leuven EMTP Center, Alternate Transients Program Rule Book, Leuven EMTP Center, Heverlee, Belgium,
Revised July, 1987, copyright 1987.
[5.23]D.D. Mairs, D.L. Stuehm and B.A. Mork, "Overvoltages on Five-Legged Core Transformers on Rural Electric Systems", IEEE Trans. on Industrial Applications, vol. 25, no. 2,
pp. 366-370, March, 1989.
[5.24]L.W. Match and J.D. Morgan, Electromagnetic and
Electromechanical Machines, Third Edition, Harper & Row
Publishers, Inc., New York, copyright 1986.
[5.25]R.D. Millet, D.D. Mairs and D.L. Stuehm, "The Assessment and Mitigation Study of Ferroresonance on GroundedWye to Grounded-Wye 3-Phase Padmounted Transformers",
Summary Report, NRECA Project 86-7, July, 1987.
[5.26]B.A. Mork, Ferroresonant Modeling Using EMTP, MS
Thesis, North Dakota State University, September 1981.
[5.27]B.A. Mork and D.L. Stuehm, "Application ofNonlinear
Dynamics and Chaos to Ferroresonance in Distribution Systems," IEEE Trans. Power Systems, vol. 9, no. 2, pp. 10091017, April 1994.

3-26

[5.28]B.A. Mork, "Five-Legged Wound-Core Transformer


Model: Derivation, Parameters, Implementation, and Evaluation," Submitted for IEEE PES Winter Meeting, 98WM414,
January 1998.
[5.29]B.A. Mork, Ferroresonance and Chaos - Observation
and Simulation of Ferroresonance in a Five-Legged Core
Distribution Transformer, Ph.D. Dissertation, North Dakota
State University, May 1992. Publication No. 9227588, UMI
Publishing Services, Ann Arbor, MI, 48106, (800) 521-0600.

Delivery, vol. 4, no. 3, pp. 1786-1793, July, 1989.


[5.42]D.L. Stuehm., "Final Report - Three Phase Transformer
Core Modeling," Bonneville Power Administration Award
No. DE-BI79-92BP26700, February 28, 1993. Copies available from BPA, Dept. EOHC, (503) 230-4404.
[5.43]G.W. Swift, "Power Transformer Core Behavior Under
Transient Conditions," IEEE Trans. PAS, vol. PAS-90, no. 5,
pp. 2206-2209, Sep/Oct 1971.

[5.30]A. Narang and R.H. Brierley, "Topology Based Magnetic Model for Steady-State and Transient Studies for Three
Phase Core Type Transformers," IEEE Trans. PWRS, vol. 9,
no. 3, pp. 1337-1349, August 1994.

[5.44]E.J. Tarasiewicz, A.S. Morched, A. Narang, E.P. Dick,


"Frequency Dependent Eddy Current Models for Nonlinear
Iron Cores," IEEE Trans. PWRS, vol. 8, no. 2, pp. 588-597,
May 1993.

[5.31]W.L.A. Neves and H.W. Dommel, "On Modelling Iron


Core Nonlinearities," IEEE Trans. Power Systems, vol. 8, no.
2, pp. 417-425, May 1993.

[5.45]J.M.T. Thompson and H.B. Stewart, Nonlinear Dynamics and Chaos - Geometrical Methods for Engineers and Scientists, John Wiley and Sons, New York, NY, (Reprinted
October 1987), copyright 1986.

[5.32]NRECA, Underground Distribution System Design and


Installation Guide, Section 6, National Rural Electric Cooperatives Association, 1994.
[5.33]0.E. Radulescu, "EMTP Transformer Model with
Type-96 Element - Computation of the Inrush Current",
EMTP Newsletter, vol. 6, no. 2, pp. 25-33, June, 1986.
[5.34]J. Rougin and V. Ranjamina, "Modeling of Magnetic
Circuits with EMTP", EMTP Newsletter, vol. 7, no. 1, pp.
8-28, March 1987.

[5.46]J. Usaola and G. Empereur, "Comparison Between Different Transformer Models in EMTP," EMTP News, vol. 2,
no. 2, pp. 25-34, June 1989.
[5.47]R.A. Walling, K.D. Barker, T.M. Compton, and L.E.
Zimmerman, "Ferroresonant Overvoltages in Grounded WyeWye Padmount Transformers with Low-Loss Silicon-Steel
Cores", IEEE Trans. Power Delivery, vol. 8, no. 3, pp. 16471660, July, 199.

[5.35]R.J. Rush and M.L. Good, "Wyes and Wye Nots of


Three-Phase Distribution Transformer Connections", IEEE
Conference Paper 89CH2709-4-C2, 1989.

APPENDIX A

[5.36]R. Rudenberg, Transient Performance ofElectric Power Systems, McGraw-Hill Book Company, New York, NY,
chapter 48, copyright 1950.
[5.37]G.R. SIemon, "Equivalent Circuits for Transformers
and Machines Including Non-Linear Effects," Proceedings
lEE, vol. 100, part IV, pp. 129-143, 1953.
[5.38]D.R. Smith, S.R. Swanson and J.D. Borst, "Overvoltages with Remotely-Switched Cable-Fed Grounded Wye-Wye
Transformers", IEEE Trans. PAS, vol. PAS-94, no. 5, pp.
1843-1853, Sep/Oct 1975.
[5.39]P.L. Sorenson, "Simulation of Faults and Switchings in
Electrical Distribution Networks", ATV - NESA - Electrical
Engineering Department, DTH - DEFU, Industrial Research
Project EF186, pp. 1- 120, April, 1988.
[5.40]D.L. Stuehm, B.A. Mork and D.D. Mairs, "Ferroresonance with Three Phase Five-Legged Core Transformers",
Minnesota Power Systems Conference, Minneapolis, MN,
October 3, 1988.
[5.41]D.L. Stuehm, B.A. Mork and D.D. Mairs, "Five-Legged
Core Transformer Equivalent Circuit", IEEE Trans. Power

FAST BUS TRANSFER TRANSIENTS


Introduction
Motors and other loads in utility and heavy industrial applications are supplied during normal operation from a
preferred power source. An alternate power source is normally provided to supply such motors and other loads during
planned shutdowns and upon loss of normal power from the
preferred power source. The process of disconnecting the
motors and other loads from one source and reconnecting to
an alternate source is commonly defined as "bus transfer".
Manual transfer means are normally provided to
allow transferring the motors and other loads from one power
source to the other. However, upon loss of the preferred
power source, the motors and other loads are automatically
transferred to the alternate power source. This automatic
transfer is necessary to allow uninterrupted operation of the
motors and other loads important to personnel safety and process operation.

3-27

The normal and alternate power source connections

are always selected such that they are in phase. Therefore,


manual transfers can be accomplished in a make-beforebreak, i.e., the motors and loads are connected to the second
power source before the first power source is disconnected.
In this overlapping transfer, the power supply is not interrupted and the motors are not subjected to transients. However, during automatic transfers, the motors may be
disconnected from both power sources for a short duration
depending on the type of transfer and the associated circuit
breakers operating times. The time during which the motors
are disconnected from both power sources is termed the
"dead time". It is commonly longer than two cycles and can
be as long as 12 cycles. While motors are disconnected from
both power sources they decelerate. The deceleration rate
depends on the motor-load inertia and the synchronizing
power flowing between motors due to their differing characteristics. As the motor decelerates, the relative angle
between the motor internal voltage and the power source
voltage changes. Also, the motor residual voltage decays at a
rate which depends on the motor magnetic characteristics,
speed and initial loading. If the relative angle between the
motor residual voltage and the power source voltage
becomes large enough at the time of reconnection with significant residual voltage remaining, the resultant voltage
between the power source and the motor will produce an
inrush current. The inrush current may be significantly
larger than the normal full voltage starting current. Such
high inrush currents cause high winding stresses and transient shaft torques which can damage the motor and/or the
driven equipment.
The most common bus transfer scheme is the fast
bus transfer scheme. In this scheme, opening of the normal
power source breaker initiates closing of the alternate power
source breaker without intentional time delay. The fast bus
transfer operations result in the motors being disconnected
from both power sources for a duration of as short as 2 cycles
to as long as 12 or more cycles.
Presently, there are no generic criteria to ensure
acceptable fast bus transfer operations. Therefore, it is necessary to analyze the transient behavior of motors during fast
bus transfer operations. The analysis should be on a case by
case basis to ensure that the motors will not be subjected to
excessive inrush currents and!or shaft transient torques.
A.2Modeling and Analysis

A three-phase model of the motors and the power


distribution system is required. This is to permit simulating
the breaker individual pole interruption at separate current
zeros and analyzing the effect of unbalanced faults on the
motor behavior. The model must simulate the motor stator
and rotor dynamics, the load dynamics, and the power source
dynamics when available. The larger motors should be individually modeled; smaller motors unless for the motor being
studied, if any, may be lumped together and modeled by one

equivalent motor with typical characteristics. The distinction


between large and small motors should be made on a case by
case basis.
A.2.i Motor Electrical System

The motor electrical system may be modeled by the


differential equations describing the stator and rotor quantities and flux linkages [2.20] or by the two-axis model [2.21].
A single rotor motor model may be adequate since the motor
speed usually does not drop significantly during the time a
fast transfer is accomplished. The model should account for
saturation in the magnetizing, stator and rotor leakage reactances.
A.2.2Loads

The mechanical load should be modeled by its


torque-speed characteristics and moment of inertia. Common centrifugal and axial pumps and fans may be modeled
by a quadratic torque-speed characteristic.
Non-motor loads may be lumped together and modeled by an equivalent resistance-inductance circuit. Nonmotor loads would be included in the model to account for
their damping effects on the motors during the dead time.
A.2.3Motor-Load Shaft Torsional Model

The shaft system should be modeled by the motor


rotor mass connected to the load rotor mass by a flexible
spring representing the shaft [2.22]. The motor air gap
torque excites the mass representing the motor rotor while
the load torque excites the mass representing the load rotor.
The shaft torsional model should include the effect of damping and shaft flexibility. The effect of shaft flexibility is particularly important in applications where loads have a large
inertia relative to that of the motor. An example of this application is torsional study of a large boiler fan. Under such
conditions, the shaft flexibility may cause the shaft torque to
be higher than the motor air gap torque [2.22].
A.2.4Circuit Breakers

The circuit breakers should be modeled as a three


pole switch which can be opened or closed at a preset time.
The three poles of the circuit breaker connecting the alternate
source must be modeled to close simultaneously. the individual poles of the circuit breaker disconnecting the normal
source must be modeled to open only at the respective current zero. In analysis involving transfers caused by high
level electrical faults, the individual poles may be modeled to
open at the respective first current zero following the end of
the breaker arcing time. This is a conservative approach
which, in effect, models a zero resistance arc.
A.2.5Power Sources

3-28

torques should be investigated.


The motor air gap torque at the instant of closing the
alternate source breaker is determined by the motor residual
voltage magnitude and phase angle. The magnitude of the
motor residual voltage decreases with time while the phase
angle increased with time. This causes the magnitude of the
air gap torque to be cyclic. It has a minimum value at some
short bus dead time, peaks as the dead time increases and
then decreases as the dead time increases further. The duration of the dead time at which the air gap torque attains minimum and maximum values are system specific and depends
on the connected motors characteristics and load levels.

Generally, events which initiate bus transfers such


as the loss of the generator in a generating station also initiate
disturbances to the connected power system. The dynamic
variations of the power system voltage magnitude and phase
angle are normally determined as part of system stability
studies.
Ideally, the normal and alternate power source models should reflect the dynamic variations in the voltage magnitude and phase angle following the initiating event. This
can be accomplished by a point to point representation of the
system voltage magnitude and phase angle profiles. Alternately, the system voltage magnitude and phase angle may be
modeled by polynomials fitting their profiles for the short
duration of interest. However, in the event that data on the
dynamic behavior of the power system is not available, the
normal and alternate power sources may be modeled as ideal
sources in phase.

The account for the above considerations, the following fast bus transfer operations should be simulated and
analyzed.

A.2.6TransforDlers
Transformer dynamics have a little or no effect on
bus transfer operations. Therefore, a transformer may be
modeled as an ideal transformer in series with a lumped
resistance in series with a lumped inductance representing
the transformer equivalent impedance.

Transfers caused without high level electrical faults


with motors operating at their highest loadings when the
alternate source voltage is at its maximum level.
Transfers caused without high level electrical faults
as in 1) above except without the largest high inertia motor
running.
Transfers caused by high level electrical faults (line
to ground and three line to ground faults).
The following parameters should be monitored during the simulations:

A.2.7 Cables/Lines

bus instantaneous voltages


bus voltage phase angle
individual motors instantaneous currents
individual motor air gap torques
individual motors shaft torques (when modeled)
individual motors speed

Cable and Lines may be modelled by their -equivalents.


A.2.8Simulation and Analysis

In selecting conditions to be analyzed, the following


should be taken into consideration:

A.3 Model Validation

The motor initial loading (prior to the transfer) has a


significant effect on the rate of change of the motor internal
voltage phase angle. Higher loads cause faster drop in rotor
speed and faster rates of change in the phase angle. Therefore, the worst case transfer results when the motors are operating at their highest loading.
The motor-load inertia also has a significant effect
on the internal voltage phase angle rate of change. Motors
with a high inertia have a slower rate of change than motors
with low inertia. Therefore, the effect of fast bus transfer
operation with and without such high inertia motors should
be evaluated.
Bus transfers are initiated by low and high level
electrical faults. The motor residual voltage decays at a high
rate until the fault is cleared by opening the source breaker.
This causes the transient shaft torque produced upon closing
the alternate source breaker to be relatively low. However,
faults such as line to ground faults cause the motor to experience a high oscillatory torque before the fault is cleared. The
effect of the torsional stress caused by such high oscillatory

Ideally, validating a model of a fast bus transfer


operation should include validating the individual motor
models and the circuit breakers operating times. Individual
motor models can be validated by simulating motor starting
and running conditions and comparison of the simulation
results to data recorded during an actual motor starting test.
Parameters be compared include motor instantaneous current, power, apparent power (VA), and speed. However,
since a typical bus transfer model may include 15 or more
motors, it may not be practical to validate individual motor
models. As an alternative, the bus transfer model can be
based on modeling motors using unadjusted manufacturers
supplied data and establishing a range of the expected accuracy.

3-29

Modeling Guidelines for Switching Transients


Report Prepared by the Switching Transients Task Force
of the IEEE Modeling and Analysis of System Transients Working Group
Contributing Members: D.W. Durbak(Co-Chairman), A.M. Gole (Co-Chairman),E.H. Camm, M.Marz,
R.C. Degeneff, R.P. O'Leary, R. Natarajan, J.A. Martinez-Velasco, Kai-Chung Lee, A. Morched, R. Shanahan, E.R. Pratico, G.C. Thomann, B. Shperling, A. J. F. Keri, D.A. Woodford, L. Rugeles, V.Rashkes,
A. Sarshar
overvoltage for a line energization depends on the exact
point on the wave at which the switchcontactsclose. Thus
a numberof runs for the same systemhave to be made with
the time of energization being different in each run either
in a predictable manner (i.e., for determining the peak
overvoltage) or statistically (for obtaining an overvoltage
probability distribution).

Abstract- Power Systems Switching Transients are


initiated by the action of circuit breakers and switches and by
faults. These actions include energization, de-energization,
reclosing and fault clearing. The range of frequencies of primary interest in a switching transients study vary from the fundamental power frequency up to about 10 kHz. Therefore the
proper representation must be chosen for the various components such as transmission lines and cables, transformers,
source equivalents, loads and circuit breakers. Equipment modeling aspects for the analysis of switching overvoltages are the
principal subject of this paper.

2. MODELING REQUIREMENTS
This sectiondiscusses general and specificmodeling requirements. General requirements include a discussion of the extent of the system to be modeled, frequency
ranges and simulation time-steps. Specific requirements
include the equipment models typically used for switching
transients simulation.

Keywords: Electromagnetic Transients Simulation, emtp,

Switching Transients, Transient Recovery Voltage.


1. INTRODUCTION
Switching transients are causedby the operation of
breakers and switches in a power system. The switching
operations represent two main categories: i) energization
phenomena and ii) de-energization of the system elements.
The former category include energization of transmission
lines or cables, transformers, reactors, capacitor banks etc.
The latter categoryincludes fault clearing and load rejections
and so on.
Due to the complexity of the mathematical representation of the equipment involved, digital simulation using
an electromagnetic transients simulation program plays an
important role in the study of switching transients.

2.1lRANSMISSION LINES AND CABLES

The resultsfrom such studiesare useful for:


insulation co-ordination to determine overvoltages
stresses on equipment
ii ) determining the arrestercharacteristics
iii) determining the transientrecovery voltage acrosscircuit
breakers.
iv) determining the effectiveness of transient mitigating
devices, e.g., pre-insertion resistors, inductors and controlledclosingdevices.
i)

The level of detail requiredin the modelvaries with


the study. For example, a line may be represented by a pisectionequivalent in some line energization studies. In other
situations a distributed parameter model with frequency
dependence may be necessary.
In some instances the results are highly sensitive to
the value of a certain parameter. For example, the maximum
4-1

The most efficientand accurate transmission line


modelsare distributed parametermodelsbased on the travelling time t and characteristic impedance Zc of the
line[I,2]. Lumped parametermodels (pi-circuits) are computationally more expensive (a number of cascaded shortsections are needed to approximate the distributed nature
of the physical line) and less accurate.
In the phase domain, the current in one phase will
cause a voltage in another phase, because of the mutual
impedance. In the modal domain, the modes are uncoupled, and calculations are easier. The transformation
between the domains for currentsis given by the equation:

(1)

where [Iphase] is the phase current vector, [Ij] is the transformation matrix, and [Imode] is the modal current vector.
There is a similar expression for voltage, with transformation matrix [Tv]. Digital programs only work with real
matrices, so it is helpful if the components of the transformation matrices do not have large imaginary parts. The
transformation matrix for overhead lines is nearly real, but
for cables it may have a significant imaginary part. It is
also simplest if the transformation matricesare assumed to
be frequency independent over the range of frequencies
found in switching surges. For overheadlines, the assump-

tion of frequency independence can usually be made; for


cables the matrices are often frequency dependent. In addition, for pipe-type cables, the cable impedance can be a function of the cable current, if pipe saturation occurs. The
saturation is difficult to model.
The distributed parameter model consists of a
description of each mode, and the transformation matrices to
return to the phase domain. The description of each mode
will probably consist of the surge impedance, resistance,
velocity and length. More sophisticated frequency dependent models will include information on the variation of the
parameters with frequency. This may be an important consideration when the ground return mode (zero sequence) is
involved (e.g., during a line to ground fault). In these cases, a
frequency dependent distributed parameter line model gives
a very accurate representation for a wide range of frequencies in the transients phenomenon.The parameters for the distributed parameter model (either frequency-dependent or
constant) are obtained from geometrical and physical information (line/cable dimensions, height above ground, conductor and soil resistivity) by using a line/cable constants
program usually included with the EMTP-type programs
For secondary lines (not directly feeding the phenomenon under study), and for those studies where mostly
positive sequence conditions are involved (e.g., three-phase
energization), a simple distributed constant parameters models can gives satisfactory results.
The use of nominal pi-circuits [1,3] is usually
restricted to the case of very short lines when the line's travelling time t is smaller than the integration step ~t of the simulation. However, in many instances, cascaded pi-sections
can be used without excessive loss of accuracy, for studies
such as line energization [4,5]. The number of pi-circuits
used depends on the desired accuracy, and selecting an
appropriate number is important.For overhead lines, the
parameters for the pi-section can readily be obtained from
positive and zero sequence fundamental frequency impedance values that are used in load flow studies. Typical positive and zero sequence parameters of the overhead lines are
presented in Table 1. The self and mutual impedances to be
used in the pi-representation can be obtained using Eqn. 2

Voltage
Level
Comments:

230kV

345kV

p-l00 n-m

p=100 n-m

p=100 Q-m

p=100 Q-m

Xl,Q!km

0.50

0.38

0.38

0.34

RI,Q!km

0.05

0.032

0.018

0.017

XO,Q!km

2.5

1.3

1.2

1.00

RO,Q!km

0.49

0.34

0.33

0.33

Cl, ~F/km

0.0088

0.012

0.013

0.013

CO, ~F/km

0.0041

0.0083

0.0075

0.0093

Table 1: Typical Transmission Line Parameters at 60 Hz

In many cable studies, such as disconnect switch


operation, the constant parameter assumption can be too limiting. Here a frequency dependent parameter model must be
used, because the frequencies span a large bandwidth and the
cable parameters significantly vary within this range. However for solid dielectric cables, the constant parameter model
is often adequate. The calculations shown below are useful in
determining the maximum allowable pi-section length and in
estimating errors.
Consider as an example a single phase cable with an
impedance of Z per unit length and an admittance Y per unit
length. Then the propagation constant is given by
(3)

and the surge impedance is given by

rz

zo = Vy

1
c, = 3(C
O + 2C t )

c; =

1
3(CO-C t )

(4)

Suppose the cable is lossless, and has a total length


L. Assume each pi-section is used to represent a length Ax,
The surge impedance for the pi-section is Z01t, given by

1
= 3(X
O-Xt )

765kV

No. of ccts=2 No. of ccts= 1 No. of ccts= 1 No. of ccts=1


Cond/phase= 1 Cond/phase=2 Cond/phase=3 Cond/phase=4
Gnd. wires= 1 Gnd. wires=2 Gnd. wires=2 Gnd. wires=2

x, = 3(XO + 2X t )
Xm

500 kV

(5)

(2)

From this expression it is easy to see how small x


has to be for any desired matching of the surge impedance.
Next consider the phase error across the length of the cable
for any frequency f. If Yn is the phase shift at any frequency
across one pi-section, then YnN is the phase shift across all
N sections. It can be shown that

4-2

(6)
Since the correct phase shift is yL , the error in the
phase shift can be easily found.

2.2 TRANSFORMERS
For switching surge transient studies, the transformer model used is a reduced order representation with less
detail (i.e., as in the example in Fig. 21) in comparison with a
model used for insulation studies. Usually a lumped parameter coupled-winding model with a sufficient number ofR-LC elements gives the appropriate impedance characteristics at
the terminal within the frequency range of interest. The nonlinear characteristic of the core should usually be included,
although the frequency characteristic of the core is often
ignored. This may be an oversimplification as the eddy current effect prevents the flux from entering the core steel at
high frequencies thereby making the transformer appear to be
air-cored. This effect begins to be significant even at frequencies in the order of 3-5 kHz.

break circuits. In switching surge studies, the switch is often


modeled as an ideal conductor (zero impedance) when
closed, and an open circuit (infinite impedance) when open.
Transient programs allow various options to vary the closing
time ranging from one-shot deterministic closings to multishot statistical or systematic closings.
Statistical Switching: Transient voltage and current magnitudes depend upon the instant on the voltage waveform at
which the circuit breaker contacts close electrically [12]. A
statistical switching case typically consists of 100 or more
separate simulations, each using a different set of circuit
breaker closing times. Statistical methods can be used to process the peak overvoltages from each simulation. Fig. 1 is a
plot derived from 100 peak overvoltage magnitudes from the
line energization case study presented in section III A. This
plot shows a 10% probability (Y axis) of exceeding 2 pu voltage (X axis).

Circuit breakers can close at any time (angle) on the


power frequency wave. For a single phase circuit, the set of
circuit breaker closing times can be represented as a uniform
distribution from 0 to 360 degrees with reference to the
power frequency. The standard deviation for a uniform distribution over 1 cycle is 1/(2)31) ,where fis the frequency of
the waveform.

For switching surge studies, the following


approaches may be used:
i ) The model may directly be developed from the transformer characteristic e.g., nameplate information or
Doble measurements. The standard EMTP models fall
into this category. Examples are described in [6,7]
ii) A model synthesized from measured impedance vis frequency response of the transformer as described in [8,9].
This approach is used in the Case Study of section 3.3.5
iii) A very detailed model obtained from the transformer
geometry and material characteristics may be developed.
The model is then reduced to one that is usable in the
time domain solution. Examples of this method are
described in [7,10,11].

A three phase (pole) circuit breaker can be modeled


as three single phase circuit breakers, each with independent
uniform distributions covering 360 degrees. However, an
alternative (dependent) model can be used if the three poles
are mechanically linked and adjusted so that each pole
attempts to close at the same instant. In reality, there will be a
finite time or pole span between the closing instants of the
three poles. The pole span can be modeled with an additional
statistical parameter, typically from a Gaussian (normal) distribution. For a mechanically linked three pole circuit
breaker, the closing times use both uniform distribution
parameters and Gaussian distribution parameters. All three
dependent poles use the same parameter from the uniform
distribution, which varies from 0 to 360 degrees. Each pole
uses a unique parameter from the Gaussian distribution. The
standard deviation of the maximum pole span is typically 17
~o 25 ~ercent of the maximum pole span. For the case study
in section III A, a maximum pole span of 5 ms was assumed.

When possible, the following techniques can be


used to validate the model. A frequency response obtained by
simulation can be compared within the desired bandwidth
with the actual characteristic if available. This should be
done for all possible open and short circuit conditions on the
~indings. Determining the fundamental frequency response
m the form of open and short circuit impedances is a standard
check. The turns ratio or induced winding voltages at fundament~l fre~uency are of interest. Comparison with factory
tests If available also validates the model. If terminal capacitance measurements are available a comparison between
measured and computed responses is useful.

Statistical cases with pre-insertion resistors or reactors require a second set of three phase switches. The first set
is modeled as described above. The closing times of the second set (which shorts the resistors or reactors) are dependent
upon the first set plus a fixed time delay, typically one-half to
one cycle for pre-insertion resistors used with circuit breakers, and 7 to 12 cycles (depending on application voltage
class) for pre-insertion reactors used with circuit-switchers
closing in air through high-speed disconnect blades.

2.3 SWITCHGEAR
Switchgear includes circuit breakers circuitswitchers, vacuum switches and other devices which make or

4-3

closed during the steady state solution or closed at a specific


time or voltage. Several runs with variations in the closing
instant should be carried out as the point on wave of switching can affect the transient.

100

90
80

Sometimes faults are modeled with flashover controlled switches to represent a gap. The switch is operated
typically, when the gap voltage exceeds a fixed value. More
sophisticated models include a volt-time characteristic.

70
~

60

50

""

40

'"2

Faults generally involve arcs. Arcs can be modeled


by various approximations such as:
i) Ideal Switch (R= 0, V =0)
ii) Linear resistance R or constant voltage V
iii) Constant V and series R
iv) Series V and R that vary according to some assumed
function
v) V and/or R that vary according to some differential
equation [17].

30
20
10
0
1

1.2

1.4

1.8

1.6
Voll~g

2.

P.U.

Fig. I. Overvoltage Distribution Probability

pre-Strikjng' In the model described above, a normal distribution was assumed for the closing of the phase switches. In
reality, the withstand strength of the contacts decreases as the
contacts come closer. When the field stress across the contacts exceeds this withstand strength, pre-strike occurs. If this
is taken into account, the distribution of closing angles is
confmed to the rising and peak portions of the voltage waveshapes [13].

The most commonly used option is i) above as the


arc voltage is usually small compared with voltage drops
elsewhere (i.e., along the transmission line) . Arc modeling
can be important when studying secondary arc phenomena,
such as single pole reclosing . Discussion on the modeling of
this phenomenon is available in the literature[18].

2.4 CAPACITORS AND REACTORS


Capacitor banks are usually modeled as a single
lumped element. However, some switching transient simulations require the modeling of secondary parameters such as
series inductance and loss resistance. The inductance of the
buswork is sometimes important when studying the back to
back switching of capacitor banks, or in the study of faults on
the capacitance bus . The damping resistance of this inductance should be estimated for the natural frequency of oscillations.

Some modem devices can control the closing angle


of the poles to close at or near the voltage zero between the
contacts. Such devices are being applied to capacitor bank
switching and can reduce overvoltages and inrush currents.
For such devices, the maximum angle in the tolerance of the
voltage zero closing control should be used. Alternatively, a
statistical switching method can be applied to the breaker
poles over the time span around the voltage zero, within the
tolerance of the closing time [13].

Reactors are modeled in many studies by a simple


lumped inductor with a series resistance. A parallel resistance may be added for realistic high frequency damping.
Core saturation characteristic may also have to be modeled.
A parallel capacitance across the reactor should be included
for reactor opening studies (chopping of small currents). The
total capacitance includes the bushing capacitance and the
equivalent winding to ground capacitance. For series reactors, there is a capacitance from the terminal to ground and
from terminal to terminal.

Openjng: Typical transient studies require the switch to open


at a current zero. The dynamic characteristic of the arc is usually not important and is not modeled in most cases. However in certain instances where small inductive currents are
being interrupted, the current in the switch can extinguish
prior to its natural zero crossing. Severe voltage oscillations
can result due to this current-chopping that can stress the circuit breaker. Modeling of this phenomenon is described in
additional detail in available literature [14,15] and is not covered here

2.5 SURGEARRESTERS

In cases of current chopping, an arc model may be


necessary. A good description of the methodology is available in [16].

Gapless metal oxide surge arresters are characterized with a nonlinear voltage versus resistance characteristic.
Two model types are used frequently in EMTP-type studies
[19]. The pseudo non-linear model, while easy to set up, can
cause computational problems with the solution as the char-

Eaults: Faults are usually modeled as ideal switches in series


with other series elements if necessary. The switch can be

4-4

acteristic can only change at the end of every time-step. The


preferred model is a true non-linear element which iterates at
each time-step to a convergent solution and is thus numerically robust. The V-I characteristic, usually determined from
the 36 x 90 fJ.S surge should be modeled with 5-10 (preferably
exponential as opposed to linear) segments.

Load bus

IL

1r

-I
I
I

(ZS

Waveshape dependent characteristics are usually not


required for most switching transient simulations. Likewise,
the surge arrester lead lengths and separation effects can also
be ignored for such studies. Modeling of the older series
gapped SiC arresters is not discussed in this paper.

_I

-I
---L

....,.....Xc

_-.J

2.6 LOADS
Power system loads are mostly resistive, indicative
of heating and lighting loads, and the active component of
motor loads. The reactive components of motor and fluorescent lighting loads are the other major contributors to power
system loads. In general, the power system load is represented using an equivalent circuit with parallel-connected
resistive and inductive elements. The power factor of the
load determines the relative impedance of the resistive and
inductive elements. Shunt capacitance is represented with the
resistive and inductive elements of the load if power-factor
correction capacitors are used. Whenever loads are lumped at
a load bus, the effects of lines, cables, and any transformers
downstream from the load bus need to be considered [5].
This is particularly important for the modeling of high- frequency transient phenomena. In such cases, an impedance Zs

Fig. 2. Equivalent circuit representation of power system loads


for simulatingswitchingtransients

2.7 SOURCES AND NETWORK EQUIVALENTS


In switching transient studies, the source is modeled
as an ideal sine-wave source. Generators are modeled as a
voltage behind a (subtransient) Thevenin impedance. Often a
network equivalent is used in order to simplify the representation of the portion of the power network not under study.
Some typical network equivalents are shown in Fig. 3
a) Short Circuit Impedance

in series with the parallel R-L-C load equivalent circuit is


appropriate as shown in Fig. 2. The series impedance, combined with the equivalent source impedance at the load bus,
is typically in the range of 10 to 20 percent of the load impedance.
Certain types of load, e.g., large motor loads, electronic loads, or fluorescent lighting loads, may require specific representation of certain load components (e.g.
induction motors, adjustable-speed drives, power supplies,
etc.). The need for such detailed representation will be determined by the phenomenon being investigated.

b) Surge Impedance

c) Short Circuit Impedance + Surge Impedance

Zsc

Fig. 3. Conventional Network Equivalents

Actual power system loads are distributed throughout the system. Some concentration of loads occur in certain
areas. Loads close to the substation can be lumped. Distant
loads can be lumped based on load concentration and represented along lines or distribution feeders described by suitable line or cable models.

The first type a) represents the short circuit impedance (Thevenin equivalent) of the connected system. The XI
R ratio is selected to represent the damping (the damping
angle is usually in the range 75-85). The second type b)
represents the surge impedance of connected lines. This
equivalent may be used to reduce connected lines to a simple
equivalent surge impedance and where the lines are long
enough so that reflections are not of concern in the system
under study. If the connected system consists of a known
Thevenin equivalent and additional transmission lines, the
two impedances may be combined in parallel in the manner
of Fig. 3c. It should be noted however, that this approach
may yield an incorrect steady-state solution if the equivalent
impedance of the parallel connected lines is of comparable
4-5

magnitude to the source impedance. In such a case it may not


be possible to lump the source and lines into one equivalent
impedance.
More complex equivalentswhich properly represent
the frequency response characteristic(as opposed to the ones
above that are most accurate near fundamental frequency) are
also possible [20,21]. Mutually-coupled sources are often
typical for line-fed substations.

2.8 TIME-STEP AND SIMULATION LENGTHS


The time step to be chosen should be small enough
to properly represent the smallest time constant in the modeled system. It should also be significantlysmaller (typically
1/20 th) than the period of the highest frequency oscillatory
component. Additional factors that affect the time-step are
the presence of non-linear characteristics such as arrester
characteristics, and the minimum travel time of travelling
wave cable and transmission line models. Time-steps in the
range of 5 J..1S to 50 J..1S (typically 20 J..1s) are used. The simulation time in typical switching surge studies ranges from 20
ms to 200 ms (typically 50 ms). Slightlylarger time-steps(20
J..1s-50 J..1s) can be used with programs that use interpolation[22], because the linear interpolation method calls for
less iteration of surge arrester characteristics and also does
not introduce spurious current chopping.

3.1.2 Model

The source, transformer, overhead lines, circuit breaker and


the trapped charges (if any) on the line are to be modeled in
order to study the line energizationtransients. In this study a
simple power system is used to demonstrate the simulation
results.
The network configuration of a 345 kV circuit is
shown in Fig. 4. The 345 kV source (1 pu) is connected
through a transformer to the 203 Ian overhead line. The line
was modeled with several pi-sections in the manner
described in section 2.2.1.The parameters are given at 60 Hz
as:
Source and transformer impedance,
Zl = Zo = (6.75 + j127)Q
Line impedance,Zl = (0.04+jO.318) Q/km
Line impedance,Zo = (0.26+jl.015) Q/km
Charging capacitance, C 1 = 11.86 nF/km
Chargingcapacitance,Co =7.66 nF/km

Source (1 pU,60Hz)
203 km transmission line

~---

One simple method for checking the suitable timestep is to check if no further gains in accuracy accrue from
any further time-step reduction.
3. CASE STUDIES
Typical case studies are now presented for a practical demonstrationof the modeling guidelines. Several different examples are considered: Line energization, transient
recovery voltage determination for line and transformer
faults and the switching of shunt as well as series capacitor
banks.
3.1 LINE ENERGIZATION

Aim: The aim of such a study is to determine the overvoltage


stresses and choose the insulation strength in order to achieve
an outage rate criterion [23].
3.1.1 Phenomena:

The energization of overhead transmission lines by closing


the circuit breaker produces significant transients. It is
important to distinguish between two closely related phenomena: energizationand reclosing. In the former case, there
is no trapped charge. In the latter case of reclosing, the line
may have been left with a trapped charge after the initial
breaker opening. In this case, the transient overvoltages can
reach higher values (up to 4.0 pu).

TR

CB

TR - Transformer
CB- Circuit breaker

Fig. 4. One Line Diagramof System Used for Energization Study

3.1.3

Simulation Results

First a statistical overvoltage study is conducted in order to


evaluatethe switching time at which maximum transients are
produced. The results of the statistical energization study
were presented in Fig. 1. Then the effect of various parameters and related issues on the energization transients are studied.
Four, eight or sixteen pi-sections gave similar
results although the maximum overvoltage was slightly
higher with eight pi-sections. No significant improvement
was obtained by reducing the time-step below 50 us,
The overvoltages produced in the presence of
trapped charge on the line depend on the polarity and the
magnitude of the trapped charges. Therefore additional studies were carried out to see the effect of trapped charge on the
line. For reclosure operations, it is assumed that trapped
charges on phases A, B, and Care -0.9, -0.8, and 0.8 per unit
respectively.

4-6

Phase A

Location

Phase B

pu

pu

the switching instant. The peak overvoltages are then determined using statistical switching.

Phase C

pu

Source end

1.272

2.164

2.413

Open end

1.442

2.839

2.784

3.2.2 Model
The first example that was done was a 345 kV pipe-type
(HPFF or high pressure fluid filled) cable. A drawing of the
cable is shown in Fig. 6. The 345 kV cable has 2500 kcmil
segmented conductors with a 1.824 inch diameter, 1.035 inch
of paper insulation with a dielectric constant c = 3.5. The
sheath is 0.01 inch.

Table 2: Overvoltages in the Presence of Trapped Charge

From Table 2 it can be seen that the highest overvoltage magnitude due to the presence of trapped charges is
2.839 pu. The corresponding overvoltage magnitude in the
absence of trapped charges are 2.2 pu (Fig. 1). Typical energization waveforms are shown in Fig. 5.

Corr osive Protective

Coatl"9 . .07 Inch Th;cJ(

......

,, ~~~

Additional studies (not shown) that can be con ducted on this model include the comparison of simultaneous
and non-simultaneous closing of breaker contacts, the effect
of including a closing resistance and including the effect on
surge arrester ratings.

Impregna t ed Paper
Insulation 1.035 inch
Thickness
c - 3.5

2.0

~ 1.0

10.75 inch 0 0 Stoel Pipe

.I.or------I

.25 inch Wall

2.0

2.0

thick, and the sheath resistivity was set to p = 1.0xlO5 Om to


account for the wrapping pitch. A 10.5 inch pipe with a 0.25

inch wall thickness was used; for the pipe a p = 14xlO8 Om


was used. It was assumed that all shields and the pipe were
continuously grounded.

..:

..._..._ .._ . .....

0.0

.1.01------1
-2.0

The cable was energized using the simple power


system, shown in Fig. 7. The energizing was done with a
variety of cable models, including traveling wave and pi-circuit models. A decision must be made about the number of
pi-sections to be used in the model, and the equations from
the preceding section can assist in making the choice. For
the pipe-type cable, the positive sequence propagation con-

2.0

::i 1.0 1 -_ _---,

..:

- 300

Fig. 6. Geometry of 345 kV HPFFcable example.

::i 1.0

Th lckne .s,~

0.0 --.----.

1.0

stant is Y1- 3.75xlO3/km, and the zero sequence propagation


o

10

20

Timc, l'hS

30

Fig. 5. Voltage At OpenEndOf Line on Energization withTrapped Charge

3.2 ENERGIZATION OF PIPE-TYPE CABLE

Aim.:. To determine the maximum overvoltages in the cable.


3.2.1 Phenomena
As in the case of overhead transmission line energization, the
overvoltage in the cable is a function of the point on wave of
4-7

constant is Yo -7.28xlO-3/km . Based on these values, for the


surge impedance of the pi-circuit to be within 10% of the correct value, the pi-circuit section lengths must be less than 239
km based on positive sequence parameters and less than 123
km based on zero sequence. Therefore, the surge impedance
requirements have little impact on the pi-section length for
this short cable . Next, suppose it was desired that the one
way phase shift error be less than one radian at a frequency of
900 Hz. Then, based on the positive sequence parameters 14
pi-sections would be required for the 20 km cable . For the
zero sequence parameters, 38 pi-sections would be required
for this same phase error! A 15 section model was actually

used. In addition, a 3 section model was used to see the


effect of using only a small number of sections.
83454

HIN 1

20 km

tr'8.vellins

3.

83451

we-ve

Hour 1

Cable

c-

Q2

o.
-3.

Fig. 7. Systemfor 345 kV HPFF cable energizing.

15

3.

Cable Model

HIN

HOUT

Traveling wave model with 60


Hz parameters

2.30

2.35

ea,

o.
-3.
3

3.

15 section pi-circuit model


with 60 Hz parameters

2.30

3 section pi-circuit model with


60 Hz parameters

2.25

Traveling wave model with


1000 Hz parameters

2.05

2.10

15 section pi-circuit model


with 1000 Hz parameters

2.05

2.10

pi-sections

pi-sections

2.40

=c-

0.

2.35
-3

0.

milliseconds

50.

Fig. 8. Switching surgeovervoltage for 345 kV cable using various 60 Hz


models.

tr'ave 1 Ii o

3.

wave

Table 3: Maximum switching surges in pu at each end of the cable.

=0-

3.2.3 Simulation Results


The cable was energized with no reactors installed,
to eliminate the influence of other equipment. A statistical
simulation was conducted, consisting of 100 energizations,
using a breaker with a 6 ms pole span and no insertion resistors. The maximum overvoltages obtained are shown in
Table 3 for several cable models. The breaker pole closing
times that gave the maximum voltage at the open end of the
cable for the 60 Hz traveling wave model were then selected,
and deterministic simulations were run using these closing
times. Three simulations were done, using the 60 Hz traveling wave model, the 15 section 60 Hz pi model, and the 3
section 60 Hz pi model. Plots of the voltage at the open cable
end are shown in Fig. 8.

0.

-3.
15

3.

=0-

pi-sections

0.

-3.
3

3.

=-

0-

0.

-3 0

The deterministic simulations were then repeated


using cable models evaluated at 1000 Hz. The results are
shown in Fig. 9. As can be seen from the table, there is little
difference in the maximum switching surge for any of the 60
Hz models. It appears that either the traveling wave model or
pi- circuit model can be used to obtain a switching surge distribution when the cable is energized. The results for the
1000 Hz model are also consistent, but the values obtained
with the 1000 Hz models are considerably smaller than those
obtained with the 60 Hz models. Therefore, it would appear
to be advisable to use a frequency dependent cable model if it
is available.

pi-sections

.
milliseconds

50.

Fig. 9. Switching surgefor345 kV cable overvoltageusing various 1000Hz


models.

3.3 ENERGIZATION OF A SOLID DIELECTRIC CABLE

Aim:. As in the previous section, the aim of this study is to


determine the maximum overvoltages in the cable resulting
from energization. The effect of using different cable modelling options such as various numbers of pi-section or distributed parameters is also presented.
4-8

3.3.1 Phenomena
8 1384

Eddy current losses in the iron pipe around the


cables in an HPFF system discussed above would have considerable effect on the switching surges, resulting in lower
overvoltages as compared to those for the solid dielectric
cables. Therefore, another example was done using a 138 kV
solid dielectric (SD) cable.

8 1381

HIN 1

20 km
Ca ble
Q2

01

Fig. II. Systemfor 138kV SO cableenergizin

3.3.2 Model

Ground Surface

0 .85 inch
insulati on
~ = 2 .3

500 mm 2 conductor
1.031 inc h diameter
0palyethe
. 11 inch
lene
Jacket

h eath

25 em

-i

HOUT

Traveling wave model with 60


Hz parameters

2.05

2.20

15 section pi-circuit model with


60 Hz parameters

2.00

2.15

3 section pi-circuit model with


60 Hz parameters

2.00

2.15

Traveling wave model with


1000 Hz parameters

1.95

2.10

15 section pi-circuit model with


1000 Hz parameters

2.00

2.15

1.2 m

Table 4: Overvoltages when 138 kV cross bonded cable is energized.


0 0 0

The breaker pole closing times were recorded that


resulted in the largest overvoltages at the open end of the
cable when the 60 Hz traveling wave model was used. Then,
deterministic simulations were run with several cable models
using these closing times . The resulting waveforms for the
60 Hz models is shown in Fig . 12. As can be seen, all the
waveforms are very similar, probably because there is little
high frequency content in the switching surge waveform.

0 .11 inch lead

138SD.GCD

HIN

Cable Model

A 138 kV solid dielectric cable with the geometry


shown in Fig. 10 was modelled.The three cables were
installed 1.2 m underground with a 25 cm horizontal spacing
between the conductors. The lead sheath was grounded at
only one end, and the sheaths were crossbonded at 1000 m
intervals.

Fig. 10. 138kV SO cable.

The circuit for energizing the 138 kV cable was


approximately the same as used for the 345 kV HPFF cable,
except of course the voltage levels had to be changed, and
some changes had to be made in the equipment. A typical
138 kV compact design overhead line was used, and the
autotransformer was turned around, with 230 kV used for the
high side transformer voltage . The transformer size was also
reduced to 100 MVA A sketch of the energizing circuit is
shown in Fig. 11. In the several cases simulated, various different models, pi-section as well as distributed parameter
models were used for the cable.

2.

t r av el l i n g

wave

0 .

-2 .
2 .

15

p i - s e c t i ons

o.

3.3.3 Simulation Results


-2.

A series of statistical energizing simulations were


done, and the maximum overvoltages are shown in Table 4.
As can be seen, the values obtained with the 60 Hz models
are very close to each other. The 1000 Hz values are also
consistent, and, unlike the HPFF cable, the 1000 Hz values
are very close to those obtained at 60 Hz. Therefore, the frequency dependent model may not be necessary for the SD
cable.

2 .

:3

p i - se c t i o n s

o.

mi l l i sec o n ds

so.

Fig. 12. Overvoltages whenenergizing 138kV SO cable with various60 Hz


models.

4-9

The deterministic simulations were then rerun using


the 1000 Hz cable models. The results are shown in Fig. 13.
As can be seen, for the SD cable there is not as much difference between the 60 Hz and 1000 Hz results as there was for
the pipe-type cable. Again, this would seem to indicate that
the frequency dependent model is not as important for the SD
cable as it is for the pipe-type.

HIN 1
HOUT 1
o-e-e-------'-.;....;;;.,)-c

HIN 2
HOUT 2
o-e-e---------)-c

2.

:::::::I

c-

o.

Fig. 14. Circuit used to apply pulse to one cable phase.

-2.

15

2.

:::::::I

c-

3.

pi-sections
:::::::I
0..

o.

2.

c-

3.

pI-sectIons
:::::::I
0..

o.
-2 0

wave

- 1

-2.

:::::::I

travelling

100

pi-sections

- 1

.
milliseconds

50.

3.

15

pi-sections

Fig. 13. Results of energizing 138 SD cable with various 1000 Hz models.
:::::"

0..

3.3.4 Simulations for a High Frequency UnitStep


The simulations that were done with the simple
power systems did not result in much high frequency content
in the cable voltage waveform. In order to produce a wave
with more high frequency content, one phase of the 138 kV
SD cable was energized with a 1 pu unit step function. The
circuit used to do the energizing is shown in Fig. 14. Both 60
and 1000 Hz cable models were used.
Fig. 15 shows the result when 60 Hz models were
used. The top curve in the figure is when the constant parameter model is used, the second curve is with the 15 pi-section
model, the third with the 3 pi-section model, and the bottom
with a 100 pi-section model. Because of the high frequency
content in the wave, the limitations of the 3 and 15 section pi
models are now seen. The 100 section pi model seems to be
able to reproduce the high frequencies, but the voltage waveform from this pi-circuit model looks considerably damped
than does the one obtained when the constant parameter
model is used. This leads to some uncertainty about which of
the two models would be preferable.

1.

- 1.
3.

:::::::I
0..

pi-sections

-1

0.

milliseconds

2.

Fig. 15. Results from pulse energizing for 138 kV SD cable with various 60
Hz models

The results from the 1000 Hz models are shown in


Fig. 16. The limitations of the 3 and 15 section pi models are
again evident, although the 15 section model appears to give
reasonably good results. Now, however, the constant parameter and 100 section pi-circuit models give results that are
very close to each other. In the front edge of the first pulse, a
stair step effect can be seen. This is caused by voltages
induced in the other two cables. Some oscillation can also be
seen in these stair steps when the 100 section pi model is
used. These oscillations are probably similar to the Gibb's
phenomenon encountered with Fourier Transforms,

4-10

receiving end circuit breaker after clearing a fault.


3.

:=1

c..

travelling

wave

3.4.1 Phenomena
Consider the circuit in Fig. 17 which shows a fault
fed from a single line "L", which in turn is fed by a bus with
substantial capacity and seven connected long transmission
lines.When a fault at the remote end of a transmission line is
cleared, the receiving end voltage at the remote end oscillates
with a half period equal to the travel time of the line. The
peak magnitude in the lossless case, can be up to twice the
sending end voltage at the instant of fault clearing. This voltage now appears as the TRV across the open breaker. In the
actual case, the slope and magnitude of the TRV is dependent
on the damping present in the system.

- 1

3.
::::s
c..

100

pi-sections

- 1

3 .

15

pi-sections

3.4.2 Model
:=1

c..

The network equivalent (Fig. 18) is of type c) presented in section 2 2.7. The inductance value is obtained
from the short circuit current (30 kA) at the bus. The parallel
resistance is the combined surge impedance (parallel combination) of the 7 unfaulted lines. This representation is appropriate because the lines are long and no reflections affect the
protective device during the transient period under consideration. Note that as the fundamental frequency impedance of
the source (7.04 mH x 377 rad/s) is much smaller than the
equivalent parallel impedance of the transmission lines
(51.57 Q), the warning in section 2 2.7 does not apply. However, when considering unbalanced faults, a full model may
be necessary.

- 1

3.
::::s
c..

pi-sections

-1

0.

milliseconds

2.

Fig. 16. Results from pulse energizing for 138 kV SO cable with various
1000 Hz models.

The following general conclusions can be drawn


from the switching studies presented in subsections 3.2
(HPFF cable) and 3.3 (SD cable):
For both the HPFF and SD cable, when statistical
energizings are done, it appears that either a constant parameter traveling wave or a pi-circuit model can be used. The
overvoltage results are similar with either model. In addition, the overvoltage waveform does not appear to have
much frequency content at 1000 Hz or above, so the number
of pi-sections used for modeling can be evaluated at 1000 Hz
or below.

Line"L"

Multiple Lines

Fig. 17. System for Simulating Single-line Fed Bus Fault

For the HPFF cable, there was considerable difference in the switching surge results obtained with the 60 Hz
and 1000 Hz model. Therefore, if a frequency dependent
model is available, it should be used with the HPFF cable.

51.570

Aim.:. To fmd the Transient Recovery Voltage (TRY) across a

Line
360 0 SUrge Impedance

However, the SD cable results did not change appreciably from 60 to 1000 Hz. Therefore, it is probably acceptable to model the SD cable with a single frequency 60 Hz
model for switching surge simulations

3.4 SINGLELINE BUS FED TRANSIENT RECOVERY


VOLTAGE (TRV)

OOO

pF

600 PF

-=-

Fig. 18. Equivalent Circuit for System in Fig. 17

The line "L" is represented as a low-frequency lossless line with lumped resistance at the midpoint and at the
end of the line. For a 138 kV substation, the available fault
current at the main bus is 30 kA and 3.7 kA at the fault loca-

4-11

tion. Circuit parameters were selected for a 795 MCM line of


length 40 km to the fault location with a surge impedance of
360 ohms.
Lumped bus capacitance of 10000 pF is represented
at the supply station while 600 pF, which is typical for a
small substation, is represented at the station at the end of the
line
3.4.3 Simulation Results

Fig. 19 shows the resultant bus voltage, fault current, and protective device transient recovery voltage. The
protective device recovery voltage is a ramp whose magnitude, neglecting damping, would be 2 times 0.88 per unit
(since about 12% of the voltage is dropped across the source
impedance during the fault), or 1.76 per unit; circuit damping
would reduce this by about 5 to 10%. The time-to-peak of the
recovery voltage is the round-trip travel time of a voltage
wave on a single line supplying the fault. The rate-of-rise of
the voltage ramp is determined by the product of the surge
impedance of the line and the rate-of-change of the fault current. Since the first peak is typically reached in only a few
hundred microseconds, the rate-of-change of a symmetrical
fault current can be considered constant and equal to

mined by the leakage inductance of the transformer and the


effective source impedance as shown in Fig. 20. At the same
time, the transformer secondary-side voltage collapses to
zero, dropping the bus voltage (reduced from its pre-fault
value due to the fault) across the leakage inductance of the
transformer. When the fault is cleared, the source-side bus
voltage recovers in an oscillatory fashion with a frequency
determined by the source inductance and its equivalent
capacitance. If the transformer is located at the end of a line,
the source-side bus voltage will attempt to recover to the prefault voltage level through a ramp, and overshoot. This sets
up a damped "oscillation" on the source side of the protective
device with a period determined by the positive- and zerosequence travel times of the line. For short lines the source
inductance dominates, reducing the magnitude of oscillations
that occur at a higher frequency. The voltage on the transformer side of the switch collapses to zero in an oscillatory
fashion with a frequency determined by the leakage reactance of the transformer and its equivalent terminal capacitance. The resulting switch transient recovery voltage rateof-rise is very steep with a substantial peak value (see Fig.
22).

Jilt .It should be noted that the TRV for a three phase to

138 kV/13.8 kV
80MVA
10.7k Z

ground fault would vary significantly from that for a three


phase ungrounded fault.

Fig. 20. System for Study of Secondary Fault TRV

20

:;-

Faultcurrent

l:!!-

Ie
~~

-20

(J

-100

eD

11:=

-60

~::s

l~

-140

-180

-gal

Fault
Switchtransientrecoveryvoltage

::s

Fig. 21. The Equivalent Circuit for the Case in Fig. 20


-220

3.5.2 Model

Fig. 19. Bus Voltage, Switch Recovery Voltage and Fault Current for a Single-line Fed Bus Fault.

3.5 TRANSFORMER SECONDARY-FAULT TRV (WITH


PRIMARY-SIDE PROTECTIVE DEVICE)

Aim.:. To fmd the TRV on the circuit breaker on the primary


side of a transformer after it clears a secondary side fault.
3.5.1 Phenomena

When a fault occurs on the secondary-side of a


transformer, the relatively large leakage inductance of the
transformer will limit the magnitude of the fault current
through the primary-side protective device. When the fault
occurs, the source-side bus voltage drops to a level deter-

To illustrate the transient recovery voltage that


occurs across the primary-side protective device when a
transformer secondary fault is cleared, consider the system in
Fig. 27 (Case D). Assume that a fault occurs on the secondary side of the 80 MVA 138 kV/13.8 kV radially fed transformer. Based on the 10.7% transformer impedance, the
inherent 3-phase fault current of the transformer is approximately 3.1 kA. Because of the source and line impedances,
the 3-phase secondary-fault current magnitude is further limited to about 1.0 kA. To simulate the protective device transient recovery voltage, the transformer can be represented as
shown in Fig. 21. Transformer terminal capacitances are calculated from the transformer oscillation frequency when a
fault on the one side of the transformer is cleared from the

4-12

other side. Representative frequencies for power transformers are reported by Hamer and Rodriguez [24]. For the 138kV winding, the frequency of oscillation is approximately 9.6
kHz, while that of the 13.8-kV winding is approximately
72 .3 kHz. The high-frequency capacitive coupling ratio
(i.e., Ch t / ( Chi + CI) ) is generally lower than 0.4 and was

3.5.3 Simulation Results

Fig. 22 shows the transient recovery voltage for the


switching device, the source-side and transformer-side voltages, and the 138 kV substation bus voltage for interrupting a
fault on the secondary side of the transformer.

selected to be equal to 0.2 for the simulation. As described in


section 2.2.2, the capacitance is calculated from the known
winding frequencies.

0.5

/1

"e -D.5

:r
1

The effective terminal capacitances can be determined based on the frequency of oscillation of each winding
by using the equation C

= 1/[(21tj)2 LT]

frequency of oscillation of each of the windings in Hz, L T


(Henries) is the transformer leakage inductance (referred to
the winding of interest) and C (Farads) is the effective capacitance. For the high-voltage winding:
C=Ch+Ch/

and, for the low-voltage winding :

"E
:

8:

-1

-1.5

-2

Protective device transient


recovery voltage

Fig. 22. Source, Transformer Side and 138kV substationBus Voltages for a
Secondary Side Fault on a 80 MVA 138kV/213.8 kV Transformer

3.6 SHUNT CAPACITOR SWITCHING

C = C l+ Chi
Based on the winding frequencies, and the transformer leakage inductance of 67.48 mH (referred to the highvoltage winding), the winding terminal capacitances are:

= 2.64nF
Chi = 1.44 nF
C l = 5.75 nF
Ch

Due to high-frequency winding resistance and eddy


current losses, the oscillations are damped . This damping is
represented by the resistance to ground in the equivalent circuit shown in Fig. 21. For most transformers the damping is
usually such that the damping factor (i.e., the ratio of successive peaks of opposite polarity in the oscillation) is on the
order of 0.6 to 0.8. A conservative value of 0.8 was selected
for this simulation. The time between peaks (of the same
polarity) of the oscillation is: 1/f = 21tJLC ,hence, for an
assumed damping factor, DF, the high-frequency damping
resistance, RD ' can be calculated using the equation:

-1t~

RD

:I

,wherefis the

= InDF

where L is the effective leakage inductance of the transformer (referred to the winding of interest) and C is the effective capacitance of the winding of interest.
Based on the transformer leakage inductance of
67.48 mH and the terminal capacitances, the high-voltage
winding damping resistance is equal to 57.3 kO and that of
the low-voltage winding is 7.48 kU

Aim:. To present by example, modeling guidelines that should


be observed when simulating capacitor switching transients .
A brief discussion of the transient phenomena associate with
capacitor switching is presented as background to the case
study used to illustrate modeling guidelines. Understanding
the transient phenomena associated with any simulated event
will allow a model of sufficient accuracy to be created while
avoiding needlessly complicated models that waste computer
and engineering time.
3.6.1 Phenomena

Capacitor switching can cause significant transients


at both the switched capacitor and remote locations. The
most common transient problems when switching capacitors
are (1) overvoltages at the switched capacitor during energization, (2) voltage magnification at lower voltage capacitors
during capacitor energization, (3) transformer phase-to-phase
overvoltages at a line termination during capacitor energization, (4) arrester energy duty during capacitor breaker
restrike, (5) breaker current due to inrush from capacitors at
the same bus as a capacitor being energized and (6) breaker
current due to outrush from a capacitor into a nearby fault.
Although all of these phenomena can be initiated by capacitor switching or fault initiation near a capacitor, they each
produce different types of transients that can adversely affect
different power system apparatus. Some of the phenomena
also have different modeling requirements. Each phenomena
is briefly discussed before being illustrating by example.
3.6.2 Switched Capacitor Overvoltages During Energization

Energizing a shunt capacitor from a predominately


inductive source results in an oscillatory transient voltage at

4-13

the capacitor bus with a magnitude that can approach twice


the peak bus voltage prior to energization. The characteristic
frequency of the energization transient is:

j=

2rcJLsC

The highest transient voltages, on a per unit basis, occur at the


lower voltage capacitance (C2) during capacitor C1 energization when (1) the capacitive Mvar rating of C 1 is significantly
greater than that of C2 and (2) the natural frequencies fi and h
(as defined below) are nearly equal.

where: L s = source inductance (Henries)


C = capacitor bank capacitance (Farads)
This energization transient can excite system resonances or
cause high frequency overvoltages at transformer tenninations. The magnitude and duration of the energizing voltage
transient is dependent upon a number of factors including system strength, local transmission lines, system capacitances,
and switching device characteristics. Voltage transient magnitudes increase as system strength is reduced, relative to capacitor size. In addition to reducing system surge impedance and
increasing system strength, transmission lines provide damping. These three characteristics of transmission lines help reduce capacitor energizing transients. Other capacitors in the
vicinity of a switched bank help reduce capacitor energizing
transients because they reduce system surge impedance.
Switching devices can be designed to reduce transients by using closing control, pre-insertion resistors, or pre-insertion inductors. The closer to zero voltage at which a capacitor is
energized, the lower the resulting transients. The optimum
closing resistor size is approximately equal to the surge impedance of the source inductance and capacitor bank capacitance
as calculated below:
R
=
optimum

where:

h
~C

L s = source inductance (H)


C = capacitor bank capacitance (F)

3.6.3 Voltage Magnification at Lower Voltage Capacitors


Normal capacitor bank energizing transients, which
are limited to twice the pre-switch capacitor bus voltage, are
not a concern at the switched capacitor location. Significant
transient voltages can occur at remote capacitors or cables
when magnification of the capacitor energizing transient
occurs. The simple circuit in Fig. 23 illustrates the voltage
magnification phenomena.

Fig. 23. CircuitIllustrating VoltageMagnification

The magnitude of the voltage magnification transient at C2 is


dependent on switched capacitor size, source impedance, the
impedance between the two capacitances, system loading, and
the existence of other nearby low voltage capacitors. Moderate
increases in distribution system loading can significantly reduce voltage magnification transients. Because transformer
losses increase significantly at higher frequencies, modeling
the frequency dependence of transformer losses, or simply
modeling the transformer X/R ratio at the capacitor's natural
frequency, can improve model accuracy and reduce the severity of the voltage magnification simulated. Controlled breaker
closing, pre-insertion resistors, or pre-insertion inductors can
be used to reduce voltage magnification related transients.
Voltage magnification can also cause excessive
energy duty at arresters protecting distribution capacitors.
High energy arresters may be necessary if other methods of
reducing voltage magnification are not implemented.
3.6.4 Transformer Termination Phase-to-Phase Overvoltages
Capacitor energization can initiate traveling waves
that will increase in magnitude when reflected at transformer
terminations, These reflected surges will be limited to approximately two per unit by the transformer line-to-ground arresters. Four per unit phase-to-phase voltage transients can be
caused by 2 pu surges of opposite polarity appearing simultaneously on different phases. This four per unit switching transient may exceed a transformer's switching surge withstand
capability. IEEE standards do not specify transformer phaseto-phase switching surge withstand capability. As a worst case
assumption, the phase-to-ground withstand could be used, but
a value closer to 3.4 pu is probably more realistic. The transformer manufacturer should be consulted to determine the
phase-to-phase switching surge withstand voltage of a specific transformer,
System short circuit capability and the number of
lines at the switched capacitor location do not significantly
affect this phenomena. Switched capacitor size affects the frequency of oscillation that occurs when a capacitor is energized, and thus the voltage that the traveling wave component
of the transient rides on, but no generalization relating capacitor bank size and reflected phase-to-phase transient can be
made. Radial line length may have a more predicable effect.
Higher phase-to-phase transients often occur on longer lines
as the traveling wave oscillation peak begins to match up with
the natural frequency of the capacitor energization transient.
Oscillations that occur on very short lines may also be impor4-14

tant, as they have the potential for exciting transformer internal resonances.
As with other capacitor switching related transients,
these transients can be reduced by the use of synchronous
closing control, pre-insertion resistors, or pre-insertion
inductors.

3.6.5 Capacitor Breaker Restrike Arrester Energy Duty


Arresters applied at large shunt capacitors should be evaluated for their energy duty during capacitor breaker restrike. This
is true even when the capacitor breakers are designed to be
"restrike free."
There are several methods of determining arrester
energy requirements during the first capacitor breaker
restrike. The energy during subsequent restrikes can be much
higher, but is usually not considered when sizing arresters.
The chart shown in Fig. 24 [25] can be used to determine
arrester energy duty based on arrester protective level and
capacitor size. Hand calculations which include the effects of
capacitor size, can be used to more accurately determine
arrester energy requirements. The equations for hand calculating arrester energy during restrike of a grounded capacitor
is shown below. The details of the hand calculation for both
grounded and ungrounded capacitor can be found in [25].

Because both the chart and hand calculation methods do not


include the effects of system losses, loads, or transmission
lines, the arrester energy requirements determined by them
will be conservatively, but not excessively, high. The most accurate method of determining arrester energy requirements
during capacitor breaker restrike is to simulate the restrike
event using a detailed transient model. The transient simulation should model the system in detail at least two busses in
each direction from the capacitor.
It has been reported that the energy handling capability of an arrester during capacitor restrike is significantly
less than the published arrester energy handling capability.
Some derating of arrester energy ratings may be required
because of the high magnitude currents which may be associated with capacitor restrike transients. The arrester manufacturer should be consulted to determine the level of arrester
energy derating, if any, is necessary.

3.6.6 Inrushfrom Another Capacitor During Energization

The inrush currents associated with back-to-back


capacitor switching must be evaluated with respect to the
capacitor switch capabilities and overvoltages on CT secondaries. A circuit illustrating back-to-back switching is shown
in Fig. 25.
The equations for calculating current magnitude and
frequency are shown below.

(joules)

I
where: C = Capacitor Capacitance (farads)
Vp = Arrester Protective Level (volts)
Vs = Peak Line-to-Ground Voltage (volts)

= Vel f =
z '
2n~Leq

where:

I x

f =~
2nL eq

=Voltage across Cl as switch closes


Ll, L2 = Self Inductances of Capacitor Banks
L3 = Inductance between Capacitor Banks

VCl

Z =Surge Impedance

10.0

x Ceq'

= J~eq,

L eq

=L1 + L2 + L3,

eq

DUTY

1.5

p~r ]
Cap

Mvar

5.0

2.5

O.O--_""'--_ _...a-._ _~ - -........--..;;:I~

1.5

1.8

2.1

2.4

2.1

ARRESTER PROTECTIVE LEVEL(PU)

Fig. 24. MOV Arrester Duty for Capacitor Switch Restrike

3.0

ANSI Circuit Breaker Standard C37.06 contains


specific inrush current magnitude and frequency limits for
general and definite purpose breakers. Although hand calculations are very accurate in determining inrush currents, a
simple model that includes all impedances between the energized and switched capacitors is all that is necessary to simulate back-to-back switching inrush currents. If the inrush
currents calculated are excessive current limiting reactors can
be used to bring them within acceptable limits. The size of
the current limiting reactor necessary to limit the inrush current to an acceptable level can be estimated by rearranging
4-15

the equation for Ixfabove as shown below and using peak


pre-switch current and voltage values:

Breaker

S~stem
L =
eq

Vel
2JZ(Ixf)

3.6.7 Current Outrush into a Nearby Fault


Current outrush from a capacitor can be a concern
when a breaker closes into a fault. For general purpose breakers, ANSI standards indicate that the product of the outrush
current peak magnitude and frequency is limited to less than
severe, generally 6.8 x 107 . Fig. 26 illustrates the capacitor
current outrush phenomena
The equations necessary to calculate peak current
and frequency are shown below.
1=

where:

VCl

,f= 21t

VCl

rrc-' Ixf= Aj~eq'-'eq


21tL

eq

VCl = Voltage across C 1 when Switch Closes

L1 = Self Inductance of Capacitor Bank


L3 =Inductance between Capacitor Banks

Z= SurgeImpedance =
Leq = L1 + L3,

Breaker

L3

2 x 107. The limitation for definite purpose breakers is less

I
~

Ll

CiT

Vel

L2

JC2

Fig. 25. Circuit Illustrating Back-to-Back Switching

~,

~~

S~5tem

Ceq = C1

If outrush currents are a concern, they can be


brought within limits by the use of outrush reactors. The
reactor size can be quite accurately determined by the following equation when peak pre-switch voltage and current
values are used:

L
eq

Vel

2 JZ(Ix f)

faul t

3.6.8 Additional Concerns


In addition to the capacitor switching phenomena
listed above, which will be illustrated in the example later in
this paper, there are two other capacitor switching phenomena that should be considered. The fITst is dynamic overvoltage. Dynamic overvoltage may occur when energizing a
capacitor and transformer simultaneously during fault clearing and line re-energization. During line faults, even if the
capacitors are normally switched separately, the bus transformer and capacitor bank may be de-energized and subsequently reenergized together with the line. The resulting long
term, low magnitude, but high energy, overvoltage cannot be
effectively limited by surge arresters. It must be controlled
by using an acceptable switching scheme.
4-16

L3

Ll

I~
Cl

Fig. 26. CircuitIllustratingOutrush Switching

Another concern when switching shunt capacitor


banks is internal overvoltages at remote transformers. These
overvoltages are a function of the switching transient and
transformer internal resonance characteristics. Transformer
terminal arresters may not adequately protect for this condition. Possible solutions include (1) capacitor switch preinsertion resistors or reactors and (2) capacitor bank reactors.
3.6.9 The Model

A one line diagram of a three-phase transient model


assembled to illustrate capacitor switching phenomena is
shown in Fig. 27. The individual components of the model
are discussed below.

Source: The system source is modeled as an ideal voltage


source behind a system equivalent impedance. The equivalent
impedance consists of both positive and zero sequence inductance and resistance. The ideal voltage source magnitude is
set so that the 138 kV bus voltage prior to capacitor energization will be 1.025 pu. The actual magnitude can vary depending upon system loading and capacitor operating procedures.
In this case the positive sequence equivalent impedance is 5.8
ohms reactive and 0.58 ohms resistive and the zero sequence
system equivalent impedance is 5.0 ohms reactive and 0.50
ohms resistive. This results in a 138 kV bus three phase fault
current of approximately 13.7 kA and a single line-to-ground
fault current of approximately 14.3 kA.

_-+-_SOURC
EQ138

TRTER

40 MVar

40 MVar

LOAD

TR138
13.8 kV

Fig. 27. One Line Diagram of Transient Model

Capacitors: Three capacitors are modeled. There are two 40


Mvar (5.571 microfarad) capacitors located at the 138 kV
equivalent source bus. These capacitors are each equipped
with 0.15 mH reactors to limit back-to-back switching currents and a common 1 mH reactor to limit outrush currents.
How these reactor sizes were determined is presented in subsection 3.6.10. The third capacitor (3.6 Mvars or 50.10
microfarads) is located on the low voltage side of the 138/

13.8 kV transformer located at the 138 kV equivalent bus.


All three capacitors are grounded.

Loads: Two loads are modeled, each half the peak system
load. Both are modeled as parallel resistance and inductance
elements. The first load (90 +j40 MYA) is modeled at the 138
kV equivalent source bus. This load contains series as well as
parallel components to represent the impedances of transformers not explicitly modeled. The load fed from this bus is
assumed to have a uncorrected power factor of about 90% and
a corrected power factor of 100% when both 40 Mvar capacitors are in service. This full load condition is represented by
parallel resistive and reactive loads of 180 Mvars (105.8
ohms) and 80 Mvars (238.05 ohms) respectively. Full load is
represented by half this load when one 40 Mvar capacitor is in
service or to be switched into service.
The second load (1.8 + jl.8 MYA) is modeled on the
low side of the 138/13.8 kV transformer located at the same
equivalent source bus. This load has an uncorrected power
factor of 70.7% and a corrected power factor of unity. With a
3.6 Mvar capacitor placed at this bus, this means that the
resistive and reactive components of the load at this bus are
both equal to 3.6 Mvars (52.9 ohms).
Load modeling is very important because loads help
attenuate and damp out capacitor switching transients. Simulations with no loads modeled will produce transients that are
much higher than those found on the actual system. Similarly, models with the entire load modeled at higher voltage
busses rather than dispersed at lower voltage busses will simulate transients lower than those on the actual system.
Because of the limited size of the model used to illustrate
capacitor switching phenomena, accurate load modeling is
not possible. The model would have to be expanded about
two busses out in all directions to model loads with reasonable accuracy. To help compensate for this, loads half the size
ofthose described above are placed at the appropriate busses.
In a real study the effect of load modeling and
model size must be analyzed. The best way to optimize the
size and detail of a model is to keep adding to the modeled
area until the transients are no longer affected by additional
components. Because this can be time consuming, rules of
thumb, such as modeling the system one or two busses from
all locations of interest, are often used when assembling transient model.
TransfQnners: Two transformers are modeled. They both include 138/13.8 kV transformations, but their locations and
winding configurations are different. The transformer at the
equivalent source bus is an 18 MYA rated three winding
transformer with primary (138 kV) and secondary (13.8 kV)
grounded wye windings and a delta tertiary (4.8 kV). The
high, low, and tertiary impedances are represented as 39.44%,
0.01%, and 17.78% on a 100 MYA base. The transformer XI
R ratio was assumed to be 20. Saturation was modeled with a
knee point of approximately 1.15 pu. The remote transformer
is an 80 MYA rated two winding transformer with grounded
wye primary (138 kV) and delta secondary (13.8 kV) windings. The transformer impedances is 10.7% on its 80 MYA

4-17

base. Half this impedance is modeled on each winding . The


transformer X/R ratio was assumed to be 20. Saturation was
modeled with an approximately 1.2 pu knee.

200 kV

Lioe Mode)' The line modeled is a 40 km long 138 kV line


connecting the equivalent source bus with the remote bus
labeled "TRTER". The line uses 477 ACSR "Hawk" conductor in a horizontal configuration. The conductor has 27 aluminum strands and 6 steel strands, a DC resistance of 0.1221
ohms per km at 25 degrees C, and a geometric mean radius of
0.884 em. Because of the need to accurately model voltage
reflections at transformer terminated lines, this line was modeled using a frequency dependent distributed parameter
transmission line model.

-200 kV
Fig. 28. Maximum 138 kV Cap Bus Voltage (HalfLoad)

Surge Arrester Mode)' Following normal practices on solidly


grounded 138 kV systems, a 108 kV station class gapless
MOV surge arrester was included at the capacitor location.
The non-linear arrester characteristic is modeled by a number
of exponential segments based on the arrester's 36/90 usee
current/voltage characteristics. Arrester energy was monitored during capacitor breaker restrike.

The voltage at the 13.8 kV bus was 3.06 pu in the


half load case (Fig . 29), indicating a voltage magnification
condition . This voltage was 4.202 pu in the no load case and
2.364 pu in the full load case. These three cases demonstrate
the effect of system load modeling.
40 kV

Fault Model ' The fault model used in the outrush simulations is a 0.1 milliohm resistance in series with an ideal
switch. When the fault is initiated, the switch is closed and
when the fault is cleared the switch is opened.

20 kV

3.6.10 Simulation Results:


Simulations were run to illustrate four different
capacitor switching events: capacitor energizing, capacitor
breaker restrike during de-energization, back-to-back capacitor inrush, and capacitor outrush into a fault. Each of these
events are discussed below.
Capacitor Energization: Capacitor energization was simu lated to demonstrate three different phenomena. The first is
the transient overvoltage at the switched capacitor location.
The second is voltage magnification at a lower voltage
capacitor. The third is phase-to-phase overvoltage at a transformer terminated line.
The capacitor energizing simulation used 100 statistical switching events to determine the worst case overvoltage . With the half load model, the worst overvoltage
simulated at the 138 kV capacitor location was 1.805 pu (Fig.
28). This transient's peak value was 2.032 pu in the no load
case and 1.695 pu in the full load case.

-40 kV
Fig. 29. Voltage Magnification (Half Load Model)

As discussed before, for voltage magnification to


occur, there must be two circuits resonant at about the same
resonant frequency. The first circuit is usually the source
impedance and switched capacitor and the second is usually
a low voltage capacitor and a transformer. The resonant frequency of the first circuit in this example is 544 .1 Hz as
shown below . The 138 kV 40 Mvar capacitor has a capacitance of 5.571 j.l.F and the system equivalent positive
sequence impedance has a inductance of 15.39 mH (5.800
Q) .

f, 1 -

1
_
1
= 544.IHz
2fffLC - 2~15.36mHx5 .571,tF

The resonant frequency for the second circuit, the


low voltage capacitor and the capacitor connecting it to the
switched capacitor bus is 543.6 Hz as calculated below. The
13.8 kV 3.6 Mvar capacitor has a capacitance of 50.1 j.l.F and
the transformer has an impedance of 1.711 mH (0.6452 Q).

4-18

f =
2

2tNLC

2;r,j1.71lmH x50.l,tF

Juu kV

= 5416Hz

Voltage magnification results from the fact that the


two resonance frequencies are so close together.
The third phenomena of concern during capacitor
energization is excessive phase-to-phase voltages at the end
of a transformer terminated line . As previously discussed, if
this value exceeds 3.4 pu there should be some concern for
the transformer insulation. In the half load case, the maximum phase-to-phase voltage simulated at the remote transformer 's 138 kV terminals was 4.895 pu (Fig. 30). Phase-tophase overvoltages of 5.286 and 4.673 were simulated under
no load and full load conditions. All of these voltages were
simulated without arresters modeled. If arresters were modeled at the transformer terminals, the phase to phase overvoltage would be limited to twice the arrester discharge
voltage, appro ximately 4 pu.
Breaker Restrike: The most severe energy duty for arresters
applied at capacitor bank locations is often when a breaker restrikes as a capacitor is taken out of service. For capacitor
switching transients, an arrester's kJ/kV rating may be have to
be derated. The arrester manufacturer should be consulted to
determine the derating for a specific arrester. Since a properly
functioning breaker will always open at a current zero, statistical simulations are not required when simulating capacitor
restrike. Generally only one phase of a breaker will restrike
and, while the phase may reopen soon after the restrike , restrikes are often simulated as being permanent. Restrike is
most severe when it occurs at the time of peak breaker transient recovery voltage (TRY). The breaker TRVs simulated
when a restrike occurs as both 40 Mvar capacitors in the half
load model are opened is shown in Fig. 31.

-200 kV
-JOO kV

Fig. 31. Restrike Breaker TRV (HalfLoad Model)

The 108 kV Station Class arrester modeled has a switching


surge protective level of 200 kV line-to-ground, 1.775 pu on
the 138 kV system. According to Figure 2, this arrester would
have to be able to dissipate about 6 kJ/kV of arrester rating.
This may be excessive after derating the normal 7.2 kJ/kV of
rated voltage (8.9 kJ/kV ofMCOY) of a station class arrester
energy used for capacitor protection. Under this condition
transient simulation is necessary.
Simulated arrester voltages during capacitor breaker
restrike are shown in Fig. 32.
The simulated energy duty of the capacitor arrester,
263 kJ, is shown in Fig . 33 . A 108 kV station class arrester
can be expected to be able to dis sipate about 778 kJ under
normal conditions. Derating the arrester energy handing
capability by half for capacitor breaker restrike still gives 389
kJ of capability, well above the 263 kJ required. Although
not examined in this case, arrester energies at remote capacitors where voltage magnification may occurred should also
be monitored.
300 leV

600 kV

200 leV

400 kV

200 kV

o kV-f---'<---+f-t-

-300 leV

Fig. 32. ArresterBus Voltages DuringCapacitorBreakerRestrike


-600 kV

Fig. 30. Ph-to-Ph Voltage at Remote Transfo rmer (HalfLoad)

4-19

Figure 5. In this case the reactor size was calculated to be


0.942 mH, as shown below.
300 kJ

L=

200 kJ

Vmax

2 JZ(I x f)

= l18.3lkV = 0.942mH

2 JZ(2 X 10 7 )

100 kJ

An outrush reactor value of 1.0 mH was used to simulate this


event. This simulation gave a peak current (first current peak)
of 1,966 amps at a frequency of9,454 Hz. This results in an I

okJ .J...-..-t-----+--+-~-_t_-_+__-+_____t-__+_-.....;
.885

.81

Seconds

.815

.82

.8Z5

Fig. 33. ArresterEnergyDuringBreakerRestrike

Capacitor InDlsh During Back-to-Back Switching The concern during back-to-back switching is that capacitor inrush
currents will exceed breaker ratings. The magnitude and frequency of the inrush current can exceed breaker capabilities
if the impedance between the two capacitors is too low.
Breakers applied between two capacitor banks at a single bus
are usually definite purpose breakers. According to Table 3A
of ANSI/IEEE C37.06, the product of the breaker current
magnitude and frequency must be less than 6.8 x 107 (16 kA
times 4250 Hz) for definite purpose breakers.
An equation for calculating the inductance necessary to limit the I x f product to an acceptable level was given
in subsection 3.6.6. With Vmax equal to the peak line-toground voltage, times a conservative 1.05 pu voltage, the
inductance necessary to meet the 6.8 x 107 breaker rating can
be calculated to be 0.277 mH or 0.139 mH per capacitor as
shown below. Some of this inductance may be supplied by
the buswork between the two capacitors. Buswork rated for
use on 138 kV systems is usually considered to have an
inductance of 0.9 JlH per meter.

L=

Vmax
= 118.3lkV = 0.277mH
21Z{I x f) 21Z{6.8x 10 7 )

Back-to-back capacitor switching inrush currents are independent of load or nearby system components. Inrush currents
were simulated with a with a 0.15 mH reactor in series with
each 40 Mvar 138 kV capacitor. This resulted in a peak current of 12 kA at a frequency of5.5 kHz, giving an Ix/product
of 6.6 x 107, below the 6.8 x 107 limit.
Capacitor Outmsh into a Fault The concern during capacitor outrush into a fault is again breaker I x / ratings, but
because the fault current may go through a general purpose
breaker rather than a defmite purpose breaker, the breaker I x
frating will probably be a much lower 2.0 x 107 rather than
6.8 x 107. The equation derived in subsection 3.6.7 can be
used, but the I x f product will be different and the reactor
must placed so that the fault current discharged from both
capacitors will have to flow through the reactor to get to the
main bus, as shown between busses CAP40 and CPOUT in

xfproduct of 1.86 x 107, which is below the 2.0 x 107 limit.

3.7 SERIES CAPACITOR SWITCHING


Series capacitors may be installed on transmission
lines to increase power transfer capability. Electromagnetic
transient studies are required to determine the impact of the
series compensation on the existing system to ensure safe
and reliable operation.
~To evaluate several aspects of system performance,
including the following:
Surge Arrester Sjzjng Establish surge arrester duty and
related protection settings for the capacitor bank.
Line Protection Investigate relay requirements.
Line Breaker Transient Recoyery Voltage (TRY) Determine the transient recovery voltage for the transmission
line breakers of the compensated line.
Line Energization Investigate system behavior when the
compensated line is energized.
Bank Insertion and Bypass Investigate system behavior
when the series capacitor is bypassed or inserted.
Single-phase Reclosing Determine line end arrester
duty for single-phase reclosing operation.
Simulated events include varying size and location
of the series capacitor. However, these are generally determined by steady-state, transient stability and subsynchronous
resonance studies and by relaying requirements which are
not applicable to this document. Additionally, minimum and
maximum generator conditions may also be considered.

3.7.1 Model
Fig. 34 shows a representative system to be studied.
The system model typically includes lines and transformers
at least one bus back from the switching locations of interest.
Transmission lines are modeled as distributed parameter
lines considering their positive and zero sequence characteristics. Transformers are modeled using the saturable transformer component model which represents each winding of
the transformer as well as its saturation characteristics. One
bus away are equivalent sources modeled as mutually-coupled elements considering their positive and zero sequence
characteristics. Series capacitors and other system components are modeled as lumped circuit elements with typical
quality factors represented. Also pertaining to series capaci-

4-20

tor modeling are its associated components such as the


bypass breaker with its series reactor and the surge arrester
connected across the series capacitor. The surge arrester
model uses the 36x90 us voltage-current characteristic,
3.7.2 Phenomena and Simulation Results
The worst case fault conditions that keep the capacitor bank inserted determine the maximum surge arrester
energy requirements. The case list includes three-phase, double-phase and single-phase faults. Also considered are single-phase reclosing events under fault conditions: the line
end breakers open on the faulted phase only to clear the fault,
and then one end recloses.
Line protection may be evaluated by monitoring
currents that would flow in the line relays during three-phase
and single-phase faults which are internal or external to the
capacitor bank.
The maximum TRV of line breakers may be evaluated by applying three-phase and single-phase faults at various locations along the line and at the series capacitor. In
some cases arresters or pre-insertion devices may be required
to reduce the TRV to acceptable levels.
The effect of energizing the series compensated line
with and without the capacitor bypassed can be evaluated.

should be simulated under varying power flow and other


operating conditions. The bypass switch TRV is evaluated
from the simulation of capacitor bank insertion. The simulation of capacitor bypass determines the inrush currents.
Results are compared to the withstand ratings at the breaker
and its series reactor.
Waveforms of sample results are shown 5 for these
switching transients cases:
i ) Single-Phase Fault, Clearing, and Reclosing (Fig. 35)
ii) Three-Phase Fault at Middle of Line and Clearing (Fig.
36 and Fig. 37)
iii) Series Capacitor Bank Insertion (Fig. 38)

4. CONCLUSIONS
This report presented general rules for the study of
switching surges using electromagnetic transients simulation.
The main goal is to have as simple a model as possible without a significant loss in accuracy. In addition to the modeling
representations, general concerns such as the time-step to be
used and the extent of the system to be studied were also
addressed. The modeling techniques were illustrated with
case studies on line energization, TRV, shunt capacitor bank
switchings and series capacitor bank switchings.

The impact of capacitor bank insertion and bypass

BUS 1

BUS2

115KV

115KV

69KV

69KV

Fig. 34. SystemModelfor SeriesCapacitorStudy

4-21

:~ :~I

:'1iFiIr-

1:] . . : .. ; .. : :

0Jl0~

o..oor.. . . .", "' . . ... . . . . . .

'~ J
O.llOJ

~
. : : :~
: .: : : : :

~1 : : : : : : : : : :

t:

'~ ~~~!A~

ILQDJINII ..,".',\\y.tNItYo ~ ,

0..00
.1llO

-a.IlO

Bus 2 115 kV [pu]

0.00

:::::.:::.

~----------

Capacitor Current ll'u -Irated]

, :j~
:~ :] ... =]1.--_
:~~]
~j
: ~ :jW/N'~'

4.00

0..00

a2S

'.

OJll

0Jl0

iii

iii
a2S

I~;::=;r=;::=;r=;=r=r=r=;=::;
I

iii

0..00

lI.5O

Time In Seconds

Time In Seconds

Q.2S

Time In Seconds

Fig. 35. SimulationResults: Single-PhaseFault, Clearing,and Reclosing

j f\ ~ ~ ~

Bus 1 115 kV [pu]

I~

~f

I~

'..

Bus 2 115 kV [pu]

:jA~I\~I\~A6Ai

'I~ V. -r~\TV'(V. Q.V.


~ 'I\ ' h h ~ .~ '~ A 11
\TV\} VlJ

I ~

~Jf\fJ"lVVoJIMP
Ii'

0.0

0.1

1.IlO

~~

OJlO\)YtYVv

.1.00

'

Time in Seconds

iii

lU

'

: :.L r e l

Ctlen~ lkAl

'1.IlO ~

: L_lll

flf\f\

:}fA~~~~~AAI\
V\TV~VV \{\[v

: PdtANIJ./ . .

.
ITV\Jv \T\ :14MMJ
"

I\Of\Of\

o.ooVV\TV

i\ i

ITVlJVlJ

1\

O~ 1/\JVV\I
IJO

~ Af\

Capacitor Voltage [pu-Vrated]

~t-J1MM

~'I

..

1.IlO~

~L1llJi

:~

:~:(2~
:LJ1ill:L ." =] .>:
'1JO~

:HM--- :1 ~ .
0.00

0.0

0.1

Time in Seconds

lU

Ii

0.0

Tim e in Seconds

Fig. 36. Simulation Results: Three-Phase Fault at Middle of Line and Clearing

4-22

ii

0.1

0.2

!J~er ~ [pu].
"

.
.

.
.

,.
2

B~!=r ~ghtlpu]

0+----------------

-,-;.

.. ,,--i--T-,;-;,-r---;-';-;'--+--;-i---r-r--r-;;-T--;-"';'-;-;--T-';-;'--i--+-';-;'--+---;-;--;'--+-";-;--;---+-";-i---r-i
i
i
i
I
i
a.ooo
O.CW
O.ll5O
cum
0.100
0.12'

Time In Seconds

Fig. 37. SimulationResults: Three-Phase Fault at Middleof Line and Clearing

Bus 1 115 kV [pu)

Capa citor Volta ge [pu-Vrated]

:JNvVNrNVV. ::]

::: ] .A~WM~A o.33::'J

'1.00 ]

1~1

'

f\f\f\/\f\f\f\f\f\/\

.: VlJ VVV V\TV ~

'$p
'I~O V VYV\f\TV'! V.
f\f\f\f\/\f\/\/\f\/\

CUlO

Bus 2 115 kV [pu]

: j"A"AA""AAj
VV VVlJ \[\{\TVlJ

.\ .00

V. . . . . . . .o.~

. ur. re.nt .I ~ ]
A.rr.ester C

i\~i\~A~AA/:J

\JVV\J\) V \TV\)

o.~

\T\T~V

0.00 ]

1.00

f\ rd\ /\ 1\ /\ 1\ 1\
V \Tv V \TVlJlJ \.

1\ ' /\ ' /\ ' /\

V VlJ V. \.

Capacitor Current [pu-Irated]


0.730 ]
. f\ .
f\ ' f\ '

0.00 ]
0.3'~

A'/\.A A' A'/\ ' 0.4$~

\fIrV\TVVV .

AI\I\I\I\/\/\/\/

J VV V V V vVvlJ ]
A
'1\ '1\ '1\ . o.~ ]

1.00 ]

A 1\/\ 1\ /\ 1\ 1\ /\ 1\
V

Ar res ter

En~ rg,v

[M.lJ .

.:J lfVVITVVVV\",,: J ~
J .Ar\ At\ t\ t\ t\ r\ f :: ] :'. . . . z
:N\AAAAfNVt VV VlllJ \[VV ]

1.50

.0.:

:YII

~1~

/I /I /I /Iii Ii /I /I
\T\fV
\TV \[\{VlJ .

u o I i i
0.0

0.1

Time In Seconds

ii
0.2

0.:

.o.7S0

] V

=====

0.00

J . AAi\ Ai\ i\ i\ i\ ;::: J ' . : . :


]

0.0

V VlJV'if\)\[V
j

iii

ii

Vi
~

0.00

L
I

0.0

Time In Seconds

Fig. 38. SimulationResults: SeriesCapacitorBank Insertion

4-23

Ii

Time In Seconds

0 "

Você também pode gostar