Micafil Transformer Bushings

AirRIP/RTKF 24 550 kV

Micafil RIP bushings

Micafil brand products combine functionality, high performance


and long service life. The optimized solutions are based on
our long-term, trustworthy partnerships with customers and our
understanding of their needs. With proven components and a
variety of designs, our new AirRIP series meets customer-specific
requirements. To date, our factory in Zurich Altstetten has
delivered more than 600000 bushings. The worlds leading
transformer manufacturers and electric power utilities rely on us.
With the new Micafil AirRIP series, we will continue to live up to
our reputation.

Page
Todays technology for tomorrow

The AirRIP bushing in detail

Choice of insulator

Choice of current conductor

General information

Ordering information
AirRIP overview

9
10

AirRIP bushings 24 170 kV


Data for types with cable conductor

11

Data for types with rod conductor

15

Data for types with fixed conductor

19

AirRIP bushings 245 550 kV


Data for types with cable conductor

23

Data for types with rod conductor

27

Data for types with fixed conductor

31

Other Micafil RIP bushings

35

Todays technology for tomorrow

Micafils AirRIP outdoor transformer bushings are the product


of a sophisticated design using a small number of components:
insulating body, main flange, insulator shell and current
c onductor. They are produced in a wide variety of d esigns
and thus can easily fulfil specific customer requirements.
A irRIP bushings are completely dry, pressurized, explosionproof, fire-resistant and allow high application temperatures.

Outer insulation
For decades, porcelain has proved its worth as a material for
outer insulation. With the development of composite hollow
insulators in recent decades an alternative has gained market
maturity. Our customers appreciate the benefits these offer,
such as reduced weight, easier handling, and the explosion
safety characteristics of these silicone composite insulators.
We offer the AirRIP bushings both with silicone composite
insulators as well as with porcelain insulators.

RIP insulation
Capacitor bushings enable control of electric field distribution
in radial and axial directions by inserting conductive layers
in the insulator body. The insulating body of the Micafil RIP
(Resin Impregnated Paper) s ystem consists of wound strips
of crepe paper. Aluminium foils of graduated lengths are
wrapped at exactly calculated points.
The wrap is heated, vacuum dried, as well as impregnated
and cured under vacuum with an epoxy resin formulated by
ABB. The impregnation process requires high skills in setting
and in the control of process parameters, as well as a broad
knowledge and experience in the field of materials science
and in materials selection.
We have developed our expertise over decades and gained
market experience as first-class supplier. The result is RIP
bushings with very good thermal and chemical resistance
and high mechanical strength and stiffness.

AirRIP stands for quality and versatility


High-voltage bushings must meet the highest standards of
operational safety and minimize the risk of damage for people
and facilities. The greatly increased and growing environmental awareness requires gentle production and clean operation.
The Micafil AirRIP series meets these requirements thanks to
high-quality materials and reliable processing techniques. The
technical standard is very high and development and manufacturing processes are regularly reviewed. High product quality is ensured with comprehensive testing during production
and in the electrical testing laboratory.

Advantages of Micafil AirRIP technology

Dry bushings
In line with our product philosophy of compact design and dry
bushing, the space between the insulating body and insulator
is filled with the time-tested dry filler MICAGEL. MICAGEL is
poured in a liquid form into the bushing and after curing forms
a compressible dry filling.

4 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

Partial discharge free up to double service voltage


High temperature resistance (class E, 120C)
Low dielectric losses (tan < 0.35%)
High flexural strength, heavy load
according to IEC 60137 (2008)
Completely dry bushing, i.e., no oil spills, no explosion risk
No maintenance or constant monitoring necessary
Transport and storage is possible in all positions
Flexible design allows for adaptation to different customer
needs and transformer requirements

The AirRIP bushing in detail


 c2

Current conductor terminal


with de-aeration of central tube

Head with clamp for conductor

Dry lling MICAGEL


RIP insulating body
with capacitor control and central tube

Porcelain or silicon composite insulator

Flange with test tap


and transformer de-aeration (DA)
DA

Tap
Bolted ange plate

Sub-section extension for current


transformers

Oil side shield

The bushing in principle


(for example: bushing for cable conductor)

Insulating body
The core of the AirRIP bushing is the insulating body of RIP
with capacitor inserts for electric field control. The production of RIP is based on time-tested and proven technology.
Complex production processes compress the material into
a compact, liquid and gas-tight insulating body, which complies with current partial discharge and temperature requirements.
To accommodate current transformers, the lower body part
can be extended in steps of 100 mm up to 600 mm. The
short oil side is consistent with our proven and balanced
dimensioning and optimizes the strength of the interface
between the insulating body and transformer oil. These
dimensions also guarantee a high level of interchangeability
with older bushing types.

Flange and insulator


The insulator is the supporting part of the bushing and takes
over the mechanical loads with the two integrated fittings,
head and flange. The flange not only holds the insulating
body, it also forms the lower fitting of the insulator. The connection to the transformer takes place via the flange plate
bolted to the flange.
With a multiple O-ring system, the transition between body
and flange is oil-and gas-tight. The aluminium alloy used for
this purpose is corrosion-resistant and mechanically robust.
This ensures safe control of the bending moments in occurring operating stresses or in bending test loads. The whole
series is designed and type-tested in accordance with the
highest bending load class of IEC 60137 (2008).
The standard flange plate bolt circles conform to currently
common dimensions. Deviations can easily be executed as
variants. The flange is equipped with a test tap and has an
opening (M12) with a closure screw that can be used to deaerate the transformer or as connector for a Buchholz relay.
Also mounted on the flange: identification tag, connection
thread M12 for the flange earthing and, with larger bushings,
eyebolts for lifting purposes.
The head of the bushing closes the bushing and carries the
current conductor fixing. The 420 kV and 550 kV bushings
have a separate shield to avoid external corona discharges.

Oil side end


The shape of the opening ensures that no shield electrodes
are required up to 73 kV. We offer shielding as a variant.
From 123 kV, depending on current conductor version,
either fixed shields (cable conductors) or removable shields
(rod conductor and fixed conductor) are used, which are
attached to the end of the bushing. They prevent the excessive use of transformer oil and facilitate the assembly of the
conductor insulation beneath the bushing.
Our shield electrodes are dimensioned using modern methods
and their surface is provided as standard with a high-quality
solid insulation layer.
Please note our installation recommendations.

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV5

Choice of insulator

The choice of insulator type has no influence on the perform


ance of the bushing.
Please note corresponding weights as well as head and shed
diameters for each insulator type.

Silicone composite insulators made of glass fibrereinforced tube with helical or straight sheds
Hydrophobicity and the ability to transfer these properties
also to foreign layers is the most important value-added
feature of these insulators. They have many advantages:
Excellent contamination behaviour due to hydrophobic
s urface properties and low leakage currents
Improved safety for personnel and equipment
Lower weight

Porcelain insulators made of high-quality


electrical porcelain, brown and grey
High-quality electrical porcelain for decades an excellent,
proven material is available as always in the standard
c olour brown and alternatively in light grey.

Creepage distances
All types of insulation are made with alternate shed profiles.
Creepage distances are measured for the high pollution
requirements of IEC 60 815:
Bushings Ur

class

SCD 1 USCD 2

up to 420 kV

very heavy

31 mm/kV

53.7 mm/kV

The helical shed is the outcome of intensive development


efforts of ABB. Outstanding results in tough long-term pollution tests have proven their quality (certificates on request).
Insulators with conventional straight sheds complement our
product range.

550 kV

heavy

25 mm/kV

43.3 mm/kV

Composite insulator with silicone sheds

Porcelain insulator

1 SCD: specific creepage distance


2 USCD: unified specific creepage distance

These long creepage distances ensure optimum dielectric


strength even under extreme environmental conditions.

Helical sheds Straight sheds Brown Grey


Standard 123 kV

Standard 72.5 kV

Standard

Optional

Optional 123 kV

(all voltages)

(all voltages)

6 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

Choice of current conductor

The rated current is the starting point for choosing the type
of conductor.
However, current levels of conductor types partially overlap
and can be selected according to individual preferences.
Please follow the respective icons when making your choice.

Low currents with cable conductor


The current is led through a multi-stranded
flexible conductor joined to the terminal of
the winding. The lead is drawn up through
the central tube of the bushing and provided
with the top connector (cable bolt) that is
fastened to the bushing head. In the standard model, the air
side terminal is a round, bare copper bolt. As an option, the
surfaces can be silver- or nickel-plated and other terminal
sizes can be selected.
To avoid unnecessary contact junctions, the draw lead bolt is
of a single-piece design. A tried-and-tested fixing device with
few parts ensures that no inadvertent displacement in axial
direction or twisting is possible. It also allows the positioning
of the cable bolt to 10 mm from nominal dimensions.
The manufacturers of the transformers must provide the conductor cable with a thin insulation in order to keep transient
voltages to the central bushing tube.

High currents with fixed conductor


Bushings with a directly wound and nonremovable conductor are suitable for
high currents. Various terminal solutions are
available, see data tables and figures.

Current data
The type designation of the bushings contains the standard
current according to IEC 60137 (2008). The actually perm is
sible operating currents depend on the lower part extension
L6 and are shown in the data tables.

Air side terminal


The standard air side terminal mentioned in the data tables
covers the entire current range of the bushing.
Guidelines for the dimensions of air side terminals:
Maximum permissible
d2
Length c2
operating current (A)
1600

30

80

2500

40

125

3500

50

125

4300

60

125

5000

flat 90105

thickness 30

Medium currents with removable


rod conductor
For a better current utilization of the bushing
with central tube, it is equipped with
a removable conductor rod of copper.
In the standard model, the air side terminals
are bare. As an option, the surfaces can be silver- or nickelplated and the shapes of the terminals can be selected. The
rod conductor can be fitted with a joint, usually near the flange.
Various terminal shapes are available for their lower end.
Conductor installation and de-aeration of the central tube are
similar in both the version with rod conductor and with cable
conductor.

In case the full current range of the bushing is not utilized as


an option one may use smaller dimensions, as long as above
rules are observed.

Please note: The rod conductor is a separate component


and must be selected separately.

If overload capacity is required for the transformer according


to IEC 60076-7 (normal load cycles), the rated current of the
bushing should be chosen with at least 120% of the transformer-rated current, in accordance with IEC 60137 (2008).

Overload

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV7

General information

Each AirRIP bushing meets all requirements of IEC 60137


(2008) and the electrical values under the IEEE C57.19.01
(2000).

Type designation
RTKF 170750 / 1600 B KSI
Composite insulator
B = Removable conductor bar

Recommended installation
Our bushings are designed and tested for mineral oil appli
cations. The field strengths in oil on the lower part of the
bushing depend on the shape of the surrounding parts, as
well as on the quality and the conditions of the transformer oil.
As a guideline, the following table shows the respective
d istances A to grounded transformer parts under standard
conditions.
They are valid for the oil side ends (standard and variants) as
per the data tables. Due to limiting conditions additional
insulating measures or larger distances may be necessary.
Uninsulate edges around the bushing should be rounded
to R min = 5 mm.
 c2
Ur

AC test A

(mm)
(kV) voltage
(kV)
52

80

100

160 125

123 185 130


230 145

Min. R5

L6 + 20

72.5 140 120

F = Fixed conductor
Rated current (A)
Lightning impulse voltage 1.2/50 s (kV)
Maximum voltage (kV)
R = RIP bushing
T = Transformer application
K = Short lower part
F = Outdoor use

Test tap
Each bushing is equipped with a
standard test tap. The test tap
is connected to the outermost cap
acitor foil and is always grounded
d uring operation. For measurement,
the cap must be unscrewed and the
supplied 4-mm plug coupling must
be inserted.
As an option we provide transition connectors for continuous
voltage measurements.

145 275 170


30

310 200

170 325 210


365 230

245 460 300


300 510 330
420 630 450

680 500

550 750 550


790 600

The diameter of the current conductor should be at least half


of the inner tube diameter d3. Oil access in the central
b ushing opening and in the open space of the shield electrodes must not be obstructed.

8 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

Routine and type tests


The standard routine tests are carried out in accordance
with IEC 60137 (2008) and the protocols are supplied; tests
according to other standards are available on request.
The type tests were performed on representative bushings in
accordance with current standards IEC 60137 (2008), and
IEEE C57.19.00 (2004) / C57.19.01 (2000). These tests cover
the entire AirRIP portfolio and were successfully passed in
the presence of an independent observer from KEMA. Protocols are supplied to customers on request.

Packaging and storage


The bushings are packaged and sent in a dry and clean
s tate. On request, we offer long-life packaging. The bushings
can be transported and stored in any position.

Inquiry / Order data sheet

Our order confirmation includes drawings of the bushing and


a detailed bushing data sheet.

When ordering, please specify the following:


Type:

Customized modifications as for example in


flange dimensions
terminal variants
other lower part lengths
etc.
can be made available on request. We are happy to provide
information on feasibility, price and delivery time of such
c ustomized modif ications.

Drawing no: 1ZCD 0 6 4


Quantity:
Current conductor
Cable bolt for draw lead
Rod conductor
Fixed conductor
Air side terminal
Dimensions:
Standard
Variant 1*
Variant 2*

Galvanization:
bare
silver-plated
nickel-plated

Removable rod conductor


Rod conductor, one-piece
Rod conductor, split
Oil side terminal:
Standard
Variant 1
Variant 2
Silicone comp. insulator
Helical sheds (123 kV )
Straight sheds
Flange pitch circle 
Standard
Variant 1*

Porcelain
Brown
Grey

Company:
Name/First name:
Phone:
E-mail:

Note
We reserve the right to make technical changes or modify the contents of this
document without prior notice. With regard to purchase orders, the a
greed particulars shall prevail. ABBS witzerlandLtd does not accept any responsibility
whatsoever for p otential errors or possible lack of information in this document.
We reserve all rights in this d ocument and in the subject matter and illustrations
contained therein. Any reproduction, d isclosure to third parties or u
tilization of
its c ontents in w hole or in parts is forbidden w
ithout prior written c
onsent of
ABB Switzerland Ltd.
Copyright 2012 ABB. All rights reserved.

Current transformer extension L6 (mm)


For further information please contact:
0
100 200 300 400 500 600
ABB Switzerland Ltd
High Voltage Components
Badenerstrasse 780
Oil side end
CH-8048 Zurich/Switzerland
Standard
Phone + 41 58 586 03 33
Variant 1*
Fax +41 58 586 04 44
Variant 2*
E-mail: info.micafil @ch.abb.com
www.abb.com/electricalcomponents
* If available

Reset Form

1ZCD067719

Micafil Transformer Bushings


AirRIP/RTKF 24 550 kV

AirRIP overview

L6

Ir (A)

Ir (A)

Drawing no: 1ZCD

Ir (A)

Drawing no: 1ZCD

kV

mm

Cable

Rod

Silicone composite Porcelain

Fixed

Silicone composite Porcelain

conductor conductor insulator


1550
2350
064001
1380
2100
1250
1850
2500
3600
064002
2200
3200
2100
2850
3750
5000
064003
3200
4300
2880
3850
1500
2300
064004
1330
2050
1200
1800
2500
3500
064005
2200
3150
2100
2850
3600
4800
064006
3120
4200
2840
3800
1550
2250
064007
1380
2000
1250
1750
2100
2800
064008
1850
2470
1650
2200
2600
3500
064009
2300
3100
2100
2850
1000
1750
064010
890
1580
800
1430
2000
2650
064011
1800
2380
1650
2150
2500
3400
064012
2230
3050
2040
2780
920
1670
064013
830
1520
770
1370
1940
2610
064014
1750
2370
1600
2180
1400
2000
064015
1260
1800
1160
1670
2000
2900
064016
1840
2720
1730
2550
880
1360
064017
805
1250
755
1170
1900
2800
064018
1800
2620
1700
2450
1030
1650
064019
880
1510
820
1400
1700
2400
064020
1560
2230
1450
2100
1000
1600
064021
850
1440
780
1340
2250
3000
064022
2100
2800
2000
2600
1100
1800
064023
1250
2000
1000
2000
2000
2800
064024
1850
2650
1700
2500
1050
1850
064025
1100
2000
900
1750

c onductor
3050
2650
2400
4200
3800
3500
5200
4500
4100
3000
2600
2350
4150
3750
3450
5150
4500
4100
2840
2520
2300
3400
3000
2680
4250
3800
3500
2200
1950
1800
3250
2950
2700
4100
3700
3400
2250
2100
2000
3150
2900
2700
2420
2230
2100
3600
3380
3150
2100
2000
1900
3500
3280
3050
2150
2050
1950
3150
3000
2900
2100
2000
1900
3800
3600
3400
2300
2600
2400
3250
2900
2600
2100
2200
1950

insulator

insulator

0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600
0
300
600

064026

064076

064027

064077

064028

064078

064029

064079

064030

064080

064031

064081

064032

064082

064033

064083

064034

064084

064035

064085

064036

064086

064037

064087

064038

064088

064039

064089

064040

064090

064041

064091

064042

064092

064043

064093

064044

064094

064045

064095

064046

064096

064047

064097

064048

064098

064049

064099

064050

064100

150 n.a.

24

150 n.a.

36

200 n.a.

36

200 n.a.

36

200 n.a.

52

250 n.a.

52

250 n.a.

52

250 n.a.

72.5

350 n.a.

72.5

350 n.a.

72.5

350 n.a.

123

550 n.a.

123

550 n.a.

145

650 n.a.

145

650 n.a.

170

750 n.a.

170

750 n.a.

245

1050

750

245

1050

750

300

1175

850

300

1175

850

420

1675 1175

420

1675 1175

550

1800 1240

insulator
064051
064052
064053
064054
064055
064056
064057
064058
064059
064060
064061
064062
064063
064064
064065
064066
064067
064068
064069
064070
064071
064072
064073
064074
064075

Data pages 3134

24

Data pages 2730

150 n.a.

Data pages 2326

24

Data pages 1922

SIL

kV

Data pages 1518

BIL

kV

Data pages 1114

Ur

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV10

AirRIP bushings 24170 kV


Types with cable conductor
Explanations of the table columns
36 Rated voltages according to IEC 60137 (2008)
710 Rated voltages according to IEEE C57.19.01 (2000)
11, 12 Maximum operating current Ir for the largest cable

cross-section, depending on the current transformer
extension L6
13
Maximum thermal short-circuit current, 2 sec., after

operation at maximum operating current
16
Bending test load, 1 min.
17, 18 Maximum cantilever operating load and permissible

installation position (v = vertical, h = horizontal,

from vertical)
21
Standard current transformer extension L6

11 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

24
Inner diameter of the central tube ( d3)
28, 29 Maximum head and shed diameter for silicone

composite insulator
30, 31 Maximum head and shed diameter for porcelain insulator
34, 35 Sealing area
Bushing length L, without air side terminal and
40

oil side shield
41, 42 Standard terminal on air side
43, 44 Optional terminal on air side
45 48 Standard design of oil side end
49 52 Optional design of oil side end

Bushings with cable conductor 24 170 kV


Fig. 1

Fig. 2

Legend

 d2
c2

 d2

1
L 5 max.

L 5 max.

c2

1 Copper, bare (optional:

 D5

nickel-plated, silver-plated)

2 Test tap
3 De-aeration

 D5

4 Earthing screws 2M12/180


5
6 Sealing area
the transformer lead)

20

L6 Current transformer extension

L6

 D1

c7

L16 5

 D1

L6

L16 5

 D6
max.

L4 cable bolts

L 2 (5)
(L)

L4 cable bolts

 D6
max.

20

(L)

L 2 (5)

7 Removability (for connecting

Flange

Flange detail
Fig. 12

Fig. 11

30

60

nv

12

45

15

30

22.5

30

2
 D3
 D4

 D3
 D4

Fig. 21

 D3
 D4

Fig. 22

 d3
L16
20

 d3

c7

 d5

c7

50

L16

L16

 d3

 d5
 d6

12 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

6
 D2
 D8

Oil side end


Fig. 20

5 45

Fig. 10

 d5
 d6

All dimensions in mm, unless otherwise indicated

RTKF 24150/1250 KSI

RTKF 24150/1250

1ZCD064001

1ZCD064051

RTKF 24150/2500 KSI

RTKF 24150/2500

1ZCD064002

1ZCD064052

RTKF 24150/3150 KSI

RTKF 24150/3150

1ZCD064003

1ZCD064053

RTKF 36200/1250 KSI

RTKF 36200/1250

1ZCD064004

1ZCD064054

RTKF 36200/2500 KSI

RTKF 36200/2500

1ZCD064005

1ZCD064055

RTKF 36200/3150 KSI

RTKF 36200/3150

1ZCD064006

1ZCD064056

RTKF 52250/1250 KSI

RTKF 52250/1250

1ZCD064007

1ZCD064057

RTKF 52250/2000 KSI

RTKF 52250/2000

1ZCD064008

1ZCD064058

RTKF 52250/2500 KSI

RTKF 52250/2500

1ZCD064009

1ZCD064059

24

14

24

14

24
36
36

1ZCD064063

RTKF 123550/1600 KSI

RTKF 123550/1600

1ZCD064014

1ZCD064064

RTKF 145650/1250 KSI

RTKF 145650/1250

1ZCD064015

1ZCD064065

RTKF 145650/2000 KSI

RTKF 145650/2000

1ZCD064016

1ZCD064066

RTKF 170750/800 KSI

RTKF 170750/800

1ZCD064017

1ZCD064067

RTKF 170750/1600 KSI

RTKF 170750/1600

1ZCD064018

1ZCD064068

55/ 125 25

16

21

36

21

77/ 170 34.5


77/ 170 34.5

22

77/ 170 34.5

22

30 105/ 250 46

95/
42 155/ 325 69
42 155/ 325 69

29 105/ 250
44 160/ 350
44 160/ 350
140/

42 155/ 325 69
140/

44 160/ 350
140/

123

71 255/ 550 92

123

71 255/ 550 92

TR
TR

84 305/ 650 138


275/

73 185/ 450
155/
73 185/ 450
155/
88 310/ 650
275/

84 305/ 650 138


275/

88 310/ 650
275/

170

98 355/ 750 161 102 365/ 750

170

98 355/ 750 161 102 365/ 750

325/
325/

TR
TR

315/
315/

15

[kA]

[mm]

[mm]

744

1500

744

1500
2800
665
1200

744
1116
1116
1116
1612
1612

1500

1612

400

2248

1200

2248

1500
400
1200
665
1500
400
1500

18

design

665

665

17

data

[mm 2]

2800

16

Mechanical

Arcing distance (minimum)

[A]
1550
1380
1250
2500
2200
2100
3750
3200
2880
1500
1330
1200
2500
2200
2100
3600
3120
2840
1550
1380
1250
2100
1850
1650
2600
2300
2100
1000
890
800
2000
1800
1650
2500
2230
2040
920
830
770
1940
1750
1600
1400
1260
1160
2000
1840
1730
880
805
755
1900
1800
1700

14

Insulator

2248
3813
3813
4495
4495
5270
5270

[N]

19

20

Weights

[N]

[kg]
18
20
23
34
210 3150 1575 vh
37
40
46
210 3150 1575 vh
50
54
20
310 3150 1575 vh
22
25
36
310 3150 1575 vh
39
42
49
310 3150 1575 vh
53
57
24
460 3150 1575 vh
27
29
40
460 3150 1575 vh
44
48
52
460 3150 1575 vh
57
62
30
630 3150 1575 vh
33
35
45
630 4000 2000 vh
49
53
60
630 4000 2000 vh
65
70
62
1010 4000 2000 vh
66
70
79
1010 4000 2000 vh
85
90
1170 4000 2000 v30 87
93
99
130
1170 4000 2000 vh
139
148
1400 5000 2500 v30 100
106
112
145
1400 5000 2500 vh
154
163
210 3150 1575 vh

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV13

With porcelain insulator

13

Creepage distance (minimum)

Lightning impulse voltage,


1.2/50 s

AC test voltage dry/wet

29 105/ 250

140/

140/

145

29 105/ 250

95/

140/

145

80/ 200

95/

30 105/ 250 46

230/

22

95/

30 105/ 250 46

230/

80/ 200

75/

95/
52

80/ 200

75/

95/
52

60/ 150

75/

70/
52

60/ 150

50/

70/

RTKF 72.5350/2500 KSI RTKF 72.5350/2500 72.5

1ZCD064013

21

60/ 150

50/

70/

1ZCD064061

RTKF 123550/800

16

50/

RTKF 72.5350/2000 KSI RTKF 72.5350/2000 72.5

RTKF 123550/800 KSI

14

[kV] [kV]
50/

55/ 125 25
50/

1ZCD064060

1ZCD064062

16

50/

RTKF 72.5350/1000 KSI RTKF 72.5350/1000 72.5

1ZCD064012

[kV] [kV] [kV] [kV]


55/ 125 25

12

Thermal short-time current


Ith 2sec.

[kV] [kV]

Rated max.
line-to-ground voltage

(2000)

System voltage

insulator

IEEE C57.19.01

Lightning impulse voltage,


1.2/50 s

composite insulator

11

Current

With silicone composite insulator

10

Installation (v = vertical,
h = horizontal, from vertical)

Cantilever operating load

Ith 2sec. [kA] = 0.055 S [mm 2 ] if S = 1200 mm 2


Ith 2sec. [kA] = 0.045 S [mm 2 ] if S = 2800 mm 2

(2008)

AC test voltage dry/wet

With porcelain

1ZCD064011

IEC 60137

Rated Voltage Ur

With silicone

1ZCD064010

Ith 2sec. [kA] = 0.06 S [mm 2 ] if S 700 mm 2


Ith 2sec. [kA] = 0.05 S [mm 2 ] if S = 1500 mm 2

With copper cable section S

Electrical characteristics

Maximum operating current


(in respect to CT extension L6)

Type and drawing

Ur/3

Cantilever test load, 1min.

Data for bushings with cable conductor 24 170 kV

[kg]
31
34
36
50
53
56
65
69
73
38
41
43
60
63
66
77
81
85
49
51
53
72
76
79
87
92
97
63
65
68
91
95
99
110
115
120
132
136
141
156
162
167
173
179
185
245
255
264
203
209
215
282
291
300

23

24

25

26

27

28

29

30

31

Air side

32

33

34

35

36 37 38 39 40

Flange

41 42

43 44

Air side

45

46

47

48 49

50

51

52

Figure

22

Oil side

Shield length below L16

21

Oil side end

terminal

185 225 135 165

6 16 18 10

250 290 180 222

8 16 18 11

290 335 205 261 12 16 18 12


185 225 135 165

6 16 18 10

250 290 180 222

8 16 18 11

290 335 205 261 12 16 18 12


185 225 135 165

6 16 18 10

250 290 180 222

8 16 18 11

290 335 205 261 12 16 18 12


250 290 180 222

8 16 18 11

290 335 205 261 12 16 18 12


290 335 205 261 12 16 18 12
400 450 245 365 12 20 22 12
290 335 205 261 12 16 18 12
400 450 245 365 12 20 22 12

Shield length below L16

c2 d2

c2

d5

d6

30

80 40 125

61

20

40 125 50 125

91

20

60 125 50 125 111

20

30

c7 Fig d5

d6

c7 Fig

67 109

80 21

67 109

80 21

Figure

Shield diameter

290 335 205 261 12 16 18 12

d2

Opening

8 16 18 11

Shield diameter

250 290 180 222

L
645
945
1245
685
985
1285
695
995
1295
765
1065
1365
805
1105
1405
815
1115
1415
915
1215
1515
955
1255
1555
965
1265
1565
1150
1450
1750
1190
1490
1790
1200
1500
1800
1705
2005
2305
1715
2015
2315
1925
2225
2525
1945
2245
2545
2215
2515
2815
2235
2535
2835

Opening

s Fig

Length of terminal

6 16 18 10

Variant

Terminal diameter

Standard

Length of terminal

Hole diameter

D8

Var.

Terminal diameter

Number of holes

D2

Figure

Sealing area: max. diameter

D4

185 225 135 165

Bushing length, without air


side terminal and lower shield

Sealing area: min. diameter

D3

Flange plate thickness

Outside flange diameter

L6 L16 D1 d3
L2
L4 L5 D5 D6 D5 D6
0 120 92 50 525 350 135 135 270 178 300
300 420
600 720
0 120 120 80 565 390 135 165 300 216 350
300 420
600 720
0 120 144 100 575 400 145 200 322 245 380
300 420
600 720
0 140 92 50 625 450 135 135 270 178 300
300 440
600 740
0 140 120 80 665 490 135 165 300 216 350
300 440
600 740
0 140 144 100 675 500 145 200 322 245 380
300 440
600 740
0 140 92 50 775 600 135 135 270 178 300
300 440
600 740
0 140 120 65 815 640 135 165 300 216 350
300 440
600 740
0 140 144 80 825 650 145 200 322 245 380
300 440
600 740
0 175 92 40 975 800 165 135 270 178 300
300 475
600 775
0 175 120 65 1015 840 165 165 300 216 350
300 475
600 775
0 175 144 80 1025 850 175 200 322 245 380
300 475
600 775
0 310 120 40 1395 1220 165 165 300 216 350
300 610
600 910
0 310 144 65 1405 1230 175 200 322 245 380
300 610
600 910
0 360 144 50 1565 1390 175 200 322 245 380
300 660
600 960
0 360 185 80 1585 1410 175 245 370 315 450
300 660
600 960
0 420 144 40 1795 1620 175 200 322 245 380
300 720
600 1020
0 420 185 80 1815 1640 175 245 370 315 450
300 720
600 1020

Pitch circle diameter

Head diameter (with silicone


composite insulator)
Max. shed diameter (with
s ilicone composite insulator)
Head diameter
(with porcelain insulator)
Max. shed diameter
(with porcelain insulator)

Height of head (maximum)

Cable bolt:
distance from the flange plate

Terminal: distance from the


flange plate (tolerance 5 mm)

Inside tube diameter

Core diameter

Lower core length


(tolerance 5 mm)

Current transformer extension

Std.

80 40 125

61

20

40 125 50 125

91

20

60 125 50 125 111

20

30

80 40 125

61

20

67 109

80 21

40 125 50 125

76

20

75 134

90 21

50 125 40 125

91

20

30

51

20

67 109

80 21

40 125 50 125

76

20

75 134

90 21

40 125 50 125

91

20

30

67 109

80 21 107 160 200 22

40 125 50 125

75 134

90 21 140 180 200 22

30

75 134

90 21 107 160 200 22

80

80

80 40 125

40 125 50 125 140 180 170 22 140 180 200 22


30

80

75 134

90 21 107 160 200 22

40 125 50 125 140 180 170 22 140 180 200 22

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV14

AirRIP bushings 24170 kV


Types with rod conductor
Determination of the rod conductor
 d2

Air side terminal


Standard terminals as per columns 39/40,
variants as per columns 41/42.
Guidelines for the terminal dimensions:

30
c2

30

Max. operating current (A)

d2

c2

1600

30

80

2500

40

125

3500

50

125

4300

60

125

5000

flat 90105

thickness 30

 90
a1
40

20
105 50

18

L2
In = 5000 A

30

30

a1

screws

length e1

40

38

2M8

80

50

45

3M10

110

65

60

3M10

110

80

75

3M12

110

100

95

6M12

110

20

d4

d3*

e1

Optional splitting of the rod conductor


Determine whether the rod conductor should be split or not.
Rod conductors are split 20 mm below the base plate and
have the following characteristics:

* See column 23 of the data table

30

a1

30

Oil side terminal


Standard

Var. 1

Standard: flat

Var. 2

ng1
a1

threadc1

L16
d1c1

40

38

20

214

3085

50

45

20

218

M36360

30
4085

65

60

30

218

M42380

5085

80

75

30

218

100

95

30

418

30

L16

thickness
holes

30

 g1
40
 g1
40 20
 d4
85
20
a1
 d4
85

30

c1

30

Var.1:
thread
L16
L16
 d4
 d4

L: Bushing length, without airside terminal and lower shield,


see column 38 of the data table
15 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

30

d1G
d1G

 d4

30

30

40
40 20
20

 g1
 g1
40
85
40  d4 85
 d4

5085

* See column 23 of the data table

30

L16
L16

Var.2:
L16round
L16
 d4
 d4
5
5

30
30

d4

flat thread
round

c1
c1

10

d3*

10
d1
d1

c1
c1

Bushings with rod conductor 24 170 kV


Fig. 3

Fig. 4

Legend
 d2

c2

c2

 d2
1

1 Copper, bare (optional:


3 De-aeration

 D5

 D5

4 Earthing screws 2M12/180

L5
max.

L5
max.

nickel-plated, silver-plated)

2 Test tap

5
6 Sealing area
 c2
7 Removability (for connecting

L 2 (5)

 D6
max.

the transformer lead)

L6 Current
transformer extension
Spaltenbreiten

(L)

(L)

L 2 (5)

 D6
max.

Air side

25

 D1

a1

 18

c7

L2

105

L16 5

30 40

50

20

d2
30

L6

 D1

L6

L16 5

20

In = 5000 A

Flange detail

Flange
30

60

15

30

22.5

2
 D3
 D4

 D3
 D4

 D3
 D4

Fig. 22

 d3

L16

L16
20

 d3

50

c7

 d5

 d5
 d6

16 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

6
 D2
 D8

Oil side end


Fig. 20

a1

12

30

30
nv

45

30

Fig. 12

Fig. 11

5 45

Fig. 10

All dimensions in mm, unless otherwise indicated

Data for bushings with rod conductor 24 170 kV


6

10

RTKF 24150/5000 B KSI

RTKF 24150/5000 B

1ZCD064003

1ZCD064053

RTKF 36200/2000 B KSI

RTKF 36200/2000 B

1ZCD064004

1ZCD064054

RTKF 36200/3150 B KSI

RTKF 36200/3150 B

1ZCD064005

1ZCD064055

RTKF 36200/4000 B KSI

RTKF 36200/4000 B

1ZCD064006

1ZCD064056

RTKF 52250/2000 B KSI

RTKF 52250/2000 B

1ZCD064007

1ZCD064057

RTKF 52250/2500 B KSI

RTKF 52250/2500 B

1ZCD064008

1ZCD064058

RTKF 52250/3150 B KSI

RTKF 52250/3150 B

1ZCD064009

1ZCD064059

[kV]

24

14

55/50

125 25

16

60/50

24

14

55/50

125 25

16

60/50

24

14

55/50

125 25

16

60/50

36

21

77/70

170 34.5

22

80/75

36

21

77/70

170 34.5

22

80/75

36

21

77/70

170 34.5

22

80/75

52

30

105/95

250 46

29

105/95

52

30

105/95

250 46

29

105/95

52

30

105/95

250 46

29

105/95

RTKF 72.5350/1600 B KSI RTKF 72.5350/1600 B 72.5

42

155/140

325 69

44

160/140

42

155/140

325 69

44

160/140

42

155/140

325 69

44

160/140

123

71

255/230

550 92TR

73

185/155

123

71

255/230

550 92TR

73

185/155

145

84

305/275

650 138

88

310/275

145

84

305/275

650 138

88

310/275

170

98

355/325

750 161TR 102

365/315

170

98

355/325

750 161TR 102

365/315

1ZCD064010
1ZCD064011
1ZCD064012

1ZCD064062

RTKF 123550/1600 B KSI

RTKF 123550/1600 B

1ZCD064013

1ZCD064063

RTKF 123550/2500 B KSI RTKF 123550/2500 B

1ZCD064065

RTKF 145650/2500 B KSI RTKF 145650/2500 B


1ZCD064016

1ZCD064066

RTKF 170750/1250 B KSI

RTKF 170750/1250 B

1ZCD064017

1ZCD064067

RTKF 170750/2500 B KSI

RTKF 170750/2500 B

1ZCD064018

1ZCD064068

data

design

[kV] [kV]

1ZCD064064

RTKF 145650/2000 B KSI RTKF 145650/2000 B


1ZCD064015

[kV]

1ZCD064061

RTKF 72.5350/3150 B KSI RTKF 72.5350/3150 B 72.5

1ZCD064014

[kV] [kV]

1ZCD064060

RTKF 72.5350/2500 B KSI RTKF 72.5350/2500 B 72.5

16

17

Installation (v = vertical,
h = horizontal, from vertical)

1ZCD064052

15

Mechanical

Cantilever operating load

RTKF 24150/3150 B

1ZCD064002

14

Cantilever test load, 1min.

1ZCD064051

RTKF 24150/3150 B KSI

13

Insulator

Arcing distance (minimum)

1ZCD064001

[kV] [kV]

Lightning impulse voltage,


1.2/50 s

RTKF 24150/2000 B

AC test voltage dry/wet

RTKF 24150/2000 B KSI

Rated max.
line-to-ground voltage

insulator

12

IEEE C57.19.01 (2000)

Lightning impulse voltage,


1.2/50 s

composite insulator

AC test voltage dry/wet

With porcelain

Rated Voltage Ur

With silicone

Ur/3

IEC 60137 (2008)

11

Current

Creepage distance (minimum)

Thermal short-time current


Ith 2sec.

Electrical characteristics

[A] [kA] [mm] [mm]


[N]
[N]
150 2350
744
210 3150 1575 vh
2100
1850
150 3600
744
210 3150 1575 vh
3200
2850
150 5000
744
210 3150 1575 vh
4300
3850
200 2300
1116
310 3150 1575 vh
2050
1800
200 3500
1116
310 3150 1575 vh
3150
2850
200 4800
1116
310 3150 1575 vh
4200
3800
250 2250
460 3150 1575 vh
1612
2000
1750
250 2800
1612
460 3150 1575 vh
2470
2200
250 3500
1612
460 3150 1575 vh
3100
2850
350 1750
2248
630 3150 1575 vh
1580
1430
350 2650
2248
630 4000 2000 vh
2380
2150
350 3400
2248
630 4000 2000 vh
3050
2780
450 1670
3813 1010 4000 2000 vh
1520
1370
450 2610
3813 1010 4000 2000 vh
2370
2180
650 2000
4495 1170 4000 2000 v30
1800
1670
650 2900
4495 1170 4000 2000 vh
2720
2550
750 1360
5270 1400 5000 2500 v30
1250
1170
750 2800
5270 1400 5000 2500 vh
2620
2450
Ith 2sec. = 25 Ir

Maximum operating current


(in respect to CT extension L6)

System voltage

1
Type and drawing

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV17

18

19

Weights

20

21

22

23

Oil side

24

25

26

27

28

29

Air side

30

31

32

33 34 35 36 37 38

Flange

39

40

41 42

Air side

43

44

45 46 47 48

49 50

Oil side end

terminal

s Fig

135 165

6 16 18 10

180 222

8 16 18 11

205 261 12 16 18 12
135 165

6 16 18 10

180 222

8 16 18 11

205 261 12 16 18 12
135 165

6 16 18 10

180 222

8 16 18 11

205 261 12 16 18 12
135 165

6 16 18 10

180 222

8 16 18 11

205 261 12 16 18 12
180 222

8 16 18 11

205 261 12 16 18 12
205 261 12 16 18 12
245 365 12 20 22 12
205 261 12 16 18 12
245 365 12 20 22 12

Figure

Shield length below L16

Shield diameter

Figure

Opening

Variant

Shield length below L16

Shield diameter

Opening

Standard

Length of terminal

Terminal diameter

Var.

Length of terminal

Terminal diameter

Bushing length, without air


side terminal and lower shield

Figure

Flange plate thickness

D8

Hole diameter

Sealing area: max. diameter

D2

Number of holes

Sealing area: min. diameter

Outside flange diameter

Pitch circle diameter

Head diameter (with silicone


composite insulator)
Max. shed diameter (with
s ilicone composite insulator)
Head diameter
(with porcelain insulator)
Max. shed diameter
(with porcelain insulator)

Height of head (maximum)

Terminal: distance from the


flange plate (tolerance 5 mm)

L6 L16 D1 d3
L2 L5 D5 D6 D5 D6 D3 D4
0 120 92 50 525 135 135 270 178 300 185 225
300 420
600 720
0 120 120 80 565 135 165 300 216 350 250 290
300 420
600 720
0 120 144 100 575 145 200 322 245 380 290 335
300 420
600 720
0 140 92 50 625 135 135 270 178 300 185 225
300 440
600 740
0 140 120 80 665 135 165 300 216 350 250 290
300 440
600 740
0 140 144 100 675 145 200 322 245 380 290 335
300 440
600 740
0 140 92 50 775 135 135 270 178 300 185 225
300 440
600 740
0 140 120 65 815 135 165 300 216 350 250 290
300 440
600 740
0 140 144 80 825 145 200 322 245 380 290 335
300 440
600 740
0 175 92 40 975 165 135 270 178 300 185 225
300 475
600 775
0 175 120 65 1015 165 165 300 216 350 250 290
300 475
600 775
0 175 144 80 1025 175 200 322 245 380 290 335
300 475
600 775
0 310 120 40 1395 165 165 300 216 350 250 290
300 610
600 910
0 310 144 65 1405 175 200 322 245 380 290 335
300 610
600 910
0 360 144 50 1565 175 200 322 245 380 290 335
300 660
600 960
0 360 185 80 1585 175 245 370 315 450 400 450
300 660
600 960
0 420 144 40 1795 175 200 322 245 380 290 335
300 720
600 1020
0 420 185 80 1815 175 245 370 315 450 400 450
300 720
600 1020

Inside tube diameter

Current transformer extension

[kg]
40
46
53
74
88
103
84
98
112
49
55
61
88
103
118
100
114
128
61
68
74
94
105
117
122
139
155
73
79
84
119
130
141
153
170
187
150
157
165
198
211
224
201
211
221
318
339
360
226
235
244
366
387
407

Core diameter

With porcelain insulator

[kg]
27
33
39
57
72
87
66
80
94
30
37
43
64
79
94
73
87
101
37
43
49
63
74
85
87
104
120
41
46
52
73
84
95
104
121
138
80
87
94
121
134
147
114
125
135
203
224
245
122
132
141
230
250
271

Lower core length


(tolerance 5 mm)

With silicone composite insulator

Std.

L d2 c2 d2 c2 d5 d6 c7 Fig d5 d6 c7 Fig
645 40 125
61
20
945
1245
685 60 125 50 125 91
20
985
1285
695 F90 105
111
20
995
1295
765 40 125
61
20
1065
1365
805 60 125 50 125 91
20
1105
1405
815 F90 105
111
20
1115
1415
915 40 125
61
20
1215
1515
955 50 125 40 125 76
20
1255
1555
965 60 125 50 125 91
20
1265
1565
1150 30 80
51
20 107 160 200 22
1450
1750
1190 50 125 40 125 76
20
1490
1790
1200 60 125 50 125 91
20
1500
1800
1705 30 80
107 160 200 22
2005
2305
1715 50 125 40 125 140 180 200 22
2015
2315
1925 40 125
107 160 200 22
2225
2525
1945 50 125
140 180 200 22
2245
2545
2215 30 80
107 160 200 22
2515
2815
2235 50 125
140 180 200 22
2535
2835
Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV18

AirRIP bushings 24170 kV


Types with fixed conductor
Explanations of the table columns
36 Rated voltages according to IEC 60137 (2008)
710 Rated voltages according to IEEE C57.19.01 (2000)
11
Maximum operating current Ir as a function of the

current transformer extension L6
12
Maximum thermal short-circuit current, 2 sec.,

after operation at maximum operating current
Bending test load, 1 min.
15
16, 17 Maximum cantilever operating load and permissible

installation position (v = vertical, h = horizontal,

from vertical)
25, 26 Maximum head and shed diameter for silicone

composite insulator

19 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

27, 28 Maximum head and shed diameter for porcelain insulator


31, 32 Sealing area
Bushing length L, without air side terminal and
37

oil side shield
38, 39 Standard terminal on air side
40, 41 Optional terminal on air side
42, 43 Standard design of oil side terminal
4446 Standard design of oil side end
4749 Optional design of oil side end

Bushings with fixed conductor 24 170 kV


Fig. 3

Fig. 4

Legend
 d2

1 Copper, bare (optional:

c2

c2

 d2
1

3 De-aeration

 D5

 D5

4 Earthing screws 2M12/180

L5
max.

L5
max.

5
6 Sealing area
 c2
7 Removability (for connecting

L 2 (5)

 D6
max.

the transformer lead)

L6 Current
transformer extension
Spaltenbreiten

(L)

(L)

L 2 (5)

 D6
max.

nickel-plated, silver-plated)

2 Test tap

Air side
In = 5000 A
20

25

30 40

a1

 18

c7

L2

105

L16 5

L6

 D1

50

20

 D1

L6

L16 5

d2
30

Flange detail

Flange
Fig. 11

30

60

12

15

30

22.5

2
 D3
 D4

6
 D2
 D8

 D3
 D4

Oil side end

a1

nv

30

30

45

30

Fig. 12

5 45

Fig. 10

 D3
 D4

Oil side

Fig. 24

Fig. 30

Fig. 31

30
 d5
 d6

20 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

 d4

30
30

40
 d4

85


18

20 40


18

20 40

85

c7

30

L16

L16

L16
20

 d3

All dimensions in mm, unless otherwise indicated

Data for bushings with fixed conductor 24 170 kV


6

10

RTKF 24150/5000 F KSI

RTKF 24150/5000 F

1ZCD064028

1ZCD064078

RTKF 36200/2500 F KSI

RTKF 36200/2500 F

1ZCD064029

1ZCD064079

RTKF 36200/4000 F KSI

RTKF 36200/4000 F

1ZCD064030

1ZCD064080

RTKF 36200/5000 F KSI

RTKF 36200/5000 F

1ZCD064031

1ZCD064081

RTKF 52250/2500 F KSI

RTKF 52250/2500 F

1ZCD064032

1ZCD064082

RTKF 52250/3150 F KSI

RTKF 52250/3150 F

1ZCD064033

1ZCD064083

RTKF 52250/4000 F KSI

RTKF 52250/4000 F

1ZCD064034

1ZCD064084

[kV]

24

14

55/50

125 25

16

60/50

24

14

55/50

125 25

16

60/50

24

14

55/50

125 25

16

60/50

36

21

77/70

170 34.5

22

80/75

36

21

77/70

170 34.5

22

80/75

36

21

77/70

170 34.5

22

80/75

52

30

105/95

250 46

29

105/95

52

30

105/95

250 46

29

105/95

52

30

105/95

250 46

29

105/95

RTKF 72.5350/2000 F KSI RTKF 72.5350/2000 F 72.5

42

155/140

325 69

44

160/140

42

155/140

325 69

44

160/140

42

155/140

325 69

44

160/140

123

71

255/230

550 92TR

73

185/155

123

71

255/230

550 92TR

73

185/155

145

84

305/275

650 138

88

310/275

145

84

305/275

650 138

88

310/275

170

98

355/325

750 161TR 102

365/315

170

98

355/325

750 161TR 102

365/315

1ZCD064035
1ZCD064036

[kV]

[kV] [kV]

1ZCD064086

RTKF 72.5350/4000 F KSI RTKF 72.5350/4000 F 72.5


1ZCD064037

[kV] [kV]

1ZCD064085

RTKF 72.5350/3150 F KSI RTKF 72.5350/3150 F 72.5

1ZCD064087

RTKF 123550/2000 F KSI RTKF 123550/2000 F


1ZCD064038

1ZCD064088

RTKF 123550/3150 F KSI

RTKF 123550/3150 F

1ZCD064039

1ZCD064089

RTKF 145650/2000 F KSI RTKF 145650/2000 F


1ZCD064040

1ZCD064090

RTKF 145650/3150 F KSI

RTKF 145650/3150 F

1ZCD064041

1ZCD064091

RTKF 170750/2000 F KSI

RTKF 170750/2000 F

1ZCD064042

1ZCD064092

RTKF 170750/3150 F KSI

RTKF 170750/3150 F

1ZCD064043

1ZCD064093

16

17

data

design

[A]
150 3050
2650
2400
150 4200
3800
3500
150 5200
4500
4100
200 3000
2600
2350
200 4150
3750
3450
200 5150
4500
4100
250 2840
2520
2300
250 3400
3000
2680
250 4250
3800
3500
350 2200
1950
1800
350 3250
2950
2700
350 4100
3700
3400
450 2250
2100
2000
450 3150
2900
2700
650 2420
2230
2100
650 3600
3380
3150
750 2100
2000
1900
750 3500
3280
3050

[kA]

[mm]

[mm]

[N]

Installation (v = vertical,
h = horizontal, from vertical)

1ZCD064077

15

Mechanical

Cantilever operating load

RTKF 24150/4000 F

1ZCD064027

14

Cantilever test load, 1min.

1ZCD064076

RTKF 24150/4000 F KSI

13

Insulator

Arcing distance (minimum)

1ZCD064026

[kV] [kV]

Lightning impulse voltage,


1.2/50 s

RTKF 24150/2500 F

AC test voltage dry/wet

RTKF 24150/2500 F KSI

Rated max.
line-to-ground voltage

insulator

12

IEEE C57.19.01 (2000)

Lightning impulse voltage,


1.2/50 s

composite insulator

AC test voltage dry/wet

With porcelain

Rated Voltage Ur

With silicone

Ur/3

IEC 60137 (2008)

11

Current

Creepage distance (minimum)

Thermal short-time current


Ith 2sec.

Ith 2sec. = 25 Ir

Electrical characteristics

Maximum operating current


(in respect to CT extension L6)

System voltage

1
Type and drawing

[N]

744

210 3150 1575 vh

744

210 3150 1575 vh

744

210 3150 1575 vh

1116

310 3150 1575 vh

1116

310 3150 1575 vh

1116

310 3150 1575 vh

1612

460 3150 1575 vh

1612

460 3150 1575 vh

1612

460 3150 1575 vh

2248

630 3150 1575 vh

2248

630 4000 2000 vh

2248

630 4000 2000 vh

3813 1010 4000 2000 vh


3813 1010 4000 2000 vh
4495 1170 4000 2000 v30
4495 1170 4000 2000 vh
5270 1400 5000 2500 v30
5270 1400 5000 2500 vh

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV21

19

Weights

20

21

22

Oil side

23

24

25

26

27

28

Air side

29

30

31

32 33 34 35 36 37

38

Flange

39

40

41

Air side

Oil side

terminal

terminal

42

43

44

45 46 47

538 108 165 300 216 350 250 290 180 222

8 16 18 11

548 118 200 322 245 380 290 335 205 261 12 16 18 12
598 108 135 270 178 300 185 225 135 165

6 16 18 10

638 108 165 300 216 350 250 290 180 222

8 16 18 11

648 118 200 322 245 380 290 335 205 261 12 16 18 12
748 108 135 270 178 300 185 225 135 165

6 16 18 10

788 108 165 300 216 350 250 290 180 222

8 16 18 11

798 118 200 322 245 380 290 335 205 261 12 16 18 12
948 138 135 270 178 300 185 225 135 165

6 16 18 10

988 138 165 300 216 350 250 290 180 222

8 16 18 11

998 148 200 322 245 380 290 335 205 261 12 16 18 12
1368 138 165 300 216 350 250 290 180 222

8 16 18 11

1378 148 200 322 245 380 290 335 205 261 12 16 18 12
1538 148 200 322 245 380 290 335 205 261 12 16 18 12
1558 148 245 370 315 450 400 450 245 365 12 20 22 12
1768 148 200 322 245 380 290 335 205 261 12 16 18 12
1788 148 245 370 315 450 400 450 245 365 12 20 22 12

Shield diameter

Shield length below L16

d6

Opening

d5

c7 Fig d5

d6

c7 Fig

Figure

Shield diameter

Fig

Variant

Shield length below L16

Opening

L d2 c2 d4
618 50 125 52
918
1218
658 60 125 80
958
1258
668 F90 105 100
968
1268
738 50 125 52
1038
1338
778 60 125 80
1078
1378
788 F90 105 100
1088
1388
888 50 125 52
1188
1488
928 50 125 65
1228
1528
938 60 125 80
1238
1538
1123 40 125 45
1423
1723
1163 50 125 65
1463
1763
1173 60 125 80
1473
1773
1678 40 125 45
1978
2278
1688 50 125 65
1988
2288
1898 40 125 52
2198
2498
1918 60 125 80
2218
2518
2188 40 125 45
2488
2788
2208 60 125 80
2508
2808

Figure

s Fig

Terminal width

Length of terminal

6 16 18 10

Terminal diameter

D8

498 108 135 270 178 300 185 225 135 165

Bushing length, without air


side terminal and lower shield

D2

Figure

D4

Flange plate thickness

D3

Hole diameter

D6

Number of holes

D5

Sealing area: max. diameter

D6

Sealing area: min. diameter

D5

Outside flange diameter

L5

Pitch circle diameter

Height of head (maximum)

L2

Head diameter (with silicone


composite insulator)
Max. shed diameter (with
s ilicone composite insulator)
Head diameter
(with porcelain insulator)
Max. shed diameter
(with porcelain insulator)

Terminal: distance from the


flange plate (tolerance 5 mm)

Current transformer extension

L6 L16 D1
0 120 92
300 420
600 720
0 120 120
300 420
600 720
0 120 144
300 420
600 720
0 140 92
300 440
600 740
0 140 120
300 440
600 740
0 140 144
300 440
600 740
0 140 92
300 440
600 740
0 140 120
300 440
600 740
0 140 144
300 440
600 740
0 175 92
300 475
600 775
0 175 120
300 475
600 775
0 175 144
300 475
600 775
0 310 120
300 610
600 910
0 310 144
300 610
600 910
0 360 144
300 660
600 960
0 360 185
300 660
600 960
0 420 144
300 720
600 1020
0 420 185
300 720
600 1020

Core diameter

With porcelain insulator


[kg]
47
57
66
88
108
128
92
107
122
57
67
76
105
124
144
108
123
139
71
81
90
108
123
138
116
130
144
82
89
97
137
152
167
145
159
173
162
171
181
249
266
283
221
234
247
303
321
339
241
252
263
348
366
384

Lower core length


(tolerance 5 mm)

With silicone composite insulator

Standard Standard Standard

[kg]
34
44
53
72
92
112
73
89
104
39
49
58
81
101
121
81
96
111
47
56
66
77
92
107
81
95
109
49
57
64
91
106
121
96
110
124
92
101
110
172
189
206
135
148
161
187
205
224
138
149
160
212
229
247

48 49

Oil side end

Figure

18

30

30

31

31

31

31

30

30

31

31

31

31

30

30

30

30

31

31

30

30 107 160 200 24

30

30

31

31

30 107 160 200 24


30 140 180 200 24
30 107 160 200 24
31 140 180 200 24
30 107 160 200 24
31 140 180 200 24

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV22

AirRIP bushings 245550 kV


Types with cable conductor
Explanations of the table columns
37
812
13, 14


15

18
19, 20


23

Rated voltages according to IEC 60137 (2008)


Rated voltages according to IEEE C57.19.01 (2000)
Maximum operating current for the largest cable
cross-section, depending on the current transformer
extension L6
Maximum thermal short-circuit current, 2 sec.,
after operation at maximum operating current
Bending test load, 1 min.
Maximum cantilever operating load and permissible
installation position (v = vertical, h = horizontal,
from vertical)
Standard current transformer extension L6

23 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

26
Inner diameter of the central tube ( d3)
30, 31 Maximum head and shed diameter for silicone

composite insulator
32, 33 Maximum head and shed diameter for porcelain insulator
36, 37 Sealing area
Bushing length L, without air side terminal and
42

oil side shield
43, 44 Standard terminal on air side
45, 46 Optional terminal on air side
4750 Standard design of oil side end
5154 Optional design of oil side end

Bushings with cable conductor 245 550 kV


Fig. 5

Fig. 6

Legend

c2

 d2

 d2

c2

 D5

nickel-plated, silver-plated)

2 Test tap

L5
max.

L5
max.

1 Copper, bare (optional:

 D5

3 De-aeration
4 Earthing screws 2M12/180

L 2 (5)

7 Removability (for connecting


 D6
max.

the transformer lead)

L6 Current transformer extension

20

20

(L)

(L)

 D6
max.

6 Sealing area

L4 cable bolts

L4 cable bolts

L 2 (5)

5 Eyebolts 2M16/180

L6

 D1

c7

c7

L16 5

L16 5

L6

 D1

Flange

Flange detail
Fig. 13

Fig. 14

nv
2 2.

15

15

30

30

2. 5
2

16

12

12

.25
11

30

5 45

Fig. 12

6
 D2
 D8

 D3
 D4

 D3
 D4

 D3
 D4

Oil side end


Fig. 23

Fig. 22
 d3

 d3

c7

L16

L16
20

L16
20

 d3

c7

c7

Fig. 21

 d5
 d6
 d5
 d6

24 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

 d5
 d6

All dimensions in mm, unless otherwise indicated

Data for bushings with cable conductor 245 550 kV


6

[kV]

1ZCD064069

RTKF 2451050/1600 KSI RTKF 2451050/1600 245 141 505/460 1050


1ZCD064070

RTKF 3001175/1000 KSI RTKF 3001175/1000 300 173

750/ 1675

1ZCD064074

RTKF 5501800/1000 KSI RTKF 5501800/1000 550 318


1ZCD064025

750/ 1675

1ZCD064073

RTKF 4201675/2000 KSI RTKF 4201675/2000 420 242


1ZCD064024

560/ 1175

1ZCD064072

RTKF 4201675/1000 KSI RTKF 4201675/1000 420 242


1ZCD064023

560/ 1175

1ZCD064071

RTKF 3001175/2000 KSI RTKF 3001175/2000 300 173


1ZCD064022

11

12

1ZCD064075

13

14

15 16

Current

870/ 1800

17

18

19

Insulator

Mechanical

data

design

[kV]

[A]
750 230 146 425/350 900 750 1030
880
820
750 230 146 425/350 900 750 1700
1560
1450
1000
850
850
780
2250
850
2100
2000
1100
1175
1250
1000
2000
1175
1850
1700
1240 500 318
750/ 1675 1175 1050
1100
900

[mm2]

[mm] [mm]

[N]

20

Installation (v = vertical,
h = horizontal, from vertical)

Cantilever operating load

Cantilever test load, 1min.

[kV]

Arcing distance (minimum)

[kV]

Creepage distance (minimum)

AC test voltage dry/wet

Rated max.
line-to-ground voltage

[kV] [kV] [kV]

Switching impulse voltage


250/2500 s

[kV]

RTKF 2451050/1000 KSI RTKF 2451050/1000 245 141 505/460 1050

1ZCD064021

10

Lightning impulse voltage,


1.2/50 s

[kV] [kV]

Switching impulse voltage


250/2500 s

insulator

1ZCD064020

IEEE C57.19.01 (2000)

Lightning impulse voltage,


1.2/50 s

composite insulator

AC test voltage dry/wet

With porcelain

Rated Voltage Ur

With silicone

Ur/3

IEC 60137 (2008)

1ZCD064019

Thermal short-time current Ith2sec.

[N]

665

7595 2050 5000 2500 v30

1500

7595 2050 5000 2500 v30

665

9300 2370 5000 2500 v30

2800
1200
1500
1500
2800
1200
1500
1500

see footnote *

With copper cable section S

Electrical characteristics

Maximum operating current


(in respect to CT extension L6)

System voltage

1
Type and drawing

9300 2370 5000 2500 v30


13020 3600 5000 2500 v30
13020 3600 5000 2500 v30
13750 4000 5000 2500 v30

* Ith 2sec. [kA] = 0.06 S [mm 2 ] if S 700 mm 2


Ith 2sec. [kA] = 0.055 S [mm 2 ] if S = 1200 mm 2
Ith 2sec. [kA] = 0.05 S [mm 2 ] if S = 1500 mm 2
Ith 2sec. [kA] = 0.045 S [mm 2 ] if S = 2800 mm 2

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV25

21 22

23

24

25

26 27

Weights Oil side

28

29

30

31

32

33

Air side

34

35

36

37 38 39 40 41 42

Flange

43 44 45 46 47 48
Air side

49 50 51

52

53 54

Oil side end

terminal

[kg]
190
200
209
272
286
301
296
312
328
422
444
466
614
632
654
782
813
845
862
889
921

[kg]
L6 L16 D1 d3
L2
L4 L5 D5 D6 D5 D6
376
0 590 185 50 2465 2290 175 245 370 315 450
386
300 890
396
600 1190
487
0 590 234 80 2474 2299 184 315 428 375 480
502
300 890
516
600 1190
574
0 590 234 50 2794 2619 184 315 428 375 480
590
300 890
606
600 1190
801
0 590 285 100 2920 2745 200 365 479 435 520
823
300 890
845
600 1190
1130 0200 790 285 65 4150 3975 200 550 479 550 520
1148
300 1090
80
1170
600 1390
80
1423
0 790 338 100 4200 4025 200 550 547 550 580
1454
300 1090
1486
600 1390
1553 0200 850 338 65 4600 4425 200 550 547 550 580
1580
300 1150
80
1612
600 1450
80

D3 D4 D2 D8 n v s Fig
L d2
400 450 245 365 12 20 22 12 3055 30
3355
3655
400 450 295 365 12 20 22 13 3064 30
3364
3664
400 450 295 365 12 20 22 13 3384 30
3684
3984
450 500 355 415 12 20 25 13 3510 40
3810
4110
620 680 355 580 16 22 25 14 4940 30
5240
5540
620 680 410 580 16 22 25 14 4990 40
5290
5590
620 680 410 580 16 22 25 14 5450 30
5750
6050

c2 d2 c2 d5 d6
80 40 125

c7 Fig d5 d6

Shield length below L16

Figure

Shield diameter

Opening

Figure

Variant

Shield length below L16

Shield diameter

Opening

Standard

Length of terminal

Terminal diameter

Var.

Length of terminal

Terminal diameter

Figure

Bushing length, without air


side terminal and lower shield

Flange plate thickness

Hole diameter

Number of holes

Sealing area: max. diameter

Sealing area: min. diameter

Outside flange diameter

Pitch circle diameter

Head diameter (with silicone


composite insulator)
Max. shed diameter (with
s ilicone composite insulator)
Head diameter
(with porcelain insulator)
Max. shed diameter
(with porcelain insulator)

Height of head (maximum)

Cable bolt:
distance from the flange plate

Terminal: distance from the


flange plate (tolerance 5 mm)

Inside tube diameter

Core diameter

Lower core length


(tolerance 5 mm)

Current transformer extension

With porcelain insulator

With silicone composite insulator

Std.

c7 Fig

95 180 130 21 140 180 200 22

80 40 125 140 180 170 22 140 180 200 22


80 40 125 134 230 200 23
125 50 125 176 292 230 23
80 40 125 176 292 230 23
125 50 125 176 292 230 23
80 40 125 176 292 230 23

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV26

AirRIP bushings 245550 kV


Types with rod conductor
Determination of the rod conductor
 d2

c2

Air side terminal


Standard terminals as per columns 39/40,
variants as per columns 41/42
Guidelines for the terminal dimensions:
Max. operating current (A)

d2

c2

1600

30

80

2500

40

125

3500

50

125

screws

length e1

50

45

3M10

110

65

60

3M10

110

80

75

3M12

110

100

95

6M12

110

20

d4

d3*

e1

Optional splitting of the rod conductor


Determine whether the rod conductor should be split or not.
Rod conductors are split 20 mm below the base plate and
have the following characteristics:

* See column 25 of the data table

30

a1

30

Oil side terminal


Standard

Var. 1

Standard: flat

Var. 2

thread
round

30

L16

thickness
holes

L16

a1
ng1

threadc1

d1c1

50

45

20

218

M36360

4085

65

60

30

218

M42380

30
5085

80

75

30

218

100

95

30

418

5085

30

 g1
40
 g1
40 20
 d4
85
20
a1
 d4
85

30

* See column 25 of the data table

c1

30

Var.1:
thread
L16
L16
 d4
 d4

L: Bushing length, without airside terminal and lower shield,


see column 40 of the data table
27 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

 d4

30
30

d1G
d1G

30

L16
L16

30

40
40 20
20

 g1
 g1
40
85
40  d4 85
 d4

Var.2:
L16round
L16
 d4
 d4
5
5

30
30

d4

flat

c1
c1

10

d3*

10
d1
d1

c1
c1

Bushings with rod conductor 245 550 kV


Fig. 7

Fig. 8

Legend
 d2

 d2

c2

c2

1 Copper, bare (optional:


nickel-plated, silver-plated)

2 Test tap
 D5

 D5

3 De-aeration

L5
max.

4 Earthing screws 2M12/180


5 Eyebolts 2M16/180
6 Sealing area

L 2 (5)

L 2 (5)

L5
max.

 D6
max.

the transformer lead)

L6 Current transformer extension

20

20

(L)

(L)

 D6
max.

7 Removability (for connecting

L6

 D1

c7

c7

L16 5

L16 5

L6

 D1

Flange detail

Flange
Fig. 14

30

nv

15

15

5
2 2.

30

30

2. 5
2

16

12

12

.25
11

5 45

Fig. 13

Fig. 12

6
 D2
 D8

 D3
 D4

 D3
 D4

 D3
 D4

Oil side end


Fig. 22

Fig. 23
 d3

c7

 d5
 d6

c7

L16
20

L16
20

 d3

 d5
 d6

28 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

All dimensions in mm, unless otherwise indicated

Data for bushings with rod conductor 245 550 kV


6

1ZCD064069

[kV]

750 230 146

425/

750 230 146

425/

460/
460/

RTKF 3001175/1600 B KSI RTKF 3001175/1600 B 300 173


1ZCD064071

RTKF 3001175/2500 B KSI RTKF 3001175/2500 B 300 173


1ZCD064072

RTKF 4201675/1600 B KSI RTKF 4201675/1600 B 420 242


1ZCD064073

RTKF 4201675/2500 B KSI RTKF 4201675/2500 B 420 242


1ZCD064024

1ZCD064074

RTKF 5501800/2000 B KSI RTKF 5501800/2000 B 550 318


1ZCD064025

1ZCD064075

560/ 1175

350/
350/
850

/
560/ 1175

850

/
750/ 1675 1175
/
750/ 1675 1175
/
870/ 1800 1240 500 318
/

13

14 15

16

17

18

19

Insulator

Mechanical

data

design

750/
/

[A] [kA] [mm] [mm]


[N]
750 1650
7595 2050 5000
1510
1400
900 750 2400
7595 2050 5000
2230
2100
1600
9300 2370 5000
1440
1340
3000
9300 2370 5000
2800
2600
1800
13020 3600 5000
2000
1800
2800
13020 3600 5000
2650
2500
1675 1175 1850
13750 4000 5000
2000
1750
900

Installation (v = vertical,
h = horizontal, from vertical)

Cantilever operating load

[kV]

Cantilever test load, 1min.

[kV]

Arcing distance (minimum)

AC test voltage dry/wet

[kV] [kV] [kV]

1ZCD064020

1ZCD064070

Rated max.
line-to-ground voltage

[kV]

Switching impulse voltage


250/2500 s

[kV]

505/ 1050

1ZCD064023

12

Current

505/ 1050

RTKF 2451050/2000 B KSI RTKF 2451050/2000 B 245 141

1ZCD064022

11

Lightning impulse voltage,


1.2/50 s

[kV] [kV]
RTKF 2451050/1600 B KSI RTKF 2451050/1600 B 245 141

Switching impulse voltage


250/2500 s

insulator

1ZCD064021

10

IEEE C57.19.01 (2000)

Lightning impulse voltage,


1.2/50 s

composite insulator

AC test voltage dry/wet

With porcelain

Rated Voltage Ur

With silicone

Ur/ 3

IEC 60137 (2008)

1ZCD064019

Creepage distance (minimum)

Thermal short-time current Ith2sec.

Ith 2sec. = 25 Ir

Electrical characteristics

Maximum operating current


(in respect to CT extension L6)

System voltage

1
Type and drawing

[N]
2500 v30
2500 v30
2500 v30
2500 v30
2500 v30
2500 v30
2500 v30

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV29

20

21

Weights

22

23

24

25

Oil side

26

27

28

29

30

31

Air side

32

33

34

35

36 37 38 39 40

Flange

41

42

43

44 45

Air side

46

47

48

Oil side end

terminal

315

428

375

315

428

375

365

479

435

550

479

550

550

547

550

550

547

550

d2

d5

d6

Figure

c2

Shield length below L16

c2 d2

Shield diameter

Opening

Bushing length, without air


side terminal and lower shield

Figure

Flange plate thickness

Hole diameter

Number of holes

Sealing area: max. diameter

Sealing area: min. diameter

Outside flange diameter

Pitch circle diameter

D6 D3 D4 D2 D8 n v s Fig
L
450 400 450 245 365 12 20 22 12 3055
3355
3655
480 400 450 295 365 12 20 22 13 3064
3364
3664
480 400 450 295 365 12 20 22 13 3384
3684
3984
520 450 500 355 415 12 20 25 13 3510
3810
4110
520 620 680 355 580 16 22 25 14 4940
5240
5540
580 620 680 410 580 16 22 25 14 4990
5290
5590
580 620 680 410 580 16 22 25 14 5450
5750
6050

Shield diameter

D5
315

Opening

D6
370

Standard

Shield length below L16

D5
245

Max. shed diameter


(with porcelain insulator)

Head diameter
(with porcelain insulator)

Max. shed diameter (with


s ilicone composite insulator)

Head diameter (with silicone


composite insulator)

Height of head (maximum)

Terminal: distance from the


flange plate (tolerance 5 mm)

Inside tube diameter

Core diameter

Lower core length


(tolerance 5 mm)

Current transformer extension

[kg]
L6
L16 D1 d3
L2 L5
417
0
590 185 50 2465 175
431
300
890
445
600 1190
601
0
590 234 80 2474 184
628
300
890
654
600 1190
618
0
590 234 50 2794 184
638
300
890
659
600 1190
915
0
590 285 100 2920 200
947
300
890
980
600 1190
1252 0200
790 285 65 4150 200
1348
300 1090
80
1382
600 1390
80
1588
0
790 338 100 4200 200
1629
300 1090
1669
600 1390
1687 0200
850 338 65 4600 200
1800
300 1150
80
1845
600 1450
80

Var.

Figure

[kg]
231
244
258
386
412
439
340
360
381
537
569
601
736
832
866
947
988
1029
996
1110
1154

With porcelain insulator

With silicone composite insulator

Std

c7 Fig

40 125 30 80 140 180 200

22

40 125

140 180 200

22

40 125 30 80 134 230 200

23

50 125

176 292 230

23

40 125

176 292 230

23

50 125

176 292 230

23

40 125

176 292 230

23

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV30

AirRIP bushings 245550 kV


Types with fixed conductor
Explanations of the table columns
37
812
13

14

17
18, 19

Rated voltages according to IEC 60137 (2008)


Rated voltages according to IEEE C57.19.01 (2000)
Maximum operating current as a function of the
current transformer extension L6
Maximum thermal short-circuit current, 2 sec.,
after operation at maximum operating current
Bending test load, 1 min.
Maximum cantilever operating load and permissible
installation position (v = vertical, h = horizontal,
from vertical)

31 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

22
Standard current transformer extension L6
27, 28 Maximum head and shed diameter for silicone

composite insulator
29, 30 Maximum head and shed diameter for porcelain insulator
33, 34 Sealing area
Bushing length L, without air side terminal and
39

oil side shield
40, 41 Standard terminal on air side
42, 43 Standard oil side terminal
4447 Standard design of oil side end

Bushings with fixed conductor 245 550 kV


Fig. 7

Fig. 8

Legend

 d2

 d2

1
 D5

L5
max.

3 De-aeration

6 Sealing area
 D6
max.

the transformer lead)

L6 Current transformer extension

L6

 D1

c7

c7

L16 5

L16 5

20

(L)

20

5 Eyebolts 2M16/180
7 Removability (for connecting

 D1

L6

4 Earthing screws 2M12/180

L 2 (5)

L 2 (5)

L5
max.

 D6
max.

nickel-plated, silver-plated)

2 Test tap

 D5

(L)

1 Copper, bare (optional:

c2

c2

Flange detail

Flange
Fig. 13

Fig. 14

30

nv

2 2.

15

15

30

30

2. 5
2

16

12

12

.25
11

5 45

Fig. 12

6
 D2
 D8

 D3
 D4

 D3
 D4

 D3
 D4

Oil side end

Oil side

Fig. 24

Fig. 25
 d3

Fig. 30

Fig. 31

30
 d5
 d6

 d5
 d6

32 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

 d4

30
30

40
 d4

85


18

20 40


18

85

20 40

c7

c7

30

L16

L16

L16
20

L16
20

 d3

All dimensions in mm, unless otherwise indicated

Data for bushings with fixed conductor 245 550 kV


6

1ZCD064094

[kV]

750 230 146

425/

460/
460/

RTKF 3001175/2000 F KSI RTKF 3001175/2000 F 300 173


1ZCD064096

RTKF 3001175/3150 F KSI RTKF 3001175/3150 F 300 173


1ZCD064097

RTKF 4201675/2500 F KSI RTKF 4201675/2500 F 420 242


1ZCD064098

RTKF 4201675/3150 F KSI RTKF 4201675/3150 F 420 242


1ZCD064049

1ZCD064099

RTKF 5501800/2000 F KSI RTKF 5501800/2000 F 550 318


1ZCD064050

1ZCD064100

560/ 1175

350/
750 230 146

425/
350/

850

/
560/ 1175

850

/
750/ 1675 1175
/
750/ 1675 1175
/
870/ 1800 1240 500 318
/

13

14 15

16

17

18

19

Insulator

Mechanical

data

design

750/
/

[A] [kA] [mm] [mm]


[N]
750 2150
7595 2050 5000
2050
1950
900 750 3150
7595 2050 5000
3000
2900
2100
9300 2370 5000
2000
1900
3800
9300 2370 5000
3600
3400
2300
13020 3600 5000
2600
2400
3250
13020 3600 5000
2900
2600
1675 1175 2100
13750 4000 5000
2200
1950
900

Installation (v = vertical,
h = horizontal, from vertical)

Cantilever operating load

[kV]

Cantilever test load, 1min.

[kV]

Arcing distance (minimum)

AC test voltage dry/wet

[kV] [kV] [kV]

1ZCD064045

1ZCD064095

Rated max.
line-to-ground voltage

[kV]

Switching impulse voltage


250/2500 s

[kV]

505/ 1050

1ZCD064048

12

Current

505/ 1050

RTKF 2451050/3150 F KSI RTKF 2451050/3150 F 245 141

1ZCD064047

11

Lightning impulse voltage,


1.2/50 s

[kV] [kV]
RTKF 2451050/2000 F KSI RTKF 2451050/2000 F 245 141

Switching impulse voltage


250/2500 s

insulator

1ZCD064046

10

IEEE C57.19.01 (2000)

Lightning impulse voltage,


1.2/50 s

composite insulator

AC test voltage dry/wet

With porcelain

Rated Voltage Ur

With silicone

Ur/ 3

IEC 60137 (2008)

1ZCD064044

Creepage distance (minimum)

Thermal short-time current Ith2sec.

Ith 2sec. = 25 Ir

Electrical characteristics

Maximum operating current


(in respect to CT extension L6)

Type and drawing

System voltage

[N]
2500 v30
2500 v30
2500 v30
2500 v30
2500 v30
2500 v30
2500 v30

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV33

L5

D5

D6

D5

148

245

370

315

157

315

428

375

157

315

428

375

173

365

479

435

173

550

479

550

173

550

547

550

173

550

547

550

35 36 37 38 39

Bushing length, without air


side terminal and lower shield

Figure

Flange plate thickness

Hole diameter

Number of holes

D6 D3 D4 D2 D8 n v s Fig
L
450 400 450 245 365 12 20 22 12 3028
3328
3628
480 400 450 295 365 12 20 22 13 3037
3337
3637
480 400 450 295 365 12 20 22 13 3357
3657
3957
520 450 500 355 415 12 20 25 13 3483
3783
4083
520 620 680 355 580 16 22 25 14 4913
5213
5513
580 620 680 410 580 16 22 25 14 4963
5263
5563
580 620 680 410 580 16 22 25 14 5423
5723
6023

40

41

42

43

Air side

Oil side

terminal

terminal

Standard

Standard

44

45

46

47

Oil side end


Standard

d5

d6

Figure

34

Shield length below L16

33

Shield diameter

32

Sealing area: max. diameter

Max. shed diameter


(with porcelain insulator)

Head diameter
(with porcelain insulator)

Max. shed diameter (with


s ilicone composite insulator)

Head diameter (with silicone


composite insulator)

Height of head (maximum)

Terminal: distance from the


flange plate (tolerance 5 mm)

[kg]
L6
L16 D1
L2
0
449
590 185 2438
300
466
890
600 1190
483
0
577
590 234 2447
300
601
890
600 1190
624
0
656
590 234 2767
300
679
890
600 1190
703
0
936
590 285 2893
300
969
890
600 1190
1003
1323 0200
790 285 4123
300 1090
1306
600 1390
1337
0
1618
790 338 4173
300 1090
1660
600 1390
1703
1769 0200
850 338 4573
300 1150
1757
600 1450
1799

31

Flange

Opening

30

Figure

29

Terminal width

28

Length of terminal

27

Terminal diameter

26

Sealing area: min. diameter

25

Air side

Outside flange diameter

24

Pitch circle diameter

23

Oil side

Core diameter

With porcelain insulator

With silicone composite insulator


[kg]
263
280
297
361
385
409
378
401
425
557
591
625
807
790
821
977
1019
1062
1079
1066
1108

22

Lower core length


(tolerance 5 mm)

21

Weights

Current transformer extension

20

d2

c2

d4

Fig

40

125

52

30 140 180 200

c7 Fig
24

50

125

80

31 140 180 200

24

40

125

52

30 134 230 200

25

60

125

100

31 176 292 230

25

40

125

65
80
80

30 176 292 230


31
31

25

50

125

100

31 176 292 230

25

40

125

65
80
80

30 176 292 230


31
31

25

Micafil Transformer Bushings | AirRIP/RTKF 24 550 kV34

Other Micafil RIP bushings

ABB offers an extensive range of high-quality products.


They can be adapted to different transformer and plant
designs and thus meet the requirements of the most varied applications. In addition, our company is specialized
in tailor-made solutions including custom designs and
small series production.
Our range of products encompasses bushings for
o il-outdoor, oil-SF 6, oil-oil transformer systems as well as
outdoor-SF 6 bushings for GIS. If you dont see what you need
right here, please get in touch with us we can address
your individual needs in a highly professional, f lexible and
efficient manner. Our bushings are developed and approved
for m ineral oil applications.

Transformer bushings, oil-outdoor


Series: A irRIP / RTKF KSI
Silicone composite insulator available with straight
or helical sheds
Voltage range: from 24 to 550 kV
Current range: up to 5000 A

Series: A irRIP / RTKF


Porcelain insulator
Voltage range: from 24 to 550 kV
Current range: up to 5000 A

Series: S eismicRIP / RTKF KSI


Silicone composite insulator
Voltage range: from 69 to 550 kV
Current range: up to 5000 A
Standard: IEEE 693 (2005)
High seismic performance level

Series: H IRIP high-current RTXF


Porcelain insulator
Voltage range: up to 36 kV
Current range: up to 40000 A

35 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

Transformer bushings, oil-SF 6

Outdoor-SF6 bushings for GIS

Series: G ARIP / RTKG


Voltage range: from 36 to 550 kV
Current range: up to 4000 A

Series: RAKF
Porcelain or silicone composite insulator
Voltage range: from 245 to 550 kV
Current range: up to 4000 A

Transformer bushings, oil-oil

Wall bushings

Series: O RIP / RTKK


Voltage range: from 72.5 to 550 kV
Current range: up to 4000 A

Series: RMI indoor-indoor



RMF outdoor-indoor

RMFF outdoor-outdoor
Porcelain or silicone composite insulator
Voltage range: from 24 to 300 kV
Current range: up to 5000 A

Railway bushings
Series: R MF / RTAK porcelain insulator
Voltage range: from 15 to 36 kV
Current range: up to 2000 A

36 AirRIP/RTKF 24 550 kV | Micafil Transformer Bushings

ABB Switzerland Ltd


High Voltage Components
Badenerstrasse 780
CH-8048 Zurich/Switzerland
Phone + 41 58 586 03 33
Fax +41 58 586 04 44
E-mail: info.micafil @ch.abb.com
www.abb.com/electricalcomponents

Note
We reserve the right to make technical changes or
modify the contents of this document without prior
notice. With regard to purchase orders, the a greed
particulars shall prevail. ABBS witzerlandLtd
does not accept any responsibility whatsoever
for p otential errors or possible lack of information
in this document. We reserve all rights in this
d ocument and in the subject matter and illustrations
contained therein. Any reproduction, d isclosure to
third parties or u tilization of its c ontents in w hole
or in parts is forbidden w
ithout prior written
c onsent of ABB Switzerland Ltd.
Copyright 2012 ABB
All rights reserved.

1ZCD066580/May 2012

Contact

Você também pode gostar