Presentation
058579N
Our Fusarc CF, Solfuse, Tpfuse and MGK fuses make up a broad, consistent
and uniform range of high breaking capacity fuses and current limitors.
They are all of combined type and are manufactured so that they can be installed
both indoors and outdoors (depending on the type).
Schneider Electric fuses provide protection to medium voltage distribution devices
(from 3 to 36 kV) from both the dynamic and thermal effects of short-circuit currents
greater than the fuses minimum breaking current.
Considering their low cost and their lack of required maintenance, medium voltage
fuses are an excellent solution to protect various types of distribution devices:
b Medium voltage current consumers (transformers, motors, capacitors, etc.)
b Public and industrial electrical distribution networks.
Public distribution
058580N
They offer dependable protection against major faults that can occur either
on medium or low voltage circuits.
This protection can be further enhanced by combining the fuses with low voltage
protection systems or with an overcurrent relay.
Selection table
Depending on the equipment to be protected and its voltage rating, the table below
gives the range of fuses which are best suited to the protection application.
Voltage
(kV)
3.6
7.2
Motor protection
12
17.5
24
36
MGK
(UTE standard;
motor protection)
Fusarc CF
(DIN standard;
transformer, motor and
capacitor protection)
Tpfuse
(UTE standard;
voltage transformer protection)
PE56920
Solfuse
(UTE standard;
transformer protection)
Motors
Fusarc CF
MGK
Fusarc CF
MGK
Fusarc CF
Power
transformers
Fusarc CF
Capacitors
Fusarc CF
Solfuse
Fusarc CF
Solfuse
Fusarc CF
Solfuse
Fusarc CF
Fusarc CF
Solfuse
Fusarc CF
Solfuse
Fusarc CF
Solfuse
Fusarc CF
Solfuse
Fusarc CF
Solfuse
Fusarc CF
Solfuse
Fusarc CF
Voltage
transformers
Fusarc CF
Fusarc CF
Tpfuse
Fusarc CF
Tpfuse
Fusarc CF
Tpfuse
Fusarc CF
Solfuse
Tpfuse
Fusarc CF
Fusarc CF
Fuses
Table no. 1
Reference
757372AR
Rated
voltage (kV)
2.000
0.6
58
20
762
20
51006500M0
6.3
36
205
12
51006501M0
10
34
102
14
51006502M0
16
50
68.5
26
51006503M0
20
62
53.5
32
51006504M0
25
91
36.4
35
51006505M0
31.5
101
26
42
40
135
18
46
51006507M0
50
180
11.7
44
51006508M0
63
215
8.4
52
51006509M0
80
280
6.4
68
51006510M0
100
380
5.5
85
757352BN
125
650
3.4
88
757352BP
160
1.000
2.2
87
757352BQ
200
1.400
1.8
95
757374BR
250
2.200
0.9
95
51311007M0
20
1143
27
3/7.2
250
50
7.2
3/3.6
Min. breaking
current I3 (A)
51311006M0
51006506M0
3.6
Operating
Rated
Max. breaking
voltage (kV) current (A) current I1 (kA)
63
50
51006511M0
6.3
36
319
16
51006512M0
10
34
158
18
51006513M0
16
50
106
37
51006514M0
20
62
82
42
51006515M0
25
91
56
52
51006516M0
31.5
101
40
59
40
135
28
74
51006518M0
50
180
17.4
70
51006519M0
63
215
13.8
82
51006520M0
80
280
10
102
51006521M0
100
380
120
757364CN
125
650
5.3
143
757354CP
160
1.000
3.5
127
757354CQ
200
1.400
2.7
172
51006522M0
10
34
203
23
51006523M0
16
50
132
47
51006524M0
25
91
71
72
51006525M0
31.5
101
51
78
51006526M0
40
135
35
90
51006517M0
12
6/12
51311008M0
51006527M0
6.3
51006528M0
63
40
40
20
1436
34
36
402
21
10
34
203
25
16
50
132
46
51006530M0
20
62
103
52
51006531M0
25
91
71
66
51006532M0
31.5
101
51
74
51006533M0
40
135
35
94
51006534M0
50
180
22
93
51006535M0
63
215
19.4
121
51006536M0
80
330
13.5
145
51006537M0
100
450
11
192
51006529M0
17.5
10/17.5
31.5
* Resistances are given at 10% for a temperature of 20C. Fuses > 100 A rated current,
are manufactured in glass fibre (for indoor use).
Length
(mm)
292
Diameter Weight
(mm)
(kg)
86
3.4
50.5
76
2.1
192
292
86
442
3.4
5
50.5
1.2
76
3.2
86
50.5
1.2
76
3.2
50.5
1.5
76
3.9
86
4.6
292
442
292
367
Fusarc CF
Fuses
Rated
voltage (kV)
Operating
Rated
Max. breaking
voltage (kV) current (A) current I1 (kA)
Min. breaking
current I3 (A)
51108915M0
6.3
38
484
26
51108916M0
10
40
248
35
51108917M0
16
60
158
64
51108918M0
20
73
123
84
51108919M0
25
100
88
79
51108920M0
31.5
112
61
90
51108921M0
40
164
45
120
51108922M0
50
233
30
157
51108923M0
63
247
23
177
51108807M0
6.3
36
485
26
51108808M0
16
50
158
58
51108813M0
20
62
123
67
25
91
85
76
31.5
101
61
93
51108810M0
40
135
42
115
51311009M0
20
1436
34
51006538M0
6.3
36
485
25
51006539M0
10
34
248
31
51006540M0
16
50
158
58
51006541M0
20
62
123
67
51006542M0
25
91
85
79
51006543M0
31.5
101
61
96
51006544M0
40
135
42
119
51006545M0
50
180
31.5
136
51006546M0
63
215
22.8
144
51006547M0
80
330
18
200
51006548M0
100
450
13.5
240
51311010M0
20
2109
51
51006549M0
6.3
36
750
39
51006550M0
10
34
380
50
51006551M0
16
50
252
98
51108814M0
51108809M0
51006552M0
51006553M0
24
36
10/24
20/36
20
25
31.5
40
31.5
20
62
197
120
91
133
133
51006554M0
31.5
101
103
171
51006555M0
40
135
70
207
51006556M0
50
200
47
198
51006557M0
63
250
35
240
Length
(mm)
292
Diameter Weight
(mm)
(kg)
50.5
1.2
76
3.2
86
50.5
1.5
76
3.9
50.5
1.7
76
4.5
86
5.7
50.5
1.9
76
5.4
86
6.5
367
442
442
537
* Resistances are given at 10% for a temperature of 20 C. Fuses > 100 A rated current,
are manufactured in glass fibre (for indoor use).
Fusarc CF
Fuses
250 A
160 A
125 A
100 A
31.5 A
40 A
50 A
63 A
80 A
10 A
16 A
20 A
25 A
6.3 A
1000
8
6
4
4A
DE58241
Time (s)
8
1000
2
100
8
6
4
2
10
8
6
4
2
1
8
6
4
2
0.1
8
6
4
2
0.01
10
100
8
10000
Current (A)
100
8
6
4
Ia
8
1.
Ik
Is
Ik
250 A
200 A
160 A
125 A
100 A
80 A
63 A
50 A
40 A
10
8
31.5 A
25 A
20 A
16 A
6
4
10 A
6.3 A
1
8
4A
6
4
0.1
0.1
10
100
10
Solfuse
Fuses
Electrical characteristics
Table no. 2
Reference
Rated voltage
(kV)
Operating voltage
(kV)
Rated current
(A)
Cold resistance *
(m)
757328BC
6.3
31.5
158.6
757328BE
16
80
51.7
757328BH
31.5
157.5
757328BK
7.2
3/7.2
63
315
757328BN
125
625
50
24.5
11.3
4.8
757328CM
7.2/12
3/12
100
500
50
7.7
757328DL
7.2/17.5
3/17.5
40
15.1
80
400
757328EC
6.3
31.5
445.9
757328EE
16
80
93.2
757328EH
31.5
157.5
757328EJ
43
215
38.5
757328EK
63
315
18.9
757331EC**
6.3
31.5
447.3
757331EE**
16
80
147.4
757331EH**
12/24
157.5
43
215
39
757331EK**
63
315
19.3
757328FC
6.3
31.5
618.9
757328FD
10
50
252.9
30/36
30
45.8
31.5
20
67.9
16
80
757328FF
20
100
133.2
757328FG
25
125
124
757328FH
31.5
157.5
93
207.8
Dimensions (mm)
Figure 5
DE55752
36
10/24
30
757331EJ**
757328FE
12/24
10/24
Striker
520
55
35
Weight: 2.3 kg
450
23 max.
11
Solfuse
Fuses
1000
8
6
4
16 A
20 A
25 A
31.5 A
43 A
63 A
80 A
6.3 A
10 A
DE58243
Time (s)
2
100
8
6
4
2
10
8
6
4
2
1
8
6
4
2
0.1
8
6
4
2
0.01
10
100
8
1000
8
10000
Current (A)
100
8
6
4
Ia
.8
Ik
Is
Ik
2
125 A
100 A
80 A
63 A
10
43 A
31.5 A
25 A
20 A
16 A
10 A
8
6
4
6.3 A
2
1
8
6
4
0.1
0.1
10
100
12
Tpfuse, Fusarc CF
Fuses
Characteristics
Table no. 3
Type
Tpfuse
Fusarc CF
Reference
Rated
voltage
(kV)
Operating
voltage
(kV)
781825A
12
< 12
781825B
24
13.8/24
51311002M0
7.2
3/7.2
51311000M0
51311003M0
51311011M0
51311001M0
51311004M0
51311005M0
12
6/12
17.5
10/17.5
24
10/24
36
20/36
Rated
current
(A)
0.3
40
6.1
40
301
11.6
2.5
1278
63
3834
2.5
1917
2.5
9.5
2407
40
2.5
2407
2.5
20
3537
Weight
(mm)
(kg)
27.5
0.4
192
0.9
292
1.2
367
4815
Diameter
50.5
1.5
442
1.6
537
1.8
Dimensions (mm)
Fusarc CF (Figure 6)
1000
8
6
4
DE55760
Tpfuse (Figure 7)
331
50.5
45
33
1 A (Fusarc CF)
0.3 A (Tpfuse)
DE55759
DE58245
Time (s)
2
100
8
6
4
27.5
2
15
301
10
8
6
4
2
1
8
6
4
2
0.1
8
6
4
2
0.01
1
10
8
100
Current (A)
13
MGK
Fuses
Dimensions (mm)
DE55761
Figure 8
Striker
Electrical characteristics
81
Table no. 4
Reference
55
Rated
voltage
(kV)
Weight: 4.1 kg
Rated
current
(A)
757314
100
360
50
6.4
757315
125
570
50
4.6
160
900
50
2.4
757317
200
1400
50
1.53
757318
250
2200
50
0.95
757316
438
Operating
voltage
(kV)
7.2
y 7.2
250 A
160 A
1000
8
6
4
100 A
125 A
DE58246
Time (s)
2
100
8
6
4
2
10
8
6
4
2
1
8
6
4
2
0.1
8
6
4
2
0.01
10
100
8
1000
8
10000
Current (A)
100
8
6
4
Ia
1.
Ik
Is
Ik
2
250 A
200 A
160 A
125 A
100 A
10
8
6
4
1
8
6
4
0.1
0.1
10
100
14
Fuses
General
Transformer protection
DE55764
General
Icc
Short circuit
current
According to their specific characteristics, the various types of fuses (Fusarc CF,
Solfuse, Tpfuse and MGK) provide real protection for a wide variety of medium
and high voltage equipment (transformers, motors, capacitors).
It is of the utmost importance to always remember the following points:
b Un of the fuse must be greater than or equal to the network voltage
b I1 of a fuse must be greater than or equal to the network short circuit current
b The characteristics of the equipment to be protected must always be taken into
consideration.
Transformer protection
A transformer imposes three main stresses on a fuse. This is why the fuses must be
capable of:
I3
(1)
Closing
In
In
Fuse
Transformer
15
Fuses
Transformer protection
Selection table
Fusarc CF fuses DIN standard for transformer protection (rating in A) (1) (2) (3)
Table no. 6
Operating Rated
voltage
voltage
(kV)
(kV)
7.2
7.2
7.2
6.6
10
11
13.2
13.8
15
20
22
7.2
12
12
17.5
17.5
17.5
Transformer power
(kVA)
25
50
75
16
25
31.5
40
50
63
63
80
20
31.5 40
50
63
80
80
100
100
125
125
25
40
16
50
25
63
31.5
80
31.5
100
40
100
50
160
80
160
63
125
63
10
20
31.5 40
40
50
63
80
80
100
100
16
6.3
25
16
40
20
50
25
50
31.5
63
40
80
40
100
50
100
63
63
125
80
10
20
25
31.5 40
50
50
63
80
80
100
100
6.3
25
16
31.5
20
40
25
63
31.5
63
40
80
50
100
50
100
63
80
10
20
25
31.5 31.5 40
50
63
63
80
100
100
25
31.5
40
16
40
20
50
25
63
31.5
80
31.5
80
40
100
50
63
125
63
10
16
20
25
31.5 40
40
50
63
80
80
16
20
10
25
16
31.5
20
40
25
50
31.5
63
40
80
50
100
50
100
63
10
16
20
25
31.5 31.5 40
50
63
63
80
80
100
25
16
31.5
16
40
20
40
25
63
31.5
80
40
80
50
100
50
100
63
125
6.3
20
10
10
16
20
20
25
31.5 31.5 40
50
63
63
80
80
10
25
16
31.5
20
40
25
63
40
80
50
80
50
100
63
100
6.3
25
10
10
16
16
20
25
31.5 31.5 40
50
63
63
80
80
20
10
25
16
31.5
16
40
40
25
63
40
80
40
80
50
100
63
100
63
80
80
80
100
6.3
6.3
4
4
4
24
24
100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000
50
25
50
31.5
125
160
200
250
160
125
125
160
200
250
125
125
160
200
250
80
100
125
125
160
100
125
125
125
160
125
20
20
25
31.5 40
50
50
63
10
16
6.3
20
25
10
25
16
31.5
16
40
20
50
25
63
31.5
63
31.5
80
40
50
6.3
10
10
16
20
20
25
31.5 40
40
50
63
63
16
20
10
25
10
25
16
31.5
20
40
25
50
31.5
63
40
10
16
16
20
25
31.5 31.5 40
50
20
10
25
16
31.5
16
40
40
25
10
16
20
20
25
10
6.3
20
25
10
25
16
31.5
16
10
10
16
20
16
20
25
36
50
31.5
125
160
16
6.3
6.3
30
40
25
250
10
6.3
36
50
25
200
6.3
10
25
50
25
160
6.3
10
6.3
6.3
10
100
100
100
100
100
80
80
100
100
63
100
40
80
50
50
63
80
80
63
40
63
40
80
50
100
100
31.5 40
50
50
63
63
63
40
50
25
63
31.5
63
31.5
40
50
20
25
31.5 40
40
50
63
25
31.5
40
50
63
50
25
50
31.5
50
100
63
63
100
63
Solfuse fuses UTE standard for transformer protection (rating in A) (1) (2) (3)
Table no. 7
Operating Rated
voltage
voltage
(kV)
(kV)
3
3.3
4.16
5.5
6
6.6
10
11
13.8
15
20
22
30
7.2
7.2
7.2
7.2
7.2
7.2
12
12
17.5/24
17.5/24
24
24
36
Transformer power
(kVA)
25
50
100
125
160
200
250
315
400
500
630
800
16
16
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
16
16
16
16
16
16
6.3
6.3
6.3
6.3
6.3
6.3
31.5
31.5
31.5
16
16
16
16
16
16
16
6.3
6.3
6.3
63
31.5
31.5
31.5
31.5
16
16
16
16
16
6.3
6.3
6.3
63
63
31.5
31.5
31.5
31.5
16
16
16
16
16
16
6.3
63
63
63
31.5
31.5
31.5
31.5
16
16
16
16
16
16
80
80
63
63
63
31.5
31.5
31.5
16
16
16
16
16
100
80
80
63
63
63
31.5
31.5
31.5
31.5
16
16
16
100
100
80
63
63
63
43
31.5
31.5
31.5
31.5
16
16
125
125
100
80
80
80
43
43
31.5
31.5
31.5
31.5
16
125
100
100
80
63
63
43
43
43
31.5
31.5
125
100
100
80
63
63
43
43
31.5
31.5
125
125
80
80
63
63
43
43
31.5
(1) Fuse ratings correspond to open air installation with a transformer overload of 30%. or to an indoor installation without transformer overload.
(2) If the fuse is incorporated in a distribution switchboard. please refer to the selection table provided by the manufacturer of this device.
(3) although the ratings shown in bold type are the most appropriate. the others also protect transformers in a satisfactory manner.
16
100
100
80
80
63
43
80
63